building services 2
TRANSCRIPT
Group Members : Chiam Jia Ern (0318524)
Hii Pai Ling (0320598)
Jenny Hoo Yee Tyng (0321841)
Khor Ka Nee (0321789)
Liew Chia Niu (0313338)
Na Yeow Sing (0320385)
Ng Jia Nan (0321451)
Building Services II (BLD60503)
Case Study: Giant Mall Kelana Jaya
SCHOOL OF ARCHITECTURE, BUILDING AND DESIGN
BACHELOR IN QUANTITY SURVEYING (HONOURS)
Lecturer : Dr. Kam Kenn Jhun
Table of Content
No Content Pages
1.0 Acknowledgment 1
2.0 Abstract 2
3.0 Part 1 (Purpose of the building as case study) 3
4.0 Part 2 (Existing types of system)
4.1 Mechanical and Air-conditioning System 5
4.2 Fire Protection System 18
4.3 Vertical Transportation System 33
4.4 Electrical Supply System 39
5.0 Part 3 (Problems and Recommendations)
5.1 Fire Protection 44
5.2 Vertical Transport 55
6.0 Conclusion 64
7.0 Appendix 65
8.0 References 66
1.0 Acknowledgment
We want thanks those who had helped and guided us to complete this group assignment.
First, we want to thank our lecturer, Dr. Kam Kenn Jhun. During this assignment, he has
encouraged and guided us in the choosing building and preparation of our case study
report.
Besides, we also want to thanks Ms Sarryan from the divisional office of Architecture,
Building, and Design for providing the approval letter for us to site visit at Giant Kelana
Jaya Mall.
Lastly, thanks to the group mates of hardly to complete their own part and contributed
suggestions and give own opinion for this assignment. We also need to thank our leader
for having the good leadership and worked hard to gain approval for site visit and his
encouragement in order to ensure that we can finish our work.
Acknowledgement 1
2.0 Abstract
Our group members who are Chiam Jia Ern, Hii Pai Ling, Jenny Hoo Yee Tyng, Khor Ka
Nee, Liew Chia Niu, Na Yeow Sing and Ng Jia Nan had chosen Giant Kelana Jaya Mall
as our Building Services 2 Case Study. In this case study, we are requested to select a
building as a case study project and observe the building services systems taught in this
module. This assignment consists of four parts. Part 1 is describe the purpose of the
building as a case study. Part 2 is discuss about the existing types of system there have
in building. Part 3 is identify the problems, comment on two systems, compare and contrast
the current system with our recommendation and solution for that two problem system that
we find in the building. Lastly, part 4 is justify our finding from Part 3 and recommend the
best system for this building. This assignment has given us an opportunity to learn and do
more research regarding to building services.
Figure 2.0A – Outside view of Giant Mall.
Abstract 2
3.0 Part 1 (Purpose of the building as case study)
What is Building Services? Imagine yourself in one of the building in this world. Now take
away all the system that have in this building like ventilation, mechanical, air conditioning,
vertical transport and fire protection system. What you will feel? So, everything inside a
building which makes us feel safe and comfortable that is under the title of 'Building
services'. Building Services is important to us, nowadays people can’t live without any
building services.
We choose Giant Mall as our case study is because it is an old building at Kelana Jaya
compare to Paradigm Mall. Besides that, we choose this mall also because it has the
system that we learn in this module such as mechanical and air conditioning, fire protection,
vertical transport and electrical supply.
Giant Mall is located opposite of Paradigm Mall. It has three floors including 75 shop lots,
15 food court, 15 pushcarts, and 60 promotion spaces. It also consists 809 parking bars,
which is indoor and outdoor parking. All parking bays are at ground floor.
Figure 3.0A – Map of Giant Mall. Location of Giant Mall: No. 33, Jalan SS 6/12, Kelana Jaya,
47301, Petaling Jaya, Selangor, MALAYSIA
Purpose of the building as case study 3
Available Lots
Mall Info Total Lots Availability
Shop lots 75 √
Food court 15 √
Pushcarts 15 √
Promotion Space 60 √
Total 165
Figure 3.0B – Floor Plan of Gaint Mall.
Purpose of the building as case study 4
4.0 Part 2 (Existing types of system)
4.1 Mechanical and Air-conditioning System
Ventilation is a process that replacing air in an enclosed space to control the temperature.
A proportion of air within the enclosed space should be continuously withdrawn and
replaced by fresh air.(Greeno, R., 1997, Building Services, Technology and Design)
4.1.1 Natural Ventilation
Natural Ventilation is a process of supplying and removing air through an indoor space
without using mechanical systems. It refers to the flow of external air to an indoor space
as a result of pressure or temperature differences.
4.1.2 Mechanical Ventilation
Mechanical ventilation systems circulate fresh air using ducts and fans rather than relying
on airflow through small holes or crack’s in a home’s wall, roof or windows. By using the
mechanical ventilation, we have more control to provide the proper fresh air flow along with
appropriate locations for intake and exhaust. The components of mechanical ventilation
include:
1) Fan
Figure 4.1.2B - Three type of fan.
Figure 4.1.2A - Cross-flow fan.
Existing types of system 5
2) Filter
-to ensure a specified air change and force the air under fan pressure
3) Ductwork
-to deliver and remove air
Figure 4.1.2C - The replacement air filter
Figure 4.1.2D - The ducting located at the carpark.
Existing types of system 6
4) Fire dampers
-to prevent the spread of fire inside the ductwork and diffusers (to have more complex
and efficient coned air distributors)
Diffuser
Diffuser is the mechanical device that is designed to control the characteristics of a fluid at
the entrance to a thermodynamic open system. It can be as a shape of round, rectangular,
or can be as linear slot diffusers. There are two type of diffuser we found in Giant Kelana
Jaya which are four-way louvre bladed diffuser and side-wall inlet.
Figure 4.1.2E - The fire damper place at staircase area
Existing types of system 7
1) Louvre Bladed Diffuser
Louvre bladed diffuser is commonly used to supply air at ceiling level. The curved blades
deflect air in one, two, three or four directions depending on where the diffuser is situated.
In Giant Kelana Jaya, it is the four-way louvre bladed diffuser. This type of diffuser is a
multi-cone adjustable diffuser, which can be changed from horizontal 4-way diffusion to
vertical projection.
