Protection Relay Testing:

Testing of Generator Protection Relay type SEL300G

Page 3: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Under & Over Voltage Protection (27/59)Negative sequence Protection (46)Reverse & Low Forward Power Protection (32)Over Excitation Protection (24)Over & Under Freq. Protection (81O/81U)Under Impedance Protection (21)Loss of Excitation Protection (40G)100% Stator E/F Protection (27TN/64G2)

Page 4: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Out of Step Protection (78)Voltage Restrained O/C Protection (51VR)Voltage Controlled O/C Protection (51VC)Rotor E/F Protection (64R)Breaker Failure ProtectionGenerator Differential Protection (87D)Ground differential Protection (87N)95% Stator E/F Protection (59GN/64G1)

Page 5: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Primary & Backup Protection

Page 6: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Rotor Earth Fault Protection

Page 7: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 8: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 9: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Characteristic plotted in F6TEST2.21 software for testing

Load Encroachment characteristic plotted

Zone2 Reach

Zone1 Reach

Page 10: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Select “D” from List

Page 11: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

GCB Status Close Input

Page 12: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Breaker close input & VT fuse fail input

Page 13: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 14: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 15: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 16: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 17: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

VT fuse fail Status Input

Characteristic selection

Page 18: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

V/Hz Curve1

Page 19: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

V/Hz Curve2

Page 20: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

V/Hz Curve3

Page 21: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Selection of Curve

Page 22: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 23: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 24: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Set as a Low Forward Power threshold range

Set as a Reverse Power threshold range

Page 25: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Set as Reverse Power function

VT Fuse fail Input

Page 26: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300GRelay Logic for Reverse Power Function

Page 27: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 28: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 29: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

VT fuse fail Status Input

Offset reactance for Zone1

Zone1

Zone2

Offset reactance for Zone2

Directional Angle for Zone2

Page 30: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Directional Angle for Zone2

Page 31: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Relay Logic for Loss of Excitation Function

Page 32: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 33: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 34: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Enter Setting of NPS Threshold

Enter Time Dial Setting

Page 35: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300GRelay Logic for Negative Sequence current Function

Page 36: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 37: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Select function “V”

Page 38: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Threshold value

Curve selection “C1”

VT fuse fail status input

Page 39: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

K = 0.25Normal Inverse Curve

Page 40: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 41: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Select function “C”

Page 42: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Threshold value

Curve selection “C1”

VT fuse fail status input

Page 43: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

K = 0.2Normal Inverse Curve

Page 44: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 45: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

0-95% SEF

100% SEF

Page 46: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 47: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 48: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 49: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Page 50: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Under Freq. function

Under Freq. function

Page 51: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Test Equipment

• Make : DOBLE

• Model : F6150

Software

• F6TesT Version 2.21-1165

Page 52: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

F6150 Connections:

CT ConnectionsPT Connections

Page 53: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300 Connections:PT ConnectionsCT Connections

Connections of 4th Voltage for 100% SEF

Page 54: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Over Excitation Function (24)

Page 55: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

I1

I2

I3

SEL

Test Circuit: Over Excitation Function Test

Source Configurations:3V X 3I

CT Inputs

Page 56: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Inverse Time Curve Test

Tests conducted:

Page 57: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “VFChar” Module for Characteristic Search Test

Page 58: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Curve3 selection

Enter Time Dial

Page 59: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Curve3 for Testing

Page 60: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Expected Curve

Actual Curve from relay

Phasor

Select “ABC” Fault for testing

Relay settings:V/Hz = 1PUCurve = 3Time Dial = 1

Page 61: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Reverse Power Function (32)

Page 62: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Reverse Power Protection (32R): Example1

G D Y

GT

GCB

Gen Set

G D Y

GT

GCB

Gen Set

CB1

CB2

CB3

CB4

CB

5

TL Line

TL Line

MW

MW

Healthy Prime-mover

Failed Prime-mover

MVAR

MVAR

E

E

Page 63: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Reverse Power Protection (32R): Example2

G D Y

GT

GCB

Gen Set

G D Y

GT

GCB

Gen Set

CB1

CB2

CB3

CB4

CB

5

TL Line

TL Line

MW

MW

Healthy Prime-mover

Failed Prime-mover

MVAR

MVAR

E

E

Page 64: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Reverse Power Protection (32R): Example3

