Page 1: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

BNI PBS-202-000-Z001

BNI PBS-206-000-Z001

Short Guide

Page 2: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001

1 Notes for the user 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typografical conventions 2 1.3.1 Enumerations 2 1.3.2 Actions 2 1.3.3 Syntax 2 1.3.4 Cross references 2 1.4 Symbols 2 1.5 Abbreviations 2

2 Safety 2.1 Intended use 3 2.2 General safety notes 3 2.3 Meanings and warnings 3

3 Getting started 3.1 Connection overview, BNI PBS-202-000-Z001 4 3.2 Connection overview, BNI PBS-206-000-Z001 5 3.3 Mechanical connection 6 3.4 Electrical connection 6 3.4.1 Supply voltage 6 3.4.2 Profibus interface 7 3.4.3 Connecting actuators 8

4 Technical data 4.1 Dimensions 9 4.2 Mechanical data 9 4.3 Elektrical data 9 4.4 Operating conditions 9 4.5 Function indicators 10

5 Included material 5.1 Included material 11

6 Appendix 6.1 Ordercode / order informations 12

Page 3: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001

www.balluff.com 2

1 Notes for the user

1.1 About this guide The BNI EIP-… serves as a decentralized input/output module for connecting to a Profibus

network. 1.2 Structure of the

guide The guide is organized so that the sections build on one another.

Section 2: Basic safety information.

Section 3: Getting started.

Section 4: Technical data for the device.

Section 5: Included Material.

1.3Typografical

conventions The following typographical conventions are used in this Guide.

1.3.1 Enumerations Enumerations are shown in list form with bullet points.

- Entry 1, - Entry 2.

1.3.2 Actions Action instructions are indicated by a preceding triangle. The result of an action is indicated

by an arrow. Action instruction 1.

Action result. Action instruction 2.

1.3.3 Syntax Numbers:

Decimal numbers are shown without additional indicators (e.g. 123).

Hexadecimal numbers are shown with the additional indicator hex (e.g. 00hex).

1.3.4 Cross references Cross references indicate where additional information on the topic can be found (see

section 4 „Technical Data”).

1.4 Symbols Note Tip!

This symbol indicates general notes.

Note!

This symbol indicates a security notice which most be observed.

1.5 Abbreviations O port

BCD BNI EMV I-Port FE GSD file LSB MSB SELV PLC PELV

Profibus DP

Digital output port Binär coded switch Balluff Network Interface Elektromagnetische Verträglichkeit Digital input port Functions earth Geräte-Stamm-Daten-Datei (Generic Station Description) Least Significant Bit Most Significant Bit Safety Extra Low Voltage Process logic control Protective Extra Low Voltage -

Profibus DP: Profibus dezentrale peripherie

Page 4: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001

www.balluff.com 3

2 Safety

2.1 Intended use-

This guide describes The BNI PBS-… serves as a decentralized output module for

connecting to a Profibus network.

2.2 General safety notes

Installation and startup

Installation and startup are to be performed only by trained specialists. Any damage

resulting from unauthorized manipulation or improper use voids the manufacturer’s

guarantee and warranty.

The device is in accordance with EMC Class A. Such equipment may generate RF noise.

The operator must take precautionary measures accordingly.

The device must be powered only using an approved power supply (see section 4

“Technical data”). Only approved cable may be used.

Operating and testing

The operator is responsible for observing local prevailing safety regulations.

When defects and non-clearable faults in the device occur, take it out of service and secure

against unauthorized use.

Approved use in ensured only when the housing is fully installed.

2.3 Meanings

and warnings Note!

The pictogram used with word “Caution“ warns of a possible hazardous situation affecting the health of persons or equipment damage. Ignoring these warnings can result in injury or equipment damage.

Always observe the described measures for preventing this danger.

Page 5: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001

www.balluff.com 4

3 Getting started

3.1 Connection- overview

BNI PBS-202-…

Fig.: 3.1: Connection overview BNI PBS-202-…

1 Mounting hole 2 M12 Profibus IN 3 Address switch 4 Supply power POWER IN 5 Standard Output port 1, Pin 4 6 Standard Output port 3, Pin 4 7 Standard Output port 5, Pin 4 8 Standard Output port 7, Pin 4 9 Standard Output port 6, Pin 4

10 Standard Output port 4, Pin 4 11 Standard Output port 2, Pin 4 12 Standard Output port 0, Pin 4 13 Status LED module 14 Supply power Power OUT 15 Label 16 M12 Profibus OUT 17 Earth connection

1

2

3

5

6

7

8

1

10

9

11

13

14

16

12

15

4

17

Page 6: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001

www.balluff.com 5

3 Getting started

3.1 Connection overview

BNI PBS-206-…

Abb. 3.2: Connection overview BNI PBS-206-…

1 Mounting hole 2 M12 Profibus IN 3 Address switch 4 Supply power POWER IN 5 Standard Output port 1, Pin 2 / 4 6 Standard Output port 3, Pin 2 / 4 7 Standard Output port 5, Pin 2 / 4 8 Standard Output port 7, Pin 2 / 4 9 Standard Output port 6, Pin 2 / 4

10 Standard Output port 4, Pin 2 / 4 11 Standard Output port 2, Pin 2 / 4 12 Standard Output port 0, Pin 2 / 4 13 Status LED module 14 Supply power Power OUT 15 Label 16 M12 Profibus OUT 17 Earth connection

1

2

3

5

6

7

8

1

10

9

11

13

14

16

12

15

4

17

Page 7: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001

www.balluff.com 6

3 Getting started

3.3 Mechanical connection

The module is attached using 2 M6 screws and 2 washers.

