3- electrical maintenance (em)

91
Princess Noura Bint Abdulrahman University اﻟﻤﺤﺪودة اوﺟﻴﻪ ﺳﻌﻮدي ﺷﺮآﺔSAUDI OGER LTD

Upload: jorge-andres

Post on 21-Oct-2015

271 views

Category:

Documents


7 download

DESCRIPTION

electrical

TRANSCRIPT

Page 1: 3- Electrical Maintenance (EM)

Note: save/convert in adobe PDF then print in A3 sizeSet “Page Scaling” to “Fit to Printable Area”

Princess Noura Bint Abdulrahman University

شرآة سعودي اوجيه المحدودة

SAUDI OGER LTD

Page 2: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

1

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Flyleaf Page 1

OPERATING SYSTEMS & EQUIPMENT MAINTENANCE

MANUAL FOR

College of Arts and Sciences (West Building)

BUILDING REF No. 1.2.1

VOLUME No. EM

ELECTRICAL - HIGH CURRENT

BOOK No. 1

PRINCESS NOURA BINT ABDULRAHMAN UNIVERSITY

AIRPORT ROAD

NORTH OF RIYADH KSA

Page 3: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

2

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Flyleaf Page 2

PREAMBLES

LIST OF CONTENTS Title Page List of Contents 2 Contractors, Equipment Supplier and / or Manufactures Details 3 Master Index 4-5 List of Contents 6 Section Index 7 Foreword 8 General Information 9

Building Name 9 Employers Name 9 Engineers Details 9 Main Contractors Details 9 Date of Completion 9 Date of Handover 9 Date of Issue 9

Modification Details 10 Modification to Equipment 11 Modification to Manual 12 Additional Modification Information 13 Issue Register 14 Personnel Training Record 15

Page 4: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

3

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Flyleaf Page 3

CONTRACTORS, SUPPLIERS & MANUFACTURERS DETAILS The details contained within this Volume have been produced by the following Contractors, Equipment Suppliers and / or Manufacturers as detailed below

Product Name of

Provider Address Tel No. E Mail Address

Subcontractor Drake & Skull P.O. BOX 151 059 858 9082 [email protected]

MVSG & EMVSG SCHNEIDER ELECTRIC

P.O. BOX 89249, Riyadh 11682

01 2651515 050 5100216 [email protected]

Transformer SCHNEIDER ELECTRIC

P.O. BOX 89249, Riyadh 11682

01 2651515 050 5100216 [email protected]

Power Factor (QC) & ATS MESCO P.O. BOX 41380,

Riyadh 11521 01 2650101 050 7257497 [email protected]

MDB & EMDB MESCO P.O. BOX 41380, Riyadh 11521

01 2650101 050 7257497 [email protected]

DLP & DP MOTS P.O. BOX 23560, Riyadh 11436

0 12653701 050 2881293 [email protected]

ECB CEAG/ SAUDLIGHTING 01 265 1010 [email protected]

EDP MOTS P.O. BOX 23560, Riyadh 11436

0 12653701 050 2881293 [email protected]

EIB HONEYWELL 050 415 1560 [email protected]

ELP MOTS P.O. BOX 23560, Riyadh 11436

0 12653701 050 2881293 [email protected]

EMCP, MCC & EMCC MOTS P.O. BOX 23560,

Riyadh 11436 0 12653701 050 2881293 [email protected]

EPP MOTS P.O. BOX 23560 0 12653701 050 2881293 [email protected]

ESDP MOTS P.O. BOX 23560 0 12653701 050 2881293 [email protected]

LP MOTS P.O. BOX 23560 0 12653701 050 2881293 [email protected]

PP MOTS P.O. BOX 23560 0 12653701 050 2881293 [email protected]

UDP MOTS P.O. BOX 23560 0 12653701 050 2881293 [email protected]

UPP MOTS P.O. BOX 23560 0 12653701 050 2881293 [email protected]

USDP MOTS P.O. BOX 23560 0 12653701 050 2881293 [email protected]

UPS

Page 5: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

4

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Flyleaf Page 4

MASTER INDEX Building Ref. Title 1.2.1 College of Arts, Humanities and Sciences (West Building) 1.2.2 College of Arts, Humanities and Sciences (East Building) 1.3.0 College of Social Service and Human Welfare 1.4.0 College of family and Consumer Services 1.5.0 College of Arts and Design 1.7.0 College of Computer and Information Sciences 1.9.0 Student Union 1.9.1 Clock Tower 2.1.0 School of Medicine 2.2.0 School of Basic Sciences 2.3.0 School of Clinical Skills Development Center 2.4.0 School of Nursing and Physiotherapy 2.5.0 School of Pharmacy and Dentistry 2.6.0 School of Applied Medical Sciences 2.7.0 Student Amenities 2.8.0 Hospital Bridge 3.1.0 Female Main Administration Building 3.2.0 Administration Building for Men 3.4.0 Conference and Convention Center 3.5.0 Central Library/ Worship Area 3.6.0 Main Mosque (Type A) 3.7.1 Main Student Gate (Type B) 3.7.2 Main Ceremonial Gate (Type A) 3.7.3.1 Emergency and Mosque Gate (Type C) 3.7.5.1 Medical Entrance Gate (Type C2) 3.7.5.2 Medical Entrance Gate (Type C2) 4.1.0 Research Center 4.2.0 Medical Center 5.3.1/5.3.1.1 Married Senior Staff Villas (Type A) 5.3.2/5.3.2.1 Married Senior Staff Villas (Type B) 5.3.3/5.3.3.1 Married Senior Staff Villas (Type C)

Page 6: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

5

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Flyleaf Page 5

MASTER INDEX

Building Ref. Title 5.5.1.1 Mosque 1 (Type B) 5.5.2.1 Mosque 2 (Type C) 5.5.2.2 Mosque 2 (Type C) 5.6.1.1 Students Security Building 5.6.1.2 Students Security Building 5.6.3.1 Married Senior Staff Utility Building 5.6.3.2 Married Senior Staff Utility Building 5.6.4.1 MSH Security Building 5.6.4.2 MSH Security Building 5.6.5.1 MSH Guard House 5.6.5.2 MSH Guard House 5.6.5.3 MSH Guard House 5.8.1.1 Pedestrian Bridge 5.8.1.2 Pedestrian Bridge 5.8.2.1 Pedestrian Bridge 5.8.2.2 Pedestrian Bridge 7.3.1 Security Building

Page 7: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

6

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Flyleaf Page 6

VOLUME INDEX

Volume Title

Page 8: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

7

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Flyleaf Page 7

SECTION INDEX Each of the above Volumes consists of the Sections listed below. The main Section Titles for each Volume is as listed below.

Section Title Content 1 Introduction Manual Index and general useful information 2 Maintenance

Procedures Maintenance Procedures: Include the following information and items that detail essential maintenance procedures: Test and inspection instructions, Aligning, adjusting, & checking instructions, Fault finding guide, Lubrication requirements, list of required lubricants for equipment, Schedules for preventive & routine maintenance and service. Scheduled Maintenance & Service: Tabulate actions for daily, weekly, monthly, quarterly, semi-annual, and annual frequencies. Maintenance & Service Record: Include manufacturers' forms for recording maintenance.

3 Spare Parts List & Source Information

Spare Parts List and Source Information: Including lists of replacement & repair parts, with parts identified & cross referenced to manufacturers' maintenance documentation & local sources of maintenance materials & related services.

4 Maintenance Information

Maintenance Service Contracts: Including copies of maintenance agreements with name and telephone number & contact details of service agent. Warranties and Bonds: Including copies of warranties & bonds & lists of circumstances & conditions that would affect validity of warranties or bonds along with notification procedures.

5 Test & Commissioning Records

Factory and site test reports. Commissioning records and reports.

6 Manufacturers’ Literature

Manufacturers' Maintenance literature Standard printed maintenance instructions & bulletins, Drawings, diagrams, & instructions required for maintenance,

Page 9: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

8

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Flyleaf Page 8

FOREWORD Each of the Volumes has been prepared in a format to give easy reference to all plant and equipment. Every effort has been made to deal with each system in a concise manner. However, to obtain a full and detailed picture of any particular system or plant item, this manual must be read in conjunction with the record drawings and relevant manufacturer's literature.

To assist in the day to day running of the various plant a description of each is given, together with routine attention necessary to the main components.

Regular inspection, monitoring and checking are necessary if the efficiency and control of plant is to be maintained at the level required.

Regular maintenance and inspections are essential, if inconvenient and costly breakdowns are to be avoided. Although there is no way of guaranteeing against the possibility of breakdown, with regular and detailed inspections together with a preventive maintenance programme, the likelihood of such an occurrence can be greatly reduced.

A correct maintenance programme will also ensure that the individual plant is running at maximum efficiency at all times. This will also extend plant life due to the continual monitoring of wear and changes that the systems undergo during their operating period and life. The maintenance programme will provide anticipated and continuous corrective action to avert and minimise deterioration.

THE MANUAL DOES NOT REPLACE THE NEED FOR FULLY QUALIFIED OPERATORS.

It is important that the modification records in this section are referenced every time that the manual is used in order to ensure that information obtained from other sections is still valid.

All operators must be made fully cognizant with the contents of this manual before operating the system.

Page 10: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

9

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Flyleaf Page 9

GENERAL INFORMATION Building Name : College of Arts and Sciences (West Building)

Information within this manual

: Operating Systems & Equipment Maintenance Manual

Name of employer : Ministry of Finance – Riyadh, KSA Address : Airport Road

Riyadh 11177

Name of Engineer : Dar Al-Handasah (Shair & Partners) Address : 15 Amr Street

Mohanddessin Giza 12411

Name of Main Contractor : Saudi Oger LTD Address :

Date of Completion :

Date of Handover :

Date of Issue :

Page 11: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

10

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Flyleaf Page 10

MODIFICATION DETAILS Modifications and authorised changes, which may affect the safety, reliability or maintenance of the health and safety files, are to be recorded and registered. Information on permitted modifications allowed for by manufacturers or designers should be included.

All modification and changes must be recorded as they occur on the following record sheets:

Modifications to Buildings

Modifications to the Manual

Page 12: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

11

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Flyleaf Page 11

MODIFICATIONS TO THE EQUIPMENT To be completed in the event of any technical or engineering modifications.

Ref. Equipment Date Modification By:

Page 13: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

12

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Flyleaf Page 12

MODIFICATIONS TO THE MANUAL To be completed in the event of any modification applicable to the content of this manual.

Ref. Page/Section Date Modification By:

Page 14: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

13

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Flyleaf Page 13

ADDITIONAL MODIFICATION INFORMATION (Additional modification information can be added to this sheet. Sign and date information added)

Page 15: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

14

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Flyleaf Page 14

ISSUE REGISTER Schedule of persons to whom each revision of this Manual should be issued

Controlled Copy No.

Name Company

Page 16: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

15

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Flyleaf Page 15

PERSONNEL TRAINING RECORDS Details of personnel training records applicable to the systems covered by this manual should be recorded within the table below:

Name Course Training

Module Certificate No. Date Completed

Page 17: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

1

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences (West Building)

Introduction Page 1

SECTION 1

PRELIMINARIES

LIST OF CONTENTS Section Title Page

1.1 Manual Index 2

1.2 Services Identification 3 1.2.1 Identification of Conductors 3 1.2.2 Fire Extinguisher Color Code 4

Page 18: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

2

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences (West Building)

Introduction Page 2

1.2 MANUAL INDEX

The maintenance manual consists of the sections listed below.

Section Title Content 1 Introduction Manual Index and general useful information 2 Maintenance

Procedures Maintenance Procedures: Include the following information and items that detail essential maintenance procedures: Test and inspection instructions, Aligning, adjusting, & checking instructions, Fault finding guide, Lubrication requirements, list of required lubricants for equipment, Schedules for preventive & routine maintenance and service. Scheduled Maintenance & Service: Tabulate actions for daily, weekly, monthly, quarterly, semi-annual, and annual frequencies. Maintenance & Service Record: Include manufacturers' forms for recording maintenance.

3 Spare Parts List & Source Information

Spare Parts List and Source Information: Including lists of replacement & repair parts, with parts identified & cross referenced to manufacturers' maintenance documentation & local sources of maintenance materials & related services.

4 Maintenance Information

Maintenance Service Contracts: Including copies of maintenance agreements with name and telephone number & contact details of service agent. Warranties and Bonds: Including copies of warranties & bonds & lists of circumstances & conditions that would affect validity of warranties or bonds along with notification procedures.

5 Test & Commissioning Records

Factory and site test reports. Commissioning records and reports.

6 Manufacturers’ Literature

Manufacturers' Maintenance literature Standard printed maintenance instructions & bulletins, Drawings, diagrams, & instructions required for maintenance,

Page 19: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

3

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences (West Building)

Introduction Page 3

1.2 SERVICES IDENTIFICATION

1.2.1 Identification of Conductors

Function Alpha Numeric Color Green & Yellow

Protective Conductors

`

A.C. Power Circuit

Red

Phase of Single Phase Circuit L

Black

Neutral of Single or Three Phase Circuit N

Red

Phase 1 of Three Phase Circuit L1

Yellow

Phase 2 of Three Phase Circuit L2

Blue

Phase 3 of Three Phase Circuit L3

Page 20: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

1

Page

4

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences (West Building)

Introduction Page 4

1.2.2 Fire Extinguisher Color Code

Page 21: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

1

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 1

SECTION 2

MAINTENANCE PROCEDURES

LIST OF CONTENTS

Section Content Page

2.1 General Inspection & Maintenance Notes 3 2.1.1 Foreword 3 2.1.2 Electrics ~ General Note 3 2.1.3 Emergency Maintenance 4

2.2 Medium Voltage Switch Gears & Power Transformers 13.8KV 5 2.2.1 Maintenance Procedures (Planned) 5 2.2.2 Maintenance Procedures (Corrective) 6 2.2.3 Maintenance Hazards 7 2.2.4 Disposal Instructions 7

2.3 Low Voltage Main Distribution Boards & Distribution Panel Boards 380/230V 8 2.3.1 Maintenance Procedures (Planned) 8 2.3.2 Maintenance Procedures (Corrective) 11 2.3.3 Maintenance Hazards 11 2.3.4 Disposal Instructions 11

2.4 Other Electrical Low Voltage Equipments, UPS, ATS, MCC, ECB, Capacitor Banks, Dimming System 12

2.4.1 Maintenance Procedures (Planned) 12 2.4.2 Maintenance Procedures (Corrective) 14 2.4.3 Maintenance Hazards 15 2.4.4 Disposal Instructions 16

2.5 Lighting & SMALL Power System 17 2.5.1 Maintenance Procedures (Planned) 17 2.5.2 Maintenance Procedures (Corrective) 18 2.5.3 Maintenance Hazards 19 2.5.4 Disposal Instructions 19 2.5.5 Cleaning of Luminaires 19

2.6 Earthing & Lightning Protection 20 2.6.1 Maintenance Procedures (Planned) 20 2.6.2 Maintenance Procedures (Corrective) 21

2.6.3 Maintenance Hazards 21 2.6.4 Disposal Instructions 21 2.7 Elevator System 21 2.7.1 Maintenance Procedures (Planned) 21 2.7.2 Maintenance Procedures (Corrective) 21

2.7.3 Maintenance Hazards 21 2.7.4 Disposal Instructions 21 2.8 Maintenance Schedule 22 2.8.1 Introduction 22

Page 22: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

2

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 2

2.8.2 Schedule 23 2.9 Fault Finding 24 2.9.1 Sub-Main Distribution System 24 2.9.2 Un-switch Switchgear 25 2.9.3 General Lighting 26

Page 23: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

3

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 3

SECTION 2

MAINTENANCE & TROUBLESHOOTING 2.1 GENERAL INSPECTION AND MAINTENANCE NOTES

2.1.1 Foreword

Any plant area is potentially dangerous.