2) Side-wall Inlet Diffuser
This diffuser is suitable when there is no false ceiling. Each inlet is equipped with a grill. A
series of grill distributed at the internals along the inner partition wall with ducts in the
corridor. Double deflection type is the most common and effective form. There are 2 sets
of adjustable louvers used to control the air delivery in vertical and horizontal plane.
Figure 4.1.2G - The diffuser at the food court area.
Figure 4.1.2F - The four-way louvre bladed diffuser.
Existing types of system 8
Outlet Air Conditioning
An air outlet is the outermost panel within any type of object that controls the rate in which
air passes into the surrounding area. Many air outlets have the ability to be open or shut
at varying degrees to restrict the flow of currents coming and going; some of them can also
be sealed off completely to stop airflow. This function is especially important, because if
without the proper filtration, the air itself could reach life-threatening levels.
Figure 4.1.2H - The side-wall inlet
diffuser in Giant.
Figure 4.1.2 - The air outlet at the carpark area.
Figure 4.1.2J - The air outlet inside the Giant mall.
Existing types of system 9
Air Conditioning System
An air conditioning system is composed of components and equipment arranged in
sequence to condition the air, to transport it to the conditioned space, and to control the
indoor environmental parameters of specific space within required limits. There are three
type of air conditioning which are unitary system, package system and centralized system.
In our cases, Giant Kelana Jaya is a large area building and requires high cooling. The air
conditioning system that has been adopted by the building is centralized system.
Centralized System
Centralized systems is a manufacturer of air movement and control equipment. This
system mostly can serve multiple spaces from one base location. These typically use
chilled water as a cooling medium and use extensive ductwork for air distribution.
The advantages of central air conditioning systems are better control of comfort conditions,
higher energy efficiency and greater load-management potential when compare to other
system. However, centralized system are more expensive to install and are usually more
sophisticated to operate and maintain. Thus, this system is more suitable for mid to high
rise buildings. Furthermore, it is not suitable for the existing building because this system
must be incorporated in the design of new building.
Existing types of system 10
0
Centralized systems are defined as those in which the cooling (chilled water) is generated
in a chiller at one base location and distributed to air-handling units or fan-coil units located
throughout the building spaces.
Figure 4.1.2K - Centralized air-
conditioning system.
Figure 4.1.2L - This is the
centralized system how
works in Giant Kelana
Jaya.
Existing types of system 11
Chilled Water Air- conditioning System
Chilled Water systems is a system that employ water chillers. This system makes use of
water as its secondary refrigerant. Chiller is used to remove heat from the water which is
then circulated through other components to absorb heat from the space. Chilled water air
conditioning systems are commonly used in applications that need large cooling capacity
such as hypermarket, industrial process, commercial air conditioning such as offices and
factories.
The advantages of this system are cost-effectiveness and no hazard of having refrigerant
piped all over the building. There are three major subsystems in this system which are the
chilled water plant, the condenser water system (or heat rejection system) and the air-
delivery system.
Figure 4.1.2M - A typical chilled water central system
Existing types of system 12
Water Chiller
A device that removes heat from a liquid via a vapor-compression or absorption
refrigeration cycle. This cooled liquid flows through pipes in a building and passes through
coils in air handlers, fan-coil units, or other systems, cooling and usually dehumidifying the
air in the building. Chillers are of two types; air cooled or water cooled.
Evaporator
The evaporator works the opposite of the condenser, here refrigerant liquid is converted
to gas, absorbing heat from the air in the compartment.
Figure 4.1.2N - The example of water chiller device
Figure 4.1.2O - A typical evaporator of chiller
Existing types of system 13
Compressor
The compressor compacts the refrigerant vapor and pumps it to the reversing valve.
Condenser
An equipment that converts a gas to a liquid to obtain either the substance or the released
heat.
Figure 4.1.2P - The example of compressor.
Figure 4.1.2Q - The condenser mechanical drawing.
Existing types of system 14
Cooling Tower
Cooling towers are heat rejection devices used to transfer process waste heat to
the atmosphere. Cooling towers may either use the evaporation of water to reject process
heat and cool the working fluid to near the wet-bulb air temperature or rely solely on air to
cool the working fluid to near the dry-bulb air temperature.
AHU (Air Handling Unit)
AHU is a device used to condition and circulate air as part of HVAC system. Usually, an
air handler is a large metal box containing a blower, heating or cooling
elements, filter racks or chambers, sound attenuators, and dampers. Air handlers usually
connect to ductwork that distributes the conditioned air through the building, and returns it
to the AHU.
Figure 4.1.2R - The cooling tower of Giant is located at the roof of this building.
Existing types of system 15
Condenser Pump Room
This is a set of device by using mechanical forces to move the condenser water.
Figure 4.1.2U - The pump which use to pump the refrigerant (water).
Figure 4.1.2T - The ducting and piping in condenser pump room.
Figure 4.1.2S - The Condenser pump room of Giant Kelana Jaya.
Existing types of system 16
Figure 4.1.2W - This is the hot water supply because the pipe is connecting to the mall.
Figure 4.1.2X - The condenser which convert the gas to the liquid.
Figure 4.1.2Z - The piping in Condenser
Pump Room
CWR: Condenser Water Return CWS: Condenser Water Supply
Figure 4.1.2V - The water supply in the room.
Figure 4.1.2Y - The air filters are put on the ground in the room.
Existing types of system 17
4.2 Fire Protection System
Fire protection refers to measures taken in order to prevent fire from becoming destructive,
reduce the effects of uncontrolled fire and save lives and property. The duty of the fire
protection system may be to extinguish the fire or control the fire. The basic factors of a
fire triangle are fuel, heat and oxygen, together with the chemical reaction between one
another. Combustion is a chemical reaction which substances combine chemically with
oxygen from the air and typically give out bright light, heat and smoke. Fire protection
systems are subdivided into two, which are active fire protection system and passive fire
protection system.
4.2.1 Active Fire Protection System
Active Fire protection system includes the action of extinguishes the fire, or being notified
of fire happenings and smoke conditions by automatic or manual operation system. These
systems are always on alert and first to act in case of fire. It interacts with their surroundings
by:
Operating fans for smoke extraction.
Operating a fire sprinkler to extinguish a fire.
Opening a vent to allow assisted natural ventilation.
