ELECTRONIC I MPSeng_rev. 05 September 09 Diaphragm Valves Via per Cinise Phone ++39 0362 0 SEQUENCER with P C Model “MPS” Instruction Manual MECAIR S.r.l. s and Electronic Controls for Dust Collecto ello 97 – 20054 Nova Milanese – Milano – It 2 3751, Fax ++39 0362 367279 http:www.me CONTROL or Filters taly ecair.it

Upload: phamminh

Post on 22-Aug-2018

236 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

ELECTRONIC SEQUENCER with

Instruction Manual MPSeng_rev. 05 September 09

Diaphragm Valves and Electronic Controls for Dust Collector FiltersVia per Cinisello 97

Phone ++39 0362 3751, Fax ++39 0362 367279

0

ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROLModel “MPS”

Instruction Manual

MECAIR S.r.l. Diaphragm Valves and Electronic Controls for Dust Collector Filters

Via per Cinisello 97 – 20054 Nova Milanese – Milano – ItalyPhone ++39 0362 3751, Fax ++39 0362 367279 http:www.mecair.it

P CONTROL

Diaphragm Valves and Electronic Controls for Dust Collector Filters Italy

http:www.mecair.it

Page 2: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

1

ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL Model “MPS”

Instructions for use

INDEX 1. FEATURES Pag. 2 2. TECHNICAL CHARACTERISTICS Pag. 2 3. INSTALLATION GUIDELINES Pag. 3 4. PRELIMINARY CHECK Pag. 3 5. ELECTRICAL CONNECTIONS Pag. 4 6.

6.1 6.2 6.3

FILTERED PRESSURE TAPS INSTALLATION CONNECTION TECHNICAL DRAWING

Pag. 4 Pag. 4 Pag. 4 Pag. 5

7. 7.1 7.2

START UP VOLTAGES SELECTION PARAMETERS SELECTION

Pag. 6 Pag. 6 Pag. 7

8. SHUT DOWN CLEANING Pag. 9 9. PRECOATING FUNCTION Pag. 9 10. REMOTE Pag. 10 11. DELTA-P / VALVES SELECT BUTTON Pag. 10 12. HOUR COUNTER Pag. 10 13. ZERO kPa ADJUSTMENT Pag. 10 14.

14.1 14.2

REMOTE TRANSMISSION of the ∆P VALUE (option) 4 ÷ 20 mA ACTIVE OUTPUT 4 ÷ 20 mA PASSIVE OUTPUT

Pag. 11 Pag. 11 Pag. 11

15. DISPLAY MESSAGE Pag. 12 16. TROUBLESHOOTING Pag. 12 17. FUSES Pag. 12 18. LEGEND Pag. 13 19. MPS 4-16 GENERAL ASSEMBLY Pag. 14 20. MPS 4-16 FRONT PANEL Pag. 15

CAUTION: before operating the product, read this sheet thoroughly to acquire sufficient knowledge of the product. For your convenience, keep this sheet for your disposal.

Page 3: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

2

1. FEATURES

The Model “MPS” has been designed to guarantee the control of diaphragm valves mounted on pulse jet dust collector filters containing filter bags or cartridges. MPS main features include: – Operates in MANUAL or AUTOMATIC mode – Automatic start up of cleaning cycle according to set ∆P – SHUT DOWN CLEANING with selectable number of cleaning cycles – PRECOATING function for new filters or filters equipped with new filtering elements – REMOTE function – ALARM contact enabling connection to external alarms – HOUR COUNTER – ∆P value playback (option)

2. TECHNICAL CHARACTERISTICS

ENCLOSURE ABS grey – transparent cover PROTECTION RATING IP65

DIMENSIONS MPS 4 / 8 / 12 / 16 outlets: box 213 × 185 × 113 mm WEIGHT Approx. 2 kg circa for all models

CONNECTIONS Terminal blocks – max.section 2.5 mm²

TEMPERATURE Storage: -20°C/+80°C. Operation: -10°C/+50°C, with duty cycle 30%.