(1) Never attempt to stop motive plant that is in the process of slowing down by holding belts or shafts.

The following points should be remembered for day-to-day work.

(2) Ensure that electrical equipment is securely isolated, preferably by the removal of fuses before commencing work.

(3) Always wear protective clothing, overalls, hard-hat, safety shoes, goggles, ear protection etc., relevant to the type of work being carried out.

(4) When working in remote areas, always inform a responsible person of your location and when you expect to return. Always remember to inform that person when you have safely returned, to avoid false alarms.

(5) If possible, remove hand wheels from valves on a system or plant item that has been isolated. This will prevent inadvertent reopening of the valve. This is particularly important when the isolation valves are remote from the place of work. If it is not possible to remove the hand wheel, place a notice on the valve indicating that it is closed for a reason.

(6) Always remember to replace guards and access panels when work is complete.

2.1.2 Electrics ~ General Note

It should be established that the means of protection against direct contact with live conductors is provided by one or more of the following methods:

• Insulation of live parts • Installation of barriers or enclosures • Obstacles

It should be established that the means of protection against direct contact with any live conductors meets the requirements for the safety of any person and property from the effects of electric shock, fire and burns.

For each method of protection against direct contact it should be established that there has been no deterioration of insulation; no removal of barriers or obstacles; no alterations to enclosures or access to live conductors which would reduce its effectiveness.

Precautions should be taken, where necessary, to disconnect electronic and other equipment which may be damaged by subsequent testing. Special care must be taken where electronic components are fitted to protective and control devices, and installed in HF luminaires. If inspection and testing cannot be carried out in any part of the system, or is limited in any way, this should be recorded in the Periodic Inspection Report.

Page 24: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

4

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 4

2.1.3 Emergency Maintenance

Depending on the type of breakdown, a decision must be taken on whether the matter is urgent or not, e.g. lamp failure, individual circuit fault or non-essential plant failure. In each of the above cases, the fault needs attention but is not generally considered urgent.

When a breakdown occurs, action is to be taken immediately to render the system safe. In such cases the procedure is outlined in the operation manual for shutting down the system and switching off plant, etc. This must be carried out before any other action necessitated by the breakdown is initiated. This would include work on boilers or pumps, isolation of plant and electrical circuits because of leaks, etc.

Always try to establish the cause of a breakdown rather than merely rectifying the effect. Although the immediate need may be to restore the system to working order without delay, by whatever means possible, never be satisfied with any action which only repairs the defect or replaces the part. Investigation in depth may be required to reveal some underlying fault which, if not corrected, may result in a recurrence of the trouble, or even perhaps later development of other more serious faults which are not yet apparent.

Careful and complete details should be recorded of all breakdowns in a Maintenance Logbook. Date of occurrence and relevant equipment, details of breakdown, any previous maintenance work carried out, previous warnings or evidence of trouble which may (or may not) have been attended to, how the system was operating, any special circumstances, or similar information should be accurately and fully recorded, together with details of action taken, including temporary and/or permanent repairs or replacements. These records are not only useful to the operating staff, but often provide invaluable clues to outside specialists and service engineers.

Page 25: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

5

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 5

2.2 Medium Voltage Switch Gears and Power Trans formers 13.8KV

2.2.1 Maintenance Procedures (Planned)

Daily

1. Check that all meters and indicators are functioning correctly. Note readings and compare with those taken previously.

2. Check alarm indicators on the front compartment of the switchgear and transformer cabinet, carry out any corrective action as necessary.

3. Check for overheating, vibration and undue noise etc., and report to the Management for correction or repair immediately. Carry out repair as necessary.

4. Visually inspect indicator lamps and display units, replace any faulty ones as necessary, or check any wire disconnection.

5. Check warning and indication labels are securely in position.

Bi-Annually

1. Clean and free from dust inside and outside the switchgear or transformer cabinet, one at a time; using compressed air and a suitable plastic nozzle.

2. Check the battery and charger (following the charger instruction). 3. Check the electrical and mechanical operation of the MV switchgear and

transformer with OFF or ON load, following the manual instructions.

Note:

Yearly

It is important to choose public holiday to do these checking and inspections.

1. Carry out tasks as described Bi-Annually. 2. The switchgear and transformer rooms shall be kept as clean and free from dust as

possible. All accumulations of dust inside the switchgear and the transformer cabinet should be removed by blowing with compressed air or vacuum cleaner, using plastic nozzles. Finish by wiping with cloth moistened in alcohol.

3. Check all control and power cables and busbar joints. 4. Check all bolts are well tightened with a torque wrench. 5. Check the damping of cable bundles and that no cable is passing in sharp edges or

corners. 6. Check all fixing components especially: the cover of busbar compartment, door

access, tumbler, motor drive, transformer cabinet, protection relay, auxiliary relay, indicators, push buttons and selector switches.

7. All metering and protection units should be checked.

Page 26: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

6

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 6

2.2.2 Maintenance Procedures (Corrective)

Corrective maintenance operations allow for defective subassemblies to be replaced. The operations mentioned in the summary table here after can be carried out by the customer or by The Manufacturer’s After Sales agents. After each operation, carry out electric tests in compliance with the standards in force.

Description Execution Comments Replacement on MV cubicles Busbar rating

For any intervention, call the nearest Manufacturer

agents.

Earthing switch clamps and capacitive isolators

Plug-in pins Upper and lower bushing Increase in the number of cables Flaps and flap operating mechanisms Extraction of a cubicle VT fuse Customer/ See Manufacturer Manual VPIS voltage indicator box Customer/ See Manufacturer Manual CT Customer/ See Manufacturer Manual Anti-condensation resistor Customer/ Consult Agent Earthing switch position auxiliary contact block

Customer/ See Manufacturer Manual

Surge arrester Customer/ Consult Agent Locking using plug-in padlocking lock(s) Customer/ See Manufacturer Manual Plug-in padlocking electromagnetic locking Customer/ See Manufacturer Manual Locking using earthing switch lock(1) Customer/ See Manufacturer Manual Locking using earthing switch locks(2) Customer/ See Manufacturer Manual Earthing switch electromagnetic lockin Customer/ See Manufacturer Manual Locking using lock(s) for prevention of withdrawal

Customer/ Consult Agent

Zero frequence toroid Customer/ See Manufacturer Manual VT and VT compartment Customer/ See Manufacturer Manual High voltage contacts on VT fuses Customer/ See Manufacturer Manual Cable connection bar support isolators Customer/ Consult Agent MV handles Customer/ See Manufacturer Manual Circuit-breaker carriage position auxiliary contacts

Customer/ See Manufacturer Manual

Withdrawable VT auxiliary contacts Customer/ Consult Agent Withdrawable VT fuse blowing auxiliary contacts

Customer/ See Manufacturer Manual

Printed circuit and relay support (STPI) Customer/ Consult Agent Replacing the fans on cubicles Customer/ See Manufacturer Manual Cleaning ventilation grids on cubicles Customer/ See Manufacturer Manual

Page 27: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

7

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 7

2.2.3 Maintenance Hazards

• Care should be taken when removing SF6 which may contain decomposition products. It should not be released in an indoor environment and should be collected in a storage vessel. Care should be taken not to breathe SF6 removed from an item of equipment. If this possibility cannot be avoided, a respirator should be worn. This should be fitted with a filter capable of removing the gases described in “arc decomposition products”.

• Enclosures should be evacuated such as to remove as much as possible of the residual SF6.

In some cases, flushing enclosures with dry air

2.2.4 Disposal Instructions

• When the installation has reached the end of its useful life, the equipment should be carefully stripped out and removed from the premises and disposed of in a careful and controlled manner.

• End of life of SF6 - filled equipment SF6 - filled equipment which has been removed from service may require treatment to neutralize any decomposition products remaining after the SF6 has been removed. For environmental reasons. SF6 has to be removed and not released to the atmosphere, (see § SF6 and the global environment). The need for neutralization is dependent on the level of decomposition. Prior to treatment, the SF6 should be removed and stored for recycling. The equipment should then be treated according to the expected decomposition level. After treatment, the equipment can be disposed of as normal waste (respecting local regulations), for example in a landfill site, or subjected to reclamation processes to recover the metals. Solutions used in the neutralization process can be disposed of as normal waste.

Low decomposition:

• No special action is required.

Medium and high decomposition:

• The internal surfaces of gas enclosures should be neutralized using a solution of lime (calcium hydroxide) prepared by diluting 1 kg of lime in 100 liters of water. The enclosure to be treated should, if possible, be filled with the lime solution for a period of 8 hours before emptying. If it is subsequently necessary to work on the enclosure, it should first be rinsed with clean water. For larger enclosures where filling is impractical, powders should be removed, using a vacuum cleaner equipped with a suitable filter, for neutralization separately. The internal surfaces should then be washed with the lime solution which should be left in place for at least one hour followed by rinsing with clean water.

Page 28: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

8

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 8

2.3 Low Voltage Main Dis tribution Boards and Dis tribution Panel Boards 380/230V

2.3.1 Maintenance Procedures (Planned)

Main Distribution Boards

Weekly

1. Check that all metering instruments are functioning. Note readings and compare with those taken previously.

2. Check that operating tools, handles, keys, etc. are readily available in switchboard. 3. Inspect switchboard or circuit breakers enclosure for undue heating.

Monthly

1. Carry out tasks as detailed for Weekly. 2. Check for undue noise, overheating or vibration, loose parts, tightness of

screw/bolts and warping, and report to the management for correction or repair. 3. Visually check PACB’s, MCCB’s, fuse switches or isolators, for signs of arcing or

burning. (Checking of the PACB may only be done if the circuit breaker is permitted to be opened for servicing and only under the instruction of the engineer in charge).

4. Examine resistors and devices object to overheating, where and when possible, without shutting down the essential loads. (Check with the supervising engineer).

5. Inspect earthing connections, power terminations and control circuits without shutting down the MDB as per Engineer’s instruction.

6. Remove all dust and debris inside cubicles or enclosures with the aid of a vacuum cleaner.

7. Check that PACB’s stored energy mechanisms are charged. Correct any defects.

Bi-annually

1. Carry out tasks as detailed for Monthly. 2. Check operation of MCCB’s, PACB’s and isolators using their integral switching

arrangements to ensure that mechanisms are in good order. 3. Check for links, bridges for sign arcing. Ensure correct grade of fuse is fitted.

Correct any defects. 4. Check electrical and/or mechanical operation of withdrawable main PACB at a time,

in the test position and in the connected position, strictly in accordance with Engineer’s instructions, when MDB is not in use.

Annually

1. Carry out tasks as detailed for Bi-annually.

Note:

2. Inspect electrical primary and secondary connections, cables and supports, insulation for discoloration, excessive corrosion, secure connections, clean contacts, insulation chaffing and embroiled or discoloured cable or insulator. Correct any defects.

Substation must be shut down and dead before further tasks are carried out.

3. Clean the stationary part of the switchgear with a clean cloth, use compressed dry air for inaccessible areas.

4. Examine all air filters for dust content, flush with water and re-coat with supercoat adhesive as recommended per manufacture.

Page 29: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

9

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 9

5. Check that all conduits and cable gland terminations associated with the switchboard are secure.

Withdrawable LV Switchgear

6. Manually discharge (for safety) and draw out the circuit breakers, check, clean and lubricate the carriages.

7. Check all stationary primary disconnects for evidence of overheating and corrosion. 8. Inspect all circuit breakers draw-out captive positions, interlocks and shutter

mechanism operation.

All Circuit Breakers

9. Check anti-pump relay operation. 10. Check and clean insulated parts using a mild detergent, a lint free cloth, rinsing with

clear water and dry. 11. Inspect arc chutes and contacts of circuit breakers, fuse-switches, isolators and

repair or replace as per manufacturer’s procedures. 12. Check security of all electrical terminations and connections and tighten as

necessary. 13. Check that all barriers and guards are in place and secure. 14. Check that phase labels giving circuit references are securely fixed. Replace any

missing items and update information as necessary. 15. Ensure that 380 Volts and any other warning labels are in position where applicable. 16. Check door interlocks and that doors can be securely closed. If lock is provided,

check that it functions correctly. 17. Check enclosure for paintwork condition and signs of corrosion. (Correct any

defects.). 18. Visually inspect any under-voltage relays, clean and carry out a simulation test. 19. Check that the rating of the circuit breakers and setting of microprocessors (MPS),

over-current and ground fault relay are correct with respect to the loading, type of load, cabling, etc., in the design data. Report any overloading and/or loads that are up to the set rating of the breaker. Make any possible adjustments. Report need for replacements and adjustments to the management.

