Distribution Automation solutionL500 MV network management

Page 2: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 2

Content

I.I.I.I. Context

II. II. II. II. Our Distribution Automation solution

III.III.III.III. References

Page 3: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 3

An increasing demand for Energy

●Energy must be available●Reduced outages

●Reduced outage duration

●Energy must be of high quality●Guarantee of voltage level

●Harmonic management

●Energy must be cost effective● Investment cost optimization

●Reduced operational cost●Real-time cost mastering

Page 4: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 4

Electric utilities need to Improve their Efficiency

●Reduce number and duration of outages●Cables, lines and switchgears improvement:Use Schneider Electric MV equipment!●More looped-network, shorter feeders●Staff competencies improvement● Fault location and network reconfiguration●Distribution automation

● Improve quality of distributed energy ●Voltage level control●Harmonic filtering

●Optimize investment costs● Load flow monitoring● Transformer monitoring●SCADA feeding with reliable and accurate data

Page 5: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 5

Electricity outages: an economic stake

●Financial consequences of defective power supply● For end users

●Loss of revenues (non productive time)●Deterioration of production or even process itself

● For electricity suppliers●Loss of revenues●Maintenance costs●Damage to distribution hardware●Customer satisfaction●Regulator penalties

Source:Coûts

Le Coût des Défauts de

l’Alimentation Electrique

David Chapman

Copper Development

Association

Juillet 2002

Typical financial loss per outage

Semi-conductors production 3,800,000 €Financial firm 6,000,000 € per hourInformatics Centre 750,000 €Telecommunications 30,000 € per minuteSteel works 350,000 €Glass industry 250 000 €

Page 6: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 6

Cost of Non-Distributed Energy (NDE)

● yearly incidents rate● average power consumption● outage time● kWh price

Cost of resulting consumer perturbationsS = W x c x dt

S: distributor benefitsW: Non-distributed energy dt : outage time reduction thanks to networks remote controlc: 20 to 50 times selling price: according to country wealth

Page 7: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 7

●SAIDI (System Average Interruption Duration Index) can vary from a few minutes to several hours,

●SAIFI (System Average Interruption Frequency Index) can vary from 0,1 to10 and more, depending on :● population density (rural or urban area)

● proportion between underground and overhead distribution

●maximum accepted costs for non distributed energy

Excellent Average Poor

Urban area < 10 mn 30 mn >2 hrs

Rural area < 30 mn 2 hrs >10 hrs

Permanent Interruptions (>1 mn)

SAIDI/SAIFI variations

Page 8: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 8

Content

I.I.I.I. Context

II.II.II.II. Our Distribution Automation solution

III.III.III.III. References

Page 9: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 9

●Substations●Motorization of MV equipment●Replacement of MV equipment

●Remote Terminal Units● Installation of RTUs● Interface with communication network

●SCADA●Adapt existing SCADA if possible● Installing SCADA

●Communication network settling●Create private network:

●Radio, lease line, Ethernet cabled network

●Utilize public network:

●PSTN, GSM, GPRS

Distribution automation, practically

Page 10: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 10

Underground network typical outage management

Without Distribution Automation system

With FPIs

with full Distribution Automation system

Page 11: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 11

Overhead network typical outage management

Without Distribution Automation system

with Distribution Automation system (with sectionalizer)

with Distribution Automation system

(without sectionalizer)

Page 12: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 12

Our Distribution Automation, contributes to

● Network reliability of supply●Decreased number and duration of

outages (SAIFI and SAIDI)●Reduced size of zones affected by

the faults.

●Monitored & improved power quality

● Operation and capital costs reduction●Reduced cost of non distributed

energy●Reduced operating cost , during

major fault on the network●Reduced maintenance cost● Load monitoring

Page 13: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 13

Our distribution automation solution

Page 14: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 14

Our Distribution Automation Solution

●…will help you to● improve quality of service● reduce operational and maintenance costs● defer capital expenditures

●…through●Step by step and easy implementation of an affordable and global solution for

underground and overhead network management

●…within● the frame of your operating budget

Page 15: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 15

●Substations●Motorization of MV equipment

●Replacement of MV equipment

●Remote Terminal Units● Installation of RTUs

● Interface with communication network

●SCADA●Adapt existing SCADA if possible

● Installing SCADA

●Communication network settling●Create private network:

●Radio, lease line, Ethernet cabled network

●Utilize public network:

●PSTN, GSM, GPRS

Distribution automation, practically

Page 16: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 16

SCADA installation and implementation,a long and expensive process?

●Definition of needs and specification writing by experts - 12 months●Which SCADA-DMS functions?

●Which transmission networks?●Which units rehabilitation works?

●More than 12-months tendering process●18-months implementation ●Long training, configuration before system

handling●Long capital mobilization and delayed return

on investment (>36 months)

Page 17: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 17

SCADA-DMS Vs Easergy L500

● Apprehensions regarding a SCADA project● Long● Complex● Resources consuming● Capital mobilization● Delayed ROI

● Focus investment on network instrumentation thanks to:● Preconfigured SCADA for Easergy devices● Basic SCADA with just enough functions to manage Easergy devices data, not

more

Page 18: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 18

L500: Electric Utilities targetted

Energy sales in TWh

GDP in US$

50,000

25,000

#13Leaders

Second league

#500

Diffuse#10,000

1 TWh

Emerging

#500

200 TWh

10,000

1,000

Sources : International Monetary Fund, Eurostat.