The first stage of active fire protection is to detect the fire, by detecting heat, smoke or
flames, an automatic fire alarm system is commonly used to trigger most active systems,
then, automatically operates the active systems.
a) Fire alarm bell
The fire alarm bells in Giant Mall are activated by the fire detector throughout the
building. There are two type of fire alarm bell which are continuous bells and single-
stroke bells. Giant Mall is using the continuous type of fire alarm bell. Continuous
bells have a component inside which utilizes an electric loop got back to a solenoid
to force a mallet. At the point when the mallet backtracks, it separates the circuit
and bringing on the solenoid to give up, sending the sledge into the gong and ringing
Existing types of system 18
it. When the hammer moves forward, it reconnects the circuit which pulls the sledge
back once more. It proceeds with this cycle until the force is detached.
b) Manual Call Point
A manual call point also called as an emergency break glass is a device that
enables the occupants to raise the alarm by breaking the frangible element on the
fascia. Most of the manual call points mounted 1.4m from the floor and installed
where they can be easily seen especially on the floor and installed where they can
be easily seen especially on floor landings of stairways and at exists to open air.
Figure 4.2.1A - Fire alarm bell in Giant Mall.
Figure 4.2.1B - Fire alarm with break glass.
Existing types of system 19
c) Wet Riser
Wet riser is constantly filled with water. The water supply shall be capable of
maintaining a running pressure of 410 kPa at the highest landing valve and given a
flow rate of 2.3litre/second. In Giant Mall, wet riser is located near the emergency
staircase in each and every floor.
Figure 4.2.1C - Manual Call Point is connected to the alarm bell.
Figure 4.2.1D - Hose Reel.
Existing types of system 20
d) Fireman Intercom System
Fireman intercom system provide a two1way communication between remote
areas and the fire command centre in Giant Mall.
Figure 4.2.1G - “Telefon Bomba Api” located at emergency exit.
Figure 4.2.1F - Wet riser outlet. Figure 4.2.1E - Wet riser pipe and hose reel.
Existing types of system 21
e) Fire alarm control panel
The fire alarm panel is designed to monitor each circuit, zone or point of any
condition display the status of that condition and to operate any required output.
(Firewize nd)
f) Pendent Sprinkle
For most fires, water represents the ideal extinguishing agent. Fire sprinklers utilize
water by direct application onto flames and heat, which causes cooling of the
combustion process and prevents ignition of adjacent combustibles. They are most
effective during the fire’s initial flame growth stage, while the fire is relatively easy
to control.
Fire sprinkler system are actually heat activated, one sprinkler head at a time and
most fires usually require only one or two sprinklers to be extinguished.
Figure 4.2.1H - Fire control panel that
indicates the area and zones in case of fire.
Existing types of system 22
Figure 4.2.1I - pendent sprinkler in Giant Mall.
g) External Fire Hydrant
External fire hydrant consists of a system of pipework connected directly to the
water supply mains to supply water to every hydrant outlet and intended for the
fireman to fight fire. Fireman will connect their equipment to the outlets of the
hydrant, forcing water into the system. The distance between the fire hydrant and
the building is between 4m to 8m. Fire hydrant is place beside the road so that the
fire brigade could get easy access to input their hose. The type of fire hydrant used
is two-way fire hydrant.
Figure 4.2.1J - External Fire Hydrant in Kelana Jaya Giant Mall.
Existing types of system 23
Figure 4.2.1K - Hydrant System Detail Drawing.
h) Water Tank
The water storage tank is located at the top floor of Giant Mall. The wet riser
system and water sprinkler system uses the same water. The volume of water
contained in the water tank is sufficient to supply water to the whole building.
Figure 4.2.1L - Water storage tank on the top floor of Giant Mall.
Existing types of system 24
i) Fire Man Switch
The fireman switch is designed to turn off the neon lighting or other hazardous
electrical equipment in case of fire (ABB 2012). This is to prevent the equipment
from being overheated and in turn causes explosion. In Giant Mall, there are a lot
of fire switches which are fixed onto the wall and painted red, thus, fire man switch
are easily spotted.
Figure 4.2.1M - Fire Man Switch.
j) Smoke Detector
All smoke detectors consist of two basic parts, a sensor to sense the smoke and a
very loud electronic horn to wake people up. There are two types of smoke detector
commonly found in the market which are photoelectric smoke detector and
ionization smoke detector. Diagram above shown the ionization smoke detector
used in Giant Mall. This kind of alarm uses a little measure of radioactive material
to ionize air in an internal sensing chamber. Subsequently, the air in the chamber
gets to be conductive allowing current to flow between two charged electrodes. At
the point when smoke particles enter the chamber, the conductivity of the chamber
air will decrease. When this reduction in conductivity is reduced to a predetermined
Existing types of system 25
level, the alarm is set off. Smoke detectors in Giant Mall are powered by a central
fire alarm system, which is powered by the building power with a battery backup.
Figure 4.2.1N - Smoke Detector.
k) Fire extinguishing system
Fire extinguishing systems are commonly used to protect areas containing valuable
or critical equipment such as data processing rooms, telecommunication switches
and process control rooms. Their main function is to quickly extinguish a developing
fire and alert occupants before extensive damage occurs by filling the protected
area with a gas or chemical extinguishing agent. Usually they can be found at exits,
where they are easy to get hold of, in the case of an emergency. Basically, the fire
extinguisher can be found at all the floors, to be specific besides every fire escape
doors and hose reel rooms and almost every corner that easy to reach in Giant Mall.
The type of fire extinguisher that Giant Mall uses throughout the building is dry
powder extinguisher. Portable Fire extinguishers installed are primarily of Dry
Powder variety which can extinguish majority of classes of fire.
Existing types of system 26
Fire Class Properties Travel Distance
Class A Solid material of
organic nature with
formation of glowing
ambers (e.g. paper,
wood)
75 ft. (22.9m)
Class B Liquid or liquefiable
solids (e.g. petrol,
kerosene, diesel)
50 ft. (15.2m)
Class C Gases (e.g. Oxygen,
Carbon Monoxide)
Based on A or B
Hazard
Class D Metals (e.g. Sodium,
Potassium,
Magnesium)
75 ft.
Class E Electrical equipment -
Figure 4.2.1P - Portable Fire Extinguisher in Giant Mall.