Two-yearly

1. Carry out tasks as detailed for Annually. 2. Measure insulation resistance for busducts, busbars and circuit breakers with

1000V megger, and compare with previous record. Repair as necessary. 3. Measure the insulation resistance of the secondary wiring selected on random basis

with a 500V megger and record results. (It must not be less than 0.5 megohm). 4. Check continuity of all control circuits. 5. Measure circuit breaker contact resistance. 6. Carry out injection testing of all relays. 7. Carry out insulation resistance measurement of instrument transformers

Withdrawable P.A.C.B’s

1. Clean and lubricate the circuit breaker housing safety shutter mechanisms. 2. Manually check the operation of the safety shutter mechanisms in accordance with

manufacturer’s instruction procedures. 3. Inspect and clean the main isolating contact orifice bushings, using a clean, dry and

non-fluff cloth.

Page 30: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

10

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 10

4. Clean the isolating contact plugs, using a carbon tetrachloride or silver polish, and under no circumstances abrasive material. Apply a thin film of silicon grease or petroleum jelly.

5. Clean and lubricate all moving surfaces of the position selector mechanism, including wheels, track and operating handle mechanism.

Distribution and Branch Circuit Panelboards

Quarterly

Note:

1. Visually check all MCCB’s and/or isolators for any signs of arcing, burning or overheating. Carry out repairs as necessary.

Advice and program with management, before carrying out tests, operation or repairs on any panel-board.

2. Test any residual current devices (RCD’s) where available by using their integral test mechanism.

3. Check contactors for undue noise or overheating. Check indicator lights and push buttons.

4. Clean out dust and debris from the individual items of equipments with the aid of a vacuum cleaner.

5. Check the loading of all outgoing circuits and record readings.

Bi-annually

1. Carry out tasks as detailed Quarterly. 2. Check the operation of all breakers, isolators, RCD’s etc. and ensure mechanisms

are working in order. Correct any defaults. 3. Check that the rating of the MCCB is correct with regard to loading cabling, type of

load etc. with particular reference to design data. Report any overloading and/or loads that are up to the set rating of the breaker. Report need for adjustment.

4. Check for proper fixation of all circuit breakers, security of all electrical termination and connections, and tighten as necessary.

5. Check that all barriers and guards are in place and secure. Adjust as necessary. 6. Check that all trunking, conduit or cable gland terminations associated with the

panel are secure. Adjust as necessary. 7. Check that doors can be securely closed. If a lock is provided, check that it

functions correctly. 8. Ensure that 380Volt and other warning labels are in position where applicable. 9. Check that phase discs and labels giving the panel and circuit references are

securely fixed to the enclosure door. Replace or provide any missing items and update information as necessary.

Annually

1. Carry out tasks as detailed Bi-Annually. 2. Test earth continuity of incoming supply circuit and measure loop resistance of each

panelboard. 3. Check all exposed cable insulation for signs of damage inside each panelboard.

Correct any defects. 4. Check enclosures for paint work condition and signs of corrosion. Correct any

defects. 5. With a 500V Megger, test insulation resistance between busbars, and between

busbars and earth. (N.B. All circuit breakers must be in “Open” position),

Page 31: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

11

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 11

6. Select at random two circuit breakers out of each panelboard and test its time-current curve using appropriate current injection test instrument. Report any discrepancies. (Tests are to be carried out in accordance to NFPA 70B, section 18-10, 2.4).

2.3.2 Maintenance Procedures (Corrective)

Circuit Breakers

General

• Circuit breakers interrupt electrical current to stop power flow both for switching operations and during fault conditions. Molded case circuit breakers are usually located in low voltage distribution panels and in control boards. These are typically 120-volts alternating current (Vac), 125-volts direct current (Vdc), 240-Vac, and 480-Vac breakers for control, protection, and auxiliary power. Molded case breakers in panel boards should not be loaded more than 80% of rating per NFPA 70B, 11-2.

• Low voltage air breakers are usually located in motor starter cabinets, motor control

centers, station service switchgear, or similar enclosures. These are typically 480 Vac for auxiliary power.

Most breaker maintenance (except infrared scanning) must be performed with equipment de-energized.

2.3.3 Maintenance Hazards

2.3.4 Disposal Instructions

Page 32: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

12

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 12

2.4 Other Electrica l Low Voltage Equipments , UPS, ATS, MCC, ECB, Capac itor Banks , Dimming Sys tem)

2.4.1 Maintenance Procedures (Planned)

Static Uninterruptable Power Supply UPS

Daily

1. Check the installation and operating conditions: distance from wall, ventilation inlet and outlet, vents free, operating temperature, especially for the batteries.

2. Check that no faults are signalled by the lights. 3. The battery is automatically checked by the equipment and it indicates if the

batteries should be checked or a battery fault is present. 4. Check that all fans are working properly. 5. Check all the fuses, replace if necessary. 6. Check the thrusters of the charger.

Annually

1. A complete check-up can be done only by qualified personnel certified by UPS Supplier.

2. Check the status of the batteries through regular test (no supply and temporarily load)

3. Check the maintenance by-pass switch 4. Check the operation of the UPS in both cases, once the electricity is ON and the

other when electricity is OFF 5. Check Fans and Ventilation of the UPS 6. Check if no permanent fault appears at its control panel.

Dimming Control Panel

Annually:

1. Check dimming and switches modules within the dimming panel. 2. Check the setting of all presets switches regarding the scenes and channels. 3. Check the interfaces with other systems such as fire alarm. 4. Check overheating and the ventilation of the room housing the dimming panel. 5. Clean using appropriate means the accumulated dust in the panels. 6. Check all electrical connection

Power factor corrector (CAPACITOR)

Monthly

1. Check the connection of capacitor bank to switchboards. 2. Check the good functioning of the switching of capacitor banks based on the

variation of the loads. 3. Check the good operation of its control panel. 4. Test and inspect the improvement of power factor. 5. Clean the accumulated dust using appropriate cleaning means.

Page 33: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

13

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 13

Annually

1. Check all reactors 2. Check all contactors 3. Check all cables and connections 4. Check manufacturer and installation settings 5. Check alarm history 6. Check out the right settings of the circuit breakers and fuses ratings according to

the capacitor range

Motor Control Centre (MCC)

Annually:

1. Bolted connections should be tight. Discoloration, excessive corrosion, embrittled or discolored insulation may indicate an overheated connection.

2. Inspect all cables for tight connections and ample support. 3. Inspect control wiring for signs of wear and damage. Replace wire wherever

doubtful. 4. Examine resistors and other devices prone to over-heating. 5. Open all hinged doors and remove bolted panels. 6. Clean insulation thoroughly. 7. Withdraw and clean all draw-out components. 8. Clean the stationary portion of the switchgear by wiping with a clean cloth. Use dry,

compressed air in inaccessible areas. 9. Remove the covers of all panel devices where possible. Check wiring for secure

connections. Clean contacts on relays and switches wherever necessary. Replace covers.

10. Remove air filters when used. Flush with clean water if necessary Coat filters with Randolf Products’, Super Coat Adhesive or equivalent.

Emergency Central Battery (ECB)

Annually

1. Carry out tasks as Annually 2. Inspect all battery connections (battery to battery, and battery to terminal block) for

the presence of corrosion. Clean and retighten all connections to factory specifications. Spot checks for connection torques

3. Visual inspection for leaks or bad cells 4. Check and recalibrate the charger output voltage and current settings and Total

battery terminal voltages 5. Check the input and output parameters. Measure of cell voltage levels. 6. Testing of cell/unit internal ohmic values. 7. Check the cooling fans. 8. Exercise all circuit breakers 9. Inspect the battery environment. 10. Clean the inside and outside of all system cabinets 11. Run a system performance check by simulating an input power outage and

discharging the batteries to 87.5% of nominal voltage 12. During the system performance check, take periodic battery readings to determine

battery array capability for stated system run time 13. Verify the operation of all installed options and remote panels 14. Detailed written inspection report of battery test and inspection results and

recommendations for corrective actions

Page 34: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

14

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 14

Automatic Transfer Switch (ATS)

Monthly

1. Test the transfer switch’s automatic control system 2. Check the operation of manual by pass. 3. Inspect the cleanness of the switch.

2.4.2 Maintenance Procedures (Corrective)

UPS (Uninterruptable Power Supply)

General

This section is provided for maintenance technicians. It is assumed that all are familiar with:

• The laws of electricity

• The hazards of working with electricity.

• The basic principles of hybrid diaode-thyristor rectifier bridge technology for battery application.

Equipment

All diagnostic verification can be performed with a multi-meter. The multi-meter must have AC/DC, capability, good accuracy and in some cases, a test clamp attachment.

Preliminary Checks

Always perform a few preliminary checks before starting maintenance:

• General visual inspection of equipment (for signs of overheating or electric discharge).

• Make sure that power is available.

• Attempt to clear the fault by pressing the button “RESET”.

Corrective Action

The charger systems are composed of easy to locate functional modules (power pack, display unit, etc.). Corrective maintenance will usually entail no than changing a module if it is diagnosed as malfunctioning. A minimum recommended set spares should be kept on hand.

Typically, evaluation of the battery voltage/charger output relationship for the giver settings and charge curve will be sufficient to determine whether there is a malfunction.

Keep the following in mind to make a rapid, reliable diagnosis:

• If the equipment is inoperable (for instance if it is not powered), the charge should still operate with its basic functions.

Page 35: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

15

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 15

1. Voltage regulation (floating)

2. Limitation of total current.

3. Limitation of battery current

• The equipment controller determines:

1. Measurement

2. Protection thresholds

3. Secondary charge curve function (equalization, etc.)

Overcharging is usually the result of a control unit malfunction. Undercharging or no charging usually results from a power pack failure (mains fuse, circuit breaker, etc.) or, much rarely, from a control unit failure.

2.4.3 Maintenance Hazards

Batteries have to be carefully maintained, frequent visual inspection for spill and bloating of batteries shall be carried out regularly. Cleaning of Corrosion on the enclosure has to be carried out to avoid accumulation.

Electrical Hazards

Battery systems present a risk of electrical shock and high short circuit currents. The following precautions should be observed when installing and maintaining batteries:

1. Remove all personal metal objects (watches and rings).

2. Use insulated tools, Wear full eye protection and rubber gloves.

3. Observe circuit polarities.(do not make or break live circuits)

4. Prior to handing batteries on a metal rack, assure the battery is not inadvertently grounded by measuring the voltage between the battery and the rack. It should be zero. If not, determine the cause and correct prior to proceeding.

Fire, Explosion and Heat Hazards

Lead acid batteries can contain an explosive mixture of hydrogen gas which can vent under overcharging conditions.

Do not smoke of induce sparks in the vicinity of the battery.

Do not install and charge batteries in a seals container.

Mount the individual batteries with 0.5 inches of space between the batteries to allow for convection cooling. If contained, assure the container or cabinet and room have adequate ventilation to prevent an accumulation of potentially vented gas.

Page 36: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

16

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 16

Chemical Hazards

Any Gelled or liquid emissions from Battery is electrolyte which contains dilute sulphuric acid which is harmful to the skin and eyes; is electrically conductive; and is corrosive.

If electrolyte contacts the skin, wash immediately and thoroughly. If electrolyte enters the eyes, wash thoroughly for 10 minutes with clean water or a special neutralizing eye wash solution and seek immediately medical attention.

Neutralized any spilled electrolyte with the special solutions contained in a “spill kit” or with a solution of 1lb. Bicarbonate of soda to 1 gallon of water.

Refer to the current issue of the national Electrical Code.

2.4.4 Disposal Instructions

ENVIRONMENTAL COMPATIBILITY, DISPOSAL

• Environmental concerns during development

In contrast to earlier UPS devices, the number of components has been greatly reduced through the use of highly integrated components and modular construction. As a result, energy consumption during production is reduced. Particular attention was paid to reducing the volume, mass and variety of metals and plastics used. Environmental compatibility was an important criterion in the selection of parts obtained from vendors.

• Environmental concerns during production Components obtained from vendors are delivered primarily in reusable packaging. ASIC components and SMD elements are used on the flat component groups. Production is emission free.

• Environmental concerns for disposal The device can be stripped down into recyclable mechanical components with screw and snap connections. Within the area of the EU, disposal should be carried out by a certified disposal company. In other countries local regulations must be observed.

Page 37: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

17

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 17

2.5 Lighting and small power system

2.5.1 Maintenance Procedures (Planned)

General Instructions

Note: Obtain a permit before proceeding with the work in each of the respective areas involved.

• Prepare a “Log Book”, complete with all necessary forms to record the work carried out and any special notes.

• Ensure that details of lighting installations, luminaires (make, type, date of installation, size and type of lamps) and any other relevant data are listed in the Log Book.

• Defects noted during inspection checks and tests shall be noted in the logbook. • Dangerous defects shall be reported directly to the user, and the affected luminaire

is to be disconnected from the electrical supply, and reported to the management. • Remedy minor defects using tools and materials readily available. • Refer to suggested lamp life guide at the end of this schedule. • Harsh abrasive cleaners and organic solvents should not be used for cleaning

lighting units. • Staining of aluminium reflectors and yellowing of plastic reflectors can sometimes

be removed by pre-cleaning with metal polish or a mild abrasive paste. Painted or stove enamelled surfaces must not be abraded to remove stains or to restore colour.

Weekly

1. Visually inspect all luminaires to ensure that they remain clean. 2. Check all lighting units and replace any failed lamps, using same type, size and

rating. 3. Correct any defective floodlight/luminaire immediately. Replace worn seals or

gaskets and broken glass fronts or covers where required.

Monthly

1. Carry out tasks as detailed Weekly. 2. Check all circuits for proper function and correct any defective ones immediately

(breakers are ON, power is available to all circuit outlets and visual inspection of wiring, fixing, support, etc.).

3. Clean all luminaires and floodlights externally only with a damp cloth or sponge. An antistatic solution can be used.

4. Simulate mains failure condition on non-maintained emergency lighting units by putting off the power supply for a short period, to ensure correct functioning. Correct or replace any defective unit immediately.

5. Ensure correct operation of remote or local control where applicable. 6. Check incandescent lighting fixtures and re-lamp at 2000 hours running time as

applicable to type of lamps. Note: Ladders or mobile low height lifters may be required.

Page 38: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

18

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 18

Bi-annually

1. Carry out tasks as detailed for Monthly. 2. Check local switches (were provided) for correct operation and check security of

switches and plates. Correct any defects. 3. Check cable and terminal exterior conditions to luminaires or floodlights. Replace

any defective equipment. Correct as necessary or replace devices. 4. Visually inspect socket outlets and weatherproof plates for broken, damaged or

deteriorated parts. 5. Inspect disconnect switches for proper fixation, loose springs, breaks or cracks in

insulation, signs of flash over, clamps and straps, loose connections, blades and contacts, locking and interlocking mechanism, cable insulation for signs of overheating. Correct as necessary.

