Page 1: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

C13-SeriesInstallation, Operation and Maintenance Manual

Effective September 2018

HorizontalAir-Cooled, Water-Cooled, Chilled Water and Heat Pump

Page 2: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides
Page 3: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

3Subject to change without notice. 10.20-IM (0918)

Contents

Contents � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 3Wiring Diagram � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 4Important Notice� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5Use of Symbols� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5C13-Series Air-Cooled Package � � � � � � � � � � � � � � � � � � � 6C13-Series Water-Cooled Package � � � � � � � � � � � � � � � � � 7General Information � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8

Inspection Of Equipment � � � � � � � � � � � � � � � � � � � � � � � � 8Handling � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8Location � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8Mounting And Setting In Place � � � � � � � � � � � � � � � � � � � � 8

Installation� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9Split Systems � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9Separation Of Sections � � � � � � � � � � � � � � � � � � � � � � � � � � 9Interconnecting Refrigerant Tubing � � � � � � � � � � � � � � � 10Single Package Unit Wiring� � � � � � � � � � � � � � � � � � � � � � 13Split System Wiring � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13Duct Connection� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13Pressure Switches � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13Water-Cooled Condensing Units � � � � � � � � � � � � � � � � � 13

Water-Cooled Condenser� � � � � � � � � � � � � � � � � � � � � � � 13Water Piping and Connections� � � � � � � � � � � � � � � � � � � 13Hook Up � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 14Water Connection� � � � � � � � � � � � � � � � � � � � � � � � � � � � � 14

Condensate Drain Connection � � � � � � � � � � � � � � � � � � � 14Maintenance Procedures� � � � � � � � � � � � � � � � � � � � � � � � 15Filters� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 15Cleaning The Water-Cooled Condenser� � � � � � � � � � � � 15Blowers � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 16Blower Motors� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 17Blower Speed Adjustment � � � � � � � � � � � � � � � � � � � � � � � 17Blower Motor Lubrication � � � � � � � � � � � � � � � � � � � � � � � 17Belts� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 18Refrigerant Systems� � � � � � � � � � � � � � � � � � � � � � � � � � � � 18Evaporator And Air-Cooled Condenser Coils � � � � � � � 18Minimum Service Access � � � � � � � � � � � � � � � � � � � � � � � 18Application Data � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 18

Hard Start Kit � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 18Sequence Of Operation � � � � � � � � � � � � � � � � � � � � � � � � � 19Cooling Sequence Of Operation � � � � � � � � � � � � � � � � � � 19Heat Pump Heating Sequence Of Operation � � � � � � � � 20Options � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 20Condensate Pump � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 20Thermostat � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 21Checking Hot Gas Bypass Valve� � � � � � � � � � � � � � � � � � 21Adjustment Of Hot Gas Bypass Valve � � � � � � � � � � � � � 22Microprocessor Controller � � � � � � � � � � � � � � � � � � � � � � 22Humidifier � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 22Electric Heat � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 22Electric Reheat � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 22Steam Coil � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 22Hot Water Coils� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 23Flooded Condenser � � � � � � � � � � � � � � � � � � � � � � � � � � � � 23Buck/Boost Transformer � � � � � � � � � � � � � � � � � � � � � � � � 23Chilled Water Valves Or Hot Water Valves � � � � � � � � � � 24Head Pressure Control Valves � � � � � � � � � � � � � � � � � � � 24Economizer Operation (Airside) � � � � � � � � � � � � � � � � � � 24

Economizer Operation � � � � � � � � � � � � � � � � � � � � � � � � � 24

Economizer Operation – (Waterside) � � � � � � � � � � � � � � 24Split Condenser / Condensing Sections � � � � � � � � � � � 24Vertical Stacking Unit� � � � � � � � � � � � � � � � � � � � � � � � � � � 25Troubleshooting � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 27Limited Warranty � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 31Limited Warranty for Hermetic Compressors � � � � � � � 32Limited Warranty Condensing Section � � � � � � � � � � � � 33Limited Warranty for Hermetic Compressors � � � � � � � 34Air-Cooled Unit � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 35Start-Up Procedures (R-410a Systems)� � � � � � � � � � 35–36Air-Cooled Unit � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 37Water-Cooled Unit � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 39Start-Up Procedures (R-410a Systems)� � � � � � � � � � 39–40Water-Cooled Unit � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 41Basic Model Designation� � � � � � � � � � � � � � � � � � � � � � � � 43

Page 4: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

4Subject to change without notice. 10.20-IM (0918)

Wiring Diagram

United CoolAir provides a wiring schematic for each unit produced� To retrieve the diagram for your unit please visit www�unitedcoolair�com, on your computer or mobile device, scroll to the footer section or Home/industry-resources, enter your serial number in the Serial Search field and press return to retrieve your product-wiring diagram.

Your serial number is a combination of the year, month and sequential order of build date�

This action will return the Model number, Job Number and the wiring diagram for viewing as well as downloading�

NOTE: Only units shipped since November 2016 are available on the site, for older units please contact the factory directly at 717-843-4311�

Page 5: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

5Subject to change without notice. 10.20-IM (0918)

Use of Symbols

The electrical hazard icon indicates the presence of an electrical hazard which could result in electrical shock or death�

The warning icon indicates a potentially hazardous situation which could result in death or serious bodily injury if not avoided�

The caution icon indicates a potentially hazardous situation which may result in minor or moderate injury if not avoided�

The information icon indicates a situation that may result in equipment or property damage� The information provided alerts the reader to relevant facts and/or conditions�

ELECTRICAL HAZARD

WARNING

CAUTION

INFORMATION

This publication includes warnings, cautions and information icons that point out safety related issues or conditions as well as other pertinent information relative to a safe installation, service or maintenance situation� The following icons should be interpreted as follows:

Important Notice

This manual is the property of the owner�

Please be sure to leave it with the owner when you leave the job�

Page 6: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

6Subject to change without notice. 10.20-IM (0918)

C13-Series Air-Cooled Package

Evaporator Section

TOP

FRONT RIGHT

REAR LEFT

S

B

J

P

G F

H

V

AA

AB AC

AD

Z X Y

K

L M N 1 1

A

1

Refrigerant Quick-Connect Access Panel

Condensate Drain

Filter Access

C

1⅛

D E 5

T R½

W

Clearance Hole for ⅜" Hanging Rod

TYP 8 PLS

Field Installation Power & Control Wiring

Evap Return

Air

Cond Air In

Evap Supply

Air

Cond Air Out

Elect Box

Coil Access Panel

Coil Access Panel

Motor & Blower Access Panel

Motor & Blower Access Panel

Elect Box

Condensing Section

Service Clearance

All SizesLeft Side 36"Right Side 36

Tons A B C D E F G H J K L M N P Q R S T V W X Y Z AA AB AC AD

2–3 78 56 22 44 34 119⁄16 20 1 59 7 25 1011⁄16 91⁄16 3¼ 57 40½ 1¾ 30½ 91⁄16 3½ 24 35⁄16 13¼ 119⁄16 7 111⁄16 19

4–5 86 64 25 46 40 13 9⁄16 25 0 67 81⁄16 31½ 123⁄8 91⁄16 3 65 42½ 1¾ 36½ 91⁄16 3½ 32 35⁄16 123⁄8 139⁄16 81⁄16 111⁄16 22

6–8 108½ 70½ 32 63 45½ 18¾ 31½ ¼ 73½ 65⁄8 39½ 161⁄16 613⁄16 15⁄8 71½ 59½ 1¾ 42 91⁄16 3½ 24 11⁄16 1811⁄16 16 97⁄16 111⁄16 29

Figure 1: Dimension Drawing

Page 7: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

7Subject to change without notice. 10.20-IM (0918)

C13-Series Water-Cooled Package

Evaporator Section

TOP

FRONT RIGHT

REAR LEFT

S

B

J

P

G F

H K

L M N 1 AK

AJOut

In

AHAE

Refrigerant Quick-Connect Access Panel

Condensate Drain

Filter Access

C

1⅛

EAF 5

T AG½

W

Clearance Hole for ⅜" Hanging Rod

TYP 8 PLS

Field Installation Power & Control

Wiring

Evap Return

Air

Evap Supply

Air

Elect Box

Elect Box

Coil Access Panel

Motor & Blower Access Panel

Compressor Access Panel

Cond Section

Service Clearance

All SizesLeft Side 36"Right Side 36

Tons B C E F G H J K L M N P Q R S T W AE AF AG AH AJ AK Water Piping In & Out

2–3 56 22 34 119⁄16 20 1 59 7 25 1011⁄16 91⁄16 3¼ 57 40½ 1¾ 30½ 3½ 50 16 12½ 6¼ 91⁄8 13 Ø⅞

4–5 64 25 40 13 9⁄16 25 0 67 81⁄16 31½ 123⁄8 91⁄16 3 65 42½ 1¾ 36½ 3½ 56 16 12½ 6½ 115⁄8 13 Ø11⁄8

6–8 70½ 32 45½ 18¾ 31½ ¼ 73½ 65⁄8 39½ 161⁄16 613⁄16 15⁄8 71½ 59½ 1¾ 42 3½ 56½ 20 16½ 71⁄8 10½ 17 Ø13⁄8

Figure 2: Water Cooled Dimension Drawing

Page 8: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

8Subject to change without notice. 10.20-IM (0918)

General Information

Inspection Of EquipmentUpon receipt of the unit, inspect for visible or concealed damage. Report any damage to the carrier, and file a damage claim�

HandlingTo facilitate handling, the unit is set on a wooden skid so that it may be picked up with a two-wheel hand truck or fork lift� Under no circumstances should the unit be “walked” on the corners of the skid� Use dolly trucks or pipe rollers to move the unit to its proper location�

LocationUnit can be installed either as a complete package or split into two sections. It can be either floor mounted or ceiling mounted�Before unit is installed, a thorough study should be made of the structure� Careful consideration must be given to location of wiring, condensate disposal, ductwork and accessibility to the unit for maintenance and servicing� It is necessary that a minimum clearance space be allowed on each side of the unit to accommodate maintenance and servicing� This minimum clearance must be 36" for all units. Attention must also be given to floor, ceiling or wall load limitations (See Figure 2)� Location should also provide for condensate removal, trapping and disposal�

Discharge Air from condenser coil should be deflected away from supply air to condenser, to prevent recirculation�

CAUTION

Unit should not be located in space subject to freezing temperatures�

Mounting And Setting In PlaceUnits can be shipped as an integral package with a tie rail attached to both sides of the unit at each of the four mounting channels�If unit is not to be split but is to be hung, do not remove tie rail. Use field supplied (3/8" minimum diameter) hanging rods, with proper washers and locknuts, then elevate unit to the exact location where it is to be installed� Fasten the rods securely to the supporting structure. Install field supplied vibration isolation as required� Level unit�If unit is to be floor mounted and not separated, do not remove tie rails� Locate on a level pad and secure as necessary� Field supplied unit isolation can be installed as required�

Page 9: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

9Subject to change without notice. 10.20-IM (0918)

Installation

1� Air conditioner is shipped assembled and ready for operation�

2� Unit contains a full charge of R-410a refrigerant�3� Install unit so that controls and side panels are

accessible to the operator and maintenance personnel�4� Run the condensate drain line by following the

guidelines on page 11�5� Electrical Wiring

a� Once the unit is installed, refer to the wiring diagrams which are provided on the backside of the control box covers�

b� Units are completely internally wired at the factory for commonly rated supply voltages� Check unit data tags for required voltage, wire and fuse sizing� The factory wiring terminates in two boxes; one each in the evaporator and condensing sections� These control boxes are located behind the outer access panels� Each is supplied with an individual control box cover with a wiring diagram attached inside�

c� All the units are provided with terminal blocks�d� The power wiring to the unit is to be brought through

one of the available holes for the unit electrical power connection(s)�

e� The control wiring is brought through the holes provided in the unit�

f� Supply wiring must comply with all National or Local codes� The power supply must be suitably fused for wire protection�

g� Use copper conductors only� The unit must be earth grounded using the ground lug provided in the electrical box� Metal conduit is not an acceptable ground�

h� Run the low voltage wiring from the thermostat to the unit� Connect to low voltage terminal block supplied� See “Thermostat” under “Options”, page 20�

Wire Size1 AWG� Gauge

22 20 19 18 16

40 120 150 190 305

Maximum Wire Length2 Feet

Note:1� Solid, Class II copper wire2� Based on a voltage drop of 1�2 volts per wire�3� Total wire length is from unit to room thermostat, and

back to unit�

FIGURE 3: Control Wire Sizes

Select a location to install the thermostat to avoid vibration, drafts, sun exposure, or internal heat sources� Use an inside wall�

Split SystemsIf the unit was ordered for a split system application each section will contain male resealable refrigerant fittings. Install the mating female fittings and field supplied tubing per the instructions that follow� Note that Optional Interconnect Kits are required for each circuit and external Hot Gas Bypass circuit�

Separation Of SectionsIf the unit is to be installed as a split system, the following steps must be carefully followed in performing the separation�1� Remove evaporator access panel�2� Using an open-end wrench and turning counter-

clockwise, disconnect the female half of the self-sealing couplings on both the suction and discharge lines� These are located in the bottom left area of the evaporator section� When there is a hot gas bypass option, that connection is to the right of the self-sealing coupling connections� There is one suction line, one liquid line, and one hot gas by-pass line (option) for each compressor�

Page 10: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

10Subject to change without notice. 10.20-IM (0918)

INFORMATION

Two circuit units have 2 groups of couplings� It’s a good idea to label or mark the various connections on both the evaporator and condensing sections BEFORE DISCONNECTING THE COUPLINGS to eliminate the possibility of intermixing the circuits when the interconnecting tubing is installed� The suction and discharge lines in the evaporator section will now be dangling, be careful not to damage the tubing connections� Do not disconnect the male half of the self-sealing couplings, which are still attached to the bulkhead of the condensing section�

3� Remove the unit top tie piece*, removing only those screws which attach the top piece to the two top panels� (*If unit is already shipped split, these are not included�)

4� Remove control box access panels from the evaporator section and the condensing section by removing the screws at the top and bottom of each access panel�

5� Disconnect and discard the wires which run between the two internal control boxes� Single circuit units will have two low voltage wires to be disconnected, dual units will have 3 low voltage wires� See Wiring Diagram on the inside of the evaporator control box access panels for disconnecting power wiring�

6� Remove the two unit tie rails attached to the unit mounting rails on each side of the unit�

7� Carefully pull the evaporator section away from the condensing section�

8� Verify that the self-sealing couplings are completely disengaged and not leaking refrigerant�

The sections may now be moved to their individual locations for installation (either floor-mounted or hung).

