excel 10 w7750a,b,c constant volume ahu controller - honeywell · excel 10 w7750a,b,c constant...

116
SYSTEM ENGINEERING 74-29582 Excel 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER Contents Introduction .................................................................................................................................. 6 Description of Devices .............................................................................................. 6 Control Application .................................................................................................... 6 Control Provided ....................................................................................................... 7 Products Covered...................................................................................................... 8 Applicable Literature ................................................................................................. 8 Organization of Manual ............................................................................................. 8 Product Names ......................................................................................................... 8 Agency Listings ......................................................................................................... 8 Abbreviations and Definitions.................................................................................... 9 Construction .............................................................................................................. 11 Controllers ........................................................................................................... 11 Performance Specifications ............................................................................. 13 LONMARKfi Functional Profile .......................................................................... 17 Inputs/Outputs ..................................................................................................... 18 Analog Inputs................................................................................................... 18 Digital Inputs .................................................................................................... 19 Triac Outputs (W7750B,C Models Only) ......................................................... 19 Digital Outputs ................................................................................................. 19 Wall Modules ....................................................................................................... 20 Duct Sensor ......................................................................................................... 20 Configurations ........................................................................................................... 21 General ................................................................................................................ 21 Allowable Heating and Cooling Equipment Configurations ................................. 23 Staged Heating/Cooling Control ...................................................................... 24 Modulating Heating/Cooling Control ................................................................ 24 Heat Pump Control .......................................................................................... 24 Economizer Control ......................................................................................... 25 Pneumatic Actuator Control ............................................................................. 26 Mixed Output-type Control ............................................................................... 26 Occupancy Sensor .............................................................................................. 26 Window Open/Closed Digital Input ...................................................................... 26 Wall Module Options ........................................................................................... 26 Dirty Filter Monitor ............................................................................................... 27 Indoor Air Quality (IAQ) Override ........................................................................ 27 Smoke Control ..................................................................................................... 27 Freeze Stat (W7750B2011 or W7750C) .............................................................. 27 Modes of Operation................................................................................................... 27 Application Steps .................................................................................................................................. 28 Overview ................................................................................................................... 28 Step 1. Plan the System ............................................................................................ 29 Step 2. Determine Other Bus Devices Required ....................................................... 29 Step 3. Lay Out Communications and Power Wiring ................................................ 30 LONWORKSfi Bus Layout ..................................................................................... 30 Power Wiring ....................................................................................................... 32 Power Budget Calculation Example ................................................................ 32 Line Loss ......................................................................................................... 32 Step 4. Prepare Wiring Diagrams .............................................................................. 35

Upload: dinhnga

Post on 27-Jul-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

SYSTEM ENGINEERING

74-2958�2

Excel 10W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

ContentsIntroduction .................................................................................................................................. 6

Description of Devices .............................................................................................. 6Control Application .................................................................................................... 6Control Provided ....................................................................................................... 7Products Covered...................................................................................................... 8Applicable Literature ................................................................................................. 8Organization of Manual ............................................................................................. 8Product Names ......................................................................................................... 8Agency Listings ......................................................................................................... 8Abbreviations and Definitions.................................................................................... 9Construction .............................................................................................................. 11

Controllers ........................................................................................................... 11Performance Specifications ............................................................................. 13LONMARK® Functional Profile .......................................................................... 17

Inputs/Outputs ..................................................................................................... 18Analog Inputs................................................................................................... 18Digital Inputs .................................................................................................... 19Triac Outputs (W7750B,C Models Only) ......................................................... 19Digital Outputs ................................................................................................. 19

Wall Modules ....................................................................................................... 20Duct Sensor ......................................................................................................... 20

Configurations ........................................................................................................... 21General ................................................................................................................ 21Allowable Heating and Cooling Equipment Configurations ................................. 23

Staged Heating/Cooling Control ...................................................................... 24Modulating Heating/Cooling Control ................................................................ 24Heat Pump Control .......................................................................................... 24Economizer Control ......................................................................................... 25Pneumatic Actuator Control............................................................................. 26Mixed Output-type Control............................................................................... 26

Occupancy Sensor .............................................................................................. 26Window Open/Closed Digital Input ...................................................................... 26Wall Module Options ........................................................................................... 26Dirty Filter Monitor ............................................................................................... 27Indoor Air Quality (IAQ) Override ........................................................................ 27Smoke Control ..................................................................................................... 27Freeze Stat (W7750B2011 or W7750C) .............................................................. 27

Modes of Operation................................................................................................... 27

Application Steps .................................................................................................................................. 28Overview ................................................................................................................... 28Step 1. Plan the System............................................................................................ 29Step 2. Determine Other Bus Devices Required....................................................... 29Step 3. Lay Out Communications and Power Wiring ................................................ 30

LONWORKS® Bus Layout ..................................................................................... 30Power Wiring ....................................................................................................... 32

Power Budget Calculation Example ................................................................ 32Line Loss ......................................................................................................... 32

Step 4. Prepare Wiring Diagrams.............................................................................. 35

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 2

General Considerations ...................................................................................... 35W7750 Controllers .............................................................................................. 35

Factory Default Digital Outputs........................................................................ 37LONWORKS® Bus Termination Module ................................................................ 43

Step 5. Order Equipment .......................................................................................... 45Step 6. Configure Controllers.................................................................................... 48Step 7. Troubleshooting ............................................................................................ 48

Troubleshooting Excel 10 Controllers and Wall Modules .................................... 48Temperature Sensor and Setpoint Potentiometer Resistance Ranges ............... 49Alarms ................................................................................................................. 49Broadcasting the Service Message ..................................................................... 50W7750 Controller Status LED ............................................................................. 51T7770C,D Wall Module Bypass Pushbutton and Override LED ......................... 51T7560A,B Bypass Pushbutton and LCD Display Occupancy Symbols ............... 51

Appendices .................................................................................................................................. 52Appendix A: Using LONSPEC�/Care to Commission a W7750 Controller................ 52

Sensor Calibration ............................................................................................... 52Setting the Pid Parameters ................................................................................. 52

Appendix B: Sequences of Operation....................................................................... 53Common Operations ........................................................................................... 53

Room Temperature Sensor (RmTemp) ........................................................... 54Remote Setpoint (RmtStptPot) ........................................................................ 55Setpoint Limits (LoSetptLim and HiSetptLim).................................................. 55Bypass Mode (StatusOvrd and StatusLed)...................................................... 55BYPASSTIME.................................................................................................. 55OverrideType................................................................................................... 55OverridePriority ............................................................................................... 55Cycles per Hour (ubHeatCph and ubCoolCph) ............................................... 55T7770C,D or T7560A,B Wall Module Bypass Pushbutton Operation ............. 55Standby Mode (StatusOcySen) ....................................................................... 56Continuous Unoccupied Mode ........................................................................ 56Occupancy Mode and Manual Override Arbitration ........................................ 56Time Clock (Occ_Time_Clock) ........................................................................ 57Schedule Master (Sched_Master)................................................................... 57Setpoint Ramping............................................................................................ 57Recovery Ramping for Heat Pump Systems................................................... 57Fan Operation ................................................................................................. 58Window Sensor (StatusWndw)........................................................................ 58Smoke Control................................................................................................. 58Demand Limit Control (DLC) ........................................................................... 58Dirty Filter Monitor ........................................................................................... 59Start-Up ........................................................................................................... 59

Temperature Control Operations ......................................................................... 59Staged Cooling Control ................................................................................... 59Staged Heating Control ................................................................................... 60Cascade Control of Modulating Cooling/Heating ............................................ 61Series 60 Modulating Control .......................................................................... 61Pulse Width Modulating (PWM) Control .......................................................... 61Outdoor Air Lockout of Heating/Cooling.......................................................... 61Economizer Damper Control ........................................................................... 61Indoor Air Quality (IAQ) Override .................................................................... 61Freeze Stat ...................................................................................................... 62Discharge Air Low Limit Control ...................................................................... 62Economizer Enable/Disable Control................................................................ 62

Appendix C: Complete List of Excel 10 W7750 Controller User Addresses ............. 63User Address Indexes ......................................................................................... 63Mappable User Addresses and Table Number ................................................... 65Failure Detect User Addresses and Table Number ............................................. 65

Appendix D: XL5000 Q7750A Excel 10 Zone Manager Point Estimating Guide ......109Approximate Memory Size Estimating Procedure. ..............................................109

Appendix E: Sensor Data for Calibration .................................................................. 110Resistance Sensors ............................................................................................ 110Voltage/Current Sensors ..................................................................................... 111

0 A,B,C nt Vol-

HU Con-

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

3 74-2958�2

List of FiguresFig. 1. Typical system overview. ................................................................................................................................................ 6Fig. 2. Typical W7750 control application. ................................................................................................................................. 7Fig. 3. Excel 10 W7750A Constant Volume AHU Controller. ..................................................................................................... 12Fig. 4. W7750A construction in in. (mm). ................................................................................................................................... 13Fig. 5. Excel 10 W7750B Constant Volume AHU Controller. ..................................................................................................... 14Fig. 6. Excel 10 W7750C Constant Volume AHU Controller. .................................................................................................... 15Fig. 7. W7750B,C construction in in. (mm). W7750C (shown) has three 4 to 20 mA analog outputs.) ..................................... 16Fig. 8. DIN rail adapters. ............................................................................................................................................................ 17Fig. 9. Functional profile of LONMARK® RTU object details (variables not implemented in Excel 10 CVAHU are greyed). ....... 18Fig. 10. T7770A,B,C,D construction in in. (mm). ....................................................................................................................... 20Fig. 11. T7560A,B construction in in. (mm)................................................................................................................................. 21Fig. 12. C7770A construction in in. (mm).................................................................................................................................... 21Fig. 13. Fan with two stages of heating and two stages of cooling............................................................................................. 24Fig. 14. Fan, modulating heating and modulating cooling. ......................................................................................................... 24Fig. 15. Heat pump with two compressors and auxiliary heat stage(s)....................................................................................... 25Fig. 16. Economizer control. ...................................................................................................................................................... 25Fig. 17. Modulating heat with pneumatic valve actuator. ............................................................................................................ 26Fig. 18. Connecting the portable operator terminal to the LONWORKS® Bus.............................................................................. 29Fig. 19. Wiring layout for one doubly terminated daisy-chain LONWORKS® Bus segment. ........................................................ 31Fig. 20. Wiring layout for two singly terminated LONWORKS® Bus segments. ............................................................................ 32Fig. 21. NEMA class 2 transformer voltage output limits. ........................................................................................................... 33Fig. 22. Power wiring details for one Excel 10 per transformer. ................................................................................................. 33Fig. 23. Power wiring details for two or more Excel 10s per transformer. .................................................................................. 34Fig. 24. Transformer power wiring details for one Excel 10 used in UL 1995 equipment (U.S. only)......................................... 34Fig. 25. Attaching two or more wires at terminal blocks.............................................................................................................. 36Fig. 26. W7750B High-Side/Low-Side selectable switching and jumper location (on W7750B2011 and W7750C)................... 36Fig. 27. Typical W7750A Controller AHU application wiring. (For more information on note 2, refer to Fig. 25.)....................... 38Fig. 28. Typical W7750A Controller with separate transformer application wiring.

(For more information on note 2, refer to Fig. 25.) ............................................................................................................ 38Fig. 29. W7750A Controller floating economizer damper wiring. (For more information on note 2, refer to Fig. 25.)................. 39Fig. 30. Typical W7750B Controller with staged heating and cooling wiring. (For more information on note 2, refer to Fig. 25.) 40Fig. 31. W7750B Controller with floating heating, cooling and economizer wiring.

(For more information on note 2, refer to Fig. 25.) ............................................................................................................ 40Fig. 32. W7750B,C Controller PWM damper actuator wiring. (For more information on note 2, refer to Fig. 25.) ..................... 41Fig. 33. W7750B,C wiring with 4 to 20 mA enthalpy sensors and digital inputs.

(For more information on note 2, refer to Fig. 25.) ............................................................................................................ 41Fig. 34. W7750B,C wiring with C7600C 4 to 20 mA solid state humidity sensor.

(For more information on note 2, refer to Fig. 25.) ............................................................................................................ 42Fig. 35. W7750C Controller with 4 to 20 mA heating, cooling and economizer wiring. AOs must use terminals 16, 17 or 18.

The AOs can be set to be reverse acting. (For more information on note 2, refer to Fig. 25.)......................................... 42Fig. 36. Pneumatic transducer to W7750B,C.............................................................................................................................. 43Fig. 37. RP7517,B pneumatic transducer to W7750C. ............................................................................................................... 43Fig. 38. Typical doubly terminated daisy-chain LONWORKS® Bus segment termination module wiring. ................................... 44Fig. 39. LONWORKS® Bus termination wiring options. ............................................................................................................... 45Fig. 40. Temperature sensor resistance plots............................................................................................................................. 49Fig. 41. Location of the Service Pin Button................................................................................................................................. 51Fig. 42. LED location on W7750. ................................................................................................................................................ 51Fig. 43. The T7770C,D Wall Modules LED and Bypass pushbutton locations. .......................................................................... 51Fig. 44. T7560A,B Digital Wall Module Bypass pushbutton location. ......................................................................................... 51Fig. 45. LED and Bypass pushbutton operation. ....................................................................................................................... 56Fig. 46. Setpoint ramping parameters with ramp rate calculation............................................................................................... 57Fig. 47. Setpoint ramping parameters with setpoint calculation.................................................................................................. 58Fig. 48. Setpoint ramping parameters with ramp rate calculation............................................................................................... 58Fig. 49. Schematic diagram for a typical W7750B Unit. ............................................................................................................. 59Fig. 50. Staged output control versus PID Error. ....................................................................................................................... 60Fig. 51. Point capacity estimate for Zone Manager. .................................................................................................................. 109Fig. 52. PT3000 Sensor resistance versus temperature............................................................................................................. 110Fig. 53. 20K ohm sensor resistance versus temperature. .......................................................................................................... 110Fig. 54. C7600B Sensor voltage versus humidity. ...................................................................................................................... 111

Excel 10 W7750A,B,C Constant Vol-ume AHU Con-troller

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 4

Fig. 55. C7600C output current versus humidity......................................................................................................................... 111Fig. 56. C7400A Sensor current versus enthalpy (volts). ........................................................................................................... 112Fig. 57. Partial psychrometric chart for a C7400A Solid State Enthalpy Sensor. ...................................................................... 113Fig. 58. C7400A Solid State Enthalpy Sensor output current versus relative humidity. ............................................................. 113Fig. 59. C7232, C7632 voltage versus CO2 concentration. ........................................................................................................ 114Fig. 60. P7640 voltage (Vdc) versus pressure (in. w.c.). ............................................................................................................ 114

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

5 74-2958�2

List of TablesTable 1. Agency Listing. ............................................................................................................................................................. 9Table 2. List of Differences in W7750A and W7750B,C Controllers........................................................................................... 11Table 3. Common Configuration Options Summary For W7750A,B,C Controllers..................................................................... 22Table 4. Configuration Options Summary for W7750A,B,C Controllers. .................................................................................... 23Table 5. Modes Of Operation For The Excel 10 W7750 Controller . .......................................................................................... 27Table 6. Application Steps. ......................................................................................................................................................... 28Table 7. LONWORKS® Bus Configuration Rules and Device Node Numbers. ............................................................................ 30Table 8. VA Ratings For Transformer Sizing. ............................................................................................................................. 32Table 9. Field Wiring Reference Table (Honeywell listed as AK#### or equivalent).................................................................. 35Table 10. W7750A Version I/O Description. ............................................................................................................................... 37Table 11. Excel 10 W7750 Controller Ordering Information. ...................................................................................................... 46Table 12. Excel 10 Alarms. ......................................................................................................................................................... 50Table 13. Recommended Values For PID Parameters............................................................................................................... 52Table 14. Common Configuration Options Summary For W7750A,B,C Controllers................................................................... 53Table 15. Configuration Options Summary For W7750A,B,C Controllers. ................................................................................. 54Table 16. Bypass Pushbutton Operation. ................................................................................................................................... 55Table 17. Interstage Minimum Times.......................................................................................................................................... 60Table 18. Excel 10 W7750 Controller User Address Point Types. ............................................................................................. 63Table 19. Engineering Units For Analog Points. ......................................................................................................................... 66Table 20. Input/Output Points. .................................................................................................................................................... 67Table 21. Control Parameters..................................................................................................................................................... 74Table 22. Energy Management Points........................................................................................................................................ 78Table 23. Status Points............................................................................................................................................................... 81Table 24. Calibration Points........................................................................................................................................................ 93Table 25. Configuration Parameters. .......................................................................................................................................... 94Table 26. LONMARK®/Open System Points. ............................................................................................................................... 98Table 27. Direct Access And Special Points............................................................................................................................... 106Table 28. Data Share Points....................................................................................................................................................... 108Table 29. PT3000 Sensor Resistance Versus Temperature. ..................................................................................................... 110Table 30. C7600B Sensor Voltage Versus Humidity. ................................................................................................................. 111Table 31. C7600C Sensor Current Versus Humidity. ................................................................................................................. 111Table 32. C7400A Sensor Current Versus Enthalpy (volts)........................................................................................................ 112Table 33. C7232, C7632 Voltage Versus CO2 Concentration. ................................................................................................... 114Table 34. P7640 Voltage (Vdc) Versus Pressure (in. w.c.)......................................................................................................... 114

Excel 10 W7750A,B,C Constant Vol-ume AHU Con-troller

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 6

INTRODUCTION

Description of DevicesThe W7750 is the Constant Volume Air Handling Unit (CVAHU) Controller in the Excel 10 product line family. The CVAHU is a LONMARK® compliant device designed to control single zone and heat pump air handlers. W7750 systems control the space temperature in a given zone by regulating the heating and cooling equipment in the air handler that delivers air to that space. The W7750 air handler is typically an all-in-one constant air volume packaged unit, located on the roof of the building. In addition to standard heating and cooling control, the W7750 provides many options and advanced system features that allow state-of-the-art commercial building control. The W7750 Controller is capable of stand-alone operation; however, optimum functional benefits are achieved when the network communication capabilities are used. The W7750 utilizes the Echelon® LONWORKS® network (LONWORKS Bus) for communications, and conforms with the LONMARK HVAC Interoperability standard for Roof Top Unit Controllers (see Fig. 9).

The T7770 or T7560 direct-wired Wall Modules are used in conjunction with W7750 Controllers. The zone controlled by the W7750 Controller typically can use a T7770A through D or a T7560A,B Wall Module. Additional features available in T7770A through D models include analog setpoint input knob, override digital input pushbutton, override status LED and LONWORKS Bus network access jack. Additional features available in T7560A,B models include analog setpoint input knob, override digital input pushbutton, humidity sensor (T7650B model), override status LCD and digital display.

The Q7750A Excel 10 Zone Manager is a communications interface that allows devices on the LONWORKS Bus network to communicate with devices on the standard EXCEL 5000® System C-Bus. Fig. 1 shows an overview of a typical system layout. The Q7750A also provides some control and monitoring functions.

Fig. 1. Typical system overview.

Control ApplicationW7750 systems in commercial buildings typically incorporate a packaged air handler system that delivers a constant volume of air at preconditioned temperatures to the zone being served. Each zone is usually serviced by a separate AHU; however, sometimes two or more AHUs service the same zone. Note that the W7750 is not designed to control Variable Air Volume (VAV) air handlers or Multi-Zone air handlers, where one air handler simultaneously controls the space temperature in many zones.

The W7750 can control staged or modulating heating and cooling coils, mixed air economizer dampers, and the system fan. Control of heat pump units, where the compressor(s) is used for both cooling and heating, is also provided. The zone the W7750 services can use a T7770 or T7650 for space temperature sensing and an LONWORKS Bus network access for users. Fig. 2 shows a typical W7750 control application.

PERSONAL COMPUTER TOOLS

LONSPEC, LONSTATION OR

CARE

Q7752A

LONWORKS BUS

SERIAL

ADAPTER

EXCEL 10

Q7750A

ZONE

MANAGER

C-BUS COMMUNICATION NETWORK

EXCEL 500EXCEL BUILDING SUPERVISOR

C-BUS TO LONWORKS BUS

INTERFACE DEVICE

EXCEL 10 W7751F

PANEL PLENUM

MOUNT VERSION

VARIABLE AIR VOLUME

CONTROLLER

LONWORKS-BUS COMMUNICATIONS NETWORK LONWORKS BUS COMMUNICATIONS NETWORK

Q7751A

FTT

LONWORKS BUS

ROUTER

EXCEL 10 T7770

WALL MODULE

EXCEL 10 T7560A, B

WALL MODULE

M17487A

EXCEL 10

W7750B

CVAHU

CONTROLLER

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 J3

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16

Q7740A

2-WAY

REPEATER

0 A,B,C nt Vol-

HU Con-

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

7 74-2958�2

Fig. 2. Typical W7750 control application.

Control ProvidedThe W7750 Controller is designed to control a single air handler to maintain the units space temperature at the current setpoint. Heating and cooling control is provided for either staged or modulating equipment. Up to four stages of mechanical cooling and up to four stages of heating are allowed. Modulating outputs can be either floating type such as a Series 60 control, or Pulse Width Modulated (PWM W7750B,C only) control.

The economizer dampers can be controlled directly with floating or PWM outputs, or indirectly using a digital output as an enable/disable signal to a packaged economizer controller. The economizer enable function, which decides when to allow outdoor air to be used for free cooling, can be configured to one of ten strategies based on the inputs. For more details, see Appendix B�Sequences of Operation. When the economizer position is controlled from the W7750, the minimum position setting (for ventilation requirements) can be adjusted based on indoor air quality (IAQ) needs in the space. IAQ monitoring is provided through either a CO2 sensor or a digital input from a space-mounted IAQ limit switch.

For heat pump configurations, up to four compressors can be controlled, along with up to four stages of auxiliary heat, and a heat/cool change over valve. Including the supply fan, the combination of these items may not exceed eight outputs if a W7750B,C is used, or six outputs for a W7750A. (The eight outputs on the W7750C consist of five digital and three analog outputs.)

Like the W7751 VAV Box Controller, the W7750 Controller can monitor a space-mounted occupancy sensor, and a door/window contact. These inputs affect the operational mode of the controller (see Table 5 for a list of all possible modes of operation).

The W7750 Controller allows other controllers in the system to use the W7750s physical inputs and outputs. A digital input and an analog input can be configured to read switch states and voltage sensor values, respectively, and send them out over the LONWORKS Bus network. The Q7750A Zone Manager can use these values in custom control strategies. Additionally, two of the W7750 digital outputs are available for control program use. These outputs only respond to signals sent over the network, and are not controlled by the W7750 internal control algorithms.

WINDOW CONTACT

OCCUPANCYSENSOR

M

OA TEMP

FILTER

FAN

COOLCOIL

HEATCOIL

DA TEMPRA TEMP

EXCEL 10W7750CVAHU

T7770 OR T7560A,BRETURNAIR

DISCHARGEAIR

OUTDOORAIR

CEILING

ROOF

- +

M17488

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 8

Products CoveredThis System Engineering Guide describes how to apply the Excel 10 family of W7750 CVAHU Controllers and related accessories to typical applications. The specific devices covered include:� W7750A,B,C Controllers.� T7770A through D Wall Modules.� T7560A,B Wall Modules.� Q7751A,B Router (FTT to FTT and TPT to FTT).� Q7752A Serial Interface.� Q7740A,B Repeaters (2-way and 4-way).� 209541B FTT Termination Module.

Applicable LiteratureThe following list of documents contains information related to the Excel 10 W7750 CVAHU Controller and the LCBS/ EXCEL 5000® OPEN� SYSTEM in general:

Organization of ManualThis manual is divided into three basic parts: the Introduction, the Application Steps, and the Appendices that provide supporting information. The Introduction and Application Steps 1 through 5 provide the information needed to make accurate material ordering decisions. Application Step 6 and

the Appendices include configuration engineering that can be started using LONSPEC� or Care PC Software after the devices and accessories are ordered. Application Step 7 is troubleshooting.

The organization of the manual assumes a project is being engineered from start to finish. If an operator is adding to, or is changing an existing system, the Table of Contents can provide the relevant information.

Product NamesThe W7750 Controller is available in three models:� W7750A Constant Volume AHU Controller - W7750A

Version.� W7750B Constant Volume AHU Controller - W7750B

Version.� W7750C Constant Volume AHU Controller - W7750C

Version.

The T7770 Wall Module is available in four models. The T7770 Wall Modules will work with all Excel 5000 and Excel 10 Controllers (except the W7751A,C,E,G):� T7770A1xxx Wall Module with nonlinearized 20K ohm

NTC sensor only.� T7770A2xxx Wall Module with nonlinearized 20K ohm

NTC sensor and LONWORKS Bus jack.� T7770A3xxx Wall Module with nonlinearized 10K ohm

NTC sensor for averaging two sensors.� T7770B1xxx Wall Module with nonlinearized 20K ohm

NTC sensor, 10K ohm setpoint, and LONWORKS Bus jack.� T7770C1xxx Wall Module with nonlinearized 20K ohm

NTC sensor, 10K ohm setpoint, bypass button and LED, and LONWORKS Bus jack.

� T7770D1xxx Wall Module with nonlinearized 20K ohm NTC sensor, bypass button and LED, and LONWORKS Bus jack.

NOTE: The T7770B,C Models are available with a absolute 55 to 85°F (10 to 85°C) or a relative scale plate adjustable to ±9°F (±5°C).

The T7560A,B Wall Module is available in two models:� T7560A Wall Module displays and provides space

temperature, setpoint, Occ/Unocc override, override status LCD and digital display.

� T7560B Wall Module displays and provides space temperature, humidity sensor, setpoint, Occ/Unocc override, override status LCD and digital display.

Other products:� Q7750A Excel 10 Zone Manager.� Q7751A,B Bus Router.� Q7752A Serial Adapter.� Q7740A,B FTT Repeaters.� 209541B FTT Termination Module.Refer to Table 11 in Application Step 5. Order Equipment for a complete listing of all available part numbers.

NOTE: The Q7750A Zone Manager is referred to as (E-Link) in internal software and CARE.

Agency ListingsTable 1 provides information on agency listings for Excel 10 products. Be sure to always follow Local Electrical Codes.

Form No Title74-2956 Excel 10 W7750A,B,C Controller Specification Data74-2697 Excel 10 T7770A,B,C,D,E,F,G Wall Module Specification Data74-3097 T7560A,B Digital Wall Module Specification Data74-2950 Excel 10 Q7750A, Zone Manager Specification Data74-2952 Excel 10 Q7751A,B Router Specification Data74-2954 Excel 10 Q7752A Serial Interface Specification Data74-3067 Q7752B PCMCIA LONWORKS PCC-10 Card Specification Data74-2858 Excel 10 Q7740A,B FTT Repeaters Specification Data74-2951 Excel 10 Q7750A Zone Manager Checkout and Test Manual95-7521 Excel 10 W7750A,B,C Controller Installation Instructions95-7538 Excel 10 T7770A-G Wall Module Installation Instructions95-7620 T7560A,B Digital Wall Module Installation Instructions95-7509 Excel 10 Q7750A Zone Manager Installation Instructions95-7510 Excel 10 Q7751A,B Router Installation Instructions95-7511 Excel 10 Q7752A Serial Interface Installation Instructions95-7613 Q7752B PCMCIA LONWORKS PCC-10 Card Installation

Instructions95-7555 Excel 10 Q7740A,B FTT Repeaters Installation Instructions95-7554 Excel 10 209541B Termination Module Installation Instructions74-2937 LONSPEC� User�s Guide74-3068 LONSTATION� User�s Guide74-5587 CARE User�s Manual74-1392 CARE Excel 10 Zone Manager User�s Guide74-5577 CARE Icon Guide74-2039 XBS User�s Manual74-5018 XBS Application Guide

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

9 74-2958�2

Table 1. Agency Listing.

Abbreviations and DefinitionsAHU⎯Air Handling Unit; the central fan system that includes

the blower, heating equipment, cooling equipment, ventilation air equipment, and other related equipment.

CO⎯Carbon Monoxide. Occasionally used as a measure of indoor air quality.

CO2⎯Carbon Dioxide. Often used as a measure of indoor air quality.

CARE⎯Computer Aided Regulation Engineering; the PC based tool used to configure C-Bus and LONWORKS Bus devices.

C-Bus⎯Honeywell proprietary Control Bus for communications between EXCEL 5000® System controllers and components.

CPU⎯Central Processing Unit; an EXCEL 5000® OPEN™ SYSTEM controller module.

cUL⎯Underwriters Laboratories Canada

CVAHU⎯Constant Volume AHU; refers to a type of air handler with a single-speed fan that provides a constant amount of supply air to the space it serves.

DDF⎯Delta Degrees Fahrenheit.

D/X⎯Direct Expansion; refers to a type of mechanical cooling where refrigerant is (expanded) to its cold state, within a heat-exchanging coil that is mounted in the air stream supplied to the conditioned space.

Echelon⎯The company that developed the LONWORKS Busand the Neuron® chips used to communicate on theLONWORKS Bus.

Economizer⎯Refers to the mixed-air dampers that regulate the quantity of outdoor air that enters the building. In cool outdoor conditions, fresh air can be used to supplement the mechanical cooling equipment. Because this action saves energy, the dampers are often referred to as economizer dampers.

EMI⎯Electromagnetic Interference; electrical noise that can cause problems with communications signals.

E-Link⎯Refers to the Q7750A Zone Manager. This name is used in internal software and in CARE software.

EMS⎯Energy Management System; refers to the controllers and algorithms responsible for calculating optimum operational parameters for maximum energy savings in the building.

Device Agency CommentsW7750A,B,C Controllers UL Tested and listed under UL916 (file number E87741). The CVAHU W7750A,B,C

Controllers are UL94-5V listed and suitable for plenum mounting.cUL Listed (E87741).CE General Immunity per European Consortium Standards EN50081-1 (CISPR 22, Class B)

and EN 50082-1:1992 (based on Residential, Commercial, and Light Industrial).EN 61000-4-2: IEC 1000-4-2 (IEC 801-2) Electromagnetic Discharge.EN 50140, EN 50204: IEC 1000-4-3 (IEC 801-3) Radiated Electromagnetic Field.EN 61000-4-4: IEC 1000-4-4 (IEC 801-4)

Electrical Fast Transient (Burst). Radiated Emissions and Conducted Emissions:

EN 55022: 1987 Class B.CISPR-22: 1985.

FCC Complies with requirements in FCC Part 15 rules for a Class B Computing Device. Operation in a residential area can cause interference to radio or TV reception and require the operator to take steps necessary to correct the interference.

T7770A,B,C,D and T7560A,B Wall Modules

UL (Not applicable.)cUL (Not applicable.)FCC (Not applicable.)

Q7750A Excel 10 Zone Manager UL Tested and listed under UL916, file number S4804 (QVAX, PAZY).

CSA Listing pending.FCC Complies with requirements in FCC Part 15 rules for a Class A Computing Device.

Operation in a residential area can cause interference to radio or TV reception and require the operator to take steps necessary to correct the interference.

Q7740A,B FTT Repeaters, Q7751A,B Routers and

UL UL1784.

Q7752A Serial Adapter CSA Listed.FCC Complies with requirements in FCC Part 15 rules for a Class B Computing Device.

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 10

EEPROM⎯Electrically Erasable Programmable Read Only Memory; the variable storage area for saving user setpoint values and factory calibration information.

Enthalpy⎯The energy content of air measured in BTUs per pound (KiloJoules per Kg).

EPROM⎯Erasable Programmable Read Only Memory; the firmware that contains the control algorithms for the Excel 10 Controller.

Excel 10 Zone Manager⎯A controller that is used to interface between the C-Bus and the LONWORKS Bus. The Excel 10 Zone Manager also has the functionality of an Excel 100 Controller, but has no physical I/O points.

NOTE: The Q7750A Zone Manager can be referred to as E-Link in the internal software, CARE.

E-Vision⎯User interface software used with devices that operate via the FTT LONWORKS Bus communications protocol.

Firmware⎯Software stored in a nonvolatile memory medium such as an EPROM.

Floating Control⎯Refers to Series 60 Modulating Control of a valve or damper. Floating Control utilizes one digital output to pulse the actuator open, and another digital output to pulse it closed.

FTT⎯Free Topology Transceiver.

IAQ⎯Indoor Air Quality. Refers to the quality of the air in the conditioned space, as it relates to occupant health and comfort.

I/O⎯Input/Output; the physical sensors and actuators connected to a controller.

I x R⎯I times R or current times resistance; refers to Ohms Law: V = I x R.

K⎯Degrees Kelvin.

Level IV⎯Refers to a classification of digital communication wire. Formerly known as UL Level IV, but not equivalent to Category IV cable. If there is any question about wire compatibility, use Honeywell-approved cables (see Step 5 Order Equipment section).

LONWORKS Bus⎯Echelons LONWORKS network for communication among Excel 10 Controllers.

LONWORKS Bus Segment⎯An LONWORKS Bus section containing no more than 60 Excel 10s. Two segments can be joined together using a router.

NEC⎯National Electrical Code; the body of standards for safe field-wiring practices.

NEMA⎯National Electrical Manufacturers Association; the standards developed by an organization of companies for safe field wiring practices.

Node⎯A Communications Connection on a network; an Excel 10 Controller is one node on the LONWORKS Bus network.

NV⎯Network Variable; an Excel 10 parameter that can be viewed or modified over the LONWORKS Bus network.

PC⎯An Personal Computer with Pentium processor capable of running Microsoft® Windows™ 95.

Pot⎯Potentiometer. A variable resistance electronic component located on the T7770B,C or T7560A,B Wall Modules; used to allow user-adjusted setpoints to be input into the Excel 10 Controllers.

PWM⎯Pulse Width Modulated output; allows analog modulating control of equipment using a digital output on the controller.

RTD⎯Resistance Temperature Detector; refers to a type of temperature sensor whose resistance output changes according to the temperature change of the sensing element.

Subnet⎯A LONWORKS Bus segment that is separated by a router or repeater.

TOD⎯Time-Of-Day; the scheduling of Occupied and Unoccupied times of operation.

TPT⎯Twisted Pair Transceiver.

VA⎯Volt Amperes; a measure of electrical power output or consumption as applies to an ac device.

Vac⎯Voltage alternating current; ac voltage rather than dc voltage.

VAV⎯Variable Air Volume; refers to either a type of air distribution system, or to the W7751 Excel 10 VAV Box Controller that controls a single zone in a variable air volume delivery system.

VOC⎯Volatile Organic Compound; refers to a class of common pollutants sometimes found in buildings. Sources include out-gassing of construction materials, production-line by-products, and general cleaning solvents. A VOC is occasionally used as a measure of indoor air quality.

W7750⎯The model number of the Excel 10 CVAHU Controllers (also see CVAHU).

W7751⎯The model number of the Excel 10 VAV Box Controllers (also see VAV).

Wall Module⎯The Excel 10 Space Temperature Sensor and other optional controller inputs are contained in the T7770 or the T7560A,B Wall Modules. See Application Step 5. Order Equipment for details on the various models of Wall Modules.

XBS⎯Excel Building Supervisor; a PC based tool for monitoring and changing parameters in C-Bus devices.

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

11 74-2958�2

Construction

ControllersThe Excel 10 W7750 Controller is available in three different models. The W7750A Model, which is a low cost controller made for simple single zone air handlers and heat pump controls. The W7750B,C Models are intended for more complex applications.

The W7750B,C Models use Triacs for their digital outputs, where as the W7750A Model uses dry-contact relays. The W7750C Model also has three analog outputs available on terminals 16, 17 and 18.

All wiring connections to the controller are made at screw terminal blocks. Connection for operator access to the LONWORKS Bus is provided by plugging the SLTA connector cable into the LONWORKS Bus communications jack.

The W7750A,B,C Models consist of a single circuit board that is mounted in a sheet metal subbase and protected by a factory snap-on cover. The three controllers have the same physical appearance except for terminals 16 through 20

(W7750A) and different labels next to the wiring terminals (see Fig. 3, 5 or 6). Wires are attached to the screw terminal blocks on both sides of the controller. The controllers mount with two screws (see Fig. 4 or 7). The W7750 can also be mounted using DIN rail. To mount the W7750 on DIN rail, purchase two DIN rail adapters (obtain locally) part number TKAD, from Thomas and Betts, see Fig. 8, then snap onto standard EN 50 022 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.) DIN rail. DIN rail is available through local suppliers.

A channel in the cover allows the controller status LED to be visible when the cover is in place. There are no field-serviceable parts on the circuit board and, therefore, it is intended that the cover never be removed.

The W7750A,B,C can be mounted in any orientation. Ventilation openings were designed into the cover to allow proper heat dissipation regardless of the mounting orientation. See Fig. 4 and 7.

The input/output and control differences between the two models are summarized in Table 2. The I/O points in Table 2 are the free I/O points that are not reserved for Wall Module use.

Table 2. List of Differences in W7750A and W7750B,C Controllers.

a The T7770 or the T7560 Wall Modules includes I/O points for two analog inputs for the space temperature and the setpoint knob, a digital input for the Bypass pushbutton, and a digital output for the LED Bypass Indicator. These W7750 I/O points are configurable, but are normally used for the Wall Module.

W7750A Model W7750B,C ModelsDigital Outputs Six Relay Outputs Eight Triac Outputs (Five Triac outputs on W7750C)Digital Inputs Two FourWall Module One* Onea

Analog Outputs None Three 4 to 20 mA Outputs (W7750C only)Analog Inputs One (Resistive Input Only) Four (Two Resistive and two Voltage/Current Inputs)DC Power None 20 Vdc available to power optional sensorsFloating (Series 60) Control Economizer Only Heating, Cooling, and/or EconomizerPWM Control None Heating, Cooling, and/or Economizer

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 12

Fig. 3. Excel 10 W7750A Constant Volume AHU Controller.

M10099B

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 J3

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16

EGND

LED SNSR GND SET PT AI-1 OHM

GND DI-1 GND GND DI-2 NOTUSED

LONWORKSBUS

LON

JACK

W1 W2 Y1 Y2 GNETWORK

DO Rc Rh24

VAC

W7750A

24 VACCOM

NOTUSED

NOTUSED

NOTUSED

NOTUSED

NOTUSED

BYPASS

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

13 74-2958�2

Fig. 4. W7750A construction in in. (mm).

Performance Specifications

Power:24 Vac with a minimum of 20 Vac and a maximum of 30 Vac at either 50 or 60 Hz. The W7750A power consumption is 6 VA maximum at 50 or 60 Hz. The W7750B,C power consumption is 12 VA maximum at 50 or 60 Hz.The W7750A,B,C is a NEC Class 2 rated device. This listing imposes limits on the amount of power the product can consume or directly control to a total of 100 VA.

Special Note for the W7750B,C Unit:The individual Triac outputs incorporate an internal common connection with the input power transformer. The Triacs provide a switched path from the hot side (R - high-side switching) of the transformer through the load to the common of the transformer. (Refer to Fig. 26 and 30 for low-side switching - J2 jumper.) The W7750B,C Controller design must use the same power transformer for any loads connected to that controller; see Fig. 30.

Each individual Triac is rated 1A at 30 Vac maximum. Under all operating conditions, the maximum load/source power budget for the W7750B,C Controller is 100 VA. Actual allowable Triac current is 500 mA MAX.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 J3

E

GND

LED BYPASS SNSR GND SET PT AI-1

OHM

GND DI-1 GND GND DI-2 NOT

USEDLONWORKS

BUS

LON

JACK

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16

WI W2 Y1 Y2 G

NEYWORK

DORc Rh

24

VAC

5-3/16 (132)

5-5/8(143)

3-1/16(77)

2-1/8(54)

6 (152)

M10098B

24

VAC

COM

NOT

USEDNOT

USED

NOT

USEDNOT

USED

NOT

USED

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 14

Fig. 5. Excel 10 W7750B Constant Volume AHU Controller.

CPU:Motorola or Toshiba 3150 Neuron processor, containing three eight-bit CPUs. Each Neuron has a unique 48-bit network identification number.

Memory Capacity:64K ROM/PROM (6K reserved for network operations, 58K usable for control algorithm code).512 bytes EEPROM.2K RAM.

Specified Space Temperature Sensing Range:45 to 99°F (7 to 37°C) with an allowable control setpoint range from 50 to 90°F (10 to 32°C) when initiated from the network and 55 to 85°F (13 to 29°C) when configured and connected to T7770 or T7560 Wall Modules.

M6854B

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 J3

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16

E GND

LED BYPASS SNSRSET PT AI-1

OHMA1-2 OHM

AI-3 V/mA

AI-4V/mA

20VDCOUT

DI-4DI-3 DI-2

DI-1VAC24

VAC24

COM1

OUT2

OUT3

OUT4

OUT5

OUT6

OUT7

OUT8

OUT

AIGND AI

GND AIGND LONWORKS

BUSLON

JACK

DIGND DI

GND

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

15 74-2958�2

Fig. 6. Excel 10 W7750C Constant Volume AHU Controller.

M17489

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 J3

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16

E GND

LED BYPASS SNSRSET PT AI-1

OHMA1-2 OHM

AI-3 V/mA

AI-4V/mA

20VDCOUT

DI-4DI-3 DI-2

DI-1VAC24

VAC24

COM1

OUT2

OUT3

OUT4

OUT5

OUTA01

A02

A03

AIGND AI

GND AIGND LONWORKS

BUSLON

JACK

DIGND DI

GND

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 16

Fig. 7. W7750B,C construction in in. (mm). W7750C (shown) has three 4 to 20 mA analog outputs.)

Communications:The W7750A,B,C Controller uses a Free Topology Transceiver (FTT) transformer-coupled communications port running at 78 kilobits per second (kbps). Using the transformer-coupled communications interface offers a much higher degree of common-mode noise rejection while ensuring dc isolation.

Approved cable types for LONWORKS Bus communications wiring is Level IV 22 AWG (0.34 mm2) plenum or nonplenum rated unshielded, twisted pair, solid conductor wire. For

nonplenum areas, use Level IV 22 AWG (0.34 mm2) such as: U.S. part AK3781 (one pair), U.S. part AK3798 (one pair stranded), or U.S. part AK3782 (two pair). In plenum areas, use plenum-rated Level IV, 22 AWG (0.34 mm2) such as U.S. part AK3791 (one pair) or U.S. part AK3792 (two pair). (See Tables 9 and 11 for part numbers.) Contact Echelon Corp. Technical Support for the recommended vendors of Echelon approved cables.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 J3

E GND

LED BYPASS SNSR AIGND

AIGND

AIGND

SET PT AI-1OHM

AI-2OHM

AI-3V/mA

AI-4V/mA

20VDCOUT

LONWORKS

BUSLON

JACK

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16

DI-4DI

GNDDI-3 DI-2

DIGND

DI-1VAC24

VAC24

COM1

OUT

2OUT

3OUT

4OUT

5OUT

A01

A02

A03

5-3/16 (132)

5-5/8(143)

3-1/16(77)

2-1/8(54)

6 (152)

M17490

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

17 74-2958�2

Fig. 8. DIN rail adapters.

The FTT supports polarity insensitive free topology wiring. This frees the system installer from wiring using a specific bus topology. T-tap, star, loop, and mixed wiring topologies are all supported by this architecture. The maximum LONWORKS Bus length when using a combination of T-tap, star, loop, and bus wiring (singly terminated) is 1640 ft. (500m) with the maximum node-to-node length of 1312 ft. (400m). In the event that the total wire length is exceeded, then a Q7740A 2-Way Repeater or a Q7740B 4-Way Repeater can be used to allow the number of devices to be spread out as well as increasing the length of wire over which they communicate. The maximum number of repeaters per segment is one. A Q7751A,B LONWORKS Bus Router can also be used to effectively double the maximum LONWORKS Bus length.

NOTE: For LCBS the router must be configured as a repeater.

The advantage of using the router is that it segregates traffic to a segment while when using the repeater, all traffic is repeated on each segment. When utilizing a doubly

terminated LONWORKS Bus structure, use a continuous daisy-chain with no stubs or taps from the main backbone, The maximum LONWORKS Bus length is 4593 ft. (1400m) with the maximum node-to-node length of 3773 ft. (1150m).

FTT networks are very flexible and convenient to install and maintain, but it is imperative to carefully plan the network layout and create and maintain accurate documentation. This aids in compliance verification and future expansion of the FTT network. This also keeps unknown or inaccurate wire run lengths, node-to-node (device-to-device) distances, node counts, total wire length, inaccurate repeater/router locations, and misplaced or missing terminations minimized. Refer to LONWORKS Bus Wiring Guidelines form, 74-2865 for complete description of network topology rules.

LONMARK® FUNCTIONAL PROFILEW7750 Controllers support the LONMARK Functional Profile number 8030 Roof Top Unit Controller, version 1.0 (see Fig. 9).

M6857

1

2

3

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 18

Fig. 9. Functional profile of LONMARK® RTU object details (variables not implemented in Excel 10 CVAHU are

greyed).

Environmental:Operating Temperature: -40 to 150°F (-40 to 65.5°C).

Shipping Temperature: -40 to 150°F (-40 to 65.5°C).

Relative Humidity: 5% to 95% noncondensing.

Vibration: Rated V2 level compliant.

Inputs/OutputsThe W7750A Unit supports the following hardware features:� Three 20K ohm NTC (2021 ohms at 180°F through

834K ohms at -40F) or PT3000 (3973 ohms at 180ºF through 2916 ohms at -40°F) resistive analog inputs (one reserved for space temperature and one reserved for the setpoint knob).

� Three dry contact digital inputs (one reserved for the Bypass pushbutton).

� LED digital output (only for the wall module LED) 2.5V at 3 mA.

� Six 24 Vac relay digital outputs (1.5A relays rated at 7.5A inrush current).

The W7750B,C Units support the following hardware features:� Four 20K ohm NTC (2021 ohms at 180°F through

834K ohms at -40°F) or PT3000 (3973 ohms at 180ºF through 2916 ohms at -40°F) resistive analog inputs (one reserved for space temperature and one reserved for the setpoint knob).

� Two 0.2 to 10 Vdc or 4 to 20 mA (user selectable) analog inputs.

� Five dry contact digital inputs (one reserved for the Bypass pushbutton).

� Eight on the W7750B (five on the W7750C) 24 Vac Triac digital outputs (500 mA MAX). The W7750C Unit also supports three 4 to 20 mA analog outputs.

� LED digital output (only for the wall module LED, T7770 models or LCD, T7560A,B) 2.5V at 3 mA.

� One 20 Vdc power supply for auxiliary devices with a maximum current of 50 mA.

ANALOG INPUTSOnly one of each type of input is allowed. For example, only one Outdoor Air Temperature sensor is allowed. No duplicate Outdoor Air Temperature sensors are usable on the same controller.

Space Temperature: Type: RTD.Supported Sensors: T7770A,B,C,D; T7560A,B.

Discharge Air Temperature:Type: RTD.Supported Sensors: C7041B,C,D,F,J,K, C7100A1015 (see

note below), C7770A1006.

Outdoor Air Temperature:Type: RTD.Supported Sensors:

PT3000: C7170A1002, C7031G2014.20K ohm: C7041F.

Return Air Temperature:Type: RTD.Supported Sensors: C7041B,C, C7100A, C7770A.

NOTE: PT3000 sensors (such as the C7100A) are not recommended for floating control (real time - discharge or return configured as space sensor). They are intended for monitoring or differential (staged) control.

Outdoor Air Humidity (W7750B,C only):Type: Voltage/Current.Supported Sensors:

0-10 Vdc or 4-20 mA: H7635C.2 to 10 Vdc only: C7600B.4 to 20 mA only: C7600C.

HardwareOutput

Roof Top Unit Controller number 8030

Mandatory NetworkVariables

ManufacturerDefinedSection

OptionalNetworkVariables

nv9nviOutsideRH

SNVT_lev_percent

nv8nviOutsideTemp

SNVT_ temp_p

nv7nviSetPtOffset

SNVT_ temp_p

nv6nviOccCmd

SNVT_occupancy

nv5nviApplicModeSNVT_hvac_mode

nv16nvoCO2SNVT_ppm

nv12nvoOutsideRHSNVT_ lev_percent

nv11nvoOutsideTemp

SNVT_ temp_p

nv10nvoEffectSetPt

SNVT_ temp_p

nv2nviSetPoint

SNVT_temp_p

nv1nviSpaceTemp

SNVT_temp_p

nv4nvoUnitStatus

SNVT_hvac_status

nv3nvoSpaceTemp

SNVT_ temp_p

nv13nviSpaceRHSNVT_ lev_percent

nv14nviCO2SNVT_ppm

HardwareInput

nc42 - CO2Limit

nc49 - Send Heartbeat (mandatory)

nc60 - Occupancy Temperature Setpoints

(optional)nc48 - Maximum Receive Timenc17 - Location

(mandatory)

(optional)(mandatory)

Configuration Properties

nv15nviEmergCmd

SNVT_hvac_emerg

M11580

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

19 74-2958�2

Return Air Humidity (W7750B,C only):Type: Voltage/Current.Supported Sensors:

0-10 Vdc or 4-20 mA: H7625B, H7635B, H7655B.2 to 10 Vdc only: C7600B.4 to 20 mA only: C7600C.

Outdoor Air Enthalpy (W7750B,C only):Type: Current.Supported Sensors: C7400A1004 (4 to 20 mA).

Return Air Enthalpy (W7750B,C only):Type: Current.Supported Sensors: C7400A1004 (4 to 20 mA).

Air Filter Differential Pressure (W7750B,C only):Type: Voltage.Supported Sensors: P7640 (set for 4 to 20 mA; use 500 ohm

resistor for 2 to 10 Vdc) 0 to 5 in. w.c. (1.25 kPa).

CO2 Sensor (W7750B,C only):Type: Voltage.Supported Sensors: C7232A,B (set for 0-2000 ppm);

C7632A,B (0-2000 ppm, fixed), 0-10 Vdc for both.

Monitor Sensor for network use (W7750B,C only):Type: Voltage.Supported Sensors: Third party 2 to 10 Vdc, 2 to 10V dis-

played.

DIGITAL INPUTS

NOTE: Only one of each type of input is allowed. For example, only one Smoke Monitor is allowed. No duplicate Smoke Monitors are usable on the same controller.

Dry-contact inputs are sensed using a 9 milliamp at 4.8 volts detection circuit. It is very important that the device used contains high quality, noncorroding contacts with resistivity that does not degrade; that is, increase over time. Use noble metal (such as gold or silver), or pimpled or sealed contacts to assure consistent, long-term operation.

Two of the following Digital Inputs (DIs) can be configured when using the W7750A, and four of the following when using the W7750B,C:� Fan Status:

Contact Closed = Fan on� IAQ Switch:

Contact Closed = Poor Air Quality� Time Clock:

Contact Closed = Occupied Mode; Contact Open = Unoccupied Mode

� Schedule Master:Contact Closed = Local time clock is used as master time clock

� Economizer Enable Signal:Contact Closed = Economizer Enabled for cooling use

� Smoke Monitor:Contact Closed = Smoke Detected

� Dirty Filter:Contact Closed = Dirty Filter

� Shutdown Signal:Contact Closed = Shut off all equipment

� Occupancy Switch:Contact Closed = Room is Occupied; Contact Open = Room is Unoccupied

� Window Monitor:Contact Closed = Window is Closed

� Coil Freeze Stat: (Only use this DI when using E-Vision.)Contact Closed = Coil Freeze condition sensed

� Wall Module Bypass Pushbutton:Momentary DI (See Appendix B�Sequences of Operation for bypass details.)

TRIAC OUTPUTS (W7750B,C MODELS ONLY)

Power ratings: 20 Vac to 30 Vac at 25 mA MIN to 500 mA MAX current for any voltage.

IMPORTANTWhen any device is energized by a Triac, the device must be able to sink a minimum of 25 mA.

NOTE: Triacs sink current to the 24 Vac hot (high side switching - factory default) or common (low side switching); see Fig. 30 for wiring example of high side switching.

IMPORTANTIf non-Honeywell motors, actuators, or transducers are to be used with Excel 10 Controllers, Triac compatibility must be verified (see previous NOTE).

DIGITAL OUTPUTSCOOL STAGE 1COOL STAGE 2COOL STAGE 3COOL STAGE 4HEAT STAGE 1HEAT STAGE 2HEAT STAGE 3HEAT STAGE 4CHANGE OVER RELAYFANAUX ECONOCCUPANCY STATUSECON OPENECON CLOSECOOL OPENCOOL CLOSEHEAT OPENHEAT CLOSEHEAT COOL STAGE 1HEAT COOL STAGE 2HEAT COOL STAGE 3HEAT COOL STAGE 4FREE1 (NOTE: Free1, Free1 Pulse On and Free1 Pulse Off are three separate and unique digital output points. Because they are not related, they all can be configured in a CVAHU controller at the same time.)FREE2FREE1 PULSE ONFREE1 PULSE OFFECON PWMHEAT PWMCOOL PWMUNUSED

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 20

Wall ModulesThe T7770 or T7560 Wall Modules for the Excel 10 Controllers are available in a variety of configurations. The models T7770A1006 and T7770C1002 are shown in Fig. 10. The T7770B,D are the same physical size (see Product Names section for differences). The models T7560A, and T7560B are shown in Fig. 11. The T7560A,B are the same physical size.

Duct SensorThe dimensions of the C7770A duct-mounted sensor are shown in Fig. 12.

Fig. 10. T7770A,B,C,D construction in in. (mm).

STANDARD

UTILITY

CONDUIT

BOX (2 X 4)

MOUNTING

HOLES

KNOCKOUTS FOR EUROPEAN

APPLICATIONS

3-5/32 (80)

2-3/8 (60)

29/32 (23)

5-1/16(128)

2-3/8(60)

T7

77

0A

10

06

M15119

STANDARD

UTILITY

CONDUIT

BOX (2 X 4)

MOUNTING

HOLES

KNOCKOUTS FOR EUROPEAN

APPLICATIONS

3-5/32 (80)

2-3/8 (60)

1-1/4 (32)

5-1/16(128)

2-3/8(60)

T7

77

0C

7065

60

55 85

80

75D

IP S

witch

S4

Se

ttin

gs:

1,3

,5=

on; 2,4

=off 2,4

=on; 1,3

,5=

off 1,2

,3,4

=on; 5=

0ff

W7

75

3X

L6

00

-XL

20

W7

75

2

LE

D R

ET

UR

N

BY

PA

SS

LE

D

FA

N

SE

TP

T

SE

NS

OR

GN

D

LE

D

SE

TP

T

SE

NS

OR

AL

CO

M

LE

D

SE

TP

T

SE

NS

OR

GN

D

BY

PA

SS

/FA

NB

YP

AS

S/F

AN

9 8 7 6 5 4 3 2 1

E-B

US

E-B

US

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

21 74-2958�2

Fig. 11. T7560A,B construction in in. (mm).

