422 South Forest Street, Seattle, WA 98134

Tel: 206-623-8750 Fax: 206-623-2091

PCI Job # 15-2210

MacDonald Miller7717 Detroit Ave SWSeattle, WA 98106

Attention: Dan McCarttProject: Block 45Reference: Submittal Insulation 230713 Ductwork Insulation

Section Product230713 2.1 A Johns-Manville230713 2.2 A Johns Manville FSK 1.5" .75lb Microlite Duct Wrap230713 2.2 B Johns Manville FSK 3" .75lb Microlite Duct Wrap230713 2.2 C Johns Manville Linacoustic RC Sound Liner230713 2.2 D ***not applicable to this project230713 2.2 E MEI 22-15 Eco-Hanger Grip Adhesive Lo Voc230713 2.2 F AGM Perforated Base Insul-hangers230713 2.2 G Venture Tape FSK Insulation Tape 1525CW230713 2.2 H RPR 16 ga T316 SS Tire Wire

Attached are the manufacturer’s submittal data. Please return a copy of the signedsubmittal.

Respectfully,

Carrie Grage

Estimator

February 23, 2015

Certified JM Formaldehyde-free™ Fiber Glass InsulationCertified JM Formaldehyde-free™ fiber glass insulation offers superior thermal and acoustical performance—and it improves indoor air quality because it’s made without formaldehyde. Why is that important? Because the U.S. Environmental Protection Agency (EPA) recommends limiting exposure to formaldehyde as much as possible, and the California Air Resources Board, a division of the California EPA, recommends that builders and architects use building materials and insulation made without formaldehyde.

Air Handling Systems

Microlite® EQFormaldehyde-free™ Fiber Glass Duct Wrap Insulation

DescriptionMicrolite EQ Formaldehyde-free™ duct wrap insulation is a brown, lightweight, highly resilient, blanket-type thermal insulation. The insulation blanket is manufactured from rotary-process fiber glass bonded with a resin made primarily from rapidly renewable plant-based materials.

Available Forms Microlite EQ Formaldehyde-free™ insulation is available in a variety of densities, thicknesses and roll lengths. It is supplied with an FSK (foil-scrim-kraft) vapor barrier facing to meet installed performance requirements, with a 2" (51 mm) stapling tab.

UsesMicrolite EQ insulation is recommended as thermal insulation for the exterior of HVAC systems or other spaces or surfaces where temperature control is required.

Facing Information

FSK Aluminum Foil Reinforced with fiber glass scrim laminated to UL-rated kraft. Permeance: 0.02 perms*

* Per ASTM E96, Procedure A for facing material prior to lamination. After lamination, permeance values may be higher.

General Properties

Temperature (max.) – ASTM C411 250°F (121°C) Water vapor sorption – ASTM C1104 <5% by weight Corrosivity with steel – ASTM C665 Does not accelerate Fungi resistance – ASTM C1338 Does not breed or promote

Standard Thicknesses and Packaging

100' Roll 75' Roll 50' Roll (31 m) (23 m) (15 m)Type Thickness, in (mm) 75 1½ (38) 2, 21⁄3 (51, 58) 3 (76)100 1½ (38) 2 (51) – 150 – 1½ (38) 2 (51)Note: Additional thicknesses, widths and other lengths available on special order. Contact Regional Sales Office for availability.

Surface Burning CharacteristicsMicrolite EQ insulation meets the Surface Burning Characteristics and Limited Combustibility of the following standards:

Standard/Test Method• ASTME84• UL723• NFPA90Aand90B• ULGuideNo.40U8.3.CardR3711• CAN/ULCS102-1188Note: Faced materials are tested as composite products (insulation, adhesive and facing).

Specification Compliance

ASTMC1290 Type75,100&150ASTM C553*TypeII Type75,100&150 Type III Type 150*For faced material: 250°F (121°C) maximum temperature.

ASTM C1136s† Type II FSK Facing†Replaces HH-B-100B, Type II.

Canada:CGSB51-GP-11M NYCMEA40-75-M

Recycled Content

15% minimum post consumer

Maximum Flame Spread Index 25Maximum Smoke Developed Index 50

a a

aa

Carrie_G
Typewritten Text
230713 2.1 A Johns Manville
Carrie_G
Typewritten Text
Carrie_G
Typewritten Text
Carrie_G
Typewritten Text
230173 2.2 A Johns Manville FSK Microlite Duct Wrap
myersh
Text Box
Section 230713 2.2.A Ductwork Insulation

a a

aa 717 17th St. Denver, CO 80202 (800) 654-3103 specJM.com

North American Sales Offices, Insulation Systems

Eastern RegionP.O. Box 158 Defiance, OH 43512 (800)334-2399 Fax:(419)784-7866

Western Region and CanadaP.O. Box 5108 Denver, CO 80217 (800) 368-4431 Fax:(303)978-4661

The physical and chemical properties of the Microlite® EQ Formaldehyde-free™ fiber glass duct Wrap Insulation listed herein represent typical, average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. They are supplied as a technical service and are subject tochangewithoutnotice.Numericalflamespreadandsmokedeveloped ratings are not intended to reflect hazards presented by these or any other materials under actual fire conditions. Check with the Regional Sales Office nearest you to ensure current information. All Johns Manville products are sold subject to Johns Manville’s standard Terms and Conditions, including Limited Warranty and Limitation of Remedy. For a copy of the Johns Manville standard Terms and Conditions, Limited Warranty and Limitation of Remedy, and information on other Johns Manville thermal insulation and systems, call (800) 654-3103.