VOLTAGES AVAILABLE

CODE INPUT OUTPUT P1 230 V (±10%) − 50/60 Hz 230 V − 50/60 Hz P2 230 V (±10%) − 50/60 Hz 115 V − 50/60 Hz P3 115 V (±10%) − 50/60 Hz 115 V − 50/60 Hz P4 230 V (±10%) − 50/60 Hz 24 V − 50/60 Hz

P4D 230 V (±10%) − 50/60 Hz 24 V DC P5 115 V (±10%) − 50/60 Hz 24 V − 50/60 Hz

P5D 115 V (±10%) − 50/60 Hz 24 V DC P6 24 V (±10%) − 50/60 Hz 24 V − 50/60 Hz

P6D 24 V (±10%) − 50/60 Hz 24 V DC ABSORBED POWER Without outlet: 2,5 VA. Outlet: 25 VA – 20 W

RELAY 250 V AC 2 A MAIN FUSE 500 mA delayed 115/230 V; 2 A delayed 24/48 V. PULSE TIME 0,01 ÷ 9,99 sec. PAUSE TIME 1 ÷ 999 sec.

PAUSE TIME IN AUTOMATIC 1 ÷ 999 sec. OPERATING ∆P 0,01 ÷ 3,00 kPa

MAX DUTY CYCLE 30% MAX INLET PRESSURE 75KPa

SET ALARM ∆P 0,01 ÷ 3,00 kPa SHUT DOWN CLEANING 0 ÷ 99 cycles

REMOTE CONTROL To be operated from a non-powered external contact (normally open). ∆P PRECOATING 0,01 ÷ 3,00 kPa HOUR COUNTER 0 ÷ 65,999 hour

WEEE

The device should be disposed of in accordance with current European regulations

Page 4: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

3. INSTALLATION GUIDELINES

• Do not expose the unit to direct sunlight in order to avoid overheating of the circuit board.• Connect unit to a continually powered line to allow SHUT

and to have maximum precision in the • Protect unit from rain, water infiltrat

infiltration which can seriously damage the circuit board.• The initial length of conduit which holds the electric cables which run to the

upwards or interrupted before thunit.

• Avoid cables to enter via the upper part of the • Avoid installing any electronic devices on vibrating structures• Use only cable gland with protection grade IP65 and of proper

• A disconnecting switch has to be installed on the power line before the • Do not attempt to repair unit• All wiring should be carried out by a qualified electrician to avoid risk of fire and electrical shocks • unit wiring has to be performed in order to separate the different types of cables,

contact, valve output , 4-20ma output) and in ord• Before opening the unit , be sure that ,

clamps (4) disconnected , including connection to alarm / signal relays .• All unit electrical connections , including solenoi

the other loads . • Voltage selectors jumpers have o be positioned only by skilled personnel and following the

instructions. • A wrong Voltage selectors jumpers positioning may cause potential danger to the pe

4. PRELIMINARY CHECK

1) Check that the MPS unit does not have power (on/off switch [19] on disconnected).

2) Make sure that the power supply indicated by the yellow label [16] as “INGRESSOcorresponds to the available power supply. (Voltage and frequency)

3) Make sure that power supply to valves indicated by the yellow label [16] as “USCITAcorresponds to the voltage/freq as indicated on the coils.

3

INSTALLATION GUIDELINES

to direct sunlight in order to avoid overheating of the circuit board.to a continually powered line to allow SHUT-DOWN CLEANING when the fan stops

and to have maximum precision in the ∆P measurements. from rain, water infiltration and humidity. Incomplete closing of the cover may cause

infiltration which can seriously damage the circuit board. The initial length of conduit which holds the electric cables which run to the upwards or interrupted before the appliance. This will stop any water or condensate entering the

Avoid cables to enter via the upper part of the unit.box. Avoid installing any electronic devices on vibrating structures

nly cable gland with protection grade IP65 and of proper size ( according to the cable used )

A disconnecting switch has to be installed on the power line before the unit unit – contact MECAIR!

All wiring should be carried out by a qualified electrician to avoid risk of fire and electrical shocks wiring has to be performed in order to separate the different types of cables,

20ma output) and in order not to pass close to the PCB.Before opening the unit , be sure that ,unit is switched off (switch on/off (1) on 0clamps (4) disconnected , including connection to alarm / signal relays .

electrical connections , including solenoid valves have to use separate paths in

Voltage selectors jumpers have o be positioned only by skilled personnel and following the

A wrong Voltage selectors jumpers positioning may cause potential danger to the pe

Check that the MPS unit does not have power (on/off switch [19] on 0 and terminals [15]

Make sure that the power supply indicated by the yellow label [16] as “INGRESSOto the available power supply. (Voltage and frequency)

