1 Notes for the user 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typographical conventions 2 1.3.1 Enumerations 2 1.3.2 Actions 2 1.3.3 Syntax 2 1.3.4 Cross-references 2 1.6 Symbols 2 1.7 Abbreviations 2 2 Safety 2.1 Intended use 3 2.2 General safety notes 3 2.3 Meaning of the warnings 3 3 Getting Started 3.1 Connection overview, Standard type, BNI EIP-104-000-Z016 4 3.2 Connection overview, Display type, BNI EIP-104-100-Z016 5 3.3 Mechanical connection 6 3.4 Electrical connection 6 3.4.1 Power supply 6 3.4.2 Ethernet IP interface 6 3.4.3 Sensor / Actor interface 7 4 Technical data 4.1 Dimensions 8 4.2 Mechanical data 8 4.3 Operating conditions 8 4.4 Electrical data 8 4.5 Ethernet port 9 4.6 Function indicators 9 5 Integration 5.1 Integration into RSLogix 10 6 Display 6.1 General 16 6.2 Default address 16 6.3 Display informations 16 6.4 Menu structure 17 6.5 Edit mode 18 7 Included Material 7.1 Included Material 19 8 Appendix Ordering code 20 Bit Layout 21

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 2

1 Notes to the user

1.1 About this guide The BNI EIP-… serves as a decentralized input module for connecting to an EtherNet/IP™ network.

1.2 Structure of the

guide The guide is organized so that the sections build on one another.

Section 2: Basic safety information. Section 3: The main steps for installing the device. Section 4: Technical data for the device Section 5: Integration into RS Logix Section 6: Display Section 7: Included Material …

1.3 Typographical

Conventions The following typographical conventions are used in this Guide.

1.3.1 Enumerations Enumerations are shown in list form with bullet points.

- Entry 1, - Entry 2.

1.3.2 Actions Action instructions are indicated by a preceding triangle. The result of an action is indicated by an arrow.

Action instruction 1. Action result. Action instruction 2.

1.3.3 Syntax Numbers:

Decimal numbers are shown without additional indicators (e.g. 123), Hexadecimal numbers are shown with the additional indicator hex (e.g. 00hex).

1.3.4 Cross-references Cross references indicate where additional information on the topic can be found (see

section 4 ”Technical Data”). 1.4 Symbols Note tip

This symbol indicates general notes. Note

This symbol indicates a security notice which most be observed. 1.5 Abbreviations BNI Balluff Network Interface

IPAP IP address plug I port Standard input port EIP…….EtherNet/IP™ EMC Electromagnetic Compatibility FE Function ground O port Standard output port

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 3

2 Safety

2.1 Intended use

This guide describes The BNI EIP-… serves as a decentralized input module for connecting to an EtherNet/IP™ network.

2.2 General safety notes

Installation and startup Installation and startup are to be performed only by trained specialists. Any damage resulting from unauthorized manipulation or improper use voids the manufacturer’s guarantee and warranty. The device is in accordance with EMC Class A. Such equipment may generate RF noise. The operator must take precautionary measures accordingly. The device must be powered only using an approved power supply (see section 4 “Technical data”). Only approved cable may be used. Operating and testing The operator is responsible for observing local prevailing safety regulations. When defects and non-clearable faults in the device occur, take it out of service and secure against unauthorized use. Approved use in ensured only when the housing is fully installed.

2.3 Meaning of the warnings

Note! The pictogram used with word ”Caution“ warns of a possible hazardous situation affecting the health of persons or equipment damage. Ignoring these warnings can result in injury or equipment damage.

Always observe the described measures for preventing this danger.

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 4

2 Getting Started

2.1 Connection overview Standard type BNI EIP-104-000…

Figure: 3-1: BNI EIP-104-000-Z016 1 Mounting hole

2 IPAP / Programming interface 3 Status LED: Communication / module 4 Standard input port 08 + 09 5 Pin/Port LED : Signal status 6 Standard input port 10 + 11 7 Standard input port 12 + 13 8 Standard input port 14 + 15

9 Standard input port 06 + 07 10 Standard input port 04 + 05 11 Standard input port 02 + 03 12 Standard input port 00 + 01 13 Aux Power Supply Port 14 Label 15 EtherNet/IP™ port 16 Earth connection

1

13

12

2

3

4

5

6

7

8 9

10

11

14 15

16

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 5

3 Getting Started

3.2 Connection overview Display type BNI EIP-104-000…

Figure: 3-2: BNI EIP-104-100-Z016 1 Mounting hole

2 IPAP / Programming interface 3 Display 4 Status LED: Communication / module 5 Standard input port 08 + 09 6 Pin/Port LED : Signal status 7 Standard input port 10 + 11 8 Standard input port 12 + 13 9 Standard input port 14 + 15