© 2013 Johns ManvilleJMCO

M130010A

Microlite® EQ Formaldehyde-free™ Fiber Glass Duct Wrap Insulation

Application Recommendations The R-value will vary depending upon how much the insulation is compressed during installation. To obtain the published installed R-values, the insulation stretch-out should be determined using the following table:

Duct Wrap Stretch-outs Installed Labeled Compressed Thick. (in) Thickness (in) Round Square Rectangular 1 0.75 P+ 7.0" P+ 6.0" P+ 5.0"1½ 1.125 P+9.5" P+8.0" P+7.0"2 1.50 P+ 12.0" P+ 10.0" P+ 8.0"21⁄3 1.75 P+ 13.0" P+ 11.0" P+ 8.5"3 2.25 P+ 17.0" P+ 14.5" P+11.5"Stretch-outs include 2" (51 mm) for overlap. P = perimeter of duct to be insulated.

Prepare overlap by removing approximately 2" (51 mm) of insulation from facing.

Stretch-outDimension

2" (51 mm)Overlap

Before applying duct wrap, sheet metal duct shall be clean, dry and tightly sealed at all joints and seams.

Wrap insulation around duct with facing to the outside so the 2" (51 mm) flap completely overlaps facing and insulation at the other end of stretch-out. Insulation shall be snugly butted.

Secure seams with outward clinching staples placed approximately 6" (152 mm) on center. If required, seal seam with pressure-sensitive tape designed for use with duct insulation. Insulation on the underside of ducts spanning 24" (610 mm) or greater shall be secured with mechanical fasteners and speed clips spaced approximately 18" (457 mm) on center. Fasteners should be cut off flush after the speed clips are installed, and when required, sealed with the same tape as specified above.

Adjacent sections of duct wrap insulation shall be snugly butted with the circumferential 2" (51 mm) tape flap overlapping and secured as recommended for the longitudinal seam. When a vapor seal is required, two coats of vapor retarder mastic reinforced with one layer of 4" (102 mm) wide, open-weave glass fabric may be used in lieu of pressure-sensitive tape.

Guide SpecificationsInsulation for Metal Ducts. All ducts shall be insulated on the outside with a Formaldehyde-free™, flexible glass fiber blanket. Microlite EQ Formaldehyde-free™ fiber glass duct wrap insulation should have a minimum installed R-value* of _______, and a Type_____ facing. Insulation shall be furnished with a factory-applied facing with a composite UL FHC rating of 25/50.* The minimum insulation installed R-value should be determined in accordance to the duct operating and ambient conditions.

Installed R-values

Labeled Thickness Installed “R”** Out-of-Package “R”

Type in mm (hr•ft2•°F)/Btu m2•°C/W (hr•ft2•°F)/Btu m2•°C/W75 1½ 38 4.2 0.74 5.2 0.92

2 51 5.6 0.99 6.9 1.2221⁄3 58 6.5 1.15 8.0 1.413 76 8.3 1.46 10.3 1.81

100 1½ 38 4.5 0.79 5.6 0.992 51 6.0 1.06 7.4 1.30

150 1½ 38 4.7 0.83 6.0 1.062 51 6.3 1.11 8.0 1.41

** Installed R-value calculated with a material thickness compressed to a maximum of 25% following recommended duct wrap stretch-outs.

Thermal Conductivity (ASTM C518) k* k Compressed Thickness Labeled ThicknessType Btu•in/(hr•ft2•°F) W/m•°C Btu•in/(hr•ft2•°F) W/m•°C75 0.27 0.039 0.29 0.042100 0.25 0.036 0.27 0.039150 0.24 0.035 0.25 0.036Conductivity at 75°F (24°C) mean temperature. *Tested with material thickness compressed 25%.

AHS-44801/13(New)

Certified JM Formaldehyde-free™ Fiber Glass InsulationCertified JM Formaldehyde-free™ fiber glass insulation offers superior thermal and acoustical performance—and it improves indoor air quality because it’s made without formaldehyde. Why is that important? Because the U.S. Environmental Protection Agency (EPA) recommends limiting exposure to formaldehyde as much as possible, and the California Air Resources Board, a division of the California EPA, recommends that builders and architects use building materials and insulation made without formaldehyde.

Air Handling Systems

Microlite® EQFormaldehyde-free™ Fiber Glass Duct Wrap Insulation

DescriptionMicrolite EQ Formaldehyde-free™ duct wrap insulation is a brown, lightweight, highly resilient, blanket-type thermal insulation. The insulation blanket is manufactured from rotary-process fiber glass bonded with a resin made primarily from rapidly renewable plant-based materials.

Available Forms Microlite EQ Formaldehyde-free™ insulation is available in a variety of densities, thicknesses and roll lengths. It is supplied with an FSK (foil-scrim-kraft) vapor barrier facing to meet installed performance requirements, with a 2" (51 mm) stapling tab.