Figure 4.2.1O - Table of Classes of Fire and Travel Distance
Existing types of system 27
2.1.2 Passive Fire Protection System
Passive Fire protection (PFP) is a term used to describe the parts of a building that
provides a barrier to fire which slowing the spread rate of fire. It is achieved by included
the fire resistant walls, escape route, emergency access and opening protection in a
building. Passive fire protection also protects load bearing columns and other critical
structures to prevent the building collapsing during fires. It is often used where water or
other active protection media supplies are inadequate, such as in remote locations, or
where there are difficulties with handling fire water run-off. Passive fire protection is only
effective for short duration exposure about 1-2 hours.
a) Fire Escape Plan
Fire escape provides a method of escape in the event of fire or other emergency
that makes the stairwells inside a building inaccessible which allow the occupant to
leave the building to a safer area range outside of the building, such as fire
assembly area. There are routes and exits that were designed particularly in Giant
Mall in case of fire.
Figure 4.2.2A - ground floor fire escape plan.
Existing types of system 28
Figure 4.2.2B - first floor fire escape plan.
Figure 4.2.2C - second floor fire escape plan.
b) Emergency Exit Signage
Exit signs designed to indicate the closest emergency exit or other emergency
information. It is an effective guidance tool, helping to reduce panic and confusion
by providing a clear directional system. The letters are written in block letters
adequately enormous to be seen and green on colour to attract attention. In our
country, the exit signage is written in Malay word “Keluar”, which mean EXIT.
Existing types of system 29
Figure 4.2.2D - Emergency exit sign found at every floor of Giant Mall.
Figure 4.2.2E - “Keluar” Sign found on top of each fire escape door.
c) Fire Escape Door
Location: All escape door
Material: Solid hardwood core with asbestos insulation board
Dimension: Single leaf 900mm x 2100mm x 38mm
Double leaf 1800mm x 2100mm x 38mm
Fire rated: 1 hour
Existing types of system 30
Figure 4.2.2F - Single leaf door. Figure 4.2.2G - Double leaf door.
d) Fire Escape Staircase
Giant Mall has its own fire escape staircases with door boundaries at every floor of
the shopping mall. The type of fire escape staircase used is half landing staircase
and the material used is cements concrete. There is an opening to the outdoor at
each stairway exit enabling smoke to escape during fire and also for ventilation
purpose. The landing area has a dimension of 1.2m X 2.4m. The stairway landing
is sufficiently wide to accommodate the occupants in the event of fire to escape.
Figure 4.2.2H - Fire escape staircase
that links to outside of mall.
Existing types of system 31
Figure 4.2.2I - Tread = 275mm Figure 4.2.2J - Riser = 170mm
According to UBBL section 168 part 8, treads of fire escape staircase are more than
255mm and the riser is less than 180mm.
e) Fire assembly point
There is 2 assembly points that found in Giant Mall, fire assembly point A and B.
The capacity shall be classified according to its capacity as follows class A, B and
C. For class A-capacity is to accommodate 1000 persons and above, class B-
capacity is to accommodate 300 to 1000 persons, for class C-capacity is to
accommodate 100 to 300 persons. The assembly point of Giant Mall is subject to
class-A capacity and class-B capacity.
Figure 4.2.2K - Fire assembly point A. Figure 4.2.2L - Fire assembly point B.
Existing types of system 32
4.3 Vertical Transport
An elevator or lift is a type of vertical transport equipment that efficiently moves people or
goods between floors, levels or decks of a building, vessel or other structures. Forms of
vertical transportation may be found within, around and in general association with modern
buildings and developments.
Figure 4.3A - This is the first floor plan of Giant Mall.
Travelator
Lift/Elevator
Travelator &
Escalator
Existing types of system 33
4.3.1Elevator
Elevators are generally powered by electric motors that either drive traction cables or
counterweight systems like a hoist, or pump hydraulic fluid to raise a cylindrical piston like
a jack.
Hydraulic freight elevator
The type of elevator that used in Giant Mall are hydraulic freight elevator. The hydraulic
elevator has a two speed and centre opening and load capacity of 2600kg which can hold
up to 38 passengers or 2600kg. The door closing time is 3 seconds. Time for the lift to
travel from the highest floor to the lowest floor is 17 seconds. Time for the lift to travel from
one floor to another floor needs 9 seconds. The lift arrangement consists of only one lift
for 3 floors, so the quality of the service is excellent. The main usage of this particular lift
is to move the trolley.
Hydraulic elevator are elevator that has an underground cylinder. Hydraulic elevator are
powered by the piston that travels inside a cylinder to lift the elevator cab. The cost for
installing this type of elevator is cheaper compare to a traction elevator. Hydraulic elevator
are usually installed in a building that has fewer floor. The low maintenance cost of this
type elevator makes them the ideal choice for low rise and low traffic installation. There is
only one elevator installed in the mall, the overall maintenance of the elevator is good
expect the aesthetic appearance inside the elevator.
Existing types of system 34
Figure 4.3.1A - The section view and components of hydraulic lift.
Figure 4.3.1B - The lift car of elevator. Figure 4.3.1C - The hydraulic elevator located at level 2 near to maintenance office.
Existing types of system 35
4.3.2 Escalator & Travelator
An escalator is a conveyor transport designed for moving people quickly and efficiently
between floors of a building. It also requires no waiting time for us and reversible to suit
the main flow of traffic during peak times. Escalator is normally located at department store,
exhibition hall, air terminal and railway station. Several escalators will be required and can
be grouped in a number of ways to suit the building functions when large numbers of
people are anticipated.
The speeds of the escalators in Giant Mall is between 0.5 m/s and 0.6 m/s. Step width is
about 1000mm, which allow two people to stand side by side or to pass on the step
A travelator (moving walkway, moving sidewalk) is a slow conveyor belt that transports
people horizontally up to the practical limitations of about 300 m. They work in a similar
manner to an escalator. In both cases, riders can walk or stand. The walkways are often
supplied in pairs, one for each direction. They are particularly useful in large railways and
airports terminals, as well shopping complexes, and may be inclined up to about 15° where
level differentials occurs.
The speeds of the travelators in Giant Mall is 0.8 m/s. The step width is about 1200mm,
which allow two people to stand side by side, or to allow adequate room for customers to
Figure 4.3.1D - The load capacity of
elevator.
Figure 4.3.1E - The lift of Giant is normally used for transport and move the goods and trolley.
Existing types of system 36
pass easily with the trolleys because the main purpose of these travelators in Giant is
easier to the customers to carry their stuff with trolley and travel from one floor to another
floor.