Annually

1. Carry out tasks as detailed for Bi-Annually. 2. Re-lamp all fluorescent luminaires and metal halide floodlight in public spaces using

same type, size and rating of lamps respectively. 3. Dispose of all lamps in a clean and safe professional manner. (Discharge lamps

contain toxic substances. Wear protective gloves for this task). 4. Check security of all fixings, suspensions, poles, supports and cable termination,

etc. and correct any defects. 5. Clean down all luminaires using compatible cleaning agent, damp cloth and rinsing

where necessary, then dry up with dry cloth. 6. Examine lamp holders, sockets, fuses, fuse carriers or holders, control gear, cables

and terminations, and internal wiring for signs of overheating and corrosion. Replace any defective component.

7. Check insulation resistance of socket outlet circuits (taking a minimum of two socket outlets) using a megger 500V. (Insulation resistance should not be less than 0.5 mega-ohms). Check continuity of earth conductors.

8. Test insulation resistance of disconnects switch circuit and continuity of earth conductors.

9. Carry out painting of all supports, brackets and poles. 10. Re-lamp all lighting fixtures with high pressure mercury vapour lamps (below 150W

only) using same type, size and rating of lamps where applicable in public areas after every 1000 hours, elsewhere when 20% of lamps are burnt.

Two-yearly

1. Carry out tasks as detailed for Bi-annually. 2. Test insulation resistance of all lighting circuits selected on random basis (shall not

be less than 0.5 mega-ohms) earth continuity and check condition of insulation, conduits, flexible conduits, and connections at junction boxes and at luminaries.

3. Re-lamp all high pressure sodium fixtures and luminaries’ (150W and over) using same type, sizing and rating of lamps.

2.5.2 Maintenance Procedures (Corrective)

When a defect in the system is discovered or reported, the defect should be recorded in a maintenance logbook and the appropriate action taken to remedy the defect as soon as practicable.

Page 39: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

19

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 19

2.5.3 Maintenance Hazards

A thorough inspection should always be carried out as soon as possible following a circuit fault. All equipment should be positively isolated and checked to ensure that the supply has been de-energised before any work is carried out on it.

2.5.4 Disposal Instructions

Disposal of Exhausted Lamps - Fluorescent Lamps

Small quantities of linear and compact fluorescent tubes should be broken in the packaging provided with the new lamps, if at all possible, and then disposed of as normal refuse. In the case of large quantities of fluorescent tubes, these must be disposed of in a suitable container and disposed of in accordance with Local Regulations. Care must also be taken, whether large or small quantities are being broken, to avoid flying glass. It is recommended that protective clothing, gloves and eye protectors be worn and the operation should be carried out in a well ventilated area.

Fluorescent lamps are known to release a very small quantity of airborne dust when broken which has the potential to cause respiratory irritation in susceptible individuals. In such cases it is advisable to wear disposable filtered respiratory protection or preferably carry out the task in the open air.

2.5.5 Cleaning of Luminaires

Diffusers and Plastic Controllers

Note: Operatives undertaking the cleaning work should be well instructed and supervised to ensure continuing awareness of the fragility of the louvre optic. This awareness should be maintained throughout the cleaning work, when damage is most likely to occur, and be continued when handling and storing.

Cleaning should be scheduled whenever necessary and co-ordinated with general maintenance if possible. Recommended procedures are as follows:

(1) Wash in a solution of water and domestic detergent

(2) Rinse with clean water after washing

(3) Allow to dry

(4) Apply an anti-static solution to prolong protection against dust contamination

Paint Finished Surfaces

Paint finished surfaces should be cleaned with a solution of water and domestic detergent applied with a cotton cloth. All surfaces should be wiped clean taking care not to scratch the paint finish.

Satin Anodised Aluminium Surfaces

Care must be taken when cleaning satin anodised aluminium surfaces, as it is only a surface finish and will be damaged if abrasive materials are used.

Surfaces should be cleaned with a solution of water and domestic detergent applied with a cotton cloth. This will remove most stains

Page 40: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

20

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 20

2.6 EARTHING AND LIGHTNING PROTECTION SYSTEM

2.6.1 Maintenance Procedures (Planned)

Earthing System

Bi-annually

1. Check security of connections to main earth bar and tighten as necessary. 2. Check the integrity of all bonding connections and ensure that they remain secure

and tight. 3. Check the integrity of the main neutral earthing connection at the L.V. switchgear

neutral or at the transformer neutral. Ensure that a false leakage tripping will not occur.

Note: Logbook is to be prepared for all inspection and testing procedures in which records will be kept. Electrode resistance is not to exceed 10ohm except for communication for which a maximum of 1.15ohm must be reached. Test is to be carried out with the power shut down.

4. Test electrode resistance between main earth bar and the electrode at the substation (once during the winter and once during the summer).

5. Inspect all the earthing installation for damage, deterioration and corrosion; check the conductor fixings for security, the connections for tightness and the continuity of earthing conductors.

6. Clean out all inspection pits and ensure lids fit correctly, and are appropriately marked as initially installed.

Lightning Protection System

Bi-annually

1. Check the fixings of conductors and components for security and check the installation for damage, deterioration and corrosion.

2. Ensure bonding of the lightning protection system to the main earth bars. 3. Check and verify that metallic structures are bonded to the lightning protection

installation. 4. Test the electrical continuity of the conductors, bonds and joints. 5. Measure the resistance to earth of each earth rod or group of earth rods when

disconnected from the installation. Compare the measured resistance with previous test results and investigate any significant change in resistance.

6. Measure the resistance of the installation o earth from random points in the installation. The resistance to the general mass of earth from any point of the complete installation should not normally exceed 10 ohms.

7. Record the situation of the installation, the measured earth electrode resistance, the individual earth rods or group of earth rods and the highest resistance measured at random points on the installation.

8. Clean out all inspection pits and ensure concrete lids fit correctly. 9. Inspect vertical down conductors and earth terminations. Check that conductors are

securely fixed to the structure. 10. Check by air terminals, connections at air terminals or structures behaving as air

terminals.

Page 41: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

21

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 21

2.6.2 Maintenance Procedures (Corrective)

Treatment of soil is needed by mixing additive chemicals.

2.6.3 Maintenance Hazards

N/A

2.6.4 Disposal Instructions

N/A

2.7 ELEVATOR SYSTEM

2.7.1 Maintenance Procedures (Planned)

Refer to Annex document

2.7.2 Maintenance Procedures (Corrective)

Refer to Annex document

2.7.3 Maintenance Hazards

Refer to Annex document

2.7.4 Disposal Instructions

N/A

Page 42: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

22

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 22

2.8 MAINTENANCE SCHEDULE

2.8.1 Introduction

The schedules indicate the recommended intervals between routine maintenance tasks.

Please note that these are for guidance only. The intervals stated may need to be varied depending upon the age of the plant, usage, etc.

It is advisable to monitor plant operation regularly and maintain an up-to-date logbook. In this way, it will be possible to obtain a reliable indication of the amount of maintenance that the plant requires.

It is important to remember that before work or inspection begins on any item of electrically operated plant, it must be isolated, preferably by removing the fuses in the control panel. Notices must also be posted advising others that the plant is being worked on.

It should be noted that operation of the primary plant serving the works is controlled automatically by the Building Management System and may activate without warning at any time. Check before de-energising the plant whether it is interlinked with other plant (for example duty/standby fans), that may also need to be de-energised.

A basic requirement of any piece of equipment that contains moving parts is correct lubrication. Reference should be made to the manufacturer’s literature and the lubrication schedule contained in this manual for details. Failure to lubricate as recommended will lead to a shortened plant life and premature failure.

Systems will have been balanced to their correct design rates by commissioning engineers. Therefore if it is necessary to alter the set position of a valve, duct damper, etc. or to adjust the speed on a variable speed motor these must all be restored to their previous settings when the maintenance work is complete.

Page 43: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

23

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 23

2.8.2 Schedule

DESCRIPTION SEE PARA

D W M Q S A T

MEDIUM VOLTAGE SWITCH GEARS AND POWER TRANSFORMERS 13.8KV

2.2.0 X X X

LOW VOLTAGE MAIN DISTRIBUTION BOARDS AND DISTRIBUTION PANEL BOARDS 380/230V

2.3.0 X X X X X X

ELECTRICAL LOW VOLTAGE EQUIPMENTS, UPS, ATS, MCC, ECB, CAPACITOR BANKS, DIMMING SYSTEM.

2.4.0 X X X X

LIGHTING AND SMALL POWER SYSTEM.

2.5.0 X X X X X X

EARTHING AND LIGHTNING PROTECTION SYSTEM

2.6.0 X

LEGEND D W M Q S A T Frequency Daily Weekly Monthly Quarterly Every Six

Months Annually Every

Two Years or More

Page 44: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

24

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 24

2.9 FAULT FINDING

2.9.1 Sub-Main Dis tribution Sys tem Fault Possible Cause Check Remedial Action

Failure of supply

Excessive current drawn

Main protective devices

Check main protective devices. Wiring fault may have tripped breaker. Investigate fault, repair, test and reset protective device.

Supply outage Regional electricity Consult regional electricity company.

Insufficient voltage

Supply voltage low Supply voltage Check if voltage at source is low and consult regional electricity company.

Faulty MCCB/MCB MCCB/MCB Reset or replace MCCB/MCB as necessary.

Excessive voltage drop on sub-mains Sub-main current

Check actual current drawn at distribution board is equal to or less than the design current.

Excessive current drawn

Excessive load on circuit Circuit load

Check and reduce loading as necessary. Consult electrical engineer for advice if wiring/distribution system requires to be upgraded to meet increased demand

Phase failure in 3-phase system. Phases Check phases are correct.

Out of balance 3-phase load. Phases

Check loads are evenly balanced across all phases. Balance single phase loads across phases where necessary.

Loss of continuity Broken termination Distribution board

connections

Check all connections at MCCB/MCB distribution boards and re-terminate cables as necessary.

Page 45: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

25

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 25

2.9.2 Un-switch Switchgear Problem Action

All cubicle types

Switch-disconnector cannot be closed.

Check that the switch is in the open position. Check that the interlocking selector is in the ‘Operation’ position. Turn the operating handle clockwise.

Switch-disconnector cannot be opened.

Check that the switch is in the closed posit Check that the interlocking selector is in the ‘Operation’ position. Turn the operating handle anti-clockwise.

Switch-disconnector cannot be moved to the earthed position.

Check that the switch is in the open position. Check that the interlocking selector is in the ‘Test’ position. Turn the operating handle clockwise.

Switch-disconnector cannot be moved from the open to earthed position.

Check that the switch is in the earthed position. Check that the interlocking selector is in the ‘Test’ position. Turn the operating handle clockwise.

Cable compartment door will not open or close.

Check that the switch is in the earthed position. Check that the interlocking selector is in the ‘Door open’ position.

Switch-fuse cubicle

Switch-fuse will not close.

If the switch is in the open position due to a fuse trip or motor operation, the notch on the operating shaft is to be turned downwards before the switch can be operated to the closed position. Check to see if a fuse has blown.

The switch-fuse has not operated even though a fuse has blown.

Check that the fuse is correctly fitted so that the trip pin indicator is pointing upwards.

Circuit-breaker cubicle

The cable compartment door will not open.

Check that the switch is in the earthed position. Check the interlocking selector is in the ‘Door open’ position. Remove the key from the circuit-breaker before opening or closing the door.

The circuit-breaker will not go to the closed position.

Ensure that the closing spring is fully charged, and that the interlocking coil is not energised Check that the circuit-breaker key is in place and turned to the correct operating position. Check that the circuit-breakers auxiliary voltage plug is properly locked into the socket. Check that the control pin is on its position (HD4/S & VD4/S) Action

Instrument Transformers Secondary measurements from the current transformers are not possible.

Check that all shorting links on the secondary terminals of the current transformers have been removed.

Check the connections.

Page 46: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

2

Page

26

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities and Sciences ( West Building)

Maintenance Procedures Page 26

2.9.3 General Lighting Fault Possible Cause Remedial Action

Equipment will not operate.

MCB tripped. Refer to “MCB Trips” fault

Switch failure. Check connections to switch and renew if necessary.

Circuit continuity.

Check all connections to the distribution board. Conduct a capacitance ratio test to locate the approximate location of the break and renew the faulty section of cable.

Equipment fault. Check condition of lamp and control gear and renew as necessary.

Sub-mains failure. Refer to ‘Troubleshooting – Electrical Sub-main’ above.

MCB Trips. Equipment fault. Check condition of luminaires for excess

current drawn. MCB fault. Test and renew MCB if necessary.

Group of luminaires not functioning. Faulty local switch. Check and renew switch if necessary.

Single luminaire not functioning.

Loose connection within luminaire.

Check security of connections and re-tighten any that are loose.

Luminaires in an area of the building not functioning.

Fault in final circuit wiring has caused circuit breaker to trip.

Investigate fault and remedy. Test cabling and return circuit breaker to the energised state.

Two lamps within a four lamp luminaire are not functioning.

Usually each electronic ballast serves two lamps (one ballast per two lamps). If one lamp is defective, the other cannot function.

Determine which lamp is defective and renew.

Luminaire appears to be ‘humming’. Faulty ballast. Check and renew ballast if necessary.

Page 47: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

1

College of Arts, Humanities & Sciences (West Building

Equipment Schedules Page 1

SECTION 3

SPARE PARTS & SOURCE INFORMATION

LIST OF CONTENTS Section Content Page 3.1 LV panel boards and Motor Control Centres 3.2 UPS 3.3 MV Switchgears 3.4 Wiring Devices

Page 48: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

2

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 2

SECTION 3

SPARE PARTS & SOURCE INFORMATION 3.1 LV PANEL BOARDS Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

DP,ECB,EDP, EDLP,ELP,EMCP.MCC, EPP,ESDP,LP,PP,UDP, UPP,UPS Panel,USDP

Fuse carriers STI Isolatable (500V-IEC 947.3 Iemax-32A) 1P 10.3x38 mm 15636

SETRAA-AL AMAL MANUFACTURING CO.

