12 Main Classes Of Power Transformer
SIEMENS – View of the main production hall of the Nuremberg transformer plant.
Transformer Classes //
Transformers are used for a wide variety of purposes, with the complete range of voltage
and power ratings as well as many special features for particular applications.
The following covers the main types:
1. Transformers for electronics
Transformers for electronic circuits or for low-voltage power supplies are used to match the supply
voltage to the operating voltage of components or accessories, or to match the impedance of a
load to a supply in order to maximize power throughput. They may be used to match impedances
in primary and secondary circuits.
The core is usually constructed in low-power transformers from C- and I-laminations or from E-
and I-laminations. The windings are usually of round enamelled wire, and the assembly may be
http://electrical-engineering-portal.com/what-are-the-main-classes-of-transformerhttp://electrical-engineering-portal.com/change-output-voltage-of-transformer-with-tapshttp://electrical-engineering-portal.com/what-are-the-main-classes-of-transformer
-
8/20/2019 12 Main Classes of Power Transformer _ EEP
2/8
varnished or encapsulated in resin for mechanical consolidation and to prevent ingress of
moisture.
Increasing numbers of this type operate at high frequencies in the kilohertz range and use
laminations of special steel often containing cobalt to reduce the iron losses
2. Small transformers
These are used for stationary, portable or hand-held power supply units, as isolating transformers
and for special applications, such as burner ignition, shavers, shower heaters, bells and toys.
They may be used to supply three-phase power up to 40 kVA at frequencies up to 1 MHz. These
transformers are usually air insulated, the smaller units using enamelled windings wires and ring
cores and the larger units using C- and I- or E- and I-laminated cores.
Safety is a major concern for these transformers and they are identified as class I, class II or
class III. Class I units are insulated and protected by an earth terminal. Class II transformers have
double insulation or reinforced insulation. Class III transformers have outputs at Safety Extra-Low
Voltages (SELV) below 50 V ac or 120 V dc.
3. Distribution transformers
These are used to distribute power to domestic or industrial premises. They may be single-
phase or three-phase, pole-mounted or ground-mounted, and they have ratings ranging from 16kVA up to 2500 kVA.
The windings and core are immersed in mineral oil, with natural cooling, and there are two
windings per phase. The primary (high-voltage) winding has a highest voltage ranging from 3.6 kV
to 36 kV; the secondary (low-voltage) winding voltage does not exceed 1.1 kV. The high-voltage
winding is usually provided with off-circuit tappings of ± 2.5 per cent, or + 2 × 2.5 per cent, – 3 ×
2.5 per cent.
The preferred values of rated output are 16, 25, 50, 100, 160, 250, 400, 630, 1000,
1600 and 2500 kVA, and the preferred values of short-circuit impedance are 4 or 6
per cent.
Losses are assigned from lists, for instance from BS 7281-1, or by using a loss–capitalization
formula.
The core and windings of a typical distribution transformer rated at 800 kVA, 11 000/440 areshown in Fig. 1.
http://electrical-engineering-portal.com/short-circuit-currentshttp://electrical-engineering-portal.com/difference-between-power-transformer-and-distribution-transformerhttp://electrical-engineering-portal.com/transformer-losses-standards
-
8/20/2019 12 Main Classes of Power Transformer _ EEP
3/8
Figure 1 – Core and winding of an 800 kVA, 11 000/440 V distribution
transformer
4. Supply transformers
These are used to supply larger industrial premises or distribution substations. Ratings range from
4 MVA to 30 MVA, with primary windings rated up to 66 kV and secondary windings up to 36 kV.
Transformers in this class are fluid cooled. Most supply transformers use mineral oil; but for
applications in residential buildings, oil rigs and some factories, the coolant may be synthetic
esters, silicone fluid or some other fluid with a higher fire point than mineral oil.
5. Transmission (or intertie) transformers
These are among the largest and highest voltage transformers in use. They are used to transmit
-
8/20/2019 12 Main Classes of Power Transformer _ EEP
4/8
power between high-voltage networks. Ratings range from 60 MVA to 1000 MVA and the
windings are rated for the networks which they link, such as 33, 66, 132, 275 and 400 kV in the
UK, or voltages up to 500 kV or 800 kV in other coun-tries.
The impedance of a transmission transformer is usually 18 per cent in the UK, or 8 per cent in
continental Europe, but for some system conditions, an impedance of up to 30 per cent is used.
Figure 2 – Core and windings of a 1000 MVA, 400/275 kV transmission transformer
Transmission transformers are oil filled, and are usually fitted with oil pumps and radiator fans to
assist cooling of the windings and cores. They are usually fitted with OLTCs, but some networks
at 400 kV and 275 kV are linked by transformers without regulating windings.
The core and windings of a three-legged transmission trans-former rated at 1000 MVA and 400
kV/275 kV/11 kV are shown in Fig. 2 .
6. Generator (or step-up) transformers
Power is usually generated in large power stations at typically 18–20 kV, and generator
transformers are used to step up this voltage to the system voltage level. These trans-formers are
usually rated at 400, 500, 630, 800 or 1000 MVA.
Generator transformers are usually fitted with regulating windings and OLTCs.