Make sure that power supply to valves indicated by the yellow label [16] as “USCITAcorresponds to the voltage/freq as indicated on the coils.

to direct sunlight in order to avoid overheating of the circuit board. DOWN CLEANING when the fan stops

Incomplete closing of the cover may cause

The initial length of conduit which holds the electric cables which run to the unit, should be turned condensate entering the

( according to the cable used )

All wiring should be carried out by a qualified electrician to avoid risk of fire and electrical shocks wiring has to be performed in order to separate the different types of cables, ( power , relay’s

er not to pass close to the PCB. is switched off (switch on/off (1) on 0 and wires on

d valves have to use separate paths in respect to

Voltage selectors jumpers have o be positioned only by skilled personnel and following the

A wrong Voltage selectors jumpers positioning may cause potential danger to the personnel safety .

and terminals [15]

Make sure that the power supply indicated by the yellow label [16] as “INGRESSO-IN”,

Make sure that power supply to valves indicated by the yellow label [16] as “USCITA-OUT”,

Page 5: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

4

5. ELECTRICAL CONNECTION

1) Check that the MPS unit does not have power (on/off switch [19] on 0). 2) Unscrew and open the top cover, which contain the terminal blocks [20] (Check that the terminal

blocks [15] are disconnected). 3) Extract the removable terminals [14]. 4) Make sure that power supply to valves indicated by the yellow label [16] as “USCITA-OUT”,

corresponds to the power supply indicated on the coils. 5) Connect the valves to the terminal blocks [14], between terminal C and the numbered outlets.

· Earthing [11] of the valves is necessary when outlet voltage is ≥ 48V. · Never connect the Common or valve outlets to Ground. [11]. · The Commons are interconnected on the printed circuit board. · The outlets are “static” type, with a “zero crossing” command, to prevent electrical disturbances.

6) Check that the valve connections are correct and isolated in regard to ground, by measuring the isolation between Ground [11] and Common with outlets terminal.

7) Close the container replacing the lid and screws. [20].

6. FILTERED PRESSURE TAPS

Differential pressure inside the filter is detected by an internal pressure sensor located within the MPS, and which is connected to the filter by means of two filtered taps. Filter taps are designed to prevent the dust clogging the silicon tubes, which connect the filter to the MPS sensor.

6.1 INSTALLATION

When the fan is located downstream from the filter, we need to install one filtered tap in the clean air plenum and the other on the dust laden air plenum. In case of pressurised filters it is sufficient to install only one filtered tap on the dust laden air plenum. Please refer to drawing 1 page 5 for the installation of filtered taps. 1) Drill the 4 fixing holes of the filtered taps over the filter wall (∅ 3,75 mm., inter-axis 39 mm.). 2) In the centre of the 4 fixing holes, drill 3 to 5 pressure interception holes (∅ 4 mm) inside a circular

area of 20mm. (In alternative drill just one hole ∅ 20 mm.).

3) Fix the rubber seal with abundant silicon. 4) Position the filtered taps with their tube connections upward. 5) Fix the filtered taps with self-threading screws (∅ 4,25 mm.).

6.2 CONNECTION 1) Make sure that MPS does not have power (on/off switch [19] on 0 and terminals [15] disconnected). 2) Connect the tubes of the filtered taps to the pressure ports of MPS. The tube from the clean air

plenum needs to be connected to the inlet indicated with “-“ port while the tube from the dirty air plenum is connected to the inlet indicated with the “+” port.

N.B.: – Fix the filter taps in a position that will prevent condensation and or deposits accumulating. – The two connecting tubes (∅ 6/4) between the filtered taps and the inlet, should be positioned

in an upward oriented position. This will eliminate the possibility of water particles, caused by condensation, in entering the piping. In case of humid filtration process it is advisable to install a condensate drainage valve for each tube before the MPS pressure ports.

– When the filtered taps are correctly installed and connected to the pressure ports the display [10] will show positive ∆P values. Should the display show P---, it means that connections between the filter taps and the pressure ports have been inverted. If the problem persists: • Disconnect the pressure tubes. • Adjust the zero pressure trimmer [25] in order to bring the display back to 0 kPa. • Reconnect the pressure tubes to the filtered taps and the pressure ports.