Configurations

GeneralTables 3 and 4 provide an overview of the Excel 10 W7750 configuration options. All W7750s are assumed to have a supply fan digital output. Additionally, Tables 3 and 4 list the general mechanical equipment options available with the W7750 Controller. See Application Step 6. Configure Controllers, for further information on configurations.

IMPORTANTFor floating control, the Excel 10 W7750 Controller is designed to work only with Series 60 valve and damper actuators. Full stroke actuator drive-time must be between 20 and 240 seconds (0.25 to 4.0 minutes).

Fig. 12. C7770A construction in in. (mm).

3-15/16 (99) 1-3/16 (30)

4-1/8(104)

M17479

1/4 (6)DIAMETER (2 HOLES)M17961

1(25)

3/4 (19)

1-1/2 (38)

2 (51) 1 (25)

1/16 (2)

6 (152)8 (203)

3/8 (9)FITTING

NEOPRENEGASKET

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 22

Table 3. Common Configuration Options Summary For W7750A,B,C Controllers.Option Possible Configurations Common To All W7750 Models

Supply Fan 1. Mandatory Digital Output.Type of Air Handler 1. Conventional.

2. Heat Pump.Occupancy Sensor 1. None.

2. Connected: Contacts closed equals Occupied.3. Network (Occ/Unocc signal received via the LONWORKS Bus network).

Window Sensor 1. None.2. Physically Connected: Contacts closed equals window closed.3. Network (Window Open/Closed signal received via the LONWORKS Bus).

Wall Module Option 1. Local (direct wired to the controller).(The T7560A,B has no LONWORKS Bus access) 2. Network (sensor value received via the LONWORKS Bus).Wall Module Type 1. Sensor only.(All wall modules have a LONWORKS Bus access 2. Sensor and Setpoint adjust.jack except T7560A,B) 3. Sensor, Setpoint adjust and Bypass.

4. Sensor and Bypass.Smoke Emergency Initiation 1. None.

2. Physically Connected: Contacts closed equals smoke detected.3. Network (Emergency/Normal signal received via the LONWORKS Bus).

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

23 74-2958�2

Table 4. Configuration Options Summary for W7750A,B,C Controllers.

Allowable Heating and Cooling Equipment ConfigurationsEach W7750 device can control a variety of different types of mechanical cooling and heating equipment within roof top air

handlers. See Fig. 13 through 17 for a conceptual overview of some typical configurations. For specific wiring details, see the Prepare Wiring Diagrams section.

OptionPossible Configurations for the

W7750A Model Possible Configurations for the W7750B,C ModelsType of 1. One stage. 1. One stage.Heating 2. Two stages. 2. Two stages.

3. Three stages. 3. Three stages.4. Four stages. 4. Four stages.5. None. 5. Series 60 Modulating electric valve, or pneumatic via transducer.

6. Pulse Width Modulating electric valve, or pneumatic via transducer.7. None.

Type of 1. One stage. 1. One stage.Cooling 2. Two stages. 2. Two stages.

3. Three stages. 3. Three stages.4. Four stages. 4. Four stages.5. None. 5. Series 60 Modulating electric valve, or pneumatic via transducer.

6. Pulse Width Modulating electric valve, or pneumatic via transducer.7. None.

Type of Economizera

1. Digital Output Enable/Disable signal for controlling an external economizer package (comes on with the fan).

1. Digital Output Enable/Disable signal for controlling an external economizer package.

2. Series 60 Modulating electric damper motor, or pneumatic via transducer.

2. Series 60 Modulating electric damper motor, or pneumatic via transducer.

3. None. 3. Pulse Width Modulating electric damper motor, or pneumatic via transducer.

4. None.IAQ Option 1. None. 1. None.

2. Local IAQ Digital Input�directly wired to the controller. (Contacts closed means poor IAQ is detected.)

2. Local IAQ Digital Input�directly wired to the controller. (Contacts closed means poor IAQ is detected.)

3. Network (IAQ Override signal received via the LONWORKS Bus).

3. Network (IAQ Override signal received via the LONWORKS Bus).

4. Local CO2 Analog Input�directly wired to the controller. (The sensor must be a 0 to 10V device representing 0 to 2000 PPM CO2.)

Coil Freeze 1. None. 1. None.Stat Option 2. Local Coil Freeze Stat Digital

Input�directly wired to the controller. (Contacts closed means that coil freeze condition is sensed.)

2. Local Coil Freeze Stat Digital Input�directly wired to the controller. (Contacts closed means that coil freeze condition is sensed.)

Filter Monitor 1. None. 1. None.Option 2. Local Dirty Filter Digital

Input�directly wired to the controller. (Contacts closed means that the filter is dirty.)

2. Local Dirty Filter Digital Input�directly wired to the controller. (Contacts closed means that the filter is dirty.)

3. Local Analog Input for Differential Pressure across the Filter (directly wired to the controller). The sensor must be a 2 to 10V device representing 0 to 5 in. w.c. (1.25 kPa).

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 24

Staged Heating/Cooling ControlStaged equipment control is available for up to four stages of heating or four stages of cooling. On the W7750, the stages are activated through digital outputs (Triacs on the W7750B,C and dry-contact relays on the W7750A) one for each stage wired to 24 Vac contactors (see Fig. 27 and 30 in Step 4. Prepare Wiring Diagrams section for wiring details). Note that the number of physical Digital Outputs (DOs) on the controller limits the total number of stages that can be controlled. For example, the W7750A Model has six digital outputs, and because one is used for the supply fan, there are five DOs available for any combination of heating and cooling stages (with a maximum of four stages of heating and four stages for cooling). The W7750B Model offers two additional DOs, for a total of eight. The W7750C offers five DOs and three Analog Outputs (AOs). Fig. 13 shows a typical application of two stages of heat and two stages of cooling.

Fig. 13. Fan with two stages of heating and two stages of cooling.

Modulating Heating/Cooling ControlThe W7750 Controller provides modulating equipment control for heating and cooling equipment (and economizer dampers, see Fig. 16) using either Series 60 Floating Control or Pulse Width Modulated (PWM) control, (PWM control is available on the W7750B,C only). The Series 60 Modulating Control is provided through two Relay digital outputs on the W7750A (for economizer only) or two Triac digital outputs on the W7750B,C (one to pulse the valve actuator open and one to pulse it closed). PWM control positions the actuator based on the length, in seconds, of the pulse from the digital output. For PWM, the controller outputs a pulse whose length consists of two parts, a minimum and a maximum. The minimum pulse

time represents the analog value of 0 percent and the maximum pulse length that represents an analog value of 100 percent. If the analog value is greater than 0 percent, an additional time is added to the minimum pulse time. The length of time added is directly proportional to the magnitude of the analog value. The PWM actuator will begin to use the analog value at the end of the pulse and will continue to use this value until a new pulse is received. Refer to Appendix B under PWM Control for an example. Series 60 actuators are generally less expensive than those for PWM, but the trade-off is that PWM requires only a single controller digital output while floating control uses two DOs. Refer to Appendix B under Series 60 Modulating Control for an example. Fig. 14 illustrates a system with modulating heating and cooling (see Fig. 29 and 31 in Step 4. Prepare Wiring Diagrams section.

Fig. 14. Fan, modulating heating and modulating cooling.

NOTE: Pneumatically actuated valves can be controlled using a pneumatic transducer device. See Fig. 17. Also, transducer devices are available from third party vendors to convert PWM outputs to a voltage or current signal if desired.

Heat Pump ControlThe W7750 Controller handles heat pump applications similarly to staged heating/cooling control. Heat pump applications are supported by providing outputs for up to four compressor stages, a change-over relay for the refrigerant reversing valve, and up to four stages of auxiliary heat. Note that the W7750A Model has six digital outputs, and therefore, with one DO used for the supply fan and one for the change-over relay, there are four outputs available for any combination of compressors and auxiliary heat stages. The W7750B Model offers two additional DOs for a total of eight, while the W7750C Model offers five DOs and 3 AOs. Fig. 15 illustrates a typical heat pump system with auxiliary heat.

M17491

MIXEDAIR

HEATCOIL

COOLCOIL

DISCHARGEAIR

W1 W2

Y1 Y2

- +

FAN

FANSTARTER

COMPRESSORS

GAS COMBUSTIONCONTROLS

EXCEL 10CVAHU

W7750A,B,C

T7560A,B OR T7770

MIXEDAIR

HEATCOIL

COOLCOIL

DISCHARGEAIR

- +

FAN

FANSTARTER

CHILLEDWATERVALVE

HOTWATERVALVE

M17492

EXCEL 10CVAHU

W7750A,B,C

T7560A,B OR T7770

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

25 74-2958�2

Fig. 15. Heat pump with two compressors and auxiliary heat stage(s).

Economizer ControlEconomizer control is available concurrently with any configuration in the W7750 when DOs are not all used by the heating and cooling equipment. Two types of economizer controls are supported by the W7750 Controller, modulating control and enable/disable control. Modulating control can be either Series 60 Floating Control or PWM control (PWM

control is available on the W7750B,C only). A discharge air temperature sensor is required for modulating economizer damper control. Enable/disable control is provided to emulate the Honeywell T7300 thermostat economizer operation, where a DO tracks the occupancy status of the controller. An external packaged economizer control then modulates the dampers. For modulating control, the economizer is enabled or disabled based on one of ten available strategies (see Appendix B�Sequences of Operation�Economizer Enable/Disable Control section, for further details). Fig. 16 illustrates a system with modulating economizer dampers (see Fig. 29, 31, 32 and 35 in Step 4. Prepare Wiring Diagrams section, for wiring details).

Fig. 16. Economizer control.

MIXEDAIR

AUXILIARYHEATSTAGE(S)

SHARED HEAT ANDCOOL COIL

DISCHARGEAIR

+

FAN

FANSTARTER

COMPRESSOR ANDCHANGEOVER VALVE

COMP 1

COMP 2

CHANGEOVER RELAY

M17493

EXCEL 10CVAHU

W7750A,B,CT7560A,B OR T7770

OUTDOORAIR

RETURNAIR

HEATCOIL

COOLCOIL

DISCHARGEAIR

- +

FAN

FANSTARTER

DISCHARGETEMPERATURESENSOR REQUIREDFOR ECONOMIZERCONTROL

M

PWM ORSERIES 60FLOATINGMOTOR

M17494

EXCEL 10CVAHU

W7750A,B,C

T7560A,B OR T7770

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 26

Pneumatic Actuator ControlThe W7750B,C Controller can control pneumatic actuators for any or all of the three modulating outputs provided by the control algorithm (heat, cool and economizer). Control of pneumatic water/steam valves and damper actuators is provided through a transducer device using either Series 60 Floating Control or PWM DOs. A floating-to-pneumatic, or a PWM-to-pneumatic transducer is required for each output signal. The W7750A Controller can drive Series 60 Floating Control for only economizer control. There are no PWM outputs configurable on the W7750A model.

For projects with existing pneumatically actuated reheat valves, the Excel 10 W7750 Controller output must be converted to a pneumatic signal using a transducer device developed for use with Excel 10 Controllers. The transducer is available through Honeywell, or directly from a third party manufacturer.

Fig. 17 depicts a typical W7750 System with modulating heating valve using a pneumatic valve actuator. Also see Fig. 37 for wiring an RP7517B Pneumatic Transducer to a W7750C Controller.

NOTE: When choosing the pneumatic pressure range, make sure that the close-off pressure is 2 to 3 psi greater than that of the spring range. When using a spring range of 5 to 10 psi with 10 psi as the closed posi-tion, do not use a 0 to 10 psi model transducer; use a 0 to 20 psi transducer as the recommended selec-tion.

Fig. 17. Modulating heat with pneumatic valve actuator.

Mixed Output-type ControlThe W7750B,C Controller provides control for mixed-output-types of applications such as PWM heating and staged cooling control occurring simultaneously with Series 60 Floating Economizer Damper Control.

Occupancy SensorExcel 10 W7750 Controllers provide a digital input for connection to an occupancy sensor. This is a device, such as a passive infrared motion detector, that contains a dry contact

(see following NOTE) closure to indicate whether or not people are present in the space. The Excel 10 W7750 Controller expects a contact closure to indicate the space is Occupied. See Fig. 27 through 35 in Application Step 4, Prepare Wiring Diagrams, for details on wiring connections.

The control algorithm in the Excel 10 Controller uses the occupancy sensor, if configured, to determine the Effective Occupancy (see Table 5) mode of operation. If the Time Of Day (TOD) schedule indicates an Occupied state, and the occupancy sensor contact is closed, the Effective Occupancy mode is Occupied. However, if the TOD schedule indicates an Occupied state and the occupancy sensor contact is open, then the Effective Occupancy mode is STANDBY. The temperature control algorithm is then controlled to the STANDBY Cooling and Heating Setpoints.

If the occupancy sensor is not configured, a local controller can be put in the STANDBY mode only by either a one-to-one association of the occupancy sensor from another Excel 10 Controller to the local controller, or by receiving the STANDBY mode signal via the LONWORKS Bus.

NOTE: The Excel 10 Controller has limited power available (only 9 mA at 4.8 volts) for checking the digital inputs for contact closures. It is very important that the device used contains high quality, noncorroding con-tacts with resistivity that does not degrade; that is, increase over time. Use noble metal (such as gold or silver), or pimpled or sealed contacts to assure con-sistent, long-term operation.

Window Open/Closed Digital InputA digital input is also provided for detecting whether a window in the space was opened. The Excel 10 W7750 Controller can be connected to a dry contact (see the following NOTE and Fig. 27 through 35 in Application Step 4. Prepare Wiring Diagrams, for details) or a set of contacts wired in series (for monitoring multiple windows) to verify that the window(s) are closed. The algorithm expects a contact closure to indicate the window is closed. If an open window is detected, the algorithm changes the mode of operation to FREEZE_PROTECT, which shuts down the control functions, and watches for low space temperature conditions. The frost protection setpoint is 46.4°F (8°C), and the frost alarm occurs at 42.8°F (6°C).

NOTE: (This is the same NOTE as in the Occupancy Sensor section.) The Excel 10 has limited power available (only 9 mA at 4.8 volts) for checking the digital inputs for contact closures. It is very important that the device used contains high quality, noncorroding con-tacts with resistivity that does not degrade; that is, increase over time. Use noble metal (such as gold or silver), or pimpled or sealed contacts to assure con-sistent, long-term operation.

Wall Module OptionsAs previously discussed, there are four basic varieties of the T7770 Wall Modules and two of the T7560 Digital Wall Module (see the Product Names and the Construction sections). Also, a T7770 and T7560 Wall Modules can be shared among two or more W7750s. The control algorithm must be given this wall module information when configuring the W7750.

VALVE

PNEUMATIC

ACTUATOR

PNEUMATIC

TRANSDUCER

M

1

1

PNEUMATIC MAIN OR BRANCH LINE MUST BE 1/4 IN. (6 MM)

OR LARGER TUBING. A MINIMUM OF 6 FT (1.8M) OF TUBING

IS NEEDED IN A BRANCH LINE.

MIXED

AIR

HEAT

COIL

DISCHARGE

AIR

+

FAN

FAN

STARTER

M17495A

T7560A,B OR T7770

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

27 74-2958�2

Dirty Filter MonitorThe air filter in the air handler can be monitored by the W7750 and an alarm is issued when the filter media needs replacement. The two methods of monitoring the filter are:

1. Connecting a differential pressure switch to a digital input on the W7750A or W7750B,C.

2. Wiring a 2 to 10V differential pressure sensor (such as the P7640A,B 4-20 mA with 500 ohm resistor) to a voltage input on the W7750B,C. If the analog input sensor is used, its measured value 0 to 5 in. w.c. (0 to 1.25 kPa) is compared to a user-selectable setpoint [FltrPressStPt�valid range: 0 to 5 in. w.c. (0 to 1.25 kPa)], and the Dirty Filter alarm is issued when the pressure drop across the filter exceeds the setpoint.

Indoor Air Quality (IAQ) OverrideThe Excel 10 W7750 Controller provides IAQ ventilation control using one of two different methods of detecting poor air quality. The first is with an IAQ switch device connected to a digital input on the W7750 Controller, where a contact closure indicates poor air quality, and initiates the IAQ Override mode. The device can detect poor air quality using any desired measure such as CO2, VOC, CO, etc. The second method, which is only available on the W7750B,C, is through an analog input that connects to a CO2 sensor (0 to 10 Vdc, as provided with the C7232A,B). The measured value of CO2 from this sensor (0 to 2000 PPM) is compared to the setpoint (IAQSetpt). When the CO2 level is higher than the

setpoint (800 PPM adjustable), the IAQ Override is initiated. The IAQSetpt hysteresis is 50 PPM, IAQ Override is deactivated at a CO2 level less than 50 PPM below setpoint.

The effect of initiating the IAQ Override mode is that the economizer dampers are allowed to open above the standard minimum position setting to allow more fresh air to enter the building. See Appendix B�Sequences of Operation, for further control details.

Smoke ControlThe Excel 10 W7750 Controller supports smoke-related control strategies that are initiated either via a network command (DestEmergCmd) or from a local (physically connected) smoke detector digital input. The details of the W7750 smoke-related control operation are described in Appendix B�Sequences of Operation.

Freeze Stat (W7750B2011 or W7750C)A freeze stat can be monitored by the W7750 and issue a freeze stat alarm indicating the CVAHU is in danger of freezing its coil. The details of the W7750 freeze stat related control operation are described in Appendix B�Sequences of Operation.

Modes of OperationThe possible modes of operation for the W7750 Controller are listed in Table 5.

Table 5. Modes Of Operation For The Excel 10 W7750 Controller .Mode Description Events causing a controller to switch to this mode

Effective Occupancy (User Address: StatusOcc)OCCUPIED Controller is in Occupied mode Any of the following: Network input (DestSchedOcc) containing a

time-of-day schedule or a Time Clock DI, Occupancy Sensor DI; or from Network input (DestManMode) for manual override to OCC mode. DestManMode has the highest priority, followed by the Time Clock DI, and then DestSchedOcc.

STANDBY Controller is in Standby mode Either: (A) Network input (DestSchedOcc) containing a time-of-day schedule or other LONWORKS Bus node is STANDBY, or (B) Network input (DestSchedOcc) is OCCUPIED and the Occupancy Sensor DI is UNOCCUPIED.

UNOCCUPIED Controller is in Unoccupied mode Network input (DestSchedOcc) containing a time-of-day schedule or the network input DestManOcc has a value of UNOCCUPIED.

BYPASS OCCUPIED

Controller is in Occupied mode through a Bypass command

This mode is derived from the schedule occupancy (DestSchedOcc) having a state of UNOCCUPIED and a manual request for occupancy from one of three sources. Two of these are signals originated external to the unit, and received by DestManOcc and DestBypass. The third source for an occupancy request is from an override button located on a wall module. These three sources are arbitrated in a scheme determined by the configuration parameter (Network Wins or Last-in Wins from OvrdPriority).

Override Modes (User Address: StatusOvrd)OCCUPIED Controller occupancy mode was

overridden to Occupied modeNetwork input (DestManOcc) containing a time-of-day schedule override signal of OCCUPIED from another LONWORKS Bus device.

STANDBY Controller occupancy mode was overridden to Standby mode

Network input (DestManOcc) containing a time-of-day schedule override signal of STANDBY from another LONWORKS Bus device.

UNOCCUPIED Controller occupancy mode was overridden to Unoccupied mode

Network input (DestManOcc) containing a time-of-day schedule override signal of UNOCCUPIED from another LONWORKS Bus device.

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 28

NOTE: During all modes all digital and analog physical inputs are periodically read, the diagnostic output network variables can be polled, the input network variables are received, and the output network variables are sent periodically.

APPLICATION STEPS

OverviewThe seven application steps shown in Table 6 are planning considerations for engineering an Excel 10 W7750 System. These steps are guidelines intended to aid understanding of the product I/O options, bus arrangement choices, configuration options and the Excel 10 W7750 Controller role in the overall LCBS/EXCEL 5000® OPEN� SYSTEM architecture.

Table 6. Application Steps.

BYPASS Controller occupancy mode was overridden to Bypass the current Unoccupied mode

DI (Bypass) was pressed, and the Bypass duration timer has not yet expired, or the network input DestManOcc has a value of BYPASS.

NOT ASSIGNED

No Bypass action No Override input received.

Operational Modes (User Address: StatusMode)START-UP AND WAIT

On power-up, provides a staggered start sequence to evenly apply the load to the electrical system.

This mode occurs on controller power-up, and after downloading to the controller from the configuration tool. Temperature control loops are disabled.

COOLING The Excel 10 is controlling the Cooling mode.

Space temperature has risen above the current cooling setpoint, or the network input (DestHvacMode) is COOL.

HEATING The Excel 10 is controlling the Heating mode.

Space temperature has fallen below the current heating setpoint, or the network input (DestHvacMode) is HEAT.

EMERGENCY HEAT

Compressors are disabled and only Auxiliary Heat stages are allowed to operate.

The network input (DestManHvacMode) is EMERG_HEAT.

OFF MODE The heat/cool control is turned off immediately. The node is not running its normal temperature control.

Network input (DestManMode) containing AHU operational mode information from C-Bus has value of MORNING WARM-UP.

DISABLED MODE

The heat/cool control and frost protection are turned off immediately. The node is not running its normal temperature control.

SMOKE EMERGENCY

The node has entered a smoke emergency. The fan and dampers are then set to the conditions configured by SmkCtlMode. The control remains in SMOKE_ EMERGENCY until power is cycled or the node receives DestEmergCmd set to EMERG_NORMAL.

Network input (DestEmergCmd) containing smoke control signal from another LONWORKS Bus device has value of SMOKE_EMERG.

FREEZE PROTECT

The temperature control is set to HEAT with the setpoint set to the frost limit setpoint 46.4°F (8°C).

The Window digital input detects an open window.

MANUAL POSITION

The physical outputs are being controlled manually. The temperature control loop is turned off.

Typically this is done by the user through LONSPEC� setting the point DestManMode to MANUAL mode.

FAN ONLY Control algorithm is disabled, except that the fan is turned on.

The space temperature sensor has failed, or the network input (DestHvacMode) is FAN ONLY.

DISABLED Control algorithm is shut off. Network input (DestManMode) containing AHU operational mode information from an operator or the network that has a value of DISABLED.

Table 5. Modes Of Operation For The Excel 10 W7750 Controller (Continued).Mode Description Events causing a controller to switch to this mode

Step No. Description1 Plan The System2 Determine Other Bus Devices Required3 Lay Out Communications and Power Wiring

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

29 74-2958�2

Step 1. Plan the SystemPlan the use of the W7750 Controllers according to the job requirements. Determine the location, functionality and sensor or actuator usage. Verify the sales estimate of the number of W7750 Controllers, T7770 and T7560 Wall Modules required for each model type. Also check the number and type of output actuators and other required accessories.

When planning the system layout, consider potential expansion possibilities to allow for future growth. Planning is very important to be prepared for adding HVAC systems and controllers in future projects.

T7560 Wall Modules can only be hard-wired, they have no LONWORKS Bus access. T7770 Wall Modules can be installed as either hard-wired I/O-only devices or additional wiring can be run to them (for the LONWORKS Bus network) to allow a LONSPEC� or Care user access to the LONWORKS Bus. The application engineer needs to determine how many wall modules, T7770s and T7560s are required. All T7770 Wall Modules, except the T7770A1006, can be connected via the LONWORKS Bus jack. Also the application engineer needs to know how many T7770s without LONWORKS Bus network connections are being installed on the job, and then clearly document which wall modules (if any) have network access. This information is required during installation to ensure that the proper number and type of wires are pulled to the wall modules, and the building operators are informed about where they can plug in to the LONWORKS Bus network with a portable operator terminal (see Fig. 18, 19 and 20). Refer to Step 4. Prepare Wiring Diagrams for details, about the about the wiring differences between the two types.

The FTT communication wiring, (LONWORKS Bus) between controllers is a free topology scheme that supports T-tap, star, loop, and mixed wiring architecture. Refer to the LONWORKS Bus Wiring Guidelines form, 74-2865 for complete description of network topology rules. See Application Step 3. Lay Out Communications and Power Wiring, for more information on bus wiring layout, and see Fig. 27 through 35 in Application Step 4. Prepare Wiring Diagrams, for wiring details.

Fig. 18. Connecting the portable operator terminal to the LONWORKS® Bus.

The application engineer must review the Direct Digital Control (DDC) job requirements. This includes the Sequences of Operation for the W7750 units, and for the system as a whole. Usually there are variables that must be passed between the W7750 Controllers and other zone controller(s), or central plant controller(s) that are required for optimum system-wide operation. Typical examples are the TOD Occ/Unocc signal, the outdoor air temperature, the demand limit control signal, and the smoke control mode signal.

It is important to understand these interrelationships early in the job engineering process to ensure implementation when configuring the controllers. (See Application Step 6. Configure Controllers, for information on the various Excel 10 parameters and on Excel 10 point mapping.)

Step 2. Determine Other Bus Devices RequiredA maximum of 62 nodes can communicate on a single LONWORKS Bus segment. Each W7750 (CVAHU) Controller constitutes one node. If more nodes are required, a Q7740A1008 Two-way Repeater, a Q7740B1006 Four-way Repeater, or a Q7751A,B Router is necessary. Using a router allows up to 125 nodes, divided between two LONWORKS Bus segments. The router accounts for two of these nodes (one node on each side of the router); an XL5000 Q7750A Excel 10 Zone Manager takes one node and two nodes are available for operator terminal nodes, leaving 120 nodes available for Excel 10/15 Controllers. All 120 controllers are able to talk to each other through the repeater/router.

Each LONWORKS Bus segment is set up with two unused nodes to allow for a LONSPEC�/LONSTATION� or CARE operator terminal to be connected to the LONWORKS Bus. Multiple CARE terminals (for XL5000 system), or one LonSpec and one LonStation (for LCBS systems) can be connected to the LONWORKS Bus at the same time. Table 7 summarizes the LONWORKS Bus segment configuration rules.

4 Prepare Wiring Diagrams5 Order Equipment6 Configure Controllers7 Troubleshooting

Step No. Description

M15120B

NOTEBOOK PC

LONWORKS BUS

PORT

EIA-232

SERIAL

PORT

LCBS/

Q7760A SLTA

CABLE

PART

NO. 205979

SHIELDED

INTERFACE

CABLE

EXCEL 10

W7750

CVAHU

CONTROLLER

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 30

Table 7. LONWORKS® Bus Configuration Rules and Device Node Numbers.

Refer to the LONWORKS Bus Wiring Guidelines form, 74-2865 for complete description of network topology rules and the maximum wire length limitations. If longer runs are required, a Q7740A 2-Way or Q7740B 4-Way Repeater can be added to extend the length of the LONWORKS Bus. A Q7751A,B Router can be added to partition the system into two segments and effectively double the length of the LONWORKS Bus. Only one router is allowed with each Excel 10 Zone Manager, and each network segment can have a maximum of one repeater.

NOTE: LCBS does not support a router unless it is config-ured as a repeater.

In addition, all LONWORKS Bus segments require the installation of a 209541B Termination Module for a singly terminated LONWORKS Bus or two 209541B Termination Modules for a doubly terminated LONWORKS Bus. For more details on LONWORKS Bus termination, refer to the LONWORKS Bus Wiring Guidelines form, 74-2865, or see Application Step 3. Lay Out Communications and Power Wiring, and the LONWORKS Bus Termination Module subsection in Application Step 4.

Step 3. Lay Out Communications and Power Wiring

LONWORKS® Bus LayoutThe communications bus, LONWORKS Bus, is a 78-kilobits per second (kbps) serial link that uses transformer isolation and differential Manchester encoding. Approved cable types for

LONWORKS Bus communications wiring is Level IV 22 AWG (0.34 mm2) plenum or non-plenum rated unshielded, twisted pair, solid conductor wire. For nonplenum areas, use Level IV 22 AWG (0.325 mm2), such as U.S. part AK3781 (one pair) or U.S. part AK3782 (two pair). In plenum areas, use plenum-rated Level IV, 22 AWG (0.325 mm2) such as U.S. part AK3791 (one pair) or U.S. part AK3792 (two pair). See Tables 9 and 11 for part numbers. Contact Echelon Corp. Technical Support for the recommended vendors of Echelon approved cables. The FTT communications bus, LONWORKS Bus, supports a polarity insensitive, free topology wiring scheme that supports T-tap, star, loop, and mixed bus wiring.

LONWORKS Bus networks can be configured in a variety of ways, so refer to the LONWORKS Bus Wiring Guidelines form, 74-2865 for complete description of network topology rules and Table 7. Fig. 19 and 20 depict two typical LONWORKS Bus network topologies; One has only one doubly terminated LONWORKS Bus segment that has 60 nodes or less, and one showing two singly terminated LONWORKS Bus segments that has 120 nodes or less (60 MAX per each segment). The bus configuration is set up using the Network Manager tool from within LONSPEC� or CARE.

NOTE: For wiring details see the LONWORKS Bus Termination Module subsection in Step 4. For wall module wiring, U.S. part AK3782 (non-plenum) or U.S. part AK3792 (plenum) can be used. For a LONWORKS Bus that is a doubly terminated daisy-chain, these cables contain two twisted pairs (one for the run down to the wall module, and one for the run back up to the controller) for ease of installation.

One LONWORKS Bus Segment Example Maximum Number of Nodes Equals 62One Q7750A Excel 10 Zone Manager 1 node

Port for operator terminal access (LONSPEC� or CARE) 1 nodeMaximum number of Excel 10/15s 60 nodes (Excel 15s supported by LCBS only)

Total 62 nodes

Two LONWORKS Bus Segments Example Maximum Number of Nodes Equals 125One Q7750A Excel 10 Zone Manager 1 node (supported on XL5000 only)

One Q7751A,B Router 2 nodes (1 in each Bus Segment); Repeaters do not have nodesPorts for operator terminal access: two CARE terminals,

or one LONSPEC� and one LONSTATION� terminal2 nodes (1 in each Bus Segment)

Maximum number of Excel 10/15s in segment number one 60 nodes (Excel 15s supported by LCBS only)Maximum number of Excel 10/15s in segment number two 60 nodes (Excel 15s supported by LCBS only)

Total 125 nodes

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

31 74-2958�2

Fig. 19. Wiring layout for one doubly terminated daisy-chain LONWORKS® Bus segment.

NOTE: See the LONWORKS Bus Termination Module section for wiring details.

IMPORTANTNotes on communications wiring:� All field wiring must conform to local codes and

ordinances or as specified on installation wiring diagrams.

� Approved cable types for LONWORKS Bus communi-cations wiring is Level IV 22 AWG (0.34 mm2) plenum or non-plenum rated unshielded, twisted pair, solid conductor wire. For nonplenum areas, use Level IV 22 AWG (0.34 mm2), such as U.S. part AK3781 (one pair) or U.S. part AK3782 (two pair). In plenum areas, use plenum-rated Level IV, 22 AWG (0.34 mm2) such as U.S. part AK3791 (one pair) or U.S. part AK3792 (two pair). See Tables 9 and 11 for part numbers. Contact Echelon Corp. Technical Support for the recommended vendors of Echelon approved cables.

� Unswitched 24 Vac power wiring can be run in the same conduit as the LONWORKS Bus cable.

� Do not use different wire types or gauges on the same LONWORKS Bus segment. The step change in line impedance characteristics causes unpredictable reflections on the bus. When using different types is unavoidable, use a Q7751A,B Router at the junction.

� In noisy (high EMI) environments, avoid wire runs parallel to noisy power cables, or lines containing lighting dimmer switches, and keep at least 3 in. (76 mm) of separation between noisy lines and the LONWORKS Bus cable.

� Make sure that neither of the LONWORKS Bus wires is grounded.

M22743

EXCEL 10

VAV

EXCEL 10

VAV

EXCEL 10

CVAHU

EXCEL 10

CVAHU

EXCEL 10

CVAHU

EXCEL 10

CVAHU

EXCEL 10

VAV

EXCEL 10

VAV

EXCEL 10

VAV

LONWORKS BUS

LONWORKS BUS

LO

NW

OR

KS

BU

S

UP TO 60

TOTAL NODES

T7770T7770

T7770

T7770

JACK FOR

OPERATOR

TERMINAL

209541B

TERMINATION MODULES

(AT ENDS OF

LONWORKS BUS

DAISY-CHAIN)

T7770s

WITH

NO

LONWORKS BUS

ACCESS

LONWORKS BUS

I/O CONNECTIONS

EXCEL 10

CVAHU

EXCEL 10

CVAHU

T7770 OR T7560A,B

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 32

Fig. 20. Wiring layout for two singly terminated LONWORKS® Bus segments.

Power WiringA power budget must be calculated for each Excel 10 W7750 Controller to determine the required transformer size for proper operation. A power budget is simply the summing of the maximum power draw ratings (in VA) of all the devices to be controlled by an Excel 10 W7750 Controller. This includes the controller itself, the equipment actuators (ML6161, or other motors) and various contactors and transducers, as appropriate, for the Excel 10 configuration.

Power Budget Calculation ExampleThe following is an example power budget calculation for a typical Excel 10 W7750B Controller.

Assume a W7750 unit with a fan, two stages of D/X cooling, modulating steam valve for heating, and modulating economizer dampers. The power requirements are:

NOTE: For this example, assume the cooling stage outputs are wired into a compressor control circuit and, therefore, have no impact on the power budget.)

M6410A Steam 0.7 TRADELINE®

Heating Coil Valve Catalog, 0.32A at 24 Vac

TOTAL: 35.9 VA

The Excel 10 System example requires 35.9 VA of peak power; therefore, a 40 VA AT72D Transformer is able to provide ample power for this controller and its accessories. Alternatively, a 75 VA AT88A Transformer could be used to power two Excel 10 Systems of this type, or a 100 VA AT92A Transformer could be used to power two of these Excel 10 Systems and meet NEC Class 2 restrictions (no greater than 100 VA). See Fig. 22 and 23 for illustrations of power wiring details. See Table 8 for VA ratings of various devices.

Table 8. VA Ratings For Transformer Sizing.

For contactors and similar devices, the in-rush power ratings should be used as the worst case values when performing power budget calculations. Also, the application engineer must consider the possible combinations of simultaneously energized outputs and calculate the VA ratings accordingly. The worst case, that uses the largest possible VA load, should be determined when sizing the transformer.

Line LossExcel 10 Controllers must receive a minimum supply voltage of 20 Vac. If long power or output wire runs are required, a voltage drop due to Ohms Law (I x R) line loss must be considered. This line loss can result in a significant increase in total power required and thereby affect transformer sizing. The following example is an I x R line-loss calculation for a 200 ft. (61m) run from the transformer to a W7750 Controller drawing 37 VA using two 18 AWG (1.0 mm2) wires.

The formula is:Loss = [length of round-trip wire run (ft.)] X [resistance in

wire (ohms per ft.)] X [current in wire (amperes)]From specification data:

18 AWG twisted pair wire has 6.52 ohms per 1000 feet.Loss = [(400 ft.) X (6.52/1000 ohms per ft.)] X

[(37 VA)/(24V)] = 4.02 voltsThis means that four volts are going to be lost between the transformer and the controller; therefore, to assure the controller receives at least 20 volts, the transformer must output more than 24 volts. Because all transformer output voltage levels depend on the size of the connected load, a larger transformer outputs a higher voltage than a smaller one for a given load. Fig. 21 shows this voltage load dependence.

Device VA Information Obtained fromExcel 10 W7750B,C Controller

12.0 W7750 Specification Data

ML6161 Damper Actuator

2.2 TRADELINE® Catalog

R8242A Contactor for fan

21.0 TRADELINE® Catalog in-rush rating

D/X Stages 0.0

EXCEL 10

VAV

EXCEL 10

VAV

EXCEL 10

VAV

LONWORKS BUS

SEGMENT NUMBER 2

LONWORKS BUS

SEGMENT NUMBER 1

LONWORKS BUS

SEGMENT NUMBER 2

T7770

LONWORKS

BUS

ACCESS

FTT

LONWORKS

BUS

REPEATER

EXCEL 10

VAV

209541B

TERMINATION

MODULE

209541B

TERMINATION

MODULE

M22744

EXCEL 10

CVAHU

EXCEL 10

CVAHU

EXCEL 10

CVAHU

EXCEL 10

CVAHU

EXCEL 10

CVAHU

T7560A,B

Device Description VAW7750A Excel 10 W7750 Controller 6.0W7750B,C Excel 10 W7750 Controllers 12.0ML6161A/B Damper Actuator, 35 lb-in. 2.2R8242A Contactor 21.0M6410A Valve Actuator 0.7ML6464 Damper Actuator, 66 lb-in. 3.0ML6474 Damper Actuator, 132 lb-in. 3.0ML6185 Damper Actuator SR 50 lb-in. 12.0ML7984B PWM Valve Actuator 6.0

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

33 74-2958�2

In the preceding I x R loss example, even though the controller load is only 37 VA, a standard 40 VA transformer is not sufficient due to the line loss. From Fig. 21, a 40 VA transformer is just under 100 percent loaded (for the 37 VA controller) and, therefore, has a secondary voltage of 22.9 volts. (Use the lower edge of the shaded zone in Fig. 21 that represents the worst case conditions.) When the I x R loss of four volts is subtracted, only 18.9 volts reaches the controller, which is not enough voltage for proper operation.

In this situation, the engineer basically has three alternatives:1. Use a larger transformer; for example, if an 80 VA

model is used, see Fig. 21, an output of 24.4 volts minus the four volt line loss supplies 20.4V to the controller. Although acceptable, the four-volt line-loss in this example is higher than recommended. See the following IMPORTANT.

2. Use heavier gauge wire for the power run. 14 AWG (2.0 mm2) wire has a resistance of 2.57 ohms per 1000 ft. which, using the preceding formula, gives a line-loss of only 1.58 volts (compared with 4.02 volts). This would allow a 40 VA transformer to be used. 14 AWG (2.0 mm2) wire is the recommended wire size for 24 Vac wiring.

3. Locate the transformer closer to the controller, thereby reducing the length of the wire run, and the line loss. The issue of line-loss is also important in the case of the output wiring connected to the Triac digital outputs. The same formula and method are used. The rule to remember is to keep all power and output wire runs as short as practical. When necessary, use heavier gauge wire, a bigger transformer, or install the transformer closer to the controller.

IMPORTANTNo installation should be designed where the line loss is greater than two volts to allow for nominal operation if the primary voltage drops to 102 Vac (120 Vac minus 15 percent).

To meet the National Electrical Manufacturers Association (NEMA) standards, a transformer must stay within the NEMA limits. The chart in Fig. 21 shows the required limits at various loads.

With 100 percent load, the transformer secondary must supply between 23 and 25 volts to meet the NEMA standard. When a purchased transformer meets the NEMA standard DC20-1986, the transformer voltage-regulating ability can be considered reliable. Compliance with the NEMA standard is voluntary.

The following Honeywell transformers meet this NEMA standard:

Fig. 21. NEMA class 2 transformer voltage output limits.

Attach earth ground to W7750 Controller terminal 1. See Fig. 22, 23, 24, and 27 through 35.

Fig. 22. Power wiring details for one Excel 10 per transformer.

See Fig. 23. for wiring more than one Excel 10 per transformer.

Transformer Type VA RatingAT20A 20

AT40A 40AT72D 40AT87A 50AK3310 Assembly 100

Transformer Type VA Rating

27

26

25

24

23

22

21

20

19

18

17

16

15

14

0 50 100 150

% OF LOAD

SE

CO

ND

AR

Y V

OL

TA

GE

200

M993

M10089B

CONNECT POWER TO TERMINALS 24 AND 25

TRIAC LINESTO ACTUATORSAND CONTACTORS

TRANSFORMER

W7750B,C

EARTHGROUND

20222425

1

OUTPUTDEVICEPOWER

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 34

Fig. 23. Power wiring details for two or more Excel 10s per transformer.

IMPORTANTIf the W7750 Controller is used on Heating and Cooling Equipment (UL 1995 U.S. only) devices and the transformer primary power is more than 150 volts, connect the transformer secondary to earth ground, see Fig. 24.

Fig. 24. Transformer power wiring details for one Excel 10 used in UL 1995 equipment (U.S. only).

IMPORTANTNotes on power wiring:

� All field wiring must conform to local codes and ordi-nances or as specified on installation wiring dia-grams.

� To maintain NEC Class 2 and UL ratings, the installa-tion must use transformers of 100 VA or less capac-ity.

� For multiple controllers operating from a single trans-former, the same side of the transformer secondary must be connected to the same input terminal in each controller (21 on the W7750A and 24 on the W7750B,C) and the ground terminals must be con-nected to a verified earth ground for each controller in the group. See Fig. 23. (Controller configurations are not necessarily limited to three devices per trans-former.)

� For the W7750B,C Controller (which has Triac out-puts), all output devices must be powered from the same transformer as the one powering the Excel 10 W7750 Controller.

� Use the heaviest gauge wire available, up to 14 AWG (2.0 mm2) with a minimum of 18 AWG (1.0 mm2) for all power and earth ground connections.

� To minimize EMI noise, do not run Triac output wires in the same conduit as the input wires or the LON-WORKS Bus communications wiring.

� Unswitched 24 Vac power wiring can be run in the same conduit as the LONWORKS Bus cable.

� Make earth ground connections with the shortest possible wire run using 14 AWG (2.0 mm2) wire. A good earth ground is essential for W7750 operation. Ideally, connect the earth ground to the ground bus at a motor control center or circuit breaker panel. However, if the nearest ideal earth ground is inac-cessible, consider an alternate source for earth ground. Metal water pipe is generally a good ground, but do not use sprinkler pipe if prohibited by local codes. Attention must be given when duct work, con-duit, or rebar are to be considered as ground sources. It is the responsibility of the installer to assure that these structures are tied back to a known earth ground.

M10090A

24 VAC120/240 VAC

TRANSFORMER

W7750B,C

EARTHGROUND

2425

1

W7750B,C

EARTHGROUND

2425

1

W7750B,C

EARTHGROUND

2425

1

M10088A

24 VAC

LINE VOLTAGEGREATERTHAN 150 VAC

TRANSFORMER

W7750

EARTHGROUND

EARTHGROUND

IF THE W7750 CONTROLLER IS USED IN UL 1995 EQUIPMENT AND THE PRIMARY POWER IS MORE THAN 150 VOLTS, GROUND 24 VAC COM SIDE OF TRANSFORMER SECONDARY.

1

1

1

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

35 74-2958�2

Step 4. Prepare Wiring Diagrams

General ConsiderationsThe purpose of this step is to assist the application engineer in developing job drawings to meet job specifications. Wiring details are included for the W7750A,B,C Controllers and the T7770 and T7560A,B Wall Modules. The drawings detail I/O, power, and LONWORKS Bus communication wiring connections.

NOTE: For field wiring, when two or more wires, other than 14 AWG (2.0 mm2) are to be attached to the same connector block terminal, be sure to twist them together. Deviation from this rule can result in improper electrical contact. See Fig. 25.

The connector block terminals on the W7750 Controllers and on the T7770 Wall Modules accept 14 through 22 AWG (2.0 to 0.34 mm2) wire. The connector block terminals on the T7560A,B Wall Modules accept 18 through 22 AWG (1.0 to 0.34 mm2) wire. Table 9 lists wiring types, sizes, and length restrictions for Excel 10 products.

Table 9. Field Wiring Reference Table (Honeywell listed as AK#### or equivalent).

W7750 ControllersFig. 27 through 35 illustrate W7750A,B,C Controller wiring for various configurations. Connections to the wall module terminals (2 through 6) and the communications terminals (14

and 15) are made at terminal blocks. Connection for access to the LONWORKS Bus is provided by plugging the connector into the communications jack.

Wire Function

Recommended Minimum Wire

Size AWG (mm2) Construction

Specification or

Requirement Vendor Wire Type Maximum Length ft. (m)LONWORKS Bus (Plenum)

22 AWG (0.34 mm2)

Twisted pair solid conductor, nonshielded or Echelon approved cable.

Level IV 140°F (60°C) rating

HoneywellAK3791 (one twisted pair) AK3792 (two twisted pairs)

Refer to LONWORKS Bus Wiring Guidelines for maximum length

LONWORKS Bus (Non-Plenum)

22 AWG (0.34 mm2)

Twisted pair solid/stranded conductor, nonshielded or Echelon approved cable.

Level IV 140°F (60°C) rating

HoneywellAK3781 (one twisted pair) AK3782 (two twisted pairs) AK3798 (one twisted pair - stranded)

Refer to LONWORKS Bus Wiring Guidelines for maximum length

Input Wiring Sensors Contacts

18 to 22 AWG (1.0 to 0.34 mm2)

Multiconductor (usually five-wire cable bundle). For runs >200 ft. (61m) in noisy EMI areas, use shielded cable.

140°F (60°C) rating

Standard thermostat wire 1000 ft. (305m) for 18 AWG 200 ft. (61m) for 22 AWG

Output Wiring Actuators Relays

14 AWG (2.0 mm2) 18 AWG (1.0 mm2) acceptable for short runs)

Any pair nonshielded (use heavier wire for longer runs).

NEC Class 2 140°F (60°C) rating

HoneywellAK3702 (18 AWG) AK3712 (16 AWG) AK3754 (14 AWG)

Limited by line-loss effects on power consumption. (See Line Loss subsection.)

Power Wiring

14 AWG (2.0 mm2) Any pair nonshielded (use heavier wire for longer runs).

NEC Class 2 140°F (60°C) rating

HoneywellAK3754 (14 AWG) twisted pair AK3909 (14 AWG) single conductor

Limited by line-loss effects on power consumption. (See Line Loss subsection.)

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 36

Fig. 25. Attaching two or more wires at terminal blocks.

The W7750B provides a jumper to select High-Side or Low-Side switching of the digital outputs. Fig. 26 shows the W7750B High-Side/Low-Side selectable switching. (See wiring diagrams, Fig. 30 through 34.)

Fig. 26. W7750B High-Side/Low-Side selectable switching and jumper location (on W7750B2011 and W7750C).

NOTE: If an Excel 10 W7750A,B,C Controller is not connected to a good earth ground, the controller internal transient protection circuitry is compromised and the function of protecting the controller from noise and power line spikes cannot be fulfilled. This can result in a damaged circuit board and require replacing the controller.

See Table 10 for a description of the W7750A terminals.

1/2(13)

STRIP 1/2 IN. (13 MM) FROM WIRES TO BE ATTACHED AT ONE TERMINAL.

1.

2. TWIST WIRES TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS).

3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION. M17207

U3

Q4

J2

JUMPER

TERMINAL 24

J2 IS LOCATED NEAR TERMINAL 24 (COVER REMOVED).

W7750B IS FACTORY-DELIVERED WITH JUMPER ON HIGH-SIDE (PINS CLOSEST TO TERMINAL BLOCK). LOW-SIDE PINS ARE TWO PINS CLOSEST TO Q4.

1

1

2

2

M16418A

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

37 74-2958�2

Table 10. W7750A Version I/O Description.

IMPORTANTIf the W7750A controller is configured by LONSPEC� or Care, the outputs may be assigned in different order than the factory defaults. Use the Custom Wiring function to re-assign the outputs to the desired terminals.

The W7750B,C Versions are preconfigured with the same factory default setup as the W7750A Model; however, some terminals for wiring connections differ on the W7750B,C Models. See Fig. 30 for the terminal names on the W7750B Model and Fig. 35 for the terminal names on the W7750C Model. The factory default configuration of the digital output points on the W7750B,C Models follow (terminal names are from the W7750A):

Factory Default Digital Outputs

The Wall Module terminals are identical for the W7750A,B,C Models.

The W7750B,C Models offers two voltage/current sensor input terminals. When current-type sensors (4 to 20 mA) are configured, the W7750B,C automatically switches a 249 ohm resistor into the sensing circuit; so no external resistor is required. The W7750A Model does not support voltage or current inputs.

NOTE: If using factory defaults, Di1 is local Time clock input, and the DI-2 input is configured for ScheduleMaster (nvoIO.SchedMaster). For a stand-alone unit, either connect an external time clock to terminals 9 and 10 or put a jumper on terminals 9 and 10 (using a jumper puts the controller in continuous occupied mode).

Terminal Terminal Number DescriptionDO6�(W1) 31 Heat 1 (or Reversing Valve for a Heat Pump)DO5�(W2) 30 Heat 2 (or Aux. Heat for a Heat Pump)DO4�(Y1) 29 Cool 1 (or Compressor 1 for a Heat Pump)DO3�(Y2) 28 Cool 2 (or Compressor 2 for a Heat Pump)DO2�(G) 27 FanDO1�NET 26 Network Digital OutputDO1�NET 25 Network Digital Output (connect to terminal number 22 +24Vac)Rc 24 Control power for relay contacts DO2 (G), DO3 (Y1) and DO4 (Y2) Rh 23 Control power for relay contacts DO5 (W1) and DO6 (W2)+24Vac (H) 22 Power for the controllerCOM (N) 21 Return for power to controllerE-Bus 14 and 15 Echelon communications (LONWORKS Bus) screw terminalsDI - 2 12 Digital Input 2DGND 11 Digital GroundDGND 10 Digital GroundDI - 1 9 Digital Input 1AGND 8 Analog groundAI - 1 OHM 7 Analog Input 1 (used for Discharge Air Temperature Sensor)SET PT 6 Space temperature setpoint potentiometerGROUND 5 Wall ModuleSENSOR 4 Space temperature sensorBYPASS 3 Space override buttonLED 2 Space LED for indication of manual occupancy statusEARTH GND 1 Earth Ground

FREE 1 (OUT 1) DO1 NETWORK DO(OUT 2) DO2 SUPPLY FAN START/STOP(OUT 3) DO3 COOL_STAGE_2(OUT 4) DO4 COOL_STAGE_1(OUT 5) DO5 HEAT_STAGE_2(OUT 6) DO6 HEAT_STAGE_1DO7 UNUSEDDO8 UNUSED

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 38

Fig. 27. Typical W7750A Controller AHU application wiring. (For more information on note 2, refer to Fig. 25.)

Fig. 28. Typical W7750A Controller with separate transformer application wiring.

(For more information on note 2, refer to Fig. 25.)

1 2 3 4 5 6 7 8

1

3

2

2

1

2

3

EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.

TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTEDTOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.

LOAD POWER WIRE CAN BE CONNECTED TO TERMINAL 22.

LO

NW

OR

KS-B

US

EA

RT

HG

RO

UN

D

JACK FOR LONWORKS-BUS NETWORKACCESS

7 6 5 4 3 2 1

T7770C

WALL

MODULE

SE

T P

T

GN

D

SE

NS

OR

BY

PA

SS

LE

D

E-B

US

E-B

US

9 10 11 12 14 J315

31 30 29 28 27 26 25 24 23 22 21 20

WALL MODULE

SE

T P

T

AI

GR

OU

ND

AI

GR

OU

ND

DI

GR

OU

ND

DI

GR

OU

ND

SE

NS

OR

BY

PA

SS

LE

D

LO

N

JA

CK

LO

NW

OR

KS

BU

S

NO

T U

SE

D

9 8

19 18 17 16

AI-

1 O

HM

DI-

1

DI-

2

13

TIME CLOCK

M10085C

DISCHARGE AIR TEMP

24

VA

C

24

VA

C C

OM

Rc

Rh

W1

W2

Y1

Y2 G NOT USED

24 VAC

+

-

LOAD AND CONTROLLERPOWERFAN

COMP2COMP 1HEAT 2HEAT 1

W7750A

CONSTANT

VOLUME AHU

CONTROLLER

NE

TW

OR

KD

O

1 2 3 4 5 6 7 8

W7750A

CONSTANT

VOLUME AHU

CONTROLLER

1

2

2

1

2

EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.

TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTEDTOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.

LO

NW

OR

KS-B

US

EA

RT

HG

RO

UN

D

JACK FOR LONWORKS-BUS NETWORKACCESS

7 69 8 5 4 3 2 1

T7770C

WALL

MODULE

SE

T P

T

GN

D

SE

NS

OR

BY

PA

SS

LE

D

E-B

US

E-B

US

9 10 11 12 14 J315

31 30 29 28 27 26 25 24 23 22 21 20

WALL MODULE

SE

T P

T

SE

NS

OR

BY

PA

SS

LE

D

NO

T U

SE

D

19 18 17 16

AI-

1 O

HM

DI-

1

DI-

2

13

TIME CLOCK

M10084C

DISCHARGE AIR TEMP

24

VA

C

24

VA

C C

OM

Rc

Rh

W1

W2

Y1

Y2 G NOT USED

24 VAC

24 VAC LINE AC

+

-

CONTROLLER POWER

LOAD POWERFAN

COMP2COMP 1HEAT 2HEAT 1

H

C

NE

TW

OR

KD

O

AI

GR

OU

ND

AI

GR

OU

ND

DI

GR

OU

ND

DI

GR

OU

ND

LO

N

JA

CK

LO

NW

OR

KS

BU

S

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

39 74-2958�2

Fig. 29. W7750A Controller floating economizer damper wiring. (For more information on note 2, refer to Fig. 25.)

NOTE: Digital outputs are configurable. The terminal locations for each function are user-selectable. The Network DO is configured to be economizer float close in this figure and W2 is configured to be economizer float open. Physical output terminal features are done in LONSPEC�/Care by the custom wiring function.

1 2 3 4 5 6 7 8

W7750A

CONSTANT

VOLUME AHU

CONTROLLER

1

2

2

1

2

3

EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.

TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTEDTOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.

LOAD POWER WIRE CAN BE CONNECTED TO TERMINAL 22.

LO

NW

OR

KS-B

US

EA

RT

HG

RO

UN

D

JACK FOR LONWORKS-BUS NETWORKACCESS

7 69 8 5 4 3 2 1

T7770C

WALL

MODULE

SE

T P

T

GN

D

SE

NS

OR

BY

PA

SS

LE

D

E-B

US

E-B

US

9 10 11 12 14 J315

31 30 29 28 27 26 25 24 23 22 21 20

WALL MODULE

SE

T P

T

SE

NS

OR

BY

PA

SS

LE

D

NO

T U

SE

D

19 18 17 16

AI-

1 O

HM

DI-

1

DI-

2

13

TIME CLOCK

M10083C

DISCHARGE AIR TEMP

24

VA

C

24

VA

C C

OM

Rc

Rh

NE

TW

OR

KD

O

W1

W2

Y1

Y2 G

24 VAC

+

-

3

LOAD AND CONTROLLER POWER

NOT USED

ML6161 FLOATINGACTUATOR

CW COM CCW

HEAT 1

AI

GR

OU

ND

AI

GR

OU

ND

DI

GR

OU

ND

DI

GR

OU

ND

LO

N

JA

CK

LO

NW

OR

KS

BU

S

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 40

Fig. 30. Typical W7750B Controller with staged heating and cooling wiring. (For more information on note 2, refer

to Fig. 25.)Fig. 31. W7750B Controller with floating heating, cooling

and economizer wiring. (For more information on note 2, refer to Fig. 25.)