10 Standard input port 06 + 07 11 Standard input port 04 + 05 12 Standard input port 02 + 03 13 Standard input port 00 + 01 14 Aux Power Supply Port 15 Label 16 EtherNet/IP™ port 17 Earth connection

1

5

2

3

11

10

12

13

14

17

7

9

6

8

16

15

4

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 6

3 Getting Started

3.3 Mechanical connection

The module is attached using 2 M6 screws and 2 washers. Isolation pad as accessory available

3.4 Electrical connection

3.4.1 Power supply Power supply (7/8”, male)

Pin Function Description 1 +24 V Output Power 2 +24 V Input Power 3 0 V Input Power Common GND 4 0 V Output Power Common GND Connection of the module

24 V DC. Provide sensor/bus power and actuator power from separate power sources if possible. Total current <9A. The total current of all modules may not exceed 9A even when daisy

chaining the actuator supply.

Function ground

Note! The FE connection from the housing to the machine must be low-impedance and kept as short as possible.

3.4.2 Ethernet IP Ethernet IP (M12, D-coded, female) interface PIN Function 1 Tx+ 2 Rx+ 3 Tx- 4 Rx-

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 7

3 Getting Started

3.4.3 Sensor- Standard input port (M12, A-coded, female) interface Pin Input port

Function

1 +24V, 200mA 2 Input 1 3 0 V, GND

4 Input 2

5 FE Note!

For the digital sensor inputs follow the input guideline per EN61131-2, type 2.

Note!

Unused I/O port socket must be fitted with cover caps to ensure IP67 protection rating.

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 8

4 Technical data

4.1 Dimensions

4.2 Mechanical data Housing material Die case zinc, matt nickel plated

Enclosure rating per IEC 60529 IP 67 (only when plugged-in and threaded-in)

Supply voltage 7/8” 4-pin male

Input ports / Output ports M12, A-coded (8 x female)

Dimensions (W x H x D in mm) 68 x 224 x 30.9

Mounting type 2-hole screw mount

Ground strap attachment M4

Weight Approx. 700gr. 4.3 Operating condition

Operating temperature Ta Storage temperature

-5 °C ... 55 °C -25 C ... 75 °C

EMC - EN 61000-4-2/3/4/5/6 - EN 55011

- Severity level 4A/3A/4B/2A/3A - Gr.1, CL. A

Shock/vibration EN 60068-2-6, EN 60068-2-27 EN 60068-2-29, EN 60068-2-64

4.4 Electrical data Supply voltage 18...30.2 V DC, per EN 61131-2

Ripple <1%

Input current at 24 V 130 mA

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 9

4 Technical data

4.5 Ethernet port Ethernet IP port 1 x 10Base-/100Base-Tx

Connection for Ethernet IP port M12, D-coded

Cable types per IEEE 802.3 Shielded twisted pair min. STP CAT 5/ STP CAT 5e

Data transmission rate 10/100 Mps

Max. cable length 100 m

Flow control Half Duplex/Full Duplex (IEEE 802.33x-Pause) 4.6 Function indicators

LED indicators

LED Indicator Function LED 4 Green/Red Module Status LED 6 Green/Red Network connection LED 7 Yellow / Off Network data transmission: 100 Mbit/s / 10 Mbit/s LED 8 Green/Red US Power supply / Under voltage LED 9 Off / Green/Green

blinking No Link / Link is active / Link with Data transfer

Each M12 Port (digital Input) is assigned two 2-color LED’s which indicate the operating

states. Input ports LED Function LED Pin 2 / Pin 4 Off Input signal = 0 Yellow Input signal = 1 Red Input signal = SC Short circuit* *SC=Short circuit detection between Pin 1 and Pin 3.

Port/Pin LED: status input ports

LED 4-9, Status LED

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 10

5 Integration

5.1 Integration into RSLogix

• Start/Open RSLogix 5000 Project • Add EtherNet/IP Communication Module to the I/O Configuration

• (1) Right-Click I/O Configuration Folder and Choose “New Module”

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 11

5 Integration

• (1) Choose Communication Module from List • (2) Click “OK”

• (1) Choose Major Revision Level of Communication Module • (2) Click “OK”

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 12

5 Integration

• Configure Communication Module • (1) Name Module • (2) Verify Slot Number • (3) Choose desired Electronic Keying Match • (4) Click “OK”

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 13

5 Integration

• Add Balluff EtherNet/IP™ Module • (1) Right-Click I/O Configuration Folder and Choose “New Module”

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 14

5 Integration

• (1) Choose “Generic Ethernet Module” from List • (2) Click “OK”

