post-earthquake fire performance-based behavior of unprotected moment resisting 2d steel frames
TRANSCRIPT
Post-Earthquake Fire Performance-based Behavior of
Unprotected Moment Resisting 2D Steel Frames
Behrouz Behnam* and Hamid Reza Ronagh**
Received October 26, 2012/Revised December 16, 2013/Accepted February 16, 2014/Published Online August 20, 2014
··································································································································································································································
Abstract
Post-Earthquake Fire (PEF) can lead to the collapse of buildings that are partially damaged in a prior earthquake that occurredimmediately before the fire. The majority of standards and codes for the design of structures against earthquake ignore the possibilityof PEF and thus buildings designed with those codes fail prematurely when subjected to PEF. A sequential analysis based onFEMA356 is performed here on the Immediate Occupancy (IO), corresponding to a structure designed as school occupancy, and LifeSafety (LS) performance levels, corresponding to a structure designed as reside ntial occupancy, of two steel moment resistingframes. These frames are first subjected to an earthquake load with the PGA of 0.35g. This is followed by a fire analysis, using boththe ISO834 model and the Natural fire model. The time it takes for the structure weakened by the earthquake to collapse under fire isthen calculated. As a point of reference, fire only analyses are also performed for the undamaged structures. The results show thatearthquake weakened structures are more vulnerable to fire than undamaged structures. The results also show that both fire resistanceand PEF resistance of the frame designed as school are more than the frame designed as residential. Whilst the investigation is for acertain class of structures (steel moment resisting frames, 5 stories), the results confirm the need for the incorporation of PEF in theprocess of analysis and design and provides some quantitative measures on the level of associated effects.
Keywords: post earthquake fire, sequential analysis, fire resistance, steel moment resisting structures, performance based design,
immediate occupancy, life safety
··································································································································································································································
1. Introduction
The “life safety” criterion is the criterion by which most (if not
all) building structures are designed. Life safety guarantees that
even under extreme loading situation, structures will remain
gravity load bearing allowing occupants to safely evacuate the
building even though minor to major damage depending on the
level of importance of structure is allowed during an extreme
load level (Borden, 1996). While the codes guarantee the safety
under a number of load combinations representing the extreme
loading possibilities, the Post-Earthquake Fire (PEF) loading has
not been considered in the available codes. Recorded experiences
have proved that PEF can potentially bring about even more
damage in comparison with the earthquake itself. For instance, in
the PEF in Kanto, Japan in 1923, more than 447000 houses were
destructed (Scawthorn et al., 2005).
From a different perspective, as earthquake causes serious
damage to lifelines structures, arterial roads and bridges, the fire
brigades will have difficulty in suppressing burning buildings
(Collier, 2005). Accordingly, more time will be spent to control
the fire than the usual situations. This time may even be more as
helping people trapped under the rubble take priority. Thus, the
requirements of the code for the fire resistance which is often
expressed in time will be considerably more in a PEF situation in
comparison to fire alone situation. Mitigation the effect of PEF
on buildings in such a way that provides adequate time for
evacuating people trapped under the rubble shall therefore be a
key aspect of any PEF safety strategy.
Using the philosophy of earthquake design based on performance
(ATC, 2001), structural elements are normally designed to satisfy
various levels of performance some of which are Operational
(O), Immediate Occupancy (IO), Life Safety (LS) and Collapse
Prevention (CP). In buildings designed for IO performance level,
it is expected that after an earthquake, only minor damage is
sustained by structural elements. These structures are expected to
remain below 0.7% drift. Hospitals and educational centers are
normally designed to meet the IO level of performance as these
buildings are expected to remain serviceable after earthquake. By
contrast, buildings designed to meet the LS level of performance,
will sustain notable damage with the values of total drift around
2.5%, if hit by the design level earthquake. However, the
structures at this level of performance can still carry all gravity
loads and no failure will occur. Most buildings in urban areas,
such as residential and light commercial buildings are designed
Post-Earthquake Fire Performance-based Behavior of Unprotected Moment Resisting 2D Steel Frames
Vol. 19, No. 1 / January 2015 − 275 −
to meet the LS level of performance. The main objective at this
performance level is to limit the level of damage in the buildings
and as a result ensure life safety of the inhabitants. Obviously,
buildings designed for CP performance level, will sustain more
damage compared to the other mentioned levels of performance.
At this level, it is expected that the imposed drift would be more
than 5%, which can lead to extensive damage to structural
components (FEMA356, 2000). Often, temporary structures are
designed to meet the CP level of performance. These types of
structures are not considered in this study.
Understanding the structural behavior is more important when
a fire occurs after earthquake as it adds to the level of complexity.
In general, fire resistance rating is defined as a period of time in
which the integrity of a member subjected to fire is maintained to
resist applied loads (Kodur and Dwaikat, 2007). This definition
is correlated with various factors, one of which is the type of the
building being designed. Indeed, the purpose is not only to
provide sufficient time to evacuate people entrapped due to the
fire, but also to reduce the possibility of any conflagration (Taylor,
2003). Although, typically fire-resistance rating are presented in
national building codes such as NRCC (2005) and IBC (International
Building Code, 2006); much of them are provided for fire alone
and not for PEF (Mousavi et al., 2008).