Interconnecting Refrigerant TubingAfter the separated sections have been installed, the field supplied interconnecting tubing can be run, using the self-sealing couplings supplied in the optional interconnecting tubing kit� For dual circuit units, two kits are supplied� It is recommended that some refrigerant oil be placed on the coupling threads (Item (10), Figure 5), to facilitate threading� The following instructions apply:1� Hand thread the female halves of the self-sealing

couplings (supplied with the interconnect tubing kit) onto the male couplings (fastened to the unit, Item (5), Figures 4 and 5)� Turn union nut (Item (11), Figure 5), approximately 1 to 1-1/2 turns� This is to make sure that the interconnecting tubing will be routed and brazed with the self-sealing couplings in their final proper location, so that there will be no difficulty when the final coupling assembly is made.

2� If there is a hot gas bypass option, connect that coupling the same way�

3� Run the interconnecting tubing required�

5

4

5

13 1015

4

11

14

1312

Figure 4: Disconnect/Connect Self-Sealing Coupling Figure 5: Install/Service Self-Sealing Coupling

Coupling Threads

Union Nut

Rubber Seal

Metal Seal

Page 11: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

11Subject to change without notice. 10.20-IM (0918)

Always follow accepted industry practices for sizing lines based on line length and elevation differences�Max� total equivalent line length = 100 ft� (a)Max� elevation difference between Evap� and Cond� = 40 ft� (a) (b)

Tons Suction Line Liquid Line2 Ton 3/4 1/23 Ton 7/8 1/24 Ton 1-1/8 1/25 Ton 1-1/8 5/86 Ton (2) 7/8 (2) 1/28 Ton (2) 1-1/8 (2) 1/2

a� Contact the factory for installations with elevation differences greater than 40 feet or total equivalent line lengths greater than 100 feet� Alternate line sizes and specific refrigerant components may be required�

b� If condensing section is 20 feet or more above the evaporator include an oil separator for each circuit�

Systems not ordered from the factory to be installed as a split system will contain Female Fittings on the evaporator section� Interconnect kit(s) must be ordered indicating that a Male / Female Kit is required�United CoolAir Corporation’s C13-Series horizontal units are provided with unique self-sealing fittings on the refrigerant lines between sections. These fittings or couplings allow the two-section unit to be separated and reconnected without loosing refrigerant charge�When installed as a split system, an interconnect kit is required for each refrigerant circuit or hot gas bypass line�If the unit is defined as a split system when ordered, the fittings will be male fittings on both sections. The interconnect kit will then consist of the matching female fittings. An interconnect kit is required for the field to connect refrigerant lines between both sections� Refrigerant piping between the sections is field supplied.The interconnect kit also contains four (4) Schrader fittings. The installer can place at least one in each refrigerant line or at the end of the refrigerant line� These enable the refrigerant line to be evacuated and charged as needed based on size and length�In some situations, the desired refrigerant line size may differ from the self-sealing fitting size provided. The line size should be reduced or enlarged at the self-sealing fittings as necessary

The drawing below illustrates a typical piping arrangementA� Male self-sealing fittings on unit sectionsB� Refrigerant piping between sections (field-supplied)C� Female self-sealing fittings in interconnect kit (4)D� Schrader fittings in interconnect kit (4)

FIGURE 6: Guidelines for Interconnecting Tubing Sizing

5� Disconnect and discard the wires which run between the two internal control boxes (Item (9), Figure 5)� Single circuit units will have two low voltage wires to be disconnected, dual and triple units will have 3 low voltage wires� See Wiring Diagram on the inside of the evaporator control box access panels (Item (7), Figure 3) for disconnecting power wiring�

6� Remove the two side cross-member angles (Item (1), Figures 3 and 5; and Item (2), Figure 4)�

7� Carefully pull the evaporator section away from the condensing section� Double check that the self-sealing couplings are completely disengaged�

The sections may now be moved to their individual locations, either floor-mounted or hung.

INFORMATION

NOTE: Installations may be made with up to 100 feet equivalent line lengths by installing the recommended tube sizes (See Figure 6) and adding the necessary additional refrigerant, R-410a for the field installed line set. (See Step 7, page 10)� For equivalent line lengths greater than 100 ft�, contact the factory for line sizing and additional refrigerant circuit accessories required�

Evaporator Section

Condensing Section

A

A

A

A

C

C

C

C

B

B

D

D

D

D

Page 12: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

12Subject to change without notice. 10.20-IM (0918)

INFORMATION

IMPORTANT! On units with more than one refrigerant circuit, be careful not to inter- mix liquid, suction and/or hot gas lines of the various circuits� If the connections were labeled before disconnecting the couplings, this should not be a problem� The 6 Ton and 8 Ton units have 2 circuits (with 2 suction line couplings and 2 liquid line couplings)�

CAUTION

When brazing tubing to the self- sealing couplings, use a water-soaked wet rag, running water bath or chill blocks on the quick-connects to prevent overheating the valves and damaging the seals� Always apply heat toward the field installed refrigerant line� Do not apply heat toward the coupling valve and seal�

INFORMATION

NOTE: The interconnect tubing kit (Figure 6) contains a sufficient number of Schrader access valves to permit installation of one Schrader in each end of both the liquid and suction lines of the field supplied tubing� Each interconnecting line (suction, liquid, or hot gas) must have at a minimum one Schrader access fitting. However for short lengths of tubing, only one Schrader in each line is necessary�

4� The suction line should be pitched downward to the compressor, sloping approximately 1/4" every ten feet to facilitate oil return�

5� “P” traps (field supplied) are required for all suction line risers every 15 feet� When the evaporator is above the condensing section, an inverted “P” trap should be incorporated as close as possible to the evaporator

(this minimizes floodback/oil slugging during the off cycle)� If the condensing section is more than 40 feet above the evaporator, consult the factory for specific refrigeration components�

6� Install the Schrader valve fittings into the tubing before brazing the couplings onto the ends of the tubing� Use a 1/4" hole to mount the valve. Clean and debur the tubing before doing any brazing to ensure that no chips or debris are left in the refrigerant circuit� Remove the Schrader valve cap and core before doing any brazing�

7� Leak check line sets with nitrogen at 500 psig� After brazing the tubing to the self-sealing coupling halves, evacuate each line to 300 microns� Check to make sure that each line holds a vacuum after removal of the vacuum pump (indicating no leaks) (micron level should not go above 500 microns within 10 minutes)� Add the appropriate charge of R- 410a Refrigerant using the Schrader valves� Wipe off coupling seals and threaded surfaces with a clean cloth to prevent the inclusion of dirt or foreign material into the system (See Figure 5)� Lubricate rubber seal (Item (14)) and metal seal (Item (15)) in the male halves (Item (5)) with refrigeration oil� Thread coupling halves together by hand to insure proper mating of threads� Continue to hand-thread each half-coupling to its mating half until resistance is felt (approximately 1-1/2 to 1-3/4 turns)� Complete the connection of the mating half-couplings with a wrench� The suction line couplings will be totally engaged after an additional 5-1/2 to 5-3/4 turns� The liquid line couplings will be totally engaged after an additional 4-1/2 to 4-3/4 turns�

8� Refrigerant piping shall be insulated in accordance with local codes and / or applicable ASHRAE Standards� Insulation exposed to weather shall be suitable for outdoor use� Provide protection from water and shielding from solar radiation as necessary�

9� Add R-410A refrigerant to the system to compensate for the additional interconnecting tubing as follows:a� For 3/8" liquid line – add 0.6 oz. per footb� For 1/2" liquid line – add 1.2 oz. per footc� For 5/8" liquid line – add 1.8 oz. per foot

Page 13: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

13Subject to change without notice. 10.20-IM (0918)

Single Package Unit WiringIf the system is to be installed as a single package unit route the low voltage wiring through the appropriate hole in the condensing section� A single power supply can be routed through the appropriate hole in the condensing section� The unit is factory wired internally for the evaporator� Refer to the unit data tag for power wiring minimum circuit ampacity and maximum fuse size� Power wiring must be wired through over current protective devices such as a circuit breaker or fused disconnect as required by the National Electric Code� A method to dis- connect main power such as a non-fused service disconnect must be installed within sight of the unit�

Split System WiringIf the unit was ordered for a split system application (condensing section remote from the evaporator section) each section will require separate power supplies� Route these through the appropriate holes for each section� Power wiring must be wired through over circuit protective devices such as a circuit breaker or fused disconnect as required by the National Electric Code� A method to disconnect main power such as a non-fused service disconnect must be installed within sight of the unit� Route the low voltage wiring through the appropriate holes in the evaporator section� Run the interconnecting low voltage wiring out of the evaporator section and through the appropriate hole in the condensing section�

INFORMATION

NOTE: Make sure to use the appropriate gauge of low voltage wire based on the total wire length so that no more than a 1�2 volt drop is experienced�

Duct ConnectionIt is recommended to use a flex collar or other means to isolate any unit vibration from being transmitted to the duct or structure�Ductwork and plenums shall be insulated in accordance with applicable ASHRAE standards or local codes�

Pressure SwitchesHigh PressureThis switch shuts the unit down in the event of excessive high pressure in the discharge line� A manual reset is required at the high pressure switch�

Low PressureThis switch shuts the unit down in the event of excessive low pressure in the suction line�

INFORMATION

NOTE: The low pressure switch(es) are connected to lock-out relay(s)� If the unit goes off on low pressure, the lock-out relay(s) must be reset by switching the thermostat to the “OFF” position and then back to the “COOL” position� Refer to the separate instructions for any units that incorporate a microprocessor for control�

INFORMATION

NOTE: Microprocessor controlled units do not incorporate a lock out relay� After resolving the high or low pressure situation reset the microprocessor as required� Consult separate manual for microprocessor control�

Water-Cooled Condensing UnitsWater-Cooled CondenserThe condenser is a tube-in-tube, chemically-cleanable configuration. The inner tube carries the water and the outer tube the refrigerant�

Water Piping and ConnectionsDo not reduce the water pipe sizes from the factory connections on the unit� Both the water inlet and outlet of the condensing section should be equipped with field supplied shut off ball valves� This is needed for shutdown of water supply during long periods of unit shutdown and/or condenser removal, if required�

INFORMATION

The condensate drain line should not be connected to the condenser outlet, as flooding is likely to occur. Provisions should be made for ease of piping cleaning by using plugged tees at all turns, rather than ordinary elbows�

Page 14: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

14Subject to change without notice. 10.20-IM (0918)

Hook UpEach refrigerant circuit requires 3 gallons per minute (GPM) of water per ton of refrigeration� If the unit does not have water regulating valves or head pressure control valves field supplied balancing valves may be required. For future reference when cleaning is needed, record details on temperatures entering and leaving the heat exchanger and the pressure drop as a new installation during the initial unit start-up� See “Cleaning The Water-Cooled Condenser” on page 13�

Water ConnectionInstall and connect a fresh water strainer (field supplied) to the water inlet line� Strainer should be readily accessible for periodic cleaning� Shut-off valves on both strainer inlet and outlet are recommended to facilitate cleaning�

