SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller 369609f 1 01.09.17 Energi Savr Node QS Phase Adaptive Fixture Controller The Energi Savr Node QS family is a group of modular products for the control of lighting loads. This product is compatible with Quantum and QS systems. Features • Automatically selects leading-edge or trailing-edge dimming for incandescent / halogen, electronic/magnetic low-voltage and neon/cold cathode light sources. • Controls dimmable CFL/LED loads. Refer to Lutron P/N 048478 on www.lutron.com for compatibility with dimmable CFL / LED light sources. • RTISS Equipped technology compensates for incoming line-voltage variations (up to ± 2% change in frequency/second) such as changes in Root Mean Square (RMS) voltage, frequency shifts, harmonics and line noise. • RTISS-TE operates on the trailing edge of the AC sine wave. This allows for true instantaneous voltage compensation. QSNE-4A-D Note: Multiple QSMs can be added to increase the number of wireless inputs and Pico wireless controllers. LUTRON LUTRON H M L QSNE-4A-D DIN Rail Power Module 230 V~50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 Input S1 S2 S3 S4 CCI Switch Occ Photo IR Type 500 W Max 800 W Max 500 W Max 500 W Max Zone 2 Zone 1 Zone 3 Zone 4 Input Hi Temp Prog Power Opt1 Opt2 Opt3 Def Option Notes: 1 Up to four wired inputs total (of any type). 2 See "Output Zone Ratings" in "Specifications" section, for specific load type ratings. QS Link Energi Savr Node QS unit Energi Savr Node QS Phase Adaptive unit Energi Savr Node Programming Interface seeTouch QS Wallstation Wired IR Receiver 1 IR Transmitter Wired Daylight Sensor 1 Wired Occupancy Sensor 1 Emergency Contact Closure Input Up to 100 total QS devices 220-240 V~ Control Power 800 W Adaptive load 2 500 W Adaptive load 2 500 W Adaptive load 2 500 W Adaptive load 2 Four multi-function inputs that accept multiple sensor types Wireless Communication QS Sensor Module (QSM) QS Power Supply Radio Powr Savr Occupancy Sensor (up to 10 per QSM) Radio Powr Savr Daylight Sensor (up to 10 per QSM) Pico Wireless Controller (up to 10 per QSM) Wired Daylight Sensors Wired Occupancy Sensors Wired IR Receivers IR Transmitter IEC PELV/NECR Class 2 Dry Contact Switch (by others) 1 H M L QSNE-4A-D DIN Rail Power Module 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657 Input S1 S2 S3 S4 CCI Switch Occ Photo IR Type 500 W Max 800 W Max 500 W Max 500 W Max Zone 2 Zone 1 Zone 3 Zone 4 Input Hi Temp Prog Power Opt1 Opt2 Opt3 Def Option System Example • Unit is 12 DIN modules (216 mm) wide. • Four multi-function inputs compatible with the following: Daylight sensors – Occupancy sensors IR receivers IEC PELV / NEC® Class 2 dry contact switches • Provides air gap off (when all zones are off). • Integral protection for common temporary over- current and over-voltage conditions. • LEDs on front of unit provide diagnostic information. • Includes QS link for seamless integration of lights and controls.

Upload: trinhkhuong

Post on 22-Jun-2018

232 views

Category:

Documents


0 download

TRANSCRIPT

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 1 01.09.17

Energi Savr Node QS Phase Adaptive Fixture ControllerThe Energi Savr Node QS family is a group of modular products for the control of lighting loads. This product is compatible with Quantum and QS systems.

Features

•Automaticallyselectsleading-edgeortrailing-edge dimming for incandescent / halogen, electronic/magnetic low-voltageandneon/coldcathodelightsources.

•ControlsdimmableCFL/LEDloads.RefertoLutronP/N 048478 on www.lutron.com for compatibility with dimmableCFL/LEDlightsources.

•RTISSEquippedtechnologycompensatesforincomingline-voltagevariations(upto±2%changeinfrequency/second)suchaschangesinRootMeanSquare(RMS)voltage,frequencyshifts,harmonicsandline noise.