Investigating PEF resistance, Della Corte et al. (2003) studied
unprotected steel moment-resistant frames and their response to fire
following earthquake. Assuming elastic Perfectly Plastic (EPP)
behavior for steel and considering P-∆ effect with P from gravity
loads and ∆ from the earthquake, the fire resistance rating was
then studied. Della Corte et al., ignoring of the degradation of
stiffness is an issue subject to discussion. Another study which
contained both numerical and experimental elements on single-
story, multi-bays steel frames when are exposed to large
uncontrolled PEF was carried out by Hosam et al. (2004). They
considered unprotected elements in their analyses, however,
every bay was assumed to be protected by firewalls to reduce
losses in uncontrolled fire. Using ABAQUS software (ABAQUS,
2008), a method was then proposed to simulate the effect of
thermal activity on laterally deformed frames. It was also shown
that the type of failure, whether inward or outward collapse, and
the PEF resistance of the models are greatly dependent on both
fire scenarios and the values of gravity loads. Compared with the
previous studies, this study was more comprehensive as it allowed
for geometrical effects as well as degradation in stiffness of
models exposed to fire. However, extrapolation to multi-storey
frames with various bays and different fire scenarios cannot be
made without further research. Further study on steel frames was
carried out by Zaharia and Pintea (Zaharia and Pintea, 2009).
They investigated two different steel frames, designed for two
various return periods of ground-motion: 2475 years return
period and 475 years. The seismic response of the structures was
then evaluated by a pushover analysis developed by Fajfar. While
the frame designed for the 2475 years return period remained
elastic in the pushover analysis, the weaker frame designed for
475 years return-period sustained notable inter storey drift. They
then performed a fire analyses on both frames, which confirmed
that the fire resistance of the structures considering their
deformed state under earthquake is lower than the structures that
do not have any history of deformation prior to the application of
the fire.
Another study was performed by Faggiano et al. (2010) on
steel structures exposed to post earthquake fire. They performed
a couple analyses consisting of both earthquake and fire. Based
on FEMA356 procedure, Faggiano et al. developed a method for
evaluating the various fire performance levels for different
conditions of fire. Recently et al. (2011) investigated the performance
of steel-concrete composite joints when seismic actions were
followed by fire loads. Using numerical analysis and experimental
tests, they showed that the composite joints designed for fire or
earthquake separately, could not provide the required minimum
fire resistance if subjected to same level fire following a same
level earthquake. They then suggested that at least 15 minutes
fire resistance should be provided in case of fire following
earthquake and accordingly, proposed a design method. A similar
studies on the performance of steel frames Sprayed by Fire-
Resistive Materials (SFRM) was performed by Ryder et al. (2002)
and Braxtan and Pessiki (2011). Two SFRM beam-columns joints
were analyzed in different situations; fire alone as a benchmark,
and quasi-static cyclic loading that was followed by fire. Their
study showed that PEF has a negative effect on the bond of
SFRM to steel when joints sustain significant deformation as a
result of earthquake load. Imperfection of insulation, i.e., SFRM,
accordingly, causes increases of heat inside the elements, which
in turn accelerates the rate of decrease in both strength and
stiffness.
Aligned with the abovementioned studies and FEMA356
performance levels definition, in this study, a series of numerical
investigations are carried out on the PEF resistance of two types
of buildings designed as a school building (corresponding to the
IO level of performance) and a residential building (corresponding
to the LS level of performance). The study includes a sequential
analysis of steel frames designed based on the AISC (2005) together
with FEMA356 definition of performance levels, subjected to
earthquake and the aftermath fire.
Fig. 1. PEF in Natori City, Japan, 2011 (Thomson, 2011)
Behrouz Behnam and Hamid Reza Ronagh
− 276 − KSCE Journal of Civil Engineering
2. Methodology
2.1 Sequential Analysis
A sequential analysis is a proper method for considering the
effect of both earthquake and fire on a structure. Fig. 2 schematically
shows the stages of the nonlinear sequential analysis.
The first stage of loading is the application of gravity loads,
which are assumed to be static and uniform. A pseudo earthquake
load then follows in a pushover form reaching its maximum and
returning back to zero in a short time. Clearly, during this time,
gravity loads are also applied. The pattern that is chosen for the
application of earthquake load is similar to pushover analysis
with the difference that the structure is unloaded after reaching
certain level of load. Here, it is assumed that the maximum level
of earthquake load corresponds to IO or LS level of FEMA356
(2000). This assumption is in-line with the seismic design
philosophy in which the performance level of structures shall not
exceed the intended level when subjected to the “Design
earthquake”. Therefore, the structures are pushed to these levels
and then are unloaded. Load duration is not important for both
gravity and earthquake loads, as long-term effects such as creep
are not incorporated in the analysis. Thus, any arbitrary load
duration could be chosen for the loads patterns. It should also be
noted that no dynamic effects are considered in this study, which
can be an issue subject to discussion. Finally, as can be seen in
Fig. 2, the fire load is applied to the structure. Prior to fire
loading, properties of structures are set to the reference
temperature, but during fire, mechanical properties change with
time.