CAUTION

High inlet water temperature or low water flow rate may result in nuisance tripping of the high pressure switch�

CAUTION

Water-cooled units with a glycol cooling fluid will require a higher GPM / Ton flow rate� Contact the factory for details�

INFORMATION

NOTE: Optional Head Pressure Control Valve(s) should be incorporated into the unit circuit(s) if the cooling fluid will be less than 65°F

WARNING

Water cooled units are for use with fresh water application only� Do not use for brackish water or salt water unless appropriate condenser has been installed as an option�

Condensate Drain ConnectionUnits are equipped with two 3/4" IPS drains; one for the evaporator condensate; one for the condensing section� All units require evaporator section drains to be installed� Heat pumps and water cooled condensing units also always require the installation of a condensing section drain� Units with air-cooled condensers need a condensing section drain when units are installed in areas which may permit rain to enter� It is EXTREMELY IMPORTANT that the lines attached to these connections contain a trap, to ensure positive draining� It is highly recommended that the trap be primed with water prior to start-up�The drain lines must be trapped because the coils are located on the negative sides of the blowers� The purpose of the condensate trap is to neutralize the negative pressure created within the cabinet by the blower�This negative pressure can vary from less than 1" up to 2" column. The condensate trap must be of sufficient depth in water column to permit the condensate to flow from the drain pan (See Figure 7)�The “A” dimension must equal or exceed the negative static pressure developed by the supply air blower� If it does not, the condensate will not drain properly and may overflow the drain pan. The trap must be at least 2-1/2" deep to maintain a water seal under all operating conditions, especially during blower start-up�

Figure 7: Condensate Trap Installation

Unit

"A"

2-1/2"

Page 15: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

15Subject to change without notice. 10.20-IM (0918)

Maintenance Procedures

FiltersDo NOT run unit without filters.Throw-away filters are supplied which are an Underwriters Laboratories Class 2 pleated extended surface type� Filters should be checked monthly for dirt accumulation and changed when necessary. Replacement filters must be the same type as originally supplied�In some situations, an external filter box will be incorporated or included in the mixing box�

UNIT FILTER SIZE/TYPE QUANTITY

2 & 3 Ton 25 X 20 X 2 1

4 & 5 Ton 20 X 16 X 2 2

6 & 8 Ton 20 X 16 X 2 4

Figure 8: Filter Sizes And Types

INFORMATION

NOTE: Unit must be shut off at the disconnect switch before the filters are serviced. Be sure to check that the air flow direction arrows on the filters point in the correct direction of airflow.

Cleaning The Water-Cooled CondenserCleaning a water cooled condenser helps to improve the heat transfer rate, reduce operational cost, restore efficiency, prolong heat exchanger life, and reduce pressure drop pumping cost� Deposits from water or water treatments, such as scale, lime, rust, or mud are removed�Each installation is unique. Therefore, the fluid quality and operating conditions will dictate when the heat exchanger needs to be cleaned�For future reference, it may be beneficial during the startup to record the water pressure drop across as well as the inlet and outlet water temperatures of the water condenser� After a period of time these values can be checked to see how much loss of operating performance has occurred� If a 10% or greater change has occurred it would be beneficial to clean the heat exchanger�

A 5% solution of Phosphoric Acid or Oxalic Acid can be considered for cleaning� However, there are several other commercially available environmentally safe products on the market that will do an excellent job� Contact your local wholesaler for availability� Follow all safety guidelines published by the cleaner manufacturer�There is a safety concern whenever using any chemical cleaner at elevated temperatures� The cleaner manufacturers recommend using the cleaners at 120°F or lower� Since the heat exchanger might be in operation just prior to the cleaning, it should be cooled to lower than the 120°F threshold� Due to the ability of the heat exchangers mass to hold heat, this may take a period of time� If possible, circulate cool water through the unit to help dissipate some of the heat�Check each field installed component to ensure the chemical cleaner will not damage them when the cleaner is circulated� For example, the structural makeup of the strainer may not stand up to the chemical detergent and rapidly deteriorate or fail to function after cleaning� If there is a possibility of this happening, use an alternative cleaner that all components will withstand or create another method of circulating the cleaner that would isolate the component in question from the cleaner� While cleaning the heat exchanger, it may also be a good idea to check and clean the strainer as well�

INFORMATION

NOTE: Do not chemically clean a refrigerant circuit�

1� Record performance values (Ref� following charts)� Turn off the fluid source.

2� Cool the heat exchanger, if above 120°F�3� Close the valves to and from the fluid circuit loop.4� Open the drain valve and drain all fluid from the heat

exchanger�5� Back flush the heat exchanger to remove any loose

particles�6� Attach pump and hoses as illustrated below, making

sure all fittings and connections are secure.7� Check all valving to make sure valves to system are

closed and valves for cleaning loop are open�8� Calculate the total gallons volume of the heat

exchanger and the piping using the following charts:

Page 16: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

16Subject to change without notice. 10.20-IM (0918)

NOMINAL PIPE SIZE

STD. STEEL PIPE VOLUME GAL./FT.

TYPE L COPPER TUBE

VOLUME GAL./FT.1/2" .0157 .01215/8" —— .01813/4" .0277 .02511" .0449 .0429

1-1/4" .0779 .06531-1/2" .1060 .0924

2" .1740 .16102-1/2" .2490 .2480

UNIT � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � _______GallonsPipe ( “) ______Gallons/ft x ______ft = _______GallonsPipe ( “) ______Gallons/ft x ______ft = _______GallonsPipe ( “) ______Gallons/ft x ______ft = _______Gallons TOTAL = ______ Gallons9� Calculate the volume of de-scaler required:

Water Quantity = 1/2 Total Gallons = _____Gallons De-Scaler Quantity = 1/2 Total Gallons = _____Gallons

10� Make sure pump is primed�11� Circulate the required quantity until fluid characteristics

indicate that de-scaling process is complete� Manufacturer’s instructions will provide details on this�

12� Disconnect pump, hoses and tank from heat exchanger�

13� Flush entire water system with water�14� Return heat exchanger and system components to

service. Check all valves and fitting connections.15� Record performance values: Before AfterPressure Drop ____________Psig ___________ PsigEntering Temp� ____________°F ___________ °FLeaving Temp� _____________°F ___________ °F

BlowersDisconnect power and lockout service before doing any service or maintenance�Air-cooled units are provided with adjustable belt drive blower packages for both the evaporator and condensing sections� Check that the blower wheel is tight on the shaft and does not contact the housing� Bearings are permanently sealed, but should be checked periodically for signs of wear� Check for restrictions or foreign material in the air circuit� The drive may be adjusted for different static pressures� If such an adjustment is made, check that the motor current draw does not exceed the motor nameplate current by more than 10%�

Heat Exchanger

Cleaning Solution

Pump

Figure 9: Cleaning Process Diagram

Page 17: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

17Subject to change without notice. 10.20-IM (0918)

INFORMATION

On units with three-phase fan motors, check for proper blower rotation at start-up� If they run backwards, interchange two of the incoming power leads�

Blower MotorsAll blower motors are equipped with thermal over- load protectors�

CAUTION

Open disconnects to unit, as motor will start when automatic thermal overload resets�

Blower Speed AdjustmentBlower speed may be changed by adjusting the variable diameter sheave provided on the blower drive motor� Sheave may be adjusted by removing the belt and loosening the setscrew located in the hub of the outer flange. With the setscrew loosened, the flange may be turned clockwise to increase blower speed and counter-clockwise to reduce blower speed

UNIT EVAPORATOR CFM CONDENSER CFM2 Ton 800 16003 Ton 1200 20004 Ton 1600 25005 Ton 2000 29006 Ton 2400 40008 Ton 3200 5200

Figure 10: Fan Capacities

CAUTION

Setscrew must be positioned directly above a flat section of the threaded sheave shaft before tightening to hold adjustment�

CAUTION

Reduction of airflow through excessive external air friction losses, lowered blower speed operation with dirty filters, or obstructed air flow may result in excessive condensation at air outlets, short cycling, or total unit shutdown due to evaporator coil icing�

INFORMATION

Verify that the motor current draw does not exceed the motor nameplate current by more than 10%�

Blower Motor LubricationMotor manufacturers indicate that motors never need re-lubrication, but if units run continuously, it is recommended that they be re-lubricated every 5500 hours for 3600 RPM motors and 10,000 hours for 1800 RPM motors� If unit motors are run in a cyclical manner, lubrication is recommended every 5 years�If the unit has been inactive or in storage for over a year, re-lubricate before starting�Use Polyrex EM, Texaco Polystar, Pennzoil Penn #2 or Chevron SRI #2 lubricant or equivalent in the following quantities: 0�6 cu� in� or 2 teaspoons, approximately 1 1/2 to 2 handle pumps using a standard grease gun� Keep grease clean, and do not mix dissimilar greases�Clean area around fitting. Remove purge plug (only on larger motors) for greasing, and replace after at least 20 minutes of operation after greasing� For safety, we recommend re-lubricating while the motor is stopped�Rotate the motor by hand as the grease is being applied to avoid air pockets� Over greasing, either in quantity or speed of injection, can cause premature bearing failure� Apply the recommended quantity of grease gradually�

CAUTION

Disconnect power and lockout service before doing any service or maintenance to the unit�

Page 18: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

18Subject to change without notice. 10.20-IM (0918)

BeltsDrive belts should be examined periodically for wear and for correct tension� Belts that are too tight cause bearing wear while belts that are too loose cause slippage� If the midpoint (midway between the blower and motor shaft) of the belt is pressed inward, there should be about 1/2" to a 1" of deflection when the belt is properly tensioned. Belt tension can be adjusted by means of the adjusting bolt, which requires loosening of a nut to move the motor and change belt position�

Refrigerant SystemsAll United CoolAir systems contain a liquid line sightglass� If bubbles appear in the sightglass, the system is either undercharged with refrigerant or there may be a restriction in the liquid line upstream of the sightglass� However, bubbles will appear every now and then in units with the hot gas bypass option� Bubbles will also appear upon compressor start up but normally clear to pure liquid after a few minutes of operation�The sightglass contains a moisture indicator which changes color when moisture is present in the system� This indicator is the circular dot in the center of the sight glass� If the color of this indicator is green, the refrigerant is normal� When the indicator is yellow, an abnormal condition exists such as moisture within the refrigerant circuit� If an abnormal appearance exists, servicing is required� See Figure 10 for unit charges�

INFORMATION

NOTE: After installation and during equipment start-up, the sight glass may appear pink or purple� This occurs during prolonged periods of non-operation and should turn blue after several hours (up to 12) of operation�

Evaporator And Air-Cooled Condenser CoilsCheck semi-monthly the condition of the face of both the evaporator and condenser coils�A dirty condenser coil will cause high condensing pressures, resulting in higher power consumption and possibly system shut-down by high-pressuresafety control� A dirty evaporator coil will reduce unit capacity and eventually will cause shut-down by the low pressure safety control�

Minimum Service AccessAll Service and Maintenance access is through both sides of the unit. 36" clearance is required.

Application Data208 / 230 460

Voltage Variation 187 / 253 414 / 504

Cooling (Air Over Evap.)

DB (Min./Max.) 45 / 120WB (Min./Max.) 57 / 72

Heat Pump (Air Over ID Coil) DB (Min./Max.) 50 / 80

Water-CooledGPM/Ton (Min./Max.) 2.5 / 3.5Leaving Water Temp.