1 2 3 4 5 6 7 8

24

VA

C

W7750B CONSTANT

VOLUME AHU

CONTROLLER

1

2

2

1

2

3

4

3

4

EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.

TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTEDTOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.

WIRING DIAGRAM SHOWS JUMPER (FOR J2) IN FACTORY DEFAULT HIGH-SIDE POSITION.

ISOLATING RELAYS MUST BE USED WHEN CONNECTING TO STAGEDHEAT/COOL EQUIPMENT.

LO

NW

OR

KS-B

US

EA

RT

HG

RO

UN

D

JACK FOR LONWORKS-BUS NETWORKACCESS

7 69 8 5 4 3 2 1

T7770C

WALL

MODULE

SE

T P

T

GN

D

SE

NS

OR

BY

PA

SS

LE

D

E-B

US

E-B

US

9 10 11 12 14 J315

31 30 29 28 27 26 25 24 23 22 21 20

24

VA

C C

OM

WALL MODULE

SE

T P

T

SE

NS

OR

BY

PA

SS

LE

D

20

VD

C O

UT

19 18 17 16

AI-

1 O

HM

AI-

2 O

HM

AI-

4 V

/mA

OU

T 7

OU

T 6

OU

T 5

OU

T 4

OU

T 8

OU

T 1

OU

T 3

OU

T 2

AI-

3 V

/mA

13

DI-

2

DI-

4

DI-

1

DI-

3

DI

GR

OU

ND

M10082D

DI

GR

OU

ND

TRIAC EQUIVALENT CIRCUIT

24 VAC

+

-

HEATSTAGE 1

HEATSTAGE 2COOL

STAGE 1FANCOOLSTAGE 2

COOLSTAGE 3

COOLSTAGE 4

AI

GR

OU

ND

AI

GR

OU

ND

AI

GR

OU

ND

LO

N

JA

CK

LO

NW

OR

KS

BU

S

1 2 3 4 5 6 7 8

24

VA

C

W7750B CONSTANT

VOLUME AHU

CONTROLLER

1

2

2

1

2

3

EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.

TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTEDTOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.

WIRING DIAGRAM SHOWS JUMPER (FOR J2) IN FACTORY DEFAULTHIGH-SIDE POSITION.

LO

NW

OR

KS-B

US

EA

RT

HG

RO

UN

D

JACK FOR LONWORKS-BUS NETWORKACCESS

7 69 8 5 4 3 2 1

T7770C

WALL

MODULE

SE

T P

T

GN

D

SE

NS

OR

BY

PA

SS

LE

D

E-B

US

E-B

US

9 10 11 12 14 J315

31 30 29 28 27 26 25 24 23 22 21 20

24

VA

C C

OM

WALL MODULE

SE

T P

T

SE

NS

OR

BY

PA

SS

LE

D

20

VD

C O

UT

19 18 17 16

AI-

1 O

HM

AI-

2 O

HM

AI-

4 V

/mA

OU

T 7

OU

T 6

OU

T 5

OU

T 4

OU

T 8

OU

T 1

OU

T 3

OU

T 2

AI-

3 V

/mA

13

DI-

2

DI-

4

DI-

1

DI-

3

M10081C

TRIAC EQUIVALENT CIRCUIT

DISCHARGE AIR TEMP

24 VAC

+

-

SERIES 60 VALVE ACTUATOR

SERIES 60ACTUATOR

CW COM CCW

COM

STEMUP

STEMDOWN

SERIES 60 VALVE ACTUATOR

COM

STEMUP

STEMDOWN

ECONOMIZERDAMPER

TWO - OR THREE-WAYHOT WATER/STEAM VALVE

TWO - OR THREE-WAYCHILLER WATER VALVE

3

DI

GR

OU

ND

DI

GR

OU

ND

AI

GR

OU

ND

AI

GR

OU

ND

AI

GR

OU

ND

LO

N

JA

CK

LO

NW

OR

KS

BU

S

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

41 74-2958�2

Fig. 32. W7750B,C Controller PWM damper actuator wiring. (For more information on note 2, refer to Fig. 25.)

Fig. 33. W7750B,C wiring with 4 to 20 mA enthalpy sensors and digital inputs.

(For more information on note 2, refer to Fig. 25.)

1 2 3 4 5 6 7 8

24

VA

C

W7750B CONSTANT

VOLUME AHU

CONTROLLER

1

2

2

1

2

3

4

EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.

TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTEDTOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.

WIRING DIAGRAM SHOWS JUMPER (FOR J2) IN FACTORY DEFAULT HIGH-SIDE POSITION.

FOR WIRING DETAILS FOR PWM DEVICES, REFER TO DOCUMENTATIONINCLUDED WITH PWM DEVICES.

EA

RT

HG

RO

UN

D

7 69 8 5 4 3 2 1

T7770C

WALL

MODULE

SE

T P

T

GN

D

SE

NS

OR

BY

PA

SS

LE

D

E-B

US

E-B

US

9 10 11 12 14 J315

31 30 29 28 27 26 25 24 23 22 21 20

24

VA

C C

OM

WALL MODULE

SE

T P

T

GR

OU

ND

SE

NS

OR

BY

PA

SS

LE

D

20

VD

C O

UT

19 18 17 16

AI-

1 O

HM

GR

OU

ND

GR

OU

ND

AI-

2 O

HM

AI-

4 V

/mA

OU

T 7

OU

T 6

OU

T 5

OU

T 4

OU

T 8

OU

T 1

OU

T 3

OU

T 2

AI-

3 V

/mA

13

DI-

2

DI-

4

DI-

1

DI-

3

DI

GR

OU

ND

M10080C

DI

GR

OU

ND

TRIAC EQUIVALENT CIRCUIT

DISCHARGE AIR TEMP

24 VAC

+

-

4PWM ACTUATOR

24V COM 24V

ECONOMIZERDAMPER

POWER SIGNAL

SIG

LO

NW

OR

KS

BU

S

LO

N

JA

CK

LO

NW

OR

KS-B

US

JACK FOR LONWORKS-BUS NETWORKACCESS

3

1 2 3 4 5 6 7 8

24

VA

C

24 VAC

W7750B CONSTANT

VOLUME AHU

CONTROLLER

1

2

2

1

2

3

EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.

TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTEDTOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.

WIRING DIAGRAM SHOWS JUMPER (FOR J2) IN FACTORY DEFAULT HIGH-SIDE POSITION.

LO

NW

OR

KS-B

US

EA

RT

HG

RO

UN

D

JACK FORLONWORKS-BUS NETWORKACCESS

7 69 8 5 4 3 2 1

T7770C

WALL

MODULE

SE

T P

T

GN

D

SE

NS

OR

BY

PA

SS

LE

D

E-B

US

E-B

US

9 10 11 12 14 J315

31 30 29 28 27 26 25 24 23 22 21 20

24

VA

C C

OM

WALL MODULE

SE

T P

T

SE

NS

OR

BY

PA

SS

LE

D

20

VD

C O

UT

19 18 17 16

AI-

1 O

HM

AI-

2 O

HM

AI-

4 V

/mA

+

-

OU

T 7

OU

T 6

OU

T 5

OU

T 4

OU

T 8

OU

T 1

OU

T 3

OU

T 2

AI-

3 V

/mA

13

DI-

2

DI-

4

DI-

1

DI-

3

OCCUPANCY SENSOR(CONTACTS CLOSED EQUALS OCCUPIED)

WINDOWS CONTACTS(CONTACTS CLOSEDEQUALS WINDOWCLOSED)

M10079C

TRIAC EQUIVALENT CIRCUIT

DISCHARGE AIR TEMP

OUTDOORENTHALPY RETURN

ENTHALPY

3

DI

GR

OU

ND

DI

GR

OU

ND

AI

GR

OU

ND

AI

GR

OU

ND

AI

GR

OU

ND

LO

N

JA

CK

LO

NW

OR

KS

BU

S

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 42

Fig. 34. W7750B,C wiring with C7600C 4 to 20 mA solid state humidity sensor.

(For more information on note 2, refer to Fig. 25.)

Fig. 35. W7750C Controller with 4 to 20 mA heating, cooling and economizer wiring. AOs must use terminals

16, 17 or 18. The AOs can be set to be reverse acting. (For more information on note 2, refer to Fig. 25.)

1 2 3 4 5 6 7 8

24

VA

C

24 VAC

W7750B CONSTANT

VOLUME AHU

CONTROLLER

1

2

2

1

2

3

EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.

TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTEDTOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.

WIRING DIAGRAM SHOWS JUMPER (FOR J2) IN FACTORY DEFAULT HIGH-SIDE POSITION.

EA

RT

HG

RO

UN

D

7 69 8 5 4 3 2 1

T7770C

WALL

MODULE

SE

T P

T

GN

D

SE

NS

OR

BY

PA

SS

LE

D

E-B

US

E-B

US

9 10 11 12 14 J315

31 30 29 28 27 26 25 24 23 22 21 20

24

VA

C C

OM

WALL MODULE

SE

T P

T

GR

OU

ND

SE

NS

OR

BY

PA

SS

LE

D

20

VD

C O

UT

19 18 17 16

AI-

1 O

HM

GR

OU

ND

GR

OU

ND

AI-

2 O

HM

AI-

4 V

/mA

+

-

OU

T 7

OU

T 6

OU

T 5

OU

T 4

OU

T 8

OU

T 1

OU

T 3

OU

T 2

AI-

3 V

/mA

13

DI-

2

DI-

4

DI-

1

DI-

3

DI

GR

OU

ND

OCCUPANCY SENSOR(CONTACTS CLOSED EQUALS OCCUPIED)

WINDOWS CONTACTS(CONTACTS CLOSEDEQUALS WINDOWCLOSED)

M11619B

DI

GR

OU

ND

TRIAC EQUIVALENT CIRCUIT

+–

C7600C

HUMIDITY(4 TO 20 MA)

LO

NW

OR

KS

BU

S

LO

N

JA

CK

LO

NW

OR

KS-B

US

JACK FOR LONWORKS-BUS NETWORKACCESS

3

1 2 3 4 5 6 7 8

24

VA

C

W7750C

CONSTANT VOLUME

AHU CONTROLLER

1

2

2

3

1

2

EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.

USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2)

WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.

TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED

TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.

IF AN ANALOG OUTPUT DEVICE HAS A SIGNAL COM (-) TERMINAL,

CONNECT IT TO THE 24 VAC COM TERMINAL NUMBER 24.

WIRING DIAGRAM SHOWS JUMPER (FOR J2) IN FACTORY DEFAULT

HIGH-SIDE POSITION.

LO

NW

OR

KS-B

US

EA

RT

H

GR

OU

ND

JACK FOR

LONWORKS-BUS

NETWORK

ACCESS

7 69 8 5 4 3 2 1

T7770C

WALL

MODULE

SE

T P

T

GN

D

SE

NS

OR

BY

PA

SS

LE

D

E-B

US

E-B

US

9 10 11 12 14 J315

31 30 29 28 27 26 25 24 23 22 21 20

24

VA

C C

OM

WALL MODULE

SE

T P

T

SE

NS

OR

BY

PA

SS

LE

D

20

VD

C O

UT

19 18 17 16

AI-

1 O

HM

AI-

2 O

HM

AI-

4 V

/mA

AO

2

AO

1

OU

T 5

OU

T 4

AO

3

OU

T 1

OU

T 3

OU

T 2

AI-

3 V

/mA

13

DI-

2

DI-

4

DI-

1

DI-

3

M16417C

TRIAC EQUIVALENT CIRCUIT

DISCHARGE

AIR TEMP

24 Vac

+

+ +

-

-

3

4

SERIES 70

VALVE

ACTUATORML7161

4-20

mA

2-10

V24

Vac

COM 24

Vac

T1

IN-

PUTCOM

SERIES 70

VALVE

ACTUATOR

24

Vac

IN-

PUTCOM

ECONOMIZER

DAMPER

TWO - OR

THREE-WAY

HOT WATER/

STEAM VALVE

TWO - OR

THREE-WAY

CHILLER

WATER VALVE

FAN

T2

DI

GR

OU

ND

DI

GR

OU

ND

AI

GR

OU

ND

AI

GR

OU

ND

AI

GR

OU

ND

LO

N

JA

CK

LO

NW

OR

KS

BU

S

4

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

43 74-2958�2

See Fig. 36 or 37 to wire a pneumatic transducer to a W7750B or W7750C.

Fig. 36. Series 60 pneumatic transducer to W7750B,C.

To use the analog outputs on the W7750C with 2 to 10V actuators or transducers, a 500 ohm (1 percent or better tolerance) resistor must be placed across the 4 to 20 mA devices input and ground terminal. See Fig. 37 for an example. The resistor converts a 4 to 20 mA signal into a 2 to 10V signal.

NOTE: Wire the 500 ohm resistor physically as close as possible to the driven device. If the resistor is located far away from the driven device, it is possible that noise will be added onto the 2 to 10V signal to ground line. This noise could cause an actuator to re-position (jitter) and reduce the actuators life.

Fig. 37. RP7517B Pneumatic Transducer to W7750C.

LONWORKS® Bus Termination ModuleOne 209541B Excel 10 FTT Termination Module is required for a singly terminated LONWORKS Bus segment. Two 209541B Excel 10 FTT Termination Modules are required for a doubly terminated daisy-chain LONWORKS Bus segment (see Fig. 38). Refer to LONWORKS Bus Wiring Guidelines form, 74-2865 for termination module placement rules.

For 209541B Excel 10 FTT Termination module placement and wiring options, see Fig. 39.

24

VA

C

24

(H

)

24

(N

)

24

(H

)

24

(N

)

INC

RE

AS

E

DE

CR

EA

SE

24 VAC

W7750B,C CONSTANT

VOLUME AHU

CONTROLLER

PNEUMATIC

TRANSDUCER

1

2

3

4

4

MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN;

REVERSING TERMINATIONS RESULTS IN EQUIPMENT

MALFUNCTION.

OPTIONAL 24 VAC WIRING TO NEXT CONTROLLER.

USE 1/4 IN (6 MM) PNEUMATIC TUBING. MINIMUM BRANCH LINE

MUST BE 6 FT. (1.8M) OR LONGER.

W7750B SHOWN. TERMINALS 16,17,18 ARE DIGITAL OUTPUTS.

31 30 29 28 27 26 25 24 23 22 21 20

24

VA

C C

OM

19 18 17 16

+

-

3

21

OU

T 7

OU

T 6

OU

T 5

OU

T 4

OU

T 8

OU

T 1

OU

T 3

OU

T 2

DI-

2

DI-

4

DI-

1

DI-

3

DI

GR

OU

ND

DI

GR

OU

ND

PNEUMATIC

VALVE

M10078D

M

B

M

24

VA

C

24 VAC

W7750C CONSTANT

VOLUME AHU

CONTROLLER

RP7517B PNEUMATIC TRANSDUCER

1

2

3

3

ANALOG OUTPUTS FROM W7750C ARE 4 TO 20 mA SIGNALS. A 500 OHM1% TOLERANCE (OR BETTER) PRECISION RESISTOR IS REQUIRED TODRIVE THIS (RP7517B) AND OTHER 2 TO 10V DEVICES. PLACE THISRESISTOR AS CLOSE AS POSSIBLE TO THE DRIVEN DEVICE.

USE 1/4 IN (6 MM) PNEUMATIC TUBING. MINIMUM BRANCH LINEMUST BE 6 FT. (1.8M) OR LONGER.

TERMINALS 16 TO 18 ARE ANALOG OUTPUTS (W7750C ONLY).

31 30 29 28 27 26 25 24 23 22 21 20

24

VA

C C

OM

19 18 17 16

+-

2

1

AO

2

AO

1

BL

AC

K

BL

UE

BR

OW

N

OU

T 5

OU

T 4

AO

3

OU

T 1

OU

T 3

OU

T 2

DI-

2

DI-

4

DI-

1

DI-

3

PNEUMATICVALVE ACTUATOR

500

M17368

RP7517B

1 M2 B

M

DI

GR

OU

ND

DI

GR

OU

ND

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 44

Fig. 38. Typical doubly terminated daisy-chain LONWORKS® Bus segment termination module wiring.

M10519A

PART NO. 209541BTERMINATIONMODULE

PART NO. 209541BTERMINATIONMODULE

W7750B, C

1415 1415

W7750B, C

1415

W7750B, C

BROWNBROWN

ORANGE

ORANGE

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

45 74-2958�2

Fig. 39. LONWORKS® Bus termination wiring options.

Step 5. Order EquipmentAfter compiling a bill of materials through completion of the previous application steps, refer to Table 11 for ordering information. Contact Honeywell for information about Controllers and Wall Modules with no logo. See Table 11. Excel 10 W7750 Controller Ordering Information.

M11618B

W7750

(D) LONWORKS Bus Termination network

switches in the Q7740A, B Repeaters(C) LONWORKS Bus Termination Module installed

at 2 x 4 or 60 mm box-mounted T7770

(E) Installing LONWORKS Bus Termination

Module at W7751H (terminals 11 and 12)

(F) Twist wires and attach wire nuts to RJ-45 Adapter

cables, LONWORKS Bus segment wires and Termination

Module to connect to a Q7751A,B Router

(B) Installing LONWORKS Bus

Termination Module at W7750

(A) Enabling Internal Termination Network using

jumpers in the Q7750A Zone Manager

RJ-45PLUG

PART NO. 209541BTERMINATIONMODULE

LONWORKS BUS

WIRE NUTS

LONWORKS BUS

TERMINAL BLOCKFOR Q7750A ZONE MANAGER

INSERT INTO TERMINALS 1 AND 2 WITH THE

LONWORKS BUS WIRE. TERMINATION MODULE IS

PHYSICALLY LOCATED BEHIND THE T7770

INSIDE THE 2 X 4 OR 60 MM BOX.

Q7751A LONWORKS BUSROUTER

LONWORKS BUS

8

7

6

5

4

3

LONWORKS BUS

LONWORKS BUS

INTERNALTERMINATION

NETWORK

INTERNALTERMINATION

NETWORKFIELD INSTALLED JUMPER

FIELD INSTALLED JUMPER

LONWORKS BUS

NE

T 2

SINGLY TERMINATED SEGMENT

USE FOR DOUBLYTERMINATEDDAISY-CHAINSEGMENT

PART NO. 209541BTERMINATIONMODULE

PART NO. 209541BTERMINATION MODULE

PART NO. 209541BTERMINATION MODULE

O I II

O I II

O I II

O I II

A B

C D

SWITCHES ON SIDE, UNDER Q7740A,B CIRCUIT BOARD.USE SMALL FLAT OBJECT TO MOVE THE SWITCHES AS NEEDED FROM POSITION O (NO TERMINATION)POSITION I (SINGLY TERMINATED)POSITION II (DOUBLY TERMINATED)

SEGMENTS

LABEL ON Q7740B 4 WAY REPEATER

Q7740B 4 WAY REPEATER SHOWN, Q7740A 2 WAY REPEATER HAS TWO SWITCHES.

NOTE:

1

1

1

1

1

209541B TERMINATION MODULE IS A THREE WIRE DEVICE. FOR SINGLE TERMINATED NETWORKS USE BROWN AND YELLOW LEADS.FOR DOUBLE TERMINATED NETWORKS USE BROWN AND ORANGE LEADS.

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 46

Table 11. Excel 10 W7750 Controller Ordering Information. Part Number Product Description Comments

Excel 10 W7750 Controllers:W7750A2005 Constant Volume AHU Controller (W7750A) Three Analog Inputs, Three Digital Inputs and

Six 24 Vac Relay OutputsW7750B2011 Constant Volume AHU Controller (W7750B) Six Analog Inputs, Five Digital Inputs and Eight

(High-side Low-side switchable)Triac OutputsW7750C2001 Constant Volume AHU Controller (W7750C) Six Analog Inputs, Five Digital Inputs, Five Triac

Outputs and Three Analog OutputsEchelon Based Components and Parts:

Q7750A2003 Excel 10 Zone Manager Free Topology Tranceiver (FTT)Q7751A2002 Router (FTT)Q7751B2000 Router Twisted Pair Tranceiver (78 kbps) to FTTQ7752A2001 Serial Interface (FTT)Q7752A2009 Serial Interface (PCMCIA card) (FTT)Q7740A1008 Excel 10 2-Way Repeater Used to extend the length of the LONWORKS

Bus. Contains built in termination modules.Q7740B1006 Excel 10 4-Way Repeater Used to extend the length of the LONWORKS

Bus. Contains built in termination modules.XD 505A Standard C-Bus Communications Submodule �XD 508 C-Bus Communications Submodule (1 megabit

baud rate)�

209541B Termination Module One/two required per LONWORKS Bus segment205979 Operator Terminal Cable for LONWORKS Bus Serial interface to wall module or controller

T7770 and T7560 Wall Modules:T7770A1006 Sensor with Honeywell Logo Used with Excel 5000 and Excel 10 ControllersT7770A2004 Sensor, LONWORKS Jack and Honeywell Logo Used with Excel 5000 and Excel 10 ControllersT7770B1004 Sensor with Setpoint and LONWORKS Jack,

Honeywell LogoDegrees F Absolute

T7770B1046 Sensor with Setpoint and LONWORKS Jack, Honeywell Logo

Relative Setpoint

T7770B1020 Sensor with Setpoint and LONWORKS Jack, Honeywell Logo

Degrees C Absolute

T7770C1002 Sensor with Setpoint, Bypass/LED and LONWORKS Jack, Honeywell Logo

Degrees F Absolute

T7770C1044 Sensor with Setpoint, Bypass/LED and LONWORKS Jack, Honeywell Logo

Relative Setpoint

T7770C1010 Sensor with Setpoint, Bypass/LED and LONWORKS Jack, No Logo

Degrees F Absolute

T7770C1028 Sensor with Setpoint, Bypass/LED and LONWORKS Jack, Honeywell Logo

Degrees C Absolute

T7770C1051 Sensor with Setpoint, Bypass/LED and LONWORKS Jack, No Logo

Relative Setpoint

T7770D1000 Sensor with Bypass/LED and LONWORKS Jack, Honeywell Logo

Degrees F Absolute

T7560A1018 Digital Wall Module with Sensor, Setpoint and Bypass/LCD, Honeywell Logo

T7560A1042 Digital Wall Module with Sensor, Setpoint and Bypass/LCD, Honeywell Logo

All White

T7560B1016 Digital Wall Module with Sensor, Setpoint, Bypass/LCD and Humidity, Honeywell Logo

T7560B1032 Digital Wall Module with Sensor, Setpoint, Bypass/LCD and Humidity, Honeywell Logo

All White

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

47 74-2958�2

Temperature Sensors (Various Applications):C7041C2003 Duct Discharge/Return Air Sensor. 20K ohm 18 in. (457mm) insertion length.C7041D2001 Hot or chilled Water Temperature Sensor. 20K ohm

NTCUse 50001774-001 Immersion Well

C7041F2006 Outside Air Temperature Sensor. 20K ohm NTC W7750B,C onlyC7041J2007 Averaging Discharge/Return Air Temperature

Sensor. 20K ohm NTCDuct element cord length 12 ft. (3.7m).

C7041B2005 Discharge/Return Air Temperature Sensor. 20K ohm NTC

Element length 6 in. (152 mm).

C7041B2013 Discharge/Return Air Temperature Sensor. 20K ohm NTC

Element length 12 in. (305 mm).

C7041K2005 Hot or chilled Water Temperature Sensor. 20K ohm NTC

Strap-on

C7100A1015 Averaging Discharge/Return Air Temperature Sensor. PT3000

13 in. (330mm) insertion length.

C7031G2014 Outdoor Air Temperature Sensor. PT3000 Weatherproof, 1/2 in. conduit knockout.C7170A1002 Outdoor Air Temperature Sensor. PT3000 �C7770A1006 Air Temperature Sensor. 20K ohm NTC

nonlinearizedDuct-mounted sensor that functions as a primary and/or secondary sensor.

Sensors (CO2, Humidity, Enthalpy, and Pressure):C7232A1008 CO2 Wall Mount Sensor/Monitor with display Use to measure the levels of carbon dioxide

C7232A1016 CO2 Wall Mount Sensor/Monitor without display Use to measure the levels of carbon dioxide

C7232B1006 CO2 Duct Mount Sensor/Monitor with display Use to measure the levels of carbon dioxide

C7232B1014 CO2 Duct Mount Sensor/Monitor without display Use to measure the levels of carbon dioxide

C7400A1004 Solid State Enthalpy Sensor (4 to 20 mA) For outdoor and return air enthalpyC7600B2008 Solid State Humidity Sensor (2 to 10 Vdc) For wall mount air humidityC7600C1008 Solid State Humidity Sensor (4 to 20 mA) For outdoor and return air humidityC7632A1004 Solid State Humidity Sensor without display For wall mount air humidityC7632B1002 Solid State Humidity Sensor without display For duct mount air humidityH7625A, H7635A Solid State Humidity Sensor, wall mount Includes a 20K ohm temperature sensorH7625B, H7635B, H7655B

Solid State Humidity Sensor, duct mount Includes a 20K ohm temperature sensor

H7635C Solid State Humidity Sensor, outdoor mount Includes a 20K ohm temperature sensorP7640A,B Pressure Sensor (4 to 20 mA), use 500 ohm resistor Set for 0 to 5 in. w.c.

Accessories:ML7984B3000 Valve Actuator Pulse Width Modulation (PWM) Use with V5011 or V5013 F and G ValvesML6161B1000 Damper Actuator Series 60 �M6410A Valve Actuator Series 60 Use with V5852/V5853/V5862/V5863 ValvesML684A1025 Versadrive Valve Actuator with linkage, Series 60 Use with V5011 and V5013 ValvesML6464A1009 Direct Coupled Actuator, 66 lb-in. torque, Series 60 �ML6474A1008 Direct Coupled Actuator, 132 lb-in. torque, Series 60 �ML6185A1000 Direct Coupled Actuator, 50 lb-in. spring return Series 60V5852A/V5862A Two-way terminal unit water valve; 0.19, 0.29, 0.47,

0.74, 1.2, and 1.9 Cv 1/2 in. npt (13 mm) or 2.9 and 4.9 Cv 3/4 in. npt (19 mm)

Use with M6410 Valve Actuator. Close-off rating for 0.19 to 1.9 Cv is 65 psi; for 2.9 and 4.9, Cv is 45 psi. (Coefficient of volume or capacity index Cv = gallons per minute divided by the square root of the pressure drop across the valve.)

Table 11. Excel 10 W7750 Controller Ordering Information. (Continued) Part Number Product Description Comments

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 48

Step 6. Configure ControllersLONSPEC� or Care PC Software is used to configure W7750 Controllers to match their intended application. Refer to the LONSPEC� 74-2937 or Care 74-5587 User Guides for details on operating the PC software.

W7750 Controllers are shipped from the factory with a default hardware configuration. On power-up, the controller configuration parameters are set to the default values listed in

Table 20 in Appendix C. The controller can operate normally in this mode (if the equipment and wiring match the default setup), and given valid sensor inputs, the outputs are controlled appropriately to maintain space temperature at the default setpoint. The default I/O arrangement for the W7750A is printed on the terminal labels. Also see the wiring details in Fig. 27 in Step 4, Prepare Wiring Diagrams. The labeled I/O terminals are defined in Table 10.

Step 7. Troubleshooting

Troubleshooting Excel 10 Controllers and Wall ModulesIn addition to the following information, refer to the Installation Instructions and Checkout and Test manual for each product. Most products have a Checkout and Test section in their Installation Instructions manual. If not, look for a separate Checkout and Test manual. See the Applicable Literature section for form numbers.

1. Check the version numbers of the controller firmware.2. Check the wiring to the power supply and make sure

there is a good earth ground to the controller.3. Check the occupancy and HVAC modes.

4. Compare the current actual setpoint with the actual space temperature.

5. Check the desired configuration settings.6. Check the network wiring and type of wire used.7. Check the bindings and referred points.

NOTE: If the fan shuts off periodically for no specific reason and the controller restarts the fan by itself after about 20 to 60 seconds, the cause could be a bad Air Flow switch. If the controller has a digital input assigned as a Proof of Air Flow input, try unconfiguring this digital input to see if these shutdowns continue. If not, adjust or replace the Air Flow switch to get it working.

V5853A/V5863A Three-way mixing terminal unit hot water valve; 0.19, 0.29, 0.47, 0.74, 1.2, and 1.9 Cv 1/2 in. npt (13 mm) or 2.9 and 4.9 Cv 3/4 in. npt (19 mm)

Use with M6410 Valve Actuator. Close-off rating for 0.19 to 0.74 Cv is 55 psi; 1.2 and 1.9 Cv is 22 psi; 2.9 and 4.9 Cv is 26 psi.

R8242A Contactor, 24 Vac coil, DPDT �AT72D, AT88A, AK3310, etc.

Transformers �

EN 50 022 DIN rail 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.) Obtain locally: Each controller requires 5 in.� Two DIN rail adapters Obtain locally: Part number TKAD, from Thomas

and Betts, two for each controller.Cabling:

� Serial Interface Cable, male DB-9 to female DB-9 or female DB-25.

Obtain locally from any computer hardware vendor.

Honeywell AK3791 (one twisted pair) AK3792 (two twisted pairs)

LONWORKS Bus (plenum): 22 AWG (0.34 mm2) twisted pair solid conductor, nonshielded or Echelon approved cable.

Level IV 140°F (60°C) rating

Honeywell AK3781 (one twisted pair) AK3782 (two twisted pairs)

LONWORKS Bus (nonplenum): 22 AWG (0.34 mm2) twisted pair solid conductor, nonshielded or Echelon approved cable.

Level IV 140°F (60°C) rating

Honeywell AK3725 Inputs: 18 AWG (1.0 mm2) five wire cable bundle Standard thermostat wireHoneywell AK3752 (typical or equivalent)

Outputs/Power: 14 to 18 AWG (2.0 to 1.0 mm2) NEC Class 2 140°F (60°C) rating

Honeywell AK3702 (typical or equivalent)

18 AWG (1.0 mm2) twisted pair Non-plenum

Honeywell AK3712 (typical or equivalent)

16 AWG (1.3 mm2) twisted pair Non-plenum

Honeywell AK3754 (typical or equivalent)

14 AWG (2.0 mm2) two conductor Non-plenum

Table 11. Excel 10 W7750 Controller Ordering Information. (Continued) Part Number Product Description Comments

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

49 74-2958�2

Temperature Sensor and Setpoint Potentiometer Resistance RangesThe T7770 or T7560A,B Wall Modules or the C7770A Air Temperature Sensor has the following specified calibration points, which are plotted in Fig. 40:

Temperature (°F) Resistance Value (ohms)98 1175580 1847870 2402860 3152542 52675

The T7770 Wall Module setpoint potentiometers have the following linear calibration points:

Temperature (°F) Resistance Value (ohms)85 142670 550055 9574

Fig. 40. Temperature sensor resistance plots.

NOTE: 10K ohm values apply to the T7770A3xxx Sensors.

AlarmsWhen an Excel 10 has an alarm condition, it reports it to the central node on the LONWORKS Bus (typically, the Excel 15A Building Manager or the Excel 10 Zone Manager). See Table 12. Information contained in an alarm message is:

� Subnet Number:LONWORKS Bus subnet that contains the Excel 10 node that has the alarm condition.

� Node Number:Excel 10 node that has the alarm condition (see Network Alarm).

� Alarm Type:Specific alarm being issued. An Excel 10 can provide the alarm types listed in Table 12.

TEMPERATURE (DEGREES)

oF30 40 50 60 70 80 90 100 110

0 10 20 30 40

RE

SIS

TA

NC

E (

OH

MS

)

20K OHM AT 77oF (25oC)

80K

70K

60K

50K

40K

30K

20K

10K

oC

M11620

AIR TEMPERATURE SENSOR

10K OHM SETPOINT POTRESISTANCE VALUES

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 50

NOTE: The node can be reset by switching the node to MANUAL and then to the normal operating mode (see Fan Operation in Appendix B).

Also, the Excel 10 variables, AlarmLogX where X is 1 through 5, that store the last five alarms to occur in the controller, are available. These points can be viewed through LONSPEC� LONSTATION� or Care.

Certain alarm conditions are suppressed conditionally as follows:

Broadcasting the Service MessageThe Service Message allows a device on the LONWORKS Bus to be positively identified. The Service Message contains the controller ID number and, therefore, can be used to confirm the physical location of a particular Excel 10 in a building.

There are three methods of broadcasting the Service Message from an Excel 10 W7750 Controller. One uses a hardware service pin button on the side of the controller (see Fig. 41). The second uses the wall module pushbutton (see

Fig. 43 and 44). By pressing the wall module pushbutton for more than four seconds, the controller sends out the Service Message. The third involves using the PC Configuration tool, as follows.

When an Assign ID command is issued from the commissioning tool, the node goes into the SERVICE_MESSAGE mode for five minutes. In the SERVICE_MESSAGE mode, pressing the Occupancy Override button on the remote wall module (refer to Fig. 43 and 44 for override button location) causes the Service Message to be broadcast on the network. All other functions are normal in the SERVICE_MESSAGE mode. Even if an Excel 10 W7750 Controller does not have an Override button connected, it can broadcast the Service Message on the network by temporarily shorting the Controller Bypass Input terminal to the Sensor Ground terminal on the W7750A,B,C (short terminals 3 and 5).

The LONSPEC� or Care PC tool is used to perform the ID Assignment task.

Table 12. Excel 10 Alarms.

Name of alarm or error bitAlarm type

number Meaning of alarm code or error bitRETURN_TO_NORMAL 128U Return to no alarm after being in an alarm condition. This code is added

numerically to another alarm code to indicate that the alarm condition has returned to normal.

ALARM_NOTIFY_DISABLED 255U The alarm reporting was turned off by DestManMode. No more alarms are reported until DestManMode turns on alarm reporting or on application restart.

NO_ALARM 0 No alarms presently detected.INPUT_NV_FAILURE 1 One or more NV inputs have failed in receiving an update within their specified

FAILURE_DETECT_TIME.NODE_DISABLED 2 The control algorithm has stopped because the controller is in

DISABLED_MODE, MANUAL or FACTORY_TEST mode. No more alarms are reported when the controller is in the DISABLED_MODE. Alarms continue to be reported if the controller is in the MANUAL or FACTORY_TEST mode.

SENSOR_FAILURE 3 One or more sensors have failed.FROST_PROTECTION_ALARM 4 The space temperature is below the frost alarm limit 42.8°F (6°C) when the

mode is FREEZE_PROTECT. The alarm condition remains until the temperature exceeds the alarm limit plus hysterisis.

INVALID_SET_POINT 5 One of the setpoints is not in the valid range.LOSS_OF_AIR_FLOW 6 The Fan Status DI indicates that there is no air flow when the node is

commanding the fan to run. The control is shut down and disabled until power is cycled or the node is reset. See NOTE below. The alarm is not issued until FanFailTime seconds have elapsed since the loss-of-flow condition was first reported

DIRTY_FILTER 7 The pressure drop across the filter exceeds the limit and the filter requires maintenance. The control runs normally.

SMOKE_ALARM 8 The smoke detector has detected smoke and the node has entered an emergency state.

IAQ_OVERRIDE 9 The indoor air quality sensor has detected that the indoor air quality is less than the desired standard and additional outdoor air is being brought into the conditioned space.

LOW_LIM_ECON_CLOSE 10 The economizer has to close beyond the minimum position to prevent the discharge air temperature from going below the discharge temperature low limit.

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

51 74-2958�2

Fig. 41. Location of the Service Pin Button.

W7750 Controller Status LEDThe LED on the front and center of a W7750 Controller provides a visual indication of the status of the device. See Fig. 42. When the W7750 receives power, the LED should appear in one of the following allowable states:

1. Off�no power to the processor.2. Continuously On�processor is in initialized state.3. Slow Blink�controlling, normal state.4. Fast Blink�when the Excel 10 has an alarm condition.

Fig. 42. LED location on W7750.

T7770C,D Wall Module Bypass Pushbutton and Override LEDPressing the bypass pushbutton, located on the T7770C,D Wall Modules in Fig. 43, causes the override LED to display the Manual Override mode of the controller. The modes are:

Fig. 43. The T7770C,D Wall Modules LED and Bypass pushbutton locations.

1. LED = Off. No override active.2. LED = Continuously on. Bypass mode (timed Occupied

override).3. LED = One flash per second. Continuous Unoccupied

override.4. LED = Two flashes per second. Remote only, continu-

ous Occupied override.

T7560A,B Bypass Pushbutton and LCD Display Occupancy SymbolsSee Fig. 44 for the T7560A,B Digital Wall Module bypass pushbutton location.

Press and release the bypass pushbutton, located on the T7560A,B Digital Wall Modules in Fig. 44 for more than one second to cause the sun symbol on the bottom right side of the LCD display to appear. Pressing the bypass pushbutton for more than four seconds causes the controller, hard-wired to the T7560A,B, to go into continuous unoccupied override. The T7560A,B displays the moon symbol.

Fig. 44. T7560A,B Digital Wall Module Bypass pushbutton location.

M10094

SERVICEPINBUTTON

M10095A

W7750

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 J3

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16

E GND

LED BYPASS SNSRSET PT AI-1

OHMA1-2 OHM

AI-3 V/mA

AI-4V/mA

20VDCOUT

DI-4DI-3 DI-2

DI-1VAC

24

VAC

24COM

1

OUT2

OUT3

OUT4

OUT5

OUT6

OUT7

OUT8

OUT

AIGND AI

GND AIGND LONWORKS

-BUSLONJACK

DIGND DI

GND

STATUSLED

M11617

T7770C T7770D

OVERRIDELED

BYPASSPUSHBUTTON

BYPASSPUSHBUTTON

7065

60

55

75

80

85

OVERRIDELED

M17500

BYPASSPUSHBUTTON

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 52

APPENDICES

Appendix A: Using LONSPEC�/Care to Commission a W7750 ControllerNOTE: When commissioning a CVAHU W7750 Controller,

the PC tool first checks that the actual hardware model (such as W7750A,B,C) is the same type which was selected from the Application Selection/Output tab. If the types do not match, the download does not occur and the user-entered values in the Application Selection screens all revert back to default values.

Sensor CalibrationThe space temperature, the optional resistive and voltage/current (W7750B,C only) inputs can all be calibrated. The wall module setpoint potentiometer can not be calibrated.

Perform the sensor calibration by adding an offset value (either positive or negative) to the sensed value using LONSPEC� or Care.

When calibrating voltage/current sensors on the (W7750B,C), the offset amount entered by the user is in volts, regardless of the inputs actual engineering units. See Appendix E for information on how to derive the proper voltage value to enter as an offset during calibration.

Setting the Pid ParametersThe W7750 is designed to control a wide variety of mechanical systems in many types of buildings. With this flexibility, it is necessary to verify the stability of the temperature control in each different type of application. Occasionally, the PID parameters require tuning to optimize comfort and smooth equipment operation. This applies to the W7750A,B,C Controllers.

CVAHU Controllers are configured by LONSPEC� or Care with default values of PID parameters as shown in Appendix C Table 21. If different values for these parameters are desired, Table 13 lists some recommended values to use as a starting point. These recommended values are based on past experience with the applications and in most cases do not require further adjustment.

Table 13. Recommended Values For PID Parameters.

If the PID parameters require adjustment away from these values, use caution to ensure that equipment problems do not arise (see Important below). If any change to PID control parameters is made, the adjustments should be gradual. After each change, the system should be allowed to stabilize so the effects of the change can be accurately observed. Then further refinements can made, as needed, until the system is operating as desired.

IMPORTANTMaking large or frequent changes to PID control parameters can cause equipment problems such as short cycling compressors (if stage minimum run times were disabled in User Addresses DisMinClTime or DisMinHtTime). Other problems that can occur include wide swings in space temperature and excessive overdriving of modulating outputs.

If adjustment of PID parameters is required, use the following. In the items that follow, the term, error, refers to the difference between the measured space temperature and the current actual space temperature setpoint.

� The Proportional Gain (also called Throttling Range) determines how much impact the error has on the output signal. Decreasing the Proportional Gain amplifies the effect of the error; that is, for a given error, a small Proportional Gain causes a higher output signal value.

� The Integral Gain (also called Integral Time) determines how much impact the error-over-time has on the output signal. Error-over-time has two components making up its value: the amount of time the error exists; and the size of the error. The higher the Integral Gain, the slower the control response. In other words, a decrease in Integral Gain causes a more rapid response in the output signal.

� The Derivative Gain (also called Derivative Time) determines how much impact the error rate has on the output signal. The error rate is how fast the error value is changing. It can also be the direction the space temperature is going, either toward or away from the setpoint, and its speed�quickly or slowly. A decrease in Derivative Gain causes a given error rate to have a larger effect on the output signal.

� The Control Band is used only for discharge temperature control of modulating outputs, which includes controlling the economizer dampers, and heating and cooling valves using Cascade Control. The Control Band dictates the

Equipment Configuration

Heat Prop. Gain

Heat Integ. Gain

Heat Deriv. Gain

Heat Control Band

Cool Prop. Gain

Cool Integ. Gain

Cool Deriv. Gain

Cool Control Band

Econ Control Band

Single Stage 2 3000 0 10 2 3000 0 10 10Two Stages 3 2000 0 10 3 2000 0 10 10Three Stages 4.5 1500 0 10 4.5 1500 0 10 10Four Stages 6 1000 0 10 6 1000 0 10 10Series 60 Modulating (Floating) 2 750 0 10 2 750 0 10 10PWM Modulating 2 900 0 10 2 900 0 10 10

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

53 74-2958�2

span through which the discharge temperature must travel to cause the output signal to go from fully closed to fully open. Also, 10 percent of the Control Band value is the size of the deadband around the setpoint where no actuator motion occurs. For example, if controlling a cooling valve with Cascade Control enabled and with the discharge temperature within 0.1 X DaTempClCtrlBd of the discharge setpoint, there is no change in the current valve position.The smaller the Control Band, the more responsive the

control output. A larger Control Band causes more sluggish control. Be careful not to set the Control Band too low and cause large over or under shoots (hunting). This can happen if the space or discharge sensors or wiring are in noisy environments and the value reported to the controller is not stable (such that it bounces). The Control Band is used only in modulating control, and has no purpose when staged control is configured.

Appendix B: Sequences of OperationThis Appendix provides the control sequences of operation for the models of the Excel 10 W7750 CVAHU Controller. The W7750A,B,C Controllers can be configured to control a wide variety of possible equipment arrangements. Tables 14 and 15 (copied from Tables 3 and 4) summarize the available options. This Appendix provides a more detailed discussion of these options.

Common OperationsThe Excel 10 W7750 Controller applications have many common operations that are applicable regardless of the type of heating, cooling, or economizer equipment configuration. These operations are available to the W7750A and the W7750B,C Versions of the CVAHU Controller, and the I/O and network configurations for them are summarized in Table 14.

Available input options are from the wall module and the hard-wired analog and digital inputs. Each application can have only a subset of these devices configured based on the number of physical I/O points available. However, some of the inputs are available over the LONWORKS Bus network.

NOTE: Each W7750 Controller must have a space temperature sensor input either wired directly to the controller, or shared from another LONWORKS Bus device, and must have a digital output configured for controlling the supply fan. In addition, if modulating economizer control is desired, a discharge air temperature sensor must be physically connected to the Excel 10 W7750 Controller. A discharge temperature signal cannot be brought into the controller through the LONWORKS Bus network.

Table 14. Common Configuration Options Summary For W7750A,B,C Controllers.Option Possible Configurations Common To All W7750 Models

Supply Fan 1. Mandatory Digital Output.Type of Air Handler 1. Conventional.

2. Heat Pump.Occupancy Sensor 1. None.

2. Connected: Contacts closed equals Occupied.3. Network (Occ/Unocc signal received via the LONWORKS Bus network).

Window Sensor 1. None.2. Physically Connected: Contacts closed equals window closed.3. Network (Window Open/Closed signal received via the LONWORKS Bus).

Wall Module Option(The T7560A,B have an optional accessory for LONWORKS Bus access)

1. Local (direct wired to the controller).2. Network (sensor value received via the LONWORKS Bus).

Wall Module TypeAll wall modules have a LONWORKS Bus access jack. (The T7560A,B requires an optional accessory.)

1. Sensor only.2. Sensor and Setpoint adjust.3. Sensor, Setpoint adjust and Bypass.4. Sensor and Bypass.

Smoke Emergency Initiation 1. None.2. Physically Connected: Contacts closed equals smoke detected.3. Network (Emergency/Normal signal received via the LONWORKS Bus).

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 54

Table 15. Configuration Options Summary For W7750A,B,C Controllers.

ROOM TEMPERATURE SENSOR (RmTemp)This is the room space temperature sensor. This sensor is the T7770 or the T7560A,B Wall Module. When it is configured, it provides the temperature input for the W7750 temperature control loop. If it is not configured, it is required that a room temperature sensor value be transmitted from another

LONWORKS Bus device. If no valid room temperature value is available to the W7750 Controller, the temperature control algorithm in the controller is disabled, causing the heating, cooling, and economizer control outputs to be turned off. If the W7750 Controller is configured for Continuous Fan (rather

OptionPossible Configurations for the

W7750A Model Possible Configurations for the W7750B,C ModelsType of 1. One stage. 1. One stage.Heating 2. Two stages. 2. Two stages.

3. Three stages. 3. Three stages.4. Four stages. 4. Four stages.5. None. 5. Series 60 Modulating electric valve, or pneumatic via transducer.

6. Pulse Width Modulating electric valve, or pneumatic via transducer.7. None.

Type of 1. One stage. 1. One stage.Cooling 2. Two stages. 2. Two stages.

3. Three stages. 3. Three stages.4. Four stages. 4. Four stages.5. None. 5. Series 60 Modulating electric valve, or pneumatic via transducer.

6. Pulse Width Modulating electric valve, or pneumatic via transducer.7. None.

Type of Economizer

1. Digital Output Enable/Disable signal for controlling an external economizer package.

1. Digital Output Enable/Disable signal for controlling an external economizer package.

2. Series 60 Modulating electric damper motor, or pneumatic via transducer.

2. Series 60 Modulating electric damper motor, or pneumatic via transducer.

3. None. 3. Pulse Width Modulating electric damper motor, or pneumatic via transducer.

4. None.IAQ Option 1. None. 1. None.

2. Local IAQ Digital Input�directly wired to the controller. (Contacts closed means poor IAQ is detected.)

2. Local IAQ Digital Input�directly wired to the controller. (Contacts closed means poor IAQ is detected.)

3. Network (IAQ Override signal received via the LONWORKS Bus).

3. Network (IAQ Override signal received via the LONWORKS Bus).

4. Local CO2 Analog Input�directly wired to the controller. (The sensor must be a 0 to 10V device representing 0 to 2000 PPM CO2.)

Coil Freeze 1. None. 1. None.Stat Option 2. Local Coil Freeze Stat Digital

Input�directly wired to the controller. (Contacts closed means that coil freeze condition is sensed.)

2. Local Coil Freeze Stat Digital Input�directly wired to the controller. (Contacts closed means that coil freeze condition is sensed.)

Filter Monitor 1. None. 1. None.Option 2. Local Dirty Filter Digital

Input�directly wired to the controller. (Contacts closed means that the filter is dirty.)

2. Local Dirty Filter Digital Input�directly wired to the controller. (Contacts closed means that the filter is dirty.)

3. Local Analog Input for Differential Pressure across the Filter (directly wired to the controller). The sensor must be a 2 to 10V device representing 0 to 5 in. w.c. (1.25 kPa).

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

55 74-2958�2

than Intermittent Fan (see Fan Operation in this Appendix), and the mode is Occupied when the RmTemp value becomes invalid, the fan continues to run.

REMOTE SETPOINT (RmtStptPot)

NOTE: Unocc heat and cool setpoints cannot be changed without the pc tool.

This is the Setpoint Potentiometer contained in the T7770 or the T7560A,B Wall Module. When configured, this occupant value is set to calculate the actual cooling or heating Occupied Setpoint. There are two options for how to calculate the actual setpoint to be used by the temperature control algorithm: (Offset) and (Absolute Middle). When SetPtKnob is set to Offset, the Wall Module setpoint knob represents a number from -9° to +9°F (-5° to +5°C) which is added to the software occupied setpoints for the heat and the cool modes (CoolOccSpt and HeatOccSpt). When SetPtKnob is set to Absolute Middle, the setpoint knob becomes the center of the Zero Energy Band (ZEB) between the cooling and heating occupied setpoints. The size of the ZEB is found by taking the difference between the software heating and cooling occupied setpoints; therefore, for Absolute Middle, the actual setpoints are found as follows:

ActualCoolSpt = RmtStptPot + (CoolOccSpt - HeatOccSpt) / 2

ActualHeatSpt = RmtStptPot - (CoolOccSpt - HeatOccSpt) / 2

During Standby and Unoccupied times, the remote setpoint pot is not referenced, and the software setpoints for those modes are used instead.

SETPOINT LIMITS (LoSetptLim AND HiSetptLim)Remote setpoint pot limits are provided by LoSetptLim and HiSetptLim. The occupied setpoints used in the control algorithms are limited by these parameters. When the setpoint knob is configured to be of type Absolute Middle, the lowest actual setpoint allowed is equal to LoSetptLim, and the highest actual setpoint allowed is equal to HiSetptLim. When the setpoint knob is configured to be an Offset type, the lowest actual setpoint allowed is equal to HeatOccSpt - LoSetptLim, and the highest allowed is equal to CoolOccSpt + HiSetptLim.

BYPASS MODE (StatusOvrd AND StatusLed)During Unoccupied periods, the facility occupant can request that Occupied temperature control setpoints be observed by depressing the Bypass pushbutton on the wall module. When activated, the controller remains in Bypass mode until:

1. Bypass Duration Setting has timed out (BypTime), or2. User again presses the Wall Module pushbutton to

switch off Bypass mode, or3. Occupancy schedule (DestSchedOcc network input or

TimeClckOcc digital input) switches the mode to Occupied.

4. User sets the DestManOcc network point to Not Assigned.

The LED on the T7770 Wall Module (Override LED) indicates the current bypass mode status (see the T7770C,D Wall Module Bypass Pushbutton and Override LED section). The LCD on the T7560 Digital Wall Module indicates the current bypass mode status (see the T7560A,B Digital Wall Module Bypass Pushbutton and LCD Occupancy Symbols section).

BypassTimeBypassTime is the time between the pressing of the override button at the wall module (or initiating OC_BYPASS via nviManOcc) and the return to the original occupancy state. When the bypass state has been activated, the bypass timer is set to BypassTime (default of 180 minutes).

OverrideTypeOverrideType specifies the behavior of the override button on the wall module. There are three possible states that have the following meanings:

NONE disables the override button.NORMAL causes the override button to set the OverRide

state to OC_BYPASS for BypassTime (default 180 minutes), when the override button has been pressed for approximately 1 to 4 seconds, or to set the OverRide state to UNOCC when the button has been pressed for approximately 4 to 7 seconds. When the button is pressed longer than approximately 7 seconds, then the OverRide state is set to OC_NUL (no manual override is active).

BYPASS_ONLY causes the override button to set the OverRide state to OC_BYPASS for BypassTime (default 180 minutes), on the first press (1 to 7 seconds). On the next press, the OverRide state is set to OC_NUL (no manual over ride is active).

OverridePriorityOverridePriority configures the override arbitration between nviManOcc, nviBypass.state, and the wall module override button. There are two possible states which have the following meanings:

LAST specifies that the last command received from either the wall module or nviManOcc determines the effective override state.

NET specifies that when nviManOcc is not OC_NUL, then the effective occupancy is nviManOcc regardless of the wall module override state.

CYCLES PER HOUR (ubHeatCph AND ubCoolCph)ubHeatCph specifies the mid-load number of on / off cycles per hour (default is 6), when the mode is HEAT. ubCoolCph specifies the mid-load number of on / off cycles per hour (default is 3), when the mode is COOL. This is to protect the mechanical equipment against short cycling causing excessive wear. In addition the cycle rate specifies the minimum on and off time according to Table 17.

T7770C,D OR T7560A,B WALL MODULE BYPASS PUSHBUTTON OPERATIONThe Wall Module Bypass pushbutton is located on both the T7770C,D or the T7560A,B Wall Modules, see Fig. 43 and 44. The bypass pushbutton can change the controller into various occupancy modes, see Table 16.

Table 16. Bypass Pushbutton Operation.

If the pushbutton is held down for

But for not more than The resulting mode is

Less than 1 second � No Override is active1 second 4 seconds Bypass (a timed Occupied

Override)4 seconds 7 seconds Continuous Unoccupied

Override

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 56

NOTES: If the pushbutton is held down for longer than seven seconds, the controller reverts back to No Override and repeats the cycle above. See Fig. 45.

Continuous Occupied override mode can only be initiated remotely; that is, over the LONWORKS Bus network.

Fig. 45. LED and Bypass pushbutton operation.

STANDBY MODE (StatusOcySen)The digital input for an occupancy sensor (usually a motion detector or possibly a time clock) provides the controller with a means to enter an energy-saving Standby mode whenever people are not in the room. Standby mode occurs when the scheduled occupancy is Occupied, and the occupancy sensor detects no people currently in the room (digital input contacts Closed means people are in the room, and contacts Open means the room is Unoccupied). When in Standby mode, the Excel 10 W7750 Controller uses the Standby Cooling Setpoint for cooling (CoolStbySpt), or the Standby Heating Setpoint for Heating (HeatStbySpt) as the Actual Space Temperature Setpoint. The occupancy sensor signal can also be a network input from another LONWORKS Bus device, so that no physical sensor is required at the receiving W7750 Controller.

IMPORTANTWhen the W7750 Controller is in Standby mode, the economizer minimum position setting is not observed. This means the fresh air dampers will go fully closed if there is no call for cooling.

CONTINUOUS UNOCCUPIED MODEThis mode is entered when a wall module is configured with a Bypass pushbutton that was pressed for four to seven seconds causing the wall module LED/LCD to blink. This mode can also be entered via a network command (ManualOcc set to Unoccupied). If the controller is in this mode, it reverts to the Unoccupied setpoints for temperature control, and the economizer does not observe its minimum position setting. The controller remains in this mode indefinitely until the Bypass pushbutton is pressed to exit the mode or a network command is sent to clear the mode. A configuration parameter is available to disable wall-module initiation of Continuous Unoccupied mode (OvrdType).

OCCUPANCY MODE AND MANUAL OVERRIDE ARBITRATIONThe W7750 has multiple sources for occupancy schedule information and, therefore, it employs an arbitration scheme to determine the current actual mode. Time-of-day (TOD) schedule status comes from two sources, a configured digital input for OccTimeClock or the DestSchedOcc network input received from a central control. If the digital input source is configured, it has highest priority and determines the Occupancy mode. This digital input is either ON (shorted = occupied), OFF (open = unoccupied), or not active (not configured); otherwise, the status is determined by the DestSchedOcc input from the network source. The DestSchedOcc has three possible states, occupied, unoccupied or standby.