UsesMicrolite EQ insulation is recommended as thermal insulation for the exterior of HVAC systems or other spaces or surfaces where temperature control is required.

Facing Information

FSK Aluminum Foil Reinforced with fiber glass scrim laminated to UL-rated kraft. Permeance: 0.02 perms*

* Per ASTM E96, Procedure A for facing material prior to lamination. After lamination, permeance values may be higher.

General Properties

Temperature (max.) – ASTM C411 250°F (121°C) Water vapor sorption – ASTM C1104 <5% by weight Corrosivity with steel – ASTM C665 Does not accelerate Fungi resistance – ASTM C1338 Does not breed or promote

Standard Thicknesses and Packaging

100' Roll 75' Roll 50' Roll (31 m) (23 m) (15 m)Type Thickness, in (mm) 75 1½ (38) 2, 21⁄3 (51, 58) 3 (76)100 1½ (38) 2 (51) – 150 – 1½ (38) 2 (51)Note: Additional thicknesses, widths and other lengths available on special order. Contact Regional Sales Office for availability.

Surface Burning CharacteristicsMicrolite EQ insulation meets the Surface Burning Characteristics and Limited Combustibility of the following standards:

Standard/Test Method• ASTME84• UL723• NFPA90Aand90B• ULGuideNo.40U8.3.CardR3711• CAN/ULCS102-1188Note: Faced materials are tested as composite products (insulation, adhesive and facing).

Specification Compliance

ASTMC1290 Type75,100&150ASTM C553*TypeII Type75,100&150 Type III Type 150*For faced material: 250°F (121°C) maximum temperature.

ASTM C1136s† Type II FSK Facing†Replaces HH-B-100B, Type II.

Canada:CGSB51-GP-11M NYCMEA40-75-M

Recycled Content

15% minimum post consumer

Maximum Flame Spread Index 25Maximum Smoke Developed Index 50

a a

aa

Carrie_G
Typewritten Text
230713 2.1 A Johns Manville
Carrie_G
Typewritten Text
Carrie_G
Typewritten Text
Carrie_G
Typewritten Text
230173 2.2 A Johns Manville FSK Microlite Duct Wrap

a a

aa 717 17th St. Denver, CO 80202 (800) 654-3103 specJM.com

North American Sales Offices, Insulation Systems

Eastern RegionP.O. Box 158 Defiance, OH 43512 (800)334-2399 Fax:(419)784-7866

Western Region and CanadaP.O. Box 5108 Denver, CO 80217 (800) 368-4431 Fax:(303)978-4661

The physical and chemical properties of the Microlite® EQ Formaldehyde-free™ fiber glass duct Wrap Insulation listed herein represent typical, average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. They are supplied as a technical service and are subject tochangewithoutnotice.Numericalflamespreadandsmokedeveloped ratings are not intended to reflect hazards presented by these or any other materials under actual fire conditions. Check with the Regional Sales Office nearest you to ensure current information. All Johns Manville products are sold subject to Johns Manville’s standard Terms and Conditions, including Limited Warranty and Limitation of Remedy. For a copy of the Johns Manville standard Terms and Conditions, Limited Warranty and Limitation of Remedy, and information on other Johns Manville thermal insulation and systems, call (800) 654-3103.

© 2013 Johns ManvilleJMCO

M130010A

Microlite® EQ Formaldehyde-free™ Fiber Glass Duct Wrap Insulation

Application Recommendations The R-value will vary depending upon how much the insulation is compressed during installation. To obtain the published installed R-values, the insulation stretch-out should be determined using the following table:

Duct Wrap Stretch-outs Installed Labeled Compressed Thick. (in) Thickness (in) Round Square Rectangular 1 0.75 P+ 7.0" P+ 6.0" P+ 5.0"1½ 1.125 P+9.5" P+8.0" P+7.0"2 1.50 P+ 12.0" P+ 10.0" P+ 8.0"21⁄3 1.75 P+ 13.0" P+ 11.0" P+ 8.5"3 2.25 P+ 17.0" P+ 14.5" P+11.5"Stretch-outs include 2" (51 mm) for overlap. P = perimeter of duct to be insulated.

Prepare overlap by removing approximately 2" (51 mm) of insulation from facing.

Stretch-outDimension

2" (51 mm)Overlap

Before applying duct wrap, sheet metal duct shall be clean, dry and tightly sealed at all joints and seams.

Wrap insulation around duct with facing to the outside so the 2" (51 mm) flap completely overlaps facing and insulation at the other end of stretch-out. Insulation shall be snugly butted.

Secure seams with outward clinching staples placed approximately 6" (152 mm) on center. If required, seal seam with pressure-sensitive tape designed for use with duct insulation. Insulation on the underside of ducts spanning 24" (610 mm) or greater shall be secured with mechanical fasteners and speed clips spaced approximately 18" (457 mm) on center. Fasteners should be cut off flush after the speed clips are installed, and when required, sealed with the same tape as specified above.

Adjacent sections of duct wrap insulation shall be snugly butted with the circumferential 2" (51 mm) tape flap overlapping and secured as recommended for the longitudinal seam. When a vapor seal is required, two coats of vapor retarder mastic reinforced with one layer of 4" (102 mm) wide, open-weave glass fabric may be used in lieu of pressure-sensitive tape.