(Min./Max.) 60 / 115

Hard Start KitA start assist device is utilized on all single-phase units� The purpose of this device is to assist the compressor in starting under low voltage conditions�A capacitor in conjunction with a Positive Temperature Coefficient (PTC) relay is installed across the run and start windings of the motor� The PTC device utilizes a ceramic element with a predictable thermal response to the introduction of electric current� When the compressor is called upon to start, the start capacitor provides a voltage boost to the start winding of the motor and causes the motor to turn� As the starting current is introduced across the start windings, the PTC element begins to warm� When the PTC device reaches approximately 250°F (corresponding to 0�6-0�8 seconds), the resistance in the element increases and creates an open switch that releases the start winding from the circuit and the motor continues to run� If the compressor does not start before the device heats to 250°F, it will not start until the PTC device cycles through a cool-down period (usually 2-3 minutes)� A compressor off-cycle timer is included in the electrical circuit for this purpose�The time delay relay also helps the refrigerant system pressures to equalize at the end of the run cycle� This helps the compressor during the starting process in that it is not attempting to start against a high discharge pressure�

INFORMATION

The installer should verify that this timer is set for 3 or more minutes�

Page 19: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

19Subject to change without notice. 10.20-IM (0918)

Sequence Of Operation

Cooling Sequence Of Operation1� Before starting the unit, make sure electrical power

has been turned on for a minimum of 24 hours� This assures that any liquid refrigerant is “driven” out of the crankcase�

2� For water-cooled units, make sure condenser water is available� Open all shut off valves and make sure all air is purged from the water circuit� Verify that cooling tower is functioning, if this is the source of condensing water supply� Start circulating the water to the water condenser�

3� The following sequence is based on the unit being controlled by a room thermostat� If another control type is being utilized, reference the instructions for that device may be required�a� Raise thermostat setpoint to highest level�b� Set System switch to “OFF” position�c� Set Fan switch to the “AUTO” position�d� Moving the Fan switch to the “ON” position should

cause the evaporator blower motor to run� Moving the Fan Switch back to “AUTO” should stop the blower�

e� Move the System switch to the “COOL” position� Slowly lower the thermostat setting to call for cooling� The evaporator blower should start (assuming the Fan switch is set to “AUTO”) and the System No� 1 compressor should start�

f� On those units with multiple compressors, if the thermostat setpoint continues to be lowered, the second compressor should then start�

g� Set room thermostat at desired space temperature and the Fan switch to “AUTO” or “ON”� The unit will cycle as required to maintain conditions�

4� Chilled water sequence is the same as above, except compressor activation is replaced by the chilled water valve function�

5� Heat pump cooling sequence is the same as above, except the reversing valve will also be activated when the compressor cycle is started�

Heating Sequence Of Operation (Other Than Heat Pump)1� The following sequence is based on the unit being

controlled by a room thermostat� If another control type is being utilized, reference the instructions for that device may be required�a� Lower thermostat setpoint to the lowest level�b� Set System switch to “OFF” position�c� Set Fan switch to “AUTO” position�d� Moving the Fan switch to the “ON” position should

cause the evaporator blower motor to run� Moving the Fan switch back to “AUTO” should stop the blower�

e� Move the System switch to the “HEAT” position� Slowly raise the thermostat setting to call for heating� The evaporator blower should start (assuming the Fan switch is set to “AUTO”) and the electric heating element will be activated�

f� On those units with a second stage of electric heat, if the thermostat setpoint continues to be raised, the second stage of electric heat should then be activated�

INFORMATION

NOTE: Units with more than one stage of electric heat require a two stage heat thermostat�

g� Set room thermostat at desired space temperature and set the Fan switch to “AUTO” or “ON”� The unit will cycle as required to maintain conditions�

Page 20: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

20Subject to change without notice. 10.20-IM (0918)

Heat Pump Heating Sequence Of Operation

INFORMATION

NOTE: Confirm that a heat pump thermo- stat has been used for this application�

CAUTION

Supplemental heat is recommended with all heat pump configurations.

1� Before starting the unit, make sure electrical power has been turned on for a minimum of 24 hours� This assures that any liquid refrigerant is “driven” out of the crankcase�

2� For water-cooled units, make sure condenser water is available� Open all shut off valves and make sure all air is purged from the water circuit� Verify that cooling tower is functioning, if this is the source of condensing water supply� Start circulating the water to the water condenser�

3� The following sequence is based on the unit being controlled by a room thermostat� If another control type is being utilized, reference to the instructions for that device may be required�a� Lower thermostat setpoint to the lowest level�b� Set System switch to “OFF” position�c� Set Fan switch to “AUTO” position�d� Moving the Fan switch to the “ON” position should

cause the evaporator blower motor to run� Moving the Fan switch back to “AUTO” should stop the blower�

e� Move the System switch to the “HEAT” position� Slowly raise the thermostat setting to call for heating� The evaporator blower should start (assumes Fan switch set to “AUTO”) and the System No� 1 compressor will start�

f� On those units with multiple compressors, if the thermostat setpoint continues to be raised, the second compressor should then start�

g� Set room thermostat at desired space temperature� Set the Fan switch to “AUTO” or “ON”� The unit will cycle as required to maintain conditions�

Options

Condensate PumpIf an optional condensate pump is to be used it will be mounted external to the unit� The pump incorporates mounting tabs for securing the pump in a suitable location�If the unit is an air source heat pump the unit drains from the evaporator and the condensing section will both have to go into the pump�

INFORMATION

NOTE: The condensate lines out of the unit, both evaporator and condenser, need to be trapped before going into the condensate pump�

Insert the condensate line(s) through one of the drain inlet holes of the pump sump� Make sure the condensate line does not interfere with the float. Cut an angle on the inlet tube so that it does not close off against the bottom of the pump (See Figure 11)�The pump has a built in check valve. Use 3/8" ID flexible plastic tubing from the pump to a suitable discharge location� Care should be taken not to kink the tubing as this will impede the flow of condensate out of the pump. Support the tubing as necessary with suitable clamps�Do not exceed the maximum lift of the pump which is 18 feet (35 GPH at 18´)� Provide an inverted “U” trap at the highest point of the tubing (See Figure 14)� Slope the discharge tubing downward to a point below the bottom of the condensate pump�The condensate pump has a grounded plug with a 6´ cord� Plug the condensate pump into a 115 volt outlet�Connect the low voltage leads of the auxiliary safety switch to the thermostat control circuit as shown on the unit wiring diagram� This will disrupt / shut down the unit operation until the cause of the high water condition can be rectified. In some situations an alarm (field supplied) should also be activated dependent upon the application�

Page 21: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

21Subject to change without notice. 10.20-IM (0918)

ThermostatStandard units (no heating) with one compressor require single stage thermostats, cool only� Units with two require dual stage thermostats, cool only�When a programmable thermostat is used, a sixth contact must be added to the terminal board in the evaporator section� Three connections must be made from this sixth contact… (1) to the programmable thermostat, (2) to a ground and (3) to the 24 volt coil of the evaporator fan motor contactor (K2)� See Figure 15�Heat pump units and units with auxiliary electric heat (either integral in unit or in duct) require single stage, cool/heat heat pump thermostats if units have only one compressor� Units with two compressors require dual stage heat pump thermostats with cool/ heat functions�

Figure 13: Adding Sixth Contact

Checking Hot Gas Bypass Valve1� Connect a calibrated thermocouple lead to the outlet

line at the hot gas bypass valve� Tie wrap and insulate the lead�

2� Connect a low pressure refrigerant gauge to the suction line�

3� Connect a high pressure refrigerant gauge to the liquid line�

4� Operate air conditioner in the cooling mode until system is stabilized� (Approximately 15 minutes)

5� If the high side pressure is not at or above 400 psig, block off the condenser inlet air stream until the pressure is above this threshold� This will simulate a system performance level close to the design condition of 95° F ambient�

6� The hot gas bypass valve setting is 104 psig�a� If the suction pressure is 104 psig the thermocouple

reading should be approximately 117° F or higher� Please note that it may be necessary to block off some of the evaporator air in order to check this condition�

b� If the suction pressure is above 104 psig the thermocouple reading should be less than 117° F�

c� If the suction pressure is below 104 psig the hot gas bypass valve should be adjusted to raise the pressure�

Cut tubing at an angle so that bottom of reservoir doesn’t close it� Be sure tubing does not interfere with float.

Figure 11: Condensate Tubing Termination

Figure 12: Condensate Pump and Trap Installation

18' Max�

To Drain

Inverted "U" Trap

Programmable ThermostatEvaporator

Section Enclosure

Terminal Board R

GY1

Y2

TC

K2 Evaporator Fan 24 Volt Coil

New Sixth Contact to be Added Ground

1

23

Page 22: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

22Subject to change without notice. 10.20-IM (0918)

Adjustment Of Hot Gas Bypass ValveThe function of the hot gas bypass valve is to prevent the suction pressure from falling below a per-determined set point, thereby balancing the system� The set point is typically 104 psig (R-410a)�Refer to the procedure below for Checking the Hot Gas Bypass Valve before proceeding� This will help to establish where the valve is currently set�1� Connect a low pressure refrigerant gauge to the suction

line�2� Operate air conditioner in the cooling mode until

system is stabilized� (Approximately 15 minutes)3� Remove the seal cap that covers the adjustment screw

of the hot gas bypass valve�4� Adjust the valve by turning the stem� A CLOCKWISE

turn will increase the pressure setting� A COUNTERCLOCKWISE turn will decrease the pressure setting� One complete turn is equal to approximately a 4 psi change� Adjustments should be made in small increments, allowing the system to stabilize after each turn�

5� Vary the evaporator load to test at various conditions that the suction pressure does not fall below the set point (104 psig for R-410a)�

6� Replace the seal cap on the hot gas bypass valve�

INFORMATION

NOTE:7� On split system applications the hot

gas bypass line to the evaporator should be insulated to prevent condensation�

8� Use a wet rag around the hot gas bypass valve when doing any brazing

Microprocessor ControllerFor units controlled by a microprocessor refer to the specific instructions for that device�

HumidifierThe optional steam humidifier that comes with the unit functions on the electrode principle. As water fills the plastic steam generator, it immerses metal electrodes which then permits electrical current flow through the water. This current flow produces heat which then boils the water into steam. This steam is then injected on the downstream side of the cooling coil to provide humidification for the area being served by the unit� Water is replenished through tubing and the 1/4" flare located on the evaporator coil panel structure. For further information on operation refer to the Humidifier Installation Instruction which accompanies the unit�

INFORMATION

NOTE: If the humidifier could be subjected to below freezing conditions as the result of outside air being introduced, the humidifier should not be located inside the unit air stream� Contact the factory for an externally mounted humidifier.

Electric HeatElectric heat is possible in two options� Option 1 is integrally built into the unit in the return air as a factory supplied option� A separate power supply is not required�Option 2 is field supplied and installed in the form of a duct heater� A duct heater must be installed a minimum of 4 feet downstream from the unit in the evaporator discharge / supply duct� A separate power supply will be required for the duct heater�

Electric ReheatOn a call for dehumidification the compressor comes on and the evaporator coil removes the moisture from the air passing through it� The electric heater then reheats the air passing through it to maintain the temperature in the space that needs to be conditioned

Steam CoilThe steam coil is located in the return air� The coil is copper tube/aluminum fin. Connections exit the cabinet at the coil location� Standard steam coils and non-freeze steam coils are available� Controls and valves for steam coils are supplied by others�

Page 23: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

23Subject to change without notice. 10.20-IM (0918)

Hot Water CoilsThe hot water coil is located in the return air� The coil is copper tube/aluminum fin. Connections exit the cabinet at the coil location� Controls and valves for hot water coils are supplied by others�

Flooded CondenserWhen the outdoor ambient temperature falls, the condensing pressure falls� This causes the discharge pressure to fall� Since the pressure differential across the thermostatic expansion valve port affects the rate of refrigerant flow, low discharge pressure generally causes insufficient refrigerant to be fed to the evaporator. Failure to have sufficient head pressure will result in low suction pressure and/or iced evaporator coils� The effective range for this option is down to -30°F�The purpose of a flooded condenser is to hold back enough of the condensed liquid refrigerant so that some of the condenser surface is rendered inactive� This reduction of active condensing surface results in a rise in condensing pressure and sufficient liquid line pressure for normal system operation�A three-way modulating valve and a receiver make up the flooded condenser refrigerant components.The valve is placed in the liquid line after the condenser� The receiver is downstream of the valve� The valve limits the flow of liquid refrigerant from the condenser while at the same time regulating the flow of discharge gas around the condenser to the receiver�During periods of low ambient operation, the receiver pressure falls until it approaches the setting of the control point of the valve (typically 295 PSIG for R-410a)� The valve then throttles to restrict the flow of liquid from the condenser. This raises the condenser pressure� Since it is the receiver pressure that is being maintained, the valve will then start to throttle open the discharge port when the differential between the condensing pressure and the receiver pressure exceeds 20 psi� The hot discharge gas serves to heat up the cold liquid being passed from the condenser to the receiver� Thus the liquid reaches the receiver warm and with sufficient pressure to assure proper expansion valve operation�The receiver is required to hold all of the excess/ additional liquid refrigerant in the system, since the refrigerant will be returned to the receiver when high ambient conditions exist�In the off-cycle the refrigerant can “migrate” to the condenser, during periods of low outdoor ambient� On a call for start-up, the evaporator pressure may not build up to the cut-in

point of the low pressure control� The result may be a failure of the compressor to start or to short cycle� To eliminate this potential problem, a time delay is added to bypass the low pressure switch during start-up to allow the discharge pressure to build in turn increasing the suction pressure�

Buck/Boost TransformerTable 5: Buck/Boost Transformer Table

United CoolAir Part Number LOAD Max. Size of

Fuse or Breaker

4CA1901KVA 1.44

10AAmps 6.25

4CA1902KVA 2.88

15AAmps 12.5

4CA1903KVA 4.31

20AAmps 18.75

4CA1904KVA 5.75

30AAmps 25.0

4CA1905KVA 8.63

40AAmps 37.5

4CA1906KVA 11.5

60AAmps 50.0

4CA1907KVA 17.25

80AAmps 75.0

Single-Phase

Figure 14: Transformer Wiring

Units being applied on a 277V-1PH-60Hz power supply require the use of a buck/boost transformer� The transformer will reduce the voltage from 277-1-60 to 230-1-60� The unit is supplied with components for 230-1-60 application� Table 1 lists the buck/boost transformers available from United CoolAir� Figure 16 illustrates the wiring for each transformer�

