Best Ever Alarm System Tool

Xihui Chen,

Katia Danilova,

Kay Kasemir

SNS/ORNL

kasemirk@ornl.gov

April 2009

2 Managed by UT-Battelle for the Department of Energy

Previous Attempts •  First ALH,

then soft-IOCs and EDM generated from ALH config. (Pam Gurd) –  GUI

• Static Layouts • N clicks to see (some of the) active alarms

–  Configuration •  .. was bad Always too many alarms • Operator guidance? • Related displays? • Changes required contacting one of the 2 experts, edit

correct config files, restarts: seldom happened –  Info

• Most frequent alarm? • Timeline of alarm?

3 Managed by UT-Battelle for the Department of Energy

New End-User View: Alarm Table •  All current

alarms –  new, ack’ed –  Sort by PV,

Descr., Time, Severity, …

•  Optional: Annunciate or Enunciate

•  Acknowledge one or multiple alarms –  Select by PV or description –  BNL/RHIC type un-ack’

4 Managed by UT-Battelle for the Department of Energy

Another View: Alarm Tree

•  All alarms – Disabled, inactive, new, ack’ed

•  Hierarchical – Optionally only show

active alarms – Ack’/Un-ack’ PVs or sub-tree

5 Managed by UT-Battelle for the Department of Energy

Guidance, Related Displays, Commands

  Basic Text

  Start EDM screen

  Open web page

  Run ext. command

Hierarchical: Including info of parent entries

Merges Guidance etc. from all selected alarms

6 Managed by UT-Battelle for the Department of Energy

.. Within CSS

 Alarms

 History of PV

 EPICS Config.

7 Managed by UT-Battelle for the Department of Energy

CSS Context Menus Connect the Tools

Send alarm PV to any other CSS PV tool

8 Managed by UT-Battelle for the Department of Energy

Convenient E-Log Entries

•  “Logbook” from context menu creates text w/ basic info about selected alarms. Edit, submit.

•  Pluggable implementation, not limited to Oracle-based SNS ELog

9 Managed by UT-Battelle for the Department of Energy

.. optionally w/ Authentication/Authorization

 Log in/out while CSS is running

Online Configuration Changes

10 Managed by UT-Battelle for the Department of Energy

Add PV or Subsystem

1.  Right-click on ‘parent’

2.  “Add …”

3.  Enter name

Online. No search for config files, no restarts.

11 Managed by UT-Battelle for the Department of Energy

Configure PV

•  Again online

•  Especially useful for operators – update guidance,

related screens.

12 Managed by UT-Battelle for the Department of Energy

Logging •  ..into generic CSS log also used for error/warn/

info/debug messages

•  Alarm Server: State transitions, Annunciations

•  Alarm GUI: Ack/Un-Ack requests, Config changes

• Generic Message History Viewer – Example w/ Filter on TEXT=CONFIG

13 Managed by UT-Battelle for the Department of Energy

Logging: Get timeline

•  Example: Filter on TYPE, PV

1. PV triggers, clears, triggers again

2. Alarm Server latches alarm

4. Problem fixed

3. Alarm Server annunciates

5. Ack’ed by operator

6. All OK

14 Managed by UT-Battelle for the Department of Energy

Various Web Reports

15 Managed by UT-Battelle for the Department of Energy

Technical View

Alarm Cfg & State RDB

IOCs

Alarm Server Current Alarms: Acknowledged? Transient? Annunciated?