2.2 Pushover Analysis
The static pushover analysis is one of the nonlinear static
methods that are used for analyzing structures subjected to
seismic loads. This method is becoming a popular tool for
seismic performance evaluation of existing and new structures
(Fardis, 2007; Isakovi et al., 2008). In this method, using a
specific load pattern, the structure is pushed to arrive at a
displacement called the target displacement. The target displacement
serves as an estimate of the global displacement that the
structures is expected to experience in a design earthquake often
represented by the roof displacement at the center of mass of the
structure. In this study, a vertical distribution of loads proportional
to the shape of the fundamental mode in the direction under
consideration is used. As mentioned, in FEMA356, the structural
performance level is divided into four main categories, i.e., O,
IO, LS and CP, which represent states of minor damage to
notable damage. Using the definition of lumped plasticity, the
potential locations of high plasticity are introduced by plastic
hinges in SAP2000 (2002). The moment-rotation behavior of each
plastic hinge follows FEMA definitions as shown in Fig. 3.
2.3 Steel Behavior under the Effect of Fire
Materials’ thermal and mechanical characteristics considerably
change when they are exposed to fire which in many cases result
in producing high level of thermal stresses in structures. In
addition, when a heterogeneous composite material with different
thermal characteristics is subjected to elevated temperature;
differential thermal stresses can bring about crushing and rapid
decaying. Steel, is considered as a sensitive material toward
elevated temperature with high thermal conductivity (Kathryn
and Buchanan, 2000). This characteristic leads to a rapid reduction
in the strength and the modulus of elasticity faced with elevated
temperature (Preston and Kirby, 1988). As the temperature goes
beyond 500oC, the steel ultimate strength decreases of 50%
(Purkiss, 1996).
2.4 Fire Patterns
Several parametric models have been developed to calculate
the thermal actions produced by a fire on a compartment (Lundin,
2005; Remesh and Tan, 2007). These models are established
either using “time-temperature curve” methods - sometimes called
“standard fire” - such as those mentioned in ISO 834 (ISO 834
cé
Fig. 2. Stages of the Sequential Analysis
Fig. 3. Conceptual Plastic Hinge States
Post-Earthquake Fire Performance-based Behavior of Unprotected Moment Resisting 2D Steel Frames
Vol. 19, No. 1 / January 2015 − 277 −
International Standard, 1999), and ASTM E119 (ASTM, 2006)
(based on experimental observations) or using “natural fire”
methods (British Standard, 2002) which rely mainly on the
volume of the produced gas by the combustible materials in a
covered space such as those stated in SEI and ASCE (ASCE,
2006). Fig. 4 shows the fire patterns according to ISO 834 and
ASTM E119.
While “time-temperature curve” methods are good enough for
estimating the temperature at a point of time in conventional
buildings such as residential and commercial buildings (Zehfuss
and Hosser, 2007), they present certain limitations such as being
applicable only to certain sizes of compartments and a limited
range of thermal properties (Lennon and Moore, 2003). By
contrast, “natural fire” methods are more accurate, because along
with directly applying the thermal properties of boundaries such
as openings and walls, other factors such as the situation of fire
detection/protection systems are also involved. However, both
models, i.e., the “time-temperature curve” and the “natural fire”,
only schematically represent fire from early ignition to the time
its fully developed as shown in Fig. 5. While these methods
differently arrive at the final temperature at a certain point in
time, they all share the common feature of representing the fire
through one single parameter, i.e., a time dependent single room
temperature (Buchanan, 2001).
The cooling phase in Fig. 5 (the dotted line) is based on the
assumption that after a while, either the air or the combustible
materials become less and less available and thus, temperature or
fire load decreases. This assumption is more realistic in the case
of fire before earthquake assuming closed openings. However, in
buildings previously damaged by an earthquake, there is a high
probability of windows breakage. As a result, the pattern of fire
progression is different comparing to normal fire (Tanaka, 1998).
For the purpose of this study, the above-mentioned methods
are used. In addition, calculating the fire resistance of the selected
models, a computer program written based on Finite Element
Method (FEM) called SAFIR (Franssen, 2011) is employed. The
program performs non-linear analyses on one, two or three
dimensional structures in which both geometrical and material
non-linearity are taken into account. The analyses can also be
performed under ambient or elevated temperature. The stress-
Fig. 4. Fire Pattern according to ISO834 and ASTM E119 (ISO
834 International Standard, 1999; ASTM, 2006)
Fig. 5. Temperature-Time Curve for Fully Developed Fire (Bucha-
nan, 2001)
Fig. 6. Case Study (Dimensions are in mm): (a) Plan View, (b) Geometric Properties
Behrouz Behnam and Hamid Reza Ronagh
− 278 − KSCE Journal of Civil Engineering
strain relationships for various materials as well as their thermal
characteristics are embedded in the software, according to
Eurocodes. Structures that are exposed to fire are analyzed in
two stages, thermal analysis and structural analysis. In the
thermal analysis, the temperature inside the cross-sections at
every thermal step is stored to be used for the subsequent
structural step.