INPUT

OUTPUT

H4 H3H2 H1 X4 X3 X2 X1

Page 24: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

24Subject to change without notice. 10.20-IM (0918)

Chilled Water Valves Or Hot Water ValvesChilled water or hot water valves, if supplied by United CoolAir, are typically 2 way� The valve would be shipped loose for installation in the field. The valve is to be mounted in the outlet line of the coil�

Head Pressure Control ValvesStandard water-cooled units do not include a water regulating valve for head pressure control� However, if the incoming water to the unit will be at 65˚ or below, the unit should have been ordered with Head Pressure Control Valve(s)�A pressure transducer senses the liquid refrigerant pressure leaving the heat exchanger and sends a signal to a pressure controller� The controller then provides a modulating electrical signal to the head pressure control valve to adjust the valve open or closed to control the amount of water flow to maintain a refrigerant pressure set point (factory set to 360 psig)�The valve can be 2-way, 3-way or 2-way with a bypass solenoid for heat pump applications

Economizer Operation (Airside)The optional economizer setup utilizes outdoor air as much as possible to maintain the temperature in the space being conditioned� Airside Economizer uses outdoor air to condition the space when the outdoor air enthalpy is less than the indoor air enthalpy and the outdoor air enthalpy is less than the Economizer Module’s enthalpy set point� To ensure that the outside air conditions are suitable to operate in the airside economizer mode, an outdoor air enthalpy sensor and a return air enthalpy sensor must be installed at locations where they can continuously monitor outdoor air and return air conditions�The outdoor air enthalpy sensor must be mounted in ambient outdoor air at a location not influenced by radiant sunlight or other radiating elements� If outdoor air is continuously being supplied to the space being conditioned to satisfy minimum fresh air requirements required by specific codes, the Outdoor Air Enthalpy Sensor can be installed inside the outdoor air ducting; otherwise, it must be installed outdoors in the outdoor air intake plenum� Install the Return Air Enthalpy Sensor in the return air duct before the return air damper�

Economizer OperationWhen a call for cooling is initiated by the thermostat located in the space being conditioned, and if the enthalpy conditions are satisfied as sensed by the economizer module, the outdoor air provided for cooling the space could be from a small portion up to 100% total air flow of outdoor air. The determination of how much outdoor air to use for cooling is determined by additional sensors that monitor mixed and discharge air temperatures�These additional sensors are optional and when they are used in the application, they limit the discharge air temperature so that the discharge air does not become too cold� If these optional sensors are not used, the module will drive the dampers completely open for economizer and use as much cold outdoor air as possible� Refer to the additional instructions provided and electrical diagrams for installation of Economizer Module, Enthalpy Sensors, and Setup and Operating Instructions�When the indoor air conditions are better than the outdoor air conditions the Economizer Module will send a signal to the compressors to use mechanical cooling instead of economizer and limit the amount of outdoor air provided to the setting of the minimum outdoor air set point�

Economizer Operation – (Waterside)The waterside economizer is also referred to as a “free cooling coil”�The free cooling coil is installed before the DX cooling coil in the return air stream�A sensor is provided in the water inlet side of the water cooled condenser� If the incoming water temperature is below the control setpoint, a normally closed solenoid valve opens and lets the water pass through the free cooling coil� The refrigerant circuit is deactivated during the free cooling economizer operation�

Split Condenser / Condensing SectionsCondensers (without compressors) or condensing sections (with compressors) are available for split applications, both air and water-cooled� For condensers/condensing units to be used with evaporator sections, other than United CoolAir products, the units are supplied with the refrigerant lines capped with only a holding charge of nitrogen�

Page 25: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

25Subject to change without notice. 10.20-IM (0918)

Vertical Stacking UnitThe vertical stacking option is designed for installations where floor space is minimal and a ceiling space is not available� The evaporator section is placed above the condensing section for location in small spaces� Evaporator discharge air is available through the front or top for easy duct installation�

INFORMATION

NOTE: For other sheet metal arrangements,contact your local sales office.

A rigid frame system supports the evaporator and provides vibration-free operation� Quick-connect couplings allow the unit to be split in the field, if needed, for installation. The interconnecting wiring is protected by a cover�The stacking units are available in all air-cooled models�

Page 26: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

26Subject to change without notice. 10.20-IM (0918)

S

Eva

pora

tion

Sec

tion

Con

dens

ing

Sec

tion

T

R

B

P

G

H

Evap Return

Air

Cond Air Out

Cond Air In

Evap Supply

AirF

K

J

AA AD

E

Condensate Drain

Coil Access Panel

Coil Access Panel

Filter AccessC

1 D1⅛

5

ACABV Z X Y

L M N 1

1AM

Elect Box

Elect Box

Motor & Blower Access Panel

Motor & Blower Access Panel

TOP

FRONT

REAR

Field Installation Power & Control

Wiring

RIGHT

LEFT

Clearance Hole for ⅜" Hanging Rod

Typ 8 Pls

½

Service Clearance All SizesLeft Side 36"Right Side 36"

TONS B C D E F G H J K L M N P2-3 56 22 44 34 11 5⁄16 20 1 59 7 25 10 11⁄16 9 1⁄16 3 ¼4-5 64 25 46 40 13 9⁄16 25 0 67 8 1⁄16 31 ½ 12 ⅜ 9 1⁄16 36-8 70 ½ 32 63 45 ½ 18 ¾ 31 ½ ¼ 73 ½ 6 5⁄8 39 ½ 16 1⁄16 6 13⁄16 1 5⁄8

TONS Q R S T V X Y Z AA AB AC AD AM2-3 57 40 ½ 1 ¾ 30 ½ 9 1⁄16 24 3 5⁄16 13 ¼ 11 9⁄16 7 1 11⁄16 19 46 5⁄16

4-5 65 42 ½ 1 ¾ 36 ½ 9 1⁄16 32 3 5⁄16 12 ⅜ 13 9⁄16 8 1⁄16 1 11⁄16 22 52 5⁄16

6-8 71 ½ 59 ½ 1 ¾ 42 9 1⁄16 24 1 1⁄16 18 11⁄16 16 9 7⁄16 1 11⁄16 29 66 5⁄16

Figure 18: Outline Dimensions For Air-Cooled vertical Stacking Units

Page 27: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

27Subject to change without notice. 10.20-IM (0918)

Troubleshooting

WARNING

Turn OFF power to unit before conducting any troubleshooting, unless the tests you are performing require system operation� Keep hands, clothing and tools clear of electrical terminals and rotating components�

ITEM CODE PROBLEM PROBABLE CAUSE SOLUTION

1 Control is erratic. Wired improperly or connections are broken Check wiring connections against schematic diagram.

2 Blower fails to start.Defective contactor Overload tripped Marvel alarm

Repair or replace contactor.Reset and check cause.Clear alarm(s) after correcting problem.

3 Compressor fails to start.

Thermostat set too highComplete loss of refrigerant chargeHead pressure too high (high pressure switch open)PTCR will keep compressor OFF for 3 - 5 minutesLow line voltage causing compressor to overheat and trip on thermal overload

Adjust to desired temperature.Repair leak and recharge refrigerant system.Check condenser for obstructions and remove. Check for the required water flow through the water regulating valve and the condenser coil. Manually reset thermostat. With Marvel, turn off alarm and reset.Wait for PTCR to cool off. Compressor should start in 3 - 5 minutes.Stop unit and troubleshoot power supply and compressor circuit for low voltage. Please note that it may take the compressor an hour or more for the thermal overload to reset itself.

4 Compressor short cycles.

Drain pan switch openLow line voltage causing compressor to overheatDry or icy evaporator coil (reduced air flow)Lack of refrigerant (bubbles in sight glass)Short cycling of conditioned air

Check if the unit is draining properly.Check power source for cause of electric variation of line voltage.Defrost and clean coil and replace dirty filters.Check for leak. Repair and recharge the systemMake sure that duct connections are proper for return air and supply air and ensure that they do not mix with each other.

NOTE: For operating and troubleshooting instructions for Marvel Controller or humidifier, refer to specific operating instructions that accompany the unit.

Page 28: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

28Subject to change without notice. 10.20-IM (0918)

ITEM CODE PROBLEM PROBABLE CAUSE SOLUTION

5 Evaporator coil ices.

Lack of proper air quantity

Low return air temperature

Low refrigerant charge

Check filters: Clean or replace if necessary. Check for obstruction across coil. Check rotation of evapo-rator blower to ensure correct rotation of evaporator blowers.Raise return air set point or check for short cycling of supply air.Check for leaks and repair and recharge the system.

6 Noisy compressor

Expansion valve stuck in open position (cold suction line)

Broken compressor valve (compressor knocking)Worn or scarred compressor bearingsLiquid slugging

Excessive head pressure

Ensure thermal expansion valve bulb is tight on suction line. Con- firm that bulb is located properly on suction line. Check operation and superheat.Replace compressor.

Replace compressor.System overcharged. Reclaim excess refrigerant from the high side of the systemReduce head pressure (see item 8 below).

7 System short of capacity

Flash gas in liquid line (bubbles in sight glass)Expansion valve stuck open or possibly obstructedClogged filter drierIce or dirt on evaporator coil

Head pressure control valve not fully open

Condenser coil dirty

Check for leaks. Repair and re- charge the system. Check sub- cooling.Replace Valve.

Replace with new filter-drier.Defrost or clean evaporator coil or replace dirty filter.Make sure that the required GPM of water flows through the condensing sectionClean condenser coil

Page 29: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

29Subject to change without notice. 10.20-IM (0918)

ITEM CODE PROBLEM PROBABLE CAUSE SOLUTION

8 Head pressure too high

Air or other non-condensable gas in system

Condenser air intake blockedOvercharge of refrigerant

Condenser fan not operating

Condenser water not circulating Condenser blower running backwards

Evacuate system and recharge. Install new filter-drier.Clean away debris.Reclaim excess from high pressure side of the system.Check power to motor and ensure correct rotation of blower.Check water regulating valve and adjust Check phase of incoming power to unit (3 ph units only). Reverse any two incoming power supply wires (except ground).

9 Head pressure too low See Item 3, 4, & 7 above Correct as indicated

10 Suction pressure too low

Flash gas in liquid line (bubbles in sight glass) due to a leak.Obstructed expansion valveLoss of fluid within expansion valve bulb.Clogged filter-drierIce or dirt on evaporator coil Evaporator blower running backwards

Repair leak and recharge.

Repair or replace valve.Replace power head and valve.Replace with new filter-drier.Defrost and clean evaporator coil and replace filter.Check phase of incoming power to unit (3 ph units only). Reverse any two incoming power supply wires (except ground).

11 Heater inoperative

Thermostat set too lowCircuit breaker tripped or blown

Heater high limit switch open

Heat elements burned out

Adjust thermostat to the desired temperature.Check for electrical short. . Replace breaker if defective.Insufficient air across heater elements. Check for obstructed or dirty filters.Check continuity with OHM meter. Replace heater element.

12 Water carry over Excessive air through unit Reduce CFM to unit specifications.

Page 30: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

30Subject to change without notice. 10.20-IM (0918)

ITEM CODE PROBLEM PROBABLE CAUSE SOLUTION

13 System short of capacity in free cool (water coil) mode

Check for control wiring to the free cool solenoid valve.Low water flow rate

Check wiring diagram and rewire.

Check source of water flow.

14 Condensate Pump does not run

Check to see that power to the pump is present.Float not able to move freely.Dirt or algae not allowing float to activate pump.

Locate and repair electrical connection problem.

Clean pump and float.Clean pump and float.

15 Condensate Pump runs with no discharge

Tubing blocked or kinked Check valve blocked Inpeller blockedTubing elevation or run exceeds head capability

Inspect, clean or straighten as necessary. Clean check valve.Remove debris from pump impeller.Verify tubing run is within pump head limitations.

16 Lock out relay tripped

High or low pressure condition exists Refer to items 8 & 10 above.Manually turn off system at thermostat and then back on to reset. Manually reset high pressure switch if tripped.