Page 6: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

5

6.3 TECHNICAL DRAWING

Silicon the seal well before joining the parts

Wad

4 fixing holes Ø 3,75

Self-tapping screws Ø 4,25

Filter Wall filtro

50

50 25

25 45

39

39

Seal

Pressure Holes (3÷5 Ø 4 central) Otherwise 1 hole Ø 20

Ø 20

Positioned Upward

Fan

Dusty Air Inlet

Pressure +

Pressure Tap -

MPS – +

Condesation outlets for humid processes

Bag Filter

Filtered air

Page 7: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

7. START UP

7.1 VOLTAGE SELECTION

Make sure that MPS does not have power (on/off switch [19] on Check: 1) That the value of power supply, indicated by the yellow label [16] as INGRESSO

corresponds to the available power supply (voltage / freq) 2) That power supply to the valves, indicated by the yellow label [16] as USCITA

corresponds to the voltage / freq. indicated on the coils. If the two above conditions correspond go to paragraph 7.2.

If not please follow the procedure below! A) Power supply selection: 1) Unscrew the two screws [18] and open the MPS transparent cover. 2) Remove the 4 screws of the green panel. Lift the green panel (without taking it away!).

3) Check that power supply selected with jumper power supply available.

4) Should the two voltages be different, replace jumper [23] in order to select the supply required.

5) Go to section B. B) Selection of power supply to the

1) Check that outlet power supply to the valves, selectable with jumpers [22] and [22A], correspond to power supply indicated on the coils of the valves.Jumper [22]: 1HV=110V 2HV=220V LV=24V Jumper [22A]: HV=110/220V LV=24V

2) Should the voltages be different, replace the two jumpers [22] and [22A] in order to select the same power supply indicated on the coils.Jumper [22]: 1HV=110V 2HV=220V LV=24V Jumper [22A]: HV=110/220V LV=24V • CAUTION: both jumpers [

3) Go to section C). C) Selection of the power supply frequency to the valves (AC/DC):

1) Make sure that outlet frequency to the valves, selected by jumper [24], corresponds to the value

indicated on the coils.

2) Should the two frequencies be different, replace jumper [24] in order to select the indicated on the coils.

3) Replace the green panel with its 4 screws. 4) Close the transparent cover by means of the two screws [18].

Never select 230V / DC for the outlets!

6

VOLTAGE SELECTION

Make sure that MPS does not have power (on/off switch [19] on 0 and terminals [15] disconnected).

That the value of power supply, indicated by the yellow label [16] as INGRESSOcorresponds to the available power supply (voltage / freq) That power supply to the valves, indicated by the yellow label [16] as USCITAcorresponds to the voltage / freq. indicated on the coils.

If the two above conditions correspond go to paragraph 7.2. If not please follow the procedure below!

Unscrew the two screws [18] and open the MPS transparent cover.

Remove the 4 screws of the green panel. Lift the green panel (without taking it away!).

Check that power supply selected with jumper [23] corresponds to the one available from the power supply available.

Should the two voltages be different, replace jumper [23] in order to select the

Selection of power supply to the valves:

Check that outlet power supply to the valves, selectable with jumpers [22] and [22A], correspond to power supply indicated on the coils of the valves. Jumper [22]: 1HV=110V 2HV=220V LV=24V Jumper [22A]: HV=110/220V LV=24V

Should the voltages be different, replace the two jumpers [22] and [22A] in order to select the power supply indicated on the coils.

Jumper [22]: 1HV=110V 2HV=220V LV=24V Jumper [22A]: HV=110/220V LV=24V

CAUTION: both jumpers [22] and [22A] must correspond to the same

Selection of the power supply frequency to the valves (AC/DC):

Make sure that outlet frequency to the valves, selected by jumper [24], corresponds to the value

Should the two frequencies be different, replace jumper [24] in order to select the

Replace the green panel with its 4 screws.

Close the transparent cover by means of the two screws [18].

CAUTION! Never select 230V / DC for the outlets!

and terminals [15] disconnected).

That the value of power supply, indicated by the yellow label [16] as INGRESSO-IN,

That power supply to the valves, indicated by the yellow label [16] as USCITA-OUT,

Remove the 4 screws of the green panel. Lift the green panel (without taking it away!).

[23] corresponds to the one available from the

Should the two voltages be different, replace jumper [23] in order to select the same power

Check that outlet power supply to the valves, selectable with jumpers [22] and [22A],

Should the voltages be different, replace the two jumpers [22] and [22A] in order to select the

voltage!