3. Case Study
A Steel resisting frame is selected from a building as shown in
Fig. 6, designed for two levels of performances, IO and LS; with
the former loaded as if it were a school and the later as if it were
a residential building. These assumptions are then needed for
calculating fire load density. The floor and the ceiling are made
of normal weight concrete and the compartment partitions are
done with standard bricks.
The selected frame is loaded and then is designed using steel
plates (welded compact sections) with the yield stress of 240
MPa and for PGA of 0.35 g. The frame is dimensioned for the
load combinations of 8.0 kPa for dead load and 2.5 kPa for live
load. Combination of 100% dead load and 20% of live load for
the designed frame in LS level of performance, i.e., residential
building, and 40% of live load for designed frame in IO level of
performance, i.e., school building, are used to find the required
mass for calculating the earthquake load (ASCE, 2006). The
resulting sections for the designed frames are shown in Table 1.
In order to consider thermal actions, the two methods previously
mentioned in Section 2.4 are used. In order to improve our
understanding of the behavior, fire alone analyses are also
performed on the un-deformed frames. It is worth mentioning
that while exterior side of external columns is not exposed to fire,
all sides of internal columns are subjected to fire. Meanwhile,
only three sides of beams are exposed to fire, because it is
assumed that the top side is well protected by the concrete slab.
Table 2 and Fig. 7 show the thermal characteristics of the materials
in the building and the assumed fire scenarios, respectively.
3.1 Using ISO 834 Curve
Ignoring the possibility of having fire retardant materials on
the frames, both analyses, with and without earthquake are
performed assuming unprotected frames. As we are dealing with
a comparative issue, the results would be indicative of the
worsening effects of earthquake. The frames are exposed to 60
minutes ISO834 fire.
3.2 Using the Natural Fire Method
As described in Annex E of Eurocode 1, using the Natural Fire
method is valid for a covered area smaller than 500 m2 when
there is no opening in the roof (Franssen and Real, 2010). In
addition, the maximum height of the compartment is limited to
4m. The fire load density is then calculated according to Eq. (1),
which allows for the type of occupancy and the influence of
active measures.
qt,d = qf,d × (Aroof /At) (1)
in which, qt,d (MJ/m2) is the fire load of the compartment, qf,d is
the occupancy of the fire compartment, and Aroof (m2) and At (m
2)
are the areas of the roof and the total area consisting of the area
of walls, roof and floor, respectively.
qf,d = δq1 δq2 δn m qf,k (2)
where, δq1 is the risk of fire activation, which increases while the
floor area increases. For this study, δq1 is 1.54. δq2 is the type of
occupancy, which for the purpose of this study is 1.0. Combustion
Table 1. Sections Dimensions for Two Case Studies: School and Residential
Dimensions are in mm
Section typeCase study
Col 1 Col 2 Beam 1 Beam 2
School (designed for IO level)
H=450B=350tf =20tw=15
H=400B=300tf =15tw=10
H=350B=300tf =20tw=15
H=300B=300tf =15tw=10
Residential (designed for LS level)
H=400B=300tf =20tw=15
H=350B=300tf =15tw=10
H=300B=300tf=20tw=15
H=250B=250tf =15tw=10
Table 2. Thermal Characteristics of the Considered Materials
Specific heat(J/kgK)
Material’s density(kg/m3)
Thermal conductivity(W/mK)
Floor and Roof 1000 2400 1.6
Walls 840 1600 0.7
Fig. 7. Fire Scenarios: (a) Scenario 1, (b) Scenario 2
Post-Earthquake Fire Performance-based Behavior of Unprotected Moment Resisting 2D Steel Frames
Vol. 19, No. 1 / January 2015 − 279 −
factor, shown by m in Eq. (2), is between 0 and 1, and is derived
from experimental results. It is assumed to be 0.8 for most
cellulosic materials. qf,k, or the so-called characteristic fire load
density can be calculated using the mentioned values in Annex E
of Eurocode 1, which for residential buildings and schools is 948
MJ/m2 and 347 MJ/m2, respectively. In order to take into account
the effect of active fire-fighting, the factors δn are applied in Eq.
(2). The factors are based on either available fire-extinguishing
systems established in the building such as detection systems,
and sprinklers or those used by fire brigades and rescue teams in
a professional manner. The proposed values are based on a
normal condition and as such cannot be utilized in a PEF
scenario where the whole response teams are under stress.