•RTISS-TEoperatesonthetrailingedgeoftheACsine wave. This allows for true instantaneous voltage compensation.

QSNE-4A-D

Note:MultipleQSMscanbeaddedtoincreasethenumber of wireless inputs and Pico wireless controllers.

LUTR

ON

LUTR

ON

R

LUTRON

LUTR

ON

RH

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

Notes: 1 Uptofourwiredinputstotal(ofanytype).2 See"OutputZoneRatings"in"Specifications"section,forspecificloadtyperatings.

QSLink

Energi Savr Node QS unit

Energi Savr Node QS Phase Adaptive

unit

Energi Savr Node Programming Interface seeTouch

QS Wallstation

WiredIR Receiver1IR

Transmitter

WiredDaylight Sensor1

Wired Occupancy Sensor1

EmergencyContactClosureInputUp to 100 total QS devices

220-240V~ ControlPower

800WAdaptiveload2

500WAdaptiveload2

500WAdaptiveload2

500WAdaptiveload2

Fourmulti-function inputs that accept

multiple sensor types

Wireless Communication

QS Sensor Module(QSM)

QS Power Supply

RadioPowrSavrOccupancy Sensor (upto10perQSM)

RadioPowr SavrDaylightSensor(upto 10perQSM)

Pico Wireless Controller(up to10perQSM)

Wired Daylight Sensors

Wired Occupancy

Sensors

Wired IRReceivers

IR Transmitter

IECPELV/NECR Class2DryContactSwitch(byothers)1

H

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

System Example

•Unitis12DINmodules(216mm)wide.•Fourmulti-functioninputscompatiblewiththefollowing:

– Daylightsensors – Occupancy sensors – IRreceivers – IECPELV / NEC®Class2drycontactswitches

•Providesairgapoff(whenallzonesareoff).•Integralprotectionforcommontemporaryover- currentandover-voltageconditions.

•LEDsonfrontofunitprovidediagnosticinformation.•IncludesQSlinkforseamlessintegrationoflights

and controls.

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 2 01.09.17

Specifications

Power

•220–240V~50/60Hz

•10Amaximumtotalinputcurrent

•LightningstrikeprotectionmeetsANSI/IEEEstandard62.31-1980.Canwithstandvoltagesurgesofupto 6000Vandcurrentsurgesofupto3000A.

•24V-132mA,4PDUssupplied

Regulatory Approvals

•IEC/EN60669-2-1•CEmarked•LutronQualitySystemsregisteredtoISO9001.2008

Environment

•SeeMountingsectionforthermalspecifications•Relativehumidity:lessthan90%non-condensing•Forindooruseonly

Output Zone Ratings

•No Deratingisrequiredifalltheconditionsbelowaremet: –Calibrationpointmaximumis70ºC –Roomambienttemperatureisbetween0ºCand30ºC –Panelambienttemperatureisbetween0ºCand50ºC

•100 W Deratingisrequiredonallzonesforasinglemoduleinasinglenon-ventilatedDINenclosureif: – The room ambient temperature is between 30ºCand40ºC.

•200 W Deratingisrequiredonallzonesformultiple rownon-ventilatedDINenclosureif: – The room ambient temperature is between 30ºCand40ºC.

Output Zone Ratings (continued)

•Eachzonehasnominimumloadrequirement.

•Automaticallyselectsleading-edgeortrailing-edgedimmingorcanalsobemanuallyconfiguredforaspecificloadtype.

•Internalrelayprovidesanairgapoffwhenallzonesare off.

•Oneloadtypeperzone.

•Outputmustnotbeusedtocontrolreceptacles.

•Outputmustbedirectlyconnectedtotheload.ContactLutronforapplicationswithloadsidebreakers.

•Runaseparateneutralforeachloadcircuit.Acommonneutral connection is not recommended.

•MaximumwirelengthbetweentheEnergiSavrNodeunitandtheloadmustbelessthan30.5m.