Make sure that outlet frequency to the valves, selected by jumper [24], corresponds to the value

Should the two frequencies be different, replace jumper [24] in order to select the same freq.

Page 8: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

7

7.2 PARAMETERS SELECTION

Connecting the power supply [15]: a) When 230 V (L = phase, N = neutral) b) When 110 V (L = phase, N = neutral) c) When power supply from auxiliary transformers ,it is

mandatory to earth one of the 2 terminals of the secondary and to connect it to N [15].

Switch on/off [19] on 1. The display [10] will indicate for 3 seconds the release code of the MPS.

Once the code disappears display [10] will show letter P followed by the ∆P value of the filter. LED OK [6] is on: - so LED AUTO [3] if MPS is in AUTOMATIC mode - or LED PAUSE [1] if MPS is in MANUAL mode

Caution! Display [10] must show a ∆P value of “0” kPa when the fan is switched off. Otherwise adjust the zero ∆P as indicated on page 10 in paragraph 13.

1) Press SELECT MENU [7]: 1 will flash on display [10]:

Using keys +/– [8] select MANUAL or AUTOMATIC mode. (0 = for MANUAL; 1 = for AUTOMATIC).

2) Press SELECT MENU [7]: 2 will flash on display [10] : Using keys +/– [8] select the N° OF VALVES you wish to connect. Example: If you wish to connect 6 valves to MPS, select 6. Should you skip this step of the MENU, MPS will automatically set no. of valves as if they were connected (if your model is MPS8),then 8 valves will be recognised, (if your model is MPS16), then 16 valves will be recognised.

3) Press SELECT MENU [7]: 3 will flash on display [10]: Using keys +/– [8] select PULSE TIME. (0,01 ÷ 9,99s)

4) Press SELECT MENU [7]: 4 will flash on display [10]: Using keys +/– [8] select PAUSE TIME in MANUAL mode . (1 ÷ 999s)

CAUTION! If you have selected AUTOMATIC at step 1) of the MENU, you have to select PAUSE TIME in SHUT DOWN CLEANING .

5) Press SELECT MENU [7]: 5 will flash on display [10]: Using keys +/– [8] select PAUSE TIME in AUTOMATIC mode . (1 ÷ 999s)

CAUTION! Skip this step if you have selected MANUAL at step 1) 6) Press SELECT MENU [7]: 6 will flash on display [10]:

Using keys +/– [8] select OPERATING ∆∆∆∆P. (0.01 – 3,00KPa) Each time the ∆P of the filter exceeds the OPERATING ∆∆∆∆P, filter cleaning will commence. As soon as ∆P of the filter < OPERATING ∆∆∆∆P, (with difference of -0,05 KpA)filter cleaning will be interrupted.

7) Press SELECT MENU [7]: 7 will flash on display [10]: Using keys +/– [8] select DELTA-P ALARM . (0.01 – 3,00 KPa) If DELTA-P ALARM value is reached in the filter, MPS gives the alarm. Display shows “PP1”. It is possible to have remote signalling if you connect relay’s terminals C and NC [13].

Page 9: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

8

8) Press SELECT MENU [7]: 8 will flash on display [10]: Using keys +/– [8] select N° OF CYCLES of SHUT DOWN CLEANING .(0 ÷ 99). (Select 0 if you do not wish to have shut down cleaning). Shut down cleaning starts automatically when ∆P of the filter goes below 0,10 kPa and FAN contact is open.

– CAUTION! Shut down cleaning will start only when MPS is working in AUTOMATIC mode.

9) Press SELECT MENU [7]: 9 will flash on display [10]: Using keys +/– [8] select ∆∆∆∆P PRECOATING. (0.01 – 3,00KPa) Both in AUTOMATIC and MANUAL mode the cleaning of the filter will start only when ∆P will exceed ∆∆∆∆P PRECOATING, regardless of the value of OPERATING ∆P. This is to allow the filter elements to form a dust cake on their surface.

– Select 0 if you do not wish to use PRECOATING. – Once ∆P PRECOATING is reached and exceeded, this function

will be automatically be excluded and the cleaning cycle will be performed according to the OPERATING ∆P. Please digit a new value of ∆P PRECOATING if you wish to reactivate the function.