Escalator Arrangement
There are two type of arrangement we found in Giant Mall which are double bank in two
travel direction and multi-level parallel arrangement with interrupted traffic in two travel
direction.
(Two way Traffic)
(Two way Traffic)
(One way Traffic)
(One way Traffic)
Used mainly in department
stores and public transportation
buildings with heavy traffic flow.
Used to connect two levels and
direction can be adjusted to suit
traffic flow.
This arrangement allows
customers to travel quickly to
upper floors without any waiting
time.
Customers have to walk past
strategically placed merchandise
displays.
Existing types of system 37
Figure 4.3.2A - Escalators in double
bank with interrupted traffic in two travel
direction.
Figure 4.3.2B - The other view of
escalator.
Figure 4.3.2C - The travelator is located
at the first floor to second floor.
Figure 4.3.2D - The travelator is located
at the second floor to third floor.
Figure 4.3.2E - The notice signboard is
placed on the glazing of the travelator
Figure 4.3.2F - The signboard of Giant Mall
show that the arrangement of travelator.
Existing types of system 38
4.4 Electrical Supply and Distribution System
Electricity in Giant Mall is mostly used for air conditioning, lighting, elevators, escalators,
appliances, etc. Electricity from the power station is stepped up from the power plant to
keep loss of electricity to a minimum due to resistance of the material transmitting
electricity, usually copper. As shown in the diagram below, before the distribution stations,
it is further stepped down to either 275kv or 132kv and when it reaches the substation, it
is stepped down to 33kv. The local substations would further reduce the electricity from
33kv to 11kv, which the Giant Mall uses. In the Giant Mall, the transformer further steps it
down to the usable voltages.
Figure 4.4A - Generally explanation on how power is transmitted to buildings.
Existing types of system 39
Figure 4.4B - Transmission.
a) Main Switch Board / Distribution Panel
The main switchboard is a large assembly of panels which contains switches which
allow electricity to be redirected. It is to divide the main current into smaller currents
for further distribution control of current. With main switch board, one can control
the electrical supply of the entire network from just one area. The function of a
switchboard is to allow the division of the current supplied to the switchboard into
smaller currents for further distribution and to provide switching and current
protection.
Figure 4.4C - Main Switch
Board Box.
Existing types of system 40
b) Sub-Switch Board
The sub-switch board has the same functionality of the main switch board which is
to connect and disconnect the electric supply from the main switchboard. It is
enclosed and sheet steel fabricated.
Figure 4.4D - Sub Switch Board Box is mounted on the wall in electrical riser.
Sub-switch board consists of circuit breakers and bus bars. Circuit breakers functions are
almost same as fuses. Circuit breakers are able to protect for high current incomes and
feeders power supply. Busbars is function as transmit high electrical current in a
distribution panel. Busbars connect switchgear t clear faults and de-energize equipment.
Figure 4.4E - Details of distribution panel.
Existing types of system 41
c) Generator Set
The generator sets provide adequate power and supply for the entire building to run
under emergencies such as fire and also as a standby system where it is always
ready to power the building. The generator will start running automatically when
there is a power failure.
Figure 4.4F - Gen-set room in Giant Mall.
d) Transformer
Transformer room is where the step-down transformers are placed. A transformer
is device that changes or transformers alternating current (ac) of one voltage to
alternating current of another voltage. A varying current in the transformer’s primary
winding creates a varying magnetic flux in the core and a varying magnetic field
impinging on the secondary winding. A “Danger” sign is placed on the door of
transformer room.
Figure 4.4G - Transformer room in Giant
Mall.
Existing types of system 42
e) Electrical Conduit Tee
Conduit can protect the cable physical damage and heat. PVC electrical conduit is
rigid and lightweight which is durable and readily cut.
Figure 4.4H - Electrical Conduit Tee.
f) Substation
Substations transform voltage from high to low, or the opposite, or perform any of a
few other essential capacities. Between the generating station and consumer,
electric power may flow through several substations at different voltage levels.
Figure 4.4I - Substation in Giant Mall.
Existing types of system 43
5.0 Part 3 & 4 (Problems and Recommendations)
5.1 Problems and recommendations: Fire Protection System
5.1.1 Problem and recommendation of passive fire protection system
During the visit, we observed that there were some problems of the passive fire protection
system in the Giant Kelana Jaya Mall. There are no maintenance and replacement of the
damaged systems.
First and foremost, refer to the figure 5.1.1.A, the floor of escape route is cracked and
some holes are formed, although the escape route fulfils the requirement of the UBBL
Article 169. We can observe that the maintenance was done before, but the holes still
remain and do not cover properly. As the fire occurs, the occupants would escape to the
ground floor from the second floor, there are big possibility that they will fall down as the
floor is not smooth enough for them to run to the safety place.
The figure 5.1.1.B shows that one of the nosing of the staircase is broken. If the occupant
walks down from the stair, especially a kid, they may get hurt by the sharp surface of tiles.
The rubbish is thrown at the staircase will obstruct the occupant to escape or fall down. So,
we recommend the operator of the building should provide the maintenance to cover the
holes on the floor by using the suitable grade of the concrete to perform a straight and
smooth solid walkway. New nosing tile is replaced. The cleaner should clean the staircase
regularly, according to working time schedule.
Figure 5.1.1B Figure 5.1.1A
Problems & Recommendations 44
Secondly, we can observe from the figure 5.1.1.C, the handle of the fire door is missing.
The handle must be intended against the fire such as stainless steel. The replacement
should be done as soon as possible to make sure the door is operated normally in order
to provide the basic security and safety (Figure 5.1.1.D).
Figure 5.1.1C Figure 5.1.1D
Moreover, we can observe that there is no signage or ‘crack’ signage on the fire resistant
doors (Figure 5.1.1.E, F, G). Based on the Malaysia Standard Section 7 Article 33.1.9
(page 148),
“All fire doors other than lift entrance doors should be marked with the appropriate fire
safety sign conforming to MS 982 according to whether the door is to be kept closed when
not in use. Fire doors to cupboards and to service ducts should be marked on the outside.
All other fire doors should be marked on both sides.”
The main purpose of the signage is to alert the customers and workers to keep the door
closed so as to fulfill the fire safety compliance. The extra sign on the surface of the push
bars of the fire door is used to instruct the users to push the door in the fire emergency.