Consequently, the mentioned factors shall be modified. Here
based on the high possibility of disturbance of both internal
facilities such as sprinkler and detection systems and urban
facilitates as a result of earthquake, such modifications are done
as shown in Table 3. It is worth noting that the time-temperature
curve based on the natural fire method relies on several factors
some of which are thermal characteristics of materials, type of
occupancy, total area of compartment and size and shape of
openings. The fire then may behave as ventilation controlled or
fuel controlled. In most small- and medium-size compartments,
fire is governed by a ventilation mode, which means that the
growth of fire is limited by the availability of air. By contrast, in
large compartments, fires are mostly fuel-controlled, which
means that the growth of fire is limited by the availability of
combustible materials (Zehfuss and Hosser, 2007). Fig. 8 shows
time-temperature curves for the case studies and at two different
situations, before and after earthquake.
4. Results
Sectional dimensions of the beams and columns for the considered
structures were given previously in Fig. 6. All material properties
were also introduced in previous sections. The sequential analysis
comprises three main stages that are the gravity loading, followed
by the seismic pushover analysis, and finally the PEF. In seismic
analysis, the structure is subjected to a monotonically increasing
lateral load. Indeed, the structure is pushed to a certain level of
displacement. According to the philosophy of performance-based
design, it is expected that structures designed for a specific level
of performance remain at the assumed level when subjected to
the “design earthquake”. Accordingly, for the two different
levels of performance, i.e., IO and LS, two different pushover
analyses are needed. Using the FEMA356 procedure, a target
displacement shall be calculated for controlling the situation of
the structure for the assumed performance level. To do this, the
well-accepted Eq. (3) is used, in which T stands for the target
displacement and Ci are the coefficients used to convert the
elastic structural response into the inelastic response. In addition,
Sa and Te are the spectral response acceleration and the effective
fundamental period, respectively, which are determined using
the mentioned procedure in Section 1.6.1.5 of FEMA356. Using
Eq. (3), the target displacements of 340 mm and 395 mm are
calculated for the IO and the LS levels, respectively.
(3)
In this respect, SAP2000 program is used for the pushover
analysis. Moreover, FEMA procedure is used to define hinge
positions and properties. Fig. 9 shows the state of hinges resulting
from the pushover analyses at the two mentioned performance
levels. The results show that none of the hinges go beyond the
defined levels of performance. Nevertheless, it is evident that
∆T CiSa T 2π⁄( )2
gi 0=
i 3=
∑=
Table 3. Fire-fighting Measures
Types of occupancy
Fire situation
Automatic water
extinguishing systems
Water supply
Automatic fire
detection
Automatic fire alarm
Automatic transmission
A work fire brigades
An off site fire brigades
Safe access routes
Normal fire fight devices
Smoke exhaust systems
Sum
δ1 δ2 δ3 δ4 δ5 δ6 δ7 δ8 δ9 δ10 Π δn
SchoolNormal Condition 0.61 0.7 1.0 1.0 0.87 0.61 0.71 1.0 1.0 1.5 0.37
After EQ 1.0 1.0 1.0 1.0 0.87 1.0 1.0 1.5 1.5 1.5 4.52
ResidentialNormal Condition 1.0 1.0 1.0 1.0 1.0 1.0 0.71 1.0 1.0 1.5 1.64
After EQ 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5 1.5 1.5 5.20
Note: Residential designed for LS level of performance and School designed for IO level of performance
Fig. 8. Fire Pattern according to the Natural Fire Method
Behrouz Behnam and Hamid Reza Ronagh
− 280 − KSCE Journal of Civil Engineering
after the pushover analysis some degree of damage would exist
in the structure. The damaged structure is then loaded with fire as
a sequential load, which arrives at the structure in its residually
deformed state. To do this, the SAFIR program allows a function
to be written inside its computing environment that allows
importing of the pushover loads, which are extracted from
SAP2000 at such step where the target displacement is attained.
With the structural model at the target displacement step
imported into the SAFIR environment, unloading is performed
followed by re-loading with fire.
Figure 10. shows the pushover curves for the mentioned
performance levels resulted from SAP2000 and used for the
sequential analysis in SAFIR.
The final stage of sequential analysis is to apply a PEF on the
structure. Two different scenarios are used for the fire analysis,
for both damaged and undamaged frames and using both ISO834
model and Natural Fire model. In case one, the undamaged
structure is exposed to the fire load, while in case two, the
deformed structure is exposed to the fire load. In other words, in
the first case, the fire follows the applied gravity loads, but in the
second case, the fire follows the gravity and the earthquake
loads. Fig. 11 shows the temperature distribution of fire exposure
Fig. 9. Hinge States resulted from Pushover Analyses: (a) IO Level, (b) LS Level
Fig. 10. Pushover Analysis and the Response Spectrum: (a) Pushover Curve, (b) Response Spectrum
Fig. 11. Distribution of Temperature inside the Sections using ISO834
Model: (a) Beam exposed on 3 Sides of fire, (b) Column
exposed on 4 Sides of Fire
Post-Earthquake Fire Performance-based Behavior of Unprotected Moment Resisting 2D Steel Frames
Vol. 19, No. 1 / January 2015 − 281 −
on two types of applied sections using ISO curve and after 60
minutes.