Page 31: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

31Subject to change without notice. 10.20-IM (0918)

Limited WarrantyImportant Notice!This Limited Warranty specifically provides that all installation, operation and repairs of product and parts covered under this limited warranty must be made with authorized parts and by a licensed HVAC service provider� The product(s) must be properly installed, and maintained by a licensed HVAC service provider in accordance with the installation, operation, and maintenance instructions provided by United CoolAir Corporation. Failure to conform to such specifications and/or instructions shall void this limited warranty� United CoolAir may request written documentation showing the proper preventative maintenance� United CoolAir warrants this product to be free from defects in factory workmanship and material under normal use and service and will, at its option, repair or replace any parts that prove to have such defects within a period of one (1) year from the date of product installation� This warranty extends only to the original consumer purchaser in accordance with the then current Terms and Conditions and is non-transferable�For this warranty to apply, the product must be installed according to United CoolAir recommendations and specifications, and in accordance with all local, state, national and provincial codes� The product must not be moved from its original place of installation� The replacement part assumes the unused portion of this warranty�This limited warranty applies only to products installed in the continental United States, Alaska, Hawaii and Canada�

ExclusionsThis Limited Warranty does not cover any:1� Shipping, labor or material charges�2� Damages resulting from transportation, installation or

servicing�3� Damages resulting from accident, abuse, fire, flood,

alteration or acts of God�4� Tampering with, altering, defacing or removing the

product serial number will serve to void this warranty�5� Damages resulting from use of the product in a

corrosive atmosphere (such as concentrations of acids or halogenated hydrocarbons)�

6� Damages resulting from inadequacy or interruption of electrical service, improper voltage conditions, blown fuses, or other like circumstances�

7� Cleaning or replacement of filters or belts.8� Damages resulting from failure to properly and

regularly clean air and/or water side of condenser and evaporator�

9� Damages resulting from: (I) freezing of condenser water or condensate; (II) use of corrosive water; (III)

fouling or restriction of the air/water circuit by foreign material or like causes�

10� Damages resulting from operation with inadequate or interrupted supply of air or water�

11� Damages resulting from use of components or accessories not approved by United CoolAir�

12� This warranty does not apply to the installation, plumbing and wiring not integral to the product�

13� Damages resulting from improper application or sizing of unit�

This warranty is in lieu of all other warranties, expressed or implied, including the implied warranties of merchantability and fitness for a particular purpose.Some states (provinces) do not allow the disclaimer of implied warranty, so that the above disclaimer may not apply to you�Some states (provinces) allow only a partial limitation on implied warranties to limit the duration of implied warranties to the duration of the express warranty� In such states (provinces), the duration of implied warranties is hereby expressly limited to the duration of the express warranty on the face hereof�In no event, whether as a result of breach of warranty or contract, tort (including negligence) strict liability or otherwise, shall United CoolAir be liable for special, incidental, or consequential damages, including but not limited to loss of use of the equipment or associated equipment, lost revenues or profits, cost of substitute equipment or cost of fuel or electricity� The above limitations shall inure to the benefit of United CoolAir’s suppliers and subcontractors. The above limitation on consequential damages shall not apply to injuries to persons in the case of consumer goods�Some states (provinces) do not allow the exclusion or limitation of liability for consequential damages, or for strict liability in tort, so that the above exclusions and limitations may not apply to you�United CoolAir does not assume, or authorize any other person to assume for United CoolAir, any other liability for the sale of this product�This warranty gives you specific legal rights. You may also have other rights which vary from state to state (province to province)�

To obtain warranty serviceContact the installing or servicing contractor with the details of the problem� Provide the model number, serial number and date of installation� Warranty requests directed to the factory will be referred back through the local distribution network�

Model: ______________ Serial Number: _______________ Date of Installation: ________

Page 32: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

32Subject to change without notice. 10.20-IM (0918)

Limited Warranty for Hermetic Compressors

United CoolAir warrants the hermetic compressor in this product to be free from defects in factory workmanship and material under normal use and service and will, at its option, repair or replace the hermetic compressor if it proves to have such defects within a period of five (5) years from the date of product installation� This warranty extends only to the original consumer purchaser in accordance with the then current Terms and Conditions and is non-transferable� If a United CoolAir unit is matched with another manufacturers unit the compressor warranty is limited to 1 year form the date of product installation�For this warranty to apply, the product must be installed according to United CoolAir recommendations and specifications, and in accordance with all local, state, national and provincial codes� The product must not be moved from its original place of installation� The replacement part assumes the unused portion of this warranty�This limited warranty applies only to products installed in the continental United States, Alaska, Hawaii and Canada�

ExclusionsThis Limited Warranty does not cover any:1� Shipping, labor or material charges�2� Damages resulting from transportation, installation or

servicing�3� Damages resulting from accident, abuse, fire, flood,

alteration or acts of God�4� Tampering with, altering, defacing or removing the

product serial number will serve to void this warranty�5� Damages resulting from use of the product in a

corrosive atmosphere (such as concentrations of acids or halogenated hydrocarbons)�

6� Damages resulting from inadequacy or interruption of electrical service, improper voltage conditions, blown fuses, or other like circumstances�

7� Cleaning or replacement of filters or belts.8� Damages resulting from failure to properly and

regularly clean air and/or water side of condenser and evaporator�

9� Damages resulting from: (I) freezing of condenser water or condensate; (II) use of corrosive water; (III) fouling or restriction of the air/water circuit by foreign material or like causes�

10� Damages resulting from operation with inadequate or interrupted supply of air or water�

11� Damages resulting from use of components or accessories not approved by United CoolAir�

12� This warranty does not apply to the installation, plumbing and wiring not integral to the product�

13� Damages resulting from improper application or sizing�This warranty is in lieu of all other warranties, expressed or implied, including the implied warranties of merchantability and fitness for a particular purpose.Some states (provinces) do not allow the disclaimer of implied warranty, so that the above disclaimer may not apply to you�Some states (provinces) allow only a partial limitation on implied warranties to limit the duration of implied warranties to the duration of the express warranty� In such states (provinces), the duration of implied warranties is hereby expressly limited to the duration of the express warranty on the face hereof�In no event, whether as a result of breach of warranty or contract, tort (including negligence) strict liability or otherwise, shall United CoolAir be liable for special, incidental, or consequential damages, including but not limited to loss of use of the equipment or associated equipment, lost revenues or profits, cost of substitute equipment or cost of fuel or electricity� The above limitations shall inure to the benefit of United CoolAir’s suppliers and subcontractors. The above limitation on consequential damages shall not apply to injuries to persons in the case of consumer goods�Some states (provinces) do not allow the exclusion or limitation of liability for consequential damages, or for strict liability in tort, so that the above exclusions and limitations may not apply to you�United CoolAir does not assume, or authorize any other person to assume for United CoolAir, any other liability for the sale of this product�This warranty gives you specific legal rights. You may also have other rights which vary from state to state (province to province)�

To obtain warranty serviceContact the installing or servicing contractor with the details of the problem� Provide the model number, serial number and date of installation� Warranty requests directed to the factory will be referred back through the local distribution network�

Model: ______________ Serial Number: _______________ Date of Installation: ________

Page 33: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

33Subject to change without notice. 10.20-IM (0918)

Limited Warranty Condensing SectionUnited CoolAir warrants this product to be free from defects in factory workmanship and material under normal use and service and will, at its option, repair or replace any parts that prove to have such defects within a period of one (1) year from the date of product installation, to begin no later than six (6) months after product shipment from the factory� This warranty extends only to the original consumer purchaser in accordance with the then current Terms and Conditions and is non-transferable�For this warranty to apply, the product must be installed according to United CoolAir recommendations and specifications, and in accordance with all local, state, national and provincial codes� The product must not be moved from its original place of installation� The replacement part assumes the unused portion of this warranty�This limited warranty applies only to products installed in the continental United States, Alaska, Hawaii, Puerto Rico and Canada�

EXCLUSIONSThis Limited Warranty does not cover any:1� Shipping, labor or material charges�2� Damages resulting from transportation, installation or

servicing�3� Damages resulting from accident, abuse, fire, flood,

alteration or acts of God�4� Tampering with, altering, defacing or removing the

product serial number will serve to void this warranty�5� Damages resulting from use of the product in a corrosive

atmosphere (such as concentrations of acids or halogenated hydrocarbons)�

6� Damages resulting from inadequacy or interruption of electrical service, improper voltage conditions, blown fuses, or other like circumstances�

7� Cleaning or replacement of filters or belts.8� Damages resulting from failure to properly and regularly

clean air and/or water side of condenser and evaporator�9� Damages resulting from: (I) freezing of condenser water

or condensate; (II) use of corrosive water; (III) fouling or restriction of the air/water circuit by foreign material or like causes�

10� Damages resulting from operation with inadequate or interrupted supply of air or water�

11� Damages resulting from use of components or accessories not approved by United CoolAir�

12� This warranty does not apply to the installation, plumbing and wiring not integral to the product�

13� Damages resulting from improper application or sizing of unit�

14� In the event that the refrigerant type is changed, as a result of a compressor failure and the same type of compressor is not available, any subsequent refrigerant circuit component failures will not be covered under the Limited Warranty�

This warranty is in lieu of all other warranties, expressed or implied, including the implied warranties of merchantability and fitness for a particular purpose.Some states (provinces) do not allow the disclaimer of implied warranty, so that the above disclaimer may not apply to you�Some states (provinces) allow only a partial limitation on implied warranties to limit the duration of implied warranties to the duration of the express warranty� In such states (provinces), the duration of implied warranties is hereby expressly limited to the duration of the express warranty on the face hereof�In no event, whether as a result of breach of warranty or contract, tort (including negligence) strict liability or otherwise, shall United CoolAir be liable for special, incidental, or consequential damages, including but not limited to loss of use of the equipment or associated equipment, lost revenues or profits, cost of substitute equipment or cost of fuel or electricity� The above limitations shall inure to the benefit of United CoolAir’s suppliers and subcontractors. The above limitation on consequential damages shall not apply to injuries to persons in the case of consumer goods�Some states (provinces) do not allow the exclusion or limitation of liability for consequential damages, or for strict liability in tort, so that the above exclusions and limitations may not apply to you�United CoolAir does not assume, or authorize any other person to assume for United CoolAir, any other liability for the sale of this product�This warranty gives you specific legal rights. You may also have other rights which vary from state to state (province to province)�

To obtain warranty serviceContact the installing or servicing contractor with the details of the problem� Provide the model number, serial number and date of installation� Warranty requests directed to the factory will be referred back through the local distribution network�

Continued on Next Page

Model: ______________ Serial Number: _______________ Date of Installation: ________

Page 34: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

34Subject to change without notice. 10.20-IM (0918)

Limited Warranty for Hermetic CompressorsUnited CoolAir warrants the hermetic compressor in this product to be free from defects in factory workmanship and material under normal use and service and will, at its option, repair or replace the hermetic compressor if it proves to have such defects within a period of one (1) year from the date of product installation, to begin no later than six (6) months after product shipment from the factory� This warranty extends only to the original consumer purchaser in accordance with the then current Terms and Conditions and is non-transferable�For this warranty to apply, the product must be installed according to United CoolAir recommendations and specifications, and in accordance with all local, state, national and provincial codes� The product must not be moved from its original place of installation� A second compressor failure in the same refrigerant circuit is indicative of an application issue and will not be covered under the Limited Warranty�This limited warranty applies only to products installed in the continental United States, Alaska, Hawaii, Puerto Rico and Canada�

EXCLUSIONSThis Limited Warranty does not cover:1� Shipping, labor or material charges�2� Damages resulting from transportation, installation or

servicing�3� Damages resulting from accident, abuse, fire, flood,

alteration or acts of God�4� Tampering with, altering, defacing or removing the

product serial number will serve to void this warranty�5� Damages resulting from use of the product in a

corrosive atmosphere (such as concentrations of acids or halogenated hydrocarbons)�

6� Damages resulting from inadequacy or interruption of electrical service, improper voltage conditions, blown fuses, or other like circumstances�

7� Cleaning or replacement of filters or belts.8� Damages resulting from failure to properly and

regularly clean air and/or water side of condenser and evaporator�

9� Damages resulting from: (I) freezing of condenser water or condensate; (II) use of corrosive water; (III) fouling or restriction of the air/water circuit by foreign material or like causes�

10� Damages resulting from operation with inadequate or interrupted supply of air or water�

11� Damages resulting from use of components or accessories not approved by United CoolAir�

12� This warranty does not apply to the installation, plumbing and wiring not integral to the product�

13� Damages resulting from improper application or sizing�14� Discharge air temperature control, if not provided by

the factory, will void the compressor Limited Warranty�15� In the event that the refrigerant type is changed, as

a result of a compressor failure and the same type of compressor is not available, any subsequent compressor failures will not be covered under the Limited Warranty�

This warranty is in lieu of all other warranties, expressed or implied, including the implied warranties of merchantability and fitness for a particular purpose.Some states (provinces) do not allow the disclaimer of implied warranty, so that the above disclaimer may not apply to you�Some states (provinces) allow only a partial limitation on implied warranties to limit the duration of implied warranties to the duration of the express warranty� In such states (provinces), the duration of implied warranties is hereby expressly limited to the duration of the express warranty on the face hereof�In no event, whether as a result of breach of warranty or contract, tort (including negligence) strict liability or otherwise, shall United CoolAir be liable for special, incidental, or consequential damages, including but not limited to loss of use of the equipment or associated equipment, lost revenues or profits, cost of substitute equipment or cost of fuel or electricity� The above limitations shall inure to the benefit of United CoolAir’s suppliers and subcontractors. The above limitation on consequential damages shall not apply to injuries to persons in the case of consumer goods�Some states (provinces) do not allow the exclusion or limitation of liability for consequential damages, or for strict liability in tort, so that the above exclusions and limitations may not apply to you�United CoolAir does not assume, or authorize any other person to assume for United CoolAir, any other liability for the sale of this product�This warranty gives you specific legal rights. You may also have other rights which vary from state to state(province to province)�

To obtain warranty serviceContact the installing or servicing contractor with the details of the problem� Provide the model number, serial number and date of installation� Warranty requests directed to the factory will be referred back through the local distribution network�

Model: ______________ Serial Number: _______________ Date of Installation: ________

Page 35: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

35Subject to change without notice. 10.20-IM (0918)

Air-Cooled Unit

Start-Up Procedures (R-410a Systems)Some of the numbered items below are referenced on the Start Up Form that needs to be completed�This procedure has been created based on utilizing a standard wall thermostat� If another controller is being utilized some of the steps below may need to be altered�1� Start up must be performed by a qualified HVAC

Technician�2� Make certain that all power is disconnected at the main

power circuit breaker or service disconnect before starting any of this procedure�

3� Check all electrical screw terminals and wiring lugs for tightness internal to the equipment� Components may have loosened due to vibration during transit or handling� Verify that the main power block lug connections made in the field are tight and secure.