G D Y

GT

GCB

Gen Set

CB1 CB3

CB

5

TL LineMW

Failed Prime-mover

MVAR

E

Active Power Import from Grid sources

Grid

GridMW

MW

MW

Page 65: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Reverse Power Protection (32R): Example4

GD YTR1

GCB

Gen Set

Failed Prime-mover

MVAR

E

Only Reactive Power Export to Loads

CB1 CB2

D YTR2

CB3 CB4

MC

B5CB6

Load

sLo

ads

Page 66: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

I1

I2

I3

SEL

Test Circuit: Reverse Power Function Test

Source Configurations:3V X 3I

CT Inputs

Page 67: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Pickup Test

• Time Test

Tests conducted:

Page 68: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “RAMP” Module for Pickup Test

Page 69: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test @ Unity PF:

MW- MW

- MVAR

MVAR

Watts = VA = 952.87W

- MVAR

MVAR

MW- MW

IExpected = 1A

Page 70: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test @ Unity PF:Vn = 110VIn = 5APF = 1 (Unity)PN = (1.7325*0.11*1000*5) = 952.87watts%PSet = 20% of PN

PSet = (952.87 * 20)/(PF*100) = 190.5wattsIExpected = (190.5)/(1.7325*0.11*1000*PF) = 1A

Page 71: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Expected Value = 1A Enter “Action”details

Pickup

Actual Operating Values

IA@180o

Page 72: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test @ 0.8 lag PF:

MW- MW

- MVAR

MVAR

Watts = 762.3W

- MVAR

MVAR

MW- MW

IExpected = 1.15A

VA = 952.87VA

Page 73: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Expected Value = 1.15A Enter “Action”details

Pickup

Actual Operating Values

IA@150o

Page 74: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test @ 0.8 lead PF:

MW- MW

- MVAR

MVAR

Watts = 762.3W

- MVAR

MVAR

MW- MW

IExpected = 1.15AVA = 952.87VA

Page 75: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Expected Value = 1.15A Enter “Action”details

Pickup

Actual Operating Values

IA@210o

Page 76: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “SSIMUL” Module for Time Test

Page 77: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Page 78: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

TExp = 200ms

TAct = 262ms

Page 79: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Loss of Excitation Function (40G)

Page 80: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

IA

IB

IC

SEL

Test Circuit: Field Failure Function Test

Source Configurations:3V & 3I

3V

3I

Page 81: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Characteristic Search Test

• Characteristic Time Test

• RCA (MTA) Test

Tests conducted:

Page 82: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “ZChar” Module for Characteristic Search Test

Page 83: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Zone1 setting = 20.4Ohms

Zone2 setting = 30.5Ohms

Page 84: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Show Phasors: fault voltage & current of “ABC” fault

Blue color shows expected characteristic and pink color shows actual tested characteristic

Page 85: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on Oscillograph: Shows, voltage & current waveform of “ABC” fault

Page 86: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Zone1 setting = 20.4Ohms

Zone2 setting = 30.5OhmsOffset = -3.5 Ohms

Page 87: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Show Phasors: fault voltage & current of “ABC” fault

Blue color shows expected characteristic and pink color shows actual tested characteristic

Page 88: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “ZTime” Module for Characteristic Time Test

Page 89: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Show Phasors: fault voltage & current of “ABC” fault

Results Table shows; Zone1 time is 0.1s & Zone2 time is 0.4s

Page 90: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300G: Field Failure Function Testing

Page 91: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300G: Field Failure Function Testing

LED Indicator operated

Page 92: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “ZMTA” Module for Characteristic MTA (RCA) Test

Page 93: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Fault type “ABC” selected for testing

Angle Boundary (Theta1)

Angle Boundary (Theta2)

Page 94: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300G: Field Failure Function Testing

Page 95: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Negative Sequence Function (46)

Page 96: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Negative Sequence Protection (46)

Ia

Ic

Ib

Ia

Ic

Ib

IaIc

Ib

+VE Seq. -VE Seq. Zero Seq.