Fuse STI Isolatable gG (100kA/500V-IEC/ NF/ EN 60269-1) 10.3x38- 02 A 15775

Fuse STI Isolatable gG (100kA/500V-IEC/ NF/ EN 60269-1) 10.3x38- 10 A 15779

MG Current Transformer (Ue.720V/ SC.5A/ IP20/ 1.2 In/ IEC.441)- 0 ~ 600A 16481

MG Current Transformer (Ue.720V/ SC.5A/ IP20/ 1.2 In/ IEC.441)- 0 ~ 1000A 16483

C60N 2Pole MCB (Icu-10kA/415V-IEC947,Class-3/ 30°C/ C-curve)- 16Amps 24337

C60N 3Pole MCB (Icu-10kA/415V-IEC947,Class-3/ 30°C/ C-curve)- 20Amps 24351

C60N 3Pole MCB (Icu-10kA/415V-IEC947,Class-3/ 30°C/ C-curve)- 32Amps 24353

C60N 3Pole MCB (Icu-10kA/415V-IEC947,Class-3/ 30°C/ C-curve)- 40Amps 24354

C60N 3Pole MCB (Icu-10kA/415V-IEC947,Class-3/ 30°C/ C-curve)- 63Amps 24356

C60N 1Pole MCB (Icu-10kA/240V-IEC947,Class-3/ 30°C/ C-curve)- 16Amps 24403

Page 49: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

3

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 3

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

DP,ECB,EDP, EDLP,ELP,EMCP.MCC, EPP,ESDP,LP,PP,UDP, UPP,UPS Panel,USDP

C60N 1Pole MCB (Icu-10kA/240V-IEC947,Class-3/ 30°C/ C-curve)- 20Amps 24404

SETRAA-AL AMAL MANUFACTURING CO.

C60N 1Pole MCB (Icu-10kA/240V-IEC947,Class-3/ 30°C/ C-curve)- 25Amps 24405

C60N 1Pole MCB (Icu-10kA/240V-IEC947,Class-3/ 30°C/ C-curve)- 32Amps 24406

C60N 1Pole MCB (Icu-10kA/240V-IEC947,Class-3/ 30°C/ C-curve)- 40Amps 24407

C60H 1Pole MCB (Icu-15kA/240V-IEC947,Class-3/ 30°C/ C-curve)- 20Amps 24975

C60H 3Pole MCB (Icu-15kA/415V-IEC947,Class-3/ 30°C/ C-curve)- 20Amps 25001

C60H 3Pole MCB (Icu-15kA/415V-IEC947,Class-3/ 30°C/ C-curve)- 32Amps 25003

C60H 3Pole MCB (Icu-15kA/415V-IEC947,Class-3/ 30°C/ C-curve)- 40Amps 25004

Vigi modules adaptable MCB-C60 3Pole -32~63 Amps- Sensitivity- 30mA 26556

Vigi modules adaptable MCB-C60 3Pole -0~25 Amps- Sensitivity- 30mA 26588

RCBO type MCB C60H (10kA/ IEC-1009.2.2.Icu.30°C), 30mA N+ 20 Amps 26860

Rotary Handle extended use to Moulded Case Circuit Breaker type NS80H 28052

NS80H 3Pole MCCB Magnetic Trip Unit (70kA/415V-IEC 947.2)- 80Amps 28100

NS80H 3Pole MCCB Magnetic Trip Unit (70kA/415V-IEC 947.2)- 50Amps 28101

Auxiliary contact for (IEC-60947) MCCB- NS/NSX 100/630- OF/ SDE/ SDV 29450

Page 50: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

4

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 4

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

DP,ECB,EDP, EDLP,ELP,EMCP.MCC, EPP,ESDP,LP,PP,UDP, UPP,UPS Panel,USDP

Auxiliary contact for (IEC-60947.5.1) MCCB-NS 800/1600- Trip indication 33004

SETRAA-AL AMAL MANUFACTURING CO.

Auxiliary contact for (IEC-60947.5.1) MCCB-NS 800/1600-Fault indication 33011

Auxiliary contact for (IEC-60947.5.1) MCCB-NS 800/1600- OF indication 33108

NS 3P MCCB Basic Frame 630bN (50kA/440V-IEC 60947.2)- 630Amps 33220

NS 3P MCCB Basic Frame 1000N (50kA/440V-IEC 60947.2)- 1000Amps 33240

Micrologic 6.0 with ammeter for MCCB Fixed type (Earth fault protection) 33513

NS 3P MCCB Adjustable 630bN (50kA/440V-IEC947/Micro.5.0)- 630Amps 33546

NS 3P MCCB Adjustable1000N (50kA/440V-IEC947/Micro.5.0)- 1000Amps 33558

NS 3P MCCB Adjustable1250N (50kA/440V-IEC947/Micro.5.0)- 1250Amps 33564

External sensor MCCB-NS, earth-fault protection (TCE): CT - 400/1600A 33576

Top front connection / circuit breaker 3P Fixed MCCB-NS- 630/1000 Amps 33598

Bottom front connection/ circuit breaker 3P Fixed MCCB- 630/1000 Amps 33599

Shunt trip coil for (IEC-60947-2/ 0.7xUn) MCCB-NS 800/3200-130V AC/DC 33661

Rotary Handle extended use to Moulded Case Circuit Breaker type NS 800/1600 33878

Micrologic External Power supply module 220Volt AC/ 24 Volt DC output 54444

Page 51: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

5

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 5

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

DP,ECB,EDP, EDLP,ELP,EMCP.MCC, EPP,ESDP,LP,PP,UDP, UPP,UPS Panel,USDP

Rotary Handle extended use Moulded Case Circuit Breaker type NSX 100/250 LV429338

SETRAA-AL AMAL MANUFACTURING CO.

NSX 3P MCCB Adjustable 100F (36kA/415V-IEC947/ 40°C/ TMD)-100Amps LV429630

NSX 3P MCCB Adjustable 100F (36kA/415V-IEC947/ 40°C/ TMD)- 80Amps LV429631

NSX 3P MCCB Adjustable 100F (36kA/415V-IEC947/ 40°C/ TMD)- 63Amps LV429632

NSX 3P MCCB Adjustable 100F (36kA/415V-IEC947/ 40°C/ TMD)- 40Amps LV429634

NSX 3P MCCB Adjustable 100F (36kA/415V-IEC947/ 40°C/ TMD)- 32Amps LV429635

NSX 3P MCCB Adjustable 100F (36kA/415V-IEC947/ 40°C/ TMD)- 25Amps LV429636

NSX 3P MCCB Adjustable 100F (36kA/415V-IEC947/ 40°C/ TMD)- 16Amps LV429637

NSX. 3P MCCB Magnetic Trip Unit 100F (36kA/415V/IEC947/MA)-100Amps LV429740

NSX basic frame without trip 3P MCCB 160F (Icu-36kA/415V-IEC-60947.2) LV430403

NSX 3P MCCB Adjustable 160F (36kA/415V-IEC947/ 40°C/ TMD)-160Amps LV430630

NSX 3P MCCB Adjustable 160F (36kA/415V-IEC947/ 40°C/ TMD)-125Amps LV430631

NSX 3P MCCB Adjustable 160F (36kA/415V-IEC947/ 40°C/ TMD)-100Amps LV430632

NSX 3P MCCB Adjustable 160F (36kA/415V-IEC947/ 40°C/ TMD)- 80Amps LV430633

NSX. 3P MCCB Magnetic Trip Unit 160F (36kA/415V/IEC947/MA)-150Amps LV430830

Page 52: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

6

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 6

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

DP,ECB,EDP, EDLP,ELP,EMCP.MCC, EPP,ESDP,LP,PP,UDP, UPP,UPS Panel,USDP

NSX basic frame without trip 3P MCCB 250F (Icu-36kA/415V-IEC-60947.2) LV431403

SETRAA-AL AMAL MANUFACTURING CO.

NSX basic frame without trip 3P MCCB 250N (Icu-50kA/415V-IEC-60947.2) LV431406

NSX 3P MCCB Adjustable 250F (36kA/415V-IEC947/ 40°C/ TMD)-250Amps LV431630

NSX 3P MCCB Adjustable 250F (36kA/415V-IEC947/ 40°C/ TMD)-200Amps LV431631

NSX 3P MCCB Adjustable 250F (36kA/415V-IEC947/ 40°C/ TMD)-125Amps LV431633

NSX 3P MCCB Adjustable 400F (36kA/415V-IEC947/ Micro.5.3A)-400Amps LV432678

NSX 3P MCCB Adjustable 630F (36kA/415V-IEC947/ Micro.5.3A)-630Amps LV432878

NSX Thermal Magnetic Trip unit /IEC947/ 3Pole MCCB 100/250-100Amps LV435104

NSX Thermal Magnetic Trip unit /IEC947/ 3Pole MCCB 100/250- 80Amps LV435105

NSX Thermal Magnetic Trip unit /IEC947/ 3Pole MCCB 100/250- 63Amps LV435106

NSX Thermal Magnetic Trip unit /IEC947/ 3Pole MCCB 100/250- 40Amps LV435108

NSX Thermal Magnetic Trip unit /IEC947/ 3Pole MCCB 100/250- 32Amps LV435109

NSX Thermal Magnetic Trip unit /IEC947/ 3Pole MCCB 100/250- 32Amps LV4429035

Page 53: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

7

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 7

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

DP,ECB,EDP, EDLP,ELP,EMCP.MCC, EPP,ESDP,LP,PP,UDP, UPP,UPS Panel,USDP

VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 00.75 KW ATV61H075N4

SETRAA-AL AMAL MANUFACTURING CO.

VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 11.00 KW ATV61HD11N4

VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 15.00 KW ATV61HD15N4

VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 18.50 KW ATV61HD18N4

VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 22.00 KW ATV61HD2 2N4

VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 37.00 KW ATV61HD37N4

VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 45.00 KW ATV61HD45N4

VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 55.00 KW ATV61HD55N4

VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 240V- 00.75 KW ATV61HU15M3

VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 02.20 KW ATV61HU22N4

VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 03.00 KW ATV61HU30N4

Page 54: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

8

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 8

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

DP,ECB,EDP, EDLP,ELP,EMCP.MCC, EPP,ESDP,LP,PP,UDP, UPP,UPS Panel,USDP

VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 04.00 KW ATV61HU40N4

SETRAA-AL AMAL MANUFACTURING CO.

VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 05.50 KW ATV61HU55N4

VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 07.50 KW ATV61HU75N4

Rotary Handle extended use GV2 type (standard/ IP54) Motor Circuit Breaker GV2AP01

GV2-L04 3P Magnetic Trip Unit 100kA/ 415V/ IEC-947/ AC.3- 0.63 Amps GV2L04

GV2-L06 3P Magnetic Trip Unit 100kA/ 415V/ IEC-947/ AC.3- 1.6 Amps GV2L06

GV2-L07 3P Magnetic Trip Unit 100kA/ 415V/ IEC-947/ AC.3- 2.5 Amps GV2L07

GV2-L08 3P Magnetic Trip Unit 100kA/ 415V/ IEC-947/ AC.3- 4.0 Amps GV2L08

GV2-L10 3P Magnetic Trip Unit 100kA/ 415V/ IEC-947/ AC.3- 6.3 Amps GV2L10

GV2-L14 3P Magnetic Trip Unit 100kA/ 415V/ IEC-947/ AC.3- 10 Amps GV2L14

GV2-L16 3P Magnetic Trip Unit 50kA/ 415V/ IEC-947/ AC.3- 14 Amps GV2L16

GV2-L20 3P Magnetic Trip Unit 50kA/ 415V/ IEC-947/ AC.3- 18 Amps GV2L20

GV2-L22 3P Magnetic Trip Unit 50kA/ 415V/ IEC-947/ AC.3- 25 Amps GV2L22

GV2-L32 3P Magnetic Trip Unit 50kA/ 415V/ IEC-947/ AC.3- 32 Amps GV2L32

Page 55: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

9

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 9

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

DP,ECB,EDP, EDLP,ELP,EMCP.MCC, EPP,ESDP,LP,PP,UDP, UPP,UPS Panel,USDP

Auxiliary contact (IEC-60947.5) for MCB-GV2- fault + 1NO (Side mounting) GVAD1010

SETRAA-AL AMAL MANUFACTURING CO.

Voltmeter Selector Switch (Ui 690V/ IEC 947.5/ Ith12A) Multi fixing 6+OFF K1F027MLH

Mechanical Interlock Contactor Horizontal Mounting for LC1-D 115/150 LA9D11502

Mechanical Interlock Contactor Horizontal Mounting for LC1-D 40/95 LA9D4002

LC1 side mounting instantaneous auxiliary contact blocks- 02-NO LAD8N20

Mechanical Interlock Contactor Horizontal Mounting for LC1-D 09/32 LAD9R1

LC1 front mounting instantaneous auxiliary contact blocks- 02-NO + 02-NC LADN22

LC1-D 3P Contactor (690V/IEC.947/ AC-3/ 50°) coil 110Volt/ 60Hz- 09 Amps LC1D09F7

LC1-D 3P Contactor (690V/IEC.947/ AC-3/ 50°) coil 110Volt/ 60Hz-115 Amps LC1D115F7

LC1-D 3P Contactor (690V/IEC.947/ AC-3/ 50°) coil 110Volt/ 60Hz- 12 Amps LC1D12F7

LC1-D 3P Contactor (690V/IEC.947/ AC-3/ 50°) coil 110Volt/ 60Hz- 18 Amps LC1D18F7

LC1-D 3P Contactor (690V/ IEC947/ AC-3/ 50°) coil 220Volt/ 60Hz- 18 Amps LC1D18M7

Page 56: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

10

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 10

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

DP,ECB,EDP, EDLP,ELP,EMCP.MCC, EPP,ESDP,LP,PP,UDP, UPP,UPS,USDP

LC1-D 3P Contactor (690V/IEC.947/ AC-3/ 50°) coil 110Volt/ 60Hz- 25 Amps LC1D25F7

SETRAA-AL AMAL MANUFACTURING CO.

