ECLYPSE™ Connected System Controller Overview The ECLYPSE Connected System Controller is a modular and scalable platform that is used to control a wide range of HVAC applications. It supports multi-protocol communications includ- ing BACnet/IP and is a listed BACnet Building Controller (B-BC). The ECLYPSE Connected System Controller consists of a control, automation and connectiv- ity server, power supply, and I/O extension mod- ules. This programmable Connected System Con- troller provides advanced functionality such as customizable control logic, Web-based design and visualization interface (ENVYSION embed- ded), logging, alarming, and scheduling. Applications The ECLYPSE Connected System Controller is typically used as: £ A controller for medium/large sized Air Han- dling Units (AHU), central plant, lighting, power monitoring, and other applications. £ Small building server and equipment con- troller with embedded ENVYSION. For ex- ample, it can be used to control and serve a boiler room. Features & Benefits IP Communication £ Communicate over IP for increased speed. Experience faster response and save time when programming, configuring, creating and viewing graphics, and upgrading your system. £ Control technicians can connect the ECLYPSE Wi-Fi Adapter to the Connected System Controller thereby creating a Wi-Fi Hotspot network. The control technician can then connect wirelessly to the system using a mobile device or laptop, for faster, easier system configuration, programming, com- missioning and servicing. £ The controller can be part of a Wi-Fi mesh network that increases wireless network reli- ability and robustness that allows for a larger coverage area. Wi-Fi mesh is ideal for areas where there is no line of sight or where radio signals are intermittently blocked. £ Hostname management allows the controller to be addressed by a nickname to facilitate network management. Datasheet

Upload: vuongque

Post on 09-Mar-2018

249 views

Category:

Documents


8 download

TRANSCRIPT

Page 1: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

ECLYPSE™ Connected SystemController

OverviewThe ECLYPSE Connected System Controller isa modular and scalable platform that is used tocontrol a wide range of HVAC applications. Itsupports multi-protocol communications includ-ing BACnet/IP and is a listed BACnet BuildingController (B-BC).The ECLYPSE Connected System Controllerconsists of a control, automation and connectiv-ity server, power supply, and I/O extension mod-ules.This programmable Connected System Con-troller provides advanced functionality such ascustomizable control logic, Web-based designand visualization interface (ENVYSION embed-ded), logging, alarming, and scheduling.

ApplicationsThe ECLYPSE Connected System Controller istypically used as:£ A controller for medium/large sized Air Han-

dling Units (AHU), central plant, lighting,power monitoring, and other applications.

£ Small building server and equipment con-troller with embedded ENVYSION. For ex-ample, it can be used to control and serve aboiler room.

Features & BenefitsIP Communication£ Communicate over IP for increased speed.

Experience faster response and save timewhen programming, configuring, creatingand viewing graphics, and upgrading yoursystem.

£ Control technicians can connect theECLYPSE Wi-Fi Adapter to the ConnectedSystem Controller thereby creating a Wi-FiHotspot network. The control technician canthen connect wirelessly to the system usinga mobile device or laptop, for faster, easiersystem configuration, programming, com-missioning and servicing.

£ The controller can be part of a Wi-Fi meshnetwork that increases wireless network reli-ability and robustness that allows for a largercoverage area. Wi-Fi mesh is ideal for areaswhere there is no line of sight or where radiosignals are intermittently blocked.

£ Hostname management allows the controllerto be addressed by a nickname to facilitatenetwork management.

D a t a s h e e t

Page 2: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

2 / 20 ECLYPSE™ Connected System Controller

FIPS 140-2 Inside (Pending)FIPS 140-2 Level 1 provides an enhanced levelof security to protect data the controller is col-lecting and sharing making it suitable for use inthe most sensitive environments.

ENVYSION£ Embedded web-based graphic design and

visualization interface. Host system-basedgraphics such as Air Handling Units, BoilerRoom, or Central Plant directly from the con-troller.

£ Design and create user interfaces directlyfrom a standard web browser. Responsiveinterface design support allows a singlegraphic design to be automatically adaptedto suit the display’s screen size.

£ Provides visualization for schedules, alarms,and trend logs.

ProgrammabilitySupports Distech Controls’ EC-gfxProgram,which makes Building Automation System(BAS) programming effortless by allowing you tovisually assemble building blocks together tocreate a custom control sequence for anyHVAC / building automation application.

Batch EC-gfxProgram Projects andFirmware DownloadEC-gfxProgram projects can be downloaded inbatch to multiple controllers, for greater timesavings. Batch firmware update can also be per-formed on multiple controllers.