Sequence Components

Page 97: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

G D Y

GT

GCB

Gen Set

MWMVAR

E

3

46

Operate: I2Measure>I2Set

Sys

MVARMW

F1

Negative Sequence Protection (46)

Page 98: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

G D Y

GT

GCB

Gen Set3

46

Operate: I2Measure>I2Set

F1

Negative Sequence Protection (46)

33

IR @ 0o

IY @ 120O

IB @ 240O

Page 99: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

I1@0o

I2@120o

I3@240o

SEL

Test Circuit: Negative Phase Seq. Function Testing

Source Configurations:3I

3I

Page 100: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Inverse Time Curve Test

Tests conducted:

Page 101: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “IChar” Module for Characteristic Search Test

Page 102: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Curve selection

Enter Time Dial

Page 103: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Inverse Curve for Testing

Page 104: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Blue color line shows “Expected curve” & Pink color line shows “Actual tested curve”

Phasors shows symmetrical componentsvalue (i.e. I1, I0 & I2)

Page 105: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Voltage Controlled Over Current Function (51VC)

Page 106: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Voltage Controlled over current function (51VC):

Normally Protection applied for Directly connected Generators where system voltage collapse drastically falls below set value (VSet) during faults.

Voltage Dependent Over Current Protection (51V)

G GCB

D Y

3

51VC Y Y

CB1 3

51

D YCB2 3

51

CB2 3Motpro

MVT

F1

F26.37 MVA11KVPF = 0.8, Xd”=36.4%, Xd’=26%Xd = 231%

1.5MVA, 11KV/0.415KV, %Z = 4.9%

1.5MVA, 11KV/0.415KV, %Z = 4.9%

Page 107: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

V/Vs

I*/ [I>]

0.2 0.8

0.2

1.0

51V-Voltage Controlled

Vmeasured < VsetIpickup = (k*Iset)T = (0.14*T) / ((Ipickup)0.02-1)

Vmeasured > VsetIpickup = (Iset)T = (0.14*T) / ((Ipickup)0.02-1)

Voltage Dependent Over Current Protection (51V)

Page 108: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

IA

IB

IC

SEL

Test Circuit: Voltage Controlled O/C Function Testing

Source Configurations:3V & 3I

3V

3I

Page 109: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Inverse Time Curve Test

Tests conducted:

Page 110: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “IChar” Module for Characteristic Search Test

Page 111: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Curve selection

Enter Time Dial

Relay Settings:I> = 0.5*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N

Page 112: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Characteristic created for testing

Relay Settings:I> = 0.5*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N

Page 113: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Injected Voltage to relay

Page 114: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Display Phasors

Blue color shows expected characteristic and pink color shows actual tested characteristic

Right click on check box to enable voltage O/P

Page 115: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Voltage Restrained Over Current Function (51VR)

Page 116: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Voltage Restrained over current function (51VR):

Normally Protection is applicable when Generator is connected to system through GT.

Voltage Dependent Over Current Protection (51V)

G GCB3

51VC Y Y

VT

D Y

D YCB1 3

51

D YCB2 3

51

CB2 3

Motpro

M

F1

F2

Page 117: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

IA

IB

IC

SEL

Test Circuit: Voltage Restrained O/C Function Testing

Source Configurations:3V & 3I

3V

3I

Page 118: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

V/Vs

I*/ [I>]

0.2 0.8

0.2

1.0

51V-Voltage restrained Vmeasured > Vset2Ipickup = (Iset)

Vmeasured < Vset1Ipickup = (k*Iset)

Vset1 < Vmeasured < Vset2

Slope region

Voltage Dependent Over Current Protection (51V)

Page 119: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Inverse Time Curve Test

Tests conducted:

Page 120: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “IChar” Module for Characteristic Search Test

Page 121: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Curve selection

Enter Time Dial

Relay Settings:I> = 1*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N

Page 122: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Characteristic created for testing

Relay Settings:I> = 1*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N

Page 123: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Injected Voltage to relay

Page 124: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Display Phasors

Blue color shows expected characteristic and pink color shows actual tested characteristic

Right click on check box to enable voltage O/P

Page 125: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of 0-95% Stator Earth Fault Function (64R1/59GN)