Manual Override Status can be derived from three sources and governed by two selectable arbitration schemes. The two schemes are:� Network Wins or Last-in Wins, as set in OvrdPriority.

The three sources of manual override status are:DestManOcc - Has possible states: Occupied,

Unoccupied, Bypass, Standby and Not Assigned (not active). This input source has the highest priority in determining manual override status for a Network Wins arbitration scheme, and in the event there is more than one source change at a time in the Last-in Wins arbitration scheme. Here, bypass initiates a self-timed bypass of the control unit and expires upon completion of the defined timed period. The controller then treats the bypass status of this input as Not Assigned until the next change in status.

M8483A

RESET

NOT ASSIGNED(LED OFF)

PRESS FOR ONETO FOUR SECONDS

BYPASS OCCUPIED(LED ON)

BYPASSTIMEOUT

PRESS FOR FOUR TO SEVEN SECONDS

PRESS FOR LESS THAN ONE SECOND

UNOCCUPIED(LED BLINK)

PRESS FOR LESS THAN ONE SECOND

PRESS FOR MORE THAN SEVEN SECONDS

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

57 74-2958�2

DestBypass - Has possible states: Bypass On, Bypass Off or Not Assigned (not active). This input places the controller in an untimed bypass state or turns off the bypass mode. This source is second in priority to DestManOcc under the same arbitration schemes mentioned above.

Override Button -The wall module Override pushbutton can command status of Bypass, Continuous Unoccupied and Not Assigned. This source has the lowest priority status in the above mentioned schemes. The above mention sources of override must be either Not Assigned or Off before the Override pushbutton affects the manual override status in the Network Wins scheme. All actions, in this case, taken from the Override pushbutton are locked out.

Bypass status is a controller-timed event whose duration is set in BypTime. Upon expiration of the timer, the status returns to Not Assigned. The status of this input can be overridden with the receipt of Not Assigned from DestManOcc. This, in effect, cancels a timed bypass or a continuous unoccupied mode.

The Override pushbutton can be configured as Normal (all of the above mentioned states are possible), Bypass Only (Bypass and Not Assigned only) or None (effectively Disabling the Override pushbutton).

TIME CLOCK (Occ_Time_Clock)OccTimeClock is the state of the digital input configured and wired to a time clock. When the digital input is detected to be Closed (Occupied), the scheduled occupancy will be OC_OCCUPIED. If the detected state of the digital input is Open (Unoccupied), then the scheduled occupancy will be OC_UNOCCUPIED. If the Occ_Time_Clock is not configured, then either the DestSchedOcc network input received from a central control or the time clock that is broadcast from a Sched_Master configured W7750, controls the occupied mode.

SCHEDULE MASTER (Sched_Master)Sched_Master is the state of a digital input that is configured and wired to the W7750. If the Sched_Master input is closed (input shorted), the node is the schedule master and the state of the locally connected time clock will be broadcast out over the LONWORKS Bus to the other W7750 controllers. If the Sched_Master input is open, then the node is not a schedule master and the local time clock will not be sent out over the LONWORKS Bus even if the time clock input is configured. However, the DestSchedOcc network input received from a central control has a higher priority than the local time clock, and therefore overrides the local time clock. The W7750 controllers automatically bind without the need for a configuration tool.

SETPOINT RAMPINGThe W7750 Controller incorporates a ramping feature that gradually changes the space setpoints between occupancy modes. This feature is only operational if the network variable inputs DestSchedOcc, TodEventNext, and Time Until Next Change Of State (TUNCOS) are being used to change the W7750 Occupancy mode. The applicable Setpoints are OaTempMinHtRamp, OaTempMaxHtRamp, MinHtRamp and MaxHtRamp (for HEAT mode operation), and OaTempMinClRamp, OaTempMaxClRamp, MinClRamp and MaxClRamp (for the COOL mode operation). See Fig. 46 for a pictorial representation of how these setpoints interact.

During recovery operation, the setpoint changes at a rate in degrees per hour depending on the outdoor air temperature. If there is no outdoor air temperature sensor available, then MinHtRamp is used as the recovery rate.

Fig. 46. Setpoint ramping parameters with ramp rate calculation.

NOTE: Recovery ramping applies between scheduled heating or cooling setpoint changes from UNOCCUPIED to STANDBY, UNOCCUPIED to OCCUPIED, and STANDBY to OCCUPIED. Scheduled setpoint changes from OCCUPIED to UNOCCUPIED or OCCUPIED to STANDBY do not use a ramped setpoint but instead use a step change in setpoint. Recovery ramps begin before the next scheduled occupancy time and are ramped from the setpoint for the existing scheduled occupancy state to the setpoint for the next occupancy state.

RECOVERY RAMPING FOR HEAT PUMP SYSTEMSWhen the node is controlling heat pump equipment, during the recovery ramps, the heating setpoint is split into a heat pump setpoint (for compressors) and an auxiliary heat setpoint (for auxiliary heat stages). The heat pump setpoint is a step change at the recovery time prior to the OCCUPIED time. Recovery time is computed from the configured heat recovery ramp rate. The recovery time is calculated:Recovery time = (OCC setpoint - current setpoint)/ramp rate

See Fig. 47 for the various setpoints.

HEAT RECOVERY RAMP RATE(DEGREES/HOUR)

MaxHtRamp

MinHtRamp

OaTempMinHtRamp OaTempMaxHtRamp

OUTDOOR AIRTEMPERATURE

M10109A

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 58

Fig. 47. Setpoint ramping parameters with setpoint calculation.

During the COOL recovery period, the setpoint changes at a rate in degrees per hour relative to the outdoor air temperature. If there is no outdoor air temperature sensor available, the MinClRamp is used as the recovery rate.

See Fig. 48 for the various setpoints.

Fig. 48. Setpoint ramping parameters with ramp rate calculation.

NOTES: The setpoint used during the COOL recovery period is similar to the heat mode in Fig. 46, except the slope of the line reverses for cooling.

Recovery ramping applies between scheduled heat-ing or cooling setpoint changes from UNOCCUPIED to STANDBY, UNOCCUPIED to OCCUPIED, and STANDBY to OCCUPIED. Scheduled setpoint changes from OCCUPIED to UNOCCUPIED or OCCUPIED to STANDBY do not use a ramped set-point, but instead, use a step change in setpoint. Recovery ramps begin before the next scheduled occupancy time and are ramped from the setpoint for the existing scheduled occupancy state to the set-point for the next occupancy state.

FAN OPERATIONThe W7750 supply fan can be controlled in one of two different ways. In Continuous Fan mode, the fan runs whenever the controller is in Occupied mode. When in Standby or Unoccupied modes, the fan cycles on with a call for cooling (or heating if the FanOnHtMode parameter is set). In Intermittent Fan mode, the fan cycles on with a call for cooling (or heating if the FanOnHtMode parameter is set), and cycles off when the space temperature control is satisfied.

The fan control supports an optional (Proof of Air Flow) digital input, that allows monitoring of the supply fans status. If the fan is commanded on, the Proof of Air Flow digital input is checked up to three times to verify that the fan is running after an initial delay of FanOnDelay seconds (adjustable). If the fan fails to start the CVAHU must be reset by first cycling CVAHU power. If this does not work, set DestManMode to Manual and then back to Enable. After a reset the application restarts�all outputs switch off and auto control is enabled.

Also, the W7750 Controller provides fan-run-on operation that keeps the fan running for a short time after heating or cooling shuts off. The amount of time that the fan continues to run is set in FanRunOnHeat for heating mode and FanRunOnCool for cooling mode.

WINDOW SENSOR (StatusWndw)The digital input for a window contact provides the algorithm with a means to disable its temperature control activities if someone has opened a window or door in the room. When a window is detected to be Open (digital input contacts Open equals window open), the normal temperature control is disabled, and the W7750 Controller enters the Freeze Protect mode. Freeze Protect mode sets the space setpoint to 46.4 °F (8°C) and brings on the fan and heat if the space temperature falls below this setpoint. Normal temperature control resumes on window closure. The Window sensor signal can also be a network input from another LONWORKS Bus device, so that no physical sensor is required at the receiving W7750 Controller.

SMOKE CONTROLThe Excel 10 W7750 Controller supports three smoke-related control strategies:

1. Emergency Shutdown (all outputs off).2. Depressurize (fan on, outdoor air damper closed).3. Pressurize (fan on, outdoor air damper open).

The controller is placed in one of these three control states whenever the W7750 mode becomes SMOKE_EMERGENCY, which can be initiated via a network command (DestEmergCmd) or from a local (physically connected) smoke detector digital input. When in SMOKE_EMERGENCY mode, the W7750 Controller uses the control strategy found in SmkCtlMode (one of the three listed above), and the normal temperature control function is disabled. If a W7750 local smoke detector trips, the SrcEmerg network variable (for other LONWORKS Bus devices to receive) is set to the Emergency state.

DEMAND LIMIT CONTROL (DLC)When The LONWORKS Bus network receives a high-electrical-demand signal, the controller applies a DlcBumpTemp amount to the current actual space temperature setpoint value. The setpoint is always adjusted in the energy-saving direction. This means that if the W7750 Controller is in Cooling mode, the DLC offset bumps the control point up, and when in Heating mode, bumps the control point down.

OCC setpoint

UN_OCC setpointOR

STANDBY setpoint

M10110

AUX HEATSETPOINT

HEAT PUMPSETPOINT(FOR COMPRESSORS)

RECOVERY TIME

OCCUPIED TIME

COOL RECOVERY RAMP RATE(DEGREES/HOUR)

MaxClRamp

MinClRamp

OaTempMinClRamp OaTempMaxClRamp

OUTDOOR AIRTEMPERATURE

M10111A

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

59 74-2958�2

DIRTY FILTER MONITORThe air filter in the air handler can be monitored by the W7750 and an alarm issued when the filter media needs replacement. The two methods of monitoring the filter are:

1. A differential pressure switch whose contacts are con-nected to a digital input on the W7750A or W7750B,C; and

2. A 2 to 10V differential pressure sensor wired to a current input on the W7750B,C. If the analog input sensor is used, its measured value 0 to 5 in. w.c. (0 to 1.25 kPa) is compared to a user-selectable setpoint (FltrPressStPt�valid range: 0 to 5 in. w.c. (0 to 1.25 kPa)), and the Dirty Filter alarm is issued when the pressure drop across the filter exceeds the setpoint.

START-UPSTART_UP_WAIT is the first mode after application restart or power-up. During START_UP_WAIT, the analog and digital inputs are being read for the first time, no control algorithms are active, and the physical outputs (fan and heat/cooling stages) are in the de-energized position. The node remains in

the START_UP_WAIT mode for a pseudo-random period (depending on neuron_id) between 12 and 22 seconds and then transitions to one of the operating modes, depending on the inputs that are read from the physical and network inputs. The pseudo random period prevents multiple controllers from simultaneously starting major electrical loads when power is restored to a building.

NOTES: After a controller download via LONSPEC�/Care, the delayed reset time is bypassed and the controller starts after a 40-second initialization.

Not all network inputs can be received during the START_UP_WAIT period because many network variables are updated at a slower rate; therefore some control decisions can be considered tempo-rarily inappropriate.

Temperature Control OperationsSee Fig. 49 for a diagram of a typical W7750 Unit.

Fig. 49. Schematic diagram for a typical W7750B Unit.

STAGED COOLING CONTROLThe Excel 10 W7750 Controller supports up to four stages of D/X cooling. As space temperature rises above the current

Cooling Setpoint, the controllers mode of operation is switched to the COOL mode. When in the COOL mode, all heating outputs are driven closed or off (with the exception

WINDOW CONTACT

OCCUPANCYSENSOR

M

OA TEMP

FILTER

FAN

COOLCOIL

HEATCOIL

DA TEMPRA TEMP

EXCEL 10W7750CVAHU

T7770 OR T7560A,BRETURNAIR

DISCHARGEAIR

OUTDOORAIR

CEILING

ROOF

- +

M17488

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 60

that occurs during IAQ Override Operation, see above), and the staged cooling outputs are enabled for use. When in the COOL mode, the PID cooling control algorithm compares the current space temperature to the EffectiveCoolSetPt, and calculates a PID error signal. This error signal causes the cooling stage outputs to be cycled as required to drive the space temperature back to the setpoint. Fig. 50 illustrates the

relationship between PID error and staged output activity. As the error signal increases and the space temperature is getting farther away from setpoint, or is remaining above setpoint as time elapses, additional stages of cooling are energized until, if PID error reaches 100 percent, all configured stages are on.

Fig. 50. Staged output control versus PID Error.

If economizer dampers are configured, and the outdoor air is suitable for free cooling, the economizer operates as the first stage of cooling. For example, if a controller was configured with two stages of mechanical cooling and an economizer, the application should be viewed in Fig. 50 as a three-stage system.

Setpoints for the PID gains allow for unit-by-unit adjustment of the control loop, if required; however, any change from the default values should be minimal.

The PID control algorithm used to control staged cooling is anticipator-driven, and is similar to the algorithm used in the T7300 commercial thermostat. All staging events are subject to a minimum interstage time delay, which is based on the cycles per hour user setting (CoolCycHr). The minimum interstage time delay ranges from 90 seconds (at 12 cycles per hour) to 8.5 minutes (at two cycles per hour), see Table 17. The user has the option to disable the minimum run timer (DisMinClTimer for cooling). If the minimum run timer is disabled, the interstage time delay is fixed at 20 seconds. The cycling rate is separately selectable for heating and cooling between 2 and 12 cycles per hour (cph).

Table 17. Interstage Minimum Times

STAGED HEATING CONTROLThe Excel 10 W7750B,C Controller supports up to four stages of heating. As space temperature falls below the current Cooling Setpoint, the controller mode of operation is switched to the HEAT mode. When in the HEAT mode, all cooling outputs are driven closed or off, and the staged heating outputs are enabled for use. When in the HEAT mode, the PID cooling control algorithm compares the current space temperature to the EffectiveHeatSetPt, and calculates a PID error signal. This error signal causes the heating stage

NO. STAGES

CONFIGURED

PID

ERROR

ONE STAGE

TWO STAGES

THREE STAGES

FOUR STAGES

0% 25% 33% 50% 66% 75% 100% > 100%

CYCLING

STAGE 1

CYCLING

STAGE 1 LOCKED ON

STAGE 2 CYCLING

STAGE 1

CYCLING

STAGE 1 LOCKED ON

STAGE 2 CYCLING

STAGE 1,2 LOCKED ON

STAGE 3 CYCLING

ALL STAGES

LOCKED ON

ALL STAGES

LOCKED ON

ALL STAGES

LOCKED ON

ALL STAGES

LOCKED ON

STAGE 1

CYCLING

STAGE 1

LOCKED ON

STAGE 2

CYCLING

STAGE 1,2

LOCKED ON

STAGE 3

CYCLING

STAGE 1,2,3

LOCKED ON

STAGE 4

CYCLING

M10112

Cycles/Hour Selection Minimum On/Off time (Min.)2 8.53 5.54 4.05 3.56 3.07 2.58 2.09 2.010 2.011 1.512 1.5

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

61 74-2958�2

outputs to be cycled, as required, to drive the space temperature back to the Setpoint. Fig. 50 illustrates the relationship between PID error and staged output activity.

As the error signal increases, the space temperature gets further away from the setpoint, or is remaining below the setpoint as time elapses, additional stages of heating are energized until, if PID error reaches 100 percent, all configured stages are on.

The PID control algorithm used to control staged heating is anticipator-driven, and is similar to the algorithm used in the T7300 commercial thermostat. All staging events are subject to a minimum interstage time delay, that is based on the cycles per hour user setting (HeatCycHr). The minimum interstage time delay ranges from 90 seconds (at 12 cycles per hour) to eight minutes (at two cycles per hour). See Table 17. The user has the option to disable the minimum run timer for heating (DisMinHtTimer). If the minimum run timer is disabled, the interstage time delay is fixed at 20 seconds. The cycling rate is separately selectable for heating and cooling between two and 12 cycles per hour (cph).

Setpoints for the PID gains allow for unit-by-unit adjustment of the control loop, if required; however, any change from the default values should be minimal.

CASCADE CONTROL OF MODULATING COOLING/HEATINGThe Excel 10 W7750 Controller supports modulating cooling and heating valves. These valves can be controlled directly from the space temperature (like the staged control) or, if the CascCtrl flag is set, they are modulated to maintain the discharge air temperature at its setpoint. The discharge air setpoint is calculated based on the space temperature deviation from the space setpoint. This is commonly called cascade control. In the W7750 Controller, cascade control is available for use with PWM (W7750B,C only) and Series 60 modulating heating and cooling, but not for use with staged heating/cooling.

Setpoints for the PID gains and for the control band allow for unit-by-unit adjustment of the control loops, if required; however, any change from the default values should be minimal. Also, the W7750 Controller uses an adaptive algorithm (patent pending) to continuously assess the validity of the calculated discharge setpoint, and adjust it, as needed, to ensure precise, accurate control.

SERIES 60 MODULATING CONTROLSeries 60 Control is also commonly referred to as Floating Control. The Excel 10 W7750A,B,C Controllers can drive Series 60 type actuators (economizer only for W7750A) to control a modulating cooling valve, a heating valve, and economizer dampers. When floating control is used, the full-stroke motor drive time of the actuator must be entered into the configuration parameter CoolMtrSpd (for cooling), HeatMtrSpd (for heating), or EconMtrSpd (for the economizer dampers).

PULSE WIDTH MODULATING (PWM) CONTROLThe Excel 10 W7750B,C Controllers can drive a PWM-type actuator to control a modulating cooling valve, a heating valve, and economizer dampers. PWM control positions the actuator based on the length, in seconds, of the pulse from the digital output. The controller outputs a pulse whose length consists of two parts, a minimum and a maximum. The minimum pulse time represents the analog value of zero

percent (also indicates a signal presence) and the maximum pulse length that represents an analog value of 100 percent. If the analog value is greater than zero percent, an additional time is added to the minimum pulse time. The length of time added is directly proportional to the magnitude of the analog value. If PWM control is used, the configuration parameters for the PWM operation must be specified. These are PwmPeriod, PwmZeroScale, and PwmFullScale. These three parameters are shared by all configured PWM outputs; this means the heating, cooling, and economizer actuators must be configured to accept the same style of PWM signal.

Example: To find the pulse width of a valve actuator (for example stroke mid position - 50 percent) with the PwmZeroScale = 0.1 seconds, PwmFullScale = 25.5 seconds, and the PwmPeriod = 25.6 seconds. There are 256 increments available, so the number of increments required for 50 percent would be (0.5 X 256) or 128. The time for each increment for this industry standard pulse time is 0.1 seconds. The pulse width is the minimum time (0.1 second) + the number of increments (128 times the (0.1 second) plus 0. 1) = 12.9 seconds. The W7750B,C Controllers would command the valve output on for 12.9 seconds for the PwmPeriod of 25.6 seconds to maintain the valve position at 50 percent.

OUTDOOR AIR LOCKOUT OF HEATING/COOLINGA mechanism is provided in the W7750 to disable the heating equipment if the outdoor air temperature rises above the OaTempHtLkOut setpoint. Similarly, the cooling equipment is disabled if the outdoor air temperature falls below the OaTempClLkOut setpoint. The algorithm supplies a fixed 2°F (1.1°C) hysteresis with the lock-out control to prevent short cycling of the equipment.

ECONOMIZER DAMPER CONTROLA mixed-air economizer damper package can be controlled to assist mechanical cooling in maintaining the discharge air at setpoint. Therefore, if modulating economizer damper control is desired, a discharge air temperature sensor is required. If the outdoor air is not currently suitable for cooling use (see the Economizer Enable/Disable Control section), the outdoor air damper is held at the adjustable minimum position (EconMinPos) for ventilation purposes.

Because the outdoor air can be used to supplement mechanical cooling, the economizer operates as if it were the first stage of cooling. So, if the outdoor air is suitable for cooling use, the mechanical cooling (either staged or modulating) is held off until the economizer has reached its fully open position. Then, if the discharge temperature continues to be above setpoint, the mechanical cooling is allowed to come on. If the outdoor air is not suitable for cooling use, the economizer is set to its minimum position, and mechanical cooling is allowed to come on immediately.

When the controller is in the Heat mode, the economizer is held at the minimum position setting (EconMinPos). The minimum position setting is only used during Occupied mode operation. When in Standby or Unoccupied modes, the outdoor air dampers are allowed to fully close if there is no call for cooling, or if the outside air is not suitable for cooling use.

INDOOR AIR QUALITY (IAQ) OVERRIDEThe Excel 10 W7750 Controller supports an IAQ override feature that upon detection of poor air quality in the space, allows the economizer dampers to be opened above the standard minimum position setting to a value set in

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 62

EconIAQPos. Two different methods of detecting poor air quality are supported, The first is by using an IAQ switch device connected to a digital input on the W7750 Controller, where a contact closure indicates poor air quality and initiates the IAQ override mode. The second, which is only available on the W7750B,C is through an analog input that connects to a CO2 Sensor (0 to 10V), such as the C7232A,B or C7632A,B. The measured value of CO2 from this sensor (0 to 2000 ppm) is compared to the setpoint IAQSetpt. When the CO2 level is higher than the setpoint (800 PPM), the IAQ override is initiated. The IAQSetpt hysteresis is 50 PPM, IAQ override is deactivated at a CO2 level less than 750 PPM.

When the W7750 Controller is in the COOL mode during an IAQ override, it is possible for the heating outputs to be activated. This can occur if the outdoor air temperature is cold enough to cause the discharge air temperature to drop below the DaTempLoLim setpoint when the dampers open to the EconIAQPos position, and the IaqUseHeat flag is set. If this situation occurs, the heating is controlled to maintain the discharge air temperature at 1°F (0.65°C) above the DaTempLoLim setpoint.

FREEZE STATUpon receiving a contact closure, the W7750 control algorithm will close the outdoor air damper and open the hot water and chilled water valves (if available) to the full open position as a safety precaution. If manual-reset operation is desired, the Freeze Stat device must provide the physical pushbutton, which the operator presses, to reset the system after a freeze condition has occurred.

DISCHARGE AIR LOW LIMIT CONTROLIf the discharge air temperature falls below the adjustable discharge air low limit setpoint (DaTempLoLim), an alarm is issued, and the outdoor air damper is driven below the minimum position setting until the discharge temperature is up to the low limit. If necessary, the damper can go completely closed even during Occupied mode operation. As the discharge temperature warms up, the economizer modulates open until the minimum position setting is reached. At this point, the low limit alarm is cleared.

ECONOMIZER ENABLE/DISABLE CONTROLThe W7750 Controller has inputs to determine if the outdoor air is suitable to augment cooling. The economizer dampers can be enabled/disabled for using outdoor air as the first stage of cooling based on one of ten allowable strategies:

1. Digital Input Enable/Disable�contact closure enables economizer.

2. Outdoor Temperature�when the outdoor temperature is less than OaEconEnTemp, then the outdoor air is suitable to augment cooling.

3. Outdoor Enthalpy, Type A�when the outdoor enthalpy meets the W7212 type A requirements, the outdoor air is suitable to augment cooling. See Fig. 57 and 58.

4. Outdoor Enthalpy, Type B�when the outdoor enthalpy meets the W7212 type B requirements, the outdoor air is suitable to augment cooling. See Fig. 57 and 58.

5. Outdoor Enthalpy, Type C�when the outdoor enthalpy meets the W7212 type C requirements, the outdoor air is suitable to augment cooling. See Fig. 57 and 58.

6. Outdoor Enthalpy, Type D�when the outdoor enthalpy meets the W7212 type D requirements, the outdoor air is suitable to augment cooling. See Fig. 57 and 58.

7. Differential Temperature�the difference between outdoor temperature and return air temperature is compared to DiffEconEnTemp to determine whether outdoor air or return air is more suitable for use to augment mechanical cooling.

8. Single Calculated Enthalpy�the calculated outdoor enthalpy in btu/lb is compared to the enthalpy setpoint (OaEnthEn) in btu/lb, and the outdoor temperature is compared to the outdoor temperature limit setpoint (OaEconEnTemp) for a high limit. The compared difference determines whether outdoor air is suitable for use to augment mechanical cooling.

9. Differential Enthalpy, Either Sensed or Calculated�the difference between outdoor enthalpy and return air enthalpy determines whether outdoor air or return air is more suitable to augment mechanical cooling. When enthalpy sensors are configured, they are used for comparing enthalpy. If no enthalpy sensors are available, then enthalpy is calculated using outdoor and return air humidity and temperature sensors. The switching differential is fixed at 1.0 mA for enthalpy sensors, and 0.25 btu/lb for calculated enthalpy.

NOTE: If no return temperature sensor is configured, space temperature is used to calculate return air enthalpy.

10. Network Enabled�the network input DestEconEnable controls the enabling and disabling of the economizer. When using the network input, select Econo Enable Type: No Economizer in E-Vision. The network input has priority over the other nine economizer control selections.

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

63 74-2958�2

Appendix C: Complete List of Excel 10 W7750 Controller User AddressesSee Table 18 for W7750 Controller User Address table numbers and point types.

The User Address Index following Table 18 lists the User Addresses alphabetically and gives the page number where the Address is located in each Table Number/Point Type.

An alphabetical list of Mappable User Addresses and Table Numbers follows Table 18. Following this is an alphabetical list of Failure Detect User Addresses and Table Numbers.

Table 18. Excel 10 W7750 Controller User Address Point Types.

User Address Indexes

NOTE: Following tables arranged in alphabetical order, left to right, then top to bottom.

INPUT OUTPUT POINTS (SEE TABLE 20)

CONTROL PARAMETERS (SEE TABLE 21)

ENERGY MANAGEMENT POINTS (SEE TABLE 22)

CALIBRATION POINTS (SEE TABLE 24)

Table Number Point TypesTable 20 Input/OutputTable 21 Control ParametersTable 22 Energy Management PointsTable 23 Status PointsTable 24 Calibration PointsTable 25 Configuration ParametersTable 26 LONMARK/Open System PointsTable 27 Direct Access and Special Manual PointsTable 28 Data Share Points

Address (Page) Address (Page) Address (Page)CO2Sensr (71) CORMode (67) DaTempSensr (70)EconEnSw (72) FltrPressSensr (71) IaqOvrSw (72)Model (72) ModelSw (73) MonitorSensr (71)MonitorSw (73) OaEnthSensr (71) OaHumSensr (70)OaTempSensr (70) OccSensr (72) OvrdSw (72)RaEnthSensr (70) RaHumSensr (70) RaTempSensr (70)RmTempSensr (70) RmtStptPot (70) StatusAirFlow (72)StatusDI1 (72) StatusDI2 (72) StatusDI3 (72)StatusDI4 (72) StatusDO1 (71) StatusDO2 (71)StatusDO5 (71) StatusDO3 (71) StatusDO4 (71)StatusDO6 (71) StatusDO7 (71) StatusDO8 (71)SmokeMonSw (72) TimeClkSw (72) WindowSw (73)

Address (Page) Address (Page)BypTime (77) DaTempClCtrlBd (77)DaTempEcCtrlBd (77) DaTempHiLim (74)DaTempHtCtrlBd (77) DaTempLoLim (74)DiffEconEnTemp (76) DlcBumpTemp (74)EconIAQPos (76) EconMinPos (76)FltrPressStPt (77) GainCoolDer (77)GainCoolInt (77) GainCoolProp (77)GainHeatDer (77) GainHeatInt (77)GainHeatProp (77) IAQSetpt (76)MaxClRamp (75) MinClRamp (75)MaxHtRamp (74) MinHtRamp (74)OaEconEnTemp (76) OaEnthEn (76)OaTempClLkOut (75) OaTempHtLkOut (74)OaTempMaxClRp (75) OaTempMinClRp (76)OaTempMaxHtRp (75) OaTempMinHtRp (75)PwmFullScale (76) PwmPeriod (76)PwmZeroScale (76) StptKnobHiLim (77)StptKnobLowLim (77)

Address (Page) Address (Page)DestBypass (78) DestDlcShed (78)DestFree1 (79) DestFree2 (79)DestTimeClk (80) DestWSHPEnable (79)DestSchedOcc (78) SrcBypCt (78)SrcBypass (78) SrcTimeClk (80)SrcTimeClkCt (80) TodEventNext (78)Tuncos (78)

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 64

STATUS POINTS (SEE TABLE 23)

CONFIGURATION PARAMETERS (SEE TABLE 25)

LONMARK/OPEN SYSTEM POINTS (SEE TABLE 26)

DIRECT ACCESS AND SPECIAL MANUAL POINTS (SEE TABLE 27)

DATA SHARE POINTS (SEE TABLE 28)

Address (Page) Address (Page) Address (Page)AlarmLog1 (83) BypTimer (88) CO2Sens (89)CoolPos (90) CoolStgsOn (86) DaSetpt (89)DaTemp (89) DlcShed (86) EconPos (90)FilterPress (89) Free1Stat (86) Free2Stat (86)HeatPos (90) HeatStgsOn (86) MonitorSens (90)MonitorSw (87) NetConfig (93) OaEnth (89)OaEnthCalc (85) OaHum (89) OaTemp (89)OccStatOut (86) RaEnth (89) RaEnthCalc (85)RaHum (89) RaTemp (89) RmTemp (88)RmTempActSpt (88) SaFan (86) SaFanStatus (85)ShutDown (87) SrcEmerg (81) SrcTimeClk (80)StatFreezeStat (87) StatusAlmTyp (81) StatusEconEn (85)StatusEconOut (86) StatusError (90) StatusFilter (87)StatusIaqOvr (87) StatusManOcc (85) StatusMode (84)StatusOcc (84) StatusOcySen (85) StatusOvrd (84)StatusSched (84) StatusSmoke (87) StatusWndw (87)TimeClckOcc (84) WSHPEnable (88)

Address (Page) Address (Page)CascCntrl (96) CoolCycHr (94)CoolMtrSpd (95) DisMinClTime (96)DisMinHtTime (96) EconMode (94)EconMtrSpd (95) FanFailTime (95)FanMode (94) FanOnHtMode (95)FanRunOnCool (94) FanRunOnHeat (94)HeatCycHr (94) HeatMtrSpd (95)IaqUseHeat (96) OvrdPriority (97)OvrdType (97) RmTempCal (95)SetPtKnob (97) SmkCtlMode (94)TempOffstCal1 (95) TempOffstCal2 (95)UseRaTempCtl (96) UseWallModStpt (97)VoltOffstCal1 (95) VoltOffstCal2 (95)

Address (Page) Address (Page)CoolOccSpt (98) CoolUnoccSpt (98)CoolStbySpt (98) DestEconEnable (104)DestEmergCmd (101) DestHvacMode (99)DestManOcc (99) DestOaHum (100)DestOaTemp (100) DestOccSensor (103)DestRmTemp (100) DestRmTempSpt (99)DestSptOffset (99) DestWndw (104)HeatOccSpt (98) HeatStbySpt (98)HeatUnoccSpt (98) SrcEconEnable (105)SrcEconEnCt (105) SrcOaHum (100)SrcOaTemp (100) SrcOccSensor (103)SrcRmTemp (100) SrcRmTempActSpt (100)SrcUnitStatus (101) SrcWndw (104)SrcWndwCt (104)

Address (Page) Address (Page) Address (Page)DestManMode (106) TestAuxEcon (107) TestAuxHt1 (107)TestAuxHt2 (107) TestAuxHt3 (107) TestAuxHt4 (107)TestEconPos (106) TestFree1 (107) TestFree2 (107)TestHCPos (106) TestHtClMode (107) TestHtClStg1 (107)TestHtClStg2 (107) TestHtClStg3 (107) TestHtClStg4 (107)TestMode (106) TestOccStat (107) TestSaFan (107)

Address (Page) Address (Page) Address (Page)DestIaqOvrd (108) DestOaEnth (108) SrcIaqOvr (108)SrcIaqOvrCt (108) SrcMonSw (108) SrcMonSwCt (108)SrcOaEnth (108)

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

65 74-2958�2

Mappable User Addresses and Table Number

Failure Detect User Addresses and Table Number Table 19 lists the applicable Engineering Units for the analog points found in the W7750.

User Address (Table) User Address (Table) User Address (Table) User Address (Table) User Address (Table)BypTime (21) BypTimer (23) CascCntrl (25) CO2Sen (23) CoolCycHr (25)CoolMtrSpd (25) CoolOccSpt (26) CoolPos (23) CoolStbySpt (26) CoolStgsOn (23)CoolUnoccSpt (26) DaSetpt (23) DaTemp (23) DaTempClCtrlBd (21) DaTempEcCtrlBd (21)DaTempHiLim (21) DaTempHtCtrlBd (21) DaTempLoLim (21) DestDlcShed (22) DestEmergCmd (26)DestHvacMode (26) DestManMode (27) DestSchedOcc (22) DiffEconEnTemp (21) DisMinHtTime (25)DisMinClTime (25) DlcBumpTemp (21) EconIAQPos (21) EconMinPos (21) EconMtrSpd (25)EconPos (23) EconMode (25) FanFailTime (25) FanMode (25) FanOnHtMode (25)FanRunOnCool (25) FanRunOnHeat (25) FilterPress (23) FltrPressStPt (21) Free1Stat (23)Free2Stat (23) GainCoolDer (21) GainCoolInt (21) GainCoolProp (21) GainHeatDer (21)GainHeatInt (21) GainHeatProp (21) HeatCycHr (25) HeatMtrSpd (25) HeatOccSpt (26)HeatPos (23) HeatStbySpt (26) HeatStgsOn (23) HeatUnoccSpt (26) IAQSetpt (21)IaqUseHeat (25) MaxClRamp (21) MinClRamp (21) MaxHtRamp (21) MinHtRamp (21)MonitorSens (23) MonitorSw (23) OaEconEnTemp (21) OaEnth (23) OaEnthCalc (23)OaEnthEn (21) OaHum (23) OaTemp (23) OaTempClLkOut (21) OaTempHtLkOut (21)OaTempMaxClRp (21) OaTempMinClRp (21) OaTempMaxHtRp (21) OaTempMinHtRp (21) OccStatOut (23)OvrdPriority (25) OvrdType (25) PwmFullScale (21) PwmPeriod (21) PwmZeroScale (21)RaEnth (23) RaEnthCalc (23) RaHum (23) RaTemp (23) RmTempActSpt (23)RmTempCal (25) RmtStptPot (20) SaFan (23) SaFanStatus (23) SetPtKnob (25)ShutDown (23) SmkCtlMode (25) StatFreezeStat (23) StatusAlmTyp (23) StatusEconEn (23)StatusEconOut (23) StatusFilter (23) StatusIaqOvr (23) StatusManOcc (23) StatusMode (23)StatusOcc (23) StatusOcySen (23) StatusOvrd (23) StatusSched (23) StatusSmoke (23)StatusWndw (23) StptKnobHiLim (21) StptKnobLowLim (21) TimeClckOcc (23) UseRaTempCtl (25)UseWallModStpt (25) WSHPEnable (23)

User Address (Table) User Address (Table)DestBypass 22 DestDlcShed 22DestEconEnable 26 DestFree1 22DestFree2 22 DestHvacMode 26DestIaqOvrd 28 DestOaEnth 28DestOaHum 26 DestOaTemp 26DestOccSensor 26 DestRmTemp 26DestSchedOcc 22 DestSptOffset 26DestTimeClk 22 DestWndw 26DestWSHPEnable 22

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 66

Table 19. Engineering Units For Analog Points.

All of the NvName values that are stored in EEPROM memory have a prefix of nci.

NOTE: These parameters are stored in EEPROM and are limited to 10,000 writes. Do NOT use them as outputs from Control Strategies, Time Programs, or Switching Tables. If these points are changed more than 10,000 times, irreversible hardware failure results

Tables 20 through 28 provide point attributes as follows:

EngineeringUnits� This field indicates the point valid range and

displayed Engineering Unit. For digital points, the valid states and the corresponding enumerated values are shown.

Default� The value or state of the point on controller start-up.

LONSPEC�/Care(M) Monitor� These points are viewable within the Controller

Monitoring on-line screen.(P) Parameter�These points refer to control parameters

adjustable in the Application Selection dialog boxes.

(S) Schematic�These points appear in Care monitor mode graphics.

Shareable� These points can be set up for data sharing in Command Multiple Points, Read Multiple Points, or Refer Excel 10 Points as either a data source or a destination.

Mappable� These points can be converted into a C-Bus point (XL5000) used by C-Bus devices. A mappable point has a one-to-one relationship with a C-Bus User Address.

Direct Access� These points are accessible through the

Subsystem Points mechanism in LONSPEC�/LONSTATION� or XBS - XL5000.

HardwareConfig.� These are points that involve controller I/O

configuration. Any change to Hardware Config. points causes the W7750 to perform an application reset; therefore, these points can only be modified off-line.

ManualConfig.� These points are used to set the controller

outputs when in manual mode. The W7750 is placed in manual mode through a menu selection in the LONSPEC� or Care Controller Monitor screen.

Test� These points can be controlled in LONSPEC� or Care test mode that is used for field checkout/ debuging.

Failure Detect Input Point� These points need an update periodically or a

communication alarm is generated. The failure detect mechanism is only active when the NV is bound (bindings are configured using Refer Excel 10 points). The time between the updates is adjustable.

Non-Failure Detect Input Point� These points (which are NVs that are bound or

unbound) do not check for an update periodically and do not generate an alarm.

NOTES:1. Mapped points can be viewed and changed, if

needed, through LONSPEC� or on the XI581, XI582 and XI584 C-Bus devices and on an XBS central (XL5000).

2. All Excel 10 points, mappable and calibration, configuration and internal data sharing points, can be viewed and changed, as allowed, via Direct Access (DA) mode in the LONSPEC�/LONSTA-TION� or XBS subsystem menu or via XI584.

English Units (Inch-Pound) Standard International Units (SI)Measured Item Description Abbreviation Description Abbreviation

Temperature Degrees Fahrenheit F Degrees Celsius CRelative Temperature Delta Degrees Fahrenheit DDF Degrees Kelvin KRelative Humidity Percent % Percent %Air Flow Cubic Feet per Minute CFM Meters Cubed per Hour m3hCO2 Concentration Parts Per Million PPM Parts Per Million PPMEnthalpy British Thermal Units per Pound of Air btu/lb kiloJoules/kilogram kj/kgDifferential Pressure Inches of Water Column in. w.c. kiloPascal kPa

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

67 74-2958�2

Tabl

e 20

. Inp

ut/O

utpu

t Poi

nts.

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

tsCO

RMod

enc

iIoSe

lect

CorO

nMod

eCO

R_ON

_HEA

TCO

R_ON

_COO

L0 1

COR_

ON_C

OOL

PX

CorO

nMod

e spe

cifies

the m

ode w

hen t

he C

hang

e Ove

r Rela

y (CO

R) is

en

ergiz

ed.

nciIo

Selec

tRe

sistiv

eIn[0]

DISC

HARG

E_TE

MP_P

T300

0OU

TDOO

R_TE

MP_P

T300

0RE

TURN

_TEM

P_PT

3000

DISC

HARG

E_TE

MP_2

0KNT

CRE

TURN

_TEM

P_20

KNTC

UNUS

ED_R

AI

0 1 2 3 4 255

UNUS

ED_R

AIX

Resis

tiveIn

[0] sp

ecifie

s whic

h log

ical s

enso

r is as

signe

d to e

ach p

hysic

al an

alog i

nput

sens

or ch

anne

l acc

ordin

g to t

he en

umer

ated l

ist th

at is

show

n in

the E

ngine

ering

Unit

s/Stat

es co

lumn.

Resis

tiveIn

[0] is

the o

nly in

put

avail

able

in the

W77

50A

contr

oller.

nciIo

Selec

tRe

sistiv

eIn[1]

DISC

HARG

E_TE

MP_P

T300

0OU

TDOO

R_TE

MP_P

T300

0RE

TURN

_TEM

P_PT

3000

DISC

HARG

E_TE

MP_2

0KNT

CRE

TURN

_TEM

P_20

KNTC

UNUS

ED_R

AI

0 1 2 3 4 255

UNUS

ED_R

AIX

Resis

tiveIn

[1] sp

ecifie

s whic

h log

ical s

enso

r is as

signe

d to e

ach p

hysic

al an

alog i

nput

sens

or ch

anne

l acc

ordin

g to t

he en

umer

ated l

ist th

at is

show

n in

the E

ngine

ering

Unit

s/Stat

es co

lumn.

Resis

tiveIn

[0] is

the o

nly in

put

avail

able

in the

W77

50A

contr

oller.

nciIo

Selec

tVo

ltage

In[0]

RTN_

HUM_

C760

0CRE

TURN

_ENT

HALP

YOD

_HUM

_C76

00C

OUTD

OOR_

ENTH

ALPY

FILT

ER_S

TATI

C_PR

ESS_

DIFF

SPAC

E_CO

2MO

NITO

R_SE

NSOR

1RT

N_HU

M_C7

600B

OD_H

UM_C

7600

BUN

USED

_VAI

0 1 2 3 4 5 6 7 8 255

UNUS

ED_V

AIX

Volta

geIn[

0] sp

ecifie

s whic

h log

ical s

enso

r is as

signe

d to e

ach p

hysic

al an

alog i

nput

sens

or ch

anne

l acc

ordin

g to t

he en

umer

ated l

ist th

at is

show

n in

the E

ngine

ering

Unit

s/Stat

es co

lumn.

(Volt

age i

nputs

are n

ot av

ailab

le in

the W

7750

A co

ntroll

er.)

nciIo

Selec

tVo

ltage

In[1]

RTN_

HUM_

C760

0CRE

TURN

_ENT

HALP

YOD

_HUM

_C76

00C

OUTD

OOR_

ENTH

ALPY

FILT

ER_S

TATI

C_PR

ESS_

DIFF

SPAC

E_CO

2MO

NITO

R_SE

NSOR

1RT

N_HU

M_C7

600B

OD_H

UM_C

7600

BUN

USED

_VAI

0 1 2 3 4 5 6 7 8 255

UNUS

ED_V

AIX

Volta

geIn[

1] sp

ecifie

s whic

h log

ical s

enso

r is as

signe

d to e

ach p

hysic

al an

alog i

nput

sens

or ch

anne

l acc

ordin

g to t

he en

umer

ated l

ist th

at is

show

n in

the E

ngine

ering

Unit

s/Stat

es co

lumn.

(Volt

age i

nputs

are n

ot av

ailab

le in

the W

7750

A co

ntroll

er.)

nciIo

Selec

tDi

gitalI

n[0]

OCC_

SENS

OROC

C_TI

ME_C

LOCK

PROO

F_AI

R_FL

OWEC

ON_E

NABL

EIA

Q_OV

ERRI

DESM

OKE_

MONI

TOR

DIRT

Y_FI

LTER

SHUT

_DOW

NW

INDO

W_O

PEN

MONI

TOR

SCHE

D_MA

STER

FREE

ZEST

ATUN

USED

_DI

2 3 4 5 6 7 8 9 10 11 12 13 255

OCC_

TIME

_CLO

CK_IN

XDi

gitalI

n[0] s

pecif

ies w

hich l

ogica

l swi

tch ty

pe is

conn

ected

to th

e flex

ible

digita

l inpu

t swi

tch ch

anne

l acc

ordin

g to t

he en

umer

ated l

ist th

at is

show

n in

the E

ngine

ering

Unit

s/Stat

es co

lumn.

Digit

alIn[0

] and

Digi

talIn[

1] ar

e the

on

ly inp

uts av

ailab

le in

the W

7750

A co

ntroll

er. T

he co

ntroll

er is

confi

gure

d at

the fa

ctory

with

this u

ser a

ddre

ss co

nfigu

red t

o OCC

_TIM

E_CL

OCK_

IN.

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 68

nciIo

Selec

tDi

gitalI

n[1]

OCC_

SENS

OROC

C_TI

ME_C

LOCK

PROO

F_AI

R_FL

OWEC

ON_E

NABL

EIA

Q_OV

ERRI

DESM

OKE_

MONI

TOR

DIRT

Y_FI

LTER

SHUT

_DOW

NW

INDO

W_O

PEN

MONI

TORS

CHED

_MAS

TER

FREE

ZE_S

TAT_

B&C_

ONLY

UNUS

ED_D

I

2 3 4 5 6 7 8 9 10 11 12 13 255

SHCE

D_MA

STER

_INX

Digit

alIn[1

] spe

cifies

whic

h log

ical s

witch

type

is co

nnec

ted to

the f

lexibl

e dig

ital in

put s

witch

chan

nel a

ccor

ding t

o the

enum

erate

d list

that

is sh

own i

n the

Eng

ineer

ing U

nits/S

tates

colum

n. Di

gitalI

n[0] a

nd D

igital

In[1]

are t

he

only

inputs

avail

able

in the

W77

50A

contr

oller.

The

contr

oller

is co

nfigu

red

at the

facto

ry wi

th thi

s use

r add

ress

confi

gure

d to S

CHED

_MAS

TER_

IN.

nciIo

Selec

tDi

gitalI

n[2]

OCC_

SENS

OROC

C_TI

ME_C

LOCK

PROO

F_AI

R_FL

OWEC

ON_E

NABL

EIA

Q_OV

ERRI

DESM

OKE_

MONI

TOR

DIRT

Y_FI

LTER

SHUT

_DOW

NW

INDO

W_O

PEN

MONI

TOR

SCHE

D_MA

STER

UNUS

ED_D

I

2 3 4 5 6 7 8 9 10 11 12 255

UNUS

ED_D

IX

Digit

alIn[2

] spe

cifies

whic

h log

ical s

witch

type

is co

nnec

ted to

the f

lexibl

e dig

ital in

put s

witch

chan

nel a

ccor

ding t

o the

enum

erate

d list

that

is sh

own i

n the

Eng

ineer

ing U

nits/S

tates

colum

n. Di

gitalI

n[0] a

nd D

igital

In[1]

are t

he

only

inputs

avail

able

in the

W77

50A

contr

oller.

Tabl

e 20

. Inp

ut/O

utpu

t Poi

nts.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

69 74-2958�2

nciIo

Selec

tDi

gitalO

ut[0]

COOL

_STA

GE_1

COOL

_STA

GE_2

COOL

_STA

GE_3

COOL

_STA

GE_4

HEAT

_STA

GE_1

HEAT

_STA

GE_2

HEAT

_STA

GE_3

HEAT

_STA

GE_4

CHAN

GE_O

VER_

RELA

YFA

N_OU

TAU

X_EC

ONOC

CUPA

NCY_

STAT

USEC

ON_O

PEN

ECON

_CLO

SECO

OL_O

PEN

COOL

_CLO

SEHE

AT_O

PEN

HEAT

_CLO

SEHE

AT_C

OOL_

STAG

E_1

HEAT

_COO

L_ST

AGE_

2HE

AT_C

OOL_

STAG

E_3

HEAT

_COO

L_ST

AGE_

4FR

EE1_

DEHU

MIDI

FYFR

EE1

FREE

2FR

EE1_

PULS

E_ON

FREE

1_PU

LSE_

OFF

ECON

_PW

MHE

AT_P

WM

COOL

_PW

MFR

EE1_

REV_

OUT

FREE

2_RE

V_OU

TEC

ON_P

WM_

AO_R

EV_O

UTHE

AT_P

WM_

AO_R

EV_O

UTCO

OL_P

WM_

AO_R

EV_O

UTUN

USED

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 24 25 26 27 28 29 30 31 57 58 61 62 63 255

NETW

ORK

DO(F

REE1

)(V

alue o

f Stat

e is 2

5)X

Digit

alOut[

0] sp

ecifie

s whic

h log

ical d

igital

outpu

t func

tion i

s ass

igned

to th

e dig

ital p

hysic

al ou

tput a

ccor

ding t

o the

enum

erate

d list

that

is sh

own i

n the

En

ginee

ring U

nits/S

tates

colum

n. Th

e W77

50 C

ontro

llers

are c

onfig

ured

at

the fa

ctory

with

the en

umer

ated v

alue i

n the

Defa

ult co

lumn.

Only

Digit

alOut[

0] thr

ough

Digi

talOu

t[5] a

re av

ailab

le in

the W

7750

A mo

del

which

can c

onfig

ure s

taged

outpu

ts. T

he W

7750

A Co

ntroll

er ca

n driv

e Se

ries 6

0 Floa

ting C

ontro

l to m

odula

te co

oling

valve

s, he

ating

valve

s and

ec

onom

izers.

(No P

WM

outpu

ts ar

e allo

wed i

n the

W77

50A

mode

l.) Th

e co

ntroll

er is

confi

gure

d at th

e fac

tory w

ith th

e enu

mera

ted va

lue in

the

Defau

lt colu

mn. T

he ei

ght o

utputs

on th

e W77

50B

are a

ll digi

tal ou

tputs.

Th

e eigh

t outp

uts on

the W

7750

C co

nsist

of fiv

e digi

tal an

d thr

ee an

alog

outpu

ts.

nciIo

Selec

tDi

gitalO

ut[1]

See D

igital

Out[0

] enu

mera

ted

value

s1-

31,25

5FA

N_OU

T(V

alue o

f Stat

e is 1

0)X

See D

igital

Out[0

] for e

nume

rated

name

s. Th

e W77

50 C

ontro

llers

are

confi

gure

d at th

e fac

tory w

ith th

e enu

mera

ted va

lue in

the D

efault

colum

n.nc

iIoSe

lect

Digit

alOut[

2]Se

e Digi

talOu

t[0] e

nume

rated

va

lues

1-31

,255

COOL

_STA

GE_2

(Valu

e of S

tate i

s 2)

XSe

e Digi

talOu

t[0] fo

r enu

mera

ted na

mes.

The W

7750

Con

trolle

rs ar

e co

nfigu

red a

t the f

actor

y with

the e

nume

rated

value

in th

e Defa

ult co

lumn.

nciIo

Selec

tDi

gitalO

ut[3]

See D

igital

Out[0

] enu

mera

ted

value

s1-

31,25

5HE

AT_S

TAGE

_1(V

alue o

f Stat

e is 1

)X

See D

igital

Out[0

] for e

nume

rated

name

s. Th

e W77

50 C

ontro

llers

are

confi

gure

d at th

e fac

tory w

ith th

e enu

mera

ted va

lue in

the D

efault

colum

n.nc

iIoSe

lect

Digit

alOut[

4]Se

e Digi

talOu

t[0] e

nume

rated

va

lues

1-31

,255

HEAT

_STA

GE_2

(Valu

e of S

tate i

s 3)

XSe

e Digi

talOu

t[0] fo

r enu

mera

ted na

mes.

The W

7750

Con

trolle

rs ar

e co

nfigu

red a

t the f

actor

y with

the e

nume

rated

value

in th

e Defa

ult co

lumn.

nciIo

Selec

tDi

gitalO

ut[5]

See D

igital

Out[0

] enu

mera

ted

value

s1-

31,25

5HE

AT_S

TAGE

_1(V

alue o

f Stat

e is 5

)X

See D

igital

Out[0

] for e

nume

rated

name

s. Th

e W77

50 C

ontro

llers

are

confi

gure

d at th

e fac

tory w

ith th

e enu

mera

ted va

lue in

the D

efault

colum

n.nc

iIoSe

lect

Digit

alOut[

6]Se

e Digi

talOu

t[0] e

nume

rated

va

lues

1-31

,255

UNUS

ED(V

alue o

f Stat

e is 2

55)

XSe

e Digi

talOu

t[0] fo

r enu

mera

ted na

mes.

The W

7750

Con

trolle

rs ar

e co

nfigu

red a

t the f

actor

y with

the e

nume

rated

value

in th

e Defa

ult co

lumn.

Tabl

e 20

. Inp

ut/O

utpu

t Poi

nts.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 70

nciIo

Selec

tDi

gitalO

ut[7]

See D

igital

Out[0

] enu

mera

ted

value

s1-

31,25

5UN

USED

(Valu

e of S

tate i

s 255

)X

See D

igital

Out[0

] for e

nume

rated

name

s. Th

e W77

50 C

ontro

llers

are

confi

gure

d at th

e fac

tory w

ith th

e enu

mera

ted va

lue in

the D

efault

colum

n.nc

iIoSe

lect

HtPu

mpCO

NVHP

0 1CO

NVP

XHt

Pump

spec

ifies t

he ty

pe of

equip

ment

being

contr

olled

. Whe

n HtP

ump i

s 0 (

CONV

), the

node

is co

ntroll

ing co

nven

tiona

l gas

or el

ectric

heat.

Whe

n Ht

Pump

is 1

(HP)

, the n

ode i

s con

trollin

g a he

at pu

mp.

nciIo

Selec

tFif

tySixt

yHz

SIXT

YFIFT

Y01

SIXT

YP

XFif

tySixt

yHz s

pecif

ies th

e fre

quen

cy of

the m

ain po

wer in

put fo

r the

co

ntroll

er. C

orre

ctly s

electi

ng th

e Fifty

Sixty

Hz de

creas

es th

e nois

e pick

ed

up by

analo

g swi

tch w

iring f

rom

the po

wer m

ains.

Whe

n Fifty

Sixty

Hz is

0 (S

IXTY

is th

e defa

ult),

the m

ains f

requ

ency

is si

xty H

z and

whe

n Fif

tySixt

yHz i

s 1 (F

IFTY)

, the m

ains f

requ

ency

is fif

ty Hz

.nc

iIoSe

lect

Spac

eSen

sorT

ype

T777

00

T777

0X

Spac

eSen

sorT

ype s

pecif

ies th

e typ

e of s

pace

temp

eratu

re se

nsor

co

nnec

ted to

the n

ode.

Whe

n Spa

ceSe

nsor

Type

is 0,

a T7

770 s

enso

r is

conn

ected

to th

e sen

sor t

ermi

nals.

No o

ther o

ption

s are

curre

ntly v

alid.

RmtS

tptPo

tnv

oIOsiS

etPoin

tTemp

S7De

gree

s F-9

to 85

Degr

ees C

(-23 t

o 29)

SI_IN

VALID

M,

SX

XX

SetP

ointTe

mp is

the w

all m

odule

setpo

int te

mper

ature

. Whe

n nc

iCon

fig.S

etPoin

tTemp

is A

BSOL

UTE_

COOL

or A

BSOL

UTE_

MIDD

LE,

the re

porte

d valu

e is t

he ab

solut

e setp

oint te

mper

ature

. Whe

n Co

nfig.S

etPntK

nob i

s OFF

SET,

the re

porte

d valu

e is t

he of

fset (

from

the

curre

nt ac

tive T

empS

etPts)

temp

eratu

re. If

the i

nput

is no

t con

figur

ed or

ha

s fail

ed, th

e valu

e is S

I_INV

ALID

.Rm

Temp

Sens

rnv

oIOsiS

pace

Temp

S7De

gree

s F40

to 10

0De

gree

s C(4

to 38

)

SI_IN

VALID

M,

SSp

aceT

emp i

s the

mea

sure

d spa

ce te

mper

ature

. If th

e sen

sor is

not

confi

gure

d or h

as fa

iled,

the va

lue is

SI_I

NVAL

ID.N

OTE:

The

repo

rted

tempe

ratur

es in

clude

s the

offse

t cor

recti

on pr

ovide

d by

Confi

g.Res

istive

Offse

tCal.