ENVYSION TechStudio£ ENVYSION TechStudio is packaged for a

PC-based installation dedicated to techni-cians and engineers to build ENVYSIONgraphics offline for ECLYPSE connectedcontrollers and for EC-NetAX systems.

£ All designs can be created without beingconnected to any devices. You can importand export ENVYSION projects from a con-troller or PC to any other controller seam-lessly.

£ Launch EC-gfxProgram directly from ENVY-SION TechStudio to modify and validate anENVYSION project for ECLYPSE con-trollers.

XpressNetwork UtilityThe XpressNetwork Utility saves you time andcost by giving you increased control over multi-ple ECLYPSE controllers through device discov-ery and batch operations such as configuringand updating multiple ECLYPSE controllers onthe network. It also allows you to directly accessthe controller’s Web interface or launch EC-gfx-Program to program the controllers.

Scalable and ModularThe Connected System Controller is sized tocost-effectively meet the requirements of anyHVAC application from small to medium to largesystems. The most capable Connected SystemController model can be expanded to support upto 20 input/output (I/O) modules (up to 320 I/Os)while being able to adapt to new requirementsas the need arises.A range of I/O modules are available that haveuniversal inputs and outputs, digital inputs withfast pulse support for use with energy metersand counters, 24VAC triac outputs for use withsmaller load applications (up to 1 amp) such aselectric fans and motors/actuators and relay out-puts for larger load/high power applications suchas electric heat and high power actuators.

Page 3: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

ECLYPSE™ Connected System Controller 3 / 20

The Connected System Controller’s recurrentpower supply concept can be used when morepower is required to power a series of I/O mod-ules. A 100 to 240VAC power supply moduleeliminates the need for a line voltage to 24VACpower transformer to save installation costs andtime. A 24 VAC / VDC power supply module isequally available.A connecting cable is used to connect succes-sive rows of modules within a controls’ cabinetto provide power and communication.

BACnet/IP DeviceThe Connected System Controller is BTL-listedas a BACnet Building Controller (B-BC) and iscertified WSP B-BC (Europe) and AMEV AS-A(German-speaking countries). It supports BAC-net/IP for faster communication in comparison tothe traditional twisted pair communication bus.

Multi-Protocol SupportThe Connected System Controller supports arange of communication protocols such as BAC-net MS/TP, Modbus RTU, and Modbus TCP.BACnet MS/TP and Modbus RTU communica-tions are made by connecting directly to sepa-rate RS-485 ports. The Connected System Con-troller integrates up to three RS-485 ports whenequipped with one ECY-RS485 extension mod-ule allowing the controller to support more thanone trunk or communication protocol at a time.

MS/TP to IP routingIntegrate full MS/TP trunks into a supervisorysystem like the EC-NetAX Supervisor, without theneed for other hardware components such asan external BACnet MS/TP to IP router.

Modbus RTU and TCPModbus RTU and TCP communication can beused to integrate a wide variety of Modbus de-vices such as power and water meters, VariableFrequency Drives, air flow sensors, and more,without the need for additional hardware suchas a gateway.

Smart Room Control SupportThe Smart Room Control solution is an end-to-end system for the control of HVAC equipment,lighting, and shades/sunblinds, achieving thehighest levels of comfort for occupants whilecutting costs from installation time and wiring/material requirements to energy consumption.This solution combines:£ Lighting and shade/sunblind expansion

modules to control lights (DALI, on/off ordimming) and shades/sunblinds (up/downand angle rotation).

£ Multi-sensor combining motion and luminos-ity (Lux) sensors and equipped with an In-frared receiver that works with a convenientremote control.

£ Wireless (infrared) personal remote controlfor increased occupant comfort.

£ Allure™ Series Communicating Sensors forincreased occupant comfort settings.

Allure™ Series Communicating Sensor SupportThese controllers work with a wide range of sen-sors, such as the Allure Series CommunicatingSensors that are designed to provide intelligentsensing and control devices for increased userexperience and energy efficiency.£ Allure EC-Smart-Vue sensors feature a

backlit-display and graphical menus thatprovide precise environmental zone control,with any combination of the following: tem-perature, humidity, CO2, and motion sensor.

£ Allure EC-Smart-Comfort sensors featurecolored LED indicators to provide user feed-back, rotary knobs to adjust the setpoint off-set and fan speed, and an occupancy over-ride push button. This sensor can also beexpanded with a combination of up to 4 add-on push button modules for lighting andshade/ sunblind control.