Figures 12(a) and 12(b) show the fire resistance based on the
scenario 1 and using the ISO model in both situations, i.e., fire
alone and PEF and for the defined performance levels. The sharp
increase and then decrease in PEF analysis is due to, the
structures are firstly pushed to a certain level of displacement
and the unloaded. The deformed structures are then exposed to
fire as mentioned earlier. The fire resistance is defined as a time
at which the displacements either globally (i.e., is the drift of a
certain point) or locally (i.e., the deformations at the middle of a
beam) go beyond chosen thresholds. The thresholds have been
identified by the curve for displacements versus time step
merging towards the horizontal asymptote by a 1% error. In other
words, a member is considered as failed when it unable to resist
the initially applied gravity loads (Kathryn and Buchanan, 2000;
Almand et al., 2004) which is assumed to be the case when the
response curve becomes too flat.
As is seen in Figs. 12(a) and 13(b), there is a correlation between
the fire resistance rating and the performance levels so that the
fire resistance of the designed frame at the higher performance
level, i.e., IO, is obviously more than the frame designed for the
lower level, i.e., LS performance level. In other words, the PEF
resistance is influenced by the intensity of damage induced in the
frame during the prior earthquake. On the other hand, while in
the first scenario the collapse time for PEF-IO level is around 28
minutes, it increases to about 38 minutes in the fire only situation,
which represents a 26% difference in the fire resistance. By
contract, while the fire resistance of the undamaged frame
designed for LS level is about 32 minutes, it reduces to 25
minutes in case of PEF, which signifies a 22% reduction in the
fire resistance. Although, the fire resistances based on Natural
Fire model for both cases, i.e., IO and LS, are more than those
calculated based on the ISO model, a similarity can be observed
in terms of structural behavior, as shown in Figs. 13(a) and 13(b).
The figures show that the fire resistance of both IO and LS levels
of performance decreases when the structures are subjected to
prior earthquake. While, the fire resistance of undamaged IO and
LS cases is around 51 minutes and 24 minutes, respectively, it
reduces to about 22 minutes and 18 minutes, respectively, in case
of PEF.
The lateral displacement versus time based on ISO834 curve
and scenario 2 is shown in Fig. 14. Similar to Figs. 12 and 13, the
sharp increase and the decrease is due to the loading and
unloading steps during the application of lateral loads to the
structures. It is again evident that both the fire resistance and the
Fig. 12. Fire Resistance based on ISO834 - Scenario 1 (1st Story Lateral Displacement): (a) School (IO Performance Level), (b) Residential
(LS Performance Level)
Fig. 13. Fire Resistance based on Natural Fire - Scenario 1 (1st Story Lateral Displacement): (a) School (IO Performance Level), (b) Resi-
dential (LS Performance Level)
Behrouz Behnam and Hamid Reza Ronagh
− 282 − KSCE Journal of Civil Engineering
PEF resistance of the frame designed as residential occupancy, is
lower than those of the building designed as school. In case of
fire alone scenario, the designed frame as school occupancy fails
at around 35 minutes, while the designed frame as residential
occupancy fails at around 25 minutes. The PEF resistance of
both frames- the school and the residential- then declines
considerably to around 20 minutes and 16 minutes, respectively.
In is also observed that comparing with the first scenario, i.e.,
when the fire is applied to the first floor, the fire resistance and
the PEF resistance decline. Fig. 15 shows the fire and the PEF
resistance of the frames based on the second scenario and the
application of Natural Fire curves to the frames. Again, the
results show that both fire resistance and PEF resistance of frame
designed as school occupancy is more than that of the frame
designed as residential occupancy. In the case of fire alone
situation, the frame designed as school fails at about 40 minutes,
the frame designed as residential occupancy fails at about 18
minutes. The PEF resistance of the frame designed as school is
around 19 minutes while it is around 13 minutes for the frame
designed as residential.
A comparison between the results of Figs. 14 and 15 with those
of Figs. 12 and 13 shows that there are more reductions in the
resistance of frames in the second scenario than the first scenario.
This could be attributed to the lower stiffness of the frames in the
top story comparing to the first story. It is worth noting that two
types of collapse, global collapse and local collapse were
observed during the analyses. While the global collapse is
defined as a situation in which the frame fails because of
considerable lateral movement of columns, the local collapse
involves the failure of beams mainly. In the studied cases, both
frames, i.e., the school and the residential, and in case of PEF, the
global collapse occurred. However, the local collapse occurred
when the elements are subjected to fire alone. Fig. 16 schematically
show two types of collapse failure in the scenarios considered.