LC1-D 3P Contactor (690V/IEC.947/ AC-3/ 50°) coil 110Volt/ 60Hz- 32 Amps LC1D32F7

LC1-D 3P Contactor (690V/ IEC947/ AC-3/ 50°) coil 220Volt/ 60Hz- 32 Amps LC1D32M7

LC1-D 3P Contactor (690V/IEC.947/ AC-3/ 50°) coil 110Volt/ 60Hz- 40 Amps LC1D40F7

LC1-D 3P Contactor (690V/IEC.947/ AC-3/ 50°) coil 110Volt/ 60Hz- 50 Amps LC1D50F7

LC1-D 3P Contactor (690V/ IEC947/ AC-3/ 50°) coil 220Volt/ 60Hz- 65 Amps LC1D65M7

LC1-D 3P Contactor (690V/IEC.947/ AC-3/ 50°) coil 110Volt/ 60Hz- 80 Amps LC1D80F7

LC1-D 3P Contactor (690V/ IEC947/ AC-3/ 50°) coil 220Volt/ 60Hz- 80 Amps LC1D80M7

LR9D Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 60-100 Amps LR9D5367

LR9D Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 90-150 Amps LR9D5369

LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 0.40~0.63 A LRD04

LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 1.0~1.6 Amps LRD06

Page 57: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

11

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 11

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

DP,ECB,EDP, EDLP,ELP,EMCP.MCC, EPP,ESDP,LP,PP,UDP, UPP,UPS,USDP

LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 1.6~2.5 Amps LRD07

SETRAA-AL AMAL MANUFACTURING CO.

LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 2.5~4.0 Amps LRD08

LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 4.0~6.0 Amps LRD10

LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 5.5~8 Amps LRD12

LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 7~10 Amps LRD14

LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 9~13 Amps LRD16

LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 12~18 Amps LRD21

LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 16~24 Amps LRD22

LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 23~32 Amps LRD3353

LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 30~40 Amps LRD3355

LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 37~50 Amps LRD3357

LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 55~70 Amps LRD3361

LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 63~80 Amps LRD3363

Voltage Monitoring Relay (AC15. 3A) 3Phase 50/60Hz- 380/440 Volt RM4TR32

14 - Pin plug miniature control relay (IEC-255.1) base for 250V/ 10Amps RXZE2M114

Page 58: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

12

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 12

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

DP,ECB,EDP, EDLP,ELP,EMCP.MCC, EPP,ESDP,LP,PP,UDP, UPP,UPS,USDP

VFD-(Altivar-61/ IP54) control Remote Operator Terminal Mounting Kit VW3A1102

SETRAA-AL AMAL MANUFACTURING CO.

VFD-Remote Operator Terminal Cable equipped with two RJ45 05 Meter VW3A1104R50

VFD-(Altivar-61) Remote Operator Terminal RJ45 female/ female adaptor VW3A1105

VFD Harmonice current reduction Line Chokes- ATV61H075 - HU15N4 VW3A4551

VFD Harmonice current reduction Line Chokes- ATV61HU22 - HU40N4 VW3A4552

VFD Harmonice current reduction Line Chokes- ATV61HU55 - HU75N4 VW3A4553

VFD Harmonice current reduction Line Chokes- ATV61HD11 - HD15N4 VW3A4554

VFD Harmonice current reduction Line Chokes- ATV61HD18 - HD22N4 VW3A4555

VFD Harmonice current reduction Line Chokes- ATV61HD30 - HD55N4 VW3A4556

Push Button spring return(22mm/ IEC/EN.947/IP66/AC-15) 1N/C Black color XB4BA21

Push Button spring return(22mm/ IEC/EN.947/IP66/AC-15) 1N/O Green color XB4BA31

XB4BA31

Push Button spring return(22mm/ IEC/EN.947/IP66/AC-15) 1N/C Red color XB4BA42

Selector Switch Standard - Off-ON 2Position (IEC-947.5/ IP66/4X) 1contact XB4BD21

Selector Switch Standard - A-0-M 3Position (IEC-947.5/ IP66/4X) 1contact XB4BD33

Page 59: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

13

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 13

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

DP,ECB,EDP, EDLP,ELP,EMCP.MCC, EPP,ESDP,LP,PP,UDP, UPP,UPS,USDP

Push Button Emergency turn release (22mm/IEC947/IP66/NEMA.4) Red color XB4BS542

SETRAA-AL AMAL MANUFACTURING CO.

Pilot- Lamp Integral LED bulb(IEC-60947.5/ IP66)- 40~132Volt White color XB4BVG1

Pilot- Lamp Integral LED bulb(IEC-60947.5/ IP66)- 40~132Vol Green color XB4BVG3

Pilot- Lamp Integral LED bulb(IEC-60947.5/ IP66)- 40~132Volt Red color XB4BVG4

Pilot- Lamp Integral LED bulb (IEC-60947.5/ IP66) -195~264Volt Red color XB4BVM4

Pilot- Lamp Integral LED bulb (IEC-60947.5/ IP66) -195~264Volt Yellow XB4BVM5

Pilot- Lamp Integral LED bulb (IEC-60947.5/ IP66) -195~264Volt Blue color XB4BVM6

Auxiliary contact for Normally Open use to extension for selector switch ZBE101

Auxiliary contact for Normally Closed use to extension for selector switch ZBE102

ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~100Amps ASK31.3/100

ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~160Amps ASK31.3/150

ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~200Amps ASK31.3/200

ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~250Amps ASK31.3/250

Page 60: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

14

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 14

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

DP,ECB,EDP, EDLP,ELP,EMCP.MCC, EPP,ESDP,LP,PP,UDP, UPP,UPS,USDP

ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~ 30Amps ASK31.3/30

SETRAA-AL AMAL MANUFACTURING CO.

ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~ 40Amps ASK31.3/40

ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~ 50Amps ASK31.3/50

ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~ 80Amps ASK31.3/80

ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~400Amps ASK41.4/400

ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~600Amps ASK51.4/600

ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~1000Amps ASK81.4/100

ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~1250Amps ASK81.4/120

FQ Ammeter/ M. Iron/ Class 1.5/ IEC 521/ Scale 90°/ 96x96mm- 0~1000Amps FQ0207-1000/5

FQ Ammeter/ M. Iron/ Class 1.5/ IEC 521/ Scale 90°/ 96x96mm- 0~1250Amps FQ0207-1250/5

Page 61: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

15

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 15

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

DP,ECB,EDP, EDLP,ELP,EMCP.MCC, EPP,ESDP,LP,PP,UDP, UPP,UPS,USDP

FQ Ammeter/ M. Iron/ Class 1.5/ IEC 521/ Scale 90°/ 96x96mm- 0~200Amps FQ0207-200/5

SETRAA-AL AMAL MANUFACTURING CO.

FQ Ammeter/ M. Iron/ Class 1.5/ IEC 521/ Scale 90°/ 96x96mm- 0~250Amps FQ0207-250/5

FQ Ammeter/ M. Iron/ Class 1.5/ IEC 521/ Scale 90°/ 96x96mm- 0~400Amps FQ0207-400/5

FQ Voltmeter/ M. Iron/ Class 1.5/ IEC 521/ Scale 90°/ 96x96mm- 0~500 Volt FQ0207-500

FQ Ammeter/ M. Iron/ Class 1.5/ IEC 521/ Scale 90°/ 96x96mm- 0~630Amps FQ0207-630/5

Terminal block color Grey (EN-60715) 1single connection- 2.5 mm2 39060

Terminal block color Grey (EN-60715) 1single connection- 4 mm2 39061

Terminal block color Grey (EN-60715) 1single connection- 6 mm2 39062

Terminal block color Grey (EN-60715) 1single connection- 10 mm2 39064

Terminal block color Grey (EN-60715) 1single connection- 16 mm2 39066

Terminal block color Grey (EN-60715) 1single connection- 35 mm2 39068

Terminal block color Grey (EN-60715) 1single connection- 70 mm2 39070

Terminal block color Grey (EN-60715) with blade type- 4 mm2 39084

Page 62: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

16

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 16

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

DP,ECB,EDP, EDLP,ELP,EMCP.MCC, EPP,ESDP,LP,PP,UDP, UPP,UPS,USDP

Terminal block color Green/Yellow (EN-60715) 1connection- 4 mm2 39371

SETRAA-AL AMAL MANUFACTURING CO.

Terminal block color Green/Yellow (EN-60715) 1connection- 6 mm2 39372

Terminal block color Green/Yellow (EN-60715) 1connection- 10 mm2 39374

Terminal block color Green/Yellow (EN-60715) 1connection- 16 mm2 39376

Terminal block color Green/Yellow (EN-60715) 1connection- 35 mm2 39378

Terminal block color Grey end stoper standard - 8mm pitch rail. 39403

Terminal block color Grey (EN-60715) end caps standard- 2.5/4mm2 39450

Terminal block color Grey (EN-60715) end caps standard- 6/10 mm2 39451

Terminal block color Grey (EN-60715) end caps standard- 16/35 mm2 39452

Page 63: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

17

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 17

3.2 UPS SYSTEM Panel Ref Replacement Part Details Part Identification Manufacturer Local Source MODEL 90NET/400

FUSE 1000A660V EXTRA FAST

SAUDI ELECTRONIC COMPANY SETRA

FUSE 2A 500V,2X32 DELAYED FUSE 500A 660V EXTRA FAST FUSE 6,3S, 500V, 2X32 DELAYED FUSE 800A,660V,EXTRA FAST IGBT H14, 800A, 1200V SCR 500A 1600V SCR/SCR 250A, 1600V RADIAL FAN DIODE 950A,1000V IGBT INTERFACE BOARD CAPACITOR 350VAC VARISTOR VARISTOR BOARD

Page 64: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

18

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 18

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source MODEL 90NET/400

FUSE 1000A660V EXTRA FAST FUSE 2A 500V,2X32 DELAYED FUSE 500A 660V EXTRA FAST FUSE 6,3S, 500V, 2X32 DELAYED FUSE 800A,660V,EXTRA FAST IGBT H14, 800A, 1200V SCR 500A 1600V SCR/SCR 250A, 1600V RADIAL FAN DIODE 950A,1000V IGBT INTERFACE BOARD CAPACITOR 350VAC VARISTOR VARISTOR BOARD

Page 65: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

19

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 19

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source 3.3 MV SWITCHGEARS

SCHNEIDER RIYADH INDUSTRIAL CITY 2

CURRENT TFO. CORE 1 :200-400/5-5A, 15-30VA, CL. 0.5 MG PE12500201

CURRENT TFO. CORE 2 : 200-400/5-5A, 7.5-15VA, CL. 5P10

LED PILOT LIGHT, GREEN, 24-130VDC, STYLE 4 Telemecanique XB4BVBG33

LED PILOT LIGHT, RED, 24-130VDC, STYLE 4 Telemecanique XB4BVBG43

CAPACITIVE VOLT REGULATOR MG (CDM) BBV22460 IMC500 DISCON. w/ CI2 MECH, 630A, 17.5kV, 21kA/1sec, (Inc. Cub) MG (CTC) 3985949A

MINIATURE CB, 6A 2P, 500VDC, C-CURVE SCHNEIDER ELECTRIC MGN

MINIATURE CB, 6A 2P, 500VDC, C-CURVE SCHNEIDER ELECTRIC 20545

DIGITAL POWERMETER, 24-250V AC/DC, CL. 0.5

SCHNEIDER ELECTRIC PM820

CURRENT TEST BLOCK, 4P Entrelec CCEVA16662520 VOLTAGE TEST BLOCK, 4P Entrelec TCEC4A16688922 SPRING RETURN SELECTOR SW., 3 - pos, 2 no,STD. HDLE. Telemecanique XB4BD53

STAY – PUT KEY SWITCH, 1N/O, 2 – pos Telemecanique XB4BG41 ADD – ON N.O. SWITCH Telemecanique ZBE102 Current Transd,DI125, 1PH, 4.20mA,CT 5A, CL.0.5, VX=80 – 276VAC/DC CEWE PE12500601

Page 66: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

20

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 20

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

MV CUBICLE SM6

LV FUSE, 10A MG (CTC) 25574919

SCHNEIDER RIYADH INDUSTRIAL CITY 2

SWITCH DISCONNECTING FUSE MG (CTC) 9115658 MV FUSE, 6.3A, 24kV, L=442mm MG (DIPS) 51006538MO MV FUSE, 6.3A, 24kV, L=442mm MG (DIPS) 51006538MO MV FUSE, 6.3A, 24kV, L=442mm MG (DIPS) 51006538MO CM DISC. SW., 50A, 17.5kV, 21kA/1sec, (Inc. Cub) MG (CTC) 398573A

AUXILIARY CONTACT BLOCK MG (CTC) 877942Q1 VOLTAGE TFO. 17.5kV, 13.5kV/r3, 110V/r3, 50VA, CL. 0.5 MG (CTC) VTJBS4B21F40

VOLTAGE TFO. 17.5kV, 13.5kV/r3, 110V/r3, 50VA, CL. 0.5 MG (CTC) VTJBS4B21F40

VOLTAGE TFO. 17.5kV, 13.5kV/r3, 110V/r3, 50VA, CL. 0.5 MG (CTC) VTJBS4B21F40

SCREW CLAMP TERMINAL, 44A, 6 sq.mm WEIDMULLER --- EVM – 35 VOLTMETER, 24 – 250V AC/DC, CL0.5 ENTUS K716060001 VOLTAGE TEST BLOCK, 4P Entrelec 28851125 MINIATURE CB, 6A, 2P, 500VDC, C – CURVE SCHNEIDER ELECTRIC MGN61526 CT CORE 1: 200 – 400/5A, 15 – 30VA, CL 0.5 MG (CTC) 3731105 CT CORE 2: 200 – 400/5A, 7.5 – 15VA, CL. 5P10 TORODIAL TFO., 200mm DIA MG (CTC) 59636 SEPAM SERIES 40 RELAY TYPE T40, CT:1A or 5A, 24 – 250VDC, 100 – 240VAC MG (PCR/PDM) S10MDT40J33TNT

Page 67: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

21

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 21

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

MV CUBICLE SM6

CAPACITIVE VOLT INDICATOR MG (CDM) 59903

SCHNEIDER RIYADH INDUSTRIAL CITY 2

SF1 630A CB, 17.5kV,21kA/1s,FIXED TYPE, 630A, 3P, 110V DC MTR, CL. &TRIP COIL MG (CTC) PE12501801

DOWNSTEARM EARTH SWITCH FOR DM1 MG (CTC) INTEGRAL PART DM1 – A DISC. SW., 630A, 17.5kV, 21kA/1sec, (Inc. Cub) MG (CTC) 3985916A

MINIATURE CB, 6A, 2P, 500VDC, C – CURVE MG (Voiron) MGN61526 MINIATURE CB, 6A, 2P, 500VDC, C – CURVE MG (Voiron) MGN61526 CURRENT TEST BLOCK, 4P Entrelec CCEVA16662520 LOCAL/REMOTE SELECTOR SWITCH TELEMECANIQUE XB4BG41 SPRING RETURN SELECTOR SWITCH TELEMECANIQUE XB4BD53 Current Transd,DI125, 1PH, 4.20mA,CT 5A, CL.0.5, VX=80 – 276VAC/DC CEWE PE12500601