LOG

Message RDB

JMS 2

Speech

JMS 2

RDB

Tomcat - Reports

CSS Applications

Alarm Client GUI

JMS

Alarm Updates Ack’; Config Updates Annunciations Log Messages

TALK ALARM_CLIENT ALARM_SERVER

PV Updates (Channel Access, …)

16 Managed by UT-Battelle for the Department of Energy

Alarm Server Behavior Similar to ALH

 Latch highest severity, or non-latching –  like ALH “ack. transient”

 Chatter filter ala ALH •  Alarm only if severity persists some minimum time •  .. or alarm happens >=N times within period

 Annunciation (or Enunciation, or both)

 Optional formula-based alarm enablement: –  Enable if “(pv_x > 5 && pv_y < 7) || pv_z==1” –  … but we prefer to move that logic into IOC

 When acknowledging MAJOR alarm, subsequent MINOR alarms not annunciated –  ALH would again blink/require ack’

17 Managed by UT-Battelle for the Department of Energy

Best Ever Alarm System Tools, Indeed

.. but Tools are only half the issue

Good configuration requires plan & follow-up.

B. Hollifield, E. Habibi, "Alarm Management: Seven (??) Effective Methods for Optimum Performance", ISA, 2007

18 Managed by UT-Battelle for the Department of Energy

Alarm Philosophy

Goal:

Help operators take correct actions

 Alarms with guidance, related displays  Manageable alarm rate (<150/day)  Operators will respond to every alarm

(corollary to manageable rate)

19 Managed by UT-Battelle for the Department of Energy

•  DOES IT REQUIRE IMMEDIATE OPERATOR ACTION? – What action? Alarm guidance!

• Not “make elog entry”, “tell next shift”, … • Consider consequence of no action

•  Is it the best alarm? – Would other subsystems, with better PVs, alarm at the

same time?

What’s a valid alarm?

20 Managed by UT-Battelle for the Department of Energy

How are alarms added?

•  Alarm triggers: PVs on IOCs – But more than just setting HIGH, HIHI, HSV, HHSV – HYST is good idea – Dynamic limits, enable based on machine state,...

Requires thought, communication, documentation

•  Added to alarm server with – Guidance: How to respond – Related screen: Reason for alarm (limits, …), link

to screens mentioned in guidance – Link to rationalization info (wiki)

21 Managed by UT-Battelle for the Department of Energy

Impact/Consequence Grid Category So What Minor Consequence Major Consequence

Personnel Safety PPS independent from EPICS?

Environment, Public

Can EPICS cause contained spill of mercury?

Uncontained spill??

Cost: Beam Production, Downtime, Beam Quality

No effect

Beam off < 1 sec?

Beam off <10 min

<$10000

Beam off >10min

>$10000

• Mostly: How long will beam be off?

22 Managed by UT-Battelle for the Department of Energy

.. combined with Response Time Time to Respond Minor Consequence Major Consequence

>30 Minutes NO_ALARM MINOR

10..30 minutes MINOR MAJOR

<10 minutes MAJOR MAJOR + Annunciate

–  This part is still evolving…

23 Managed by UT-Battelle for the Department of Energy

Example: Elevated Temp/Press/Res.Err./…

•  Immediate action required? –  Do something to prevent interlock trip

•  Impact, Consequence? –  Beam off: Reset & OK, 5 minutes? –  Cryo cold box trip: Off for a day?

•  Time to respond? –  10 minutes to prevent interlock?  

•  MINOR? MAJOR?

•  Guidance: “Open Valve 47 a bit, …”

•  Related Displays: Screen that shows Temp, Valve, …

24 Managed by UT-Battelle for the Department of Energy

“Safety System” Alarms

•  Protection Systems not per se high priority – Action is required, but we’re safe for now, it won’t

get worse if we wait

•  Pick One   “Mommy, I need to gooo!”   “Mommy, I went”

(Does it require operator action? How much time is there?)