4� Confirm that the voltage rating of the equipment data tag coincides with the power that will be delivered to the unit�

5� Verify that the circuit protection for the unit satisfies Local and National Codes according to the unit data tag Minimum Circuit Ampacity (MCA) and Maximum Fuse Size (MFS)�

6� Locate the unit thermostat and check all electrical terminations against the unit electrical diagram and for the unit thermostat�

Note: If using a digital thermostat with a “C” (Common) terminal, this terminal MUST be terminated to the “C” terminal in the unit� Failure to do so will result in the thermostat shorting out and being destroyed�

7� Leak check the refrigerant system� While the unit was leak checked at the factory, leaks can develop during transit and / or handling�

8� Confirm that the unit condensate has been adequately trapped and taken to a suitable point for disposal�

9� Verify that the filters are in place, clean and usable.10� Switch the unit thermostat to the “OFF” position�11� Apply power to the unit� Switch the circuit breaker or

field supplied electrical service disconnect switch to the on position�

Note: If the unit has the flooded condenser option the scroll compressors will have crankcase heaters� If the outdoor ambient is 70˚ F or lower, let the compressors sit for approximately 24 hours before proceeding�

12� Record the voltage at the unit terminals�13� If possible with the thermostat provided, switch the

evaporator blower to the RUN position� Verify that the evaporator blower is activated�

14� Verify that the evaporator blower is rotating in the correct direction (three phase units only)�

Note: If the evaporator blower motor runs backwards, shut off all power to the unit� Switch any two of the incoming power leads at the unit terminal block� The unit has been wired and phased properly at the factory� DO NOT change any factory wiring to correct for a phase problem�

Note: Before conducting the following start up sections connect a suitable refrigerant gauge set to the unit Schrader connections� Install temperature sensors to record the appropriate refrigerant line temperatures� Service gauge access ports have been provided in the cabinet corner posts so that the gauge line hoses can be run outside the cabinet with the access panels installed�

15� Set the thermostat switch to a temperature set point approximately 5˚ lower than the space temperature. Set the thermostat fan switch to the AUTO position� Set the thermostat operating mode to the COOL position� This should energize the compressor(s) and both blowers�

Note: Dependent upon the options and/or the thermostat, there may be a delay for the compressor(s) operation�

16� Verify that the condenser blower rotation is correct�17� While waiting for the compressor(s) to stabilize,

record the External Static Pressure (ESP) for both the evaporator and condenser blowers�

Note: Make sure all the unit access panels are in place when taking these readings�

18� Record the return air temperature to the evaporator coil along with the supply air temperature� (The unit should have operated for at least 15 minutes before taking these readings)�

19� Record the outdoor ambient entering the condenser coil along with the discharge air temperature of the condensing section�

20� Record the suction line pressure and the suction line temperature for each circuit near the compressor�

Continued on next page

Page 36: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

36Subject to change without notice. 10.20-IM (0918)

Start-Up Procedures (R-410a Systems) Continued:21� Using an appropriate pressure / temperature chart for

R-410a refrigerant, look up and record the saturation temperature corresponding to the suction pressure�

22� Calculate and record the suction superheat for each circuit by taking the difference between the suction line temperature and the saturation temperature corresponding to the suction pressure�

23� Record the liquid line pressure and the liquid line temperature for each circuit near the condenser coil outlet�

24� Using an appropriate pressure / temperature chart for R-410a refrigerant, look up and record the saturation temperature corresponding to the liquid line pressure�

25� Calculate and record the liquid sub-cooling for each circuit by taking the difference between the liquid line temperature and the saturation temperature corresponding to the liquid line pressure�

26� Record the Amps for the evaporator blower motor, each compressor and the condenser blower motor� If the system is single phase, use L1 and L2 only�a� Make sure the pressures on each compressor circuit

are within the proper limits:i� 290 – 550 Dischargeii� 100 – 140 psig Suction

b� Compressor Amperage is below the RLA Amps listed on the unit data tag�

i� The maximum compressor operating current (amps) at start up depends a lot on the system loading� The lower the load, the less the current� The higher the load, the higher the current�

c� The blower motor FLA values should never be exceeded�

i� If the FLA value is exceeded, shut the unit off and check the duct design, sheave turns open or make sure there is no blockage / obstruction in the duct or filters.

27� Document any additional information deemed appropriate for the specific application or installation.

28� Shut the system down and remove all test instruments and test sensors�

29� Leave the system in the operating mode as appropriate for the customer and the application�

Optional Heating Start Up:30� If the system has any optional heat, set the room

thermostat approximately 5° higher than the actual room temperature� Set the controller operating mode to the HEAT position�

31� Dependent upon the heating source the heating valve or switch / contactor should be activated�

32� After several minutes of operation, record the return air temperature and the supply air temperature�

33� Based on the heating source, document the appropriate temperatures, pressures, voltage or amp values�

Page 37: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

37Subject to change without notice. 10.20-IM (0918)

Air-Cooled Unit Start-Up ProceduresComplete the form by listing your name, company name, phone and fax number� Sign and date the form and provide a copy as required to all interested parties�

Job Name: _________________________________ Date:____________Address: ____________________________________________________City: ___________________________ State: ________ZIP ____________Country: ____________________________________________________Unit Model No�: ______________________________________________Unit Serial No�: _______________________________________________

Screw Lugs & Terminals OK? �������������������������������������������������������������������������������Yes ___________ No ___________Describe any loose connections and action(s) taken:__________________________________________________________________________________________________________________________________________________________________________________________________Power Supply Correct Voltage and Phase? ���������������������������������������������������������Yes ___________ No ___________If not in agreement with unit data tag contact the Distributor�_________________________________________________________________________________________________Is the Circuit Protection the correct type and does it meet the unit data tag requirements? ����������������������������������������������������������������������������Yes ___________ No ___________If not correct describe what action(s) have been taken to correct:__________________________________________________________________________________________________________________________________________________________________________________________________Unit controller wiring verified? ������������������������������������������������������������������������������Yes ___________ No ___________“C” Terminal hooked up if necessary? ������������������������������������������������������������������Yes ___________ No ____________________________________________________________________________________________________________Unit leak checked OK? �����������������������������������������������������������������������������������������Yes ___________ No ___________If leak was located describe where and how repaired:__________________________________________________________________________________________________________________________________________________________________________________________________Condensate trapped & run to a suitable disposal point? ��������������������������������������Yes ___________ No ____________________________________________________________________________________________________________Filters are in place, clean & usable?���������������������������������������������������������������������Yes ___________ No ____________________________________________________________________________________________________________Single Phase Unit Measured Voltage��������������������������������������������������������L1-L2 __________ L1-GND __________ L2-GND _________Three Phase Measured Voltage��������������������������������������������������������L1-L2 ____________ L2-L3 ____________ L1-L3 __________________________________________________________________________________________________________Evaporator Blower Motor Rotation OK? ���������������������������������������������������������������Yes ___________ No ___________If three phase power and rotation is not correct describe action(s) taken to correct:__________________________________________________________________________________________________________________________________________________________________________________________________Condenser Blower Motor Rotation OK? ���������������������������������������������������������������Yes ___________ No ___________If three phase power and rotation is not correct describe action(s) taken to correct:__________________________________________________________________________________________________________________________________________________________________________________________________

Continued on Next Page

Page 38: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

38Subject to change without notice. 10.20-IM (0918)

Evaporator External Static Pressure ��������������������������(ESP): ____________ In� WG _________________________________________________________________________________________________________________Condenser External Static Pressure ��������������������������(ESP): ____________ In� WG _________________________________________________________________________________________________________________

Cooling Mode_________________________________________________________________________________________________System Air Temperatures �������������������������������������Return: °F _________ Supply: °F __________________________________________________________________________________________________________________Condenser Coil �������������������������������������Outdoor Ambient: °F ___________ Condenser Discharge: °F ____________

Compressor 1 Compressor 2Suction Pressure:Suction Line Temperature:

psi _______°F ________

psi _______°F ________

Saturation Temperature: °F ________ °F ________

Suction Superheat: ° ________ ° ________

Liquid Line Pressure: psi _______ psi _______

Saturation Temperature:Liquid Line Temperature:

°F ________°F ________

°F ________°F ________

Sub-cooling: ° ________ ° ________

ElectricalEvap� Motor Amps ������������������������������������������������������������ L1 ____________ L2 ___________ L3 ____________Compressor 1 Amps ��������������������������������������������������������� L1 ____________ L2 ___________ L3 ____________Compressor 2 Amps ��������������������������������������������������������� L1 ____________ L2 ___________ L3 ____________Cond� Motor Amps ������������������������������������������������������������ L1 ____________ L2 ___________ L3 _____________________________________________________________________________________________________________

Heating Mode (Optional)_________________________________________________________________________________________________System Air Temperatures �������������������������������������Return: °F _________ Supply: °F __________________________________________________________________________________________________________________Entering Water Temperature:��������������������������������Return: °F _________Fluid Type: _________________Leaving Water Temperature: ��������������������������������Return: °F _________Steam Pressure: ���������������������������������������������������������������psi _________Electric:kW: __________ Voltage: ___________Amps: Stage1 ���������������������������������� L1 _____________ L2 ___________ L3 ____________ Stage2 ���������������������������������� L1 _____________ L2 ___________ L3 ____________ _________________________________________________________________________________________________Misc� _____________________________________________________________________________________________________________________________________________________________________________________________Technician (print name): _____________________________________________________________________________Company: ________________________________________________________________________________________Phone: __________________________________________________________ Fax: ____________________________Signature: ______________________________________________________ Date: ____________________________

Page 39: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

39Subject to change without notice. 10.20-IM (0918)

Water-Cooled Unit

Start-Up Procedures (R-410a Systems)1� Start up must be performed by a qualified HVAC

Technician�2� Make certain that all power is disconnected at the main

power circuit breaker or service disconnect before starting any of this procedure�

3� Check all electrical screw terminals and wiring lugs for tightness internal to the equipment� Components may have loosened due to vibration during transit or handling� Verify that the main power block lug connections made in the field are tight and secure.