– SHUT DOWN CLEANING may start only when ∆P PRECOATING has been previously reached, otherwise SHUT DOWN CLEANING will not start even if the fan is switched off.

10) Press SELECT MENU [7]:C will appear on the left-hand side of the display [10] , followed by a

number of three digits .Using +/- [2] to perform the 4ma tuning. Adjust the numeric value till you can read on an external instruments the correct indication of 4ma.

11) Press SELECT MENU [7]:F will appear on the left-hand side of the display [10] , followed by a number of three digits .Using +/- [2] to perform the 20ma tuning. Adjust the numeric value till you can read on an external instruments the correct indication of 20ma.

12) Press SELECT MENU [7]: letter L will flash on display with the 3 final numbers (from 0 to 999) out of the 5 indicating the total number of hours which the MPS unit has been operating. Ex.: if MPS works for 12,270 hours, display will show L 270.

13) Press SELECT MENU [7]: letter H will flash on display with the 2 initial numbers (from 0 to 65) of the 5 indicating the total number of hours which the MPS unit has been operating. Ex.: if MPS works for 12,270 hours, display will show H 12.

14) Press SELECT MENU [7]: the letters oooo (zero ∆∆∆∆P automatic) will appear on the display [10] Press the + [2] button so that the first digit will flash: P or – followed by three digits Press SELECT MENU [7] to start the economizer NB: Remove the pipes before operating

LED PULSE [2] will indicate that a valve is being pulsed. LED PAUSE [1] will indicate that MPS is waiting to pulse the next valve.

N.B.: – Valves are pulsed from outlet n° 1 onwards. - Check that during the first cleaning cycle every valve is pulsed. – – PAUSE TIME should allow an efficient filter cleaning in the worst conditions, but should

never be shorter than time needed to re-pressurise the header tank! – While selecting parameters (in SELECT MENU), MPS will return functioning if buttons are

not pressed within a 5 minute interval.

Page 10: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

9

8. SHUT DOWN CLEANING

We suggest operating one or more cycles of SHUT DOWN CLEANING at the end of each working session in order to remove the residual dust of the filter. SHUT DOWN CLEANING is started each time ∆P of the filter goes below 0,10 kPa . A free contact of the fan can be connected between clamps F and C .The contact has to be closed when the Fan is on .In this case , the SHUT DOWN CLEANING will not start until the fan will be switched off . The SHUT DOWN CLEANING will start any time the ∆P will go under the value of 0,10 Kpa and the contact is open . CAUTION: • SHUT DOWN CLEANING will start only if MPS is in AUTOMATIC mode! • SHUT DOWN CLEANING will start only if ∆P PRECOATING has already been

exceeded, otherwise SHUT DOWN CLEANING will not start even if the fan is switched off.

In order to activate SHUT DOWN CLEANING:

1) Make sure that MPS is in AUTOMATIC mode. 2) Select the number of cycles in SHUT DOWN CLEANING (see 7.2).

(Select 0 if you do not wish to use SHUT DOWN CLEANING). 3) SHUT DOWN CLEANING starts when ∆P goes below 0,10 kPa, and the Fan contact (between

F and C ) is open. SHUT DOWN CLEANING Led [4] will then flash. SHUT DOWN CLEANING will start from next valve and will consider the existing cycle as the first cycle. filter exceed 0,10 kPa, SHUT DOWN CLEANING will continue till the of cycles is completed.

4) Once SHUT DOWN CLEANING is completed, SHUT DOWN CLEANING led [4] will remain

on.

9. PRECOATING FUNCTION

PRECOATING delays beginning of the filter cleaning cycle in order to allow the filter elements to form a thin dust cake on their surface. CAUTION!: If you select ∆P PRECOATING, cleaning will start only after having reached ∆P

PRECOATING both in AUTOMATIC or MANUAL mode disregarding the OPERATING ∆P value.

In order to activate PRECOATING:

1) Select ∆∆∆∆P PRECOATING as per instructions paragraph 7.2 LED PRECOATING [5] will flash. · If you do not wish to use PRECOATING, select 0 at step 9) of paragraph 7.2. · Selecting ∆P PRECOATING must be between 0 and 3,00 kPa. 2) When ∆P in the filter reaches the ∆P PRECOATING value, the cleaning cycle is initiated and the

PRECOATING function is simultaneously excluded. LED PRECOATING [5] switches off. · If you wish to reactivate this function, select a new value of ∆P PRECOATING.