•UnitmaybepoweredbyGroundFaultInterrupter(GFI)orResidualCurrentCircuitBreakerwithOverload(RCBO)protectedcircuitifrequired.Loadcircuitwiring(frombreakertounittoload)mustberuninitsownnon-metallic conduit, or nuisance tripping may occur.

•Forapplicationsrequiring0–10V-control,useTenVoltInterface(GRX-TVI)ortheQSNE-4T10-D.

•Forapplicationsrequiringhigherwattageratings,useapowerbooster(NGRX-PB,NGRX-ELVI,NGRX-FDBI).

Each zone is rated for the following wattage and load types A, B:

Load TypeZone 1 Rating Zone 2, 3 and 4 Rating (per zone)

No Derating 100 W Derating

200 W Derating

No Derating 100 W Derating

200 W Derating

Incandescent/Halogen 800 W 700 W 600W 500 W 400 W 300W

ElectronicLow-Voltage 800 W 700 W 600W 500 W 400 W 300W

MagneticLow-VoltageD 800VA(600WC) 700VA(525WC) 600VA(450WC) 500VA(375WC) 400VA(300WC) 300VA(225WC)

Neon/ColdCathodeD 800VA(600WC) 700VA(525WC) 600VA(450WC) 500VA(375WC) 400VA(300WC) 300VA(225WC) A AdditionalloadtypeoptionsareavailableintheQuantumsoftwaresuite,somemayrequireaninterface.ContactLutronfordetails. B RefertoLutronP/N048478onwww.lutron.comforcompatibilitywithdimmableCFL/LEDlightsources. C Actuallampwattage. D OnlyuseironcoretransformersintendedforusewithanelectronicswitchordimmerperClause8.3ofIEC/EN60669-2-1.

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 3 01.09.17

Specifications (continued)

Terminals (Torque,wiregauge&typeratings)

•Mainswiring:0.6N•m 1.0 mm² to 4.0 mm²

(singlewire,solidorstranded) 1.0 mm² to 1.5 mm² (twowires,solidorstranded)

• Zonewiring: 0.6N•m 1.0 mm² to 4.0 mm²

(singlewire,solidorstranded)• CCIwiring: 0.6N•m

0.5 mm² to 4.0 mm² (singlewire,solidorstranded)

•Multi-function InputWiring: 0.6N•m 0.5 mm² to 1.5 mm²

(singlewire,solidorstranded)• QSLink: 0.6N•m 0.5 mm² to 4.0 mm²

(singlewire,solidorstranded) 0.5 mm² to 1.0 mm²

(twowires,solidorstranded)

Multi-Function Inputs

•Eachmulti-functioninputiscompatiblewithoccupancyanddaylightssensorsaswellasIRreceiversandIECPELV/NECRClass2drycontactswitches.

•DedicatedPowerSupplyOutputforeachinput –20V-50mAmaximumeach. – Anauxiliarysupplyisrequiredifaninput

requiresmorethan50mA.

Wired Occupancy Sensors

•EachoftheinputscanpoweroneLutron occupancy sensor, up to four sensors per unit.

•Lutronoccupancysensorscanbeconfiguredtohaveone of the following modes:

–Occupancy:AutomaticOn,AutomaticOff –Vacancy:ManualOn,AutomaticOff•Eacharea’soccupiedandunoccupiedscenecanbeconfiguredindependently.

•Eachoccupancysensorcancontroloneor morezones.

•Occupancysensormustprovideadrycontact closureorsolid-stateoutput.

•Eachunitmaybecontrolledbyoccupancysensorsconnectedtootherdevices,uptoamaximumof sixteenoccupancysensors.

Wired Infrared (IR) Receivers•EachoftheinputscanpoweroneIRreceiver,upto

four receivers per unit.•UseLutronIRreceiversandcompatibletransmittersforpersonalcontrolofindividuallightingzones.

Wired Daylight Sensors•Eachoftheinputscanpoweronedaylightsensor,up

to four sensors per unit.•Lutrondaylightsensorsallowdaylightharvestingand

can be programmed to affect light output.•UseLutronEC-DIR-WHsensorstocontroloneormorezones.