25 Managed by UT-Battelle for the Department of Energy

Avoid Multiple Alarm Levels •  Analog PVs for Temp/Press/Res.Err./…:

– Easy to set LOLO, LOW, HIGH, HIHI

•  Consider:

•  In most cases, HIGH & HIHI only double the alarm traffic – Set only HSV to generate single, early alarm – Adding HHSV alarm assuming that the first one is

ignored only worsens the problem

26 Managed by UT-Battelle for the Department of Energy

Bad Example: Old SNS ‘MEBT’ Alarms

•  Each amplifier trip: ≥ 3 ~identical alarms, no guidance

•  Rethought w/ subsystem engineer, IOC programmer and operators: 1 better alarm

27 Managed by UT-Battelle for the Department of Energy

Alarms for Redundant Pumps

28 Managed by UT-Battelle for the Department of Energy

Alarm Generation: Redundant Pumps the wrong way

•  Control System – Pump1 on/off status – Pump2 on/off status

•  Simple Config setting: Pump Off => Alarm: –  It’s normal for the ‘backup’ to be off – Both running is usually bad as well

• Except during tests or switchover

– During maintenance, both can be off

29 Managed by UT-Battelle for the Department of Energy

Redundant Pumps

•  Control System – Pump1 on/off status – Pump2 on/off status – Number of running pumps – Configurable number of desired pumps

•  Alarm System: Running == Desired? – … with delay to handle tests, switchover

•  Same applies to devices that are only needed on-demand

1 Required Pumps:

30 Managed by UT-Battelle for the Department of Energy

Weekly Review: How Many? Top 10?

31 Managed by UT-Battelle for the Department of Energy

A lot of information available

•  How often did PV trigger?

•  For how long?

• When?

•  Temporary issue? Or need HYST, alarm delay, fix to hardware?

32 Managed by UT-Battelle for the Department of Energy

Weekly Check: Stale? Forgotten?

33 Managed by UT-Battelle for the Department of Energy

GUI: Similar to SNS GUI shown here

JMS

CSS Other

RDB

LOG ALARM

JMS2RDB

IOC

LDAP

Interconnection Server

Similar: DESY Alarm System

Filters

Filt.Alrm

No Channel Access Monitor of selected alarm PVs!

IOCs push all alarms via new protocol into Interconn. Server.

34 Managed by UT-Battelle for the Department of Energy

Design Choices •  Similar alarm table and tree GUIs

•  JMS for communication –  slightly different messages, though

•  DESY IOCs send all alarms, then filtered in AMS –  DESY: All IOC alarms should show up in AMS, zero additional

configuration –  At SNS, how many of the 350000 PVs would send alarms?

We want to make the addition of alarms simple, but not automatic, and encourage guidance, related displays.

•  DESY/SNS: LDAP vs. RDB for configuration/state –  Choice was based on available infrastructure.

•  JMS Listeners –  SNS: Logger, Annunciator –  DESY: Logger, Send SMS, EMail, Voice Mail

35 Managed by UT-Battelle for the Department of Energy

AMS – Alarm Message System Configuration Views

-  AMS is a JMS (Java Message Service ) based Information-System.

-  It offers different options for message distribution: -  SMS -  E-Mail -  Voices-Mail -  Another JMS Topic

-  Messages are sent on the basis of filtered PV. (Filters can be combined: AND/OR – Sequence)

-  The recipients are Users or User groups. User groups can be used in two ways.

-  Send to all Users -  Send to one after another until a user confirms the message

•  User, User groups as well as Filters and Actions are configures in the AMS configuration View

Slide info from Helge Rickens, DESY

36 Managed by UT-Battelle for the Department of Energy

AMS

Editor to configure a

Filter

Different views to select User, User-

Group, Filter condition, Filter and Alarm Topics

Slide info from Helge Rickens, DESY

37 Managed by UT-Battelle for the Department of Energy

Summary

•  BEAST operational since Feb’09 –  Needs a logo –  For now without BEAUtY –  DESY AMS is similar and has been

operational for longer

•  Pick either, but good configuration requires work in any case –  Started with previous “annunciated” alarms

•  ~300, no guidance, no related displays •  Now ~330, all with guidance, rel. displays

–  “Philosophy” helps decide what gets added and how •  Immediate Operator Action? Consequence?

Response Time? –  Weekly review spots troubles and tries to improve

configuration