Guide SpecificationsInsulation for Metal Ducts. All ducts shall be insulated on the outside with a Formaldehyde-free™, flexible glass fiber blanket. Microlite EQ Formaldehyde-free™ fiber glass duct wrap insulation should have a minimum installed R-value* of _______, and a Type_____ facing. Insulation shall be furnished with a factory-applied facing with a composite UL FHC rating of 25/50.* The minimum insulation installed R-value should be determined in accordance to the duct operating and ambient conditions.

Installed R-values

Labeled Thickness Installed “R”** Out-of-Package “R”

Type in mm (hr•ft2•°F)/Btu m2•°C/W (hr•ft2•°F)/Btu m2•°C/W75 1½ 38 4.2 0.74 5.2 0.92

2 51 5.6 0.99 6.9 1.2221⁄3 58 6.5 1.15 8.0 1.413 76 8.3 1.46 10.3 1.81

100 1½ 38 4.5 0.79 5.6 0.992 51 6.0 1.06 7.4 1.30

150 1½ 38 4.7 0.83 6.0 1.062 51 6.3 1.11 8.0 1.41

** Installed R-value calculated with a material thickness compressed to a maximum of 25% following recommended duct wrap stretch-outs.

Thermal Conductivity (ASTM C518) k* k Compressed Thickness Labeled ThicknessType Btu•in/(hr•ft2•°F) W/m•°C Btu•in/(hr•ft2•°F) W/m•°C75 0.27 0.039 0.29 0.042100 0.25 0.036 0.27 0.039150 0.24 0.035 0.25 0.036Conductivity at 75°F (24°C) mean temperature. *Tested with material thickness compressed 25%.

AHS-44801/13(New)

Certified JM Formaldehyde-free™ Fiber Glass InsulationCertified JM Formaldehyde-free™ fiber glass insulation offers superior thermal and acoustical performance—and it improves indoor air quality because it’s made without formaldehyde. Why is that important? Because the U.S. Environmental Protection Agency (EPA) recommends limiting exposure to formaldehyde as much as possible, and the California Air Resources Board, a division of the California EPA, recommends that builders and architects use building materials and insulation made without formaldehyde.

Air Handling Systems

Microlite® EQFormaldehyde-free™ Fiber Glass Duct Wrap Insulation

DescriptionMicrolite EQ Formaldehyde-free™ duct wrap insulation is a brown, lightweight, highly resilient, blanket-type thermal insulation. The insulation blanket is manufactured from rotary-process fiber glass bonded with a resin made primarily from rapidly renewable plant-based materials.

Available Forms Microlite EQ Formaldehyde-free™ insulation is available in a variety of densities, thicknesses and roll lengths. It is supplied with an FSK (foil-scrim-kraft) vapor barrier facing to meet installed performance requirements, with a 2" (51 mm) stapling tab.

UsesMicrolite EQ insulation is recommended as thermal insulation for the exterior of HVAC systems or other spaces or surfaces where temperature control is required.

Facing Information

FSK Aluminum Foil Reinforced with fiber glass scrim laminated to UL-rated kraft. Permeance: 0.02 perms*

* Per ASTM E96, Procedure A for facing material prior to lamination. After lamination, permeance values may be higher.

General Properties

Temperature (max.) – ASTM C411 250°F (121°C) Water vapor sorption – ASTM C1104 <5% by weight Corrosivity with steel – ASTM C665 Does not accelerate Fungi resistance – ASTM C1338 Does not breed or promote

Standard Thicknesses and Packaging

100' Roll 75' Roll 50' Roll (31 m) (23 m) (15 m)Type Thickness, in (mm) 75 1½ (38) 2, 21⁄3 (51, 58) 3 (76)100 1½ (38) 2 (51) – 150 – 1½ (38) 2 (51)Note: Additional thicknesses, widths and other lengths available on special order. Contact Regional Sales Office for availability.

Surface Burning CharacteristicsMicrolite EQ insulation meets the Surface Burning Characteristics and Limited Combustibility of the following standards:

Standard/Test Method• ASTME84• UL723• NFPA90Aand90B• ULGuideNo.40U8.3.CardR3711• CAN/ULCS102-1188Note: Faced materials are tested as composite products (insulation, adhesive and facing).

Specification Compliance

ASTMC1290 Type75,100&150ASTM C553*TypeII Type75,100&150 Type III Type 150*For faced material: 250°F (121°C) maximum temperature.

ASTM C1136s† Type II FSK Facing†Replaces HH-B-100B, Type II.