•Eachzonemaybecontrolledbyamaximumoftwodaylight sensors.

Dry Contact Switches

•MustberatedforIECPELV/NEC®Class2operation.•Canbeconfiguredformomentaryormaintained

operation.•ZonescanbeprogrammedtoanylevelincludingOff.

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 4 01.09.17

Specifications (continued)

Communication with GRAFIK Eye QS

•EnergiSavrNodeQSunitzonescanbeconfiguredtorespondtoGRAFIKEyeQSscenebuttonswhenassociatedwiththeGRAFIKEye QS.

•EnergiSavrNode QSunitzonescanbeconfiguredtorespond to scene commands initiated by the GRAFIKEye QSastronomictimeclockwhenassociatedwiththeGRAFIKEye QS.

•EnergiSavrNodeQSunitoperatesinafterhoursmodewhenassociatedwithaGRAFIKEye QS that is in afterhours mode.

•ZonesontheGRAFIKEye QSmaybeconfiguredtoremotelycontrolzonesontheEnergiSavrNodeQSunit.

Communication with QSE-IO

•EnergiSavrNode QSunitzonescanbeconfigured to respond to scene commands initiated by the QSE-IOinsceneselectionmode.

•EnergiSavrNode QSunitcanbeconfiguredtorespondtozonetoggleoroccupancysensorcommandsinitiatedbytheQSE-IOinscenetogglemode or occupancy sensor mode.

•RefertotheQSE-IOSpecificationSubmittalformoreinformation.

Communication with QSE-CI-NWK-E

•IntegrateEnergiSavrNode QS units with touchscreens,PCs,A/Vsystemsorotherdigitalsystems and devices.

•RefertoLutronIntegrationProtocolguideon www.lutron.com for more information.

QSM (QS Sensor Module): Integrating Wired and Wireless Sensors

•UsetheQSMtointegrateRadioPowrSavr Occupancy/Vacancysensors,RadioPowrSavr Daylightsensors,andPicoWirelessControllerstocontrolzonesontheEnergiSavrNode QS unit.

•Wireupto4wiredinputs(ofanytypelistedbelow)totaltotheQSM –Daylightsensors – Occupancy sensors –Infrared(IR)receivers

•TheRadioPowrSavr sensors and Pico Wireless ControllersassociatedwiththeQSMshouldbemountedwithin18mlineofsight,or9mthroughwalls,oftheQSM.

•RefertoQSMSpecificationSubmittalformore information.

seeTouch QS Wallstation

•seeTouchQSwallstationscanbeconfiguredto: –selectscenes1-16andoff –togglezonesbetweenpresetandoff – set and display partition status – enable/disable panic mode –start/stopsequencing•Inscenemode,wallstationscanbeassignedtoone

or more Energi Savr Node QS units connected to theQSlink.

•Inzonetogglemode,zonebuttonscanbeassigned tooneormorezonesonanyEnergiSavrNodeQSunitconnectedtotheQSlink.

•LEDindicatordisplayssceneorzonestatus.

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 5 01.09.17

Out-of-Box (Default) Functionality

Multi-Function Inputs (Occupancy, Photo, IR Sensors, or Dry Contact Switches)

•Sensorsorswitcheswillhavenoeffectonany ofthezonesuntilset up via unit programming.

seeTouch QS Wallstations

•AllseeTouchQSlightingwallstationsareScene keypadsbydefault.

•Scenes1-16willdimlightstothepresetlevels in the table below:

Scene # Light Level: All Zones1,5-16 100%2 75%3 50%4 25%

•SceneOffwillturnallthelightsOff.

Emergency Contact Closure Input (CCI)

•WhentheCCIisopen,theEnergiSavrNodeQSunitwillenterEmergencyMode,whichwillturnonall loads to their emergency level and disable control oflocalzonesandQSdevices.

•WhentheCCIisclosedorjumpered,EnergiSavrNodeQSunitzoneswillreturntothesettingsorlevelsthey were at prior to entering emergency mode.