£ Allure EC-Smart-Air sensors combine pre-cise environmental sensing in a discreet andalluring enclosure for temperature, humidity,and CO2.

MobilityThe controller can be remotely accessed to pro-gram, configure, or maintain the installation thusreducing costs associated with on-site visits.Through a mobile device or PC, a range of taskscan be performed using the following free-to-usetools and interfaces:£ ENVYSION web-based graphic design and

visualization interface£ EC-gfxProgram graphical programming in-

terface£ myDC Control mobile application

Page 4: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

4 / 20 ECLYPSE™ Connected System Controller

Hand/Off/Auto Switches andPotentiometersThe front assembly of Hand/Off/Auto (HOA)equipped I/O models allow users to override thecontrol outputs for commissioning and mainte-nance purposes.Universal outputs have potentiometers providingmanual analog signal and output control to over-ride voltage or current signal.

High-Efficiency DesignThe power supply uses the latest high-efficiencyswitch-mode circuitry to make more power avail-able to operate additional modules and forcooler operation.

Hot-Swappable Tool-Less Design andUnique Latching MechanismThe I/O modules are hot-swappable for replace-ment without interrupting power and communi-cations to other modules.The front assembly of I/O modules separatefrom the wiring base by pushing the two latchesup to unlock a module’s front assembly and thenopening and pulling the hinged gull-wing covers.The latch design locks the front assembly to thewiring base.The hinged gull-wing design protects and coverthe stacked dual row I/O terminal strips.

Ease of InstallationThe Connected System Controller modules areplug & play devices. They are equipped withHD-15 connectors that transmits power andcommunications to the next module for fast andeasy assembly.

I/O Status LEDsThe status LEDs on the I/O modules allows theuser to confirm the status of the inputs/outputsand facilitate commissioning and troubleshoot-ing.

Auto-AddressingThe auto-addressing feature eliminates theneed to manually assign an address to each I/Omodule therefore reducing installation and con-figuration time.

Digital Inputs Up to 120HzThe ECY-16DI module supports pulsed signalsup to 120Hz for equipment status monitoringand alarm point monitoring, commonly used inenergy metering applications.

Color-Coded, Rising Cage TerminalsTerminal blocks are uniquely identified andcolor-coded for clarity and to prevent wiring mis-takes. The rising cage clamp terminal block con-nectors offer a more robust and secure wireconnection, designed to withstand activity andvibrations.

Robust ProtectionThe I/O modules are protected against mis-wiring and faults to prevent damage caused byincorrect wiring or other mishaps.The power supply module contains over-voltageand over-current output protection to protect theelectronics in unstable power supply conditionsand against mis-wiring.

Alarms, Trend Log, Schedule SupportEmbedded alarms, trend log and schedule sup-port allows for fully distributed data and logicproviding a more robust system. Embeddedtrend logs simplify system troubleshooting whencompared to a centralized system.

Email Notifications ServiceTechnicians & facility managers can receive au-tomatic email notifications for system status andalarms to ensure faster system servicing and re-sponse time. Email notification text can be cus-tomized to provide pertinent information aboutthe issue at hand.

Page 5: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

ECLYPSE™ Connected System Controller 5 / 20

Model SelectionThe ECLYPSE Connected System Controller consists of a power supply, a control, automation andconnectivity server, I/O extension modules, and communication modules to create a controller tai-lored to its application. The different models for each are shown in the tables below.

Power SupplyA power supply module must be added after each HD15 cable (see Accessories below).

ECY-PS24 24VAC/VDC power supply module for the ECLYPSE Connected SystemController.

ECY-PS100-240 100 to 240VAC power supply module for the ECLYPSE ConnectedSystem Controller.

Control, Automation and Connectivity ServersConnected System Controller for medium/large sized AHU and plant applications and small buildingserver/controller applications.

Model WithEmbeddedENVYSION

Application MaximumNumber ofPointsSupported

BACnet MS/TPto IP RoutingSupport –MaximumNumber ofBACnet MS/TPDevices

MaximumNumber ofModbusDevices (RTUor TCP)

ECY-S1000-16 Medium sizeequipment such asa rooftop unit, anAHU, small sizeplant room

16 No1 3ECY-S1000E-16ECY-S1000-48 48 No1 10ECY-S1000E-48ECY-S1000-48-MS 48 Yes2 10ECY-S1000E-48-MSECY-S1000 Large size

equipment such aslarge plant roomsand large datacenters.