DIGITAL POWER METER SCHNEIDER ELECTRIC PM820 VOLTAGE TEST BLOCK, 4P Entrelec TCEC4A16688922 SURGE ARRESTOR, 15kV AVERA ------ LED PILOT LIGHT, GREEN, 24 – 130VDC, STYLE 4 Telemecanique XB4BVBG33

LED PILOT LIGHT, RED, 24 – 130VDC, STYLE 4 Telemecanique XB4BVBG43 LED PILOT LIGHT, YELLOW, 24 – 130VDC, STYLE 4 Telemecanique XB4BVBG53

COMM. INTERFACE MODULE, 12/24VDC, RS485, 2 - WIRE MG (PCR/PDM) 59642

Current Transd. DI125,1PH, 4.20mA,CT 5A, VX=80 – 276VAC/DC

CEWE PE12500601

Page 68: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

22

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 22

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

MV CUBICLE SM6

THERMOSTAT,0 – 60C,230V MG (Vorion) 08998

SCHNEIDER RIYADH INDUSTRIAL CITY 2

SPRING RETURN SELECTOR SW., 3 – pos, 2 no, STD. HDLE

Telemecanique XB4BD53

ADD – ON N.O. SWITCH Telemecanique ZBE101 ADD – ON N.O. SWITCH Telemecanique ZBE101 CT : 17.5/38/95kV, 1k=21kA/1sec. MG PE12500201 CT CORE 1: 200 – 400/5A, 15 – 30VA, CL 0.5 CT CORE 2: 200 – 400/5A, 7.5 – 15VA, CL. 5P10 CT : 17.5/38/95kV, 1k=21kA/1sec. MG PE12500201 CT CORE 1: 200 – 400/5A, 15 – 30VA, CL 0.5 CT CORE 2: 200 – 400/5A, 7.5 – 15VA, CL. 5P10 CT : 17.5/38/95kV, 1k=21kA/1sec. MG PE12500201 CT CORE 1: 200 – 400/5A, 15 – 30VA, CL 0.5 CT CORE 2: 200 – 400/5A, 7.5 – 15VA, CL. 5P10 HEATING RESISTOR, 50W, 220V AC MG (DOITD) 3736436 LED PILOT LIGHT, GREEN, 24 – 130VDC, STYLE 4

Telemecanique XB4BVBG33

CAPACITIVE VOLT INDICATOR MG (CDM) 59903 ADD – ON CONTACT, 1nc Telemecanique ZB2BE102 ILLUMINATED PB BODY, 400V AC, 1nc Telemecanique ZB2BW061 ILLUMINATED P.B. HEAD, RED Telemecanique ZB2BW343 AUX. RELAY 4c/o, 110VDC Telemecanique RXM4AB2FD AUX. RELAY 4c/o, 110VDC Telemecanique RXM4AB2FD STAY – PUT SELECTOR SW., 2 POS., w/ KEY Telemecanique XB4BG41

Page 69: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

23

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 23

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

MV CUBICLE SM6

ADD – ON N.O. SWITCH Telemecanique ZBE101

SCHNEIDER RIYADH INDUSTRIAL CITY 2

ADD – ON N.C. SWITCH Telemecanique ZBE102 ADD – ON N.C. SWITCH Telemecanique ZBE102 POWER METER PM810 Square – D Florence PM810 IM500 DISCON. w/ CI2 MECH, 630A 17.5kV, 21kA/1sec, (Inc. Cub) MG (CTC) 3985941A

MINIATURE CB, 2A, 2P, 230/400VAC, C – CURVE MG (Vorion) 24332

AUX. SWITCH 1C/O CONTACTS MG (Vorion) 26924 AUX. SWITCH 1C/O CONTACTS MG (Vorion) 26924 ALARM SWITCH MG (Vorion) 26927 MINIATURE CB, 6A, 2P, 500VDC, C – CURVE MG (Vorion) MGN61526

LED PILOT LIGHT, RED, 24 – 130VDC, STYLE 4 Telemecanique XB4BVBG43

TERMINAL WEMID DARK BEIGE, 800V 41A, 6sq.mm Weidmuller 1020200000

TERMINAL WEMID DARK BEIGE, 800V 41A, 6sq.mm Weidmuller 1020200000

TERMINAL WEMID DARK BEIGE, 800V 41A, 6sq.mm Weidmuller 1020200000

TERMINAL WEMID DARK BEIGE, 1000V 57A, 10sq.mm Weidmuller 1020300000

TERMINAL WEMID DARK BEIGE, 800V 41A, 6sq.mm Weidmuller 1020200000

TERMINAL WEMID DARK BEIGE, 800V 41A, 6sq.mm Weidmuller 1020200000

Page 70: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

24

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 24

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

MV CUBICLE SM6

TERMINAL WEMID DARK BEIGE, 1000V 57A, 10sq.mm Weidmuller 1020300000

SCHNEIDER RIYADH INDUSTRIAL CITY 2

SLIDE LINK TB DISCON., 500V, 41A, 6sq.mm Weidmuller 105920000 SLIDE LINK TB DISCON., 500V, 41A, 6sq.mm Weidmuller 105920000 CURRENT TEST BLOCK, 4P Entrelec CCEVA16662520 VOLTAGE TEST BLOCK, 4P Entrelec TCEC4A16688922 TERMINAL WEMID DARK BEIGE, 1000V 57A, 10sq.mm Weidmuller 1020300000

THERMOSTAT, 0 – 60C, 230V MG (Vorion) 08998 HEATING RESISTOR, 50W, 220V AC MG (DOITD) 3736436 LV FUSE, 10A MG (CTC) 25574919 SWITCH DISCONNECTING FUSE MG (CTC) 9115658 MV FUSE, 6.3A, 24kV, L=442mm MG (DIPS) 51006538M0 MV FUSE, 6.3A, 24kV, L=442mm MG (DIPS) 51006538M0 MV FUSE, 6.3A, 24kV, L=442mm MG (DIPS) 51006538M0 ADD – ON CONTACT, 1nc. Telemecanique ZB2BE102 ILLUMINATED PB BODY, 400V AC, 1no Telemecanique ZB2BW061 ILLUMINATED P.B. HEAD, RED Telemecanique ZB2BW343 DIGITAL MULTI METER, Vx : 190 – 260VAC ENTES K716740003 CM DISC. SW., 50A, 17.5kV, 21kA/1sec, (Inc. Cub) MG (CTC) 3985973A

MINIATURE CB, 2A, 2P, 230/400VAC, C – CURVE MG (Vorion) 24332

AUX. SWITCH 1C/O CONTACTS MG (Vorion) 26924

Page 71: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

25

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 25

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

MV CUBICLE SM6

AUX. SWITCH 1C/O CONTACTS MG (Vorion) 26924

SCHNEIDER RIYADH INDUSTRIAL CITY 2

ALARM SWITCH MG (Vorion) 26927 MINIATURE CB, 6A, 2P, 500VDC, C – CURVE MG (Vorion) MGN61526

AUXILLARY CONTACT BLOCK MG (CTC) 877942Q1 VOLTAGE TFO. 17.5kV, 13.8kV/r3, 110V/r3, 50VA, CL. 0.5 MG (CTC) VTJBS4B21F40

VOLTAGE TFO. 17.5kV, 13.8kV/r3, 110V/r3, 50VA, CL. 0.5 MG (CTC) VTJBS4B21F40

VOLTAGE TFO. 17.5kV, 13.8kV/r3, 110V/r3, 50VA, CL. 0.5 MG (CTC) VTJBS4B21F40

TERMINAL WEMID DARK BEIGE, 800V, 41A, 6 sq.mm Weidmuller 1020200000

TERMINAL WEMID DARK BEIGE, 800V, 41A, 6 sq.mm Weidmuller 1020200000

TERMINAL WEMID DARK BEIGE, 800V, 41A, 6 sq.mm Weidmuller 1020200000

VOLTAGE TEST BLOCK, 4P Entrelec TCEC4A16688922 TERMINAL WEMID DARK BEIGE, 800V, 41A, 6 sq.mm Weidmuller 1020200000

Current Transd, DI125, 1PH, 4.20mA,CT 5A, VX=80 – 276VAC/DC CEWE PE12500601

THERMOSTAT, 0 – 60C, 230V MG (Vorion) 08998 SPRING RETURN SELECTOR SW., 3 – pos, 2 no, STD. HDLE. Telemecanique XB4BD53

ADD – ON N.O. SWITCH Telemecanique ZBE101

Page 72: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

26

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 26

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

MV CUBICLE SM6

ADD – ON N.O. SWITCH Telemecanique ZBE101

SCHNEIDER RIYADH INDUSTRIAL CITY 2

CURRENT TRANSFORMER, 24/50/125kV, 25kA/1sec. MG (CTC) 3731105

CT CORE 1: 200 – 400/5A, 30VA, CL. 0.5 FS10

CT CORE 1: 200 – 400/5A, 7.5VA, CL.5P15, 15VA, CL. 5P10

CURRENT TRANSFORMER, 24/50/125kV, 25kA/1sec. MG (CTC) 3731105

CT CORE 1: 200 – 400/5A, 30VA, CL. 0.5 FS10

CT CORE 1: 200 – 400/5A, 7.5VA, CL.5P15, 15VA, CL. 5P10

CURRENT TRANSFORMER, 24/50/125kV, 25kA/1sec. MG (CTC) 3731105

CT CORE 1: 200 – 400/5A, 30VA, CL. 0.5 FS10

CT CORE 1: 200 – 400/5A, 7.5VA, CL.5P15, 15VA, CL. 5P10

HEATING RESISTOR, 50W, 220V AC MG (DOITD)\ 3736436 MES114 INPUT/OUTPUT BOARD, 24 – 250VDC MG (PCR/PDM) 59646

SEPAM T40 RELAY, CT: 1A or 5A, 24 – 250VDC, 100 – 240VAC MG (PCR/PDM) S10MDT40J33TNT

LED PILOT LIGHT, GREEN, 24 – 130VDC, STYLE 4 Telemecanique XB4BVBG33

CAPACITIVE VOLT INDICATOR MG (CDM) 59903 ADD – ON CONTACT, 1nc Telemecanique ZB2BE102 ILLUMINATED PB BODY, 400V AC, 1no Telemecanique ZB2BW061

Page 73: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

27

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 27

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

MV CUBICLE SM6

ILLUMINATED P.B. HEAD, RED Telemecanique ZB2BW343

SCHNEIDER RIYADH INDUSTRIAL CITY 2

PROTECTION MODULE, 6 TO 250VDC DIODE Telemecanique RXM040W AUX. RELAY 4c/o, 6A, 110VDC Telemecanique RXM4AB2FD BASE SOCKET FOR RXM4 SEPARATE Telemecanique RXZE2S114M PROTECTION MODULE, 6 TO 250VDC DIODE Telemecanique RXM040W AUX. RELAY 4c/o, 6A, 110VDC Telemecanique RXM4AB2FD BASE SOCKET FOR RXM4 SEPARATE Telemecanique RXZE2S114M PROTECTION MODULE, 6 TO 250VDC DIODE Telemecanique RXM040W AUX. RELAY 4c/o, 6A, 110VDC Telemecanique RXM4AB2FD BASE SOCKET FOR RXM4 SEPARATE Telemecanique RXZE2S114M PROTECTION MODULE, 6 TO 250VDC DIODE Telemecanique RXM040W AUX. RELAY 4c/o, 6A, 110VDC Telemecanique RXM4AB2FD BASE SOCKET FOR RXM4 SEPARATE Telemecanique RXZE2S114M AUX. RELAY 4c/o, 6A, 110VDC Telemecanique RXM4AB2FD AUX. RELAY 4c/o, 6A, 110VDC Telemecanique RXM4AB2FD AUX. RELAY 4c/o, 6A, 110VDC Telemecanique RXM4AB2FD AUX. RELAY 4c/o, 6A, 110VDC Telemecanique RXM4AB2FD STAY – PUT SELECTOR SW., 2 POS., w/ KEY Telemecanique XB4BG41 ADD – ON N.O. SWITCH Telemecanique ZBE101 ADD – ON N.C. SWITCH Telemecanique ZBE102 ADD – ON N.C. SWITCH Telemecanique ZBE102 ADD – ON N.C. SWITCH Telemecanique ZBE102

Page 74: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

28

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 28

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

MV CUBICLE SM6

POWER METER PM810 Square – D Florence PM810

SCHNEIDER RIYADH INDUSTRIAL CITY 2

SP1 CB, 630A, 3P, FIXED TYPE, 17.5/38/95kV, 21kA/1s, MG (DIPS) PE12501801

M=110VDC, YF=110VDC, Y01=110VDC DOWNSTREAM EARTHING SWITCH FOR DM1 MG (CTC) ESDM1 AUX. CONTACT BLOCK, 2 no, 2nc MG (CTC) 3985252A IM500 DISCON. w/ CI1 MECH, 630A, 17.5kV, 21kA/1sec, (Inc. Cub) MG (CTC) 3985941A

MINIATURE CB, 2A, 2P, 230/400VAC, C – CURVE MG (Vorion) 24332

AUX. SWITCH 1C/O CONTACTS MG (vorion) 26924 AUX. SWITCH 1C/O CONTACTS MG (vorion) 26924 ALARM SWITCH MG (Vorion) 26927 MINIATURE CB, 6A, 2P, 500VDC, C – CURVE MG (Vorion) MGN61526 AUX. SWITCH 1C/O CONTACTS MG (Vorion) 26924 ALARM SWITCH MG (Vorion) 26927 MINIATURE CB, 6A, 2P, 500VDC, C – CURVE MG (Vorion) MGN61526 LED PILOT LIGHT, RED, 42 – 130VDC, STYLE 4 Telemecanique XB4BVBG43 SURGE ARRESTER AREVA DDE9808005 SURGE ARRESTER AREVA DDE9808005 SURGE ARRESTER AREVA DDE9808005 TOROIDAL TFO., 200mm DIA MG (PCR/PDM) 59636 TERMINAL WEMID DARK BEIGE, 800V, 41A, 6 sq.mm Weidmuller 1020200000

Page 75: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

29

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 29

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source

MV CUBICLE SM6

TERMINAL WEMID DARK BEIGE, 800V, 41A, 6 sq.mm Weidmuller 1020200000

SCHNEIDER RIYADH INDUSTRIAL CITY 2

TERMINAL WEMID DARK BEIGE, 800V, 41A, 6 sq.mm Weidmuller 1020200000

TERMINAL WEMID DARK BEIGE, 800V, 41A, 6 sq.mm Weidmuller 1020200000

TERMINAL WEMID DARK BEIGE, 800V, 41A, 6 sq.mm Weidmuller 1020200000

TERMINAL WEMID DARK BEIGE, 800V, 41A, 6 sq.mm Weidmuller 1020200000

TERMINAL WEMID DARK BEIGE, 1000V, 57A, 10 sq.mm Weidmuller 1020300000

COMM. INTERFACE MODULE, 12/24VDC, RS485, 2 – WIRE MG (PCR/PDM) 59642

CURRENT TEST BLOCK, 4P Entrelec CCEVA16662520 VOLTAGE TEST BLOCK, 4P Entrelec TCEC4A16688922 CURRENT TEST BLOCK, 4P Entrelec CCEVA16662520 VOLTAGE TEST BLOCK, 4P Entrelec TCEC4A16688922 TERMINAL WEMID DARK BEIGE, 1000V, 57A, 10 sq.mm Weidmuller 1020300000

LED PILOT LIGHT, YELLOW, 24 – 130VDC, STYLE 4 Telemecanique XB4BVBG53

.