· SHUT DOWN CLEANING starts only if ∆P PRECOATING has been exceeded, otherwise it will

not start even if the fan is switched off.

Page 11: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

10

10. REMOTE

CAUTION !: MECAIR fit the MPS unit with a bridge on terminals REMOTE and COMMON [12] . If you wish to operate MPS with a remote switch, read instructions below. If you do not wish to take advantage of this opportunity, do not remove the bridge to prevent MPS from going into block mode. MPS going into block mode even though if fuse F1 [26] is burnt.

To activate REMOTE :

1) Unscrew and open the lower panel [20]. 2) Remove the bridge from terminals REMOTE and COMMON [12]. 3) Bring an external no-load and normally open (NO) contact to REMOTE and COMMON

terminals [12] 4) Replace the lower panel fixing the screws [20]. 5) Close the contacts on the REMOTE and COMMON terminals [12] in order to enable the

REMOTE function. 6) Should you open the contact on REMOTE and COMMON terminals [12], MPS will stop

working. Close the contact in order to start cleaning cycle again from the position it stopped.

11. DELTA-P / VALVES SELECT BUTTON

Letter P followed by 3 numbers appear on the display [10] when MPS shows ∆P value in the filter. Press button DELTA-P/VALVES [9] to read the number of the valve that is going to be pulsed and vice versa. The MPS indicates the letter E followed by the number of the valve that is ready to be pulsed. Each time MPS is switched on, display [10] automatically shows the ∆P value in the filter. (Example: If delta-p value is 0,2 KPa, you will read P0.20).

12. HOUR COUNTER

The HOUR COUNTER counts the number of hours that the MPS has been working. Counting starts each time ∆P of the filter exceeds 0,10 kPa. How to read the HOUR COUNTER on display [10]: 1) Press SELECT MENU [7] until display [10] shows L followed by the last 3 numbers (from 0 to 999)

out of the 5 indicating total balance of MPS working hours. Ex.: if MPS has been working for 12,270 hours, display will show L270.

2) Press SELECT MENU [7] until display [10] shows H followed by the first 2 numbers (from 0 to 65) indicating the total number of hours that the MPS has been working. Ex.: if MPS has been working for 12,270 hours, display will show H12.

13. ZERO kPa ADJUSTMENT Press SELECT MENU [7]: the letters oooo (zero ∆∆∆∆P automatic) will appear on the display [10] Press the + [2] button so that the first digit will flash: P or – followed by three digits Press SELECT MENU [7] to start the economizer NB: Remove the pipes before operating

Attention! This step must be operated only after minimum 30 minutes warm up.

Page 12: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

11

14. REMOTE TRANSMISSION OF THE ∆∆∆∆P VALUE (optional) It is possible to transmit the ∆P that is shown on the display of the MSC onto another instrument by means of 4-20ma board [32]. The output signal can be of “active” or “passive” type, please refer to the drawing below explaining , how to chose the type of signal (Active is selected as default at factory ). 14.1 4 ÷÷÷÷ 20 mA ACTIVE OUTPUT No need of external power supply, connect to the terminals [20] the external instruments.

14.2 4 ÷÷÷÷ 20 mA PASSIVE OUTPUT

ATTENTION! In this case the 4 ÷ 20 mA outlet is passive. It needs to be connected to an external power source! 1) Connect the positive (+) terminal of the remote unit to the 4 ÷÷÷÷ 20 mA POS terminal[20] 2) Connect the negative (–) terminal of a STABLE POWER SOURCE (15 ÷ 24 V DC) to the 4 ÷÷÷÷

20 mA NEG terminal[20]. 3) Connect the positive terminal of power supply to the negative terminal of the external

instrument. 5) Use a SHIELDED CABLE to connect it.

Page 13: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

12

15. DISPLAY MESSAGES

PP1: MPS indicates that ALARM ∆P has been exceeded. Stabilize the filter ∆P, press key “-“ [8] to reset the unit. PPP: The maximum value of ∆P in the MPS unit has been exceeded (3,00KPa). Stabilize the filter ∆P, press key “-“ [8] to reset the unit. P---: ∆P value is < 0,50 KPa. In this case check that filtered taps are correctly connected to the pressure ports of MPS as described in paragraph 6.2. Should the problem continue:

���� Disconnect the tubes between filtered taps and pressure ports. ���� Adjust the DP indication to 0 kPa as indicated on page 10,paragraph 13. ���� Connect the tubes between filtered taps and pressure ports.

