1

Acme ElectricTransformer Seminar

2

“BUCK-BOOST”

APPLICATIONS

Transformer Seminar

3

What are BUCK-BOOST TRANSFORMERS?

BUCK-BOOST TRANSFORMERS START OUT AS ISOLATION TRANSFORMERS WITH OUTPUTS FROM 12 TO 48 VOLTS, WHICH GET FIELD CONNECTED AS “AUTO” TRANSFORMERS TO INCREASE OR DECREASE VOLTAGE WITHIN A RANGE OF 5 TO 20 PERCENT. (ie, 208 T0 230 V)

THEY DO NOT PROVIDE ISOLATION FROM THE SUPPLY BECAUSE THEY ARE “AUTO” CONNECTED DURING INSTALLATION!

4

PRIMARY SECONDARY

AUTOISOLATION

“Isolation” vs. “Auto”

5

BASIC PRINCIPLE

CURRENT WILL FOLLOW PATH OF LEAST RESISTANCE

6

PRIMARY & SECONDARY have the same CAPACITY

7

BOOSTING CONNECTION COIL VOLTAGES ADD

8

AUTO CONNECTION INCREASES KVA CAPACITY

9

DATA needed to SELECT BUCK-BOOST TRANSFORMER

1. SYSTEM PHASE2. SYSTEM FREQUENCY3. LINE VOLTAGE4. LOAD VOLTAGE5. LOAD KVA, AMPS, OR HORSEPOWER

(Available line voltage should be measured whenever possible)

10

SELECTION EXAMPLE #1

1. 1-PHASE2. 60 HZ3. LINE - 189 VOLTS4. LOAD - 208 VOLTS5. LOAD - 4 KVA

11

1-PHASE GROUP I CHART

REFER TO 1-PHASE GROUP I SELECTION CHART IN SECTION VII OF CATALOG ATD-01.

12

CONNECTION DIAGRAM

13

SELECTION EXAMPLE # 2

1. 1 - PHASE2. 60 HZ3. LINE - 208 VOLTS4. LOAD - 240 VOLTS5. LOAD - 60 AMPS

14

1-PHASE GROUP II CHART

REFER TO 1-PHASE GROUP II SELECTION CHART IN SECTION VII OF CATALOG ATD-01.

15

CONNECTION DIAGRAM

16

SELECTION EXAMPLE # 3

1. 1 - PHASE2. 60 HZ3. LINE - 240 VOLTS4. LOAD - 208 VOLTS5. LOAD - 14 KVA

17

1-PHASE GROUP II CHART

REFER TO 1-PHASE GROUP II SELECTION CHART IN SECTION VII OF CATALOG ATD-01.

18

CONNECTION DIAGRAM

19

SELECTION EXAMPLE # 4

1. 3 - PHASE2. 60 HZ3. LINE - 208 VOLTS4. LOAD - 230 VOLTS5. LOAD - 80 KVA

20

3-PHASE GROUP I CHART

REFER TO 3-PHASE GROUP I SELECTION CHART IN SECTION VII OF CATALOG ATD-01.

21

Connection Diagram B-B

22

BUCK-BOOST SLIDE CHART

DEMONSTRATE SLIDE CHART

(No longer available)

23

TYPICAL APPLICATIONS for BUCK-BOOST TRANSFORMERS

1. AIR CONDITIONERS2. AC MOTORS3. PUMPS4. TANNING BEDS (No. 1 application)5. CONTROL CIRCUITS

24

GENERAL APPLICATION COMPARISONSTANDARD ISOLATION TRANSFORMER

Handle large increases or decreases in voltageProvide electrical isolation and shielding if required

BUCK-BOOST TRANSFORMERSHandle small increases or decreases in voltage (+/-

5 to 20%)Do not provide electrical isolation (because they

get “auto” connected)

25

Effects of LOW VOLTAGE on MOTOR OPERATION

VOLTAGE CURRENT TEMPERATURE- 5 % + 5 % + 11 %

- 10 % + 11 % + 23 %

- 15 % + 17 % + 38 %

26

• DETERIORATE INSULATION• NUISANCE TRIPPING OF BREAKERS• INSUFFICIENT MOTOR TORQUE• WASTED ENERGY AND MONEY

Effects of LOW VOLTAGE on MOTOR OPERATION

27

Effects of LOW VOLTAGE on MOTOR TORQUE

% RATED VOLTS % RATED TORQUE

100% 100% 90% 81%

80% 64%

28

Causes of VOLTAGE MISMATCH

• SERVICE VOLTAGE CHANGED AFTER EQUIPMENT INSTALLED

• VOLTAGE DROP IN POWER LINE

• ERRORS IN ORDERING EQUIPMENT

• UTILITY CUTBACK IN SOURCE VOLTAGE

29

GENERAL SIZE COMPARISON

STANDARD ISOLATION TRANSFORMER• 16”H X 14”W X 11”D 125 LBS• 1O KVA RATING

BUCK-BOOST TRANSFORMER• 10”H X 6”W X 5”D 24 LBS• 1 KVA RATING

30

ACME BUCK-BOOST FEATURES

• UL LISTED/CSA CERTIFIED• UL 3R ENCLOSURES• ALLOWABLE UNDER NEC• EPOXY ENCAPSULATED• (EXCEPT 50, 100, 150 VA)• BROAD RANGE OF VOLTAGES • TEN YEAR WARRANTY

31

Buck Boost Hands-On LabIn this exercise we will wire a typical Buck-Boost transformer for the following

applications:

Input Output Diagram Connection Type 120v 12v K Isolation 120v 24v L Isolation 240v 12v M Isolation 240v 24v N Isolation 120v 132v C Auto 120v 144v D Auto 120v 100v D Auto (reverse input & output)

32

Buck Boost “Isolation” Diagrams

33

Buck Boost “Auto” Diagrams

34

Buck Boost Hands-On LabIn this exercise we will wire a typical Buck-Boost transformer for the

following applications:

Input Output Diagram Connection Type 120v 12v K Isolation120v 24v L Isolation240v 12v M Isolation240v 24v N Isolation120v 132v C Auto120v 144v D Auto120v 100v D Auto (reverse input & output)

35

Buck Boost “Isolation” Diagrams

36

Buck Boost “Auto” Diagrams

37

Questions?