fault current calculations - university of nevada, las vegaseebag/fault current calculations.pdf ·...

41
Fault Current Calculations ECG 740

Upload: others

Post on 30-Jul-2020

43 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Fault Current Calculations

ECG 740

Page 2: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Introduction

• A fault in a circuit is any failure that interferes with the normal system operation.

• Lighting strokes cause most faults on high-voltage transmission lines producing a very high transient that greatly exceeds the rated voltage of the line.

• This high voltage usually causes flashover between the phases and/or the ground creating an arc.

• Since the impedance of this new path is usually low, an excessive current may flow.

• Faults involving ionized current paths are also called transient faults. They usually clear if power is removed from the line for a short time and then restored.

Page 3: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Introduction

• If one, or two, or all three phases break or

if insulators break due to fatigue or

inclement weather, this fault is called a

permanent fault.

• Approximately 75% of all faults in power

systems are transient in nature.

• Knowing the magnitude of the fault

current is important when selecting

protection equipment (type, size, etc..)

Page 4: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

3-Phase fault current transients in synchronous generators

When a symmetrical 3-phase fault

occurs at the terminals of a

synchronous generator, the resulting

current flow in the phases of the

generator appear as shown.

The current can be represented as a

transient DC component added on top

of a symmetrical AC component.

Before the fault, only AC voltages and

currents are present, but immediately

after the fault, both AC and DC

currents are present.

Page 5: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Symmetrical AC component of the fault current:

• There are three periods of time: – Sub-transient period: first couple of cycles after the fault – AC

current is very large and falls rapidly; – Transient period: current falls at a slower rate; – Steady-state period: current reaches its steady value.

• It is possible to determine the time constants for the sub-transient and transient periods .

Page 6: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Fault current transients in machines

• The AC current flowing in the generator during the sub-transient period is called the sub-transient current and is denoted by I”. The time constant of the sub-transient current is denoted by T” and it can be determined from the slope. This current can be as much as 10 times the steady-state fault current.

• The AC current flowing in the generator during the transient period is called the transient current and is denoted by I’. The time constant of the transient current is denoted by T’. This current is often as much as 5 times the steady-state fault current.

• After the transient period, the fault current reaches a steady-state condition Iss. This current is obtained by dividing the induced voltage by the synchronous reactance:

Page 7: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Fault current transients in machines

• The rms value of the AC fault current in a synchronous generator varies over time as

• The sub-transient and transient reactances are defined as the ratio of the internal generated voltage to the sub-transient and transient current components:

""

AEX

I

" '" ' 't T t T

ss ssI t I I e I I e I

''

AEX

I A

ss

s

EI

X

Page 8: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Fault current calculations

Example 1: A 100 MVA, 13.8 kV, Y-connected, 3 phase 60 Hz synchronous

generator is operating at the rated voltage and no load when a 3 phase fault occurs

at its terminals. Its reactances per unit to the machine’s own base are

1.00 ' 0.25 " 0.12sX X X

and the time constants are

' 1.10 " 0.04T s T s

The initial DC component averages 50% of the initial AC component.

a) What is the AC component of current in this generator the instant after the fault? I” = 34,900 A.

b) What is the total current (AC + DC) in the generator right after the fault occurs?

c) What will the AC component of the current be after 2 cycles? After 5 s?

1.5 " 52,350totI I A

17,910 12,142 4,184 24,236

30I A

5 0 133 4,184 4,317I A

Page 9: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Symmetrical fault current calculations

• To determine the fault current in a large power system: – Create a per-phase per-unit equivalent circuit of the

power system using either sub-transient reactances (if subtransient currents are needed) or transient reactances (if transient currents are needed).

– Find the Thevenin equivalent circuit looking from the fault point, then divide the Thevenin voltage by the Thevenin impedance.

• You may use the Z-bus elements to determine the voltages and current flows elsewhere in the system (further away from the faulted bus)

• Today, software tools to do the calculations for us are readily available (e.g. Powerworld).

Page 10: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Fault current calculations using the impedance matrix

Before the fault, the voltage on bus 2 was Vf. If

we introduce a voltage source of value Vf

between bus 2 and the neutral, nothing will

change in the system.

Since the system operates normally before the

fault, there will be no current If” through that

source.

Page 11: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Fault current calculations using the impedance matrix

Assume that we create a short circuit on bus 2,

which forces the voltage on bus 2 to 0. This is

equivalent to inserting an additional voltage

source of value -Vf in series with the existing

voltage source. The later will make the total

voltage at bus 2 become 0.

With this additional voltage source, there will be

a fault current If”, which is entirely due to the

insertion of the new voltage source to the

system. Therefore, we can use superposition to

analyze the effects of the new voltage source on

the system.

The resulting current If” will be the current for the

entire power system, since the other sources in

the system produced a net zero current.

Page 12: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Fault current calculations using the impedance matrix

If all voltage sources except –Vf” are set to

zero and the impedances are converted to

admittances, the power system appears as

shown.

For this system, we can construct the bus

admittance matrix as discussed previously:

16.212 5.0 0 6.667

5.0 12.5 5.0 2.5

0 5.0 13.333 5.0

6.667 2.5 5.0 14.167

bus

j j j

j j j jY

j j j

j j j j

The nodal equation describing this power system is

busY V = I

Page 13: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Fault current calculations using the impedance matrix

With all other voltage sources set to zero, the voltage at bus 2 is –Vf, and the

current entering the bus 2 is –If”. Therefore, the nodal equation becomes

11 12 13 14 1

"

21 22 23 24

31 32 33 34 3

41 42 43 44 4

0

0

0

f f

Y Y Y Y V

Y Y Y Y V I

Y Y Y Y V

Y Y Y Y V

where V1, V3, and V4 are the changes in the voltages at those busses due to the

current –If” injected at bus 2 by the fault.

The solution is found as -1

bus busV = Y I = Z I

Page 14: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Fault current calculations using the impedance matrix

11 12 13 141

"

21 22 23 24

31 32 33 343

41 42 43 444

0

0

0

f f

Z Z Z ZV

Z Z Z ZV I

Z Z Z ZV

Z Z Z ZV

Which, in the case considered, is

where Zbus = Ybus-1. Since only bus 2 has current injected at it, the system reduces to

"

"

1 12

"

3 32

"

2

4

2

42

f

f

f

f f

V Z I

V Z I

V

I

Z I

V Z

Page 15: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Fault current calculations using the impedance matrix

Therefore, the fault current at bus 2 is just the prefault voltage Vf at bus 2 divided by

Z22, the driving point impedance at bus 2.

"

22

f

f

VI

Z

The voltage differences at each of the nodes due to the fault current can be

calculated by substitution:

" 121 12

22

2

" 323 32

22

" 424 42

22

f f

f f

f f

f f

ZV Z I V

Z

V V V

ZV Z I V

Z

ZV Z I V

Z

Page 16: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Symmetrical Components and Unsymmetrical Faults

Page 17: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 18: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 19: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 20: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 21: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 22: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 23: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 24: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 25: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 26: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 27: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 28: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 29: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 30: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 31: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 32: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 33: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 34: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Example 1:

Page 35: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 36: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Example 1:

Page 37: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 38: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 39: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 40: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,
Page 41: Fault Current Calculations - University of Nevada, Las Vegaseebag/fault current calculations.pdf · transient DC component added on top of a symmetrical AC component. Before the fault,

Last Assignment

• Watch the 20 min video on how to navigate Powerworld when conducting fault analysis at the link below, then calculate the 3-phase and single-phase fault currents at each of the 6 busses and resulting voltages.

https://www.powerworld.com/training/online-training/fault-analysis