Note: Unit will process any sensor events received whileinemergencymodeafteritexitsemergencymode.

Normal Mode Operation

•BydefaulteachzoneissettoanUnassigned/Non-Dimloadtype.Eachzonewillswitchloadonoroffuntilitisconfiguredviaunitprogramming.Once configured,theloadtypecannotbechangedbacktoUnassigned/Non-Dim.

•Zoneandraise/lowerbuttonsontheunitcanbeused to:

– turn loads on and off. – dim loads up and down.•InputandsensorstatusLEDs(‘Occupancy’,‘Photo’,‘IR’,and‘Switch’)verifyconnectionstodrycontact switches and sensors.

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 6 01.09.17

Programming Options

Detailsforeachoptioncanbefoundinthe“ProgrammingOptionsandFeatures”tableonthenextpage.

Manual Programming: •Use buttons on the front of the Energi Savr Node unit.•Use manual programming in installations with only one Energi Savr Node unit and with one QS Sensor Module(QSM)orfewerontheQSlink.

•Seethemanualprogrammingguide(032416)fordetails.

HHD Programming

•RequiresESNProgrammingInterface(QSE-CI-AP-D).•RequiresApple iPod touch or iPhone mobile digital device.•Use the intuitive programming application for the Apple iPod touch or iPhone to program systems with

multiple Energi Savr NodeunitsandQSMsontheQSlink.

•WirelessrouteronlyrequiredforprogrammingwithanApple iPod touch or iPhone.•Wirelessroutermayberemovedfornormaloperation.•EthernetconnectionmaybemadeviaananEnergi Savr NodeProgrammingInterface(QSE-CI-AP-D)

or an Energi Savr NodeunitwithintegralEthernetjack.•Lutron recommends that an Energi Savr NodeProgrammingInterface(orEnergi Savr Node unit with Ethernetjack)bewiredtoanEthernetjackinthespaceforeaseofaccessandproximitytopowerforthewireless router.

•Workswithanystandardwirelessrouterthatsupportsmulticastpackets.•Apple iPod touch or iPhone can program all Energi Savr Node units connected to an Energi Savr Node ProgrammingInterfaceviatheQSLink(exceptwhenpartofaQuantumsystem).

•Energi SavrappisrequiredandisavailablefromtheApple AppStoreonlinemarketplace.

Quantum Programming

•Programming is achieved using the Quantum software suite.•Requiresa Quantum Processor.

*Note:EnergiSavrNodeunitsarenotdesignedtoexistonanopennetwork. Connectiontoanopennetworkcouldresultinreducedperformanceand Ethernet connectivity issues.

QSLink

Energi Savr Node unit

QSM

DedicatedEthernet Connectionfor

Energi Savr Node units*

Apple iPod touch or iPhone

mobile digital deviceWireless

Router (byothers)

Energi Savr Node Programming

InterfaceQSE-CI-AP-D

Wire types:1 Lessthan153m:Lutroncable

GRX-CBL-346S 153mto610m:Lutroncable GRX-CBL-46L

2 StandardCAT5/CAT5Ecable:Totallengthnottoexceed100m

1 1

22

Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.AppStoreisaservicemarkofAppleInc.

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 7 01.09.17

Programming Options and Features

Manual Programming

HHD Programming:• Requires ESN Programming Interface

QSE-CI-AP-D• Requires Apple iPod touch or iPhone mobile

digital device

Energi Savr Node units (ESNs) Connected to QS Link

Not more than 1 Multiple: 100 QS devices and 100 zone limits apply

QS Sensor Modules (QSMs) Connected to QS link

Not more than 1 Multiple: 100 QS devices limit applies

Wired Occupancy SensorsSystem Limits 2 connected directly to ESN unit

Up to 4 wired to QSMUp to 100 total occupancy sensors per QS link (wired + wireless)

Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link

Occupancy Dependency and Grouping Supported

No Yes

Wireless Occupancy Sensors

System Limits Associate 10 occupancy sensors to QSM to control zones on the ESN unit

Up to 100 total occupancy sensors per QS link (wired + wireless)

Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link

Occupancy Dependency and Grouping Supported

No Yes

Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.

