Self-Healing Multi-DropFiber Optic Modem (Dual Channel)
Model TC2100
•AsyncDataRatesupto38.4Kbps
•ProtocolTransparent
•All-DigitalDesign
•MultipleMasterCapability
•Multimode(850/1300nm)orSingleMode(1300/1550nm)
•RS-232,RS-422orRS-485(2/4-wire)
•LocalandRemoteLoopbackTests
•OpticalLoopIntegrityTest
•Anti-Streaming(Anti-Jabber)
•LocalDryContactAlarmRelay
•HardenedTemperatureVersions(optional)
•Hi-Temp2VersionExceedsNEMA&CaltransTrafficControlSpecs
he TC2100 Multi-Drop Fiber Optic Modem provides maximumreliability for linking monitoring devices (typically RTUs or PLCs)
to a Host Controller or CPU. It is completely transparent to data orcommunicationsprotocols.
TheTC2100canbeconfiguredinRingorSelf-HealingRingtopologies.TheSelf-HealingRingschemeissophisticated, i.e. itdetectsupstreamanddownstreamfailuresonbothTxandRx,andautomaticallyre-routesanycableorequipmentfailure.TC2100masterandTC2101slaveunitsareinterchangeablebysettingadipswitch.“Multiplemaster”unitsareoptional.
It supports asynchronous data rates up to 38.4 Kbps. ElectricalinterfacesareRS-232,RS-422orRS-485.TheRS-485electricalportcanbemulti-dropped.Therearetwooptionalversions(ModelTC2100T)forextremetemperatureapplications(-20°Cto70°C&-40°Cto80°C).
Each unit comes standard with two pairs of fiber interfaces andeither 2-Channel RS-232 or 1-Channel RS-422/RS-485 interfaces. ThesecondchannelontheRS-232interfacecanbeusedfordata,RTS/CTShandshakingsignalsorasatelephoneextensionwiththeModelTC1900“Quick-Talk”phoneadapter.
Localandremoteloopbackisstandard.DiagnosticLEDsareprovidedto help installation and troubleshooting. Dry contact alarms can beconnected to RTUs/PLCs to indicate specifically where a fault hasoccurred.Atestsignalgeneratorforverifyinglinkintegrityisprovidedtoaid installationandtroubleshooting.“Anti-streaming”capability isstandard.
The TC2100 is compatiblewith all popular types and sizes offiberoptic cable and is availablemultimode (850/1300nm) or singlemode(1300/1550nm).FiberopticconnectorsareSTorFC.ElectricalconnectorsareDB25female.Poweris12VDC;optional24VDC,-48VDC,125VDCor115/230VACwithanexternalpowercube.
T
Applications
Renownedforitshighreliability,theTC2100Multi-DropModemisidealforRingorSelf-HealingRingcommunicationlinksinSCADA,TrafficControl,IndustrialProcessControlandSecurityNetworks.ItisfrequentlyusedtointerconnectRemoteTerminalUnits(RTUs)orProgrammableLogicControllers(PLCs)inUtilitysubstationSCADANetworks.
TC Communications, Inc.17881 Cartwright Rd. Irvine, CA 92614 U.S.A.
Tel: (949) 852-1972, Fax: (949) 852-1948Sales: (800) 569-4736
Web Site: www.tccomm.comE-mail: sales@tccomm.com
2XTC2100R(HousedinTCRM19619”Wide,1UHighRackmountCardCage)
TC2100SStandaloneUnit
SCADAMASTER
Ch. 1
Ch. 2
Ch. 1 Ch. 2
Ch. 2
RS-232
Ch.1 Ch. 2
RS-232
RS-232
Ch. 1Ch. 2
AMRMASTER
Self-HealingFiber Optic Ring(SCADA & AMR)
Fiber
Copper
MeterM
MM
M
M
TC2101
TC2101
TC2100(Master)
Sample Application #1
TC2101
TC2101
RS-232
RS-232
Ch. 1
CENTRALCOMPUTER
Ch. 1
Ch. 1
Ch. 1 RS-232
RS-232
Ch. 2
Ch. 2
RS-232
2-wire
2-wire
POTS
POTSCh. 1
RS-232
RS-232
RS-232
PBXorKEY
SYSTEM
FiberCopper
TC1900
TC1900
TC2101
TC2101
TC2100(Master)
PUBLICSWITCH
TELEPHONENETWORK
Ch. 1
Sample Application #2
Self-HealingFiber Optic Ring
(Traffic Control & Voice)
TC2101
TC2101
Typical SCADA and AMR Application Using TC2100 “ Self-Healing” Fiber Modems In a Utility Substation Environment
Typical Poll Response Application Using TC2100 “Self-Healing” Fiber Modems In a Traffic Control Environment
What Makes the TC2100 Self-Healing Ring Different from Other Vendors?