4� Confirm that the voltage rating of the equipment data tag coincides with the power that will be delivered to the unit�

5� Verify that the circuit protection for the unit satisfies Local and National Codes according to the unit data tag Minimum Circuit Ampacity (MCA) and Maximum Fuse Size (MFS)�

6� Locate the unit thermostat and check all electrical terminations against the unit electrical diagram and for the unit thermostat�

Note: If using a digital thermostat with a “C” (Common) terminal, this terminal MUST be terminated to the “C” terminal in the unit� Failure to do so will result in the thermostat shorting out and being destroyed�

7� Leak check the refrigerant system� While the unit was leak checked at the factory, leaks can develop during transit and / or handling�

8� Confirm that the unit condensate has been adequately trapped and taken to a suitable point for disposal�

9� Verify that the filters are in place, clean and usable.10� Switch the unit thermostat to the “OFF” position�11� Apply power to the unit� Switch the circuit breaker or

field supplied electrical service disconnect switch to the on position�

Note: If the unit has crankcase heaters and the surrounding ambient is 70˚ F or lower, let the compressors sit for approximately 24 hours before proceeding�

12� Record the voltage at the unit terminals�13� If possible with the thermostat provided, switch the

evaporator blower to the RUN or ON position� Verify that the evaporator blower is activated�

14� Verify that the evaporator blower is rotating in the correct direction (three phase units only)�

Note: If the evaporator blower motor runs backwards, shut off all power to the unit� Switch any two of the incoming power leads at the unit main power terminal block� The unit has been wired and phased properly at the factory� DO NOT change any factory wiring to correct for a phase problem�

Note: Before conducting the following start up sections connect a suitable refrigerant gauge set to the unit Schrader connections� Install temperature sensors to record the appropriate refrigerant line temperatures�

15� Set the thermostat switch to a temperature set point approximately 5˚ lower than the space temperature. Set the thermostat fan switch to the AUTO position� Set the thermostat operating mode to the COOL position� This should energize the compressor(s) and evaporator blower�

Note: Dependent upon the options and/or the thermostat, there may be a delay for the compressor(s) operation�

16� While waiting for the compressor(s) to stabilize, record the External Static Pressure (ESP) for the evaporator blower�

Note: Make sure all the unit access panels are in place when taking these readings�

17� Verify that the incoming water / fluid pressure does not exceed the rating for the water / fluid control valves.

18� Verify that the unit piping and heat exchangers will not be subjected to freezing conditions�

19� Confirm that no joints are leaking in the cooling fluid circuit(s)�

20� Document the type of fluid being used as the cooling medium� If glycol is being used, make sure the mixture is adequate for any low ambient conditions that may be possible�

21� If possible, record the fluid flow rate (GPM).a� Make sure the flow rate is within the proper limits:

i� Minimum 2�5 GPM / Tonii� Maximum 3�5 GPM / Ton

Continued on next page

Page 40: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

40Subject to change without notice. 10.20-IM (0918)

Start-Up Procedures (R-410a Systems) Continued:22� Record the entering and leaving fluid temperatures.

b� Make sure the leaving fluid temperature is within the proper limits:

i� Minimum 60˚ Fii� Maximum 115˚ F

23� Record the pressure drop of the water / fluid across the unit�

24� Verify that all valves on each fluid circuit function properly�

25� Check the head pressure adjustment, DO NOT assume that this has been set at the factory� Typically this value is to be 360 psi when 85˚ F water is supplied to the unit at 3 GPM/Ton�

26� Record the return air temperature to the evaporator coil along with the supply air temperature� (The unit should have operated for at least 15 minutes before taking these readings)�

27� Record the suction line pressure and the suction line temperature for each circuit near the compressor�

28� Using an appropriate pressure / temperature chart for R-410a refrigerant, look up and record the saturation temperature corresponding to the suction pressure�

29� Calculate and record the suction superheat for each circuit by taking the difference between the suction line temperature and the saturation temperature corresponding to the suction pressure�

30� Record the liquid line pressure and the liquid line temperature for each circuit near the condenser heat exchanger outlet�

31� Using an appropriate pressure / temperature chart for R-410a refrigerant, look up and record the saturation temperature corresponding to the liquid line pressure�

32� Calculate and record the liquid sub-cooling for each circuit by taking the difference between the liquid line temperature and the saturation temperature corresponding to the liquid line pressure�

33� Record the Amps for the evaporator blower motor and each compressor� If the system is single phase, use L1 and L2 only�

a� Make sure the pressures on each compressor circuit are within the proper limits:

i� 290 – 550 Dischargeii� 100 – 140 psig Suction

b� Compressor Amperage is below the RLA Amps listed on the unit data tag�

i� The maximum compressor operating current (amps) at start up depends a lot on the system loading� The lower the load, the less the current� The higher the load, the higher the current�

c� The blower motor FLA value should never be exceeded�

i� If the FLA value is exceeded, shut the unit off and check the duct design, sheave turns open or make sure there is no blockage / obstruction in the duct or filters.

34� Document any additional information deemed appropriate for the specific application or installation.

35� Shut the system down and remove all test instruments and test sensors�

36� Leave the system in the operating mode as appropriate for the customer and the application�

Optional Heating Start Up:37� If the system has any optional heat, set the room

thermostat approximately 5° higher than the actual room temperature� Set the thermostat operating mode to the HEAT position�

38� Dependent upon the heating source the heating valve or switch / contactor should be activated�

39� After several minutes of operation, record the return air temperature and the supply air temperature�

40� Based on the heating source, document the appropriate temperatures, pressures, voltage or amp values�

Page 41: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

41Subject to change without notice. 10.20-IM (0918)

Water-Cooled Unit Start-Up ProceduresComplete the form by listing your name, company name, phone and fax number� Sign and date the form and provide a copy as required to all interested parties�

Job Name: _________________________________ Date:____________Address: ____________________________________________________City: ___________________________ State: ________ZIP ____________Country: ____________________________________________________Unit Model No�: ______________________________________________Unit Serial No�: _______________________________________________

Screw Lugs & Terminals OK? �������������������������������������������������������������������������������Yes ___________ No ___________Describe any loose connections and action(s) taken:__________________________________________________________________________________________________________________________________________________________________________________________________Power Supply Correct Voltage and Phase? ���������������������������������������������������������Yes ___________ No ___________If not in agreement with unit data tag contact the Distributor�_________________________________________________________________________________________________Is the Circuit Protection the correct type and does it meet the unit data tag requirements? ����������������������������������������������������������������������������Yes ___________ No ___________If not correct describe what action(s) have been taken to correct:__________________________________________________________________________________________________________________________________________________________________________________________________Unit controller wiring verified? ������������������������������������������������������������������������������Yes ___________ No ___________“C” Terminal hooked up if necessary? ������������������������������������������������������������������Yes ___________ No ____________________________________________________________________________________________________________Unit leak checked OK? �����������������������������������������������������������������������������������������Yes ___________ No ___________If leak was located describe where and how repaired:__________________________________________________________________________________________________________________________________________________________________________________________________Condensate trapped & run to a suitable disposal point? ��������������������������������������Yes ___________ No ____________________________________________________________________________________________________________Air Filters are in place, clean & usable? ���������������������������������������������������������������Yes ___________ No ____________________________________________________________________________________________________________Single Phase Unit Measured Voltage��������������������������������������������������������L1-L2 __________ L1-GND __________ L2-GND _________Three Phase Measured Voltage��������������������������������������������������������L1-L2 ____________ L2-L3 ____________ L1-L3 __________________________________________________________________________________________________________Evaporator Blower Motor Rotation OK? ���������������������������������������������������������������Yes ___________ No ___________If three phase power and rotation is not correct describe action(s) taken to correct:__________________________________________________________________________________________________________________________________________________________________________________________________Evaporator External Static Pressure ��������������������������������������������������������������� (ESP): ________In� WG ____________________________________________________________________________________________________________Verify that incoming fluid pressure does not exceed ��������������������������������������������Yes ___________ No ___________rating for the fluid control valves._________________________________________________________________________________________________

Continued on Next Page

Page 42: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

42Subject to change without notice. 10.20-IM (0918)

Verify that unit piping and heat exchangers will not be subject to freezing conditions� ������������������������������������������������������������������������������Yes ___________ No ___________

No cooling fluid leaks�����������������������������������������������Circuit 1 ___________ Circuit 2 _________________

Cooling Fluid Type If Glycol what percentage of mix:� ______________________ Good to a temperature of ______________________

Water / Fluid flow rate ���������������������������������������������������GPM __________________

Entering Water Temperature (EFT): °F ___________ Leaving Water Temperature (LFT): °F _________

Water / Fluid Pressure Drop across unit: ������������������������ PSI _________

Verify that all valves on each circuit are functioning properly� ������������������������������Yes ___________ No ___________

Verify water/fluid discharge pressure set point. ����������������������������������������������������Yes ___________ No ___________

Cooling Mode_________________________________________________________________________________________________System Air Temperatures �������������������������������������Return: °F _________ Supply: °F _________________

Compressor 1 Compressor 2Suction Pressure:Suction Line Temperature:

psi _______°F ________

psi _______°F ________

Saturation Temperature: °F ________ °F ________Suction Superheat: ° ________ ° ________Liquid Line Pressure: psi _______ psi _______Saturation Temperature:Liquid Line Temperature:

°F ________°F ________

°F ________°F ________

Sub-cooling: ° ________ ° ________

ElectricalEvap� Motor Amps ������������������������������������������������������������ L1 ____________ L2 ___________ L3 ____________Compressor 1 Amps ��������������������������������������������������������� L1 ____________ L2 ___________ L3 ____________Compressor 2 Amps ��������������������������������������������������������� L1 ____________ L2 ___________ L3 ____________

Heating Mode (Optional)System Air Temperatures �������������������������������������Return: °F _________ Supply: °F _________________

Entering Water Temperature:�������������������������������Return: °F ________ Steam Pressure: psi __________Leaving Water Temperature: ��������������������������������Return: °F _________Electric kW: _________ Voltage: ___________Amps: Stage1 ���������������������������������� L1 _____________ L2 ___________ L3 ____________ Stage2 ���������������������������������� L1 _____________ L2 ___________ L3 ____________

Misc� _____________________________________________________________________________________________________________________________________________________________________________________________Technician (print name): _____________________________________________________________________________Company: ________________________________________________________________________________________Phone: __________________________________________________________ Fax: ____________________________Signature: ______________________________________________________ Date: ____________________________

Page 43: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

Installation, Operation and Maintenance Manual

C13-Series

43Subject to change without notice. 10.20-IM (0918)

Basic Model Designation

EXAMPLE: Ca

5b

Gc

3d

ASNe

Tf

Cg

Xj

or MAa

8b

Gc

3d

Ae

Hf

Ag

10h

Vi

Not all combinations of Basic Model Designations are valid. Check with the factory for correct model identification

a. “C”, “CW”, “H”, “HW”, “MA”, “MW”, “CCW”, “E”, “B” or “BC”“C” Air-Cooled Air Conditioner 2 thru 8 Tons“CW” Water-Cooled Air Conditioner 2 thru 8 Tons“H” Air-Cooled Heat Pump 2 thru 8 Tons“HW” Water-Cooled Heat Pump 2 thru 8 Tons“MA” Air-Cooled, MagnaCool Unit 2 thru 8 Tons“MW” Water-Cooled, MagnaCool Unit 2 thru 8 Tons“CCW” Chilled Water Unit 2 thru 8 Tons“E” Evaporator Section only of the unit 2 thru 8 Tons

(can be a prefix for some of the above)“B” Condensing Section only of the unit 2 thru 8 Tons\ “BC” Condenser Section only of the unit 2 thru 8 Tons

b. “2”, “3”, “4”, “5”, “6”, “8” Nominal Cooling Capacity in Tonsc. “G” Common to alld. “1”, “3”, “4” or “5” Indicates Voltage

“1” 208-230V, 1 PH (277 Volt Handled by Optional Buck-Boost Trans.)“3” 208-230V, 3 PH“4” 460V, 3 PH“5” 575V, 3 PH

e. “AS”, “A” Quantity of Refrigerant Circuits“AS” Indicates 1 Circuit“A” Indicates 2 Circuits

f. “H” Unit Series“H” High Efficiency

g. “A” Refrigerant Type“A” R-410a

h. “05”, “10”, “15”, “20”, “25” Indicates kW Rating for Heatersi. “V” Indicates Vertical Stacking Unitj. “X” Special Configuration

Page 44: C13-Series - United CoolAir · Installation, Operation and Maintenance Manual C13-Series Subject to change without notice 4 10 20-IM (0918) Wiring Diagram United CoolAir provides

10.20-IM (0918)

Scan to learn more about all of our

products!

491 East Princess Street, York, PA 17403 Phone: 717-843-4311 Fax: 717-854-4462email: [email protected] web: www.unitedcoolair.com

Copyright © by United CoolAir Corporation 2018. All rights reserved. Manufacturer reserves the right to make changes without notice.

Unique Solutions for All-Indoor HVAC Projects

Authorized Distributor: LIMITED WARRANTYUnited CoolAir Units are backed by a 1 year limited warranty on parts and a 5 year limited warranty on the compressor (labor not included). Maintenance items such as filters and belts are excluded under this limited warranty�

FACTORY TESTEDAll units are functionally run tested before shipment to ensure a trouble-free start-up and unit commissioning� Industry proven components are used throughout to enhance system reliability and peace of mind�

VertiCool ClassicVertical, 3 - 30 Ton

VertiCool Aurora Vertical, 3 - 35 Tons

VariCool® VAV, 9 - 70 Tons

VariCool® EZ-FitVAV, 12 - 90 Tons

Alpha Aire100 – 500 CFM

Portable Cooling and Heating Units

3-30 Tons

C13-Series Horizontal2 - 10 Tons

C-Series Horizontal1 - 15 Tons

Special Configuration Engineered to Order

OmegaAir Horizontal and Vertical100% Outside Air 150 – 3000 CFM