7. Phase-shifting transformers
-
8/20/2019 12 Main Classes of Power Transformer _ EEP
5/8
Where power is transmitted along two or more parallel transmission lines, the power flow divides
between the lines in inverse proportion to the line impedances. Higher power is therefore
transmitted through the line with lowest impedance and this can result in overload on that line,
when the parallel line is only partly loaded.
Phase-shifting transformers are used to link two parallel lines and to control power
flow by injecting a voltage 90° out of phase (in quadrature) with the system voltage into
one line, at either leading or lagging power factor. Where the transformer controls the
phase angle but not the voltage, the unit is known as a quadrature booster. Where the
voltage is also controlled, the unit is known as a phase-shifting transformer.
Figure 3 shows a 2000 MVA, 400 kV quadrature booster transformer on site; the unit is split
between two tanks in order to meet construction limitations of size and weight.
Figure 3 – 2000 MVA 400 kV quadrature booster transformer in two tanks on site
8. Converter transformers
Where power is transmitted through an HVDC system, a converter station is used to change AC
power to DC using multiple rectifier bridges. Direct current power is converted back to ac using
inverter bridges. Converter transformers handle ac power and power at mixed AC/DC voltages by
combining the power flow through 12 phases of rectifier/inverter bridges through dc valve
windings.
The insulation structure must withstand all normal and abnormal conditions when ac voltage is
mixed with DC voltage of differing polarities over the operating temperature range.
-
8/20/2019 12 Main Classes of Power Transformer _ EEP
6/8
The presence of DC currents may also cause DC saturation of the core, leading to abnormal
magnetizing currents and variations in sound.
Figure 4 – Schematic diagram of ac/dc transmission system
A phase of a three-phase converter transformer bank typically comprises a high-voltage primary
winding and two secondary AC/DC valve windings. Three such transformers together form the two
secondary three-phase systems; one is connected in delta and the other in star. Each secondary
system feeds a six-pulse bridge and the two bridges are connected in series to form a 12-pulse
arrangement, as shown schematically in Figure 4
Two such transformer banks are used with the secondary circuits connected in opposite polarity
to form a ± 215 kV dc transmission system.
9. Railway transformers
-
8/20/2019 12 Main Classes of Power Transformer _ EEP
7/8
Transformers for railway applications may be trackside units to supply power to the track, or on-
board transformers in the locomotive or under the coaches, to power the drive motors.
Trackside transformers are subjected to uneven loading depending upon the posi-tion of the train
in the railway system. On-board transformers are designed for the low-est possible weight,
resulting in a high-loss performance. Modern train control systems using thyristors, GTOs or
IGBTs subject the transformers to severe harmonic currents that require special design
consideration.
10. Rectifier and furnace transformers
Special consideration is needed for transformers in industrial applications involving arc furnaces or
heavy-current dc loads in electrochemical plant.
The primary windings in such cases are usually rated at 33 kV or 132 kV in theUK , but the secondary windings carry many thousands of amperes and are
rated at less than 1 kV .
Current sharing between parallel paths in the transformer becomes important because of the
magnetic fields created by the high currents. These strong magnetic fields can cause excess
heat-ing in magnetic steels if these are used in the structure of the transformer, because of the
flow of proximity currents in the steel. To reduce this excess heating, non-magnetic steel is often
used to form part of the tank or the cover.
The OLTCs in furnace transformers are subject to a heavy duty; they may perform hundreds of
thousands of operating cycles a year, which is more than a lifetime’s duty for many transmission
transformers.
11. Dry-type transformers
A dry-type construction is possible where a higher-temperature class of insulation is required than
is offered by cellulose and a class ‘O’ or class ‘K’ fluid.
Dry-type trans-formers use non-cellulosic solid insulation and the windings may be varnish dipped
to provide a class ‘C’ capability, or vacuum encapsulated in epoxy resin to form a class ‘F’ or
class ‘H’ system. Ratings are generally up to 30 MVA at voltages up to 36 kV, but cast resin
transformers have recently been successfully manufactured at 110 kV using a novel winding
design. Overload performance is limited but it can be augmented by the use of cooling fans.
This type is more expensive than a fluid-filled equivalent, and because of the reduced fire risk
they are used in special applications where the public are involved, such as underground tunnels,
residential blocks of flats or oil-rigs.
-
8/20/2019 12 Main Classes of Power Transformer _ EEP
8/8
Figure 5 – Dry-type 2500 kVA, 11 000/440 V transformer with cast resin
encapsulation
A typical cast-resin transformer rated 2500 kVA, 11 000/440 V is shown in Figure 5.
12. Gas-filled transformers
For applications where low flammability is paramount, designs have been developed in which the
transformer is insulated and cooled with SF6 gas. This provides an alternative to dry-typeconstruction where the risk of fire must be eliminated and the possible contamination of the
environment by oil spillage must be avoided.
High-voltage SF6 transformers are available at ratings up to 300 MVA at 275 kV and prototype
designs have been tested at up to 500 kV. Gas-filled transformers and reactors are more expen-
sive than oil-filled units but the costs may be justified to eliminate a risk of fire, particularly at a
site where the cost of land is high and where the overall ‘footprint’ of the unit can be reduced by
the elimination of fire-fighting equipment.
SOURCE: Newnes Electrical Power Engineer’s Handbook – D.F. Warne