Canada:CGSB51-GP-11M NYCMEA40-75-M

Recycled Content

15% minimum post consumer

Maximum Flame Spread Index 25Maximum Smoke Developed Index 50

a a

aa

Carrie_G
Typewritten Text
Carrie_G
Typewritten Text
Carrie_G
Typewritten Text
230713 2.2 B Johns Manville FSK
Carrie_G
Typewritten Text
3" Microlite Duct Wrap
myersh
Text Box
Section 230713 2.2.B Ductwork Insulation

a a

aa 717 17th St. Denver, CO 80202 (800) 654-3103 specJM.com

North American Sales Offices, Insulation Systems

Eastern RegionP.O. Box 158 Defiance, OH 43512 (800)334-2399 Fax:(419)784-7866

Western Region and CanadaP.O. Box 5108 Denver, CO 80217 (800) 368-4431 Fax:(303)978-4661

The physical and chemical properties of the Microlite® EQ Formaldehyde-free™ fiber glass duct Wrap Insulation listed herein represent typical, average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. They are supplied as a technical service and are subject tochangewithoutnotice.Numericalflamespreadandsmokedeveloped ratings are not intended to reflect hazards presented by these or any other materials under actual fire conditions. Check with the Regional Sales Office nearest you to ensure current information. All Johns Manville products are sold subject to Johns Manville’s standard Terms and Conditions, including Limited Warranty and Limitation of Remedy. For a copy of the Johns Manville standard Terms and Conditions, Limited Warranty and Limitation of Remedy, and information on other Johns Manville thermal insulation and systems, call (800) 654-3103.

© 2013 Johns ManvilleJMCO

M130010A

Microlite® EQ Formaldehyde-free™ Fiber Glass Duct Wrap Insulation

Application Recommendations The R-value will vary depending upon how much the insulation is compressed during installation. To obtain the published installed R-values, the insulation stretch-out should be determined using the following table:

Duct Wrap Stretch-outs Installed Labeled Compressed Thick. (in) Thickness (in) Round Square Rectangular 1 0.75 P+ 7.0" P+ 6.0" P+ 5.0"1½ 1.125 P+9.5" P+8.0" P+7.0"2 1.50 P+ 12.0" P+ 10.0" P+ 8.0"21⁄3 1.75 P+ 13.0" P+ 11.0" P+ 8.5"3 2.25 P+ 17.0" P+ 14.5" P+11.5"Stretch-outs include 2" (51 mm) for overlap. P = perimeter of duct to be insulated.

Prepare overlap by removing approximately 2" (51 mm) of insulation from facing.

Stretch-outDimension

2" (51 mm)Overlap

Before applying duct wrap, sheet metal duct shall be clean, dry and tightly sealed at all joints and seams.

Wrap insulation around duct with facing to the outside so the 2" (51 mm) flap completely overlaps facing and insulation at the other end of stretch-out. Insulation shall be snugly butted.

Secure seams with outward clinching staples placed approximately 6" (152 mm) on center. If required, seal seam with pressure-sensitive tape designed for use with duct insulation. Insulation on the underside of ducts spanning 24" (610 mm) or greater shall be secured with mechanical fasteners and speed clips spaced approximately 18" (457 mm) on center. Fasteners should be cut off flush after the speed clips are installed, and when required, sealed with the same tape as specified above.

Adjacent sections of duct wrap insulation shall be snugly butted with the circumferential 2" (51 mm) tape flap overlapping and secured as recommended for the longitudinal seam. When a vapor seal is required, two coats of vapor retarder mastic reinforced with one layer of 4" (102 mm) wide, open-weave glass fabric may be used in lieu of pressure-sensitive tape.

Guide SpecificationsInsulation for Metal Ducts. All ducts shall be insulated on the outside with a Formaldehyde-free™, flexible glass fiber blanket. Microlite EQ Formaldehyde-free™ fiber glass duct wrap insulation should have a minimum installed R-value* of _______, and a Type_____ facing. Insulation shall be furnished with a factory-applied facing with a composite UL FHC rating of 25/50.* The minimum insulation installed R-value should be determined in accordance to the duct operating and ambient conditions.

Installed R-values

Labeled Thickness Installed “R”** Out-of-Package “R”

Type in mm (hr•ft2•°F)/Btu m2•°C/W (hr•ft2•°F)/Btu m2•°C/W75 1½ 38 4.2 0.74 5.2 0.92

2 51 5.6 0.99 6.9 1.2221⁄3 58 6.5 1.15 8.0 1.413 76 8.3 1.46 10.3 1.81

100 1½ 38 4.5 0.79 5.6 0.992 51 6.0 1.06 7.4 1.30

150 1½ 38 4.7 0.83 6.0 1.062 51 6.3 1.11 8.0 1.41

** Installed R-value calculated with a material thickness compressed to a maximum of 25% following recommended duct wrap stretch-outs.

Thermal Conductivity (ASTM C518) k* k Compressed Thickness Labeled ThicknessType Btu•in/(hr•ft2•°F) W/m•°C Btu•in/(hr•ft2•°F) W/m•°C75 0.27 0.039 0.29 0.042100 0.25 0.036 0.27 0.039150 0.24 0.035 0.25 0.036Conductivity at 75°F (24°C) mean temperature. *Tested with material thickness compressed 25%.

AHS-44801/13(New)

a a

aa

HVAC-329 3/14 (Replaces 3/13)

Air Handling Systems

Linacoustic® RCFiber Glass Duct Liner with Reinforced Coating System

DescriptionLinacoustic® RC insulation is a flexible duct liner made from strong glass fibers bonded with a thermosetting resin. The airstream surface is protected with JM’s exclusive Reinforced Coating system, which combines our state-of-the-art Permacote® acrylic coating with a flexible glass mat reinforcement to provide a smooth airstream surface.