EU25

Targetted utilities:Having SCADA for HV/MV –evolution expensive/impôssible

No SCADA, lack of workforce to manage, step by step process

Page 19: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 19

Easergy L500, real time SCADA

●Management of non permanent communication ●with Easergy devices ● through Radio, PSTN, GSM, GPRS,…

●Remote Monitoring and control ●Remote MV switches status indication.●Switches / CBs Control.

●Alarms and events management.

●Archival storage of all Events and Alarms.●Easergy devices clock synchronisation through

the protocol.GSM PSTN Radio

T200 T200T200

On call stationWEB view

Ethernet Central control

Radio /PSTN / LL /GSM /GPRS /ETH

Page 20: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 20

With Easergy L500, reliably manage your network within a few clicks

●Step by step implementation ●with an annual budget compatible with your

operation budget ● starting with MV/LV substations rehabilitation●while limiting technical risks (communication,

technical choice…)●with adapted remote management system

●Short return on investment● operational system within 3 months (after order)● immediate service quality and operations

improvement●Balanced and gradual training of the personnel

in charge of networks operating

Easergy L500Existing SCADA?

Communicationnetwork:

radio, PSTN,GSM, GPRS,

Ethernet

Page 21: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 21

With Easergy L500, reliably manage your network within a few clicks

●Pre-configured with Easergy range products for monitoring and control of MV networks●MV/LV substations equipped with T200I or

Flair 200C

●Overhead LBS equipped with T200P

●Overhead line equipped with Flite 116 / G200

●Broad range of transmission supports ●Radio, GSM, GPRS, PSTN, LL, FO..

●Simple implementation●One to two weeks only for 20 MV/LV units

●Configuration, training and handling within a few days

●Simple and fast evolutions by operations managers

Page 22: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 22

Easergy L500, Man Machine Interface

●Control unit with 1 to 3 screens●Global network imaging ●Substations detailed views

●Substation single line diagram● Detailed display of alarms●Measurements● Trends display possibility●Connections planning● Individual call request

●Direct access to information●Online help

14/10/07 13:46:19:031 Défaut terre B Dagneux(T200 I 8V)

Page 23: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 23

Easergy L500, reliable and safe configuration

●Reliable data thanks to predefined and validated templates●Simple and fast configuration

●No data writing, configuration thanks to dialog boxes

●Communication network selections

●Done by operators

●Automatic building up of the supervision and communications data base●Customization of views according to MV

network scheme, and to substation, from graphic editor of Easergy L500 software●Open and scalable system by experts

Page 24: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 24

●Communication front end processor integrated into supervision PC● 1 to 8 communication ports

●Multi supports communication

● Radio , phone, GSM, GPRS, FO, Leased Line, Ethernet network

●Permanent and non permanent management of communications (Master-Master profile)●Calls management

● periodic calls

● general control

● on operator's request

●Communication protocol Modbus RTU and TCP/IP

Easergy L500a broad choice of communication supports

Page 25: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 25

Other characteristics

●Easergy L500 is delivered on CD-Rom. It encompasses:●Application editor: Easergy configurator●Supervisor: Easergy supervisor●Communication server

●Basic material required: standard PC with windows XP●Languages : French, English, Spanish●Online help for configurator and supervisor use●Password protected access

Page 26: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 26

With our Distribution Automation Solution

Invest just as necessary to significantly improve quality of service and get immediate return on investment .

Page 27: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 27

Content

I. Context

II. Our Distribution Automation solution

III. References

Page 28: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 28

Morocco : Marrakech Utility RademaSCADA DMS planned

●Customer's needs: year 2005● SCADA DMS planned project but budget problem

● Operation team want to remotely manage their MV/MV substations and remotely follow-up substations load profiles (20% growth per year): substation burn due to overload

●Customer requirement (2005)● Remote management of 4 MV/MV substation and 2

MV/LV substation of major importance

● Communication redundancy: LL/radio (MV/MV) and radio/GSM (MV/LV)

● First turnkey implementation in 2006

● 8 MV/MV and 30 MV/LV substations extension in 2007

●Generalization to the whole network is the Management's priority

Page 29: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 29

Morocco : Rabat Utility RedalExisting SCADA-DMS

●Customer's requirements: year 2003●Existing SCADA-DMS system managing HV/MV and MV/MV s/s● The DMS replacement installed in 1985 is planned for 2005

●Distribution network management considered as a priority

● Implementation● First turnkey implementation in 2004 with

●Easergy L500 with Radio UHF communication network and 20 Easergy T200I

●Yearly evolution according to operations budget●2006: 120 T200 I + 30 T200 P + 20 1st Flair 200C

●2007: 50 new T200 I + 50 Flair 200C

●Future, using new SCADA DMS (2008)● Flair 200C and T200 connected to DMS using IEC protocol

● L500 used as a maintenance tool

Page 30: Distribution Automation solution - Schneider · PDF fileOur Distribution Automation Solution ... Existing SCADA-DMS system managing HV/MV and MV/MV s/s The DMS replacement installed

Schneider Electric – Distribution Automation – 2008 30

Jordan : Irbid Utility IDECO 1st step into automation: Communicating FPIs

●Customer's requirements●No existing automation or instrumentation

● Looking for a solution to localize faults faster,

● Limited budget: Asking for a PC getting the singles from FPIs

● Implementation● First turnkey implementation in 2007 with

●Easergy L500 with GPRS communication network and 80 G200 (240 Flite 116-SA)

●Extension in progress: 100 Flair 200C

●New order 04/2008: 100 Flair 200C

●Future,●Extensions of the installation by IDECO according to ROI

●Possible similar projects for other utilities in the region