DaTe

mpSe

nsr

nvoIO

siDisc

harg

eTem

pS7

Degr

ees F

Degr

ees C

30 to

122

(-1 to

50)

SI_IN

VALID

Disc

harg

eTem

p is t

he m

easu

red d

ischa

rge a

ir tem

pera

ture.

If the

sens

or is

no

t con

figur

ed or

has f

ailed

, the v

alue i

s SI_I

NVAL

ID. R

efer t

o the

note

on

Spac

eTem

p.Ra

Temp

Sens

rnv

oIOsiR

eturn

Temp

S7De

gree

s FDe

gree

s C30

to 12

2(-1

to 50

)SI

_INVA

LIDRe

turnT

emp i

s the

mea

sure

d retu

rn ai

r tem

pera

ture.

If the

sens

or is

not

confi

gure

d or h

as fa

iled,

the va

lue is

SI_I

NVAL

ID. R

efer t

o the

note

on

Spac

eTem

p.Ra

HumS

ensr

nvoIO

Retur

nHum

idity

Perce

ntage

10 to

90SI

_INVA

LIDRe

turnH

umidi

ty is

the m

easu

red r

eturn

air h

umidi

ty. If

the se

nsor

is no

t co

nfigu

red o

r has

faile

d, the

value

is U

B_IN

VALID

.NOT

E: T

he re

porte

d tem

pera

tures

inclu

des t

he of

fset c

orre

ction

prov

ided b

y Co

nfig.V

oltag

eOffs

etCal.

RaEn

thSen

srnv

oIOsiR

eturn

Entha

lpyS7

mA 4 to 2

0SI

_INVA

LIDRe

turnE

nthalp

y is t

he m

easu

red r

eturn

air e

nthalp

y. If t

he se

nsor

is no

t co

nfigu

red o

r has

faile

d, the

value

is S

I_INV

ALID

. Sinc

e the

C74

00 re

ports

co

mfor

t due

to en

thalpy

(btu/

lb) in

milli

amps

, enth

alpy i

s also

repo

rted i

n mi

lliamp

s. Re

fer to

the N

OTE

on R

eturn

Humi

dity.

OaTe

mpSe

nsr

nvoIO

siOutd

oorTe

mpS7

Degr

ees F

Degr

ees C

-40 t

o 122

(-40 t

o 50)

SI_IN

VALID

M,

SOu

tdoor

Temp

is th

e mea

sure

d outd

oor a

ir tem

pera

ture.

If the

sens

or is

not

confi

gure

d or h

as fa

iled,

the va

lue is

SI_I

NVAL

ID. R

efer t

o the

NOT

E on

Re

turnH

umidi

ty.Oa

HumS

ensr

nvoIO

Outdo

orHu

midit

yPe

rcenta

ge10

to 90

SI_IN

VALID

M,

SOu

tdoor

Humi

dity i

s the

mea

sure

d outd

oor a

ir hum

idity.

If the

sens

or is

not

confi

gure

d or h

as fa

iled,

the va

lue is

UB_

INVA

LID. R

efer t

o the

NOT

E on

Re

turnH

umidi

ty.

Tabl

e 20

. Inp

ut/O

utpu

t Poi

nts.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

71 74-2958�2

OaEn

thSen

srnv

oIOsiO

utdoo

rEnth

alpyS

7mA 4 t

o 20

SI_IN

VALID

M,

SOu

tdoor

Entha

lpy is

the m

easu

red o

utdoo

r air e

nthalp

y. If t

he se

nsor

is no

t co

nfigu

red o

r has

faile

d, the

value

is S

I_INV

ALID

. Sinc

e the

C74

00 re

ports

co

mfor

t due

to en

thalpy

(btu/

lb) in

milli

amps

, enth

alpy i

s also

repo

rted i

n mi

lliamp

s. Re

fer to

the N

OTE

on R

eturn

Humi

dity.

FltrP

ress

Sens

rnv

oIOsiF

ilterP

ress

ureS

10in.

w.c.

(kPa

)0 t

o 5 (0

to 1.

25)

SI_IN

VALID

Filter

Pres

sure

is th

e mea

sure

d diffe

renti

al pr

essu

re ac

ross

the r

eturn

air

filter.

If the

sens

or is

not c

onfig

ured

or ha

s fail

ed, th

e valu

e is t

he

SI_IN

VALID

. Refe

r to t

he N

OTE

on R

eturn

Humi

dity.

CO2S

ensr

nvoIO

siSpa

ceCo

2S0

PPM

150 t

o 200

0SI

_INVA

LIDSp

aceC

o2 is

the m

easu

red C

O 2 in

the c

ondit

ioned

air s

pace

. If th

e sen

sor

is no

t con

figur

ed or

has f

ailed

, the v

alue i

s SI_I

NVAL

ID. R

efer t

o the

NOT

E on

Retu

rnHu

midit

y.Mo

nitor

Sens

rnv

oIOsiM

onito

rS10

volts

1 to 1

0SI

_INVA

LIDMo

nitor

is th

e volt

age a

pplie

d at th

e mon

itor in

puts

termi

nals.

If the

sens

or

is no

t con

figur

ed or

has f

ailed

, the v

alue i

s SI_I

NVAL

ID. R

efer t

o the

NOT

E on

Retu

rnHu

midit

y.St

atusD

O1nv

oIOub

Out

Byte

Offse

t = 24

Bit O

ffset

= 0(

Digit

alOut1

)

FALS

ETR

UE0 1

FALS

EDi

gitalO

ut1 is

a by

te wi

th a b

it for

ever

y phy

sical

digita

l outp

ut. O

n is a

1 (T

RUE)

and o

ff is a

0 (F

ALSE

).

Statu

sDO2

nvoIO

ubOu

tBy

te Of

fset =

24Bi

t Offs

et =

1(Di

gitalO

ut2)

FALS

ETR

UE0 1

FALS

EDi

gitalO

ut2 is

a by

te wi

th a b

it for

ever

y phy

sical

digita

l outp

ut. O

n is a

1 (T

RUE)

and o

ff is a

0 (F

ALSE

).

Statu

sDO3

nvoIO

ubOu

tBy

te Of

fset =

24Bi

t Offs

et =

2(Di

gitalO

ut3)

FALS

ETR

UE0 1

FALS

EDi

gitalO

ut3 is

a by

te wi

th a b

it for

ever

y phy

sical

digita

l outp

ut. O

n is a

1 (T

RUE)

and o

ff is a

0 (F

ALSE

).

Statu

sDO4

nvoIO

ubOu

tBy

te Of

fset =

24Bi

t Offs

et =

3(Di

gitalO

ut4)

FALS

ETR

UE0 1

FALS

EDi

gitalO

ut4 is

a by

te wi

th a b

it for

ever

y phy

sical

digita

l outp

ut. O

n is a

1 (T

RUE)

and o

ff is a

0 (F

ALSE

).

Statu

sDO5

nvoIO

ubOu

tBy

te Of

fset =

24Bi

t Offs

et =

4(Di

gitalO

ut5)

FALS

ETR

UE0 1

FALS

EDi

gitalO

ut5 is

a by

te wi

th a b

it for

ever

y phy

sical

digita

l outp

ut. O

n is a

1 (T

RUE)

and o

ff is a

0 (F

ALSE

).

Statu

sDO6

nvoIO

ubOu

tBy

te Of

fset =

24Bi

t Offs

et =

5(Di

gitalO

ut6)

FALS

ETR

UE0 1

FALS

EDi

gitalO

ut6 is

a by

te wi

th a b

it for

ever

y phy

sical

digita

l outp

ut. O

n is a

1 (T

RUE)

and o

ff is a

0 (F

ALSE

).

Statu

sDO7

nvoIO

ubOu

tBy

te Of

fset =

24Bi

t Offs

et =

6(Di

gitalO

ut7)

FALS

ETR

UE0 1

FALS

EDi

gitalO

ut7 is

a by

te wi

th a b

it for

ever

y phy

sical

digita

l outp

ut. O

n is a

1 (T

RUE)

and o

ff is a

0 (F

ALSE

).

Statu

sDO8

nvoIO

ubOu

tBy

te Of

fset =

24Bi

t Offs

et =

7(Di

gitalO

ut8)

FALS

ETR

UE0 1

FALS

EDi

gitalO

ut8 is

a by

te wi

th a b

it for

ever

y phy

sical

digita

l outp

ut. O

n is a

1 (T

RUE)

and o

ff is a

0 (F

ALSE

).

Tabl

e 20

. Inp

ut/O

utpu

t Poi

nts.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 72

Statu

sDI1

nvoIO

ubDi

gitalI

nBy

te Of

fset =

25Bi

t Offs

et =

7(Di

gitalI

n1)

FALS

ETR

UE0 1

FALS

EDi

gitalI

n1 is

a by

te wi

th a b

it for

ever

y phy

sical

digita

l inpu

t. If th

e inp

ut is

shor

ted to

grou

nd, th

e bit i

s a ze

ro or

FALS

E. If

the in

put is

open

, the b

it is

one o

r TRU

E.

Statu

sDI2

nvoIO

ubDi

gitalI

nBy

te Of

fset =

25Bi

t Offs

et =

6(Di

gitalI

n2)

FALS

ETR

UE0 1

FALS

EDi

gitalI

n2 is

a by

te wi

th a b

it for

ever

y phy

sical

digita

l inpu

t. If th

e inp

ut is

shor

ted to

grou

nd, th

e bit i

s a ze

ro or

FALS

E. If

the in

put is

open

, the b

it is

one o

r TRU

E.

Statu

sDI3

nvoIO

ubDi

gitalI

nBy

te Of

fset =

25Bi

t Offs

et =

5(Di

gitalI

n3)

FALS

ETR

UE0 1

FALS

EDi

gitalI

n3 is

a by

te wi

th a b

it for

ever

y phy

sical

digita

l inpu

t. If th

e inp

ut is

shor

ted to

grou

nd, th

e bit i

s a ze

ro or

FALS

E. If

the in

put is

open

, the b

it is

one o

r TRU

E.

Statu

sDI4

nvoIO

ubDi

gitalI

nBy

te Of

fset =

25Bi

t Offs

et =

4(Di

gitalI

n4)

FALS

ETR

UE0 1

FALS

EDi

gitalI

n4 is

a by

te wi

th a b

it for

ever

y phy

sical

digita

l inpu

t. If th

e inp

ut is

shor

ted to

grou

nd, th

e bit i

s a ze

ro or

FALS

E. If

the in

put is

open

, the b

it is

one o

r TRU

E.

Mode

lnv

oIOub

Digit

alIn

Byte

Offse

t = 25

Bit O

ffset

= 3

(Exte

nedM

odelI

n)

FALS

ETR

UE0 1

FALS

EX

Exten

edMo

delIn

is a

byte

with

a bit f

or ev

ery p

hysic

al dig

ital in

put. I

f the

input

is sh

orted

to gr

ound

, the b

it is a

zero

or FA

LSE.

If the

inpu

t is op

en,

the bi

t is on

e or T

RUE.

Ovrd

Swnv

oIOOv

erRi

deFA

LSE

TRUE

0 1FA

LSE

Over

Ride

indic

ates t

he st

atus o

f the w

all m

odule

over

ride p

ushb

utton

. It is

1 (T

RUE)

if the

butto

n is p

ress

ed, a

nd is

0 (F

ALSE

) if it

isn't p

ress

ed.

OccS

ensr

nvoIO

Occu

panc

ySen

sor

FALS

ETR

UE0 1

FALS

EM,

S

Occu

panc

ySen

sor is

the s

tate o

f the d

igital

inpu

t con

figur

ed an

d wire

d to

the lo

cal o

ccup

ancy

sens

or. 1

mean

s tha

t occ

upan

cy is

being

sens

ed (in

put

circu

it sho

rted)

and 0

mea

ns th

at no

occu

panc

y is b

eing s

ense

d (inp

ut cir

cuit o

pen)

.Tim

eClkS

wnv

oIOOc

cTim

eCloc

kFA

LSE

TRUE

0 1FA

LSE

M,

SOc

cTim

eCloc

k is t

he st

ate of

the d

igital

inpu

t con

figur

ed an

d wire

d to a

time

clock

. 1 (in

put s

horte

d) m

eans

that

the sc

hedu

led oc

cupa

ncy i

s OC

_OCC

UPIE

D, an

d 0 (in

put o

pen c

ircuit

ed) m

eans

that

the sc

hedu

led

occu

panc

y is O

C_UN

OCCU

PIED

.St

atusA

irFlow

nvoIO

Proo

fAirF

lowFA

LSE

TRUE

0 1FA

LSE

Proo

fAirF

low is

the s

tate o

f the d

igital

inpu

t con

figur

ed an

d wire

d to t

he

proo

f of a

ir flow

switc

h. 1 (

input

shor

ted) m

eans

that

air flo

w is

detec

ted an

d 0 (

input

open

circu

ited)

mea

ns th

at air

flow

is no

t dete

cted.

Econ

EnSw

nvoIO

Econ

Enab

leIn

FALS

ETR

UE0 1

FALS

EM,

S

Econ

Enab

leIn i

s the

state

of th

e digi

tal in

put c

onfig

ured

and w

ired t

o the

ou

tdoor

air s

enso

r tha

t dete

rmine

s the

suita

bly of

outdo

or ai

r for

free

co

oling

. 1 (in

put s

horte

d) m

eans

that

the ou

tdoor

air is

suita

ble fo

r coo

ling,

and 0

(inpu

t ope

n) m

eans

that

the ou

tdoor

air in

not s

uitab

le for

cooli

ng.

IaqOv

rSw

nvoIO

IaqOv

erRi

deFA

LSE

TRUE

0 1FA

LSE

M,

SIaq

Over

Ride

is th

e stat

e of th

e digi

tal in

put c

onfig

ured

and w

ired t

o the

ind

oor a

ir qua

lity se

nsor.

1 (in

put s

horte

d) m

eans

that

the in

door

air q

uality

is

poor,

and 0

(inpu

t ope

n) m

eans

that

the in

door

air q

uality

is ac

cepta

ble.

This

input

is us

ed to

caus

e the

econ

omize

r to o

pen t

o a pr

edete

rmine

d po

sition

whe

n poo

r indo

or ai

r qua

lity is

detec

ted.

Smok

eMon

Swnv

oIOSm

okeM

onito

rFA

LSE

TRUE

0 1FA

LSE

M,

SSm

okeM

onito

r is th

e stat

e of th

e digi

tal in

put c

onfig

ured

and w

ired t

o the

ind

oor s

moke

sens

or. 1

(inpu

t sho

rted)

mea

ns th

at sm

oke i

s dete

cted,

and

0 (inp

ut op

en) m

eans

that

no sm

oke i

s dete

cted.

Tabl

e 20

. Inp

ut/O

utpu

t Poi

nts.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

73 74-2958�2

DrtyF

ilterS

wnv

oIODi

rtyFil

terFA

LSE

TRUE

0 1FA

LSE

M,

SDi

rtyFil

ter is

the s

tate o

f the d

igital

inpu

t con

figur

ed an

d wire

d to t

he di

rty

filter

sens

or. 1

(inpu

t sho

rted)

mea

ns th

at filt

er is

dirty

, and

0 (in

put o

pen)

me

ans t

hat th

e filte

r is no

t dirty

.Sh

utDow

nSw

nvoIO

ShutD

own

FALS

ETR

UE0 1

FALS

ESh

utDow

n is t

he st

ate of

the d

igital

inpu

t con

figur

ed an

d wire

d to t

he sh

ut do

wn sw

itch.

1 (inp

ut sh

orted

) mea

ns th

at eq

uipme

nt sh

ould

be sh

ut do

wn,

and 0

(inpu

t ope

n) m

eans

that

the eq

uipme

nt sh

ould

be ru

nning

.W

indow

Swnv

oIOW

indow

Open

FALS

ETR

UE0 1

FALS

EM,

S

Wind

owOp

en is

the s

tate o

f the d

igital

inpu

t con

figur

ed an

d wire

d to a

wi

ndow

open

sens

or sw

itch.

1 (inp

ut op

en ci

rcuit)

mean

s tha

t the w

indow

is

open

, and

0 (in

put s

horte

d) m

eans

that

the w

indow

is cl

osed

.Mo

nitor

Swnv

oIOMo

nSwi

tchFA

LSE

TRUE

0 1FA

LSE

MonS

witch

is th

e stat

e of th

e digi

tal in

put c

onfig

ured

and w

ired t

o a ge

nera

l pu

rpos

e mon

itor s

witch

. 1 (in

put s

horte

d) m

eans

that

switc

h is c

losed

, and

0 (

input

open

) mea

ns th

at the

switc

h is o

pen.

Mode

lSw

nvoIO

Mode

lFA

LSE

TRUE

0 1FA

LSE

XMo

del in

dicate

s the

Mod

el of

the no

de. O

ne of

the d

igital

inpu

ts is

conn

ected

to a

print

ed w

iring b

oard

trac

e to l

et the

embe

dded

softw

are

know

wha

t kind

of ha

rdwa

re is

pres

ent. I

f Mod

el is

1 (inp

ut he

ld hig

h), th

e ha

rdwa

re is

the W

7750

B Mo

del. I

f Mod

el is

0 (inp

ut sh

orted

to gr

ound

), the

ha

rdwa

re is

the W

7750

A Mo

del.

nvoIO

Sche

dMas

terFA

LSE

TRUE

0 1FA

LSE

MX

If Sch

edule

Maste

r is 1

(inpu

t sho

rted)

, the n

ode i

s the

sche

dule

maste

r and

the

loca

lly co

nnec

ted tim

e cloc

k will

be se

nt via

Tim

eClk

to oth

er no

des o

n the

netw

ork.

If Sch

edule

Maste

r is 0,

(inpu

t ope

n), th

e nod

e is n

ot a

sche

dule

maste

r and

nvoT

imeC

lk wi

ll not

be se

nt on

the n

etwor

k eve

n if th

e tim

e cloc

k inp

ut is

confi

gure

d. If t

he S

ched

uleMa

ster in

put is

not c

onfig

ured

by

Sele

ct, T

imeC

lk re

ports

the s

tate o

f the l

ocall

y con

necte

d tim

e cloc

k.

Tabl

e 20

. Inp

ut/O

utpu

t Poi

nts.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 74

Tabl

e 21

. Con

trol

Par

amet

ers.

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

tsDa

Temp

LoLim

nciA

ux1S

etPt

siLow

LimitD

ischA

irTem

pS7

Degr

ees F

0 to 6

0De

gree

s C(-1

to 16

)

45P

XX

Whe

n the

disc

harg

e air t

empe

ratur

e fall

s belo

w Lo

wLim

itDisc

hAirT

emp,

the ou

tdoor

air d

ampe

rs ar

e clos

ed to

a po

sition

that

corre

cts th

e low

temp

eratu

re pr

oblem

. If m

echa

nical

cooli

ng is

activ

e whe

n the

disc

harg

e air f

alls b

elow

LowL

imitD

ischA

irTem

p, the

mec

hanic

al co

oling

cycle

s off a

fter t

he

minim

um ru

n tim

es ar

e obe

yed t

o allo

w the

damp

ers t

o retu

rn op

en

and p

rovid

e fre

e coo

ling.

DaTe

mpHi

Limnc

iAux

1SetP

tsiM

axDi

sAirT

empH

eatS

7De

gree

s FDe

gree

s C65

to 13

5(1

8 to 5

7)10

0P

XX

Whe

n the

mod

e is H

EAT,

and t

he C

asca

deCo

ntrol

is en

abled

, the

disch

arge

air t

empe

ratur

e is c

ontro

lled t

o a va

lue no

t to ex

ceed

Ma

xDisA

irTem

pHea

t.Dl

cBum

pTem

pnc

iAux

1SetP

tsiD

lcBum

pTem

pS7

Degr

ees F

Degr

ees C

0 to +

10(-1

8 to -

12)

3P

XX

Whe

n DlcS

hed i

s not

0 the

n the

setpo

int is

shifte

d by D

lcBum

pTem

p in

the en

ergy

savin

g dire

ction

. Whe

n DlcS

hed c

hang

es fr

om 1

to 0,

the se

tpoint

shift

ramp

s bac

k to 0

over

a 30

minu

te int

erva

l.Oa

Temp

HtLk

Out

nciA

ux1S

etPt

ubOd

HtLo

ckOu

tTemp

S0De

gree

s FDe

gree

s C0 t

o 90

(-18 t

o 32)

70P

XX

Whe

n the

outdo

or ai

r tem

pera

ture i

s gre

ater t

han

OdHt

Lock

OutTe

mp, th

e hea

ting i

s disa

bled.

MaxH

tRam

pnc

iAux

1SetP

tub

MaxH

tRam

pS0

Degr

ees F

/Hr

0 to 2

0De

gree

s C/H

r(0

to 11

)

8P

XX

MaxH

tRam

p is t

he m

axim

um he

at re

cove

ry ra

mp ra

te in

degr

ees F

pe

r hou

r. This

value

is us

ed to

contr

ol the

adap

tive r

ecov

ery r

amp

rate

durin

g the

HEA

T re

cove

ry pe

riod.

The s

etpoin

t is ch

ange

d at a

ra

te in

degr

ees F

per h

our d

epen

ding o

n the

outdo

or ai

r tem

pera

ture

and t

he M

inHtR

amp,

OdTe

mpMa

xHtR

amp,

and O

aTem

pMinH

tRam

p pa

rame

ters.

If the

re is

no ou

tdoor

air t

empe

ratur

e sen

sor a

vaila

ble,

then u

bMinH

tRam

p is u

sed a

s the

reco

very

rate.

NOTE

: Rec

over

y ra

mping

appli

es be

twee

n sch

edule

d hea

ting o

r coo

ling s

etpoin

t ch

ange

s fro

m OC

_UNO

CCUP

IED

to OC

_STA

NDBY

, OC

_UNO

CCUP

IED

to OC

_OCC

UPIE

D, an

d OC_

STAN

DBY

to OC

_OCC

UPIE

D. S

ched

uled s

etpoin

t cha

nges

from

OC_O

CCUP

IED

to OC

_UNO

CCUP

IED

or O

C_OC

CUPI

ED to

OC_

STAN

DBY

do no

t us

e a ra

mped

setpo

int bu

t inste

ad us

e a st

ep ch

ange

in se

tpoint

. Re

cove

ry ra

mps b

egin

befor

e the

next

sche

duled

occu

panc

y tim

e an

d are

ramp

ed fr

om th

e setp

oint fo

r the

exist

ing sc

hedu

led

occu

panc

y stat

e to t

he se

tpoint

for t

he ne

xt oc

cupa

ncy s

tate.

MinH

tRam

pnc

iAux

1SetP

tub

MinH

tRam

pS0

Degr

ees F

/Hr

0 to 2

0De

gree

s C/H

r(0

to 11

)

3P

XX

MinH

tRam

p is t

he m

inimu

m he

at re

cove

ry ra

mp ra

te in

degr

ees F

pe

r hou

r. This

value

is us

ed to

contr

ol the

adap

tive r

ecov

ery r

amp

rate

durin

g the

HEA

T re

cove

ry pe

riod.

The s

etpoin

t is ch

ange

d at a

ra

te in

degr

ees F

per h

our d

epen

ding o

n the

outdo

or ai

r tem

pera

ture

and t

he M

axHt

Ramp

, OdT

empM

axHt

Ramp

, and

Od

Temp

MinH

tRam

p par

amete

rs. If

there

is no

outdo

or ai

r tem

pera

ture s

enso

r ava

ilable

, then

MinH

tRam

p is u

sed a

s the

re

cove

ry ra

te. R

efer t

o the

NOT

E in

the co

mmen

ts co

lumn f

or

MaxH

tRam

p for

the c

ondit

ions t

hat r

ecov

ery r

ampin

g app

lies t

o.

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

75 74-2958�2

OaTe

mpMa

xHtR

pnc

iAux

1SetP

tub

OdTe

mpMa

xHtR

ampS

0De

gree

s F0 t

o 100

Degr

ees C

(-18 t

o 38)

40P

XX

OdTe

mpMa

xHtR

amp i

s the

max

imum

outdo

or ai

r tem

pera

ture

para

meter

that

is us

ed to

calcu

late t

he he

at re

cove

ry ra

mp ra

te se

tpoint

. This

value

is us

ed to

contr

ol the

adap

tive r

ecov

ery r

amp

rate

durin

g the

HEA

T re

cove

ry pe

riod.

The s

etpoin

t is ch

ange

d at a

ra

te in

degr

ees F

per h

our d

epen

ding o

n the

outdo

or ai

r tem

pera

ture

and t

he M

axHt

Ramp

, MinH

tRam

p, an

d OdT

empM

inHtR

amp

para

meter

s. If t

here

is no

outdo

or ai

r tem

pera

ture s

enso

r ava

ilable

, the

n MinH

tRam

p is u

sed a

s the

reco

very

rate.

Refe

r to t

he N

OTE

in the

comm

ents

colum

n for

Max

HtRa

mp fo

r wha

t con

dition

s tha

t re

cove

ry ra

mping

appli

es to

.Oa

Temp

MinH

tRp

nciA

ux1S

etPt

ubOd

Temp

MinH

tRam

pS0

Degr

ees F

0 to 1

00De

gree

s C(-1

8 to 3

8)

0P

XX

OdTe

mpMi

nHtR

amp i

s the

mini

mum

outdo

or ai

r tem

pera

ture

para

meter

that

is us

ed to

calcu

late t

he he

at re

cove

ry ra

mp ra

te se

tpoint

. This

value

is us

ed to

contr

ol the

adap

tive r

ecov

ery r

amp

rate

durin

g the

HEA

T re

cove

ry pe

riod.

The s

etpoin

t is ch

ange

d at a

ra

te in

degr

ees F

per h

our d

epen

ding o

n the

outdo

or ai

r tem

pera

ture

and t

he M

axHt

Ramp

, MinH

tRam

p, an

d OdT

empM

axHt

Ramp

pa

rame

ters.

If the

re is

no ou

tdoor

air t

empe

ratur

e sen

sor a

vaila

ble,

then M

inHtR

amp i

s use

d as t

he re

cove

ry ra

te. R

efer t

o the

NOT

E in

the co

mmen

ts co

lumn f

or M

axHt

Ramp

for w

hat c

ondit

ions t

hat

reco

very

ramp

ing ap

plies

to.

OaTe

mpCl

LkOu

tnc

iAux

1SetP

tub

OdCl

Lock

OutTe

mpS0

Degr

ees F

Degr

ees C

0 to 9

0(-1

8 to 3

2)50

PX

XW

hen t

he ou

tdoor

air t

empe

ratur

e is l

ess t

han O

dClLo

ckOu

tTemp

, the

cooli

ng is

disa

bled.

MaxC

lRam

pnc

iAux

1SetP

tub

MaxC

lRam

pS0

Degr

ees F

/Hr

0 to 2

0De

gree

s C/H

r(0

to 11

)

6P

XX

MaxC

lRam

p is t

he m

axim

um co

ol re

cove

ry ra

mp ra

te in

degr

ees F

pe

r hou

r. This

value

is us

ed to

contr

ol the

adap

tive r

ecov

ery r

amp

rate

durin

g the

COO

L rec

over

y per

iod. T

he se

tpoint

is ch

ange

d at a

ra

te in

degr

ees F

per h

our d

epen

ding o

n the

outdo

or ai

r tem

pera

ture

and t

he M

inClR

amp,

OdTe

mpMa

xClR

amp,

and O

dTem

pMinC

lRam

p pa

rame

ters.

If the

re is

no ou

tdoor

air t

empe

ratur

e sen

sor a

vaila

ble,

then M

inClR

amp i

s use

d as t

he re

cove

ry ra

te. R

efer t

o the

NOT

E in

the co

mmen

ts co

lumn f

or M

axHt

Ramp

for t

he co

nditio

ns th

at re

cove

ry ra

mping

appli

es to

.Mi

nClR

amp

nciA

ux1S

etPt

ubMi

nClR

ampS

0De

gree

s F/H

r0 t

o 20

Degr

ees C

/Hr

(0 to

11)

2P

XX

MinC

lRam

p is t

he m

inimu

m co

ol re

cove

ry ra

mp ra

te in

degr

ees F

pe

r hou

r. This

value

is us

ed to

contr

ol the

adap

tive r

ecov

ery r

amp

rate

durin

g the

COO

L rec

over

y per

iod. T

he se

tpoint

is ch

ange

d at a

ra

te in

degr

ees F

per h

our d

epen

ding o

n the

outdo

or ai

r tem

pera

ture

and t

he M

axCl

Ramp

, OdT

empM

axCl

Ramp

, and

Od

Temp

MinC

lRam

p par

amete

rs. If

there

is no

outdo

or ai

r tem

pera

ture s

enso

r ava

ilable

, then

MinC

lRam

p is u

sed a

s the

re

cove

ry ra

te. R

efer t

o the

NOT

E in

the co

mmen

ts co

lumn f

or

MaxH

tRam

p for

the c

ondit

ions t

hat r

ecov

ery r

ampin

g app

lies t

o.Oa

Temp

MaxC

lRp

nciA

ux1S

etPt

ubOd

Temp

MaxC

lRam

pS0

Degr

ees F

0 to 1

00De

gree

s C(-1

8 to 3

8)

70P

XX

OdTe

mpMa

xClR

amp i

s the

max

imum

outdo

or ai

r tem

pera

ture

para

meter

that

is us

ed to

calcu

late t

he co

ol re

cove

ry ra

mp ra

te se

tpoint

. This

value

is us

ed to

contr

ol the

adap

tive r

ecov

ery r

amp

rate

durin

g the

COO

L rec

over

y per

iod. T

he se

tpoint

is ch

ange

d at a

ra

te in

degr

ees F

per h

our d

epen

ding o

n the

outdo

or ai

r tem

pera

ture

and t

he M

axCl

Ramp

, MinC

lRam

p, an

d OdT

empM

inClR

amp

para

meter

s. If t

here

is no

outdo

or ai

r tem

pera

ture s

enso

r ava

ilable

, the

n MinC

lRam

p is u

sed a

s the

reco

very

rate.

Refe

r to t

he N

OTE

in the

comm

ents

colum

n for

Max

HtRa

mp fo

r the

cond

itions

that

reco

very

ramp

ing ap

plies

to.

Tabl

e 21

. Con

trol

Par

amet

ers.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 76

OaTe

mpMi

nClR

pnc

iAux

1SetP

tub

OdTe

mpMi

nClR

ampS

0De

gree

s F0 t

o 100

Degr

ees C

(-18 t

o 38)

90P

XX

OdTe

mpMi

nClR

amp i

s the

mini

mum

outdo

or ai

r tem

pera

ture

para

meter

that

is us

ed to

calcu

late t

he co

ol re

cove

ry ra

mp ra

te se

tpoint

. This

value

is us

ed to

contr

ol the

adap

tive r

ecov

ery r

amp

rate

durin

g the

COO

L rec

over

y per

iod. T

he se

tpoint

is ch

ange

d at a

ra

te in

degr

ees F

per h

our d

epen

ding o

n the

outdo

or ai

r tem

pera

ture

and t

he M

axCl

Ramp

, MinC

lRam

p, an

d OdT

empM

axCl

Ramp

pa

rame

ters.

If the

re is

no ou

tdoor

air t

empe

ratur

e sen

sor a

vaila

ble,

then M

inClR

amp i

s use

d as t

he re

cove

ry ra

te. R

efer t

o the

NOT

E in

the co

mmen

ts co

lumn f

or M

axHt

Ramp

for t

he co

nditio

ns th

at re

cove

ry ra

mping

appli

es to

.Oa

Econ

EnTe

mpnc

iAux

1SetP

tub

OdEc

onEn

ableT

empS

0De

gree

s F0 t

o 90

Degr

ees C

(-18 t

o 32)

70P

XX

If Con

fig.E

conE

nable

is O

D_TE

MP, a

nd th

e outd

oor t

empe

ratur

e is

less t

han O

dEco

nEna

bleTe

mp, th

en ou

tdoor

air is

judg

ed su

itable

to

augm

ent m

echa

nical

cooli

ng. If

Con

fig.E

conE

nable

is

SING

LE_E

NTH

and o

utdoo

r tem

pera

te is

less t

han

ubOd

Econ

Enab

leTem

p (hig

h lim

it), th

en ou

tdoor

air m

ay be

judg

ed

suita

ble to

augm

ent m

echa

nical

cooli

ng de

pend

ing on

the

relat

ionsh

ip be

twee

n calc

ulated

outdo

or en

thalpy

and

OdEn

thalpy

Enab

le.Di

ffEco

nEnT

emp

nciA

ux1S

etPt

ubDi

ffEco

nEna

bleTe

mpS0

Degr

ees F

Degr

ees C

0 to 9

0(-1

8 to 3

2)4

PX

XIf C

onfig

.Eco

nEna

ble is

DIF

F_TE

MP, a

nd re

turn a

ir tem

pera

ture

minu

s outd

oor a

ir tem

pera

ture i

s gre

ater t

han D

iffEco

nEna

bleTe

mp,

then o

utdoo

r air i

s jud

ged s

uitab

le to

augm

ent m

echa

nical

cooli

ng.

OaEn

thEn

nciA

ux1S

etPt

ubOd

Entha

lpyEn

ableS

2btu

/lb0 t

o 65

25P

XX

If Con

fig.E

conE

nable

is S

INGL

E_EN

TH, a

nd ca

lculat

ed ou

tdoor

en

thalpy

is le

ss th

an O

dEnth

alpyE

nable

, and

outdo

or te

mper

ature

is

less t

han O

dEco

nEna

bleTe

mp, th

en ou

tdoor

air is

judg

ed su

itable

to

augm

ent m

echa

nical

cooli

ng.

Econ

MinP

osnc

iAux

1SetP

tub

Econ

MinP

osS0

Perce

ntage

0 to 1

000

PX

XTh

e mini

mum

allow

ed po

sition

of th

e eco

nomi

zer d

ampe

r for

HEA

T an

d COO

L is E

conM

inPos

.Ec

onIA

QPos

nciA

ux1S

etPt

ubEc

onIaq

PosS

0Pe

rcenta

ge0 t

o 100

80P

XX

The c

ontro

l ove

rride

s the

econ

omize

r dam

per t

o Eco

nIaqP

os w

hen

poor

indo

or ai

r qua

lity is

detec

ted.

IAQS

etpt

nciA

ux1S

etPt

siCO2

IaqLim

itS0

PPM

0 to 2

000

800

PX

XW

hen a

n ana

log C

O 2 se

nsor

is co

nfigu

red a

nd th

e sen

sed C

O 2 is

gr

eater

than

CO2

IaqLim

it, the

n poo

r indo

or ai

r qua

lity is

detec

ted

and D

ata1.O

verR

ide is

set to

1. W

hen t

he se

nsed

CO 2

is le

ss th

an

CO2Ia

qLim

it, the

n the

indo

or ai

r qua

lity is

cons

idere

d acc

eptab

le an

d Data

1.Iaq

Over

Ride

is se

t to 0.

oData

1.Iaq

Over

Ride

is us

ed to

se

t the e

cono

mize

r dam

per t

o Aux

1SetP

t. Eco

nIaqP

os an

d to

poss

ibly t

urn o

n the

heat

acco

rding

to th

e stat

e of

Confi

g.Iaq

UseH

eat.

PwmP

eriod

nciA

ux1S

etPt

siPwm

Perio

dS4

100

PX

XW

hen p

ulse w

idth m

odula

tion i

s use

d, the

perio

d of o

ne pu

lse w

idth

modu

lation

cycle

is P

wmPe

riod s

econ

ds. T

he sm

alles

t res

olutio

n is

0.1 se

cond

s.Pw

mZer

oSca

lenc

iAux

1SetP

tsiP

wm0p

cntS

4Se

cond

s0 t

o 204

71

PX

XW

hen p

ulse w

idth m

odula

tion i

s use

d, the

perio

d of a

pulse

for z

ero

perce

nt ou

tput (

damp

er or

valve

at op

en po

sition

) is P

wm0p

cntS

4 se

cond

s. Th

e sma

llest

reso

lution

is 0.

1 sec

onds

.Pw

mFull

Scale

nciA

ux1S

etPt

siPwm

100p

cntS

4Se

cond

s0 t

o 204

799

PX

XW

hen p

ulse w

idth m

odula

tion i

s use

d, the

perio

d of a

pulse

for f

ull

scale

outpu

t (da

mper

or va

lve at

open

posit

ion) is

Pwm

100p

cnt

seco

nds.

The s

malle

st re

solut

ion is

0.1 s

econ

ds.

Tabl

e 21

. Con

trol

Par

amet

ers.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

77 74-2958�2

BypT

ime

nciA

ux2S

etPt

uiByp

assT

ime

minu

tes0 t

o 108

018

0P

XX

uiByp

assT

ime i

s the

time b

etwee

n the

pres

sing o

f the o

verri

de

butto

n at th

e wall

mod

ule (o

r initia

ting O

C_BY

PASS

via M

anOc

c) an

d the

retur

n to t

he or

igina

l occ

upan

cy st

ate. W

hen t

he by

pass

sta

te ha

s bee

n acti

vated

, the b

ypas

s tim

er is

set to

Byp

assT

ime.

FltrP

ress

StPt

nciA

ux2S

etPt

ubFil

terPr

essS

tPtS

5in.

w.c.

(kPa

)0 t

o 5 (0

to 1.

25)

0.5P

XX

If a fil

ter pr

essu

re se

nsor

is co

nfigu

red b

y IoS

elect

and t

he fil

ter

pres

sure

repo

rted i

n Data

1 Filte

rPre

ssur

e exc

eeds

Filte

rPre

ssSt

Pt,

then a

DIR

TY_F

ILTER

alar

m is

gene

rated

and D

ata1.D

irtyFil

ter is

se

t to 1.

StptK

nobL

owLim

nciA

ux2S

etPt

siLow

StPt

S7De

gree

s F-9

to 90

Degr

ees C

(-23 t

o 32)

55P

XX

LowS

tPt is

the l

owes

t valu

e rep

orted

for t

he se

tpoint

knob

. De

pend

ent o

n the

confi

gura

tion o

f the s

etpoin

t kno

b (se

e Co

nfig.S

etPntK

nob)

this

settin

g is e

ither

abso

lute [

degr

ee

Fahr

enhe

it (50

to 90

)] in c

ase o

f abs

olute

setpo

int kn

ob co

nfigu

ratio

n or

relat

ive [d

elta d

egre

e Fah

renh

eit (-

9 to +

9)] in

case

of re

lative

se

tpoint

knob

confi

gura

tion.

StptK

nobH

iLim

nciA

ux2S

etPt

siHigh

StPt

S7De

gree

s F-9

to 90

Degr

ees C

(-23 t

o 32)

85P

XX

High

StPt

is th

e high

est v

alue r

epor

ted fo

r the

setpo

int kn

ob.

Depe

nden

t on t

he co

nfigu

ratio

n of th

e setp

oint k

nob (

see

Confi

g.SetP

ntKno

b) th

is se

tting i

s eith

er ab

solut

e [de

gree

Fa

hren

heit (

50 to

90)] i

n cas

e of a

bsolu

te se

tpoint

knob

confi

gura

tion

or re

lative

[delt

a deg

ree F

ahre

nheit

(-9 t

o +9)

] in ca

se of

relat

ive

setpo

int kn

ob co

nfigu

ratio

n.Ga

inCoo

lPro

pnc

iAux

2SetP

tub

KpCo

olS2

Degr

ees F

Degr

ees C

2 to 3

0(1

to 30

)5

PX

XTh

is is

the th

rottli

ng ra

nge f

or th

e pro

portio

nal p

ortio

n of th

e PID

loop

ga

in for

the c

oolin

g con

trol lo

op.

GainH

eatP

rop

nciA

ux2S

etPt

ubKp

HeatS

2De

gree

s FDe

gree

s C2 t

o 30

(1 to

17)

5P

XX

This

is the

thro

ttling

rang

e for

the p

ropo

rtiona

l por

tion o

f the P

ID lo

op

gain

for th

e hea

ting c

ontro

l loop

.Ga

inCoo

lInt

nciA

ux2S

etPt

siKiC

oolS

0Se

cond

s0 t

o 500

020

50P

XX

This

is the

integ

ral p

ortio

n of th

e PID

loop

gain

for th

e coo

ling c

ontro

l loo

p.Ga

inHea

tInt

nciA

ux2S

etPt

siKiH

eatS

0Se

cond

s0 t

o 500

020

50P

XX

This

is the

integ

ral p

ortio

n of th

e PID

loop

gain

for th

e hea

ting c

ontro

l loo

p.Ga

inCoo

lDer

nciA

ux2S

etPt

siKdC

oolS

0Se

cond

s0 t

o 900

00

PX

XTh

is is

the de

rivati

ve po

rtion o

f the P

ID lo

op ga

in for

the c

oolin

g co

ntrol

loop.

GainH

eatD

ernc

iAux

2SetP

tsiK

dHea

tS0

Seco

nds

0 to 9

000

0P

XX

This

is the

deriv

ative

portio

n of th

e PID

loop

gain

for th

e hea

ting

contr

ol loo

p.Da

Temp

ClCt

rlBd

nciA

ux2S

etPt

ubDi

sCbC

oolS

0De

gree

s FDe

gree

s C5 t

o 30

(3 to

17)

10P

XX

DisC

bCoo

l is th

e thr

ottlin

g ran

ge us

ed fo

r the

cooli

ng po

rtion o

f the

disch

arge

air t

empe

ratur

e cas

cade

contr

ol loo

p.Da

Temp

HtCt

rlBd

nciA

ux2S

etPt

ubDi

sCbH

eatS

0De

gree

s FDe

gree

s C5 t

o 30

(3 to

17)

10P

XX

DisC

bHea

t is th

e thr

ottlin

g ran

ge us

ed fo

r the

heati

ng po

rtion o

f the

disch

arge

air t

empe

ratur

e cas

cade

contr

ol loo

p.Da

Temp

EcCt

rlBd

nciA

ux2S

etPt

ubDi

sCbE

conS

0De

gree

s FDe

gree

s C5 t

o 30

(3 to

1710

PX

XDi

sCbE

con i

s the

thro

ttling

rang

e use

d for

the e

cono

mize

r con

trol

loop.

Tabl

e 21

. Con

trol

Par

amet

ers.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 78

Tabl

e 22

. Ene

rgy

Man

agem

ent P

oint

s.

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.Failure Detect

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

tsDe

stDlcS

hed

nviD

lcShe

d0 t

o 10

MX

XX

XX

DlcS

hed i

s an i

nput

from

an en

ergy

man

agem

ent s

ystem

. Whe

n DlcS

hed i

s 0, th

e tem

pera

ture c

ontro

l algo

rithm

oper

ates i

n a no

rmal

mode

. Whe

n DlcS

hed i

s non

-ze

ro, th

e setp

oint is

shifte

d by A

ux1S

etPt.D

lcBum

pTem

p in t

he en

ergy

savin

g dir

ectio

n.De

stSch

edOc

cnv

iTodE

vent

Curre

ntStat

eOC

_OCC

UPIE

DOC

_UNO

CCUP

IED

OC_B

YPAS

SOC

_STA

NDBY

OC_N

UL

0 1 2 3 255

OC_O

CCUP

IED

MX

XX

XX

Curre

ntStat

e ind

icates

the c

urre

nt sc

hedu

led oc

cupa

ncy s

tate t

o the

node

. Cu

rrentS

tate i

s use

d alon

g with

othe

r occ

upan

cy in

puts

to ca

lculat

e the

effec

tive

occu

panc

y of th

e nod

e. Th

e vali

d stat

es an

d mea

ning a

re as

follo

ws:

OC_O

CCUP

IED

mean

s the

ener

gy m

anag

emen

t sys

tem is

spec

ifying

occu

pied.

OC_U

NOCC

UPIE

D me

ans t

he en

ergy

man

agem

ent s

ystem

is sp

ecify

ing th

at the

sp

ace i

s pre

sentl

y uno

ccup

ied. O

C_BY

PASS

state

s tha

t the e

nerg

y man

agem

ent

syste

m is

in by

pass

. OC_

STAN

DBY

states

that

the en

ergy

man

agem

ent s

ystem

has

the sp

ace p

rese

ntly i

s betw

een o

ccup

ied an

d uno

ccup

ied. O

C_NU

L stat

es th

at no

oc

cupa

ncy s

tate h

as be

en sp

ecifie

d.To

dEve

ntNex

tnv

iTodE

vent

NextS

tate

OC_O

CCUP

IED

OC_U

NOCC

UPIE

DOC

_BYP

ASS

OC_S

TAND

BYOC

_NUL

0 1 2 3 255

OC_O

CCUP

IED

MX

XNe

xtStat

e ind

icates

the n

ext s

ched

uled o

ccup

ancy

state

to th

e nod

e. Th

is inf

orma

tion i

s req

uired

by th

e Exc

el 10

to pe

rform

the o

ptimu

m sta

rt str

ategy

. The

sp

ace e

xpec

ted ef

fectiv

e occ

upan

cy w

ill be

Nex

tStat

e in u

iTime

ToNe

xtStat

e minu

tes.

The v

alid s

tates

and m

eanin

g are

the s

ame a

s for

Cur

rentS

tate.

Tunc

osnv

iTodE

vent

uiTim

eToN

extS

tate

minu

tes0 t

o 288

00

MX

XTim

eToN

extS

tate i

s the

time i

n minu

tes un

til the

next

chan

ge of

sche

duled

oc

cupa

ncy s

tate.

nviB

ypas

s va

lue0 t

o 100

0By

pass

.value

:The

bypa

ss st

ate of

one n

ode m

ay be

shar

ed w

ith th

e byp

ass s

tate o

f an

other

node

using

nviB

ypas

s and

nvoB

ypas

s. Th

is all

ows a

wall

mod

ule at

one

node

to be

used

to ov

er rid

e the

sche

duled

occu

panc

y of a

nothe

r nod

e. Th

e nod

e wi

th By

pass

boun

d nor

mally

does

not h

ave a

wall

mod

ule. S

ee th

e Data

1.Effe

ctOcc

an

d Data

1.Ove

rRide

for m

ore d

etails

. The

valid

state

s are

as fo

llows

: If th

e stat

e is

SW_O

N an

d the

value

is no

t zer

o the

n the

node

shou

ld by

pass

the t

ime o

f day

sc

hedu

le (su

bject

to oc

cupa

ncy a

rbitra

tion l

ogic)

. If th

e stat

e is S

W_N

UL, th

e inp

ut is

not a

vaila

ble be

caus

e it is

not b

ound

, the i

nput

is no

long

er be

ing up

dated

by th

e se

nder,

or O

C_BY

PASS

is no

long

er be

ing ca

lled.

This

mean

s tha

t the s

ame a

s SW

_OFF

. If th

e stat

e is S

W_O

FF or

othe

r and

the v

alue i

s don

�t car

e, the

node

sh

ould

not b

ypas

s the

time o

f day

sche

dule.

If the

state

is S

W_O

N an

d the

value

is 0,

the

n the

node

shou

ld no

t byp

ass t

he tim

e of d

ay sc

hedu

le. If

the no

de re

ceive

s this

co

mbina

tion o

f stat

e and

value

, then

state

is se

t to S

W_O

FF.

DestB

ypas

snv

iByp

ass

state

SW_O

FFSW

_ON

SW_N

UL

0 1 255

SW_N

ULM

XX

XX

Refer

to nv

iByp

ass.v

alue.

SrcB

ypCt

nvoB

ypas

s va

lue0 t

o 100

0nv

oByp

ass.v

alue:n

voBy

pass

is th

e cur

rent

occu

panc

y stat

e of th

e nod

e for

bypa

ss

sche

dule.

The

state

s hav

e the

follo

wing

mea

nings

: If th

e stat

e is S

W_O

FF an

d the

va

lue is

0, th

en D

ata1.E

ffectO

cc is

not O

C_BY

PASS

. If th

e stat

e is S

W_O

N an

d the

va

lue is

100 p

erce

nt, th

en D

ata1.E

ffectO

cc is

OC_

BYPA

SS.

SrcB

ypas

snv

oByp

ass

state

SW_O

FFSW

_ON

SW_N

UL

0 1 255

SW_N

ULM

XX

Refer

to nv

oByp

ass.v

alue.

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

79 74-2958�2

nviFr

ee1

value

0 to 1

000

Free

1.valu

e netw

ork v

ariab

le co

ntrols

the s

pare

or F

ree d

igital

outpu

t for a

uxilia

ry fun

ction

s. nv

iFree

1 con

trols

the F

REE1

_OUT

, FRE

E1_O

UT_P

ULSE

_ON,

and

FREE

1_OU

T_PU

LSE_

OFF

outpu

ts (o

nly o

ne o

f the

se D

O se

lectio

ns p

er co

ntro

ller

is all

owed

). Th

e stat

es ha

ve th

e foll

owing

mea

ning:

If the

state

is S

W_O

FF, th

e co

rresp

ondin

g fre

e log

ical o

utput

(and

ther

efore

the p

hysic

al ou

tput, i

f con

figur

ed) is

off

. If th

e stat

e is S

W_O

N an

d the

value

is 0,

then

the c

orre

spon

ding f

ree l

ogica

l ou

tput (

and t

here

fore t

he ph

ysica

l outp

ut, if

confi

gure

d) is

off. I

f the n

ode r

eceiv

es

this c

ombin

ation

of st

ate an

d valu

e, the

n stat

e is s

et to

SW_O

FF. If

the s

tate i

s SW

_ON

and t

he va

lue is

not z

ero,

then t

he co

rresp

ondin

g fre

e log

ical o

utput

(and

the

refor

e the

phys

ical o

utput,

if co

nfigu

red)

is on

. If th

e stat

e is S

W_N

UL or

othe

r, the

n the

netw

ork v

ariab

le is

not b

ound

, the c

ommu

nicati

ons p

ath fr

om th

e sen

ding

node

has f

ailed

, or t

he se

nding

node

has f

ailed

. The

corre

spon

ding f

ree l

ogica

l ou

tput d

oes n

ot ch

ange

if the

netw

ork v

ariab

le inp

ut fai

ls.De

stFre

e1nv

iFree

1sta

teSW

_OFF

SW_O

NSW

_NUL

0 1 255

SW_N

ULM

XX

XX

Refer

to F

ree1

.value

.

nviFr

ee2

value

0 to 1

000

Free

2.valu

e beh

aves

the s

ame a

s Fre

e 1 va

lue.

DestF

ree2

nviFr

ee2

state

SW_O

FFSW

_ON

SW_N

UL

0 1 255

SW_N

ULM

XX

XX

Refer

to F

ree2

.value

.

nviW

SHPE

nable

value

0 to 1

000

WSH

PEna

ble.va

lue is

used

to en

able

the co

mpre

ssor

stag

es in

heat

pump

ap

plica

tions

. Typ

ically

nviW

SHPE

nable

is bo

und t

o a w

ater f

low se

nsor

that

detec

ts he

ating

/cooli

ng w

ater s

uppli

ed to

the h

eat p

ump.

If the

re is

no w

ater f

lowing

the

comp

ress

or is

disa

bled.

If the

state

is S

W_O

FF, th

e com

pres

sor is

disa

bled i

n hea

t pu

mp ap

plica

tions

. If th

e stat

e is S

W_O

N an

d the

value

is 0,

the c

ompr

esso

r is

disab

led in

heat

pump

appli

catio

ns. If

the n

ode r

eceiv

es th

is co

mbina

tion o

f stat

e and

va

lue, th

en st

ate is

set to

SW

_OFF

. If th

e stat

e is S

W_O

N an

d the

value

is no

t zer

o, the

comp

ress

or is

enab

led in

heat

pump

appli

catio

ns. If

the s

tate i

s SW

_NUL

or

other,

the n

etwor

k var

iable

is no

t bou

nd an

d is i

gnor

ed.

DestW

SHPE

nable

nviW

SHPE

nable

state

SW_O

FFSW

_ON

SW_N

UL

0 1 255

SW_N

ULX

Refer

to W

SHPE

nable

.value

.

Tabl

e 22

. Ene

rgy

Man

agem

ent P

oint

s. (C

ontin

ued)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.Failure Detect

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 80

nviTi

meCl

kva

lue0 t

o 100

0nv

iTime

Clk.v

alue:n

viTim

eClk

allow

s a tim

e cloc

k at o

ne no

de to

be sh

ared

with

othe

r no

des o

ver t

he ne

twor

k. nv

iTime

Clk i

s ORe

d with

the l

ocal

time c

lock s

enso

r and

the

resu

lts ar

e plac

ed in

Data

1.Occ

TimeC

lock.

TimeC

lk is

rece

ived f

rom

anoth

er no

de

and m

ay ha

ve th

e foll

owing

value

s: If t

he st

ate is

SW

_OFF

, the s

pace

is sc

hedu

led to

be

unoc

cupie

d. If t

he st

ate is

SW

_ON

and t

he va

lue is

0, th

e spa

ce is

sche

duled

to

be un

occu

pied.

If the

node

rece

ives t

his co

mbina

tion o

f stat

e and

value

, then

state

is

set to

SW

_OFF

. If th

e stat

e is S

W_O

N an

d the

value

is no

t zer

o, the

spac

e is

sche

duled

to be

occu

pied.

If the

state

is S

W_N

UL or

othe

r and

the v

alue i

s don

�t ca

re, th

e netw

ork v

ariab

le is

not b

ound

and i

s ign

ored

.De

stTim

eClk

nviTi

meCl

ksta

teSW

_OFF

SW_O

NSW

_NUL

0 1 255

SW_N

ULX

Refer

to nv

iTime

Clk.v

alue.

SrcT

imeC

lkCt

nvoT

imeC

lkva

lue0 t

o 100

0nv

oTim

eClk

repo

rts th

e cur

rent

state

of the

phys

ical ti

me cl

ock i

nput.

The

outpu

t va

lues h

ave t

he fo

llowi

ng m

eanin

gs: If

the s

tate i

s SW

_OFF

and t

he va

lue is

0, th

e tim

e cloc

k inp

ut is

confi

gure

d and

the i

nput

is op

en ci

rcuit.