• Configure Generic Module for Balluff EtherNet/IP Module • (1) Name Module • (2) Choose “Data-SINT” for Comm Format • (3) Enter IP Address of Balluff Module • (4) Enter Assembly Instance and Size for Input, Output, and Configuration

Parameters (Module Style Specific – See Chart)(5) • Click “OK”

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 15

5 Integration

Reference Table Balluff EtherNet/IP Module Assembly

Instance Size

Input 100 5

Output 101 2

BNI EIP-104-x00-Z016

Configuration 102 0

Note: Controller Scoped Tags for the EtherNet/IP Modules will follow the name given in the Configuration of the Generic Ethernet Module

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 16

6 Display

6.1 General The BNI EIP-… serves as a decentralized Input module for connecting to an EtherNet/IP ™network. With the implemented display, the address is set directly on the BNI EIP… devices. The following address types are implemented:

- IP address - Subnet mask - Gateway address.

Each address type consists of 4 octets.

6.2 Default address IP address: 169.254.0.1 Subnet mask: 255.255.255.0 Gateway address: 0.0.0.0

6.3 Display information

IP: IP address SN: Subnet address GW: Gateway address

3: fourth octet 2: third octet 1: second octet 0: first octet

IP

SN

GW

2 3 1 0

Cursor for selecting address type

Cursor for selecting octet

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 17

6 Display function

6.4 Menu structure

Start-up screen (2 sec.)

IP Screen

SN Screen

GW Screen

Info Screen

IP-address: 192.168.015.007

Subnet-address: 255.255.255.000

Gateway-address: 000.000.000.000

Hard- and software release

Press “S” button short to scroll

+/-

+/-

+/-

Octet #0 Octet #1 Octet #2 Octet #3

Shown in

Display

3 2 1 0 3 2 1 0 3 2 1 0 3 2 1 0

Displays shows octet #1 of the IP address

Press ↑- button to scroll through the address

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 18

6 Display function

6.5 Edit mode

• “Arrow“- button for address adjustment • Long push of the “Arrow” - button initiates the fast scrolling mode • Edit mode: display flash in fast cycle • to leave and store the address push S buttons for 3 sec. again • after 10 sec. in the edit mode without any key hit, the display returns to

the read mode without any changes and shows the previous address Options: “Lock function” by PLC -> edit mode is not accessible “Ping” function by Network” “Free controllable” LEDs

Press “S” buttons for 3 sec

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 19

7 Included Material

7.1 Included Material The BNI EIP consists of the following components: IO-block 4 blind plugs M12 Ground strap Screw M4x6 20 labels

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 20

8 Appendix

Ordering code BNI EIP-104-x00-Z016 Balluff Network Interface EtherNet/ IP™ Functions 104 = IP 67 Input module, 16 Inputs Variants 000 = Standard version 100 = Display version Mechanical version Z016 = Die-cast zinc housing Material: 1. Balluff housing version Uplink: 1 x M12x1 internal thread Update: 1 x M12x1 internal thread Power: 7/8“ external thread Sensor Ports: 8 x M12x1 internal thread

Order information Product ordering code Order code

BNI EIP-104-000-Z016 BNI0010

BNI EIP-104-100-Z016 BNI0014

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 21

8 Appendix

Bit Layout

BNI EIP-104-x00-Z016 (16 Standard Inputs (5 bytes IN, 2 byte OUT) Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

IN 1/0 I-15 I-14 I-13 I-12 I-11 I-10 I-9 I-8 I-7 I-6 I-5 I-4 I-3 I-2 I-1 I-0 IN 3/2 S-15 S-14 S-13 S-12 S-11 S-10 S-9 S-8 S-7 S-6 S-5 S-4 S-3 S-2 S-1 S-0 IN 4 SP

OUT 3/2 Control Byte Display Control Byte IPAP S: Short circuit status I: Input OL: Overload status

HS: Output Handshake R: Output Reset O: Output

Control Byte Display: Bit 0: LEDs red on Bit 1: LEDs green on Bit 2: Display lock Bit 3-7: reserved, not defined

Control Byte IPAP: Bit 0: LED red on Bit 1: LED red flash Bit 2-3: reserved, not defined Bit 4: LED Yellow on Bit 5: LED Yellow flash Bit 6-7: reserved, not defined

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 22

Balluff Network Interface EtherNet/IP™, BNI EIP-104-x00-Z016

www.balluff.com 23

www.balluff.com

Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a.d.F. Germany Tel. +49 7158 173-0 Fax +49 7158 5010 [email protected]

Nr.

8662

89 E

E

ditio

n 01

09

Sub

ject

to m

odifi

catio

n