3204 Yes2 963

ECY-S1000E

1. Upgrade and enable the functionality of your ECLYPSE controller’s RS-485 ports with our capacity-based upgrade to ECYS1000-48MS.2. Up to 50 BACnet MS/TP devices recommended on each RS-485 port.3. Up to 32 Modbus RTU devices recommended on each RS-485 port.4. The ECY-S1000 models support a maximum of 320 points OR up to a maximum of 20 IO modules Maximum number of Modbus RTU devices supported based on

best practices.

Page 6: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

6 / 20 ECLYPSE™ Connected System Controller

I/O Modules SelectionInputs Outputs

Basi

c Po

wer

Con

sum

ptio

n2 , W

Qua

ntity

Digital Analog

18VD

C P

ower

Sup

ply

Qua

ntity

Digital Analog

HO

A

Con

tact

Cou

nter

120H

z Pu

lse

Cou

ntin

g0

to 1

0VD

C0

to 5

VDC

0 to

20m

AR

esis

tanc

eTh

erm

isto

r

0-27

7VAC

/ 0-

30VD

CFo

rm-C

, 10A

24VA

C T

riac,

0.5

A0

or 1

2VD

CPW

MFl

oatin

g0

to 1

0VD

C1

0 to

20m

A1

ECY-16DI 16 0.94ECY-8DOR 8 0.94ECY-8DOR-HOA 8 0.94ECY-8UI6UO 8 6 UO1

UO2UO3

0.94

ECY-8UI6UO-HOA 8 6 UO1UO2UO3

0.94

ECY-8UI6DOT 8 6 0.94ECY-8UI6DOT-HOA 8 6 0.941. 0 to 10VDC is available on UO1 to UO6. 0 to 20 mA is available on UO1, UO2, and UO3; this option is individually selected through an on-board DIP switch

setting.2. External loads excluded. See the ECLYPSE Selection Tool to calculate the number of Input/Output Extension Modules that can operate with a power supply.

Communication Modules SelectionCommunications Module DescriptionECY-RS485 ECLYPSE Communication module with two RS-485 ports for Modbus

RTU or BACnet MS/TP.

AccessoriesECLYPSE HD15 Cable 6ft (1.8m) cable for Connected System Controller multiple-row panel

installations. An HD15 cable must always be followed by a power supplymodule. For more information, refer to the Hardware Installation Guide.

ECLYPSE Wi-Fi Adapter Wi-Fi Adapter for ECLYPSE Connected Controllers.

Page 7: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

ECLYPSE™ Connected System Controller 7 / 20

Product SpecificationsPower Supply (ECY-PS24)Power Supply InputVoltage Range 24VAC/DC; ±15%; Class 2Power Consumption 60VAFrequency Range 50 to 60HzOvercurrent Protection Field replaceable fuseFuse Type 4A, fast-acting, 5 × 20mm (GMA-4A)

Power Supply OutputDC Voltage 18VDC regulatedRated Current Range 0 to 1.6ARated Power 30W1

1. The total power consumption of all modules connected to the right of this power supply, and up to the next connected power supply, including any connectedloads, must be less than this value. A separate transformer rated at 60VA minimum and 100VA maximum must be used for each ECY-PS24 power supply for it tooperate at full capacity.

HardwarePower Distribution Direction Powered modules are connected to the rightBackplane Bus Pass-through connection for data and control signalsStatus Indicator Green LED: power statusMechanicalDimensions (H × W × D) 4.74 × 2.85 × 2.31" (120.31 × 72.38 × 58.56mm)

4.74" 120.31 3.18" 80.82

18.390.72

21.130.83

2.31" 58.5672.38

Inches Millimeters

0.01" 0.40Inter-Connection Gap:

2.61" 66.190.06" 1.44

0.17" 4.24 2.85"

5.20" 132.00

Front BackProfile

Shipping weight 0.75lbs (0.34kg)Mounting DIN rail or screw mountingEnclosure Material1 FR/ABSEnclosure Rating Plastic housing, UL94-V0 flammability ratingPlenum rating per UL19951. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)

directive

Page 8: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

8 / 20 ECLYPSE™ Connected System Controller

EnvironmentalOperating Temperature 32 to 122°F (0 to 50°C)Storage Temperature -22 to 158°F (-30 to 70°C)Relative Humidity 0 to 90% non-condensingIngress Protection Rating IP20Nema Rating 1