If SC

HEDU

LE_M

ASTE

R_IN

is co

nfigu

red,

then t

he sc

hedu

le ma

ster in

put m

ust b

e sh

orted

to gr

ound

to re

ach t

his st

ate. If

the s

tate i

s SW

_ON

and t

he va

lue is

100

prec

ent, t

he tim

e cloc

k inp

ut is

confi

gure

d and

the i

nput

is a c

losed

circu

it. If

SCHE

DULE

_MAS

TER_

IN is

confi

gure

d, the

n the

sche

dule

maste

r inpu

t mus

t be

shor

ted to

grou

nd to

reac

h this

state

. If th

e stat

e is S

W_N

UL an

d the

value

is 0,

the

time c

lock i

nput

is no

t con

figur

ed by

Sele

ct or

the S

CHED

ULE_

MAST

ER_IN

phys

ical

input

is co

nfigu

red a

nd th

e inp

ut is

open

(nvo

IO.S

ched

uleMa

ster =

0).

SrcT

imeC

lknv

oTim

eClk

state

SW_O

FFSW

_ON

SW_N

UL

0 1 255

SW_N

ULRe

fer to

nvoT

imeC

lk.va

lue.

Tabl

e 22

. Ene

rgy

Man

agem

ent P

oint

s. (C

ontin

ued)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.Failure Detect

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

81 74-2958�2

Tabl

e 23

. Sta

tus

Poin

ts.

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

tsnr

oPgm

Ver

id[RT

U1R O M

A fou

r byte

ASC

II strin

g ind

icatin

g the

type

of no

de (m

odel)

.

nroP

gmVe

rma

jor_v

er1

R O M

Softw

are v

ersio

n.

nroP

gmVe

rmi

nor_

ver

0R O M

Softw

are v

ersio

n.

nroP

gmVe

rbu

g_ve

r0

R O M

Softw

are v

ersio

n.

nroP

gmVe

rno

de_ty

pe1

R O M

The N

odeT

ype i

s a nu

meric

iden

tifier

that

is sto

red i

n EPR

OM th

at ide

ntifie

s the

Exc

el 10

node

type

. Whe

neve

r a ne

w so

ftwar

e ver

sion o

r upg

rade

is

issue

d, thi

s is r

eflec

ted in

nroP

gmVe

r whic

h typ

ically

is re

ad by

a ne

twor

k ma

nage

ment

node

to id

entify

the n

ode t

ype.

The c

onten

ts of

nroP

gmVe

r co

ntain

comp

atible

mod

el typ

e info

rmati

on an

d is f

ixed a

t the t

ime w

hen t

he

node

softw

are i

s com

piled

.Sr

cEme

rgnv

oEme

rgEM

ERG_

NORM

ALEM

ERG_

PRES

SURI

ZEEM

ERG_

DEPR

ESSU

RIZE

EMER

G_PU

RGE

EMER

G_SH

UTDO

WN

EMER

G_NU

L

0 1 2 3 4 255

EMER

G_NO

RMAL

MX

XEm

erg i

s an e

merg

ency

outpu

t refl

ectin

g the

state

of th

e loc

ally w

ired

smok

e dete

ctor. I

f Eme

rg is

EME

RG_N

ORMA

L, the

n no s

moke

is be

ing

detec

ted by

the l

ocal

sens

or or

that

the sm

oke d

etecto

r inpu

t is no

t co

nfigu

red.

If Eme

rg is

EME

RG_P

URGE

, the l

ocall

y wire

d smo

ke se

nsor

is

indica

ting a

smok

e con

dition

.EME

RG_P

RESS

URIZ

E,

EMER

G_DE

PRES

SURI

ZE, a

nd E

MERG

_SHU

TDOW

N ar

e not

supp

orted

by

Eme

rg. If

Eme

rg is

not c

onfig

ured

then

it is

set to

EME

RG_N

ULnv

oAlar

msu

bnet

1 to 2

550

subn

et is

the LO

NWOR

KS su

bnet

numb

er (in

doma

in en

try 1

of the

node

s do

main

table)

to w

hich t

he no

de is

assig

ned.

nvoA

larm

node

0 to 1

270

node

is th

e LON

WOR

KS no

de nu

mber

(in do

main

entry

1 of

the no

des

doma

in tab

le) as

signe

d to t

he no

de.

nvoA

larm

type

0 to 2

550

type i

s the

alar

m typ

e bein

g iss

ued.

Whe

n an a

larm

cond

ition i

s no l

onge

r TR

UE, ty

pe is

set to

the s

um of

the a

larm

cond

itions

nume

ric va

lue an

d the

RE

TURN

_TO_

NORM

AL nu

meric

value

. The

type

also

is re

cord

ed in

Al

armL

og. W

hen a

new

alarm

is de

tected

, just

the co

rresp

ondin

g num

eric

value

for t

he al

arm

is re

porte

d. Re

fer to

Table

12 (E

xcel

10 A

larms

) in th

e Sy

stem

Engin

eerin

g Guid

e for

all th

e erro

r con

dition

s tha

t may

be re

porte

d.St

atusA

lmTy

pnv

oAlar

mStat

usala

rm_b

it[0]

Byte

Offse

t = 0

Bit O

ffset

= 0(

InputN

VFail

Alrm

)

FALS

ETR

UE0 1

FALS

EX

Xala

rm_b

it[0]B

yte O

ffset

= 0B

it Offs

et =

0(Inp

utNVF

ailAl

rm)a

larm_

bit [n

] co

ntains

a bit

for e

very

poss

ible a

larm

cond

ition.

Each

alar

m typ

e has

a co

rresp

ondin

g bit i

n alar

m_bit

[n] (A

larm.

type:

1.24,

witho

ut RE

TURN

_TO_

NORM

AL).

nvoA

larmS

tatus

alarm

_bit[0

]By

te Of

fset =

0Bi

t Offs

et =

1 (N

odeD

isable

Alrm

)

FALS

ETR

UE0 1

FALS

Eala

rm_b

it[0]

Byte

Offse

t = 0

Bit O

ffset

= 1

(Nod

eDisa

bleAl

rm)

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 82

nvoA

larmS

tatus

alarm

_bit[0

]By

te Of

fset =

0Bi

t Offs

et =

2 (S

enso

rFail

Alrm

)

FALS

ETR

UE0 1

FALS

Eala

rm_b

it[0]

Byte

Offse

t = 0

Bit O

ffset

= 2

(Sen

sorF

ailAl

rm)

nvoA

larmS

tatus

alarm

_bit[0

]By

te Of

fset =

0Bi

t Offs

et =

3 (F

rostP

rotec

tAlrm

)

FALS

ETR

UE0 1

FALS

Eala

rm_b

it[0]

Byte

Offse

t = 0

Bit O

ffset

= 3

(Fro

stPro

tectA

lrm)

nvoA

larmS

tatus

alarm

_bit[0

]By

te Of

fset =

0Bi

t Offs

et =

4 (In

valid

SetP

tAlrm

)

FALS

ETR

UE0 1

FALS

Eala

rm_b

it[0]

Byte

Offse

t = 0

Bit O

ffset

= 4

(Inva

lidSe

tPtA

lrm)

nvoA

larmS

tatus

alarm

_bit[0

]By

te Of

fset =

0Bi

t Offs

et =

5 (L

ossA

irFlow

Alrm

)

FALS

ETR

UE0 1

FALS

Eala

rm_b

it[0]

Byte

Offse

t = 0

Bit O

ffset

= 5

(Los

sAirF

lowAl

rm)

nvoA

larmS

tatus

alarm

_bit[0

]By

te Of

fset =

0Bi

t Offs

et =

6 (D

irtyFil

terAl

rm)

FALS

ETR

UE0 1

FALS

Eala

rm_b

it[0]

Byte

Offse

t = 0

Bit O

ffset

= 6

(Dirty

Filter

Alrm

)nv

oAlar

mStat

usala

rm_b

it[0]

Byte

Offse

t = 0

Bit O

ffset

= 7

(Smo

keAl

rm)

FALS

ETR

UE0 1

FALS

Eala

rm_b

it[0]

Byte

Offse

t = 0

Bit O

ffset

= 7

(Smo

keAl

rm)

nvoA

larmS

tatus

alarm

_bit[1

]By

te Of

fset =

1Bi

t Offs

et =

0 (Ia

qOve

rRide

Alrm

)

FALS

ETR

UE0 1

FALS

Eala

rm_b

it[1]

Byte

Offse

t = 1

Bit O

ffset

= 0

(IaqO

verR

ideAl

rm)

Tabl

e 23

. Sta

tus

Poin

ts. (

Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

83 74-2958�2

Alar

mLog

1nv

oAlar

mLog

type[0

]0 t

o 255

(A

larmT

ypeL

og0)

(Alar

mTyp

eLog

1)(A

larmT

ypeL

og2)

(Alar

mTyp

eLog

3)(A

larmT

ypeL

og4)

NO_A

LARM

INPU

T_NV

_FAI

LURE

NODE

_DIS

ABLE

DSE

NSOR

_FAI

LURE

FROS

T_PR

OTEC

TION

INVA

LID_S

ET_P

OINT

LOSS

_OF_

AIR_

FLOW

DIRT

Y_FI

LTER

SMOK

E_AL

ARM

IAQ_

OVER

RIDE

LOW

_LIM

_ECO

N_CL

OSE

rINPU

T_NV

_FAI

LURE

rNOD

E_DI

SABL

EDrS

ENSO

R_FA

ILURE

rFRO

ST_P

ROTE

CTIO

NrIN

VALID

_SET

_POI

NTrL

OSS_

OF_A

IR_F

LOW

rDIR

TY_F

ILTER

rSMO

KE_A

LARM

rIAQ_

OVER

RIDE

rLOW

_LIM

_ECO

N_CL

OSE

ALAR

M_NO

TIFY

_DIS

ABLE

D

0 1 2 3 4 5 6 7 8 9 10 129

130

131

132

133

134

135

136

137

138

255

NO_A

LARM

Xyp

e[0]

0 to 2

55(A

larmT

ypeL

og0)

(Alar

mTyp

eLog

1)(A

larmT

ypeL

og2)

(Alar

mTyp

eLog

3)(A

larmT

ypeL

og4)

A su

pervi

sory

node

may

poll t

he A

larmL

og ou

tput fo

r a sh

ort a

larm

histor

y. Th

e las

t five

alar

m re

ports

sent

via nv

oAlar

m ar

e rep

orted

via A

larmL

og.

Whe

n ALA

RM_N

OTIF

Y_DI

SABL

ED is

enter

ed in

to the

log,

furthe

r alar

ms

or re

turn t

o nor

mals

are n

ot en

tered

into

the lo

g, un

til ala

rm re

portin

g is

again

enab

led. If

Alar

m is

boun

d and

not b

eing a

ckno

wled

ged,

the la

st ala

rm re

port

enter

ed in

to Al

armL

og is

the o

ne th

at wa

s not

ackn

owled

ged.S

ee A

larm

and A

larmS

tatus

for r

elated

subje

cts.ty

pe [n

] sp

ecifie

s the

alar

m tha

t was

issu

ed vi

a Alar

m. S

ee A

larm

for th

e alar

m typ

es us

ed in

Alar

mLog

. The

newe

st ala

rm is

repo

rted i

n typ

e[0] a

nd th

e old

est is

repo

rted i

n typ

e[4]. W

hen a

new

entry

is m

ade t

o the

log,

the

oldes

t entr

y is l

ost.

nvoD

ata1

(nvo

CtlD

ataG1

)Fie

ldNo

UPDA

TE_A

LL_F

IELD

SMO

DE_F

IELD

EFFE

CT_O

CC_F

IELD

OVER

RIDE

_FIE

LDSC

HED_

OCC_

FIEL

DOC

C_TI

ME_C

LOCK

_FIE

LDNE

T_MA

N_OC

C_FI

ELD

SEN_

OCC_

FIEL

DEC

ON_E

NABL

E_FI

ELD

PROO

F_AI

R_FL

OW_F

IELD

CALC

_OD_

ENTH

ALPY

_FIE

LDCA

LC_R

A_EN

THAL

PY_F

IELD

HEAT

_STA

GES_

ON_F

IELD

COOL

_STA

GES_

ON_F

IELD

FREE

1_OU

T_FI

ELD

FREE

2_OU

T_FI

ELD

OCC_

STAT

US_O

UT_F

IELD

FAN_

ON_F

IELD

AUX_

ECON

_OUT

_FIE

LDEC

ON_F

LOAT

_SYN

CH_F

IELD

DLC_

SHED

_FIE

LDIA

Q_OV

ERRI

DE_F

IELD

SMOK

E_MO

NITO

R_FI

ELD

WIN

DOW

_OPE

N_FI

ELD

DIRT

Y_FI

LTER

_FIE

LDSH

UTDO

WN_

FIEL

DMO

N_SW

ITCH

_FIE

LDW

SHP_

ENAB

LE_F

IELD

UPDA

TE_N

O_FI

ELDS

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 127

UPDA

TE_A

LL_F

IELD

SFie

ldNo:

nvoD

ata1 a

nd nv

oCtlD

ataG1

are o

utput

netw

ork v

ariab

les

indica

ting t

he no

de st

atus.

The i

nform

ation

conta

ined i

n the

se ne

twor

k va

riable

s are

typic

ally u

sed t

o disp

lay th

e nod

e stat

us on

an op

erato

r ter

mina

l, use

d in a

tren

d log

, or u

sed i

n a co

ntrol

proc

ess.

The i

nform

ation

co

ntaine

d in n

voCt

lData

G1 an

d nvo

Data1

are i

denti

cal. n

voCt

lData

G1 us

es

the S

GPUC

mec

hanis

m to

upda

te the

statu

s or v

alues

. The

fields

in

nvoD

ata ar

e upd

ated w

hen n

etwor

k var

iables

are p

olled

by th

e rec

eiver.

Th

en ev

ery s

ix se

cond

s the

diffe

renc

e betw

een t

he fie

ld in

nvoD

ata an

d nv

oCtlD

ataG

is ca

lculat

ed. If

the d

iffere

nce i

s sign

ifican

t the f

ield i

s upd

ated

acco

rding

to th

e SGP

UC m

echa

nism.

Fiel

dNo i

ndica

tes w

hich o

ther d

ata

field

in the

SGP

UC ne

twor

k var

iable

has c

hang

ed si

nce t

he la

st tim

e it w

as

sent

on th

e netw

ork a

ccor

ding t

o the

SGP

UC m

echa

nism.

If Fie

ldNo i

s UP

DATE

_ALL

_FIE

LDS,

then

all fi

elds h

ave b

een u

pdate

d. If F

ieldN

o is

UPDA

TE_N

O_FI

ELDS

, then

no fie

lds ha

ve be

en up

dated

rece

ntly.

Tabl

e 23

. Sta

tus

Poin

ts. (

Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 84

Statu

sMod

env

oData

1 (n

voCt

lData

G1)

Mode

STAR

T_UP

_WAI

THE

ATCO

OLOF

F_MO

DEDI

SABL

ED_M

ODE

EMER

G_HE

ATSM

OKE_

EMER

GENC

YFR

EEZE

_PRO

TECT

MANU

ALFA

CTOR

Y_TE

STFA

N_ON

LY

0 1 2 3 4 5 6 7 8 9 10

STAR

T_UP

_WAI

TX

Mode

: The

resu

lt of th

e con

trolle

r dete

rmini

ng w

hich m

ode o

f ope

ratio

n it

curre

ntly i

s in.

At ea

ch po

wer-u

p, the

contr

oller

rema

ins in

the S

tart-U

p and

W

ait m

ode (

a ran

dom

time f

rom

0 to 2

0 minu

tes th

at is

base

d on t

he un

its

netw

ork n

umbe

r). A

fter t

hat p

eriod

, the m

ode c

hang

es to

initia

lize a

ctuato

rs tha

t will

fully

close

the d

ampe

r and

valve

actua

tors t

o ins

ure f

ull tr

avel

when

un

der p

rogr

am co

ntrol.

The

vario

us ot

her m

odes

are d

ue to

norm

al op

erati

on as

well

as m

anua

l and

netw

ork c

omma

nds.

Statu

sOcc

nvoD

ata1

(nvo

CtlD

ataG1

)Ef

fectO

ccOC

_OCC

UPIE

DOC

_UNO

CCUP

IED

OC_B

YPAS

SOC

_STA

NDBY

OC_N

UL

0 1 2 3 255

OC_N

ULX

Effec

tOcc

: Res

ult of

contr

oller

supe

rvisin

g the

vario

us O

ccup

ied co

ntroll

ing

inputs

and d

ecidi

ng w

hich o

ne to

use.

See S

tatus

inOcy

, Des

tSch

edOc

c, Ma

nualO

cc an

d Stat

usOv

rd.

Statu

sOvrd

nvoD

ata1

(nvo

CtlD

ataG1

)Ov

errid

eOC

_OCC

UPIE

DOC_

UNOC

CUPI

EDOC

_BYP

ASS

OC_S

TAND

BYOC

_NUL

0 1 2 3 255

OC_N

ULX

Over

ride:

Is the

effec

tive m

anua

l ove

rride

state

arbit

rated

from

NetM

anOc

c, the

wall

mod

ule ov

errid

e butt

on an

d the

Byp

ass T

imer.

Statu

sSch

ednv

oData

1 (n

voCt

lData

G1)

Sche

dOcc

OC_O

CCUP

IED

OC_U

NOCC

UPIE

DOC

_BYP

ASS

OC_S

TAND

BYOC

_NUL

0 1 2 3 255

OC_N

ULX

DestS

ched

Occ:

DestS

ched

Occ i

s calc

ulated

from

Occ

TimeC

lock a

nd

nviTo

dEve

nt.Cu

rrentS

tate u

sing t

he fo

llowi

ng lo

gic: If

nv

iTodE

vent.

Curre

ntStat

e is O

C_OC

CUPI

ED an

d Occ

TimeC

lock i

s ST

_NUL

, then

Des

tSch

edOc

c is O

C_OC

CUPI

ED. If

nv

iTodE

vent.

Curre

ntStat

e is O

C_UN

OCCU

PIED

and O

ccTim

eCloc

k is

ST_N

UL, th

en D

estS

ched

Occ i

s OC_

UNOC

CUPI

ED. If

nv

iTodE

vent.

Curre

ntStat

e is O

C_ST

ANDB

Y an

d Occ

TimeC

lock i

s ST

_NUL

, then

Des

tSch

edOc

c is O

C_ST

ANDB

Y. If

nviTo

dEve

nt.Cu

rrentS

tate i

s don

�t car

e and

Occ

TimeC

lock i

s ST_

ON, th

en

DestS

ched

Occ i

s OC_

OCCU

PIED

. If nv

iTodE

vent.

Curre

ntStat

e is d

on�t

care

and O

ccTim

eCloc

k is S

T_OF

F, the

n Des

tSch

edOc

c is

OC_U

NOCC

UPIE

D. O

C_OC

CUPI

ED m

eans

the s

pace

is sc

hedu

led to

be

occu

pied.

OC_U

NOCC

UPIE

D me

ans t

he sp

ace i

s sch

edule

d to b

e un

occu

pied.

OC_S

TAND

BY m

eans

the s

pace

is sc

hedu

led to

be in

a sta

ndby

state

some

wher

e betw

een O

C_OC

CUPI

ED an

d OC

_UNO

CCUP

IED.

TimeC

lckOc

cnv

oData

1 (n

voCt

lData

G1)

OccT

imeC

lock

ST_O

FFST

_LOW

ST_M

EDST

_HIG

HST

_ON

ST_N

UL

0 1 2 3 4 255

ST_N

ULX

OccT

imeC

lock:

OccT

imeC

lock s

hows

the s

tate o

f the p

hysic

al tim

e cloc

k inp

ut via

nvoIO

.Occ

TimeC

lock O

Red w

ith nv

iTime

Clk.

Valid

enum

erate

d va

lues a

re: S

T_OF

F me

ans O

C_UN

OCCU

PIED

whe

n eith

er th

e tim

e cloc

k inp

ut is

confi

gure

d and

nvoIO

.Occ

TimeC

lock i

s 0 an

d nviT

imeC

lk is

not

SW_O

N or

nviTi

meCl

k.stat

e is S

W_O

FF an

d nvo

IO.O

ccTI

meCl

ock i

s not

1. ST

_ON

mean

s OC_

OCCU

PIED

whe

n eith

er th

e tim

e cloc

k inp

ut is

confi

gure

d and

nvoIO

.Occ

TimeC

lock i

s 1 or

nviTi

meCl

k.stat

e is S

W_O

N.

ST_N

UL m

eans

that

the lo

cal ti

me cl

ock i

nput

is no

t con

figur

ed by

nc

iIoSe

lect a

nd nv

iTime

Clk.s

tate i

s SW

_NUL

. The

re is

no tim

e cloc

k co

nfigu

red o

r bou

nd to

the n

ode.

Tabl

e 23

. Sta

tus

Poin

ts. (

Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

85 74-2958�2

Statu

sMan

Occ

nvoD

ata1

(nvo

CtlD

ataG1

)Ne

tMan

Occ

OC_O

CCUP

IED

OC_U

NOCC

UPIE

DOC

_BYP

ASS

OC_S

TAND

BYOC

_NUL

0 1 2 3 255

OC_N

ULX

NetM

anOc

c: Ne

tMan

Occ r

epor

ts the

netw

ork m

anua

l occ

upan

cy st

ate fr

om

nviM

anOc

c. Th

e vali

d enu

mera

ted st

ates a

re: O

C_OC

CUPI

ED in

dicate

s oc

cupie

d OC_

UNOC

CUPI

ED in

dicate

s not

occu

pied O

C_BY

PASS

ind

icates

that

the sp

ace i

s byp

ass o

ccup

ied fo

r nc

iAux

2SetP

t.uiB

ypas

sTim

e sec

onds

after

nviM

anOc

c is f

irst s

et to

OC_B

YPAS

S OC

_STA

NDBY

indic

ates t

hat th

e spa

ce is

stan

dby.

OC_N

UL

mean

s tha

t no m

anua

l ove

rride

is ac

tive.

Statu

sOcy

Sen

nvoD

ata1

(nvo

CtlD

ataG1

)Se

nOcc

OC_O

CCUP

IED

OC_U

NOCC

UPIE

DOC

_BYP

ASS

OC_S

TAND

BYOC

_NUL

0 1 2 3 255

OC_N

ULX

SenO

cc: S

enOc

c ind

icates

the c

urre

nt sta

te of

the se

nsed

occu

panc

y and

is

calcu

lated

from

nviS

enso

rOcc

and t

he lo

cal o

ccup

ancy

sens

or vi

a nv

oIO.O

ccup

ancy

Sens

or. T

he lo

cal s

enso

r and

nviS

enso

rOcc

are O

Red

togeth

er. If

eithe

r the

loca

l sen

sor o

r nviS

enso

rOcc

show

s occ

upan

cy, th

en

SenO

cc sh

ows o

ccup

ancy

. The

valid

enum

erate

d valu

es ar

e: OC

_OCC

UPIE

D me

ans t

hat o

ccup

ancy

is se

nsed

by on

e or m

ore

sens

or.OC

_UNO

CCUP

IED

mean

s tha

t no o

ccup

ancy

is se

nsed

by an

y se

nsor

s.OC_

NUL m

eans

no lo

cal s

enso

r is co

nfigu

red a

nd nv

iSen

sorO

cc

has f

ailed

to be

rece

ived p

eriod

ically

(bou

nd or

not b

ound

).St

atusE

conE

nnv

oData

1 (n

voCt

lData

G1)

Econ

Enab

leST

_OFF

ST_L

OWST

_MED

ST_H

IGH

ST_O

NST

_NUL

0 1 2 3 4 255

ST_N

ULX

Econ

Enab

le: E

conE

nable

indic

ates t

he cu

rrent

suita

bility

of ou

tdoor

air f

or

use i

n coo

ling u

sed b

y the

contr

ol pr

oces

s Eco

nEna

ble is

perio

dicall

y ca

lculat

ed ei

ther f

rom

the se

nsor

(s) sp

ecifie

d by n

ciCon

fig.E

conE

nable

or

from

nviE

con.

Whe

n nviE

con.s

tate i

s not

SW_N

UL, th

en th

e loc

al inp

uts

are i

gnor

ed an

d nviE

con.s

tate i

s use

d ins

tead.

See n

ciCon

fig.E

conE

nable

. Th

e vali

d enu

mera

ted va

lues a

re: S

T_OF

F me

ans t

he ou

tdoor

air is

not

suita

ble to

augm

ent c

oolin

g. ST

_ON

mean

s the

outdo

or ai

r is su

itable

to

augm

ent c

oolin

g.ST_

NUL m

eans

no lo

cal s

enso

r is se

lected

by

nciC

onfig

.Eco

nEna

ble, o

r the

selec

ted lo

cal s

enso

r has

faile

d or h

as no

t be

en co

nfigu

red b

y nciI

oSele

ct, an

d tha

t nviE

con.s

tate i

s SW

_NUL

. The

ou

tdoor

air is

cons

idere

d uns

uitab

le for

cooli

ng.

SaFa

nStat

usnv

oData

1 (n

voCt

lData

G1)

Proo

fAirF

lowST

_OFF

ST_L

OWST

_MED

ST_H

IGH

ST_O

NST

_NUL

0 1 2 3 4 255

ST_N

ULX

Proo

fAirF

low: P

roofA

irFlow

indic

ates t

he cu

rrent

state

of the

Pro

ofAirF

low

switc

h use

d by t

he co

ntrol

proc

ess a

nd is

read

by th

e loc

al se

nsor

via

nvoIO

.Pro

ofAirF

low. T

he va

lid en

umer

ated v

alues

are:

ST_O

FF m

eans

air

flow

is no

t dete

cted.

ST_O

N me

ans a

ir flow

is de

tected

. ST_

NUL m

eans

no

air flo

w sw

itch i

s con

figur

ed.

OaEn

thCalc

nvoD

ata1

(nvo

CtlD

ataG1

)siC

alcOD

Entha

lpyS7

btu/lb

0 to 1

00SI

_INVA

LIDX

siCalc

ODEn

thalpy

S7: s

iCalc

ODEn

thalpy

S7 is

the c

alcula

ted ou

tdoor

air

entha

lpy in

btu /

lb ca

lculat

ed fr

om th

e siO

utdoo

rTemp

S7 an

d ub

Outdo

orHu

midit

yS1.

siCalc

ODEn

thalpy

S7 is

used

to de

termi

ne th

e su

itabil

ity of

outsi

de ai

r for

cooli

ng w

hen n

ciCon

fig.E

conE

nable

is

SING

LE_E

NTH

and b

oth ou

tdoor

temp

eratu

re an

d hum

idity

sens

ors a

re

pres

ent. s

iCalc

ODEn

thalpy

S7 is

comp

ared

to th

e enth

alpy s

etpoin

t stor

ed

in nc

iAux

1SetP

ts.ub

OdEn

thalpy

Enab

leS2.

RaEn

thCalc

nvoD

ata1

(nvo

CtlD

ataG1

)siC

alcRA

Entha

lpyS7

btu/lb

0 to 1

00SI

_INVA

LIDX

siCalc

RAEn

thalpy

S7: s

iCalc

RAEn

thalpy

S7 is

the c

alcula

ted re

turn a

ir en

thalpy

in bt

u / lb

calcu

lated

from

the s

iRetu

rnTe

mpS7

and

ubRe

turnH

umidi

tyS1.

siCalc

RAEn

thalpy

S7 is

used

to de

termi

ne th

e su

itabil

ity of

outsi

de ai

r for

cooli

ng w

hen n

ciCon

fig.E

conE

nable

is

DIFF

_ENT

H an

d both

outdo

or an

d retu

rn (o

r spa

ce) t

empe

ratur

e sen

sors

and h

umidi

ty se

nsor

s are

pres

ent. S

enso

rs ma

y be p

hysic

ally c

onne

cted t

o the

node

or av

ailab

le ov

er th

e netw

ork.

Tabl

e 23

. Sta

tus

Poin

ts. (

Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 86

HeatS

tgsOn

nvoD

ata1

(nvo

CtlD

ataG1

)He

atStag

esOn

0 to 4

0X

HeatS

tages

On: H

eatS

tages

On in

dicate

s how

man

y hea

ting s

tages

are o

n. If t

he no

de is

contr

olling

a he

at pu

mp, H

eatS

tages

On in

dicate

s how

man

y au

xiliar

y hea

ting s

tages

are t

urne

d on.

CoolS

tgsOn

nvoD

ata1

(nvo

CtlD

ataG1

)Co

olStag

esOn

0 to 4

0X

CoolS

tages

On: C

oolS

tages

On in

dicate

s how

man

y com

pres

sor s

tages

are

on. If

the n

ode i

s con

trollin

g a he

at pu

mp, c

ompr

esso

r stag

es ar

e tur

ned o

n for

both

heati

ng or

cooli

ng.

Free

1Stat

nvoD

ata1

(nvo

CtlD

ataG1

)Fr

ee1O

utFA

LSE

TRUE

0 1FA

LSE

XFr

ee1O

ut: F

ree1

Out in

dicate

s the

state

of F

REE1

_OUT

digit

al ou

tput. 1

me

ans o

n, an

d 0 m

eans

off.

Free

2Stat

nvoD

ata1

(nvo

CtlD

ataG1

)Fr

ee2O

utFA

LSE

TRUE

0 1FA

LSE

XFr

ee2O

ut: F

ree2

Out in

dicate

s the

state

of F

REE2

_OUT

digit

al ou

tput. 1

me

ans o

n, an

d 0 m

eans

off.

OccS

tatOu

tnv

oData

1 (n

voCt

lData

G1)

OccS

tatus

Out

FALS

ETR

UE0 1

FALS

EX

OccS

tatus

Out: O

ccSt

atusO

ut ind

icates

the s

tate o

f the

OCCU

PANC

Y_ST

ATUS

_OUT

digit

al ou

tput. 1

mea

ns on

(not

OC_U

NOCC

UPIE

D), a

nd 0

mean

s off (

OC_U

NOCC

UPIE

D).

SaFa

nnv

oData

1 (n

voCt

lData

G1)

FanO

nFA

LSE

TRUE

0 1FA

LSE

XFa

nOn:

FanO

n ind

icates

the s

tate o

f the F

AN_O

UT di

gital

outpu

t. 1 m

eans

on

, and

0 me

ans o

ff.St

atusE

conO

utnv

oData

1 (n

voCt

lData

G1)

AuxE

conO

utFA

LSE

TRUE

0 1FA

LSE

XAu

xEco

nOut:

Aux

Econ

Out in

dicate

s the

state

of th

e AUX

_ECO

N_OU

T dig

ital o

utput.

1 me

ans t

hat th

e pac

kage

d eco

nomi

zer is

enab

led, a

nd 0

mean

s the

econ

omize

r is di

sable

d. A

pack

aged

econ

omize

r is al

ways

tre

ated a

s the

first

stage

of co

oling

whe

n an e

cono

mize

r is co

nfigu

red b

y nc

iIoSe

lect.

nvoD

ata1

(nvo

CtlD

ataG1

)Ec

onFlo

atSyn

chFA

LSE

TRUE

0 1FA

LSE

Econ

FloatS

ynch

: Eco

nFloa

tSyn

ch in

dicate

s tha

t the e

cono

mize

r dam

per

motor

is be

ing sy

nchr

onize

d with

the r

epor

ted ec

onom

izer p

ositio

n by

drivi

ng th

e dam

per f

or a

perio

d lon

ger t

han i

t take

s to f

ully c

lose t

he

damp

er. T

he re

porte

d eco

nomi

zer p

ositio

n is s

ynch

roniz

ed w

hene

ver a

n en

dpoin

t is re

ache

d (ful

l ope

n or f

ull cl

ose)

.and w

hen t

he el

apse

d tim

e sin

ce th

e las

t syn

chro

nizati

on is

24 ho

urs.

DlcS

hed

nvoD

ata1

(nvo

CtlD

ataG1

)Dl

cShe

dFA

LSE

TRUE

0 1FA

LSE

DlcS

hed:

DlcS

hed i

ndica

tes th

e stat

e of n

viDlcS

hed.

Whe

n DlcS

hed i

s 1,

dema

nd lim

it con

trol s

et by

an en

ergy

man

agem

ent n

ode i

s acti

ve. If

the

effec

tive o

ccup

ancy

is O

C_OC

CUPI

ED or

OC_

STAN

DBY

when

dema

nd

limit c

ontro

l is ac

tive,

then t

he se

tpoint

is sh

ifted b

y nc

iAux

1SetP

t.siD

lcBum

pTem

pS7 i

n the

ener

gy sa

ving d

irecti

on. W

hen

DlcS

hed i

s 0, d

eman

d lim

it con

trol is

inac

tive.

If nviD

lcShe

d fail

s to b

e re

ceive

d per

iodica

lly or

nviD

lcShe

d bec

omes

0, th

en th

e setp

oint is

ramp

ed

back

to th

e orig

inal s

etpoin

t ove

r a 30

minu

te int

erva

l.

Tabl

e 23

. Sta

tus

Poin

ts. (

Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

87 74-2958�2

Statu

sIaqO

vrnv

oData

1 (n

voCt

lData

G1)

IaqOv

erRi

deFA

LSE

TRUE

0 1FA

LSE

XIaq

Over

Ride

: Whe

n an e

cono

mize

r is co

nfigu

red,

IaqOv

erRi

de in

dicate

s the

curre

nt sta

te of

the in

door

air q

uality

, an i

s use

d by t

he co

ntrol

proc

ess

to op

en th

e eco

nomi

zer d

ampe

r to l

et in

more

outsi

de ai

r. 1 m

eans

poor

ind

oor a

ir qua

lity, a

nd 0

mean

s ind

oor a

ir qua

lity is

OK.

Whe

n Iaq

Over

Ride

is

1, the

IAQ_

OVER

RIDE

alar

m is

initia

ted. Ia

qOve

rRide

indic

ates p

oor a

ir qu

ality

if the

analo

g sen

sor O

R a d

igital

sens

or (lo

cal o

r via

netw

ork)

show

s po

or ai

r qua

lity. S

pecif

ically

, if nv

oData

2.siS

pace

Co2S

0 is n

ot SI

_INVA

LID,

and e

xcee

ds nc

iAux

1SetP

t.siC

O2Iaq

LimitS

0, the

n poo

r air q

uality

is

detec

ted. A

lso if

nviIa

qOvr.

state

is SW

_ON,

then

poor

air q

uality

is

detec

ted. O

r if a

local

digita

l inpu

t is co

nfigu

red a

s IAQ

_OVE

RRID

E_IN

and

nvoIO

.IaqO

verR

ide is

1 the

n poo

r air q

uality

is al

so de

tected

. Whe

n poo

r air

quali

ty is

detec

ted, th

e eco

nomi

zer m

inimu

m po

sition

is se

t to

nciA

ux1S

etPts.

ubEc

onIaq

PosS

0, ins

tead o

f nc

iAux

1SetP

ts.ub

Econ

MinP

osS0

.Whe

n an e

cono

mize

r is no

t con

figur

ed,

IaqOv

erRi

de is

0.St

atusS

moke

nvoD

ata1

(nvo

CtlD

ataG1

)Sm

okeM

onito

rFA

LSE

TRUE

0 1FA

LSE

XSm

okeM

onito

r: Sm

okeM

onito

r indic

ates t

he cu

rrent

state

of the

Sm

okeM

onito

r inpu

t use

d by t

he co

ntrol

proc

ess a

nd is

read

from

anoth

er

node

via n

viEme

rg or

the l

ocal

sens

or vi

a nvo

IO.S

moke

Monit

or. If

eithe

r nv

iEme

rg is

not E

MERG

_NOR

MAL o

r nvo

IO.S

moke

Monit

or is

1, th

en

Smok

eMon

itor is

1 me

aning

that

smok

e is d

etecte

d. Ot

herw

ise

Smok

eMon

itor is

0, m

eanin

g smo

ke is

not d

etecte

d. W

hen s

moke

mon

itor

is 1,

the al

gorith

m co

ntrols

as pe

r the

settin

gs fo

und i

n nc

iCon

fig.S

moke

Contr

ol.St

atusW

ndw

nvoD

ata1

(nvo

CtlD

ataG1

)W

indow

Open

FALS

ETR

UE0 1

FALS

EX

Wind

owOp

en: W

indow

Open

indic

ates t

he cu

rrent

state

of the

wind

ow

sens

ors a

nd is

calcu

lated

from

nviW

indow

state

and t

he lo

cal o

ccup

ancy

se

nsor

via n

voIO

.Wind

owOp

en. T

he lo

cal s

enso

r and

nviW

indow

are O

Red

togeth

er. If

eithe

r the

loca

l sen

sor o

r nviW

indow

show

s tha

t the w

indow

is

open

(nvo

IO.W

indow

Open

= 1

or nv

iWind

ow.st

ate =

SW

_ON)

, then

W

indow

Open

show

s tha

t the w

indow

is op

en. 1

mea

ns th

at the

wind

ow is

op

en an

d 0 m

eans

that

the w

indow

is cl

osed

. Whe

n the

wind

ow is

open

, the

contr

oller

mod

e is s

witch

ed to

FRE

EZE_

PROT

ECT.

Statu

sFilte

rnv

oData

1 (n

voCt

lData

G1)

Dirty

Filter

FALS

ETR

UE0 1

FALS

EX

Dirty

Filter

: Dirty

Filter

indic

ates t

he st

ate of

the a

ir filte

r via

the

nvoIO

.Dirty

Filter

digit

al inp

ut or

the n

voDa

ta1.si

Filter

Pres

sure

S10 a

nalog

inp

ut. If

nvoD

ata1.s

iFilte

rPre

ssur

eS10

exce

eds

nciA

ux2S

etPt.u

bFilte

rPre

ssSt

PtS5

, a di

rty fil

ter is

indic

ated.

Dirty

Filter

is se

t to

1 whe

n a di

rty fil

ter ha

s bee

n dete

cted b

y eith

er m

ethod

for o

ne m

inute.

Di

rtyFil

ter is

set to

0 wh

en a

dirty

filter

has n

ot be

en de

tected

by ei

ther

metho

d for

one m

inute.

Whe

n Dirty

Filter

is 1,

a DI

RTY_

FILT

ER al

arm

is ge

nera

ted.

ShutD

own

nvoD

ata1

(nvo

CtlD

ataG1

)Sh

utDow

nFA

LSE

TRUE

0 1FA

LSE

XSh

utDow

n: Sh

utDow

n ind

icates

the s

tate o

f the S

hutD

own i

nput

via

nvoIO

.Shu

tDow

n. 1 m

eans

a Sh

utDow

n is b

eing c

omma

nded

and 0

mea

ns

norm

al op

erati

on.

StatF

reez

eStat

nvoD

ata1

(nvo

CtlD

ataG1

)Co

ilFre

ezeS

tatFA

LSE

TRUE

0 1FA

LSE

MX

XSt

atFre

ezeS

tat: S

tatFr

eeze

Stat

gives

the s

tate o

f the c

oolin

g coil

contr

olled

by

the C

VAHU

. Fals

e (0)

it is

not fr

eezin

g or T

rue (

1) it

is fre

ezing

. N

OTE:

Only

use t

his U

ser A

ddre

ss w

hen u

sing E

-Visi

on.

Monit

orSw

nvoD

ata1

(nvo

CtlD

ataG1

)Mo

nSwi

tchFA

LSE

TRUE

0 1FA

LSE

XMo

nSwi

tch: M

onSw

itch i

s the

state

of th

e digi

tal in

put w

ired t

o a ge

nera

l pu

rpos

e mon

itor s

witch

via n

voIO

.Mon

Switc

h. 1 m

eans

that

the sw

itch i

s clo

sed a

nd 0

mean

s tha

t the s

witch

is op

en.

Tabl

e 23

. Sta

tus

Poin

ts. (

Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 88

WSH

PEna

blenv

oData

1 (n

voCt

lData

G1)

WSH

PEna

bleFA

LSE

TRUE

0 1FA

LSE

XW

SHPE

nable

: WSH

PEna

ble re

ports

the s

tate o

f the c

urre

nt sta

te of

nviW

SHPE

nable

. The

state

s for

nviW

SHPE

nable

are a

s foll

ows:

If nv

iWSH

PEna

ble.st

ate is

SW

_OFF

and t

he nv

iWSH

PEna

ble.va

lue is

0,

then W

SHPE

nable

is 0

(Disa

ble W

ater S

ource

Hea

t Pum

p). If

nv

iWSH

PEna

ble.st

ate is

SW

_ON

and t

he nv

iWSH

PEna

ble.va

lue is

0, th

en

WSH

PEna

ble is

0 (D

isable

Wate

r Sou

rce H

eat P

ump)

. If

nviW

SHPE

nable

.state

is S

W_O

N an

d the

nviW

SHPE

nable

.value

is no

t 0,

then W

SHPE

nable

is 1

(Ena

ble W

ater S

ource

Hea

t Pum

p). If

nv

iWSH

PEna

ble.st

ate is

SW

_NUL

and t

he nv

iWSH

PEna

ble.va

lue is

any

value

, then

WSH

PEna

ble is

1 (E

nable

Wate

r Sou

rce H

eat P

ump w

hen

nviW

SHPE

nable

is no

t bou

nd to

anoth

er no

de).

nvoD

ata2

(nvo

CtlD

ataG2

)Fie

ldNo

UPDA

TE_A

LL_F

IELD

SBY

PASS

_TIM

ER_F

IELD

TEMP

_CON

TROL

_PT_

FIEL

DSP

ACE_

TEMP

_FIE

LDDI

SCHA

RGE_

TEMP

_FIE

LDDI

SCHA

RGE_

SET_

PT_F

IELD

RETU

RN_T

EMP_

FIEL

DRE

TURN

_HUM

IDIT

Y_FI

ELD

RETU

RN_E

NTHA

LPY_

FIEL

DOU

TDOO

R_TE

MP_F

IELD

OUTD

OOR_

HUMI

DITY

_FIE

LDOU

TDOO

R_EN

THAL

PY_F

IELD

FILT

ER_P

RESS

URE_

FIEL

DSP

ACE_

CO2_

FIEL

DMO

NITO

R_VO

LTS_

FIEL

DCO

OL_P

OS_F

IELD

HEAT

_POS

_FIE

LDEC

ON_P

OS_F

IELD

UPDA

TE_N

O_FI

ELDS

UPDA

TE_A

LL_F

IELD

Snv

oData

2. Fie

ldNo:

nvoD

ata2 a

nd nv

oCtlD

ataG2

are o

utput

netw

ork

varia

bles i

ndica

ting t

he no

de st

atus.

The i

nform

ation

conta

ined i

n the

se

netw

ork v

ariab

les ar

e typ

ically

used

to di

splay

the n

ode s

tatus

on an

op

erato

r ter

mina

l, use

d in a

tren

d log

, or u

sed i

n a co

ntrol

proc

ess.

The

infor

matio

n con

taine

d in n

voCt

lData

G2 an

d nvo

Data2

are i

denti

cal.

nvoD

ata2 i

s a po

lled n

etwor

k var

iable

and m

ust b

e poll

ed by

the r

eceiv

er.

nvoC

tlData

G2 us

es th

e SGP

UC m

echa

nism.

Fiel

dNo i

ndica

tes w

hich o

ther

data

field

in the

SGP

UC ne

twor

k var

iable

has c

hang

ed si

nce t

he la

st tim

e it

was s

ent o

n the

netw

ork a

ccor

ding t

o the

SGP

UC m

echa

nism.

BypT

imer

nvoD

ata2

(nvo

CtlD

ataG2

)uiB

ypas

sTim

ermi

nutes

0 to 2

880

0X

uiByp

assT

imer

: The

time l

eft in

the b

ypas

s tim

er is

uiBy

pass

Timer

minu

tes.

If uiB

ypas

sTim

er is

zero

, then

the b

ypas

s tim

er is

not r

unnin

g. If

uiByp

assT

imer

is no

t zer

o, it i

s dec

reme

nted e

very

minu

te.Rm

Temp

ActS

ptnv

oData

2 (n

voCt

lData

G2)

siTem

pCon

trolP

tS7

Degr

ees F

50 to

85De

gree

s C(1

0 to 2

9)

SI_IN

VALID

XsiT

empC

ontro

lPtS

7: Th

e cur

rent

tempe

ratur

e con

trol p

oint (

such

that,

the

curre

nt ac

tual s

pace

temp

eratu

re se

tpoint

whic

h the

contr

oller

is pr

esen

tly

trying

to m

aintai

n in t

he co

nditio

ned s

pace

) is ca

lculat

ed fr

om th

e var

ious

Setpo

ints,

oper

ating

mod

es, n

etwor

k var

iable

inputs

, and

optim

um st

art-u

p pa

rame

ters.

The f

inal re

sult i

s stor

ed in

siTe

mpCo

ntrolP

tS7.

RmTe

mpnv

oData

2 (n

voCt

lData

G2)

siSpa

ceTe

mpS7

Degr

ees F

40 to

100

Degr

ees C

(4 to

38)

SI_IN

VALID

siSpa

ceTe

mpS7

: siS

pace

Temp

S7 is

the s

pace

temp

eratu

re us

ed by

the

contr

ol pr

oces

s and

is re

ad fr

om an

other

node

via n

viSpa

ceTe

mp or

a loc

al se

nsor

via n

voIO

.siSp

aceT

empS

7 or n

voIO

.siRe

turnT

empS

7. If t

he ne

twor

k inp

ut is

not S

I_INV

ALID

, then

the n

etwor

k inp

ut ha

s prio

rity. T

he lo

cal

sens

or is

selec

ted by

nciC

onfig

.Con

trolU

sesR

tnAirT

emp.

Whe

n nc

iCon

fig.C

ontro

lUse

sRtnA

irTem

p is 0

, then

the s

pace

temp

eratu

re se

nsor

is

selec

ted. W

hen n

ciCon

fig.C

ontro

lUse

sRtnA

irTem

p is 1

, then

the r

eturn

tem

pera

ture s

enso

r is se

lected

. If th

e netw

ork i

nput

and t

he se

lected

loca

l se

nsor

has f

ailed

or ar

e not

confi

gure

d, siS

pace

Temp

S7 is

SI_I

NVAL

ID.

Tabl

e 23

. Sta

tus

Poin

ts. (

Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

89 74-2958�2

DaTe

mpnv

oData

2 (n

voCt

lData

G2)

siDisc

harg

eTem

pS7

Degr

ees F

30 to

180

Degr

ees C

(-1 to

82)

SI_IN

VALID

XsiD

ischa

rgeT

empS

7: siD

ischa

rgeT

empS

7 is t

he di

scha

rge a

ir tem

pera

ture

used

by th

e con

trol p

roce

ss an

d is r

ead f

rom

the lo

cal s

enso

r via

nvoIO

.siDi

scha

rgeT

empS

7. If t

he se

nsor

has f

ailed

or is

not c

onfig

ured

, siD

ischa

rgeT

empS

7 is S

I_INV

ALID

.Da

Setpt

nvoD

ata2

(nvo

CtlD

ataG2

)siD

ischa

rgeS

etPtS

7De

gree

s F30

to 18

0 De

gree

s C(-1

to 82

)

SI_IN

VALID

XsiD

ischa

rgeS

etPtS

7: siD

ischa

rgeS

etPtS

7 is t

he ca

lculat

ed de

sired

dis

char

ge ai

r tem

pera

ture w

hen c

asca

de co

ntrol

is be

ing us

ed.

RaTe

mpnv

oData

2 (n

voCt

lData

G2)

siRetu

rnTe

mpS7

Degr

ees F

30 to

122

Degr

ees C

(-1 to

50)

SI_IN

VALID

XsiR

eturn

Temp

S7: s

iRetu

rnTe

mpS7

is th

e retu

rn ai

r temp

eratu

re us

ed by

the

contr

ol pr

oces

s rea

d fro

m the

loca

l sen

sor v

ia nv

oIO.si

Retur

nTem

pS7.

If the

sens

or ha

s fail

ed or

is no

t con

figur

ed, s

iRetu

rnTe

mpS7

is S

I_INV

ALID

.

RaHu

mnv

oData

2 (n

voCt

lData

G2)

ubRe

turnH

umidi

tyS1

Perce

ntage

10 to

90UB

_INVA

LIDX

ubRe

turnH

umidi

tyS1:

ubRe

turnH

umidi

tyS1 i

s the

retur

n air h

umidi

ty us

ed

by th

e con

trol p

roce

ss an

d is r

ead f

rom

the lo

cal s

enso

r via

nvoIO

.Retu

rnHu

midit

y. If t

he se

nsor

has f

ailed

or is

not c

onfig

ured

ub

Retur

nHum

idityS

1 is U

B_IN

VALID

.Ra

Enth

nvoD

ata2

(nvo

CtlD

ataG2

)siR

eturn

Entha

lpyS7

mA 4 to 2

0SI

_INVA

LIDX

siRetu

rnEn

thalpy

S7: s

iRetu

rnEn

thalpy

S7 is

the r

eturn

air e

nthalp

y use

d by

the co

ntrol

proc

ess a

nd is

read

from

the l

ocal

sens

or vi

a nv

oIO.si

Retur

nEnth

alpyS

7. If t

he se

nsor

has f

ailed

or is

not c

onfig

ured

, siR

eturn

Entha

lpyS7

is S

I_INV

ALID

.Oa

Temp

nvoD

ata2

(nvo

CtlD

ataG2

)siO

utdoo

rTemp

S7De

gree

s F-4

0 to 1

22

Degr

ees C

(-40 t

o 43)

SI_IN

VALID

XsiO

utdoo

rTemp

S7: s

iOutd

oorTe

mpS7

is th

e outd

oor a

ir tem

pera

ture u

sed

by th

e con

trol p

roce

ss an

d is r

ead f

rom

anoth

er no

de vi

a nviO

dTem

p or t

he

local

sens

or vi

a nvo

IO.si

Outdo

orTe

mpS7

. If th

e netw

ork i

nput

is no

t SI

_INVA

LID, th

en th

e netw

ork i

nput

has p

riority

. If bo

th the

netw

ork i

nput

and t

he lo

cal s

enso

r hav

e fail

ed or

are n

ot co

nfigu

red,

siOutd

oorTe

mpS7

is

SI_IN

VALID

.Oa

Hum

nvoD

ata2

(nvo

CtlD

ataG2

)ub

Outdo

orHu

midit

yS1

Perce

ntage

10 to

90UB

_INVA

LIDX

ubOu

tdoor

Humi

dityS

1: ub

Outdo

orHu

midit

yS1 i

s the

outdo

or ai

r hum

idity

used

by th

e con

trol p

roce

ss an

d is r

ead f

rom

anoth

er no

de vi

a nviO

dHum

or

the l

ocal

sens

or vi

a nvo

IO.O

utdoo

rHum

idity.

If the

netw

ork i

s not

SI_IN

VALID

, then

the n

etwor

k inp

ut ha

s prio

rity. If

both

the ne

twor

k inp

ut an

d the

loca

l sen

sor h

ave f

ailed

or ar

e not

confi

gure

d, ub

Outdo

orHu

midit

yS1 i

s UB_

INVA

LID.

OaEn

thnv

oData

2 (n

voCt

lData

G2)

siOutd

oorE

nthalp

yS7

mA 4 to 2

0SI

_INVA

LIDX

siOutd

oorE

nthalp

yS7:

siOutd

oorE

nthalp

yS7 i

s the

outdo

or ai

r enth

alpy

used

by th

e con

trol p

roce

ss an

d is r

ead f

rom

anoth

er no

de vi

a nv

iOdE

nthS7

or th

e loc

al se

nsor

via n

voIO

.siOu

tdoor

Entha

lpyS7

. If th

e ne

twor

k inp

ut is

not S

I_INV

ALID

, then

the n

etwor

k inp

ut ha

s prio

rity. If

both

the ne

twor

k inp

ut an

d the

loca

l sen

sor h

ave f

ailed

or ar

e not

confi

gure

d, siO

utdoo

rEnth

alpyS

7 is S

I_INV

ALID

.Fil

terPr

ess

nvoD

ata2

(nvo

CtlD

ataG2

)siF

ilterP

ress

ureS

10in.

w.c.

(kPa

)0 t

o 5 (0

to 1.

25)

SI_IN

VALID

XsiF

ilterP

ress

ureS

10: s

iFilte

rPre

ssur

eS10

is ai

r pre

ssur

e acro

ss th

e air f

ilter

used

by th

e con

trol p

roce

ss an

d is r

ead f

rom

the lo

cal s

enso

r via

nvoIO

.siFil

terPr

essu

reS1

0. If t

he lo

cal s

enso

r has

faile

d or is

not

confi

gure

d, siF

ilterP

ress

ureS

10 is

SI_I

NVAL

ID.

CO2S

ens

nvoC

tlData

G2siS

pace

Co2S

0PP

M15

0 to 2

000

SI_IN

VALID

XsiS

pace

Co2S

0: siS

pace

Co2S

0 is t

he in

door

air C

O 2 co

ntent

used

by th

e co

ntrol

proc

ess a

nd re

ad th

e loc

al se

nsor

via n

voIO

.siSp

aceC

o2S0

. If th

e loc

al se

nsor

has f

ailed

or is

not c

onfig

ured

, siS

pace

Co2S

0 is S

I_INV

ALID

.

Tabl

e 23

. Sta

tus

Poin

ts. (

Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 90

Monit

orSe

nsnv

oCtlD

ataG2

siMon

itor1

S10

volts

1 to 1

0SI

_INVA

LIDX

siMon

itor1

S10:

siMon

itor1

S10 i

s the

volta

ge ap

plied

at th

e mon

itor in

put

termi

nals.

If the

sens

or is

not c

onfig

ured

or ha

s fail

ed, th

e valu

e is

SI_IN

VALID

.Co

olPos

nvoC

tlData

G2sb

CoolP

osS0

Perce

ntage

0 to 1

000

Xsb

CoolP

osS0

: If th

e nod

e is c

onfig

ured

for m

odula

ting c

ool, s

bCoo

lPos

S0

show

s the

curre

nt po

sition

of th

e coo

ling m

odula

ting o

utput.

HeatP

osnv

oCtlD

ataG2

sbHe

atPos

S0Pe

rcenta

ge0 t

o 100

0X

sbHe

atPos

S0: If

the n

ode i

s con

figur

ed fo

r mod

ulatin

g hea

t, sbH

eatP

osS0

sh

ows t

he cu

rrent

posit

ion of

the h

eatin

g mod

ulatin

g outp

ut.Ec

onPo

snv

oCtlD

ataG2

sbEc

onPo

sS0

Perce

ntage

0 to 1

000

Xsb

Econ

PosS

0: If t

he no

de is

confi

gure

d for

mod

ulatin

g eco

nomi

zer,

sbEc

onPo

sS0 s

hows

the c

urre

nt po

sition

of th

e eco

nomi

zer m

odula

ting

outpu

t.St

atusE

rror

nvoE

rror

erro

r_bit

[0]By

te Of

fset =

0Bi

t Offs

et =

0 (S

pace

Temp

Erro

r)

FALS

ETR

UE0 1

FALS

EX

For S

pace

Temp

Erro

r, a va

lue of

1 (T

RUE)

indic

ates t

hat d

ata w

as no

t av

ailab

le fro

m the

sens

or an

d will

resu

lt in a

SEN

SOR_

FAILU

RE al

arm.