So, we can recommend the operator to put a new signage on the fire door same as signage
on the figure 5.1.1.H.
Problems & Recommendations 45
Figure 5.1.1.E Figure 5.1.1.F Figure 5.1.1.G Figure5.1.1.H
Besides, the trolley and the letter box are placed in the fire escape route. It totally breaks
the Malaysian Standard Section 4 Article 10.4.3 (d) (page 46),
“All escape routes and escape doors (both internally and externally) can be kept free from
obstruction.”
The staircase should always clear and free of obstruction according to UBBL Article 110.
A signboard shall be placed on the wall to remind the users to keep the exit clear at any
circumstances (Figure 5.1.1.K). So, the mailbox and the trolley should be removed from
the escape route so that the maximum amount of occupants can fix into the safety route.
Figure 5.1.1.I Figure 5.1.1.J Figure 5.1.1.K
Problems & Recommendations 46
Furthermore, we found that there are some fire doors cannot close automatically as the
door closer is loosen (Figure 5.1.1.L). Section 7 Article 33.1.6.1 of the Malaysian Standard
states that, “Fire doors can only operate correctly if they are fully closed at the time of fire.
It is, therefore, normally necessary for them to be fitted with a self-closing device.”
In this situation, we recommend the owner to replace a new door closer (Figure 5.1.1.M)
to make sure all the self closure devices operate normally, then the fire doors can fully
closed and form a fully protective barrier in the fire event.
Figure 5.1.1.L Figure 5.1.1.M
In addition, the fire resistant door surface is broken. Refer to figure 5.1.1.N, the paint is
shed off. Section 7 Article 33.1.1 of the Malaysian Standard states that,
“The fire door should have function to protect escape routes from the effects of fire”
The fire door is used to prevent the spreading of fire or smoke to the safety route. A good
condition fire door is to ensure it reaches the fire resistance capability. The door should be
under maintenance or repaint it to ensure it can withstand more longer when fire occur.
We recommend the Intumescent paints for painting the old timber fire door. The purpose
of this paint is to protect all types of materials from the heat generated by the fire as it
forms an insulating coating. It is also known as fire resistant paints. It can be used for
internal and external structures. Figure 5.1.1.P shows the example of Intumescent Paint.
Problems & Recommendations 47
Figure 5.1.1.N Figure 5.1.1.O Figure 5.1.1.P
There is no fire exit stair signage through whole escape route (Figure 5.1.1.Q). Section 5
Article 16.4 of the Malaysian Standard states that,
“Every doorway or other exit providing access to a means of escape, other than exits in
ordinary use (e.g. main entrances), should be distinctively and conspicuously marked by
an exit sign in accordance with MS 983. Final exit levels from stairs should be clearly
marked as such, particularly where the exit opens off a stair that continues down or up
beyond the level of the final exit.”
So, we recommend all the fire exit stair signature should be placed on the wall to inform
the occupants of where is the final exit (Figure 5.1.1.R).
Figure 5.1.1.Q Figure 5.1.1.R
Problems & Recommendations 48
From the observation, we found that the lift didn’t have the sign board to warn the occupant
from using the lift when a fire emergency occur (Figure 5.1.1.S). Malaysian Standard
Annexe K (page 388) (i) mentioned about,
“Prohibition signs are used to prohibit behavior likely to increase or cause danger.”
So we recommend that the sign “In the event of fire do not use this lift”, shall be displayed
on the visible area or beside the lift to get the occupants’ attention. (Figure 5.1.1.T)
Figure 5.1.1.S Figure 5.1.1.T
Problems & Recommendations 49
5.1.2 Problem and recommendation of active fire protection system
Active fire protection systems such as water sprinkler and fire extinguisher are commonly
used in the industries for protection. They are used to control or extinguish the fire. Based
on Draft Malaysian Standard 11M001R1 clause 7.4, fire protection systems might not
provide for the continuity of the fire safety strategy if they are not regularly and properly
inspected, tested or maintained. However, during the visit to Giant Kelana Jaya Mall, I
found out that there are several problems with some of the active fire protection systems
inside the mall.
Firstly, the hose reels are not being sited in an accessible and appropriate position
because there are a lot of obstructions surrounding them as shown from the pictures below:
According to Malaysian Standard MS 1489-1:1999 clause 15.2.1, hose reels should be
sited in prominent and accessible positions at each floor level adjacent to exits in corridors
on exit routes, in such a way that the nozzle of the hose can be taken into every room,
having regard to any obstruction. In this case, when there is an occurrence of fire, it will
definitely take the fire fighter some time to reach the hose reel due to the obstructions
nearby, hence more human lives will be threatened. Therefore, in order to prevent
something miserable from happening, we strongly recommend the management to remove
Figure 5.1.2.A Figure 5.1.2.B
Problems & Recommendations 50
those obstructions such as the trolleys as seen in figure 5.1.2.A from obstructing a person
to reach the hose reel.
In addition, I also found out that there are a lot of wastage being disposed around the fire
protection systems.
People are taking this for granted which is a very incorrect act. This act will lead to
damages of quality of the fire protection systems. In this situation, I suggest that the
cleaning services of the mall must be improved. Also, a sign board of ‘please do not simply
litter’ or ‘no littering here’ like figure 5.1.2.E can be added as well.
Figure 5.1.2.C Figure 5.1.2.D
Figure 5.1.2.E
Problems & Recommendations 51
Moreover, the workers of the mall have treated the closet(figure 5.1.2.F) and room(figure
5.1.2.G and figure 5.1.2.H) for storing the fire protection systems such as hose reel and
fire extinguisher as their own storage space to keep unnecessary objects.
All of these objects can be considered as obstructions during the occurrence of fire. As
mentioned earlier, these obstructions will delay the time of fire being put out when a fire
occurs. Thus, the mall must set up a strict management system to inform every worker of
the mall to locate their working tools and personal belongings in a proper corner. This may
help to improve the aesthetic value of the mall as well.
Figure 5.1.2.F Figure 5.1.2.G Figure 5.1.2.H
Problems & Recommendations 52
Next, most of the water sprinkler heads inside the mall are in really bad condition.
Figure 5.1.2.I, figure 5.1.2.J and figure 5.1.2.K show us the corrosion of the water sprinkler
heads. However, the issue is being ignored by the management office as those rusted
water sprinkler heads are still not being serviced or replaced yet. This can lead to all sorts
of problems, including leaking heads, damaged pipes as well as outright failure.