Standards and RegulationsCE:£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential,

commercial and light-industrial environments£ Immunity EN61000-6-1: 2007; Generic standards for residential,

commercial and light-industrial environmentsFCC This device complies with FCC rules part 15, subpart B, class BUL Listed (CDN & US) UL916 Energy management equipment

             

Power Supply (ECY-PS100-240)Power Supply InputVoltage Range 100 to 240 VAC Universal; +10%/-15%Input Current 400mA typicalStandby Power consumption <0.5WFrequency Range 50 to 60HzOvercurrent Protection Field replaceable fuseFuse Type 2.5A, Fast-acting, high-breaking, 250VAC, 5 × 20mm (TF2.5AH250V, IEC60127-2)

Power Supply OutputDC Voltage 18VDC regulatedRated Current Range 0 to 2ARated Power 40W1

1. The total power consumption of all modules connected to the right of this power supply, and up to the next connected power supply, including any connectedloads, must be less than this value.

HardwarePower Distribution Direction Powered modules are connected to the rightBackplane Bus Pass-through connection for data and control signalsStatus Indicator Green LED: power status

Page 9: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

ECLYPSE™ Connected System Controller 9 / 20

MechanicalDimensions (H × W × D) 4.74 × 4.08 × 2.31" (120.31 × 103.65 × 58.56mm)

3.18" 80.82

18.390.72

21.130.83

2.31" 58.56

0.06" 1.44BackProfile

103.654.08"

5.24 133.03

4.74" 120.31

0.44" 11.13

3.83" 97.33Front

0.01" 0.40Inter-Connection Gap:

Inches Millimeters

Shipping weight 0.71lbs (0.32kg)Mounting DIN rail or screw mounting

Refer to Hardware Installation Guide for more informationEnclosure Material1 FR/ABSEnclosure Rating Plastic housing, UL94-5VB flammability rating1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)

directive

EnvironmentalOperating Temperature 32 to 122°F (0 to 50°C)Storage Temperature -22 to 158°F (-30 to 70°C)Relative Humidity 0 to 90% non-condensingAltitude <6562ft (2000m)Pollution Degree 2Ingress Protection Rating IP20(must be mounted in a protective enclosure to conform with electrical installation standards)Overvoltage Category II - 2.5 kVElectrical Protection DC output is Separated Extra-Low Voltage (SELV);

SELV is implemented through reinforced insulation

Page 10: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

10 / 20 ECLYPSE™ Connected System Controller

Standards and RegulationsCE:£ Electrical Safety EN 60730-1 : 2011 - Automatic electrical controls for household

and similar use - Part 1: General requirements£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential,

commercial and light-industrial environments£ Immunity EN61000-6-1: 2007; Generic standards for residential,

commercial and light-industrial environmentsUL Listed (CDN & US) UL 61010-1 Safety Requirements For Electrical Equipment

For Measurement, Control, And Laboratory Use - Part 1: General Requirements - Edition 2 - Revision Date 2008/10/28

FCC This device complies with FCC rules part 15, subpart B, class B

             

Control, Automation and Connectivity Server (ECY-S1000)Power Supply InputVoltage 18VDCPower Consumption 8.9W; external loads excluded

CommunicationsEthernet Connection Speed 10/100 Mbps£ Addressing IPv4 or HostnameBACnet Profile BACnet Building Controller (B-BC) ), AMEV Certified (AS-A profile)BACnet Listing BTL, WSP B-BCBACnet Interconnectivity BBMD forwarding capabilities

BACnet/IP to BACnet MS/TP routingBACnet Transport Layer IP & MS/TP (optional)Web Server Protocol HTML5Web Server Application Interface REST APISupported BACnet MS/TP and Modbus RTU and TCP Connectivity:£ BACnet MS/TP or Modbus RTU 1 × RS-485 serial communications ports

Each RS-485 port supports one communication protocol at a time£ RS-485 Wiring 1-pair + Common/shield£ RS-485 EOL Resistor Built-in£ RS-485 Baud Rates 9600, 19 200, 38 400, or 76 800 bps£ RS-485 Addressing Controller’s Web Configuration Interface£ Modbus TCP Devices must be on the same subnetSupported Wireless Connectivity:£ Wireless Adapter Optional, USB Port Connection£ Wi-Fi Communication Protocol IEEE 802.11b/g/n and 802.11s£ Wi-Fi Network Types Client, Access Point, Hotspot, Mesh£ Wi-Fi Mesh Max. 30 devices on a single channel

