energy insights singapore 2013-04

Upload: yh-leong

Post on 03-Jun-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 Energy Insights Singapore 2013-04

    1/66

    ENGINEERING ADVANTAGE

    ENERGY INSIGHTSOPTIMISING HYDRONIC SYSTEMS

    FOR ENERGY SAVINGS

    Jean-Christophe Carette

    Singapore, April 2013

  • 8/11/2019 Energy Insights Singapore 2013-04

    2/66

    ENGINEERING ADVANTAGE

    C

    opyrightTAHydronicsSA.Allrightsreserved.

    World's energy consumption

    2

    40% of the world's energy

    consumption is used in buildings*

    50% of this is in HVAC systems alone*

    (*) Sources: European Commission EPBD (point 6, pp1) &

    US Department of Energys Buildings Energy Data Book

  • 8/11/2019 Energy Insights Singapore 2013-04

    3/66

    ENGINEERING ADVANTAGE

    C

    opyrightTAHydronicsSA.Allrightsreserved.

    Energy savings on HVAC in buildings

    3

    HVAC installationUse of new technologies

    System approach ofhydronic design

    Shorter pay-back times

    Building structure(insulation, double glazing, )

    Best way to save energyLarger energy savings

    Long pay-back times

    Human factorAvoid interferences with

    the HVAC systemEducate tenants and

    maintenance team

    Never-ending task

    Building modifications require

    adaptation or modernization of

    the HVAC installation to take into

    account new heat gains/losses

    When modifying a HVAC

    installation one must take into

    account the capabilities of

    peopleusing the installation

  • 8/11/2019 Energy Insights Singapore 2013-04

    4/66

    ENGINEERING ADVANTAGE

    C

    opyrightTAHydronicsSA.Allrightsreserved.

    Energy savings via hydronic optimization

    4

    Optimising a building's HVAC

    system can reduce its energy

    consumption by 30% :

    By avoiding the deterioration

    of production unit

    efficiencies,

    By optimizing the energyefficiency of the hydronic

    distribution,

    By guaranteeing a stable and

    accurate room temperature.

  • 8/11/2019 Energy Insights Singapore 2013-04

    5/66

    IMPROVING

    PRODUCTION UNIT

    EFFICIENCIES

    5

  • 8/11/2019 Energy Insights Singapore 2013-04

    6/66

    ENGINEERING ADVANTAGE

    C

    opyrightTAHydronicsSA.Allrightsreserved.

    Coefficient of Performance (COP) isused to indicate chiller efficiency:

    Heat transfer (and thus COP) is good when Log Mean Temperature Differencebetween water and refrigerant is kept high

    Evaporator refrigerant temperature remains constant

    Supply water temperature Ts is usually kept constant

    Thus return water temperature Trmust be kept "high"

    to keep LMTD high

    Keeping a high Tr (thus a high T = Tr-Ts) provides higher COP at partial load

    Chillers

    6

    Evaporator

    Condenser

    Chilled water

    Tr Ts645.2

    compressor

    evaporator

    P

    PCOP

    Refrigerant saturated

    suction temp.

    Tr

    Ts

  • 8/11/2019 Energy Insights Singapore 2013-04

    7/66ENGINEERING ADVANTAGE

    C

    opyrightTAHydronicsSA.Allrightsreserved.

    Effect of a decrease of the return water temp. on COP

    7

    Example :

    Chiller: 200 tons (703 kW)

    Water condenser temperatures: 29,5/35C

    Supply temperature of chilled water Ts: 7C

    A reduction of return temperature of chilled water can lead to a

    15% drop of the COP

    Return temp. chilled water Tr[C]

    COP

    5

    4,6

    4,4

    4,24

    4,2

    4,4

    4,6

    4,8

    5

    5,2

    10,5 11 11,5 12 12,5 13

    15%

  • 8/11/2019 Energy Insights Singapore 2013-04

    8/66ENGINEERING ADVANTAGE

    C

    opyrightTAHydronicsSA.Allrightsreserved.

    6,0

    8,0

    10,0

    12,0

    14,0

    16,0

    18,0

    20,0

    22,0

    24,0

    26,0

    0% 20% 40% 60% 80% 100%

    Variable flow proportional control

    8

    Returntemp.Tr

    2-way circuit (variable flow)

    Flow through terminal unit

    Temperature regime:

    Ts/Tr/Ti = 6/12/23.5C

    qp

    STAD

    H

    C

    Variable flow circuit

    The DT through a terminal unit increases

    when the flow reduces.

    Thus the return water temperature increases

    when the flow reduces.

    All benefits for chiller COP.

    Cooling

  • 8/11/2019 Energy Insights Singapore 2013-04

    9/66

  • 8/11/2019 Energy Insights Singapore 2013-04

    10/66ENGINEERING ADVANTAGE

    CopyrightTAHydronicsSA.Allrightsreserved.

    0%

    10%

    20%

    30%

    40%

    50%

    60%

    70%

    80%

    90%

    100%

    0% 20% 40% 60% 80% 100%

    On-off control Flow increase at partial load

    Manually balanced variable flow on-offcontrol system

    100 identical units; Pump head 200 kPa; Terminal unit 20kPa; On-off CV 5 kPa

    Temperature regime:

    Ts/Tr/Ti = 6/12/23.5C

    Totalsystemflow

    System load

    At 50% load, the total flow in system reaches 77% of the total design flow.This is a 54% increase w.r.t. the required flow (50%) at 50% load.

    Seasonal flow increase lead to an estimated increased pumping energy

    consumption up to +4% of total plant energy consumption

    10

    4%

  • 8/11/2019 Energy Insights Singapore 2013-04

    11/66ENGINEERING ADVANTAGE

    CopyrightTAHydronicsSA.Allrightsreserved.

    0%

    20%

    40%

    60%

    80%

    100%

    120%

    0% 20% 40% 60% 80% 100% 120% 140% 160%

    On-off control Emission at partial load

    At flow that is near design flow,

    emitted power does not increase

    much with the flow

    Control signal switches on/off when

    room temperature deviates much

    beyond the thermostat differential

    Flow

    Em

    ission

    11

    Roomt

    Design

    set-point23.5C

    Time

    At partial load in the system,

    if a valve is open:

    k

    TqP

    D

    (Troom - Tset-point) >0