5. Conclusions
Post-Earthquake Fire (PEF) is a reality that has not received
adequate attention in the past. Investigating the effects of PEF on
structures classified as “ordinary” in the codes such as educational
and residential is important, as these buildings comprise a major
part of urban buildings. Design based on performance requires
these buildings to remain within the “life safety” level of
response under the design earthquake. These structures, however,
Fig. 14. Fire Resistance based on ISO834 - Scenario 2 (5th Story Lateral Displacement): (a) School (IO Performance Level), (b) Residential
(LS Performance Level)
Fig. 15. Fire Resistance based on Natural Fire - Scenario 2 (5th Story Lateral Displacement): (a) School (IO Performance Level), (b) Resi-
dential (LS Performance Level)
Post-Earthquake Fire Performance-based Behavior of Unprotected Moment Resisting 2D Steel Frames
Vol. 19, No. 1 / January 2015 − 283 −
are more vulnerable if loaded with fire after they are weakened to
some extent by a prior earthquake. In this research, sequential
non-linear analysis is proposed for the PEF analysis of these
structures. Two steel moment resisting frames were selected and
designed at two different occupancy purposes, a school and a
residential building. The structures were then pushed to the
maximum allowable inter-story drift, which is assumed to satisfy
the Immediate Occupancy and Life Safety performance levels.
Pushover curve was then extracted for use in subsequent analysis.
Sequential loading consisting of gravity and lateral loads that
was followed by fire (ISO834 model and Natural fire model)
was a key aspect of the study conducted using the SAFIR
software. In SAFIR, the P-∆ effect and the residual lateral
deformation as well as degradation in stiffness were considered.
Accordingly, the following remarks can be made:
• The sequential analysis is the functional tool to consider the
effects of residual deformations from an earthquake as well
as degradation in stiffness and strength.
• Structures suffered damage from earthquake loads have
lower fire resistance than undamaged structures. This can be
the result of residual lateral displacements and the degrada-
tion of strength and stiffness that exacerbate the effects of
fire.
• Fire resistance calculated based on Natural Fire model is
more than that calculated based on the ISO834 model.
Although, there seems to be consensus worldwide on using
standard fire patterns such as ISO834, using Natural Fire
models are more accurate as several factors are considered
at the same time.
• Two types of collapse mechanisms were observed during
the fire analyses; these being global collapse and local col-
lapse. While, the local collapse occurred in the beams, glo-
bal collapse was represented mostly by considerable lateral
movement in the columns. Interestingly, the majority of fires
only analysis resulted in the local collapse while all PEF
analyses resulted in the global collapse.
• Whilst the investigations performed here were for a certain
class of structures, the results confirm the need for the incor-
poration of PEF in the process of analysis and design. Fur-
ther studies thus need to be performed either numerically or
experimentally on different structures subjected to PEF in
order to develop a better understanding of the issue.
References
ABAQUS (2008). 6.8, Dassault Systemes Simulia Corp: Providence.
Almand, K., Phan, L., McAllister, T., Starnes, M., and Gross, J. (2004).
“NET-SFPE workshop for development of a national R&D roadmap
for structural fire safety design and retrofit of structures.” NlSTlR
7133, National Institute of Standards and Technology, Vol. 176, No.
2, pp. 61-69.
ASCE (2005). Specification for structural steel buildings, American
Institute of Steel Construction, Chicago, USA.
ASCE (2006). Minimum design loads for buildings and other structures,
SEI/ASCE 7-0.5. American Society of Civil Engineers.
ASTM (2006). Standard test methods for determining effects of large
hydrocarbon pool fires on structural members and assemblies,
ASTM E1529-06. American Society for Testing and Materials.
ATC (2001). Seismic evaluation and retrofit of concrete buildings (ATC
40), Chapter 2, Overview, California Seismic Safety Commission,
California.
Borden, F. (1996). The 1994 Northridge earthquake and the fires that
followed, Thirteenth meeting of the UJNR panel on fire research and
safety, California, National Institute of Standards and Technology.
Braxtan, N. L. and Pessiki, S. P. (2011). “Post earthquake fire performance
of sprayed fire-resistive material on steel moment frames.” Journal
of Structural Engineering, ASCE, Vol. 137, No. 9, pp. 946-953.
British Standard (2002). Basis of structural design, Eurocode0, National
Standards Authority of Ireland, Dublin.
Buchanan, A. (2001). Structural design for fire safety, JOHN WILEY
AND SONS, LTD, New York.
Collier, P. (2005). Post earthquake performance of passive fire protection
systems, Building Research Levy and the Department of Building
and Housing, Sydney.
Della Corte, G., Landolfo, R., and Mazzolani, F. M. (2003). “Post earthquake
fire resistance of moment resisting steel frames.” Fire Safety
Journal, Vol. 38, No. 7, pp. 593-612.
Faggiano, B. and Gregorgio, D. (2010). Assessment of the robustness of
structures subjected to fire following earthquake through a performance-
based approach, Urban Habitat Constructions under Catastorphic
Events, Taylor & Francis Group, London.