Factory-Applied Edge Coating Edge coating is factory applied to the edges of the liner core, ensuring coverage of the leading edges per NAIMA/SMACNA requirements. Shop fabrication cuts may be coated with SuperSeal® edge treatment (refer to publication AHS-202).

UsesLinacoustic RC insulation is specifically designed for lining sheet metal ducts in air conditioning, heating and ventilating systems, providing superior acoustical and thermal performance.

General Properties

Operating temperature (max.) – ASTM C411 250°F (121°C)Air velocity (max.) – ASTM C1071 6,000 fpm (30.5 m/sec)Water repellency – INDA IST 80.6 ≥6Fungi resistance – ASTM C1338 Does not breed or promote Fungi resistance – ASTM G21 No growth Bacteria resistance – ASTM G22 No growth

Standard Thicknesses and PackagingThickness Roll Length Roll Widths for All Thicknesses*

in mm lineal feet lineal meters in mm

½ 13 100, 150, 200 31, 46, 61 34 to 36 864 to 9141 25 50, 100, 150, 200 15, 31, 46, 61 44 to 48 1118 to 12191½ 38 50, 100 15, 31 56 to 60 1422 to 15242 51 50 15 66 to 72 1676 to 1829

*Available in ¼” (6.4 mm) increment.

Contact your Regional Sales Office for stock items and availability of special sizes.

Surface Burning CharacteristicsLinacoustic RC duct liner meets the Surface Burning Characteristics and Limited Combustibility of the following standards:

Standard/Test Method• ASTM E84 • UL 723 • NFPA 255• NFPA 90A and 90B• NFPA 259• CAN/ULC S102-M88UL labels supplied on packages when requested on order.

Specification Compliance• ASTM C1071, Type I• ICC Compliant• California Title 24• MEA #353-93-M• Conforms to ASHRAE 62• SMACNA Application Standards for Duct Liners• NAIMA Fibrous Glass Duct Liner Installation Standard• Canada: CGSB 51-GP-11M and CAN/CGSB 51.11

AdvantagesImproves Indoor Building Environment. Linacoustic RC duct liner improves indoor environmental quality by helping to control both temperature and sound.

Resistant to Dust and Dirt. The tough acrylic polymer Permacote coating helps guard against the incursion of dust or dirt into the substrate, minimizing the potential for biological growth.

Will Not Support Microbial Growth. Permacote coating is formulated with an immobilized EPA-registered protective agent to protect the coating from potential growth of fungi and bacteria.

Linacoustic RC duct liner meets all requirements for fungi and bacterial resistance. Tests were conducted in accordance with ASTM C1338 and ASTM G21 (fungi testing) and ASTM G22 (bacteria resistance testing). Detailed information is available in Johns Manville fact sheet HSE-103FS.

Note: As with any type of surface, microbial growth may occur in accumulated duct system dirt, given certain conditions. This risk is minimized with proper design, filtration, maintenance and operation of the HVAC system.

Cleanability. If HVAC system cleaning is required, the Reinforced Coating airstream surface may be cleaned with industry-recognized dry methods. See the North American Insulation Manufacturers Association (NAIMA) “Cleaning Fibrous Glass Insulated Air Duct Systems.”

Highly Resistant to Water. The reinforced coating surface provides superior resistance to penetration of incidental water into the fiber glass wool core.

Green Building Attributes

GREENGUARD® certification is not intended for residential environments. Instead, the certification is intended only for buildings meeting ASHRAE 62.1-2007 commercial building ventilation rates. This certification is proof that the product meets the GREENGUARD Environmental Institute’s indoor air quality standards and product emission standards for VOCs.

Maximum Flame Spread Index 25Maximum Smoke Developed Index 50

Carrie_G
Typewritten Text
230713 2.2 C Johns Manville Linacoustic RC Sound Liner
myersh
Text Box
Section 230713 2.2.C Ductwork Insulation

a a

aa

717 17th St. Denver, CO 80202 1-800-654-3103 JM.com

© 2014 Johns Manville

The physical and chemical properties of the Linacoustic® RC Fiber Glass Duct Liner with Reinforced Coating System listed herein represent typical, average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. They are supplied as a technical service and are subject to change without notice. Numerical flame spread and smoke developed ratings are not intended to reflect hazards presented by these or any other materials under actual fire conditions. Check with the Regional Sales Office nearest you to ensure current information.All Johns Manville products are sold subject to Johns Manville’s standard Terms and Conditions, including Limited Warranty and Limitation of Remedy. For a copy of the Johns Manville standard Terms and Conditions, Limited Warranty and Limitation of Remedy, and information on other Johns Manville thermal insulation and systems, call (800) 654-3103.

North American Sales Offices, Insulation Systems

Eastern RegionP.O. Box 158 Defiance, OH 43512 (800) 334-2399 Fax: (419) 784-7866

Western Region and CanadaP.O. Box 5108 Denver, CO 80217 (800) 368-4431 Fax: (303) 978-4661

JMCO

M14

0210

HVAC-329 3/14 (Replaces 3/13)

Linacoustic® RCFiber Glass Duct Liner with Reinforced Coating System

Thermal Performance

Thickness R-value Conductancein mm (hr•ft2•°F)/Btu m2•°C/W Btu/(hr•ft2•°F) W/m2•°C½ 13 2.2 0.39 0.46 2.611 25 4.2 0.74 0.24 1.361½ 38 6.3 1.11 0.16 0.912 51 8.0 1.41 0.13 0.74R-value and conductance are calculated from the material thermal conductivity tested in accordance with ASTM C518 at 75°F (24°C) mean temperature.