Page 11: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

ECLYPSE™ Connected System Controller 11 / 20

Supported Smart Room Control Components1:Maximum number of supported devices per controller combined 12£ Allure EC-Smart-Vue Series Up to 121

£ Allure EC-Smart-Comfort Series Up to 6£ Allure EC-Smart-Air Series Up to 61

£ EC-Multi Sensor Up to 4£ ECx-Light-4 / ECx-Light-4D / ECx-Light-DALI Up to 2£ ECx-Blind-4 / ECx-Blind-4LV Up to 2£ EC-Multi Sensor Up to 42

£ ECx-Light-4 / ECx-Light-4D / ECx-Light-DALI Up to 22

£ ECx-Blind-4 / ECx-Blind-4LV Up to 22

1. For more details about supported quantities, see the ECLYPSE Selection Tool.xlsm spreadsheet file available for download from SmartSource.2. A controller can support a maximum of 2 Allure sensor models equipped with a CO2 sensor. Any remaining connected sensors must be without a CO2 sensor.

HardwareProcessor Sitara ARM processorCPU Speed 1GHzMemory 4GB Non-volatile Flash (applications & storage)

512MB RAMReal Time Clock (RTC) Real Time Clock with rechargeable battery

Supports SNTP network time synchronizationRTC Battery 20 hours charge time, 20 days discharge time

Up to 500 charge / discharge cyclesCommunications Ports:£ Ethernet 2 switched RJ-45 Ethernet ports

Supported Protocols BACnet/IP, Modbus TCP, NTP, and REST£ USB Connections 2 × USB 2.0 Ports

1 × Micro-USB 2.0 Ports£ RS-485 Serial Communications Screw terminals

Supported Protocols BACnet MS/TP or Modbus RTU£ Subnet RJ-45Status Indicators Green LED: Power status, Subnet TX, and Ethernet Traffic

Orange LED: Controller status, Subnet RX, and Ethernet Speed

Page 12: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

12 / 20 ECLYPSE™ Connected System Controller

MechanicalDimensions (H × W × D) 4.74 × 3.57 × 2.31" (120.31 × 90.67 × 58.56mm)

3.18" 80.82

18.540.73

21.080.83

3.33" 84.47

0.4" 1.092.31" 58.563.57" 90.67

Inches Millimeters

Inter-Connection Gap: 0.01" 0.40

5.13" 130.29

0.06" 1.44

4.74" 120.31

0.39" 9.98 Front BackProfile

Shipping weight 0.85lbs (0.39kg)Mounting DIN rail or screw mountingEnclosure Material FR/ABSEnclosure Rating1 Plastic housing, UL94-V0 flammability rating

Plenum rating per UL19951. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)

directive

EnvironmentalOperating Temperature 32 to 122°F (0 to 50°C)Storage Temperature -22 to 158°F (-30 to 70°C)Relative Humidity 0 to 90% non-condensingIngress Protection Rating IP20Nema Rating 1

Standards and RegulationsCE:£ Emission EN61000-6-3: 2007+A1:2011; Generic standards for residential,

commercial and light-industrial environments£ Immunity EN61000-6-1: 2007; Generic standards for residential,

commercial and light-industrial environmentsFCC This device complies with FCC rules part 15, subpart B, class BUL Listed (CDN & US) UL916 Energy management equipment

                 

Page 13: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

ECLYPSE™ Connected System Controller 13 / 20

I/O ModulesPower Supply InputVoltage 18VDCPower Consumption Calculate power supply requirements with the ECLYPSE Selection Tool

HardwareStatus Indicator Green LEDs: inputs and outputs

For ECY-16DI, ECY-8UI6UO, ECY-8UI6UO-HOA, ECY-8UI6DOT, &ECY-8UI6DOT-HOA Models:

MechanicalDimensions (H × W × D) 4.74 × 3.20 × 2.31" (120.31 × 81.17 × 58.56mm)

2.95" 74.99

4.74" 120.31

3.20" 81.17 2.31" 58.56

3.18" 80.82

18.540.73

21.080.83

Inches Millimeters

Inter-Connection Gap: 0.01" 0.40

Front BackProfile0.06" 1.44

4.80" 121.75

Shipping weight 0.85lbs (0.39kg)Mounting DIN rail or screw mountingHot-swappable YesEnclosure Material FR/ABSEnclosure Rating1 Plastic housing, UL94-V0 flammability rating; Plenum rating per UL19951. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)

directive

EnvironmentalOperating Temperature 32 to 122°F (0 to 50°C)Storage Temperature -22 to 158°F (-30 to 70°C)Relative Humidity 0 to 90% non-condensingIngress Protection Rating IP20Nema Rating 1