A

value

of 0

(FAL

SE) in

dicate

s a no

rmal

cond

ition.

The h

eatin

g and

cooli

ng

contr

ol loo

ps w

ill be

turn

ed of

f it th

ere i

s a sp

ace t

emp s

enso

r fail

ure.

The

fan w

ill re

main

unde

r nor

mal c

ontro

l.nv

oErro

rer

ror_

bit[0]

Byte

Offse

t = 0

Bit O

ffset

= 1

(SetP

tErro

r)

FALS

ETR

UE0 1

FALS

EFo

r SetP

tErro

r, see

prec

eding

. Upo

n a fa

ilure

of th

e loc

al se

tpoint

, the

contr

ol loo

p will

use t

he de

fault o

ccup

ied se

tpoint

s to c

ontro

l spa

ce

tempe

ratur

e.

nvoE

rror

erro

r_bit

[0]By

te Of

fset =

0Bi

t Offs

et =

2 (O

dTem

pErro

r)

FALS

ETR

UE0 1

FALS

EFo

r OdT

empE

rror, s

ee pr

eced

ing. A

ll con

trol fu

nctio

ns as

socia

ted w

ith th

e fai

led se

nsor

are d

isable

d as i

f the s

enso

r was

not c

onfig

ured

.

nvoE

rror

erro

r_bit

[0]By

te Of

fset =

0Bi

t Offs

et =

3 (O

dHum

Erro

r)

FALS

ETR

UE0 1

FALS

EFo

r OdH

umEr

ror, s

ee pr

eced

ing. A

value

of 0

(FAL

SE) in

dicate

s a no

rmal

cond

ition.

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

sens

or ar

e dis

abled

as if

the se

nsor

was

not c

onfig

ured

.

nvoE

rror

erro

r_bit

[0]By

te Of

fset =

0Bi

t Offs

et =

4 (O

dEnth

alpyE

rror)

FALS

ETR

UE0 1

FALS

EOd

Entha

lpyEr

ror:

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

sens

or ar

e dis

abled

as if

the se

nsor

was

not c

onfig

ured

.

nvoE

rror

erro

r_bit

[0]By

te Of

fset =

0Bi

t Offs

et =

5 (D

ischg

Temp

Erro

r)

FALS

ETR

UE0 1

FALS

EDi

schg

Temp

Erro

r: Al

l con

trol fu

nctio

ns as

socia

ted w

ith th

e fail

ed se

nsor

are

disab

led as

if the

sens

or w

as no

t con

figur

ed.

nvoE

rror

erro

r_bit

[0]By

te Of

fset =

0Bi

t Offs

et =

6 Rt

nTem

pErro

r)

FALS

ETR

UE0 1

FALS

ERt

nTem

pErro

r: Al

l con

trol fu

nctio

ns as

socia

ted w

ith th

e fail

ed se

nsor

are

disab

led as

if the

sens

or w

as no

t con

figur

ed.

nvoE

rror

erro

r_bit

[0]By

te Of

fset =

0Bi

t Offs

et =

7 (R

tnHum

Erro

r)

FALS

ETR

UE0 1

FALS

ERt

nHum

Erro

r: Al

l con

trol fu

nctio

ns as

socia

ted w

ith th

e fail

ed se

nsor

are

disab

led as

if the

sens

or w

as no

t con

figur

ed.

Tabl

e 23

. Sta

tus

Poin

ts. (

Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

91 74-2958�2

nvoE

rror

erro

r_bit

[1]By

te Of

fset =

1Bi

t Offs

et =

0 (R

tnEnth

alpyE

rror)

FALS

ETR

UE0 1

FALS

ERt

nEnth

alpyE

rror:

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

sens

or ar

e dis

abled

as if

the se

nsor

was

not c

onfig

ured

.

nvoE

rror

erro

r_bit

[1]By

te Of

fset =

1Bi

t Offs

et =

1 (M

onito

rSen

sorE

rror)

FALS

ETR

UE0 1

FALS

EMo

nitor

Sens

orEr

ror:

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

sens

or

are d

isable

d as i

f the s

enso

r was

not c

onfig

ured

.

nvoE

rror

erro

r_bit

[1]By

te Of

fset =

1Bi

t Offs

et =

2 (S

pace

CO2E

rror)

FALS

ETR

UE0 1

FALS

ESp

aceC

O2Er

ror:

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

sens

or ar

e dis

abled

as if

the se

nsor

was

not c

onfig

ured

.

nvoE

rror

erro

r_bit

[1]By

te Of

fset =

1Bi

t Offs

et =

3 (F

ilterS

taticP

resE

rror)

FALS

ETR

UE0 1

FALS

EFil

terSt

aticP

resE

rror:

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

sens

or

are d

isable

d as i

f the s

enso

r was

not c

onfig

ured

.

nvoE

rror

erro

r_bit

[1]By

te Of

fset =

1Bi

t Offs

et =

4 (A

DCalE

rror)

FALS

ETR

UE0 1

FALS

EAD

CalE

rror:

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

sens

or ar

e dis

abled

as if

the se

nsor

was

not c

onfig

ured

.

nvoE

rror

erro

r_bit

[1]By

te Of

fset =

1Bi

t Offs

et =

7 (n

vApp

lMod

eErro

r)

FALS

ETR

UE0 1

FALS

EAp

plMod

eErro

r: Al

l con

trol fu

nctio

ns as

socia

ted w

ith th

e fail

ed N

V ar

e dis

abled

as if

the N

V wa

s not

confi

gure

d.

nvoE

rror

erro

r_bit

[2]By

te Of

fset =

2Bi

t Offs

et =

0 (n

vSetP

tOffs

etErro

r)

FALS

ETR

UE0 1

FALS

ESe

tPtO

ffsetE

rror:

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

NV

are

disab

led as

if the

NV

was n

ot co

nfigu

red.

nvoE

rror

erro

r_bit

[2]By

te Of

fset =

2Bi

t Offs

et =

1 (n

vSpa

ceTe

mpEr

ror)

FALS

ETR

UE0 1

FALS

ESp

aceT

empE

rror:

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

NV

are

disab

led as

if the

NV

was n

ot co

nfigu

red.

nvoE

rror

erro

r_bit

[2]By

te Of

fset =

2Bi

t Offs

et =

2 (n

vOdT

empE

rror)

FALS

ETR

UE0 1

FALS

EOd

Temp

Erro

r: Al

l con

trol fu

nctio

ns as

socia

ted w

ith th

e fail

ed N

V ar

e dis

abled

as if

the N

V wa

s not

confi

gure

d.

nvoE

rror

erro

r_bit

[2]By

te Of

fset =

2Bi

t Offs

et =

3 (n

vOdH

umEr

ror)

FALS

ETR

UE0 1

FALS

EOd

HumE

rror:

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

NV

are

disab

led as

if the

NV

was n

ot co

nfigu

red.

nvoE

rror

erro

r_bit

[2]By

te Of

fset =

2Bi

t Offs

et =

4 (n

vSen

sorO

ccEr

ror)

FALS

ETR

UE0 1

FALS

ESe

nsor

OccE

rror:

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

NV

are

disab

led as

if the

NV

was n

ot co

nfigu

red.

Tabl

e 23

. Sta

tus

Poin

ts. (

Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 92

nvoE

rror

erro

r_bit

[2]By

te Of

fset =

2Bi

t Offs

et =

5 (n

vWind

owEr

ror)

FALS

ETR

UE0 1

FALS

EW

indow

Erro

r: Al

l con

trol fu

nctio

ns as

socia

ted w

ith th

e fail

ed N

V ar

e dis

abled

as if

the N

V wa

s not

confi

gure

d.

nvoE

rror

erro

r_bit

[2]By

te Of

fset =

2Bi

t Offs

et =

6 (n

vDlcS

hedE

rror)

FALS

ETR

UE0 1

FALS

EDl

cShe

dErro

r: Al

l con

trol fu

nctio

ns as

socia

ted w

ith th

e fail

ed N

V ar

e dis

abled

as if

the N

V wa

s not

confi

gure

d.

nvoE

rror

erro

r_bit

[2]By

te Of

fset =

2Bi

t Offs

et =

7 (n

vTod

Even

tErro

r)

FALS

ETR

UE0 1

FALS

ETo

dEve

ntErro

r: Al

l con

trol fu

nctio

ns as

socia

ted w

ith th

e fail

ed N

V ar

e dis

abled

as if

the N

V wa

s not

confi

gure

d.

nvoE

rror

erro

r_bit

[3]By

te Of

fset =

3Bi

t Offs

et =

0 (n

vByP

assE

rror)

FALS

ETR

UE0 1

FALS

EBy

Pass

Erro

r: Al

l con

trol fu

nctio

ns as

socia

ted w

ith th

e fail

ed N

V ar

e dis

abled

as if

the N

V wa

s not

confi

gure

d.

nvoE

rror

erro

r_bit

[3]By

te Of

fset =

3Bi

t Offs

et =

1 (n

vOdE

nthalp

yErro

r)

FALS

ETR

UE0 1

FALS

EOd

Entha

lpyEr

ror:

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

NV

are

disab

led as

if the

NV

was n

ot co

nfigu

red.

nvoE

rror

erro

r_bit

[3]By

te Of

fset =

3Bi

t Offs

et =

2 (n

vEco

nErro

r)

FALS

ETR

UE0 1

FALS

EEc

onEr

ror:

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

NV

are d

isable

d as

if the

NV

was n

ot co

nfigu

red.

nvoE

rror

erro

r_bit

[3]By

te Of

fset =

3Bi

t Offs

et =

3 (n

vIaqO

verri

deEr

ror)

FALS

ETR

UE0 1

FALS

EIaq

Over

rideE

rror:

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

NV

are

disab

led as

if the

NV

was n

ot co

nfigu

red.

nvoE

rror

erro

r_bit

[3]By

te Of

fset =

3Bi

t Offs

et =

4 (n

vFre

e1Er

ror)

FALS

ETR

UE0 1

FALS

EFr

ee1E

rror:

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

NV

are d

isable

d as

if the

NV

was n

ot co

nfigu

red.

Tabl

e 23

. Sta

tus

Poin

ts. (

Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

93 74-2958�2

nvoE

rror

erro

r_bit

[3]By

te Of

fset =

3Bi

t Offs

et =

5 (n

vFre

e2Er

ror)

FALS

ETR

UE0 1

FALS

EFr

ee2E

rror:

All c

ontro

l func

tions

asso

ciated

with

the f

ailed

NV

are d

isable

d as

if the

NV

was n

ot co

nfigu

red.

nvoE

rror

erro

r_bit

[3]By

te Of

fset =

3Bi

t Offs

et =

6 (n

vTim

eCloc

kErro

r)

FALS

ETR

UE0 1

FALS

ETim

eCloc

kErro

r: Al

l con

trol fu

nctio

ns as

socia

ted w

ith th

e fail

ed N

V ar

e dis

abled

as if

the N

V wa

s not

confi

gure

d.

nvoE

rror

erro

r_bit

[3]By

te Of

fset =

3Bi

t Offs

et =

7 (n

vWSH

PEnE

rror)

FALS

ETR

UE0 1

FALS

EW

SHPE

nErro

r: Al

l con

trol fu

nctio

ns as

socia

ted w

ith th

e fail

ed N

V ar

e dis

abled

as if

the N

V wa

s not

confi

gure

d.

NetC

onfig

nciN

etCon

figCF

G_LO

CAL

CFG_

EXTE

RNAL

CFG_

NUL

0 1 255

CFG_

LOCA

LAl

l nod

es th

at su

ppor

t self

-insta

llatio

n pro

vide a

confi

gura

tion v

ariab

le to

allow

a ne

twor

k man

agem

ent to

ol to

also i

nstal

l the n

ode.

nciN

etCon

fig is

on

ly us

ed by

a ne

twor

k man

agem

ent to

ol an

d may

have

the f

ollow

ing

value

s: CF

G_LO

CAL -

Nod

e will

use s

elf in

stalla

tion f

uncti

ons t

o set

its ow

n ne

twor

k ima

ge. C

FG_E

XTER

NAL -

The

node

s netw

ork i

mage

has b

een s

et by

an ex

terna

l sou

rce.

Tabl

e 24

. Cal

ibra

tion

Poin

ts.

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

tsnv

oRaw

K1Ra

wK2

Raw

Ai1R

esist

iveAi

2Res

istive

Ai3V

oltag

eAi

4Volt

age

RawS

pace

Temp

RawS

etPoin

t

Coun

ts0 t

o 655

350

raw_

data

conta

ins th

e ana

log to

digit

al co

nver

ter co

unts

meas

ured

from

the

analo

g inp

ut ch

anne

l.

Tabl

e 23

. Sta

tus

Poin

ts. (

Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 94

Tabl

e 25

. Con

figur

atio

n Pa

ram

eter

s.

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

NOTE

: Phy

sical

I/O p

oint

s tha

t are

conf

igur

able

are i

n Ta

ble 2

0.

Com

men

tsnc

iDev

iceNa

meAS

CII B

lanks

Devic

eNam

e is a

n 18 c

hara

cter f

ield u

sed t

o ide

ntify

the no

de un

iquely

as

one o

bject

at the

site

or pr

oject.

The

conte

nts of

the D

evice

Name

is

maint

ained

by a

mana

geme

nt no

de. If

Dev

iceNa

me is

all A

SCII b

lanks

, it is

co

nside

red u

ncon

figur

ed.

nciA

pplVe

rap

plica

tion_

type

0 to 2

550

Appli

catio

nTyp

e ide

ntifie

s the

curre

nt ap

plica

tion n

umbe

r of th

e Exc

el 10

.nc

iApp

lVer

versi

on_n

o0 t

o 255

0Ve

rsion

Numb

er id

entifi

es th

e ver

sion n

umbe

r of th

e Exc

el 10

appli

catio

n.nc

iApp

lVer

time

Seco

nds

0Th

e tim

e stam

p of th

e las

t cha

nge t

o the

Exc

el 10

appli

catio

n co

nfigu

ratio

n. Tim

e mee

ts the

ANS

I C tim

e stam

p req

uirem

ent s

pecif

ying

the nu

mber

of se

cond

s elap

sed s

ince m

idnigh

t (0:0

0:00)

, Jan

uary

1, 19

70.

It is r

epre

sente

d in t

he In

tel F

orma

t.Fa

nMod

enc

iCon

figFa

nMod

eAU

TO_F

ANCO

NTIN

UOUS

_FAN

0 1AU

TO_F

ANP

XFa

nMod

e spe

cifies

the o

pera

tion o

f the f

an. If

the F

anMo

de is

0 (A

UTO_

FAN)

, then

the f

an cy

cles o

n and

off w

ith de

mand

for c

oolin

g and

ma

y cyc

le wi

th he

ating

if Fa

nOnH

eat is

TRU

E. If

the F

anMo

de is

1 (C

ONTI

NUOU

S_FA

N), th

en th

e fan

runs

conti

nuou

sly w

hen t

he ef

fectiv

e oc

cupa

ncy i

s OC_

OCCU

PIED

or O

C_BY

PASS

. The

fan c

ycles

on an

d off

with

dema

nd fo

r coo

ling a

nd m

ay cy

cle w

ith he

ating

if Fa

nOnH

eat is

TRU

E du

ring t

he O

C_UN

OCCU

PIED

or O

C_ST

ANDB

Y mo

des.

Econ

Mode

nciC

onfig

Econ

Enab

leDI

GITA

L_IN

OD_T

EMP

OD_E

NTH_

A_TY

PEOD

_ENT

H_B_

TYPE

OD_E

NTH_

C_TY

PEOD

_ENT

H_D_

TYPE

DIFF

_TEM

PSI

NGLE

_ENT

HDI

FF_E

NTH

ECON

_NUL

0 1 2 3 4 5 6 7 8 255

ECON

_NUL

PX

XEc

onEn

able

spec

ifies t

he m

ethod

used

to de

termi

ne w

hen o

utside

air is

su

itable

for u

se to

augm

ent c

oolin

g. Th

e vali

d valu

es ar

e acc

ordin

g to t

he

enum

erate

d list

that

is sh

own i

n the

Eng

ineer

ing U

nits/S

tates

colum

n.

SmkC

tlMod

enc

iCon

figSm

okeC

ontro

lFA

N_OF

F_DA

MPER

_CLO

SED

FAN_

ON_D

AMPE

R_OP

ENFA

N_ON

_DAM

PER_

CLOS

ED

0 1 2

FAN_

OFF_

DAMP

ER_

CLOS

EDP

XX

Smok

eCon

trol s

pecif

ies th

e ope

ratio

n of th

e eco

nomi

zer d

ampe

r and

the

fan w

hen t

he m

ode i

s SMO

KE_E

MERG

ENCY

.

HeatC

ycHr

nciC

onfig

ubHe

atCph

2 to 1

26

PX

XHe

atCph

spec

ifies t

he m

id-loa

d num

ber o

f on/o

ff cyc

les pe

r hou

r whe

n the

mo

de is

HEA

T. In

addit

ion th

e cyc

le ra

te sp

ecifie

s the

mini

mum

on an

d off

time.

Refer

to Ta

ble 17

Inter

stage

Mini

mum

Times

of th

e Sys

tem

Engin

eerin

g Guid

e for

the a

ctual

value

s.Co

olCyc

Hrnc

iCon

figub

CoolC

ph2 t

o 12

3P

XX

CoolC

ph sp

ecifie

s the

mid-

load n

umbe

r of o

n/off c

ycles

per h

our w

hen t

he

mode

is C

OOL.

In ad

dition

the c

ycle

rate

spec

ifies t

he m

inimu

m on

and o

ff tim

e. Re

fer to

Table

17 In

tersta

ge M

inimu

m Tim

es of

the S

ystem

En

ginee

ring G

uide f

or th

e actu

al va

lues.

FanR

unOn

Cool

nciC

onfig

ubFa

nRun

onCo

olS0

Seco

nds

0 to 1

200

PX

XFa

nRun

onCo

ol sp

ecifie

s how

long

the f

an ru

ns af

ter al

l the c

oolin

g stag

es

have

turn

ed of

f. The

fan i

s tur

ned o

ff Fan

Runo

nCoo

l sec

onds

after

all th

e co

oling

dema

nd ha

s tur

ned o

ff.Fa

nRun

OnHe

atnc

iCon

figub

FanR

unon

HeatS

0Se

cond

s0 t

o 120

0P

XX

FanR

unon

Heat

spec

ifies h

ow lo

ng th

e fan

runs

after

all th

e hea

ting s

tages

ha

ve tu

rned

off. T

he fa

n is t

urne

d off F

anRu

nonH

eat s

econ

ds af

ter al

l the

heati

ng de

mand

has t

urne

d off.

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

95 74-2958�2

Econ

MtrS

pdnc

iCon

figub

Econ

MtrT

imeS

0Se

cond

s20

to 24

090

PX

XEc

onMt

rTim

e spe

cifies

how

long i

t take

s the

econ

omize

r dam

per m

otor t

o tra

vel fr

om fu

lly cl

osed

to fu

lly op

en. T

his tim

e is u

sed t

o calc

ulate

the

repo

rted p

ositio

n of th

e dam

per a

nd to

deter

mine

the l

ength

of ov

er dr

ive

time r

equir

ed to

assu

re th

e dam

per is

fully

clos

ed or

open

.Co

olMtrS

pdnc

iCon

figub

CoolM

trTim

eS0

Seco

nds

20 to

240

90P

XX

CoolM

trTim

e spe

cifies

how

long i

t take

s the

cooli

ng da

mper

or va

lve m

otor

to tra

vel fr

om fu

lly cl

osed

to fu

lly op

en. T

his tim

e is u

sed t

o calc

ulate

the

repo

rted p

ositio

n of th

e coo

ling d

ampe

r or v

alve a

nd to

deter

mine

the

length

of ov

er dr

ive tim

e req

uired

to as

sure

that

it is f

ully c

losed

or op

en.

HeatM

trSpd

nciC

onfig

ubHe

atMtrT

imeS

0Se

cond

s20

to 24

090

PX

XHe

atMtrT

ime s

pecif

ies ho

w lon

g it ta

kes t

he he

ating

damp

er or

valve

moto

r to

trave

l from

fully

clos

ed to

fully

open

. This

time i

s use

d to c

alcula

te the

re

porte

d pos

ition o

f the h

eatin

g dam

per o

r valv

e and

to de

termi

ne th

e len

gth of

over

drive

time r

equir

ed to

assu

re th

at it i

s full

y clos

ed or

open

.Fa

nFail

Time

nciC

onfig

ubFa

nFail

TimeS

0Se

cond

s1 t

o 120

10P

XX

Each

time F

AN_O

UT is

ener

gized

, then

the n

ode w

aits f

or F

anFa

ilTim

e se

cond

s to s

ample

the P

roofA

irFlow

inpu

t. If P

roofA

irFlow

show

s tha

t the

fan is

not r

unnin

g for

Fan

FailT

ime c

onse

cutiv

e sec

onds

, then

the c

ontro

l is

shut

down

for t

he m

inimu

m off

time.

Then

the c

ontro

l (inc

luding

the f

an) is

re

starte

d and

Pro

ofAirF

low is

again

teste

d. If P

roofA

irFlow

show

s air f

low,

then t

he co

ntrol

conti

nues

to op

erate

, but

if Pro

ofAirF

low fa

ils to

show

air

flow,

then

the c

ontro

l is ag

ain sh

ut do

wn fo

r the

mini

mum

off tim

e. Af

ter

three

unsu

cces

sful re

starts

, a LO

SS_O

F_AI

R_FL

OW al

arm

is iss

ued a

nd

the co

ntrol

stays

in th

e DIS

ABLE

D mo

de w

ith th

e FAN

_OUT

off.

RmTe

mpCa

lnc

iCon

figsiS

pace

Temp

Zero

CalS

7De

gree

s F-5

to 5

(-3 to

3)0

XX

Spac

eTem

pZer

oCal

prov

ides o

ffset

calib

ratio

n for

the s

pace

analo

g sen

sor

input

and i

s add

ed to

the s

ense

d valu

e. Th

e ran

ge of

Spa

ceTe

mpZe

roCa

l is

betw

een -

5 and

5 de

gree

s F.

Temp

Offst

Cal1

nciC

onfig

siRes

istive

Offse

tCalS

7[0]

Degr

ees F

-15 t

o 15 (

-9 to

9)0

Resis

tiveO

ffsetC

al[0]

prov

ides o

ffset

calib

ratio

n for

the r

esist

ive an

alog

sens

or in

put a

nd is

adde

d to t

he se

nsed

value

. The

rang

e of

Resis

tiveO

ffsetC

al[0]

is be

twee

n -15

and 1

5 deg

rees

F.Te

mpOf

fstCa

l2nc

iCon

figsiR

esist

iveOf

fsetC

alS7[1

]De

gree

s F-1

5 to 1

5 (-9

to 9)

0Re

sistiv

eOffs

etCal[

1] pr

ovide

s offs

et ca

libra

tion f

or th

e res

istive

analo

g se

nsor

inpu

t and

is ad

ded t

o the

sens

ed va

lue. T

he ra

nge o

f Re

sistiv

eOffs

etCal[

1] is

betw

een -

15 an

d 15 d

egre

es F.

VoltO

ffstC

al1nc

iCon

figsiV

oltag

eOffs

etCalS

12[0]

volts

-1 to

10

Volta

geOf

fsetC

al[0]

prov

ides o

ffset

calib

ratio

n for

the v

oltag

e/cur

rent

analo

g sen

sor in

put a

nd is

adde

d to t

he se

nsed

value

. The

curre

nt an

alog

sens

or is

conv

erted

to a

volta

ge by

a 24

9 ohm

resis

ter w

ired a

cross

the

input

termi

nals.

The

rang

e of V

oltag

eOffs

etCal[

0] is

betw

een -

1 and

1 vo

lt. Vo

ltage

offse

ts ar

e new

in en

ginee

ring u

nits (

not v

olts).

VoltO

ffstC

al2nc

iCon

figsiV

oltag

eOffs

etCalS

12[1]

volts

-1 to

10

Volta

geOf

fsetC

al[1]

prov

ides o

ffset

calib

ratio

n for

the v

oltag

e/cur

rent

analo

g sen

sor in

put a

nd is

adde

d to t

he se

nsed

value

. The

curre

nt an

alog

sens

or is

conv

erted

to a

volta

ge by

a 24

9 ohm

resis

ter w

ired a

cross

the

input

termi

nals.

The

rang

e of V

oltag

eOffs

etCal[

1] is

betw

een -

1 and

1 vo

lt. Vo

ltage

offse

ts ar

e new

in en

ginee

ring u

nits (

not v

olts).

FanO

nHtM

ode

nciC

onfig

FanO

nHea

tFA

LSE

TRUE

0 1TR

UEP

XX

FanO

nHea

t spe

cifies

the o

pera

tion o

f the f

an du

ring H

EAT

mode

. If

FanO

nHea

t is 1(

TRUE

), the

n the

fan i

s on w

hen t

he m

ode i

s HEA

T. If

FanO

nHea

t is a

0 (FA

LSE)

the f

an is

neve

r tur

ned o

n whe

n the

mod

e is

HEAT

, and

typic

ally a

ther

mosta

ticall

y con

trolle

d swi

tch se

nsing

heate

d air

tempe

ratur

e tur

ns on

the f

an.

Tabl

e 25

. Con

figur

atio

n Pa

ram

eter

s. (C

ontin

ued)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

NOTE

: Phy

sical

I/O p

oint

s tha

t are

conf

igur

able

are i

n Ta

ble 2

0.

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 96

DisM

inHtT

ime

nciC

onfig

Disa

bleHe

atMinT

ime

FALS

ETR

UE0 1

FALS

EP

XX

If Disa

bleHe

atMinT

ime i

s 0 (F

ALSE

), the

heati

ng st

ages

are o

n or o

ff for

a mi

nimum

time d

eterm

ined b

y ubH

eatC

ph (R

efer t

o Tab

le 17

Inter

stage

Mi

nimum

Time

s of th

e Sys

tem E

ngine

ering

Guid

e). If

Disa

bleHe

atMinT

ime

is 1 (

TRUE

), the

heati

ng st

ages

are o

n or o

ff for

a 30

seco

nd m

inimu

m tim

e.Di

sMinC

lTime

nciC

onfig

Disa

bleCo

olMinT

ime

FALS

ETR

UE0 1

FALS

EP

XX

If Disa

bleCo

olMinT

ime i

s 0 (F

ALSE

), the

cooli

ng st

ages

are o

n or o

ff for

a mi

nimum

time d

eterm

ined b

y Coo

lCph

(Refe

r to T

able

17 In

tersta

ge

Minim

um Ti

mes o

f the S

ystem

Eng

ineer

ing G

uide)

. If D

isable

CoolM

inTim

e is

1 (TR

UE),

the co

oling

stag

es ar

e on o

r off f

or a

30 se

cond

mini

mum

time.

Casc

Cntrl

nciC

onfig

Casc

adeC

ontro

lFA

LSE

TRUE

0 1FA

LSE

PX

XW

hen C

asca

deCo

ntrol

is 0 (

FALS

E), th

en th

e disc

harg

e air t

empe

ratur

e is

not d

irectl

y con

trolle

d and

heati

ng an

d coo

ling e

quipm

ent a

re m

odula

ted to

ma

intain

spac

e tem

pera

ture.

Whe

n Cas

cade

Contr

ol is

1 (TR

UE),

then t

he

disch

arge

air t

empe

ratur

e is c

ontro

lled b

y an a

dditio

nal c

ontro

l loop

base

d on

the e

rror s

ignal

from

the sp

ace t

empe

ratur

e con

trol lo

op. C

asca

de

Contr

ol is

appli

cable

to m

odula

ting h

eatin

g/coo

ling o

nly (n

ot sta

ged)

.Us

eRaT

empC

tlnc

iCon

figCo

ntrolU

sesR

tnAirT

emp

FALS

ETR

UE0 1

FALS

EP

XX

If Con

trolU

sesR

tnAirT

emp i

s a 0

(FAL

SE),

then D

ata2.S

pace

Temp

is se

t eq

ual e

ither

the s

pace

temp

eratu

re se

nsor

(IO.

siSpa

ceTe

mp) o

r Sp

aceT

emp d

epen

ding o

n the

value

of S

pace

Temp

. Whe

n Co

ntrolU

sesR

tnAirT

emp i

s 1 (T

RUE)

and S

pace

Temp

is S

I_INV

ALID

, then

Da

ta2.S

pace

Temp

is se

t equ

al to

retur

n air s

enso

r (IO

.Retu

rnTe

mp) a

nd

the co

ntrol

uses

the r

eturn

air s

enso

r to c

ontro

l hea

ting o

r coo

ling.

Whe

n Co

ntrolU

sesR

tnAirT

emp i

s 1 (T

RUE)

and S

pace

Temp

is no

t SI_I

NVAL

ID,

then D

ata2.s

iSpa

ceTe

mp is

set e

qual

to Sp

aceT

emp a

nd th

e con

trol u

ses

Spac

eTem

p to c

ontro

l hea

ting o

r coo

ling.

IaqUs

eHea

tnc

iCon

figIaq

UseH

eat

FALS

ETR

UE0 1

FALS

EP

XX

Whe

n the

effec

tive o

ccup

ancy

is O

C_OC

CUPI

ED an

d Iaq

UseH

eat is

0 (F

ALSE

), the

n no h

eatin

g stag

es or

mod

ulatin

g hea

ting a

re tu

rned

whe

n the

disc

harg

e air t

empe

ratur

e goe

s belo

w the

low

limit.

Ener

gy ha

s prio

rity

over

venti

lation

. Whe

n the

effec

tive o

ccup

ancy

is O

C_OC

CUPI

ED an

d Iaq

UseH

eat is

1 (T

RUE)

, then

the h

eatin

g stag

es or

mod

ulatin

g hea

ting

are t

urne

d on t

o pre

vent

the di

scha

rge a

ir tem

pera

ture f

rom

going

below

the

disc

harg

e air t

empe

ratur

e low

limit.

Venti

lation

has p

riority

over

ener

gy

cost.

Tabl

e 25

. Con

figur

atio

n Pa

ram

eter

s. (C

ontin

ued)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

NOTE

: Phy

sical

I/O p

oint

s tha

t are

conf

igur

able

are i

n Ta

ble 2

0.

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

97 74-2958�2

Ovrd

Prior

itync

iCon

figOv

errid

ePrio

rityLA

STNE

T0 1

NET

PX

XOv

errid

ePrio

rity co

nfigu

res t

he ov

errid

e arb

itratio

n betw

een M

anOc

c, By

pass

.state

, and

the w

all m

odule

over

ride b

utton

. If O

verri

dePr

iority

is 0

(LAS

T), th

en th

e las

t com

mand

rece

ived f

rom

eithe

r the

wall

mod

ule or

iM

anOc

c dete

rmine

s the

effec

tive o

verri

de st

ate. If

Ove

rride

Prior

ity is

1 (N

ET),

this s

pecif

ies th

at wh

en M

anOc

c is n

ot OC

_NUL

, that

the ef

fectiv

e oc

cupa

ncy i

s Man

Occ r

egar

dless

of th

e wall

mod

ule ov

errid

e stat

e.Us

eWall

ModS

tptnc

iCon

figUs

eWall

ModS

tPt

FALS

ETR

UE0 1

TRUE

PX

XUs

eWall

ModS

tpt sp

ecifie

s the

OC_

OCCU

PIED

temp

eratu

re se

tpoint

so

urce

. If U

seW

allMo

dStpt

is 0

(FAL

SE),

then t

he oc

cupie

d Tem

pSetP

ts ar

e use

d whe

n the

effec

tive o

ccup

ancy

is O

C_OC

CUPI

ED. If

Us

eWall

ModS

tpt is

1 (T

RUE)

, then

the w

all m

odule

s setp

oint k

nob i

s use

d wh

en th

e effe

ctive

occu

panc

y is O

C_OC

CUPI

ED. S

etPt o

verri

des a

ll.Se

tPtK

nob

nciC

onfig

SetP

ntKno

bOF

FSET

ABSO

LUTE

_MID

DLE

0 1AB

SOLU

TE_M

IDDL

EP

XX

SetP

ntKno

b spe

cifies

the u

sage

of th

e setp

oint k

nob w

hen

UseW

allMo

dStP

t is TR

UE. W

hen S

etPntK

nob i

s 0 (A

BSOL

UTE_

MIDD

LE),

the se

tpoint

knob

dire

ctly d

eterm

ines t

he ce

nter p

oint o

f betw

een t

he

OC_O

CCUP

IED

cooli

ng an

d hea

ting s

etpoin

ts. W

hen S

etPntK

nob i

s 1

(OFF

SET)

, the e

ffecti

ve se

tpoint

is ca

lculat

ed by

addin

g the

remo

te se

tpoint

poten

tiome

ter va

lue (c

enter

scale

= 0)

to th

e app

ropr

iate v

alue o

f Te

mpSe

tPts.

Ovrd

Type

nciC

onfig

Over

rideT

ype

NONE

NORM

ALBY

PASS

_ONL

Y

0 1 2

NORM

ALP

XX

Over

rideT

ype s

pecif

ies th

e beh

avior

of th

e ove

rride

butto

n. If t

he

Over

rideT

ype i

s 0 (N

ONE)

then

the o

verri

de bu

tton i

s disa

bled.

An

Over

rideT

ype o

f 1 (N

ORMA

L), c

ause

s the

over

ride b

utton

to se

t the

Over

Ride

state

to O

C_BY

PASS

for A

ux2S

etPt.B

ypas

sTim

e sec

onds

whe

n the

over

ride b

utton

has b

een p

ress

ed fo

r app

roxim

ately

1 to 4

seco

nds,

or

to se

t the O

verR

ide st

ate to

UNO

CC w

hen t

he bu

tton h

as be

en pr

esse

d for

ap

prox

imate

ly 4 t

o 7 se

cond

s. W

hen t

he bu

tton i

s pre

ssed

long

er th

an

appr

oxim

ately

7 sec

onds

, then

the O

verR

ide st

ate is

set to

OC_

NUL.

If the

Ov

errid

eTyp

e is 2

(BYP

ASS_

ONLY

), the

over

ride b

utton

sets

the O

verR

ide

state

to OC

_BYP

ASS

for A

ux2S

etPt.B

ypas

sTim

e sec

onds

on th

e firs

t pr

ess.

On th

e nex

t pre

ss, th

e Ove

rRide

state

is se

t to O

C_NU

L.

Tabl

e 25

. Con

figur

atio

n Pa

ram

eter

s. (C

ontin

ued)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

NOTE

: Phy

sical

I/O p

oint

s tha

t are

conf

igur

able

are i

n Ta

ble 2

0.

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 98

Tabl

e 26

. LO

NM

AR

/Ope

n Sy

stem

Poi

nts.

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.Failure Detect

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

tsnc

iNod

eSen

dT

(SNV

T_tim

e_se

c)Se

cond

s0

The m

axim

um tim

e betw

een u

pdate

s of n

etwor

k var

iable

outpu

ts fro

m the

no

de ob

ject.

nciR

tuSen

dT

(SNV

T_tim

e_se

c)Se

cond

s0

The S

GPUC

and S

GPU

time (

hear

t bea

t time

) betw

een u

pdate

s of n

etwor

k va

riable

outpu

ts.NO

TE: R

tuSen

dT sh

ould

be se

t to 55

seco

nds b

y a

mana

geme

nt no

de to

be co

mpati

ble w

ith a

Hone

ywell

syste

m.nc

iRtuR

cvT

(SNV

T_tim

e_se

c)Se

cond

s0

This

is the

failu

re de

tectio

n tim

e for

netw

ork S

GPUC

and S

GPU

varia

bles

outpu

ts.NO

TE: R

tuRcv

T sh

ould

be se

t to 30

0 sec

onds

by a

mana

geme

nt no

de to

be co

mpati

ble w

ith a

Hone

ywell

syste

m.Co

olOcc

Spt

nciTe

mpSe

tPts

(SNV

T_tem

p_se

tpt)

occu

pied_

cool

Degr

ees F

50 to

95De

gree

s C(1

0 to 3

5)

23P, M

XX

The C

oolin

g Occ

upied

Setp

oint is

used

if no

wall

mod

ule se

tpoint

pot is

co

nfigu

red a

s the

stan

dard

Occ

upied

Coo

ling S

etpoin

t. Actu

al Co

oling

Se

tpoint

can b

e affe

cted b

y var

ious c

ontro

l par

amete

rs (su

ch as

DlcS

hed,

SrcR

mtTe

mpSp

t, etc.

). Ac

tual ro

om te

mper

ature

Setp

oint is

refle

cted i

n Rm

Temp

ActS

pt. O

verri

dden

by nv

iSetP

t. Use

d to c

ompu

te ZE

B.Co

olStby

Spt

nciTe

mpSe

tPts

(SNV

T_tem

p_se

tpt)

stand

by_c

ool

Degr

ees F

50 to

95De

gree

s C(1

0 to 3

5)

25P, M

XX

Whe

n the

contr

oller

is in

the S

tandb

y mod

e (typ

ically

via a

n occ

upan

cy

sens

or),

the ba

se C

oolin

g Setp

oint is

deter

mine

d by t

he C

oolin

g Stan

dby

Setpo

int va

lue. A

lso, w

hen a

wall

mod

ule se

tpoint

pot is

confi

gure

d, thi

s va

lue se

rves a

s the

uppe

r limi

t on t

he us

er ad

justab

le re

mote

setpo

int po

t (w

all m

odule

).Co

olUno

ccSp

tnc

iTemp

SetP

ts (S

NVT_

temp_

setpt

)un

occu

pied_

cool

Degr

ees F

50 to

95De

gree

s C(1

0 to 3

5)

28P, M

XX

Whe

n the

contr

oller

is in

the U

nocc

upied

mod

e, the

unit r

espo

nds t

o a ca

ll for

cooli

ng ba

sed o

n the

Coo

ling U

nocc

upied

Setp

oint.

HeatO

ccSp

tnc

iTemp

SetP

ts (S

NVT_

temp_

setpt

)oc

cupie

d_he

atDe

gree

s F50

to 95

Degr

ees C

(10 t

o 35)

21P, M

XX

Whe

n the

contr

oller

is in

the O

ccup

ied m

ode,

if the

spac

e tem

pera

ture

drop

s belo

w the

Hea

ting O

ccup

ied S

etpoin

t, the

unit s

witch

es to

the

Heati

ng m

ode.

This

Setpo

int is

used

only

when

ther

e is n

o wall

mod

ule

setpo

int po

t con

figur

ed. O

verri

dden

by nv

iSetP

t. Use

d to c

ompu

te ZE

B.He

atStby

Spt

nciTe

mpSe

tPts

(SNV

T_tem

p_se

tpt)

stand

by_h

eat

Degr

ees F

50 to

95De

gree

s C(1

0 to 3

5)

19P, M

XX

Whe

n the

contr

oller

is in

the S

tandb

y mod

e (typ

ically

via a

n occ

upan

cy

sens

or),

the ba

se H

eatin

g Setp

oint is

deter

mine

d by t

he H

eatin

g Stan

dby

Setpo

int va

lue. A

lso, w

hen a

wall

mod

ule se

tpoint

pot is

confi

gure

d, thi

s va

lue se

rves a

s the

lowe

r limi

t on t

he us

er ad

justab

le re

mote

setpo

int po

t (w

all m

odule

).He

atUno

ccSp

tnc

iTemp

SetP

ts (S

NVT_

temp_

setpt

)un

occu

pied_

heat

Degr

ees F

50 to

95De

gree

s C(1

0 to 3

5)

16P, M

XX

Whe

n the

contr

oller

is in

the U

nocc

upied

mod

e, the

unit r

espo

nds t

o a ca

ll for

heati

ng ba

sed o

n the

Hea

ting U

nocc

upied

Setp

oint.

nviR

eque

st (S

NVT_

obj_r

eque

st)ob

ject_i

d0 t

o 655

351

Requ

est p

rovid

es th

e mec

hanis

m to

requ

est a

partic

ular s

tatus

repo

rt (vi

a St

atus)

for a

partic

ular o

bject

withi

n this

node

. Obje

ct_id

selec

ts the

objec

t be

ing re

feren

ced b

y nviR

eque

st. T

he on

ly va

lid va

lue of

objec

t_id i

s 1 fo

r the

RTU

objec

t and

all o

thers

are i

nvali

d.

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

99 74-2958�2

nviR

eque

st (S

NVT_

obj_r

eque

st)ob

ject_r

eque

stRQ

_NOR

MAL

RQ_D

ISAB

LED

RQ_U

PDAT

E_ST

ATUS

RQ_S

ELF_

TEST

RQ_U

PDAT

E_AL

ARM

RQ_R

EPOR

T_MA

SKRQ

_OVE

RRID

ERQ

_ENA

BLE

RQ_R

MV_O

VERR

IDE

RQ_C

LEAR

_STA

TUS

RQ_C

LEAR

_ALA

RMRQ

_NUL

0 1 2 3 4 5 6 7 8 9 10 255

RQ_N

ORMA

LW

hen o

bject_

requ

est is

RQ_

NORM

AL or

RQ_

UPDA

TE_S

TATU

S the

n the

sta

tus (v

ia St

atus)

will b

e rep

orted

for t

he ob

ject a

ddre

ssed

by ob

ject_i

d. W

hen o

bject_

requ

est is

RQ_

REPO

RT_M

ASK

then t

he st

atus b

its w

ill be

re

porte

d tha

t are

supp

orted

in nv

oStat

us by

the o

bject

addr

esse

d by

objec

t_id.

Bits

that a

re su

ppor

ted by

the o

bject

are s

et to

one.

All o

ther

objec

t_req

uest

items

are n

ot su

ppor

ted at

this

time a

nd w

ill re

turn a

n inv

alid_

requ

est (

Statu

s) in

the ob

ject s

tatus

.

DestH

vacM

ode

nviA

pplM

ode

(SNV

T_hv

ac_m

ode)

HVAC

_AUT

OHV

AC_H

EAT

HVAC

_MRN

G_W

RMUP

HVAC

_COO

LHV

AC_N

IGHT

_PUR

GEHV

AC_P

RE_C

OOL

HVAC

_OFF

HVAC

_TES

THV

AC_E

MERG

_HEA

THV

AC_F

AN_O

NLY

HVAC

_NUL

0 1 2 3 4 5 6 7 8 9 255

HVAC

_AUT

OM

XX

XX

XAp

plMod

e is a

n inp

ut tha

t coo

rdina

tes th

e roo

f top u

nit co

ntroll

er op

erati

on

with

other

contr

oller

s. HV

AC_N

IGHT

_PUR

GEHV

AC_P

RE_C

OOL

HVAC

_MRN

G_W

RMUP

HVAC

_NUL

HVAC

_TES

T ar

e not

supp

orted

and w

ill de

fault t

o the

HVA

C_AU

TO se

tting

if rec

eived

.

DestM

anOc

cnv

iMan

Occ

(SNV

T_oc

cupa

ncy)

OC_O

CCUP

IED

OC_U

NOCC

UPIE

DOC

_BYP

ASS

OC_S

TAND

BYOC

_NUL

0 1 2 3 255

OC_N

ULX

XX

ManO

cc is

an in

put fr

om a

netw

ork c

onne

cted o

pera

tor in

terfac

e or o

ther

node

that

indica

tes th

e stat

e of a

man

ual o

ccup

ancy

contr

ol thu

s ove

r rid

ing th

e sch

edule

d occ

upan

cy st

ate. M

anOc

c is u

sed a

long w

ith ot

her

occu

panc

y inp

uts to

calcu

late t

he ef

fectiv

e occ

upan

cy of

the n

ode.

See t

he

Data1

.Effe

ctOcc

and D

ata1.N

etMan

Occ f

or m

ore d

etails

.The

valid

en

umer

ated v

alues

have

the f

ollow

ing m

eanin

gs: O

C_OC

CUPI

ED

indica

tes oc

cupie

d. OC

_UNO

CCUP

IED

indica

tes no

t occ

upied

. OC

_BYP

ASS

indica

tes th

at the

spac

e is o

ccup

ied fo

r Au

x2Se

tPt.B

ypas

sTim

e sec

onds

after

Man

Occ i

s firs

t set

to OC

_BYP

ASS.

Th

e tim

ing is

done

by th

e byp

ass t

imer

in th

is no

de. If

Man

Occ c

hang

es to

an

other

value

the t

imer

is st

oppe

d.OC_

STAN

DBY

indica

tes th

at the

spac

e is

in sta

ndby

mod

e.OC_

NUL a

nd al

l uns

pecif

ied va

lues m

eans

that

no

manu

al oc

cupa

ncy c

ontro

l is re

ques

ted. W

hen M

anOc

c cha

nges

from

OC

_OCC

UPIE

D, O

C_UN

OCCU

PIED

, OC_

BYPA

SS, o

r OC_

STAN

DBY

to OC

_NUL

, any

bypa

ss co

nditio

n is c

ance

led.

DestR

mTem

pSpt

nviS

etPoin

t (S

NVT_

temp_

p)De

gree

s F50

to 95

Degr

ees C

(10 t

o 35)

SI_IN

VALID

XX

XSe

tPoin

t is an

inpu

t netw

ork v

ariab

le us

ed to

deter

mine

the t

empe

ratur

e co

ntrol

point

of th

e nod

e. If S

etPoin

t is no

t SI_I

NVAL

ID, th

en it

is us

ed to

de

termi

ne th

e con

trol p

oint o

f the n

ode.

If SetP

oint is

SI_I

NVAL

ID, th

en

other

mea

ns ar

e use

d to d

eterm

ine th

e con

trol p

oint. S

ee

Data2

.Temp

Contr

olPt fo

r mor

e info

rmati

on.

DestS

ptOffs

etnv

iSetP

tOffs

et (S

NVT_

temp_

p)De

gree

s F-1

8 to 1

8De

gree

s C-1

0 to 1

0

0X

XX

XSe

tPtO

ffset

is inp

ut fro

m an

oper

ator t

ermi

nal o

r fro

m an

ener

gy

mana

geme

nt sy

stem

used

to sh

ift the

effec

tive t

empe

ratur

e setp

oint b

y ad

ding S

etPtO

ffset

to the

othe

rwise

calcu

lated

setpo

int. If

the v

alue i

s ou

tside

the a

llowe

d ran

ge of

-10 t

o +10

degr

ees C

(-18

to 18

degr

ees F

), the

n the

node

uses

the v

alue o

f the n

eare

st ra

nge l

imit.

Tabl

e 26

. LO

NM

AR

/Ope

n Sy

stem

Poi

nts.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.Failure Detect

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 100

SrcR

mTem

pActS

ptnv

oEffe

ctSetP

t (S

NVT_

temp_

p)De

gree

s F50

to 95

Degr

ees C

(10 t

o 35)

SI_IN

VALID

XX

Effec

tSetP

t is th

e cur

rent

tempe

ratur

e con

trol p

oint (

such

that

the cu

rrent

actua

l spa

ce te

mper

ature

setpo

int w

hich t

he co

ntroll

er is

pres

ently

tryin

g to

maint

ain in

the c

ondit

ioned

spac

e). S

ee D

ata2.T

empC

ontro

lPt fo

r mor

e de

tails.

Effe

ctSetP

t is up

dated

acco

rding

to th

e SGP

U me

chan

ism w

here

a sig

nifica

nt ch

ange

is pl

us or

minu

s 0.07

degr

ees C

(0.13

degr

ees F

).De

stRmT

emp

nviS

pace

Temp

(S

NVT_

temp_

p)De

gree

s F14

to 12

2De

gree

s C(-1

0 to 5

0)

SI_IN

VALID

XX

XX

Spac

eTem

p is t

he sp

ace t

empe

ratur

e sen

sed b

y ano

ther n

ode a

nd is

typ

ically

boun

d to S

pace

Temp

of an

other

node

havin

g a sp

ace t

empe

ratur

e se

nsor.

If Sp

aceT

emp h

as a

value

othe

r tha

n SI_I

NVAL

ID it

is us

ed as

the

sens

ed sp

ace t

empe

ratur

e by t

he no

de ra

ther t

han u

sing a

ny lo

cal h

ard-

wire

d sen

sor. I

f the v

alue i

s outs

ide th

e allo

wed r

ange

of -1

0 to 5

0 deg

rees

C

(-18 t

o 90 d

egre

es F

), the

n the

node

uses

the v

alue o

f the n

eare

st ra

nge

limit.

Whe

n Spa

ceTe

mp is

not b

ound

to an

other

node

, Spa

ceTe

mp m

ay be

us

ed to

fix th

e sen

sed t

empe

ratur

e. A

mana

geme

nt no

de m

ay w

rite a

value

oth

er th

an S

I_INV

ALID

, cau

sing t

he no

de to

use S

pace

Temp

inste

ad of

the

hard

-wire

d sen

sor. A

n app

licati

on re

start

or po

wer f

ailur

e cau

ses t

he fix

ed

sens

or va

lue to

be fo

rgott

en an

d Spa

ceTe

mp to

be re

turne

d to

SI_IN

VALID

.Sr

cRmT

emp

nvoS

pace

Temp

(S

NVT_

temp_

p)De

gree

s F14

to 12

2De

gree

s C(-1

0 to 5

0)

SI_IN

VALID

XX

Spac

eTem

p is t

he se

nsed

spac

e tem

pera

ture f

rom

the lo

cally

wire

d sen

sor.

Spac

eTem

p is t

ypica

lly bo

und t

o Spa

ceTe

mp of

anoth

er no

de w

hich m

ay

not h

ave i

ts ow

n spa

ce te

mper

ature

sens

or bu

t con

trol th

e sam

e spa

ce.

The r

epor

ted sp

ace t

empe

ratur

e inc

ludes

the o

ffset

corre

ction

Co

nfig.S

pace

Temp

Zero

Cal. I

f the s

pace

temp

eratu

re se

nsor

is no

t co

nnec

ted or

is sh

orted

, or if

Spa

ceTe

mp is

boun

d to a

nothe

r nod

e, the

n Sp

aceT

emp i

s set

to SI

_INVA

LID.

DestO

aTem

pnv

iOdT

emp

(SNV

T_tem

p_p)

Degr

ees F

-40 t

o 122

Degr

ees C

(-40 t

o 50)

SI_IN

VALID

MX

XX

XOd

Temp

allow

s one

outsi

de ai

r tem

pera

ture s

enso

r at a

node

to be

shar

ed

by m

any o

ther n

odes

. Whe

n OdT

emp i

s not

SI_IN

VALID

, then

any l

ocal

sens

or is

igno

red b

y the

loca

l con

trol a

lgorith

m an

d OdT

emp i

s use

d ins

tead.

If the

value

is ou

tside

the a

llowe

d ran

ge of

-40 t

o 50 d

egre

es C

(-72

to 90

degr

ees F

), the

n the

node

uses

the v

alue o

f the n

eare

st ra

nge

limit.

SrcO

aTem

pnv

oOdT

emp

(SNV

T_tem

p_p)

Degr

ees F

-40 t

o 122

Degr

ees C

(-40 t

o 50)

SI_IN

VALID

MX

XOd

Temp

allow

s the

loca

l outd

oor t

empe

ratur

e sen

sor t

o be s

hare

d with

oth

er no

des a

nd is

typic

ally b

ound

to O

dTem

p on o

ther n

odes

. If th

e loc

al se

nsor

is co

nfigu

red b

y Sele

ct, O

dTem

p is p

eriod

ically

sent

on th

e netw

ork.

If the

loca

l sen

sor is

not c

onfig

ured

or cu

rrentl

y sho

wing

an er

ror, t

he va

lue

is SI

_INVA

LID.

DestO

aHum

nviO

dHum

(S

NVT_

lev_p

erce

nt)Pe

rcenta

ge10

to 90

SI_IN

VALID

MX

XX

XOd

Hum

allow

s one

outdo

or hu

midit

y sen

sor a

t a no

de to

be sh

ared

by

many

othe

r nod

es. W

hen n

viOdH

um is

not S

I_INV

ALID

, then

the l

ocal

sens

or, is

igno

red b

y the

loca

l con

trol a

lgorith

m an

d OdH

um is

used

ins

tead.

If the

value

is ou

tside

the a

llowe

d ran

ge (1

0 to 9

0 per

cent)

, then

the

node

uses

the v

alue o

f the n

eare

st ra

nge l

imit.

SrcO

aHum

nvoO

dHum

(S

NVT_

lev_p

erce

nt)Pe

rcenta

ge10

to 90

SI_IN

VALID

MX

XOd

Hum

allow

s the

loca

l outd

oor h

umidi

ty se

nsor

to be

shar

ed w

ith ot

her

node

s and

is ty

picall

y bou

nd to

OdH

um on

othe

r nod

es. If

the l

ocal

sens

or

is co

nfigu

red b

y Sele

ct, O

dHum

is pe

riodic

ally s

ent o

n the

netw

ork.

If the

loc

al se

nsor

is no

t con

figur

ed or

curre

ntly s

howi

ng an

erro

r, the

value

is

SI_IN

VALID

.

Tabl

e 26

. LO

NM

AR

/Ope

n Sy

stem

Poi

nts.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.Failure Detect

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

101 74-2958�2

DestE

merg

Cmd

nviE

merg

(S

NVT_

hvac

_eme

rg)

EMER

G_NO

RMAL

EMER

G_PR

ESSU

RIZE

EMER

G_DE

PRES

SURI

ZEEM

ERG_

PURG

EEM

ERG_

SHUT

DOW

NEM

ERG_

NUL

0 1 2 3 4 255

EMER

G_NO

RMAL

MX

XX

XEm

erg i

s an e

merg

ency

inpu

t from

a de

vice t

hat d

eterm

ines t

he co

rrect

actio

n dur

ing a

given

emer

genc

y (su

ch as

a fire

). If E

merg

is

EMER

G_NO

RMAL

the f

an an

d eco

nomi

zer d

ampe

r are

contr

olled

by th

e he

ating

and c

oolin

g con

trol a

lgorith

m. If

Emer

g is E

MERG

_PRE

SSUR

IZE,

the

n the

fan i

s con

trolle

d on a

nd th

e eco

nomi

zer d

ampe

r is op

en. If

Eme

rg

is EM

ERG_

DEPR

ESSU

RIZE

, then

the f

an is

contr

olled

on an

d the

ec

onom

izer d

ampe

r is cl

osed

. If E

merg

is E

MERG

_SHU

TDOW

N, th

en th

e fan

is co

ntroll

ed of

f and

the e

cono

mize

r dam

per is

clos

ed. If

Eme

rg is

EM

ERG_

PURG

E, th

e fan

and d

ampe

r go t

o the

state

spec

ified b

y Co

nfig.S

moke

Contr

ol. If

Emer

g is n

ot co

nfigu

red t

hen i

t is se

t to

EMER

G_NU

L.Sr

cUnit

Statu

snv

oUnit

Statu

s (S

NVT_

hvac

_stat

us)

mode

HVAC

_AUT

OHV

AC_H

EAT

HVAC

_MRN

G_W

RMUP

HVAC

_COO

LHV

AC_N

IGHT

_PUR

GEHV

AC_P

RE_C

OOL

HVAC

_OFF

HVAC

_TES

THV

AC_E

MERG

_HEA

THV

AC_F

AN_O

NLY

HVAC

_NUL

0 1 2 3 4 5 6 7 8 9 255

HVAC

_NUL

MX

XMo

de is

set a

ccor

ding t

o the

Data

1.mod

e. If D

ata1.m

ode i

s ST

ART_

UP_W

AIT,

SMOK

E_EM

ERGE

NCY,

or FR

EEZE

_PRO

TECT

, mod

e is

set to

HVA

C_NU

L whic

h ind

icates

that

the no

de is

in a

mode

not

supp

orted

by th

e SNV

T_hv

ac_m

ode d

ata ty

pe. If

Data

1.mod

e is H

EAT,

then m

ode i

s set

to HV

AC_H

EAT

which

indic

ates t

hat h

eatin

g ene

rgy i

s be

ing su

pplie

d to t

he co

ntroll

ed sp

ace.