Page 126: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Stator Ground Fault Protection (59GN): Resistor Ground

Maximum Ground Fault Amps = (Line to Neutral Voltage)-------------------------------------

(NGR Resistance)

VLN = 21000/1.7325

100 Ohms, 10s

IFIF PTR = 21000/240V

CTR = 20/1A

Page 127: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Stator Ground Fault Protection (59GN): Impedance Ground (NGT)

VLN = 21000/1.7325KVPri = 21kVKVSec = 0.240kVKVA = 70KVA R = 0.913 Ohms Full Load current in Primary wdg = 3.33A Ground Fault Impedance = 3640.004 Ohms

IF

Page 128: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

VN

SEL

Test Circuit: 0-95% SEF Function Testing

Source Configurations:4V

3V

4th V@50Hz

Page 129: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Pickup Test

• Time Test

Tests conducted:

Page 130: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “RAMP” Module for Pickup Test

Page 131: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

4th Voltage used

Expected value = 5VActual value = 5.3V

Pickup Value = 5V

Action details for Voltage Ramp

Page 132: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “SSIMUL” Module for Time Test

Page 133: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Ground Fault condition

Display Phasor

Page 134: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Ground Fault condition

Display Waveforms (Analogue & Digital Channels)

4th Voltage

Page 135: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Actual trip time = 1s

Relay Output (Open to Close contact)

Page 136: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of 100% Stator Earth Fault Function (64R2/27TN)

Page 137: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Stator Ground Fault Protection (27TN)

3rd HarmonicCurrent circulate

Page 138: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Stator Ground Fault Protection (27TN): 3RD

Harmonic Under Voltage Method3rd Harmonic Under voltage relay

3rd Harmonic Voltage at Neutral End reduced

3rd Harmonic Voltage at Neutral End reduced

IF

3rd harmonic voltage dropBecause capacitanceIs shorted

IF

Page 139: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

VN

SEL

Test Circuit: 100% SEF Function Test

Source Configurations:4V

3V

4th V@150Hz

Page 140: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Pickup Test

• Time Test

Tests conducted:

Page 141: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “RAMP” Module for Pickup Test

Page 142: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

4th Voltage used @ 150Hz Freq.

Expected value = 1VActual value = 1.2V

Pickup Value = 1.2V

Action details for Voltage Ramp

Page 143: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “SSIMUL” Module for Time Test

Page 144: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Ground Fault condition close to Neutral

Page 145: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Actual trip time = 0.55s

Relay Output (Open to Close contact)

Page 146: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300G: 100%SEF Function Testing

LED Indicator operated

Page 147: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Under Frequency Function (81UF)

Page 148: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

IA

IB

IC

SEL

Test Circuit: Under Freq. Function Test

Source Configurations:3V & 3I

3V

3I

Page 149: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Pickup Test

• Time Test

Tests conducted:

Page 150: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “RAMP” Module for Pickup Test

Page 151: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Freq. of Voltage sources

Expected value = 48.5HzActual value = 48.498Hz

Pickup Value = 48.5Hz

Action details for Freq. Ramp

Page 152: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “SSIMUL” Module for Time Test

Page 153: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Under Frequency condition (48Hz Freq. for Voltage sources)

Page 154: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Actual trip time = 0.33s

Relay Output (Open to Close contact)

Page 155: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Over Frequency Function (81O/F)

Page 156: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

IA

IB

IC

SEL

Test Circuit: Over Freq. Function Test

Source Configurations:3V & 3I

3V

3I

Page 157: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Pickup Test

• Time Test

Tests conducted:

Page 158: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “RAMP” Module for Pickup Test

Page 159: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Freq. of Voltage sources

Expected value = 51HzActual value = 51.0002Hz

Pickup Value = 51.0002Hz

Action details for Freq. Ramp

Page 160: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “SSIMUL” Module for Time Test

Page 161: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Over Frequency condition (51Hz Freq. of Voltage sources)

Page 162: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Actual trip time = 93.9ms

Relay Output (Open to Close contact)

Page 163: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300G: 100%SEF Function Testing

LED Indicator operated

Page 164: 43.SEL300G Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Training to L&T Power at Doble Training Center