Sound Absorption Coefficients (Type “A” Mounting)

Sound Absorption Coefficient at FrequencyThickness (Cycles per Second) ofin mm 125 250 500 1000 2000 4000 NRC½ 13 0.07 0.20 0.44 0.66 0.84 0.93 0.551 25 0.08 0.31 0.64 0.84 0.97 1.03 0.701½ 38 0.10 0.47 0.85 1.01 1.02 0.99 0.852 51 0.25 0.66 1.00 1.05 1.02 1.01 0.95Coefficients were tested in accordance with ASTM C423 and ASTM E795.

ISO 9000 CertificationJohns Manville mechanical insulation products are designed, manufactured and tested in our own facilities, which are certified and registered to stringent ISO 9000 (ANSI/ASQC 90) series quality standards. This certification, along with regular, independent third-party auditing for compliance, is your assurance that Johns Manville products deliver consistent high quality.

InstallationLinacoustic RC duct liner installation must be performed in accordance with the requirements of the NAIMA Fibrous Glass Duct Liner Standards or SMACNA HVAC Duct Construction Standard. All transverse edges, or any edges exposed to airflow, must be coated with an approved duct liner coating material, such as Johns Manville SuperSeal products.

Minimizes Pre-installation Damage. Linacoustic RC duct liner’s Reinforced Coating System is highly resistant to damage that can occur during in-shop handling, fabrication, jobsite shipping and installation.

Easy to Fabricate. Linacoustic RC duct liner is lightweight and easy to handle. Clean, even edges can be accurately cut with regular shop tools.

22-15 ECO-HANGER GRIP ADHESIVE Lo VOC

WARRANTY TERMS: The physical and chemical properties of this product are representative of the typical average values derived in accordance with test methods deemed acceptable, and can vary when subjected to normal manufacturing methods. These values are supplied only as a technical service and are subject to change without notice. To be sure information is current call Mon-Eco Industries, Inc. Terms of Warranty: Warrantor, Mon-Eco Industries, Inc. warrants satisfactory results of this product only when recommendations herein established are followed. The recommendations for use are established upon tests and information deemed reliable. We recommend that adequate testing be made by the user to determine if the product is suitable for the intended purpose and use. Warrantor assumes no responsibility beyond replacement or refund of the purchase price of this product, since war- rantor has no control over the methods and application of its product, methods and conditions of transportation, handling and storage of the product. WARRANTOR EXPLICITLY DISCLAIMS ALL LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGE. No agent or representative of Mon-Eco Industries, Inc. has the authority to change or extend these conditions.

MON-ECO INDUSTRIES, INC. 5 JOANNA COURT•EAST BRUNSWICK, NJ 08816 (732) 257-7942) • 800-899-6326 • FAX (732) 257-6525

Email: [email protected] www.mon-ecoindustries.com

COLOR Brown SERVICE TEMPERATURE -20°F TO 225°F (-29°C TO 106°C) COVERAGE Approx. 80 to 100 2”x2” hangers per 1/10th gal tube (.32 Liter Tube), 800-1000 2” x 2 “ hangers per gallon BONDING TIME 0 To 4 Minutes WEIGHT PER GALLON 10.1 lbs./gal. AVERAGE NONVOLATILE 61 % by weight DRYING TIME Up to 24-48 hours, depending on drying conditions. SAFETY Flammable when wet. Flash Point 0°F < (-18°C) Red Label THRESHOLD LIMIT VALUE OF SOLVENT VAPOR (TLV):100 ppm LIMITATIONS Do not apply below 40°F (4°C) Some plastic foams may be attacked by the solvent in this product. Test before using. 22-15 Eco-Hanger Grip Lo VOC should not be used on wood surfaces or on painted or coated surfaces. WARNING CAUTION: FLAMMABLE MIXTURE RED LABEL. Do not use or store near sparks, heat or open flame. Keep container closed when not in use. Use with adequate ventilation. Avoid prolonged or repeated breathing of vapor or contact with skin. Do not take internally. In an emergency, call a physician. Keep out of reach of children.

DESCRIPTION 22-15 Eco-Hanger Grip Adhesive Lo VOC is a construction type paste adhesive specially designed for bonding insulation hangers to metal ducts, and unfinished masonry surfaces. 22-15 Eco-Hanger Grip Adhesive Lo VOC dries to a tough, yet resilient bond that withstands thermal cycling and shock. 22-15 Eco-Hanger Grip Adhesive Lo VOC has been specially formulated to meet reduced VOC requirements. APPLICATION This product is for industrial use only. It should be applied by trained and qualified craftspeople. Be sure surfaces are clean, dry and oil free. Extrude (a bead) approx. 1/16” (1.6MM) thick coat of 22-15 Eco-Hanger Grip Adhesive Lo VOC to the base of the hanger with caulking gun or apply the adhesive with a spatula, putty knife, small trowel or brush . Immediately press the hanger into place with a twisting motion. Make sure good contact is made. Always prepare and bond only one hanger at a time. Allow minimum 24-48 hours drying time before applying insulation. SPECIFICATION COMPLIANCE

CLEANUP –Mineral spirits or toluol. VOC= 1.56 lbs./gal or 187 grams/liter ASBESTOS FREE

03/09

ASTM E84 Standard Test Method For Surface Burning Chara-cteristics of Building Materials (ANSI 2.5, NFPA 255, UBC 8-1, UL 723) Applied to Inorganic Reinforced Cement Board Flame Spread 0 Smoke Developed 0 Adhesive applied in approximate 2 inch x 2 inch squares every 12 inches on center.