If Data

1.mod

e is C

OOL,

then m

ode

is se

t to H

VAC_

COOL

, whic

h ind

icates

that

cooli

ng en

ergy

is be

ing

supp

lied t

o the

contr

olled

spac

e. If D

ata1.m

ode i

s OFF

_MOD

E or

DI

SABL

ED_M

ODE,

then

mod

e is s

et to

HVAC

_OFF

whic

h ind

icates

that

the no

de is

not r

unnin

g its

norm

al tem

pera

ture c

ontro

l and

the o

utputs

are

not tu

rned

off. I

f Data

1.mod

e is E

MERG

_HEA

T, mo

de is

set to

HV

AC_E

MERG

_HEA

T wh

ere,

in a h

eat p

ump a

pplic

ation

, the c

ompr

esso

r sta

ges a

re di

sable

d and

only

auxil

iary h

eatin

g stag

es ar

e tur

ned o

n. If

Data1

.mod

e is M

ANUA

L or F

ACTO

RY_T

EST,

mode

is se

t to H

VAC_

TEST

wh

ich in

dicate

s tha

t the n

ode i

s in a

man

ual o

r tes

t mod

e. If D

ata1.m

ode i

s FA

N_ON

LY, m

ode i

s set

to HV

AC_F

AN_O

NLY

which

indic

ates t

hat th

e fan

is

runn

ing bu

t the s

pace

temp

eratu

re co

ntrol

is tur

ned o

ff.nv

oUnit

Statu

s (S

NVT_

hvac

_stat

us)

heat_

outpu

t_prim

ary

Perce

ntage

0 to 1

000

heat_

outpu

t_prim

ary r

epor

ts the

curre

nt pe

rcenta

ge of

heati

ng st

ages

or

modu

lating

heat

turne

d on.

If the

node

is co

ntroll

ing a

heat

pump

, he

at_ou

tput_p

rimar

y rep

orts

the cu

rrent

perce

ntage

of co

mpre

ssor

stag

es

turne

d on w

hen t

he no

de is

in th

e HVA

C_HE

AT m

ode.

nvoU

nitSt

atus

(SNV

T_hv

ac_s

tatus

)he

at_ou

tput_s

econ

dary

Perce

ntage

0 to 1

000

If the

node

is co

ntroll

ing a

heat

pump

, hea

t_outp

ut_se

cond

ary r

epor

ts the

cu

rrent

perce

ntage

of au

xiliar

y hea

ting s

tages

turn

ed on

whe

n the

node

is

in the

HVA

C_HE

AT or

HVA

C_EM

ERG_

HEAT

mod

e. If t

he no

de is

not

contr

olling

a he

at pu

mp, h

eat_o

utput_

seco

ndar

y is s

et to

zero

.nv

oUnit

Statu

s (S

NVT_

hvac

_stat

us)

cool_

outpu

tPe

rcenta

ge0 t

o 100

0co

ol_ou

tput r

epor

ts the

curre

nt pe

rcenta

ge of

cooli

ng st

ages

or m

odula

ting

cool

turne

d on.

If the

node

is co

ntroll

ing a

heat

pump

, coo

l_outp

ut re

ports

the

curre

nt pe

rcenta

ge of

comp

ress

or st

ages

turn

ed on

whe

n the

node

is in

the

HVA

C_CO

OL m

ode.

nvoU

nitSt

atus

(SNV

T_hv

ac_s

tatus

)ec

on_o

utput

Perce

ntage

0 to 1

000

If the

re is

a mo

dulat

ing ec

onom

izer c

onfig

ured

, eco

n_ou

tput r

epor

ts the

pe

rcenta

ge th

at the

econ

omize

r dam

per is

open

ed. If

no ec

onom

izer is

co

nfigu

red,

econ

_outp

ut re

ports

0.nv

oUnit

Statu

s (S

NVT_

hvac

_stat

us)

fan_o

utput

Perce

ntage

0 to 1

000

Whe

n the

fan i

s run

ning,

fan_o

utput

is 10

0 per

cent,

and w

hen t

he fa

n is n

ot ru

nning

, fan_

outpu

t is 0

perce

nt.

Tabl

e 26

. LO

NM

AR

/Ope

n Sy

stem

Poi

nts.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.Failure Detect

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 102

nvoU

nitSt

atus

(SNV

T_hv

ac_s

tatus

)in_

alarm

FALS

ETR

UEAL

ARM_

NOTI

FY_D

ISAB

LED

0 1 255

FALS

EW

hen t

here

is an

alar

m re

porte

d by A

larmS

tatus

, then

in_a

larm

is se

t to 1

(TRU

E), e

lse in

_alar

m is

set to

0 (F

ALSE

). If a

larms

repo

rting i

s su

ppre

ssed

via M

anua

lMod

e, the

n in_

alarm

is se

t to

ALAR

M_NO

TIFY

_DIS

ABLE

D.nv

iInUs

e(un

signe

d lon

g)0 T

o 655

350 t

o FFF

FInU

se is

used

by a

mana

geme

nt no

de to

indic

ate to

all o

ther m

anag

emen

t no

des t

hat it

is lo

gged

on to

the E

xcel

10 no

de an

d tha

t they

shou

ld no

t try

to int

erac

t with

any o

f the E

xcel

10s n

etwor

k var

iables

. Befo

re th

e ma

nage

ment

node

read

s or w

rites a

ny ne

twor

k var

iables

, the m

anag

emen

t no

de ch

ecks

nviIn

Use f

or a

zero

value

mea

ning n

o othe

r man

agem

ent

node

s are

alre

ady l

ogge

d on a

nd th

at a m

anag

emen

t nod

e may

log o

n to

the no

de. T

hen t

he m

anag

emen

t nod

e write

s a nu

mber,

1 thr

ough

6553

4, to

nviIn

Use a

nd pe

riodic

ally w

rites t

he sa

me va

lue to

indic

ate th

at the

ma

nage

ment

node

is st

ill log

ged o

n. If t

here

are n

o write

s mad

e to

nviIn

Use f

or ap

prox

imate

ly 60

seco

nds,

then t

he E

xcel

10 re

sets

nviIn

Use

to ze

ro to

autom

atica

lly lo

g off t

he m

anag

emen

t nod

e. Be

fore i

ntera

cting

wi

th an

y netw

ork v

ariab

les, th

e man

agem

ent n

ode v

erifie

s tha

t the

nviIn

Use h

as no

t cha

nged

. The

man

agem

ent n

ode l

ogs o

ff by w

riting

0 to

nviIn

Use.D

uring

powe

r up,

an ap

plica

tion r

estar

t, or r

eturn

to on

-line f

rom

off-lin

e, the

Exc

el 10

sets

InUse

to 65

535 t

o ind

icate

to the

man

agem

ent

node

that

it has

retur

ned t

o on-

line.

nvoS

tatus

(S

NVT_

obj_r

eque

st)ob

ject_i

d0 t

o 655

350

MX

objec

t_id i

s set

to the

curre

nt va

lue of

nviR

eque

st.ob

ject_i

d

nvoS

tatus

(S

NVT_

obj_r

eque

st)inv

alid_

idFA

LSE

TRUE

0 1FA

LSE

If Req

uest.

Objec

t_id i

s not

a vali

d obje

ct, in

valid

_id is

set to

1 (T

RUE)

oth

erwi

se it

is se

t to 0

(FAL

SE).

nvoS

tatus

(S

NVT_

obj_r

eque

st)inv

alid_

requ

est

FALS

ETR

UE0 1

FALS

EIf R

eque

st.ob

ject_r

eque

st is

not a

valid

requ

est fo

r the

objec

t add

ress

ed,

invali

d_re

ques

t is se

t to 1

(TRU

E) ot

herw

ise it

is se

t to 0

(FAL

SE).

nvoS

tatus

(S

NVT_

obj_r

eque

st)dis

abled

FALS

ETR

UE0 1

FALS

ETh

e disa

bled f

ield i

s not

supp

orted

and i

s set

to 0 (

FALS

E) un

less

Requ

est.o

bject_

requ

est is

RQ_

REPO

RT_M

ASK,

then

disa

bled a

nd

in_ala

rm ar

e set

to 1 (

TRUE

) to i

ndica

te tha

t thes

e fun

ction

s are

supp

orted

wh

ile al

l othe

r fiel

ds ar

e set

to 0 (

FALS

E).

nvoS

tatus

(S

NVT_

obj_r

eque

st)ou

t_of_l

imits

FALS

ETR

UE0 1

FALS

ETh

e out_

of_lim

its fie

ld is

not s

uppo

rted a

nd is

set to

0 (F

ALSE

).

nvoS

tatus

(S

NVT_

obj_r

eque

st)op

en_c

ircuit

FALS

ETR

UE0 1

FALS

ETh

e ope

n_cir

cuit f

ield i

s not

supp

orted

and i

s set

to 0 (

FALS

E).

nvoS

tatus

(S

NVT_

obj_r

eque

st)ou

t_of_s

ervic

eFA

LSE

TRUE

0 1FA

LSE

The o

ut_of_

servi

ce fie

ld is

not s

uppo

rted a

nd is

set to

0 (F

ALSE

).

nvoS

tatus

(S

NVT_

obj_r

eque

st)me

chan

ical_f

ault

FALS

ETR

UE0 1

FALS

ETh

e mec

hanic

al_fau

lt fiel

d is n

ot su

ppor

ted an

d is s

et to

0 (FA

LSE)

.

nvoS

tatus

(S

NVT_

obj_r

eque

st)fee

dbac

k_fai

lure

FALS

ETR

UE0 1

FALS

ETh

e fee

dbac

k_fai

lure f

ield i

s not

supp

orted

and i

s set

to 0 (

FALS

E).

nvoS

tatus

(S

NVT_

obj_r

eque

st)ov

er_r

ange

FALS

ETR

UE0 1

FALS

ETh

e ove

r_ra

nge f

ield i

s not

supp

orted

and i

s set

to 0 (

FALS

E).

nvoS

tatus

(S

NVT_

obj_r

eque

st)un

der_

rang

eFA

LSE

TRUE

0 1FA

LSE

The u

nder

_ran

ge fie

ld is

not s

uppo

rted a

nd is

set to

0 (F

ALSE

).

Tabl

e 26

. LO

NM

AR

/Ope

n Sy

stem

Poi

nts.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.Failure Detect

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

103 74-2958�2

nvoS

tatus

(S

NVT_

obj_r

eque

st)ele

ctrica

l_fau

ltFA

LSE

TRUE

0 1FA

LSE

The e

lectric

al_fau

lt fiel

d is n

ot su

ppor

ted an

d is s

et to

0 (FA

LSE)

.

nvoS

tatus

(S

NVT_

obj_r

eque

st)un

able_

to_me

asur

eFA

LSE

TRUE

0 1FA

LSE

The u

nable

_to_m

easu

re fie

ld is

not s

uppo

rted a

nd is

set to

0 (F

ALSE

).

nvoS

tatus

(S

NVT_

obj_r

eque

st)co

mm_fa

ilure

FALS

ETR

UE0 1

FALS

ETh

e com

m_fai

lure f

ield i

s not

supp

orted

and i

s set

to 0 (

FALS

E).

nvoS

tatus

(S

NVT_

obj_r

eque

st)fai

l_self

_test

FALS

ETR

UE0 1

FALS

ETh

e fail

_self

_test

field

is no

t sup

porte

d and

is se

t to 0

(FAL

SE).

nvoS

tatus

(S

NVT_

obj_r

eque

st)se

lf_tes

t_in_

prog

ress

FALS

ETR

UE0 1

FALS

ETh

e self

_test_

in_pr

ogre

ss fie

ld is

not s

uppo

rted a

nd is

set to

0 (F

ALSE

).

nvoS

tatus

(S

NVT_

obj_r

eque

st)loc

ked_

out

FALS

ETR

UE0 1

FALS

ETh

e loc

ked_

out fi

eld is

not s

uppo

rted a

nd is

set to

0 (F

ALSE

).

nvoS

tatus

(S

NVT_

obj_r

eque

st)ma

nual_

contr

olFA

LSE

TRUE

0 1FA

LSE

The m

anua

l_con

trol fi

eld is

not s

uppo

rted a

nd is

set to

0 (F

ALSE

).

nvoS

tatus

(S

NVT_

obj_r

eque

st)in_

alarm

FALS

ETR

UE0 1

FALS

EIf t

here

are c

urre

ntly a

ny ac

tive a

larms

repo

rted b

y SrcU

nitSt

atus.i

n_ala

rm

or S

rcUnit

Statu

s.in_

alarm

is se

t to A

LARM

_NOT

IFY_

DISA

BLED

,in_a

larm

is se

t to 1

(TRU

E), o

therw

ise in

_alar

m is

set to

0 (F

ALSE

). W

hen

Requ

est.o

bject_

requ

est is

RQ_

REPO

RT_M

ASK,

then

disa

bled a

nd

in_ala

rm ar

e set

to 1 (

TRUE

) to i

ndica

te tha

t thes

e fun

ction

s are

supp

orted

wh

ile al

l othe

r fiel

ds ar

e set

to 0 (

FALS

E).

nvoS

tatus

(S

NVT_

obj_r

eque

st)in_

over

ride

FALS

ETR

UE0 1

FALS

ETh

e in_

over

ride f

ield i

s not

supp

orted

and i

s set

to 0 (

FALS

E).

DestO

ccSe

nsor

nviS

enso

rOcc

(S

NVT_

occu

panc

y)OC

_OCC

UPIE

DOC

_UNO

CCUP

IED

OC_B

YPAS

SOC

_STA

NDBY

OC_N

UL

0 1 2 3 255

OC_N

ULM

XX

XX

nviS

enso

rOcc

allow

s an o

ccup

ancy

sens

or at

anoth

er no

de to

be us

ed as

the

occu

panc

y sen

sor f

or th

is no

de an

d is t

ypica

lly bo

und t

o Sen

sorO

cc of

an

other

node

. The

nviS

enso

rOcc

inpu

t mus

t sho

w OC

_UNO

CCUP

IED

for

300 s

econ

ds be

fore i

t is us

ed by

the c

ontro

ller f

or tr

igger

ing U

N_OC

op

erati

on. T

his m

akes

it po

ssibl

e for

seve

ral o

ccup

ancy

sens

ors t

o be

ORed

toge

ther b

y bind

ing th

em al

l to nv

iSen

sorO

cc. If

any o

ne bo

und

occu

panc

y sen

sor s

hows

occu

panc

y, the

n Sen

sorO

cc sh

ows o

ccup

ancy

for

up to

300 s

econ

ds af

ter th

e las

t sen

sor s

hows

OC_

OCCU

PIED

. The

va

lid st

ates h

ave t

he fo

llowi

ng m

eanin

gs: O

C_OC

CUPI

ED in

dicate

s oc

cupie

d. OC

_BYP

ASS,

OC_

STAN

DBY,

and a

ll uns

pecif

ied va

lues

indica

tes th

e sam

e as O

C_OC

CUPI

ED. O

C_UN

OCCU

PIED

or O

C_NU

L ind

icates

not o

ccup

ied.

SrcO

ccSe

nsor

nvoS

enso

rOcc

(S

NVT_

occu

panc

y)OC

_OCC

UPIE

DOC

_UNO

CCUP

IED

OC_B

YPAS

SOC

_STA

NDBY

OC_N

UL

0 1 2 3 255

OC_N

ULM

XX

nvoS

enso

rOcc

is an

outpu

t sho

wing

the c

urre

nt sta

te of

the ha

rd w

ired

occu

panc

y sen

sor. T

he va

lid st

ates a

re as

follo

ws: O

C_OC

CUPI

ED

indica

tes th

at the

spac

e is o

ccup

ied. O

C_UN

OCCU

PIED

indic

ates t

hat th

e sp

ace i

s not

occu

pied.

OC_N

UL m

eans

no ou

tput is

avail

able

beca

use i

t is

not c

onfig

ured

.

Tabl

e 26

. LO

NM

AR

/Ope

n Sy

stem

Poi

nts.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.Failure Detect

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 104

nviW

indow

(S

NVT_

switc

h)va

lue0 t

o 100

0W

indow

allow

s the

wind

ow se

nsor

from

anoth

er no

de to

be us

ed as

the

wind

ow se

nsor

and i

s typ

ically

boun

d to n

voW

indow

of an

other

node

. W

indow

mus

t sho

w tha

t the w

indow

is cl

osed

for 3

00 se

cond

s befo

re

Wind

ow is

used

as w

indow

clos

ed. T

his m

akes

it po

ssibl

e for

seve

ral

wind

ow se

nsor

s to b

e ORe

d tog

ether

by bi

nding

them

all to

nviW

indow

. If

any o

ne bo

und w

indow

sens

or sh

ows w

indow

open

, then

Wind

ow sh

ows

wind

ow op

en fo

r up t

o 300

seco

nds a

fter t

he la

st se

nsor

show

s wind

ow

close

d. If t

he st

ate is

SW

_OFF

or S

W_N

UL, th

en th

e res

ult is

Wind

ow

Clos

ed. If

the s

tate i

s SW

_ON

and t

he va

lue is

0, th

en th

e res

ult is

Wind

ow

Clos

ed. If

the n

ode r

eceiv

es th

is co

mbina

tion o

f stat

e and

value

, then

state

is

set to

SW

_OFF

. If th

e stat

e is S

W_O

N an

d the

value

is no

t zer

o, the

n the

re

sult i

s Wind

ow O

pen.

NOTE

: nviW

indow

is ca

lled n

viEne

rgyH

oldOf

f in

the L O

NMAR

K com

plian

ce pr

ofile.

DestW

ndw

nviW

indow

(S

NVT_

switc

h)sta

teSW

_OFF

SW_O

NSW

_NUL

0 1 255

SW_N

ULM

XX

XX

See t

he pr

eced

ing.

SrcW

ndwC

tnv

oWind

ow

(SNV

T_sw

itch)

value

0 to 1

000

XSe

e the

prec

eding

.NOT

E: nv

oWind

ow is

calle

d nviE

nerg

yHold

Off in

the

LonM

ark c

ompli

ance

profi

le.Sr

cWnd

wnv

oWind

ow

(SNV

T_sw

itch)

state

SW_O

FFSW

_ON

SW_N

UL

0 1 255

SW_N

ULM

XX

Wind

ow al

lows t

he ha

rd w

ired w

indow

sens

or to

be us

ed by

othe

r nod

es on

the

netw

ork.

The v

alid s

tates

are a

s foll

ows:

If the

state

is S

W_O

FF an

d the

va

lue is

0 the

n the

resu

lt is W

indow

Clos

ed. If

the s

tate i

s SW

_ON

and t

he

value

is 10

0 per

cent,

the r

esult

is W

indow

Ope

n. If t

he st

ate is

SW

_NUL

an

d the

value

is 0,

the r

esult

is W

indow

Sen

sor N

ot Co

nfigu

red.

NOTE

: nv

oWind

ow is

calle

d nviE

nerg

yHold

Off in

the L

onMa

rk co

mplia

nce p

rofile

.nv

iEco

n(S

NVT_

switc

h)va

lue0 t

o 100

0nv

iEco

n allo

ws on

e con

trolle

r to d

eterm

ine th

e suit

abilit

y of o

utdoo

r air f

or

free c

oolin

g and

shar

e this

with

man

y othe

r nod

es. W

hen E

con.s

tate i

s not

SW_N

UL, th

en th

e loc

al se

nsor

selec

ted by

Con

fig.E

conE

nable

is ig

nore

d an

d Eco

n is u

sed i

nstea

d. Th

e inp

uts st

ates h

ave t

he fo

llowi

ng m

eanin

gs: If

the

state

is S

W_O

FF or

othe

r and

the v

alue i

s don

�t car

e, the

n the

outdo

or

air is

not s

uitab

le for

free

cooli

ng. If

the s

tate i

s SW

_ON

and t

he va

lue is

0,

then t

he ou

tdoor

air is

not s

uitab

le for

free

cooli

ng. If

the n

ode r

eceiv

es th

is co

mbina

tion o

f stat

e and

value

, then

state

is se

t to S

W_O

FF. If

the s

tate i

s SW

_ON

and t

he va

lue is

not z

ero,

then o

utdoo

r is su

itable

for f

ree c

oolin

g. If t

he st

ate is

SW

_NUL

, then

the n

etwor

k var

iable

is no

t bou

nd, th

e co

mmun

icatio

ns pa

th fro

m the

send

ing no

de ha

s fail

ed, o

r the

send

ing

node

has f

ailed

. Outd

oor a

ir is n

ot su

itable

for f

ree c

oolin

g.De

stEco

nEna

blenv

iEco

n(S

NVT_

switc

h)sta

teSW

_OFF

SW_O

NSW

_NUL

0 1 255

SW_N

ULM

XX

XX

For n

viEco

n.stat

e, re

fer to

nviE

con.v

alue.

Tabl

e 26

. LO

NM

AR

/Ope

n Sy

stem

Poi

nts.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.Failure Detect

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

105 74-2958�2

SrcE

conE

nCt

nvoE

con

(SNV

T_sw

itch)

value

0 to 1

000

Xnv

oEco

n allo

ws on

e con

trolle

r to d

eterm

ine th

e suit

abilit

y of o

utdoo

r air f

or

free c

oolin

g and

shar

e this

with

othe

r nod

es an

d is t

ypica

lly bo

und t

o Eco

n on

othe

r nod

es. If

the e

cono

mize

r fun

ction

is co

nfigu

red b

y Co

nfig.E

conE

nable

, Eco

n is p

eriod

ically

calcu

lated

from

the l

ocal

sens

or

spec

ified b

y Con

fig.E

conE

nable

and i

s sen

t on t

he ne

twor

k. Ec

on do

es no

t aff

ect E

con.

The o

utput

has t

he fo

llowi

ng st

ates:

If the

state

is S

W_O

FF

and t

he va

lue is

0, th

en th

e outd

oor a

ir is n

ot su

itable

for f

ree c

oolin

g. If t

he

state

is SW

_ON

and t

he va

lue is

100 p

erce

nt, th

en th

e outd

oor a

ir is

suita

ble fo

r fre

e coo

ling.

If the

state

is S

W_N

UL an

d the

value

is 0,

the

corre

spon

ding e

cono

mize

r fun

ction

is no

t ena

bled b

ecau

se

Confi

g.Eco

nEna

ble is

ECO

N_NU

L, DI

FF_T

EMP,

or D

IFF_

ENTH

or

beca

use t

he se

lected

sens

or ha

s fail

ed.

SrcE

conE

nable

nvoE

con

(SNV

T_sw

itch)

state

SW_O

FFSW

_ON

SW_N

UL

0 1 255

SW_N

ULM

XX

For n

voEc

on.st

ate, r

efer t

o nvo

Econ

.value

.

Tabl

e 26

. LO

NM

AR

/Ope

n Sy

stem

Poi

nts.

(Con

tinue

d)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Hardware Config.Manual Config.Failure Detect

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 106

Tabl

e 27

. Dire

ct A

cces

s A

nd S

peci

al P

oint

s.

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

tsDe

stMan

Mode

nviM

anua

lMod

eMO

DE_E

NABL

EMO

DE_D

ISAB

LEMO

DE_M

ANUA

LSU

PPRE

SS_A

LARM

SUN

SUPP

RESS

_ALA

RMS

0 1 2 3 4

MODE

_ENA

BLE

XX

XMa

nualM

ode i

s an i

nput

which

is us

ed to

disa

ble th

e Exc

el 10

s con

trol a

lgorith

ms

and t

o man

ually

set th

e phy

sical

outpu

ts. M

anua

lMod

e rem

ains u

ncha

nged

until

anoth

er m

ode h

as be

en co

mman

ded o

r an a

pplic

ation

resta

rt ha

s bee

n per

forme

d. Se

e the

Data

1.mod

e for

mor

e deta

ils.T

he va

lid en

umer

ated v

alues

are:

MODE

_ENA

BLE

enab

les th

e nod

e so t

hat th

e con

trol a

lgorith

m de

termi

nes t

he

oper

ating

mod

e, an

d con

trols

the ph

ysica

l outp

uts. M

ODE_

ENAB

LE is

the d

efault

sta

te aft

er po

wer r

estor

e or a

pplic

ation

resta

rt. If

the m

ode w

as M

ANUA

L and

nv

iMan

ualM

ode i

s set

to MO

DE_E

NABL

E, th

e nod

e the

n goe

s thr

ough

ap

plica

tion_

resta

rt.MO

DE_D

ISAB

LE se

ts the

node

to th

e DIS

ABLE

D_MO

DE. T

he

alarm

NOD

E_DI

SABL

ED is

initia

ted, a

ll con

trol lo

ops a

re di

sable

d, an

d the

phys

ical

outpu

ts ar

e tur

ned o

ff. Th

e phy

sical

inputs

, netw

ork v

ariab

le inp

uts, a

nd ne

twor

k va

riable

outpu

ts ar

e still

func

tionin

g whe

n the

node

is in

the D

ISAB

LED_

MODE

. MO

DE_M

ANUA

L sets

the n

ode i

nto th

e MAN

UAL m

ode.

If MAN

UAL i

s sele

cted,

the

contr

oller

enter

s Tes

t Mod

e (ma

nual

over

ride o

f outp

uts).

The a

larm

NODE

_DIS

ABLE

D is

initia

ted, a

ll con

trol lo

ops a

re di

sable

d, an

d the

phys

ical

outpu

ts ar

e con

trolle

d man

ually

as co

mman

ded b

y nviM

anVa

lue. T

he no

des

confi

gura

tion v

ariab

les an

d nviM

anVa

lue ar

e use

d to s

et va

lves,

damp

ers,

and /

or

digita

l outp

ut to

the de

sired

man

ual p

ositio

ns or

state

(s). T

he ph

ysica

l inpu

ts,

netw

ork v

ariab

le inp

uts, a

nd ne

twor

k var

iable

outpu

ts ar

e still

func

tionin

g whe

n the

no

de is

in th

e MAN

UAL m

ode.S

UPPR

ESS_

ALAR

MS ca

uses

nvoA

larm.

type t

o be

set to

ALA

RM_N

OTIF

Y_DI

SABL

ED, a

nd A

larmL

og to

no lo

nger

reco

rd al

arms

. If

alarm

s are

supp

ress

ed, U

NSUP

PRES

S_AL

ARMS

caus

es A

larm.

type a

nd

Alar

mLog

to be

retur

ned t

o rep

ortin

g alar

ms. S

ee A

larm

for m

ore d

etails

. All

unsp

ecifie

d valu

es ar

e the

same

as M

ODE_

ENAB

LE.

TestM

ode

nviM

anVa

lueOu

tDriv

eNO

RMAL

_OP

OUT_

1_ON

OUT_

2_ON

OUT_

3_ON

OUT_

4_ON

OUT_

5_ON

OUT_

6_ON

OUT_

7_ON

OUT_

8_ON

ALL_

OUT_

OFF

ALL_

OUT_

ONDI

SABL

E_OU

T

0 1 2 3 4 5 6 7 8 9 10 11

NORM

AL_O

POu

tDriv

e Man

Value

is us

ed fo

r Fac

tory T

estin

g only

.

TestH

CPos

nviM

anVa

luesb

ManH

eatC

oolP

osS0

perce

ntage

-127

to 12

70

XDu

ring M

ANUA

L mod

e, Ma

nHea

tCoo

lPos

sets

the m

odula

ting p

ositio

n of th

e he

ating

or co

oling

moto

r (if c

onfig

ured

) to t

he sp

ecifie

d pos

ition.

If Man

HeatC

oolP

os

is les

s tha

n 0 or

grea

ter th

an 10

0, the

moto

r is ov

erdr

iven f

or a

perio

d lon

ger t

han

the m

otor t

ime t

o ens

ure t

hat it

is at

the e

nd of

trav

el. T

he he

at mo

tor is

drive

n whe

n He

atCoo

lMod

e is 1

and t

he co

ol mo

tor is

drive

n whe

n Hea

tCoo

lMod

e is 0

. At th

e mo

ment

when

the n

ode t

rans

fers t

o MAN

UAL_

MODE

or H

eatC

oolM

ode i

s cha

nged

, Ma

nHea

tCoo

lPos

is se

t the c

urre

nt mo

tor po

sition

.Te

stEco

nPos

nviM

anVa

luesb

ManE

conP

osS0

Perce

ntage

-127

to 12

70

XDu

ring M

ANUA

L mod

e, Ma

nEco

nPos

sets

the m

odula

ting p

ositio

n of th

e ec

onom

izer m

otor (

if con

figur

ed) t

o the

spec

ified p

ositio

n. If M

anEc

onPo

s is l

ess

than 0

or gr

eater

than

100,

the m

otor is

over

drive

n for

a pe

riod l

onge

r tha

n the

moto

r tim

e to e

nsur

e tha

t it is

at th

e end

of tr

avel.

At th

e mom

ent w

hen t

he no

de tr

ansfe

rs to

MANU

AL_M

ODE,

Man

Econ

Pos i

s set

the cu

rrent

motor

posit

ion.

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

107 74-2958�2

TestH

tClS

tg1nv

iMan

Value

HeatC

oolS

tage1

OFF

ON0 1

OFF

X

Durin

g MAN

UAL m

ode,

HeatC

oolS

tage1

para

meter

s tur

n the

corre

spon

ding h

eat,

or co

ol sta

ge to

on (1

) or o

ff (0)

. Whe

n Hea

tCoo

lMod

e is 0

, then

cooli

ng lo

ads a

re

contr

olled

. Whe

n Hea

tCoo

lMod

e is 1

and t

he no

de is

contr

olling

conv

entio

nal

equip

ment,

then

heati

ng lo

ads a

re co

ntroll

ed. W

hen H

eatC

oolM

ode i

s 1 an

d the

no

de is

contr

olling

a he

at pu

mp, th

en co

oling

load

s are

contr

olled

.Te

stHtC

lStg2

nviM

anVa

lueHe

atCoo

lStag

e2OF

FON

0 1OF

FX

For H

eatC

oolS

tage2

, refe

r to H

eatC

oolS

tage1

.

TestH

tClS

tg3nv

iMan

Value

HeatC

oolS

tage3

OFF

ON0 1

OFF

XFo

r Hea

tCoo

lStag

e3, r

efer t

o Hea

tCoo

lStag

e1.

TestH

tClS

tg4nv

iMan

Value

HeatC

oolS

tage4

OFF

ON0 1

OFF

XFo

r Hea

tCoo

lStag

e4. r

efer t

o Hea

tCoo

lStag

e1.

TestA

uxHt

1nv

iMan

Value

AuxH

eatC

oolS

tage1

OFF

ON0 1

OFF

XAu

xHea

tCoo

lStag

e1�

Durin

g MAN

UAL m

ode w

hen t

he no

de is

confi

gure

d to

contr

ol a h

eat p

ump a

nd H

eatC

oolM

ode i

s 1, th

ese p

aram

eters

turn t

he

corre

spon

ding a

uxilia

ry he

at sta

ge on

(1) o

r off (

0).

TestA

uxHt

2nv

iMan

Value

AuxH

eatC

oolS

tage2

OFF

ON0 1

OFF

XAu

xHea

tCoo

lStag

e2�

Durin

g MAN

UAL m

ode w

hen t

he no

de is

confi

gure

d to

contr

ol a h

eat p

ump a

nd H

eatC

oolM

ode i

s 1, th

ese p

aram

eters

turn t

he

corre

spon

ding a

uxilia

ry he

at sta

ge on

(1) o

r off (

0).

TestA

uxHt

3nv

iMan

Value

AuxH

eatC

oolS

tage3

OFF

ON0 1

OFF

XAu

xHea

tCoo

lStag

e3�

Durin

g MAN

UAL m

ode w

hen t

he no

de is

confi

gure

d to

contr

ol a h

eat p

ump a

nd H

eatC

oolM

ode i

s 1, th

ese p

aram

eters

turn t

he

corre

spon

ding a

uxilia

ry he

at sta

ge on

(1) o

r off (

0).

TestA

uxHt

4nv

iMan

Value

AuxH

eatC

oolS

tage4

OFF

ON0 1

OFF

XAu

xHea

tCoo

lStag

e4�

Durin

g MAN

UAL m

ode w

hen t

he no

de is

confi

gure

d to

contr

ol a h

eat p

ump a

nd H

eatC

oolM

ode i

s 1, th

ese p

aram

eters

turn t

he

corre

spon

ding a

uxilia

ry he

at sta

ge on

(1) o

r off (

0).

TestH

tClM

ode

nviM

anVa

lueHe

atCoo

lMod

eOF

FON

0 1OF

FX

Durin

g MAN

UAL m

ode,

HeatC

oolM

ode d

eterm

ines w

hethe

r hea

ting o

r coo

ling

outpu

ts ar

e tur

ned o

n or o

ff man

ually

. Whe

n Hea

tCoo

lMod

e is 0

, then

cooli

ng lo

ads

are c

ontro

lled.

Whe

n Hea

tCoo

lMod

e is 1

and t

he no

de is

contr

olling

conv

entio

nal

equip

ment,

then

heati

ng lo

ads a

re co

ntroll

ed. W

hen H

eatC

oolM

ode i

s 1 an

d the

no

de is

contr

olling

a he

at pu

mp, th

en co

oling

load

s are

contr

olled

by H

eat /

Cool

stage

s and

heati

ng st

ages

are c

ontro

lled b

y aux

iliary

heat

stage

s. Th

e CH

ANGE

_OVE

R_RE

LAY_

OUT

is aff

ected

by H

eatC

oolM

ode a

s con

figur

ed in

Se

lect.

TestS

aFan

nviM

anVa

lueFa

nOut

OFF

ON0 1

OFF

XDu

ring M

ANUA

L mod

e, Fa

nOut

turns

the f

an on

(1) o

r off (

0).

TestA

uxEc

onnv

iMan

Value

AuxE

conO

utOF

FON

0 1OF

FX

Durin

g MAN

UAL m

ode,

AuxE

conO

ut tur

ns th

e AUX

_ECO

N_OU

T on

(1) o

r off(

0).

TestO

ccSt

atnv

iMan

Value

OccS

tatus

Out

OFF

ON0 1

OFF

XDu

ring M

ANUA

L mod

e, Oc

cStat

usOu

t turn

s the

OCC

UPAN

CY_S

TATU

S_OU

T to

on(1

= no

t OC_

UNOC

CUPI

ED) o

r off (

0).

TestF

ree1

nviM

anVa

lueFr

ee1O

utOF

FON

0 1OF

FX

Durin

g MAN

UAL m

ode,

Free

1Out

turns

the F

REE1

_OUT

on(1

) or o

ff(0)

.

TestF

ree2

nviM

anVa

lueFr

ee2O

utOF

FON

0 1OF

FX

Durin

g MAN

UAL m

ode,

Free

2Out

turns

the F

REE2

_OUT

on(1

) or o

ff(0)

.

Tabl

e 27

. Dire

ct A

cces

s A

nd S

peci

al P

oint

s. (C

ontin

ued)

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct Access

Test

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

ts

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 108

Tabl

e 28

. Dat

a Sh

are

Poin

ts.

User

Add

ress

NvNa

me

Field

Nam

eEn

gine

erin

g Un

its: E

nglis

h (M

etric

) or S

tate

s plu

s Ran

ge

Digital State or Value of State

Defa

ult

E-Vision (M, P, S)Share

Map Direct AccessManual Config.Failure Detect

E-Vi

sion

Lege

nd: (

M) M

onito

r, (P

) Par

amet

er, (

S) S

chem

atic

Com

men

tsDe

stOaE

nthnv

iOdE

nthS7

mA 4 to 2

0SI

_INVA

LIDX

XX

nviO

dEnth

allow

s one

outdo

or en

thalpy

sens

or at

a no

de to

be sh

ared

by m

any

other

node

s. W

hen n

viOdE

nth is

not S

I_INV

ALID

then

any l

ocal

sens

or is

ign

ored

by th

e loc

al co

ntrol

algor

ithm

and O

dEnth

is us

ed in

stead

. If th

e valu

e is

outsi

de th

e allo

wed r

ange

(4 to

20 m

A), th

en th

e nod

e use

s the

value

of th

e ne

ares

t ran

ge lim

it.Sr

cOaE

nthnv

oOdE

nthS7

mA 4 to 2

0SI

_INVA

LIDM

XX

nvoO

dEnth

allow

s the

loca

l outd

oor e

nthalp

y sen

sor t

o be s

hare

d with

othe

r no

des a

nd is

typic

ally b

ound

to O

dEnth

on ot

her n

odes

. If th

e loc

al se

nsor

is

confi

gure

d by S

elect,

nviO

dEnth

is pe

riodic

ally s

ent o

n the

netw

ork.

If the

loca

l se

nsor

is no

t con

figur

ed or

curre

ntly s

howi

ng an

erro

r, the

value

is S

I_INV

ALID

.Sr

cMon

SwCt

nvoM

onSw

value

0 to 1

000

XMo

nSw

value

allow

s the

mon

itor s

witch

to be

shar

ed w

ith an

other

node

. Mon

Sw

is typ

ically

boun

d to a

n SBC

to in

dicate

a us

er de

fined

alar

m co

nditio

n. Th

e ou

tput v

alues

have

the f

ollow

ing m

eanin

gs: If

the s

tate i

s SW

_OFF

and t

he

value

is 0,

then

the m

onito

r swi

tch is

open

. If th

e stat

e is S

W_O

N an

d the

value

is

100 p

erce

nt, th

en th

e mon

itor s

witch

is cl

osed

. If th

e stat

e is S

W_N

UL an

d the

value

is 0,

then

the m

onito

r swi

tch is

not c

onfig

ured

by S

elect.

SrcM

onSw

nvoM

onSw

state

SW_O

FFSW

_ON

SW_N

UL

0 1 255

SW_N

ULM

XFo

r Mon

Sw.st

ate, r

efer t

o Mon

Sw.va

lue.

nviIa

qOvr

value

0 to 1

000

IaqOv

r allo

ws an

indo

or ai

r qua

lity se

nsor

to be

shar

ed by

man

y othe

r nod

es.

The s

tates

are f

ollow

s: If t

he st

ate is

SW

_OFF

and t

he va

lue is

don�t

care

, then

the

indo

or ai

r qua

lity is

acce

ptable

. If th

e stat

e is S

W_O

N an

d the

value

is 0,

the

n the

indo

or ai

r qua

lity is

acce

ptable

. If th

e nod

e rec

eives

this

comb

inatio

n of

state

and v

alue,

then s

tate i

s set

to SW

_OFF

. If th

e stat

e is S

W_O

N an

d the

va

lue is

not z

ero,

then t

he in

door

air q

uality

is no

t acc

eptab

le an

d add

itiona

l ou

tdoor

air is

need

ed to

bring

it ba

ck to

acce

ptable

. If th

e stat

e is S

W_N

UL an

d the

value

is do

n�t ca

re, th

en th

e ind

oor a

ir qua

lity is

acce

ptable

. If th

e stat

e is

other,

then

the n

etwor

k var

iable

is no

t bou

nd, th

e com

munic

ation

s path

from

the

send

ing no

de ha

s fail

ed, o

r the

send

ing no

de ha

s fail

ed. T

he in

door

air q

uality

is

acce

ptable

.De

stIaq

Ovrd

nviIa

qOvr

state

SW_O

FFSW

_ON

SW_N

UL

0 1 255

SW_N

ULM

XX

XX

For I

aqOv

r.stat

e, re

fer to

IaqO

vr.va

lue.

SrcIa

qOvrC

tnv

oIaqO

vrva

lue0 t

o 100

0X

XIaq

Ovr a

llows

an in

door

air q

uality

sens

or to

be sh

ared

with

othe

r nod

es an

d is

typica

lly bo

und t

o Iaq

Ovr o

n othe

r nod

es. If

Data

2.siS

pace

Co2 i

s not

SI_IN

VALID

, and

exce

eds A

ux1S

etPt.C

O2Iaq

Limit,

then p

oor a

ir qua

lity is

de

tected

. In ad

dition

, if a

local

digita

l inpu

t is co

nfigu

red f

or IA

Q_OV

ERRI

DE_IN

an

d IO.

IaqOv

erRi

de is

1 (T

RUE)

then

poor

air q

uality

is al

so de

tected

. The

state

ha

s the

follo

wing

mea

nings

: If th

e stat

e is S

W_O

FF an

d the

value

is 0,

then

the

indoo

r air q

uality

is ac

cepta

ble. If

the s

tate i

s SW

_ON

and t

he va

lue is

100

perce

nt, th

en th

e ind

oor a

ir qua

lity is

not a

ccep

table

and a

dditio

nal o

utdoo

r air i

s ne

eded

to br

ing it

back

to an

acce

ptable

state

. If th

e stat

e is S

W_N

UL an

d the

va

lue is

0, th

en th

e eco

nomi

zer f

or th

is no

de ha

s not

been

confi

gure

d or t

here

is

no se

nsor

(via

IO.S

pace

Do2 o

r IO.

IaqOv

erRi

de) c

onfig

ured

or th

e only

co

nfigu

red s

enso

r (via

IO.S

pace

Co2)

has f

ailed

.Sr

cIaqO

vrnv

oIaqO

vrsta

teSW

_OFF

SW_O

NSW

_NUL

0 1 255

SW_N

ULM

XX

For I

aqOv

r.Stat

e, re

fer to

IaqO

vr.va

lue.

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

109 74-2958�2

Appendix D: XL5000 Q7750A Excel 10 Zone Manager Point Estimating GuideMemory size approximation shown below (all sizes in bytes):

When memory size is less than 110,000 bytes, the size is OK.

When memory size is between 110,000 and 128,000 bytes, the application may be too large. The user must expect to reduce the application complexity, reduce the number of attached Excel 10s or distribute the Excel 10s over more than one Zone Manager.

When memory size is greater than 128,000, the size is too large. The application size must be reduced as described above.

Approximate Memory Size Estimating Procedure.1. Determine the number of points per controller required

at the Central (for example, XBS).

NOTE: All remaining points that are not mapped can be accessed through the Direct Access feature.

2. Calculate the number of Excel 10 Zone Manager pro-gram points that are used in control logic and in the switching table.

3. Estimate the program complexity of the Zone Manager (one of three levels).a. No time programs, control logic, or switching tables.b. 10K of control logic (one time program, five

switching tables, and five control loops).c. 20K of control logic (multiple time programs, ten

switching tables, and ten control loops).Use Fig. 51 to determine the number of Excel 10s that can be connected to the Zone Manager.NOTE: More than 60 Excel 10s requires a Router.

4. Repeat for each Q7750A Excel 10 Zone Manager in a project.

Fig. 51. Point capacity estimate for Zone Manager.

The exact equation for calculating memory size follows:Memory size = 21,780+ 4096 (in case of a time program).+ CARE Control Program.+ 14 x time points x Excel 10 units.+ 50 x Excel 10 units.+ map complexity x Excel 10 units x mapped points.+ 57 x C-Bus points.+ 7488 x Excel 10 types.

Where:Time points = number of switch points in time program

per Excel 10.

Excel 10 units =number of attached Excel 10s.C-Bus points = including mapped points and others; for

example, remote points.Mapped points = number of mapped points per Excel 10,

including One-to-Many and Many-to-One mechanism.

Excel 10 types = number of different Excel 10 types (currently three)

Map complexity=20 =using One-to-Many and not using points

with read/write.30 = average.45 = many points with read/write ability.

20 60 120

600

700

800

900

600

700

800

900

920

765

610

585

740

895

NUMBER OFC-BUS POINTS(EXCEL 10MAPPED POINTSPLUS ZONEMANAGERPOINTS)

(OR LESS) (ADD ROUTER)

NUMBER OF EXCEL 10s

(C)

(A)

NUMBER OFC-BUS POINTS(EXCEL 10MAPPED POINTSPLUS ZONEMANAGERPOINTS)

NO TIME PROGRAM,NO CONTROL LOOPS, NO SWITCHING TABLES.

20K CONTROL PROGRAM(I.E., MULTIPLE TIME PROGRAMS,10 CONTROL LOOPS, 10 SWITCHING TABLES.)

10K CONTROL PROGRAM(FOR EXAMPLE, 1 TIME PROGRAM,5 CONTROL LOOPS, 5 SWITCHING TABLES.)

(B)

M8729

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 110

Appendix E: Sensor Data for Calibration

Resistance Sensors

Sensor Type: C7100A, C7170A. (PT3000)

Sensor Use: Discharge air, Outdoor air.

Table 29 lists the points for sensor resistance versus temperature. Fig. 52 shows the graph of these points.

Table 29. PT3000 Sensor Resistance Versus Temperature.

Fig. 52. PT3000 Sensor resistance versus temperature.

Sensor Type: C7041B,C,D,F,J,K (W7750B,C only).

Sensor Use: Return Air, Discharge Air Temperature (20K ohm).

Fig. 53 shows the graph of 20K ohm sensor resistance versus temperature.

Sensor Type: T7770A,B,C,D; T7560A,B and C7770A. (20K ohm)

Sensor Use:Space Temperature and Discharge/Return Air Temperature.

Fig. 53 shows the graph of sensor resistance versus temperature.

Fig. 53. 20K ohm sensor resistance versus temperature.

Sensor Type:T7770B,C 10K ohm linear setpoint potentiometer (Relative).

Sensor Use: Setpoint Offset Temperature.

Sensor Resistance versus Temperature Difference (above and below the setpoint):Offset -9°F: 9574 ohms.Setpoint: 5500 ohms.Offset +9°F: 1426 ohms.

Sensor Type:T7770B,C 10K ohm setpoint potentiometer (Absolute).

Sensor Use: Direct Setpoint Temperature.

Sensor Resistance versus Temperature:55°F (13°C): 9574 ohms.70°F (21°C): 5500 ohms.85°F (29°C): 1426 ohms.

°F Resistance Ohms-40 2916.08-30 2964.68-20 3013.28-10 3061.880 3110.48

10 3159.0820 3207.6830 3256.2840 3304.8850 3353.4860 3402.0870 3450.6880 3499.2890 3547.88100 3596.48110 3645.08120 3693.68

30503000

29502900

3100

3150

3200325033003350

340034503500

3550

3600

365037003750

50403020100-10-20-30-40 60 70 80 90 100 110 120

OH

MS

DEGREES F

SENSOR RESISTANCE VERSUS TEMPERATURE

M11615

TEMPERATURE (DEGREES)

oF30 40 50 60 70 80 90 100 110

0 10 20 30 40

RE

SIS

TA

NC

E (

OH

MS

)

20K OHM AT 77oF (25oC)

80K

70K

60K

50K

40K

30K

20K

10K

oC

M5874A

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

111 74-2958�2

Voltage/Current Sensors

Sensor Type: C7600B 2 to 10V.

Sensor Use: Humidity.

Table 30 lists the points for sensor voltage versus humidity. Fig. 54 shows the graph of these points.

Table 30. C7600B Sensor Voltage Versus Humidity.

Fig. 54. C7600B Sensor voltage versus humidity.

Sensor Type: C7600C (4 to 20 mA).

Sensor Use: Humidity.

Table 31 lists the points for sensor voltage versus humidity. Fig. 55 shows the graph of these points.

Table 31. C7600C Sensor Current Versus Humidity.

Fig. 55. C7600C output current versus humidity.

Humidity Percentage Sensor Voltage10 2.6715 3.0820 3.4825 3.8830 4.2835 4.6840 5.0845 5.4850 5.8855 6.2860 6.6965 7.0970 7.4975 7.8980 8.2985 8.6990 9.09

2.50

3.00

3.50

4.00

4.50

5.00

5.50

6.00

6.50

7.00

7.50

8.00

8.50

9.00

9.50

10.00

10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90

VO

LT

S

PERCENTAGE

SENSOR VOLTAGE VERSUS HUMIDITY PERCENTAGE

M11610

Relative Humidity Percentage Sensor Current10 5.620 7.230 8.840 10.450 12.060 13.670 15.280 16.890 18.4

HUMIDITY IN % RH

CU

RR

ENT

IN m

A

4

18

8

16

6

14

12

20

10

10M3131B

5.67.28.8

10.412.013.615.216.8 18.4

102030405060708090

20 10090807060504030

RH (%) I (mA)

0

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 112

Sensor Type: C7400A.

Sensor Use: Enthalpy.

Table 32 lists the points for sensor current versus enthalpy (volts). Fig. 56 shows the graph of these points.

Table 32. C7400A Sensor Current Versus Enthalpy (volts).

Fig. 56. C7400A Sensor current versus enthalpy (volts).

See Fig. 57 for partial psychrometric chart for a C7400A Solid State Enthalpy Sensor.

See Fig. 58 for a C7400A Solid State Enthalpy Sensor output current vs. relative humidity.

Sensor Current (mA) Enthalpy (Volts)4 15 1.256 1.497 1.748 1.999 2.2410 2.4911 2.7412 2.9913 3.2414 3.4915 3.7416 3.9817 4.2318 4.4819 4.7320 4.98

1.00

1.25

1.50

1.75

2.00

2.25

2.50

2.75

3.00

3.25

3.50

3.75

4.00

4.25

4.50

4.75

5.00

4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

EN

TH

AL

PY

(V

OL

TS

)

(MA)

SENSOR CURRENT VERSUS ENTHALPY (VOLTS)

M11607

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

113 74-2958�2

Fig. 57. Partial psychrometric chart for a C7400A Solid State Enthalpy Sensor.

Fig. 58. C7400A Solid State Enthalpy Sensor output current versus relative humidity.

CONTROLCURVE

A

B

C

D

CONTROL POINTAPPROX. F ( C)

AT 50% RH

73 (23)

70 (21)

67 (19)

63 (17)12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

42

44

46

90100

80

70

60

50

40

30

20

10

EN

TH

ALPY—

BTU

PER

PO

UN

D D

RY A

IR

85(29)

90(32)

95(35)

100(38)

105(41)

110(43)

35(2)

35(2)

40(4)

40(4)

105(41)

110(43)

45(7)

45(7)

50(10)

50(10)

55(13)

55(13)

60(16)

60(16)

65(18)

65(18)

70(21)

70(21)

75(24)

75(24)

80(27)

80(27)

85(29)

90(32)

95(35)

100(38)

APPROXIMATE DRY BULB TEMPERATURE— F ( C)

A

A

B

B

C

C

D

D

M11806

RE

LA

TIV

E H

UM

IDIT

Y (%

)

20

10

30

40

50

60

70

80

90

100

605040 70 80 90 100

PE

RC

EN

T R

H

TEMPERATURE F ( C) M11605

C7400A OUTPUT CURRENT

4 m

A

6 m

A

8 m

A

10 m

A

20 m

A18 m

A16 m

A14 m

A12 m

A

(4) (10) (16) (21) (27) (32) (38)

D C B A

D = 17 MAC = 15.5 MAB = 13.5 MAA = 11 MA

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

74-2958�2 114

Sensor Type: C7232 or C7632.

Sensor Use: CO2 concentration.

Table 33 lists the points for sensor voltage versus CO2 concentration. Fig. 59 shows the graph of these points.

Table 33. C7232, C7632 Voltage Versus CO2 Concentration.

Fig. 59. C7232, C7632 voltage versus CO2 concentration.

Sensor Type: P7640A,B (4-20 mA with 500 ohm resistor to convert to 2-10 Vdc).

Sensor Use: Sensor voltage (Vdc) /pressure (in. w.c.) 2 to 10 Vdc, 0 to 5 in. w.c. (1.25 kPa).

Table 34 lists the points for sensor voltage (Vdc) versus pressure (in. w.c.). Fig. 60 shows the graph of these points.

Table 34. P7640 Voltage (Vdc) Versus Pressure (in. w.c.).

Fig. 60. P7640 voltage (Vdc) versus pressure (in. w.c.).

Sensor Type: Third party (2 to 10V).

Sensor Use: Monitor voltage.

CO2 Concentration PPM Sensor Voltage0 0.00

100 0.50200 1.00300 1.50400 2.00500 2.50600 3.00700 3.50800 4.00900 4.501000 5.001100 5.501200 6.001300 6.501400 7.001500 7.501600 8.001700 8.501800 9.001900 9.502000 10.00

0

1

2

3

4

5

6

7

8

9

10

100 300 500 700 900 1100 1300 1500 1700 1900200 400 600 800 1000 1200 1400 1600 1800 2000

VO

LT

S

PPM

SENSOR VOLTAGE VERSUS CO2 CONCENTRATION

M11611

Pressure in. w.c. (kPa) Sensor Voltage (Vdc)0.00 (0.00) 2.000.50.(0.13) 2.801.00 (0.25) 3.601.50 (0.37) 4.402.00 (0.5) 5.20

2.50 (0.62) 6.003.00 (0.75) 6.803.50 (0.87) 7.604.00 (1.00) 8.404.50 (1.12) 9.205.00 (1.25) 10.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

9.00

10.00

0 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00

VO

LT

S (

VD

C)

INW

SENSOR VOLTAGE VERSUS PRESSURE

M11606

115 74-2958�2

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Automation and Control SolutionsHoneywell International Inc. Honeywell Limited-Honeywell Limitée1985 Douglas Drive North 35 Dynamic DriveGolden Valley, MN 55422 Scarborough, Ontario M1V 4Z9customer.honeywell.com

® U.S. Registered Trademark© 2005 Honeywell International Inc.74-2958�2 B.B. Rev. 03-05

LON®, Neuron®, and LONWORKS® are registered trademarks of Echelon® Corporation.

LONMARK®and LONMARK® logo are registered trademarks of the LONMARK Interoperability Association.

LonSpec� and LONSTATION� are trademarks of Echelon® Corporation.

By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.