ManyoftheTC2100’sfeaturesarecriticaltonetworkoperation;someareuniqueforaproductofthistype.Itisimportanttonotethattheterm“Self-HealingRing”meansdifferentthingstodifferentvendors.BecausethereisnoindustrystandardforSelf-HealingRings,vendorofferingsvarygreatlyintermsoffunction,featuresandsophis-tication.
TheTC2100SelfHealingRingdiffersfromcompetitorofferingsinitssophistication.Thissophisticationenablesittobuildinavarietyofuserbenefitsoftennotavailablewithmanyothervendor’sSelf-HealingRings.
Thesebenefitsinclude:
•The TC2101 Slave Unit Provides Loop Monitor Signal LEDs that Detect if any Incorrect Fiber Cables are Con-nected.
SolidlylitgreenLPA(Loop“A”)andLPB(Loop“B”)LEDsindicateanormalsystem;blinkinggreenLEDsin-dicatethatthefibercableshavebeencross-connected.
Somevendorsdonotofferanysimplemeanstoverifythatthefiberopticcablesarecross-connectedatre-motenodes.
Thisisabsolutelycritical!Forexample,ifatechnicianin-advertentlycross-connectstheRingAandRingBcablestoamodem,thenetworkwillappeartofunctionnor-mally,buttheSelf-Healingportionwillnotbeoperable.Techniciansmusthavespecificdiagnosticstopinpointwheretheerrantcablecross-connecthasoccurred.
•The TC2100 can Detect Faults Both Upstream and Downstream from Each Unit.
TheTC2100candetectcablebreakageatbothtransmitandreceivingsides.Somevendor’sSHRproductsdetectcablebreakageonlyatthereceivingside.Unlessthedevicecandetectfailuresatthetransmitside,thereisnowaytoknowifthenextdeviceisreceivingthesignal(seeadjacentdiagram).
•The TC2100 Prevents any Type of Echo Effect.
Somevendorsofferaself-healingschemethatdoesn’tseparatebroadcastandreceivechannels.Thisoftenresultsinan“Echo”effectthatcandisablenetworkcommunications.(”Echo”happenswhenthedatasignaltransmittedintotheMasterunit,andaroundthering,isreceivedbackattheMasterunit’sport).
•Each TC2101 (Slave) Includes a Dry Contact Alarm which Enables Pinpointing any Fault.
Techniciansmustbeabletopinpointexactlywhereafaulthasoccurred.Adryalarmcontactonthemodem’smasterunitindicateswhenself-healinghasoccurredsomewhereonthering.Dryalarmcontactsfromthemodemslaveunitsoneithersideofafaulteffectivelypinpointthelocationofthebreakorfailure(seedia-gram).
•The TC2100 Offers a Multiple-Master Self-Healing Ring Topology.
Thisinnovativeconfigurationvirtuallydoublesthereli-abilityofasingleMasterbecauseitcanrecoverfaultsorfailuresinbothringsAandBintwodifferentplaces(Seediagramonpage4).SystemintegrityismaintainedbecausebothMasterunitspolltheSlavesatthesametime,butthroughdifferent“half”rings.
•The TC2100 Provides Two Channels for Data, Con-trols or a Telephone Link (via the TC1900 Telephone Adapter)
UsetwochannelsforRS-232oroneforRS-422orRS-485.YoucanalsoaddtelephoneservicebyusingtheTC1900RS-232TelephoneExtender.TheTC1900iscompatiblewithmostanalogPBXsandenablesdial-uptelephoneextensionstobepluggedintoRS-232circuits.