Continued on next page…

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 8 01.09.17

Programming Options and Features (continued)

Manual Programming

HHD Programming:• Requires ESN Programming Interface

QSE-CI-AP-D• Requires Apple iPod touch or iPhone mobile

digital device

Wired Daylight SensorsSystem Limits Maximum of 1 daylight sensor per zone

2 connect directly to the ESN unit Additional daylight sensors can connect to the QSM

Maximum of 2 daylight sensors per zone Up to 100 total daylight sensors per QS link (wired + wireless)

Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link

Disable daylighting in Scenes No Yes

Wireless Daylight SensorsSystem Limits Maximum of 1 daylight sensor per zone

Associate wireless daylight sensors to the QSM

Maximum of 2 daylight sensors per zone Associate up to 10 wireless daylight sensors per QSM Up to 100 total daylight sensors per QS link (wired + wireless)

Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link

Disable daylighting in Scenes No Yes

Pico Wireless ControllersCan be assigned to… Any zone on the local ESN unit Any number of zones or areas on ESN units on same

QS link

IR Receivers and WallstationsSystem Limits 2 connect directly to the ESN unit

Up to 4 wired to the QSMUp to 100 total controls per QS link (wired wallstations, IR receivers)

Can be assigned to… Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on same QS link

Emergency Contact Closure InputCan be assigned to… Any zone(s) on the ESN unit Any or all local ESN unit zones

Emergency Light level Configurable Configurable

Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.

Continued on next page…

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 9 01.09.17

Programming Options and Features (continued)

Manual Programming

HHD Programming:• Requires ESN Programming Interface

QSE-CI-AP-D• Requires Apple iPod touch or iPhone mobile

digital device

seeTouch QS wallstationsScene Keypads assigned to… Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link

Scene + off keypads assigned to…

Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link

Zone toggle keypad buttons assigned to…

Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link

Change Keypad to Scene or Zone

Yes Yes

Changing keypads to shade, panic, fine tune

No Yes

Zone Configuration ParametersLoad type Auto, ELV, MLV Auto, ELV, MLV

High-end trim Adjustable Adjustable

Low-end trim Adjustable Adjustable

Absolute minimum level Adjustable Adjustable

ScenesAvailable scenes Scenes 1-16 and off Scenes 1-16 and off

GRAFIK EyeR QS Follow GRAFIK Eye QS scenes, timeclock events, and/or afterhours events

Follow GRAFIK Eye QS scenes, timeclock events, and/or afterhours events

QSE-IO Scene, zone toggle, occupancy Scene, zone toggle, occupancy

QSE-CI-NWK-E Yes Yes

Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 10 01.09.17

Mounting

•SeeLutronP/N048466atwww.lutron.comformore information on mounting and installation in panels with integratedDINrail.

•MountinIP20(minimum)ratedconsumerpanelorbreaker panelwithintegratedDINrail.

•Unitis12DINmodules(216mm)wide.•Mountunitinorientationshown.•Unitmaybemountedbyunlockingthefourmountingclipsonthebackoftheunit.ClipsmustbelockedonceunitissecurelyattachedtotheDINrail.

•Mountinanaccessibleandserviceablelocation.•Unitgeneratesheat,maximum75BTUs/Hour•Mountunitsuchthatalltheconditionsbelowaremet: –Roomambienttemperatureisbetween0ºCand30ºC –Temperatureinsidemountingpanel,within20mmofunit,

isbetween0ºCand50ºC –Calibrationpointmaximum:70ºC

Unlocked

4 mounting clips on unit

Locked

H

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

Mechanical DimensionsFront View

H

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

90m

m

216mm

Left Side View

Calibration point

90m

m

55 mm70 mm

76mm

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 11 01.09.17

Overview of Wiring Terminals

QS Link

Mains Input

Load Neutrals

EmergencyContact Closure

Input

QSNE-4A-D

Phase Adaptive Outputs

H

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

Mains Wiring

Multi-Function Inputs

Zone 1

Zone 4

Zone 2

Zone 3

L L N N N N N DL1 DL2 DL3 DL4

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 12 01.09.17

QSNE-4A-D

Wiring Verification

•Unitshipswithbypassconnectorpre-installedforloadwiringverification.Bypassconnectorisusedtoapplypower to loads to identify any load or wiring faults prior to wiring loads to unit.