3.4 Elektrische Anbindung

3.4.1 Supply voltage Power OUT (7/8“ Mini Change, 5-pin, female)

PIN Function

1 0 V

2 0 V

3 FE

4 Sensor / Bus communication supply

5 Actuator supply

Power Out (7/8” Mini-Change, 5-Pin, male)

PIN Function

1 0 V

2 0 V

3 FE

4 Sensor / Bus communication supply

5 Actuator supply

Connection of the IO

module 24 V DC.

Provide sensor/bus power and actuator power from separate power sources if

possible.

Total current <9A. The total current of all modules may not exceed 9A even when

daisy chaining the actuator supply.

Note!

The use of a Profibus hybrid cable is not allowed.

Function ground

Note Tip!!

The FE connection from the housing to the machine must be low-impedance and kept as short as possible.

Page 8: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001

www.balluff.com 7

3 Getting started

3.4.2 Profibus interface

The bus connection is made using the M12 sockets Profibus IN and Profibus OUT. The address is

set on the address switch.

Profibus OUT (M12, B-coded,female)

PIN Function

1 VP

2 RxD/TxD-N, A line (Green)

3 DGND

4 RxD/TxD-P, B line (Red)

5 n.c.

Thread: Shield

Profibus IN (M12, B-coded, male)

PIN Function

1 VP

2 RxD/TxD-N, A line (Green)

3 DGND

4 RxD/TxD-P, B line (Red)

5 n.c.

Thread: Shield

Connecting the Profibus

- Connect ground conductor to FE terminal - Connect incoming Profibus line to Profibus IN

- Connect continuing Profibus line to Profibus Out or screw termination resistor to the

continuing bus terminal

Note Tip!

Each Profibus segment end must be installed with a termination resistor. Unused sockets must be fitted with over caps to ensure IP67 protecting rating.

Addressing

The Profibus address is et directly on the BNI PBS- using two BCD switches Permissible address range: 0 … 99. Each Profibus node must have a unique address assigned to it. Any change to the address does not become effective until power is reset on the modules.

Page 9: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001

www.balluff.com 8

3 Getting started

3.4.3 Connecting

actuators

8 I/O ports are provided for connecting the actuators.

PIN Standard Output port

BNI PBS-202-000-Z001

Standard Output port

BNI PBS-206-000-Z001

1 + 24 V, 200mA + 24 V, 200 mA

2 - Output, 2A

3 0 V 0V

4 Output, 2A Output, 2A

5 FE FE

Note Tip!

Unused I/O port socket must be fitted with cover caps to ensure IP67 protection rating.

Module Standard O ports

BNI PBS-202-000-Z001 8

BNI PBS-206-000-Z001 16

Page 10: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001

www.balluff.com 9

4 Technical data

4.1 Dimensions

4.2 Mechanical data

Housing material Die case zinc, matt nickel plated

Fieldbus Profibus: M12, B-coded (female and male)

Supply power 5-pin, 7/8“ (female and male)

I/O Ports M12, A-coded (8 x female)

Enclosure rating IP67 (only when plugged-in and threaded-in)

Weight ca.: 735 g

4.3 Electrical data

Operating voltage 18 ... 30 V DC

Ripple < 1 %

Current draw without load ≤ 200 mA

Service port Balluff

4.4 Operating conditions

Operating temperature Storage temperature

-5°C … 70°C -25°C….70°C

EMV - EN 61000-4-2/3/4/5/6 - EN 55011

- Severity level 4A/3A/4B/2A/3A - Gr. 1, Kl. A

Shock / vibration EN 60068 Teil2-6/27

Page 11: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001

www.balluff.com 10

4 Technical data

4.5 Function indicator

Status LEDs

LED Indicator Function

LED 1 Green US power supply sensor / bus communication ok

LED 2 Green UA power supply actuator ok

LED 3 Red US power supply sensor / bus communication under

voltage

LED 4 Red UA power supply actuator under voltage

LED 5 Green, solid

Green, blinking

BUS data transmission Profibus ok

BUS data transmission Profibus inactive

LED indicators

Standard I/O ports

Each M12 Port (digital output) is assigned to LED’s which indicate the operating states

Indicator

LED 6 (PIN 4)

Off Output = 0

Yellow Output = 1

Red I Output > Imax

LED 7 (PIN 2)

Off Output = 0

Yellow Output = 1

Red I Output > Imax

LED 6, Pin 4

LED 7, Pin 2

LED 1-5, Status

Page 12: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001

www.balluff.com 11

5 Included material

5.1 Included material

The BNI PBS … consists of the following components:

IO-block

4 blind plugs M12

Ground strap

Screw M4x6

20 labels.

Page 13: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001

www.balluff.com 12

6 Appendix

Order code BNI PBS-20x-000-Z001

Balluff Network Interface

Profibus

Functionen

202 = IP 67 Input module, 8 outputs

206 = IP 67 Input module, 16 outputs

Variante

000 = Standard version

Mechanical version

Z001 = Die-cast zinc housing

Material: Balluff housing version

Profibus ports: 1 x M12x1 internal thread, 1x M12 external thread

Power: 1 x 7/8“ external thread, 1x 7/8” external threads

IO-Ports: 8 x M12 internal thread

Order information Product ordering code Order code

BNI PBS-202-000-Z001 BNI002J

BNI PBS-206-000-Z001 BNI002K

Page 14: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001

www.balluff.com 13

Page 15: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001

www.balluff.com 14

Page 16: BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 - Balluffusa.balluff.com/manuals/BNI Network Blocks/ProfiBus Blocks/BNI PBS... · BNI PBS-202-000-Z001 BNI PBS-206-000-Z001 Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001

www.balluff.com 15

www.balluff.com

Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a.d.F. Germany Tel. +49 7158 173-0 Fax +49 7158 5010 [email protected]

Nr.

868796 E

A

usgabe 0

906

Änderu

ngen v

orb

ehalten