•The TC2100 Provides a Built-In Test Signal Generator to Verify Optical Loop Integrity
Abuilt-intestsignalgeneratorprovidesasimpleandeffectivemethodforaselftestverifyinglinkintegrity.
FiberCopper
Tra�cController
TC21011tluaF2tluaF
4tluaF3tluaF
TxA
RxBTxB
RxA
XX XX
Fiber breakage
RS-232
SCADAMASTER
RTU/PLC
RTU/PLC
RTU/PLC
RTU/PLC
TC2101
TC2101
TC2101
dry contact
dry contact
TC2101
TC2100(Master)
X
RS-232
dry contacts CLOSE
Data RatesAsyncRS-232,RS-422,RS-485..............................................upto38.4Kbps*
OpticalTransmitter............LED/ELED/LASER*Receiver...............................PINDiodeWavelength..................850/1300nm Multimode..............1300/1550nmSingleMode
FiberOpticConnectors....................................ST,OptionalFCLossBudget*-850/1300/1550nm15dB........Multimode@62.5/125μm20dB...........SingleMode@9/125μm
ElectricalConnector......................DB25FemaleInterface............(DCEorDTE)RS-232,............RS-422,orRS-485(2or4-wire)
SystemBitErrorRate.............1in109orbetter
Diagnostic Functions..............Local & Remote Loopback,......SignalGenerator,DisableAlarm,......................................LoopMonitor
Visual Indicators........MSTR,SLAV,Sync-A,Sync-B,Vcc,............PWRA,PWRB,ALARM,BRD-1,............BRD-2,RSP-1,RSP-2,LPA,LPB,..............................................A2B,B2A
AlarmDryContact....................NormalOPEN
PowerStandard...................12VDC @300mAOptional.....24VDC,−48VDC,125VDC,..........or115/230VACw/power cube
TemperatureOperating ...................−10°C to 50°CHi-Temp1 (optional)...−20°C to 70°CHi-Temp2 (optional)...−40°C to 80°CStorage .......................−40°C to 90°CHumidity ........95% non-condensing
Physical (Standalone Unit)Height..........................(3.53cm)1.39”Width.........................(18.13cm)7.14”Depth.........................(16.59cm)6.53”Weight.......................(567gm)1.25lbs
*Contactfactoryforhigherrequirements(LASER)
Note: Information contained in this data sheet is subject to change without prior notice.
TC Communications, Inc. 17881 Cartwright Road
Irvine, CA 92614 U.S.A.Factory Tel: (949) 852-1972
Fax: (949) 852-1948
Sales OfficeU.S.A. Domestic International:
(800) 569-4736 (949) 852-1973
Web Site: www.tccomm.comE-mail: sales@tccomm.com
®
#1045959
Self-healing function is activated on bothupstream and downstream TC2101 Slaves
TC2101 Unit Fails Fiber Cable Breaks
Dual MasterSelf-Healing Fiber Ring(Multimode or Single Mode)
Master #2
Master #1
TC2101
TC2100
TC2100
SCADAMASTER #1
SCADAMASTER #2
TC2101
TC2101
TC2101
TC2101
Amultiplemastertopology(seediagramatleft)providesmaximumreliability.ItcanmaintainRingintegritydespitefaultsorfailuresinbothringsinseveraldifferentplaces,dependingonthenumberofmasterunits.
ASelf-HealingRingconsistsoftwodatapaths,RingAandRingB,witheachdatapathrunninginanoppositedirectiontotheother.Undernormaloperationonlytheprimarydatapath(RingA)isused.
DTS-21000-01-04Rev.070213
TC2100 Self-Healing Ring with Multiple Masters
Whenthereisfault(cableorfaileddevice),thedatapathwillturnaroundbeforeitreachesthefaultorfailedunitandusethesecondarydatapathtocompletethelink.Inthismanner,thedata/communicationpathremainsintact.