•Loadwiringmustbeverifiedbeforewiringloadstounit.

H

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

L N N N N N DL1 DL2 DL3 DL4

a

b

c

Neutral

Line/Hot

Earth

•Toverifywiring: 1. Turn off power. 2.Wireloadstoprovidedconnector. 3.Applypower,ensurethedesiredloadsare

powered and properly wired. 4.TurnoffpowerandwireloadstoDLterminals

on unit.

L

Distribution Panel

(220–240 V~)

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 13 01.09.17

Wiring from Distribution to Energi Savr NodeT QS unit

•TurnoffallcircuitbreakersorisolatorsfeedingtheEnergi Savr Node QS unit at distribution panel.

•Runline/hot,neutral,andearth wires froma220–240V~50/60Hzfeedtothe Energi Savr Node QS unit.

•Runaseparateneutralforeachloadcircuit.A common neutral connection is not recommended.

Mains Wiring and IEC PELV Separation

•Followappropriatelocalandnationalcodestoavoidviolatingrequiredseparationguidelines.

Dim Line/Hot (220–240 V~)

Neutral

H

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

Zone 1 Example

Mains Voltage Wiring

H

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

L N N N N N DL1 DL2 DL3 DL4

Load

Earth

Neutral

Line/HotDistribution

Panel(220–240 V~)

L

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 14 01.09.17

IEC PELV Emergency Contact Closure Input

•ContactClosureInput(CCI)wiringis IECPELV/NECClass2.Followallapplicable national and local codes for proper circuit separation and protection.

•Turnoffallbreakersorisolatorsfeedingthe Energi Savr Node QS unit at distribution panel be-fore servicing unit.

•TheCCIisalocalcontrolonlyandcannotcontrolotherEnergiSavrNodeQSunitsovertheQSlink.Amaximumof32EnergiSavrNodeQSunitsmaybeconnectedinparalleltoanEmergencyorManualoverride device if the event is intended to affect multiple devices.

•Wheninemergencymode,allzoneoutputswill be at their programmed emergency light level (configurableforeachzone,defaultis100%). Allsensorsandcontrolsarelockedout.

•Emergencycontactclosureinputisnormallyclosed(NC).TheEnergiSavrNode QS unit is shipped with ajumperpre-installed.

Note: The Energi Savr Node QS unit will default to EmergencyModeiftheCCIisleftopen.IfnoEmergency ContactClosureInputisrequired,pleaseleavethewire jumperintheCCIterminals.

H

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

H

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

CCICommon

Wiring: Emergency Contact Closure Input

CCI COM

Note: Shown with pre-installedjumper.

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 15 01.09.17

Wiring: QS LinkQS Link IEC PELV Wiring

•LinkcommunicatesusingIECPELV/NEC® Class2wiring.

•TurnoffallbreakersorisolatorsfeedingtheEnergiSavrNode QS unit at distribution panel before servicing unit.

•Followallapplicablenationalandlocalcodesforproper circuit separation and protection.

•Wiringmaybedaisychainedort-tapped.•TotallengthofQSlinkmustnotexceed600m.•Forlengthsunder150m,use1.0mm2 or larger conductorsforcontrolpower(24V-,COM).

•Forlengthsover150m,use4.0mm2 conductorsforcontrolpower(24V-,COM).

•Useone,twisted-shieldedpairof1.0mm2 conductorsfordatalink(MUX,_).

•Terminal2(+24V-)shouldNEVERbeconnected betweendevicesthatsupplyPDUs.

•See“PowerDrawUnitsontheQSLink” (LutronP/N369405)onwww.lutron.comfor QSlinklimitsandPDUcounts.