Carrie_G
Typewritten Text
230713 2.2 E MEI 22-15 Eco-Hanger Grip Adhesive Lo Voc
myersh
Text Box
Section 230713 2.2.E Ductwork Insulation
Carrie_G
Typewritten Text
230713 2.2 F AGM Perforated Base Insul-hangers
myersh
Text Box
Section 230713 2.2.F Ductwork Insulation

VentureTape® 1525CW COLD WEATHER FSK is a foil/scrim/kraft (FSK) lamination coated with

Venture’s cold weather solvent acrylic pressure sensitive adhesive. This versatile FSK tape applies

easily to both fibrous and sheet metal ducts and easily conforms to irregular surfaces. Venture

Tape 1525CW excels in demanding temperature and humidity applications and provides superior

performance and durability over a wide range of environmental conditions.

Features & Benefits

• UL723 Classified (5/10 Flame/Smoke Rating)

UL file # R10984

• FSK facing meets ASTM C1136, type II and IV

• Tri-directionally reinforced 2 x 3 squares per

inch fiberglass scrim, UL listed FSK lamination

• High performance insulation tape is ideal for

use as a vapor seal for reinforced fiberglass or

mineral wool thermal insulation

• Venture CW® cold weather solvent acrylic

adhesive performs well over a wide

temperature range

FSK INSULATION TAPE

1525CW

Product Configurations

Typical values are not intended to be used for specification development. Technical data is believed to be

true and accurate; Venture Tape recommends that the purchaser test for fitness of use in all applications.

Product Construction

Release liner

Aluminum foil/scrim/kraft (FSK)

Acrylic adhesive

• Standard sizes: 3” x 50Y, 4” x 50Y, 5” x 50Y, 6” x 50Y

• Custom widths and lengths available, contact Venture Tape for specifications and requirements

Contact Venture Tape today for a complete

list of products or a free sample

Toll Free North America 800-343-1076

From United Kingdom 0-800-962-957

From Australia 1-800-122-797

www.venturetape.com

Test Typical Value

Typical Value

(Metric)

Test

Method

Product Thickness Ω 9.5 mils 0.24 mm PSTC-133

Peel Adhesion Δ 45 oz/in 12.5 N/25 mm PSTC-101

Shear Adhesion >24 hrs @ 2.2 psi >24 hrs @ 15.2 kPa PSTC-107

Tensile Strength 40 lb/in 180.8 N/25 mm PSTC-131

Elongation 2 % 2 % PSTC-131

WVTR 0.02 perms ASTM E96

Service Temperature -40 to 150 °F -40 to 66 °C Ω - excluding liner Δ - 20 minute dwell

0213

Carrie_G
Typewritten Text
230713 2.2 G Venture Tape FSK Insulation Tape 1525CW
myersh
Text Box
Section 230713 2.2.G Ductwork Insulation

RPR Insul-Mate® Fastening Devices and Accessories

STRAPPINGRPR strapping is slit in house through a quality control process which

produces a superior product. All strapping is edge conditioned eliminating

sharp edges. Product is available in coil form or convenient pre-fabricated

cut to length straps with attached seals.

Thicknesses: .015 and .020

Widths: 3/8”, 1/2”, 3/4”

Alloys: Aluminum, Stainless Steel (T304, T316) and Galvanized

Packaging: 200’ (.020 only), Ribbon Wound, Oscillated in most

thicknesses, other thicknesses available upon request,

minimums apply. Pre-fabricated straps are produced to

your specifications.

WING SEALSRPR wing seals are precision made in house for exact fit and easy application.

Sizes: 3/8”, 1/2” and 3/4”

Alloys: Aluminum, Stainless Steel (T304, T316) and Galvanized

Packaging: 1000 per box (sold in box quantities only)

SCREWSRPR stocks a variety of screws to fit most applications.

Types: Pan Head, Hex Head – Self Drillers, Self Tappers and

Mult-Tek. Other specialty screws available upon request.

WIREAlloys: T304 Stainless Steel and T316 (.0475 and .0625)

Thicknesses: 18ga (.0475), 16ga (.0625) and 14ga (.080)

Sizes: 5# Coils (.0475 and .062) and 25# Rolls

CLIPSAlloys: T304 and T316 Stainless Steel

Type: S & J Clips

Non-standard fastening devices

are available upon request.

6

t h e h i g h e s t q u a l i t y p r o d u c t s a n d f i r s t c l a s s s e r v i c e

Carrie_G
Typewritten Text
230713 2.2 H RPR 16ga T316 SS Tire Wire
myersh
Text Box
Section 230713 2.2.H Ductwork Insulation