Fardis, M. (2007). Guidelines for displacement-based design of buildings
and bridge: Risk mitigation for earthquake and landslides, IUSS
Press, Pavia, Italy.
Fig. 16. Collapse Mechanism in the assumed Fire Scenarios: (a)
Local Collapse in Scenario 1, (b) Global Collapse in Sce-
nario 1, (c) Local Collapse in Scenario 2, (d) Global Col-
lapse in Scenario 2
Behrouz Behnam and Hamid Reza Ronagh
− 284 − KSCE Journal of Civil Engineering
FEMA356 (2000). Prestandard and commentary for the seismic
rehabilitation of buildings rehabilitation requirements, American
Society of Civil Engineers, Washington, DC.
Franssen, J. M. (2011). User’s manual for SAFIR 2011: A computer
program for analysis of structures subjected to fire, University of
Liege, Belgium.
Franssen, J.-M. and Real, P. V. (2010). Fire design of steel structures,
European Convention for Constructional Steel work, Berlin.
Hosam, A., Senseny, P., and Alpert, R. (2004). “Lateral displacement
and collapse of single-story steel frames in uncontrolled fires.”
Engineering Structures, Vol. 26, No. 5, pp. 593-607.
International Building Code (2006). IBC. Facilities 3. NFPA 101-100
Chicago, National Fire Protection.
Isakovi , T., Lazaro, M. P. N., and Fischinger, M. (2008). “Applicability
of pushover methods for the seismic analysis of single-column bent
viaducts.” Earthquake Engineering & Structural Dynamics, Vol. 37,
No. 8, pp. 1185-1202.
ISO 834 International Standard (1999). Fire resistance tests, ISO 834-1.
Test conditions, Provided by IHS under license with ISO: 31, Genève,
Switzerland.
Kathryn, L. and Buchanan, A. (2000). Fire design of steel members fire
engineering research report, The University of Canterbury, New
Zealand.
Kodur, V. K. R. and Dwaikat, M. (2007). “Performance-based fire safety
design of reinforced concrete beams.” Journal of Fire Protection
Engineering, Vol. 17, November, pp. 293-320.
Lennon, T. and Moore, D. (2003). “The natural fire safety concept-full-
scale tests at Cardington.” Fire Safety Journal, Vol. 38, No. 7, pp.
623-643.
Lundin, J. (2005). “On quantification of error and uncertainty in two-
zone models used in fire safety design.” Journal of Fire Sciences,
Vol. 23, No. 4, pp. 329-354.
Mousavi, S., Kodur, V. K. R., and Bagchi, A. (2008). “Review of post
earthquake fire hazard to building structures.” Canadian Journal of
Civil Engineering, Vol. 35, No. 7, pp. 689-698.
NRCC (2005). National fire code in buildings, Ottawa,Canada.
Preston, R. and Kirby, B. (1988). “High temperature properties of hot-
rolled, structural steels for use in fire engineering design studies.”
Fire Safety Journal, Vol. 13, No. 1, pp. 27-37.
Pucinotti, R., Bursi, O. S., and Demonceau, J. F. (2011). “Post-earthquake
fire and seismic performance of welded steel–concrete composite
beam-to-column joints.” Journal of Constructional Steel Research,
Vol. 67, No. 9, pp. 1358-1375.
Purkiss, J. A. (1996). Fire safety engineering : Design of structures,
Elsevier, Burlington, MA, USA.
Remesh, K. and Tan, K. H. (2007). “Performance comparison of zone
models with compartment fire tests.” Journal of Fire Sciences, Vol.
25, No. 4, pp. 321-353.
Ryder, N. L., Wolin, S. D., and Milke, J. A. (2002). “An investigation of
the reduction in fire resistance of steel columns caused by loss of
spray-applied fire protection.” Journal of Fire Protection Engineering,
Vol. 12, No. 1, pp. 31-44.
SAP2000-V14 (2002). Integrated finite element analysis and design of
structures basic analysis reference manual, Berkeley, CA, USA.
Scawthorn, C., Eidinger, J. M., and Schiff, A. (2005). Fire following
earthquake, American Society of Civil Engineers.
Tanaka, T. (1998). Performance-based fire safety design of a high-rise
office building, Building Research Institute, Japan.
Taylor, J. (2003). Post earthquake fire in tall buildings and the New
Zealand building code, MSc Science Research, University of
Canterbury.
Thomson, A. (2011). Japan disaster: Kesennuma hit by quake, tsunami
and fire, Channel 4 News (retrieved from: http://www.channel4.
com/news/kesennuma-quake-tsunami-and-now-fire).
Zaharia, R. and D. Pintea (2009). “Fire after earthquake analysis of steel
moment resisting frames.” International Journal of Steel Structures,
Vol. 9, No. 4, pp. 275-284.
Zehfuss, J. and Hosser, D. (2007). “A parametric natural fire model for
the structural fire design of multi-storey buildings.” Fire Safety
Journal, Vol. 42, No. 2, pp. 115-126.
cé