H

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

H

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

(1) COM

(2) 24 V-

(3) MUX

(4) MUX

Energi Savr Node QS

Energi Savr Node QS

seeTouch QS wallstations

seeTouch QS wallstations

QSE-IO or QSE-CI-NWK-E

QSE-IO or QSE-CI-NWK-E

Daisy-Chain Wiring Example

T-Tap Wiring Example

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr Node QS QSNE-4A-D Phase Adaptive Fixture Controller

369609f 16 01.09.17

Wiring: IEC PELV Multi-Function InputsWiring Instructions:

•AllinputwiringisIECPELV/NEC®Class2.Followallapplicable national and local codes for proper circuit separation and protection.

•Inputterminalsaccept0.5mm2 to 1.5 mm2 solid or stranded conductors.

•MainsvoltageandIECPELV/NEC®Class2wiringmustbekeptseparate.

•Note: One device per input.•TurnoffallbreakersorisolatorsfeedingtheEnergiSavr

Node QS unit at distribution panel before servicing unit.

Daylight Sensor:•Connectthefourconductorstothefourterminals

as shown. Red=20V- White=IR* Black=Common Yellow=Daylight•MaximumwirelengthbetweentheDaylightSensor

and the Energi Savr Node QS unit must be less than 46m.

•Onedaylightsensorcanbewiredtoeachinput.

•Consultthedaylightsensorspecificationsheettoproperlyinstall sensor.

•Donotplacethesensorabovependants,fixtures, directlybelowlightingfixtures,orwithinskylightwells.

Occupancy Sensor:•Connectthreeconductorstothreeterminalsasshown.•Oneoccupancysensorcanbewiredtoeachinput.•Maximumwirelengthbetweenthesensorandthe

Energi Savr Node QSunitmustbelessthan46m. Note:Ifsensorhasanautomaticsensitivityorthresholdadjustment,Lutronrecommendsdisablingit.

IR Receiver:•Connectthethreeconductorstothethreeterminalsasshown.•Maximumwirelengthbetweenthereceiverandthe

Energi Savr Node QSunitmustbelessthan46m.•OneIRreceivercanbewiredtoeachinput.

Dry Contact Switch:•Connectoneconductortocommonandtheothertoinput(notshown).

•Maximumwirelengthbetweentheswitchandthe EnergiSavrNodeQSunitmustbelessthan46m.

H

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

* Note:DaylightsensorwithIRmayrequiretwoinputs.OnlyoneIRdevicemaybeconnectedperinput.IftheIRsignalfromadaylightsensor is connected, another control may not beconnectedtothesameinput.IfIRisnotbeing used, leave white wire disconnected.

** Note:Connectthegraywireon-ROccupancySensor models.

+ Note:SensorCommonsareinternallyshorted.

Sensor 1+20V Input

Sensor2+20V Input

Sensor3+20V Input

Com

mon

+

Com

mon

+

Sensor 4+20V Input

H

M

L

QSNE

-4A-D

DIN

Rai

l Pow

er M

odul

e

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

InputS1 S2 S3 S4 CCI

SwitchOccPhotoIR

Type

500 W Max 800 W Max 500 W Max 500 W Max

Zone 2Zone 1 Zone 3 Zone 4

Input

Hi Temp

Prog

Power

Opt1

Opt2

Opt3

DefOption

IR Transmitter

LUTR

ON

R

IR Transmitter

LUTR

ON

R

Daylight Sensor (IR)

Red

Blac

k

Yello

w

Whi

te*

Occupancy Sensor

Red

Blac

k

Blue

/Gra

y**

IR Receiver

Blac

kW

hite

Red

LUTRON

LUTRONR

Example Sensor Setup

)Lutron,Lutron,Quantum,RTISSEquipped,SeeTouch,Pico,andGRAFIKEyeareregisteredtrademarksofLutronElectronicsCo.,Inc.registeredintheU.S.andother countries.

EnergiSavrNode,RTISS-TE,andRadioPowrSavraretrademarksofLutronElectronicsCo.,Inc.