Furthermore, if the water sprinklers fail to function properly when the mall is on fire, the fire
may spread very quickly and uncontrollably, thus safety of the occupants will be affected.
As a result, building owner is responsible for replacing any sprinkler component that is
rusted or corroded. I also suggest the management to contact the specialists to perform
the repairment of the fire sprinkler system as soon as possible.
Lastly, when I entered one of the emergency exit inside the mall, I realized that there was
a fire extinguisher being placed on floor as shown in figure 5.1.2.L and figure 5.1.2.M.
Figure 5.1.2.I Figure 5.1.2.J Figure 5.1.2.K
Problems & Recommendations 53
Figure 5.1.2.M Figure 5.1.2.L
According to BS 5306-8:2000, fire extinguisher should be sited as below:
In a conspicuous location that is easily accessible.
Not in cupboards or behind doors.
Not above cookers or other heat emitters, or in any place of excessive heat or cold.
Hung on wall brackets within easy reach, not placed on floor.
Carrying handle 1 metre above floor for heavier extinguishers (liquid based) and 1.5
metres for others.
Along escape routes near to a door leading to a place of safety.
Positioned in a wall recess so as not to obstruct general movement.
A maximum distance of 30 metres from the site of a possible fire.
Repeated location on each storey.
The situation seen from figure 5.1.2.L and figure 5.1.2.M has offended some of the points
stated above because the fire extinguisher is not being hung on wall bracket within easy
reach but placed on ground. Fire extinguishers have avoidably to be kept on ground or
floor in condition where dampness may cause corrosion to them. Apart from that, the
extinguisher from figure 5.1.2.L and figure 5.1.2.M is sited near the emergency exit where
it may obstruct the general movement of the people. Hence, the fire extinguisher should
be removed away and hung back to the wall brackets immediately. The management
should also perform periodical check on every fire extinguisher to ensure that they are in
good condition.
Problems & Recommendations 54
5.2 Problems and recommendations: Vertical Transportation
5.2.1 Problem 1
The mall that we choose for our assignment is Giant Mall which is located at Kelana Jaya.
This shopping mall does not provide passenger elevator to the customers but have the
freight elevator. Although the passengers can use the freight elevator to reach the desired
floor level, the freight elevator is located far from the crowd. In addition, the freight elevator
is not showing on the floor plan of the shopping mall and it will be difficult for the customers
to find out. So, it is not convenience for the disabled people or old people to visit this mall
as escalator and travelator are not suitable for transporting wheelchairs and baby carriages.
Figure 5.1.2A –The floor plans of Giant Mall only show the location of escalator and
travelator.
Problems & Recommendations 55
Recommendation
According to UBBL 124, stating that “For all non-residential buildings exceeding 4 storeys
above or below the main access level at least one lift shall be provided”. Therefore, I will
recommend the wheelchair accessible escalator to Giant Mall in order to solve accessibility
problems for disabled people. Nowadays, this systems are commonly used at the public
space in many countries, especially train stations and airport. For example, Japan train
stations, Kuala Lumpur International Airport 2 (KLIA2).
How is it works?
The concept of this escalator is similar to the normal escalator design. The only thing that
is changed is when a disabled people who uses a wheelchair needs to use the escalator,
the staff need to help them to press a button to make three steps of the escalator move
together vertically to form a flat platform that can accommodate the wheelchair. Electric
wheelchair users also can use it. Once the user is on the platform with the wheelchair, the
escalator will move until the user reaches the end. When the user leaves the escalator,
the platform will convert back into three independent steps.
Figure 5.1.2B – Since some places do not have lift or wheelchair accessible escalator, the
passengers are being compelled to use dangerous way to reach the desired floor level. It can
cause injury to himself as well as the passengers behind.
Problems & Recommendations 56
User safety is another important element of the design. While the approximately 5cm block
can prevent the wheelchair from moving forward. The escalator also includes a backup
battery system to supply energy in the case of a power cut when the user is in the middle
of the trip so that the user will always be able to reach their destination without problems.
Figure 5.1.2E – The approximately 5cm block prevent the
wheelchair from moving forward.
Figure 5.1.2C - The three steps move together vertically
to form a platform that can accommodate the wheelchair. Figure 5.1.2D – The wheelchair
accessible escalator used in
Japan.
Problems & Recommendations 57
The advantages and disadvantages of wheelchair accessible escalator
Advantages:
It is cost effective as it can save the money to install the elevator and solve the
problem of accessibility for disabled people.
Saving the space of installing elevator instead of using wheelchair accessible
escalator.
Disadvantages:
The process takes 1-2 minutes and normal passengers cannot use during the
operation.
It requires help from the staff to press the button if the passengers are not able to
press the button.
Problems & Recommendations 58
5.2.2 Problem 2
The escalator or travelator safety signage provided beside the escalator are not sufficient.
The safety signs are important as they inform the public of the directions and cautions
while using elevators or travellator to ensure passenger safety.
Figure 5.2.2B - The escalator
safety signage in Giant Mall only
provide the basic safety
information.
Figure 5.2.2A - The escalator and travelator safety signage provided are not sufficient.
Problems & Recommendations 59
Recommendation
The relevant department should add some additional safety signage beside the escalator
or travelator in order for the public to increase their safety awareness when using the
escalator or travelator.
According to figure 5.2.2C (right), the 10 safety messages signs and symbols should apply
for the escalator and travelator:
Please use lift provided – with lift in blue circle mandatory symbol.
Hold handrail – with hand holding graphic in blue circle mandatory symbol.
Children must be supervised – with parent and child in blue mandatory circle symbol.
No wheelchairs – with wheelchair in red prohibition circle.
No prams or strollers – with pram in red prohibition symbol.
No motorized mobility equipment – with mobility scooter in red prohibition circle.
No trolleys – with shopping trolley in red prohibition symbol.
Keep feet away from sides – with person’s foot in red prohibition sign symbol.
Caution Crocs shoes – with shoe symbol in yellow safety triangle
No sitting or leaning on handrail – with persons in red prohibition symbols.
Figure 5.2.2C – Escalator safety guide can also be added to the safety signage. (left)
The example of completed safety signage. (right)
Problems & Recommendations 60
5.2.3 Problem 3
Noisy operation problem occur in the travelator which located near to KFC. Although all
travelator will generate some noise, the level of noise generated should be relatively
uniform throughout the system, and not increase over time. Squeaks, vibrations, and
rubbing noises are usually the result of excessive component wear or improper adjustment.
