converter faults & protection - … · the effects of single commutation failure are, there is...
TRANSCRIPT
CONVERTER FAULTS &
PROTECTION
INTRODUCTION
Faults in DC systems are caused by
the malfunction of the equipment and
controllers
The failure of insulation caused by external
sources such as lightning ,pollution etc…
In a converter
station
Valves are the most critical equipment
needed to be protected
CONVERTER FAULTS
Types of Converter Faults
Faults due to malfunctions of valves
and controllers
Arc backs
Arc through
Misfire
Quenching or Current Extinction
Short Circuits in converter station
Commutation Failure
ARC BACKS
In this phenomena the valve losses its capability
to block in the reverse direction
Hence conduction takes place in reverse
direction also
This is non-self clearing fault
When this fault is detected we need to block the
converter valves and open the backup AC breaker
This can be eliminated by using a bypass valve
placed across converter bridge on the valve side
The bypass valve has higher current rating than ordinary valves
ARC THROUGH
It is the failure to block a valve during a scheduled non conduction period
A malfunction in the gate pulse generator can fire a valve which is actually not supposed to conduct, but is forward biased
This malfunction is mainly because of failure of
a) Negative grid pulse b) early occurrence of positive grid pulse
This fault mainly takes place at inverter station
MISFIRE
This takes place when the
required gate pulse is missing
and the incoming valve fails to ignite
This can occur in both rectifier
and inverter stations, but
effects are more in inverter
Effects are commutation
failure and arc through. This is a self clearing
fault
CURRENT EXTINCTION
This takes place when the current through a valve reaches a value
less than the holding current
This fault may cause
overvoltage's to take place in the
valve
COMMUTATION FAILURE
It is nothing but the failure of the completion of
commutation before the reversal of commutating voltage
takes place.
The minimum value of extinction angle is defined by
Ƴ=180-α-µ
The overlap angle is a function of the commutation voltage
and the DC current.
The reduction in voltage or increase in current or both can
result in an increase in the overlap angle and reduction of
Ƴ below Ƴmin.
This gives rise to commutation failure.
Consider the circuit shown above.
Assuming initially valves 1 and 2 are conducting.
Now because of increased DC current or decreased AC
voltage or any case valve 1 fails to extinguish.
Therefore valve1 carries full link current and the current in
valve 3 becomes zero.
Hence valve 3 extinguishes and valve 1 continues its
conduction .
Next when valve 4 fires the short circuit of the bridge takes
place as valves in the same arm conducts.
This causes the voltage across valve 5 to be negative
hence it does not conducts.
Valve 4 gets extinguished and valve 6 is fired next.
Hence the normal operation is retained back.
Therefore it can be said that single commutation failure is
self clearing.
The effects of single commutation failure are,
There is no AC current for the period in which the two valves in
an arm are left conducting.
The bridge voltage remains zero for a period exceeding 1/3 of a
cycle, during which the DC current tends to increase.
Double commutation failure can also takes place in a
converter station.
A commutation failure in a bridge can cause several
sequence commutation failures in the series connected
bridges.
Hence the initial rate of rise of current has to be sufficiently
limited by connecting the smoothing reactor in the circuit.
SHORT CIRCUIT IN A BRIDGE
This fault has very low probability of occurrence.
As the valves are kept in a valve hall with air conditioning.
They may sometime occur because of flashover in
bushings.
This fault mostly occurs in rectifiers.
PROTECTION AGAINST OVER CURRENTS
It provides basic
protection
against faults in a
converter
It compares
the rectified
current on
the valve
side of
converter
transformer
to DC
current on
line side
smoothing
reactor This is used as
backup. The level
of overcurrent
required to trip
must be set
higher than VGP
to avoid tripping
This is mainly
used to detect
the ground
faults, such as
neutral faults.
The faults producing overcurrents are classified into
3 categories:
The first one being line faults. They occur frequently and
can be controlled by controlling the current.
The second being the internal faults. They cause high
overcurrents. These are infrequent.
The third fault may be commutation failure at inverters.
They occur quite frequently.
PROTECTION AGAINST OVER VOLTAGES
The sources of over voltages in converter station are:
Switching operations
Lightning strokes
Sudden load rejection
Resonance between filter and system when suppressing lower order harmonics.
Symmetrical faults in AC yard
Errors in voltage control
Converter faults
SWITCHING OPERATIONS
These over voltages are of short duration.
Switching surges are on account of circuit breaker
operation while switching inductive and capacitive loads.
Protection schemes:
Using surge absorbers with circuit breakers.
Using SF6 breakers.
LIGHTNING STROKES
The primary cause of this over voltage is lightning strikes.
These occur for a very short duration but causes more
damage to the system.
Protection schemes:
Using surge arresters and spark gaps.
Using overhead ground wire.
With the help of neutral grounding.
OTHER FAULTS
Sudden load rejection,resonance,symmetrical faults in AC yard and other causes temporary over voltages in the system.
This occurs at power frequency and lasts for a few seconds.
Protection schemes:
Using surge over voltage relays and circuit breakers.
Using fast acting static VAR sources.
Using On Load Tap Changers.
SURGE ARRESTERS
It is a device connected between a conductor and ground,
to protect the equipments against high voltage surges.
It is also known as lightning arrestors.
It diverts the lightning or switching surges from the
equipment towards the ground.
Under normal operating voltage, the impedance offered by
a surge arrester is very high.
As the current always chooses the low resistance path
equipment can perform in normal operation.
SURGE ARRESTERS CONTD…
When an over voltage occurs it causes the drop in the
impedance of surge arrester.
Thus the flow now will be through the surge arrester rather
than the main path.
Two types of arresters are there:
Gapless arresters
Zinc oxide arresters
Zinc oxide arrester is widely used as they have high
energy absorbing capability.
SMOOTHING REACTORS
It is a high inductance coil connected in series with the
converter to reduce the ripple current on the DC side of the
system.
Basically the DC current from the rectifier has harmonic
components called ripple.
As SR is in series with rectifier whole load current flows
through it.
Then their magnitude is reduced and current becomes
smoother.
CORONA ON DC LINES
The phenomena of hissing sound, violet glow accompanied with the production of ozone gas due to ionization of air surrounding the conductor, when voltage gradient exceed a particular value is called corona.
In DC transmission system, due to the discharge a current pulse is generated resulting in increase in power loss.
The effects of corona are:
Radio Interference
Audible Noise
Space charge field
RADIO INTERFERENCE
It is also known as radio influence.
It occurs in the band region of 0.5 to 1.6Mhz.
In HVDC lines, RI effect is more in positive conductor rather than in negative conductor.
It is expressed in millivolts per meter.
Mathematically it is expressed as
RI=25+10logn+10logr+1.5(g-go)
In negative conductors the value of radio interference is lower by 20dB.
AUDIBLE NOISE
The corona discharges from the conductor produce compressions and rarefactions that are propagated through the medium as acoustical energy.
The portion of the acoustical energy spectrum that lies within the sonic range is perceived as audible noise.The sound level is expressed in decibels'.
It is defined as
dB=20log(P/Pr)
where P= measured sound pressure
Pr= reference pressure level
The positive polarity conductor is the primary source of AN.