Page 14: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

14 / 20 ECLYPSE™ Connected System Controller

Standards and RegulationsCE:£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential,

commercial and light-industrial environments£ Immunity EN61000-6-1: 2007; Generic standards for residential,

commercial and light-industrial environmentsFCC This device complies with FCC rules part 15, subpart B, class BUL Listed (CDN & US) UL916 Energy management equipment

             

I/O Modules - Universal Inputs (UI)GeneralInput Type Universal; software configurableCurrent Input Option Selection DIP switchInput Resolution 16-bit analog to digital converterPower Supply Output 18VDC; 20mA maximum per 0 to 20 mA input1

ContactType Dry contact

CounterType Dry contactMaximum Frequency 1Hz maximum,Minimum Duty Cycle 500milliseconds On / 500milliseconds Off

0 to 10VDCRange 0 to 10VDC (40kΩ input impedance)

0 to 5VDCRange 0 to 5VDC (high input impedance)

0 to 20mARange 0 to 20mA

249Ω DIP-switch configurable internal resistor

Resistance/ThermistorRange 0 to 350 KΩSupported Thermistor Types Any that operate in this rangePre-configured Temperature Sensor Types:£ Thermistor 10KΩ Type 2, 3 (10KΩ @ 77ºF; 25ºC)£ Platinum Pt1000 (1KΩ @ 32ºF; 0ºC)£ Nickel RTD Ni1000 (1KΩ @ 32ºF; 0ºC)

RTD Ni1000 (1KΩ @ 69.8ºF; 21ºC)

Page 15: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

ECLYPSE™ Connected System Controller 15 / 20

I/O Modules - Digital Inputs (DI)GeneralInput Type Dry contact or Open-CollectorLow Threshold < 2.5VHigh Threshold > 3.0V

Pulse/CounterPulse Input S0 output compatibleMaximum Frequency 120HzMinimum Duty Cycle 4.167milliseconds On / 4.167milliseconds Off

I/O Modules - Universal Outputs (UO)GeneralOutput Type Universal; software configurableOutput Resolution 10-bit digital to analog ConverterOutput Protection Built-in snubbing diode to protect against back-EMF,

for example when used with a 12VDC relayLoad Resistance Minimum 200Ω for 0 to 10VDC and 0 to 12VDC outputs

Maximum 500Ω for 0 to 20mA outputAuto-reset Fuse 60mA @ 140ºF; 60ºC

0 or 12VDC (On/Off)Range 0 or 12VDC

PWMRange Adjustable period from 2 to 65seconds

FloatingMinimum Pulse On/Off Time 500millisecondsDrive Time Period Adjustable

0 to 10VDCRange 0 to 10VDC linear

0 to 20mARange 0 to 20mACurrent Source 20mA maximum per 0 to 20 mA outputPorts UO1, UO2, and UO3 only DIP switch

HOAHand-Off-Auto switch When equipped

Supervision allows control logic to read the current HOA switch and potentiometer settings

Threshold ConfigurablePotentiometer Voltage Range 0 to 12VDC

Page 16: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

16 / 20 ECLYPSE™ Connected System Controller

I/O Modules - Digital Output (DOT)GeneralOutput Type 24VAC Triac; software configurableMaximum Current 0.5A continuous

1A @ 15% duty cycle for a 10 minute periodPower Source External power supply

0 or 24VAC (On/Off)Range 0 or 24VAC

PWMRange Adjustable period from 2 to 65seconds

FloatingMinimum Pulse On/Off Time 500millisecondsDrive Time Period Adjustable

HOAHand-Off-Auto switch When equipped

Supervision allows control logic to read the current HOA switch setting

I/O Modules - Digital Output (DOR)For ECY-8DOR & ECY-8DOR-HOA Models:GeneralOutput Type Relay contactRelay Type Form CPower Source Dry contact (external power supply)Operating Voltage 0 to 277VAC or 0-30VDC ±10%, see HIG for mounting specifications

Maximum Current£ Resistive Load 10A£ Inductive Load 6A£ Motor Load 3AProtection Outputs must be protected with max 10 A external circuit breaker

DigitalRange On/Off

HOAHand-Off-Auto switch When equipped

Supervision allows control logic to read the current HOA switch setting

Page 17: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

ECLYPSE™ Connected System Controller 17 / 20

MechanicalDimensions (H × W × D) 4.74 × 5.15 × 2.31" (120.31 × 130.07 × 58.56mm)