The noise produce in this particular travelator is relatively high compare to other travelator
in the building.
Recommendation
Proper maintenance should be carry out. The maintenance officer should rate the noise
generated by the travelator relative to other travelator. So that necessary maintenance can
be carry out.
Figure 5.2.3A - Shown the location of travelator in the floor
plan.
Problems & Recommendations 61
5.2.4 Problem 4:
Although the overall maintenance of the elevator is good, there is still a slightly problem
occur in the interior part of the elevator cab which is the paint painted in the elevator started
to fall apart. This will affect the aesthetic appearance of the lift.
Recommendation
The maintenance office should carry out a paint job to restore the aesthetic appearance of
the interior part of elevator cab.
Figure 5.2.4A - Show the interior of elevator cab and the red circle represent the area
need to be fix.
Problems & Recommendations 62
5.2.5 Problem 5 (Electrical)
When we visited the loading bay at Giant Mall, the elbow is uncovered and the connection
of the wires are loose. It is very dangerous as the wires will be exposed to rain water. Once
the wires expose to the water, it may cause electrical short circuit and affect the operation
of the building.
Recommendation
This is a serviceability problem so the relevant department can repair the elbow as soon
as possible to ensure the safety of the passengers as well as the staffs. I recommend them
to change the external elbows into stainless steel and below are the advantages and
disadvantages of stainless steel.
Advantages:
More durable than plastic and steel.
Stainless steel is corrosion resistant.
Longevity and reduce the costly maintenance and
replacement.
Disadvantages:
More expensive compared to plastic and steel elbow.
Figure 5.2.5A - The elbow at the loading bay is not covered and the wires will be exposed.
Figure 5.2.5B – Stainless steel
elbow and accessories.
Problems & Recommendations 63
6.0 Conclusion
Conclusion, the building systems that used in Giant Kelana Jaya Mall all we have learned
in this module. When the officer bring us walk around, at the time we have given some our
opinion to the problem like the hose reel is located too high, the electrical riser room didn’t
lock and others. Therefore, we wish the officer will take our suggestions in order to provide
better building service systems to the public. So building services is important to a building,
especially shopping mall, commercial block, school, and others. Nowadays people cannot
live without building services like telecommunication, air-conditioning and others services.
So, we have responsibility to take care those services especially those services in public
places.
Conclusion 64
df
7.0 Appendix
Project Schedule Proposal
29th Sept 2015 Approval of Letter of Requisition by school.
16th Oct 2015 Meeting 1- Arrange each group member’s job and make a
date for site visit.
23th Oct 2015 1st Site Visit and submit the letter to composite office.
26th Oct 2015 Meeting 2- Discuss each problems and make a date for 2nd
site visit.
30th Oct 2015 2nd Site Visit.
16th Nov 2015 Meeting 3- Discuss about the presentation’s power point.
21th Nov 2015 Meeting 4- Compile, final check up and blinding the report
24th Nov 2015 Rehearsal for presentation
25th Nov 2015 Presentation & Submission of assignment
Member’s Work Scope
Content Name
Acknowledgment Jenny Hoo Yee Tyng
Abstract Jenny Hoo Yee Tyng
Part 1 : Purpose of the building as case study Jenny Hoo Yee Tyng
Part 2 : Existing types of system Chiam Jia Ern
Khor Ka Nee
Part 3 & 4 : Problems and Recommendations
Hii Pai Ling
Liew Chia Niu
Na Yeow Sing
Ng Jia Nan
Conclusion Jenny Hoo Yee Tyng
Appendix Jenny Hoo Yee Tyng
Slide arrangement Na Yeow Sing
Appendix 65
8.0 Reference
GCH Retail Sdn. Bhd. [Online] Available at http://www.giant.com.my/contact-
us/contact.aspx (Accessed on 21th October 2015)
Escalator Safety Signage – custom made symbols. (n.d.). Retrieved from
http://www.signblitz.com.au/portfolio/escalator-safety-sign/
Escalator Adapted Wheelchair. (n.d.). Retrieved from http://www.japan-
accessible.com/transport/train/escalator/escalator.htm
Universitat Politècnica de Catalunya. "Student Designs Innovative Escalator That
Is Accessible To All Users." ScienceDaily 29 June 2009. Retrieved from
www.sciencedaily.com/releases/2009/06/090615152928.htm
James E. Piper “Handbook of Facility Assesmemt” 1 Jan 2004. Retrieved on 10
Nov 2015 from
https://books.google.com.my/books?id=rUD8OqqYZzoC&printsec=frontcover&sou
rce=gbs_ge_summary_r&cad=0#v=onepage&q&f=false
Noise Control in Building Services: Sound Research Laboratories Ltd, 22 Oct
2013. Retrieved on 10 Nov 2015 from
https://books.google.com.my/books?id=xfwgBQAAQBAJ&printsec=frontcover&so
urce=gbs_ge_summary_r&cad=0#v=onepage&q&f=false
Guide to Intumescent Paint and Fire Retardant Paint and Fire Resistant Coatings |
British Safety Standard BS 476. (n.d.). Retrieved November 21, 2015, from
http://www.diydoctor.org.uk/projects/fire-retardant-paint.htm
Fire Sprinkler System Repair - Lumar Fire Protection. (n.d.). Retrieved November 23, 2015, from http://www.lumarfireprotection.com/fire-sprinkler-system-repair/
Draft Malaysian Standard. (n.d.). Retrieved November 21, 2015, from
http://www.sirim.my/srmc/documents/Sept-Oct-2014/11M001R1_PC.pdf
Fire-rated Door Preventive Maintenance Ensures Function - Facility Management
Fire Safety Quick Read. (n.d.). Retrieved November 21, 2015, from
http://www.facilitiesnet.com/firesafety/tip/Fire-rated-Door-Preventive-Maintenance-
Ensures-Function--25010
Corrosion in Fire Sprinkler Systems - Fire Sprinkler Corrosion. (n.d.). Retrieved
November 21, 2015, from http://ecscorrosion.com/faq/
MS 1489 Hose Reels - Documents. (n.d.). Retrieved November 21, 2015, from
http://documents.mx/documents/ms-1489-hose-reels.htm
References 66