Sb: the REMOTE contact is open [12].

16. TROUBLESHOOTING

PROBLEM PROBABLE CAUSE SOLUTION

Display is blank and all LED are off.

No power supply. Check the electrical terminals [15]. Check fuse F3 [21]

Display shows Sb

The bridge on terminals remote and common [12] is not connected Check fuse F1 [26]

Check bridge connection Replace the fuse (see chapter 17)

Some valves are ignored by MPS.

Wrong electrical connections between MPS and coils.

Check connections [14].

Coils are interrupted. Check coils continuity.

Display shows the pulsing sequence but valves are not functioning.

The secondary of the transformer is interrupted.

Contact MECAIR

Power circuit is damaged. Contact MECAIR

Power supply to the valves are different from voltages indicated on the coils.

Contact MECAIR

Wrong connections between MPS and coils.

Check connections [14].

LED OK [6] is off. Microprocessor failure. Contact MECAIR 17. FUSES

Name Size Value Type N° on drawing Description

F3 5 x 20 500 mA T [21] 115/230 V Main supply fuse F3 5 x 20 2A T [21] 24/ 48 V Main supply fuse F1 5 x 20 1,6A T [26] Output 24V protection F2 5 x 20 630 mA T [27] + 5V internal power supply

In case of replacement you must respect the above value

Page 14: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

13

18. LEGEND

1) LED PAUSE 2) LED PULSE 3) LED AUTO 4) LED SHUT DOWN CLEANING 5) LED PRECOATING 6) LED OK 7) Push Button SELECT MENU 8) Push Buttons +/– 9) Push Button DELTA P/VALVES 10) Display 11) Valve earthing 12) REMOTE and FAN terminal 13) Relay Terminals 14) Push in valves terminals 15) Power supply terminals 16) Yellow label indicating IN/OUT voltage –freq. 17) Product code and serial number 18) Transparent cover fixing screws 19) On/Off switch 20) Lower Cover 21) Main Fuse 22) Jumper for voltage selection to valves 22A) Jumper for voltage selection to valves 23) Jumper for inlet power supply selection 24) Jumper for outlet power supplies selection (AC/DC). 25) Output clamps for 4-20mA signal. 26) 24V output and Fan – Rem fuse 27) Internal logic supply (+5V) fuse 28) Optional 4-20mA board

Page 15: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

14

19. MPS 4-16 GENERAL ASSEMBLY

PREDISPOSIZIONE

TENSIONE INGR./USC.

VOLTAGE SET IN/OUT

INGRESSO IN USCITA OUT

20

1314 1615

18

19

321 6

7

5 4

26

11

DIFFERENTIAL

INLET

PRESSURE

R

C

Phone ++39 0362 3751 Fax ++39 0362 367279

MECAIR S.r.l. NOVA MILANESE − MILANO − ITALYMPS

Open = stop

Close = runor local jump

Remote : connect to remote start

9

8

10

12

17

22

23

21

24

DC AC AC DC

PRECOATING

SHUT DOWN CLEANING

AUTO

PULSE

0.01 − 2.50 kPa)

SET ALARM DELTA−P (0.01 − 2.50 kPa)

OPERATING DELTA−P (0.01 − 2.50 kPa)

PAUSE TIME IN AUTOMATIC (1 − 999 Sec)

SHUT DOWN (0 − 99 CYCLES)

PAUSE TIME IN MANUAL (1 − 999 Sec)

PULSE TIME (0.01 − 9.99 Sec)

6 =

8 =

7 =

=4

5 =

3

DELTA−P /OK SELECT

MENUADJUST

VALVES

SELECT

Menu

AUTOMATIC = 1 / MANUAL = 0

NUMBER OF VALVES CONNECTED

PULSE TIME (0.01 − 9.99 Sec)

=2

3 =

1 =

27 25

28

Page 16: ELECTRONIC SEQUENCER with ∆∆∆∆P CONTROL … Controllers/MPSeng_rev5.pdf · ELECTRONIC SEQUENCER with Instruction Manual MPSeng_rev. 05 September 09 Diaphragm Valves and Electronic

15

20. MPS 4-16 FRONT PANEL