4.74" 120.31

2.31" 58.56

Front Profile

O6O3O1 O4 O7 O8O5O2

MAN

AUTO

OFF

Inter-Connection Gap: 0.01" 0.40

5.15" 130.07

4.94" 125.32

Back

3.18" 80.82

18.540.73

21.080.83

Inches Millimeters0.06" 1.44

4.8" 121.75

Shipping weight 0.75lbs (0.34kg)Mounting DIN rail or screw mountingHot-swappable Yes (once high voltages have been removed)Enclosure Material FR/ABSEnclosure Rating1 Plastic housing, UL94-5VB flammability rating1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)

directive

EnvironmentalOperating Temperature 32 to 122°F (0 to 50°C)Storage Temperature -22 to 158°F (-30 to 70°C)Relative Humidity 0 to 90% non-condensingAltitude <6562ft (2000m)Pollution Degree 2Ingress Protection Rating IP20

(must be mounted in a protective enclosure to conform with electrical installation standards)Overvoltage Category II - 2.5 kV

Standards and RegulationsCE:£ Electrical Safety EN 60730-1 : 2011 - Automatic electrical controls for household

and similar use - Part 1: General requirements£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential,

commercial and light-industrial environments£ Immunity EN61000-6-1: 2007; Generic standards for residential,

commercial and light-industrial environmentsUL Listed (CDN & US) UL 61010-1 Safety Requirements For Electrical Equipment

For Measurement, Control, And Laboratory Use - Part 1: General Requirements - Edition 2 - Revision Date 2008/10/28

FCC This device complies with FCC rules part 15, subpart B, class B

             

Page 18: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

18 / 20 ECLYPSE™ Connected System Controller

Communications ModuleECY-RS485 Communications ModuleSupported Quantity 1 × ECY-RS485 per ECY-S1000

Power Supply InputVoltage 18VDCPower Consumption TBD W

CommunicationsSupported BACnet MS/TP or Modbus RTU Connectivity:£ BACnet MS/TP or Modbus RTU 2 × RS-485 serial communications ports

Each RS-485 port supports one communication protocol at a time£ RS-485 Wiring 1-pair + Common/shield£ Connection Type Screw terminals£ RS-485 EOL Resistor Built-in£ RS-485 Baud Rates 9600, 19 200, 38 400, or 76 800 bps£ RS-485 Addressing Controller’s Web Configuration Interface

MechanicalDimensions (H × W × D) 4.74 × 3.16 × 2.31" (120.31 × 80.19 × 58.56mm)

2.95 [74.99]

4.74 [120.31]

3.20 [81.17] 2.31 [58.56]

3.18 [80.82]

0.73 [18.54]

0.83 [21.08]

Inter-Connection Gap: 0.01 [0.40]

Front BackProfile0.06 [1.44]

5.30 [134.65]

Inches [Millimeters]

0.51 [12.90]

RX2 TX2RX1 TX1

Shipping weight TBD lbs (TBD kg)Mounting DIN rail or screw mountingEnclosure Material FR/ABSEnclosure Rating1 Plastic housing, UL94-V0 flammability rating

Plenum rating per UL19951. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)

directive

Page 19: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

ECLYPSE™ Connected System Controller 19 / 20

EnvironmentalOperating Temperature 32 to 122°F (0 to 50°C)Storage Temperature -22 to 158°F (-30 to 70°C)Relative Humidity 0 to 90% non-condensingIngress Protection Rating IP20Nema Rating 1

Standards and RegulationsCE:£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential,

commercial and light-industrial environments£ Immunity EN61000-6-1: 2007; Generic standards for residential,

commercial and light-industrial environmentsFCC This device complies with FCC rules part 15, subpart B, class BUL Listed (CDN & US) UL916 Energy management equipment

             

Page 20: Datasheet ECLYPSE™ Connected System Controller Controls/Fiches techniques... · ded), logging, alarming, ... Connected System Controller for medium/large sized AHU and plant applications

20 / 20 05DI-DSIPCTR-17

Specifications subject to change without notice.ECLYPSE, Distech Controls, the Distech Controls logo and Allure are trademarks of Distech Controls Inc. BACnet is a registered trademark of ASHRAE; BTL is a reg-

istered trademark of the BACnet Manufacturers Association. All other trademarks are property of their respective owner.©, Distech Controls Inc., 2014 - 2015. All rights reserved.