Page 76: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

30

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 30

Panel Ref Replacement Part Details Part Identification Manufacturer Local Source 3.4 Wiring Devices

20A SP 1W Switch Module MK/56891 BLK 20A SP 2W Switch Module MK/56892 BLK 1G W/P Enclosure single switch IP65 MK/56420 WHI 13A 1G Switched Socket Outlet MK/56486 WHI 13A 2G Switched Socket Outlet MK/56482 WHI Modular Grid Plus enclosure W/P IP56 MK/56423 GRY Data Module,EURO,RJ45,CAT5E,UTP 1Module MK/K5845 WHI

3 PIN Socket 32A MK/9762 BLU 20A DP 1W Switch with Neon- 1M MK/K4896N WHI 1 M Grid plus front plate with mounting frame MK/K24331 WHI

13A 2G Switched Socket Outlet MK/56482 WHI Industrial Plug 16A 3P+N+E-IP44 MK/K9015 RED INDS Surf SKT 16A 3P+N+E-IP44 MK/K9215 RED Industrial Plug IP67 32A 3P+N+E-380/415V MK/K9056 RED Angle Surface Socket Outlet 32A 3P+N+E-IP67 20A DP 1w switch with neon-1M MK/K9766 RED

4M Euro Datacom Front Plate MK/K24184 WHI 20A 1G 2 way SP Switch K24371 WHI W 20A Intermediate switch-1 M K4893 WHI 1M Grid Plus Front Plate with Mounting Frame K24331 WHI

13A 1G DP Switch Socket outlet,DE K24357 WHI W

Page 77: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE MANUAL

Building Ref

1.2.1

Vol

EM

Sect

3

Page

31

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Equipment Schedules Page 31

PANEL REF Replacement Part Details Part Identification MANUFACTURER LOCAL SOURCE 13A 2G SP Switch Socket outlet,DE K24347 WHI W

13A 1G DP switch Socket Outlet,DE K24357 WHI W W/P 13A,Socket Unswitched,1G,white,IP56 56480 WHI 32A 1Gang DP with Neon K24305 WHI W 20A DP 1w switch with Neon-1M K4896N WHI 16A Cord Outlet-1M K4886 WHI 2M Grid Plus Front Plate with Mounting Frame K24332 WHI

1M Euro DataCom FrontPlate K24181 WHI 4M Euro Datacom FrontPlate K24184 WHI

Page 78: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

4

Page

1

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Maintenance Documentation Page 1

SECTION 4

MAINTENANCE DOCUMENTATION

LIST OF CONTENTS

Section Content Page

4.1 Installers Details 2 4.2 Suppliers Details 3 4.3 Reference Section from Project Specification 4 4.4 Maintenance Service Agent details 5 4.5 Maintenance Service Contracts 6 4.6 Warranties & Bonds 7

Page 79: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

4

Page

2

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Maintenance Documentation Page 2

SECTION 4

MAINTENANCE DOCUMENTATION 4.1 INSTALLERS DETAILS Installers name Address Telephone No. Contact Name MV Installation Drake & Skull +966598589082 Mr. Alaa Azizi Transformer Installation Drake & Skull +966598589082 Mr. Alaa Azizi Capacitor Installation Drake & Skull +966598589082 Mr. Alaa Azizi ATS Installation Drake & Skull +966598589082 Mr. Alaa Azizi Panel Boards Drake & Skull +966598589082 Mr. Alaa Azizi UPS System Drake & Skull +966598589082 Mr. Alaa Azizi Lighting System Drake & Skull +966598589082 Mr. Alaa Azizi

Page 80: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

4

Page

3

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Maintenance Documentation Page 3

4.2 SUPPLIERS DETAILS Suppliers name Address Telephone No. Contact Name

MV Panels

Schneider Electric +96612651515 & +966505100216 Uday Kamath

Transformers

Schneider Electric +96612651515 & +966505100216 Uday Kamath

Capacitor Bank

Aqesa +96614747300 Ext: 222 Mohammad Ali Sabbidin

ATS

Aqesa +96614747300 Ext: 222 Mohammad Ali Sabbidin

MDB MESCO +966507257497 Jefferey Almario

PP/ LP/ MCC/ DP/ DLP/ EDP/ EPP/ ESDP/ UDP/ UPP/ USDP/ EMCP/ELP

MOTS +96612653701

+96612653702 +966542923263

Ghazanfar Ali Yaqub

ECB

CEAG/SAUD LIGHTING +96612651010 Mr.Fahad Al-Hobayb

EIB

HONEYWELL +966504151560 Mr. Mohammed Al-Saadi

Page 81: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

4

Page

4

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Maintenance Documentation Page 4

4.3 REFERENCE SECTION FROM PROJ ECT SPECIFICATION

Product Name Project Specification Name Specification Section No.

MV Switchgear MVSG 16341 Transformers MV Transformers 16350 Power Panels Panel Boards 16442 Motor Control Panels MCC 16482 Capacitors Power Factor Correction Capacitor 16280 Transfer Switches ATS 16415 Static Uninterruptible Power Supply UPS 16264 Central Battery System CBS 16265 Circuit Breakers Enclosed switches & Circuit Breakers 16410 Lighting Interior/Emergency / Exterior Lighting 16511 Lighting Dimming Controls 16570 Lighting controls Lighting Controls Devices 16145 Switch Boards Switch Boards 16441 Earthing System Grounding and Bonding 16060

Page 82: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

4

Page

5

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Maintenance Documentation Page 5

4.4 MAINTENANCE SERVICE AGENT DETAILS Product Name Maintenance Service Offered by Details Offered

Page 83: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

4

Page

6

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Maintenance Documentation Page 6

4.5 MAINTENANCE SERVICE CONTRACTS

For copies of the Maintenance Service Contracts along with the Service Agents contact details please refer to the following Table

Equipment Maintenance Agreement

with (Name) Telephone No.

Contact details of Service Agents

Page 84: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

4

Page

7

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Maintenance Documentation Page 7

4.6 WARRANTIES & BONDS

Copies of the following warranties and bonds are attached at the end of this section. Equipment Manufacturer

Page 85: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

5

Page

1

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Test & Commissioning Records Page 1

SECTION 5

TEST CERTIFICATES & COMMISSIONING REPORTS

LIST OF CONTENTS* Item No. Title 5.1 MV DISTRIBUTION NETWORK 5.1.1 Medium Voltage (MV) Switchgear 5.1.2 Medium Voltage (MV) Panel board 5.1.3 POWER TRANSFORMER 5.1.4 Medium Voltage Cable 5.1.5 Inner Buildings Sub Station 5.2 LV DISTRIBUTION NETWORK 5.2.1 Low Voltage (LV) Switchgear 5.2.2 Low Voltage (LV) Bus Duct 5.2.3 Low Voltage Cables and Wires 5.2.4 Switchboards 5.2.5 Automatic Transfer Switch 5.2.6 Disconnect Switch 5.2.7 Main Distribution Boards 5.2.8 Power Factor Correction (Capacitor) 5.2.9 External Power Delivery Packages 5.3 UPS EQUIPMENT 5.3.1 Uninterruptible Power Supply 5.3.2 Central Battery System 5.3.3 Battery 5.3.4 Rectifier/Charger 5.4 SMALL POWER 5.4.1 Lighting and Wiring Devices 5.4.2 Emergency and Exit Lighting 5.5 LIGHTING CONTROL SYSTEM 5.5.1 EIB Control system 5.6 EARTHING SYSTEM 5.6.1 Earthing System 5.7 LIGHTNING PROTECTION SYSTEM 5.7.1 Lightning Protection 5.8 VERTICAL TRANSPORTATION SYSTEM 5.8.1 Elevators

*The Commissioning Forms which mentioned are Templates; the Test Certificates & Commissioning Reports will be submitted in Separate Binder/ Booklet.

Page 86: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

6

Page

1

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Manufacturers Literature Page 1

SECTION 6

Manufac ture r’s Lite ra ture

LIST OF CONTENTS

Section Equipment Book n° Publication Ref.

6.1 MEDIUM VOLTAGE SYSTEM

6.1.1 MVSG EMVSG A051-100

6.1.1.1 Schneider

6.1.2 Power Transformer A052-100

6.1.2.1 Schneider 6.1.3 MV Battery Charger A053-100

6.1.3.1 Schnieder/AEES

6.1.4 XLPE Cable 6.1.4.1 RIYADH CABLE A054-100 6.1.4.2 MESC/NJC A054-101 6.2 LOW VOLTAGE SYSTEM/PANELBOARDS

6.2.1 QC Capacitor Bank

6.2.1.1 EATON CORP/AQESA A055-100

6.2.1.2 KEMET/ARCOTRONICS A055-101

6.2.1.3 ADWAN A055-102

6.2.1.4 SCHNEIDER ELECTRIC A055-103

6.2.2 ATS

6.2.2.1 EATON CORP/AQESA A056-100

6.2.2.2 EMERSON/ASCO A056-101

6.2.2.3 ADWAN A056-102

6.2.3 MDB/EMDB

6.2.3.1 MESCO A057-100

6.2.3.2 EATON CORP/AQESA A057-101

6.2.4 DLP

6.2.4.1 MOTS A060-100

6.2.4.2 SETRAA AL-AMAL A060-101

6.2.4.3 EATON CORP/AQESA A060-102

6.2.4.4 ABB/HONEYWELL A060-103

6.2.4.5 MESCO A060-104

6.2.4.6 ECO A060-105

6.2.5 DP

6.2.5.1 MOTS A061-100

6.2.5.2 MESCO A061-101

Page 87: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

6

Page

2

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Manufacturers Literature Page 2

6.2.5.3 RFPB/SCHNEIDER ELECTRIC A061-102

6.2.5.4 SETRAA AL-AMAL A061-103

6.2.5.5 ECO A061-104

6.2.6 ECB

6.2.6.1 CEAG/Saudlighting A062-100

6.2.6.2 RFPB/SCHNEIDER A062-101

6.2.6.3 SETRAA/AL AMAL A062-102

6.2.6.4 MESCO/COOPER A062-103

6.2.6.5 COOPER A062-104

6.2.7 EDP

6.2.7.1 MOTS A063-100

6.2.7.2 MESCO A063-101

6.2.7.3 RFPB/SCHNEIDER A063-102

6.2.7.4 SETRAA/AL AMAL A063-103

6.2.7.5 HONEYWELL A063-104

6.2.7.6 INARA A063-105

6.2.7.7 ECO A063-106

6.2.8 ELP

6.2.8.1 MOTS A066-100

6.2.8.2 MESCO A066-101

6.2.8.3 RFPB/SCHNEIDER A066-102

6.2.8.4 SETRAA/AL AMAL A066-103

6.2.8.5 INARA A066-104

6.2.8.6 HONEYWELL A066-105

6.2.8.7 ECO A066-106

6.2.9 EIB

6.2.9.1 HONEYWELL A065-100

6.2.9.2 ABB A065-101

6.2.9.3 ECO A065-102

6.2.10 EMCP

6.2.10.1 MOTS A068-100

6.2.10.2 MESCO A068-101

6.2.10.3 RFPB/SCHNEIDER A068-102

6.2.10.4 SETRAA/AL AMAL A068-103

6.2.10.5 HONEYWELL A068-104

6.2.10.6 SELCO A068-105

6.2.10.7 ECO A068-106

6.2.11 EMCC

6.2.11.1 MOTS A070-100

6.2.11.2 MESCO A070-101

Page 88: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

6

Page

3

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Manufacturers Literature Page 3

6.2.11.3 RFPB/SCHNEIDER A070-102

6.2.11.4 SETRAA/AL-AMAL A070-103

6.2.11.5 HONEYWELL A070-104

6.2.11.6 SELCO A070-105

6.2.11.7 LOGSTRUP A070-106

6.2.11.8 ECO A070-107

6.2.12 MCC

6.2.12.1 MOTS A069-100

6.2.12.2 MESCO A069-101

6.2.12.3 RFPB/SCHNEIDER A069-102

6.2.12.4 SETRAA/AL-AMAL A069-103

6.2.12.5 SELCO A069-104

6.2.12.6 LOGSTRUP A069-105

6.2.12.7 ECO A069-106

6.2.13 EPP

6.2.13.1 MOTS A071-100

6.2.13.2 MESCO A071-101

6.2.13.3 RFPB/SCHNEIDER A071-102

6.2.13.4 SETRAA/AL-AMAL A071-103

6.2.13.5 HONEYWELL A071-104

6.2.13.6 ECO A071-105

6.2.14 ESDP

6.2.14.1 MOTS A072-100

6.2.14.2 RFPB/SCHNEIDER A072-101

6.2.14.3 MESCO A072-102

6.2.14.4 SETRAA/AL-AMAL A072-103

6.2.15 LP/PP

6.2.15.1 MOTS A074-100

6.2.15.2 MESCO A074-101

6.2.15.3 RFPB/SCHNEIDER A074-102

6.2.15.4 SETRAA/AL-AMAL A074-103

6.2.15.5 ECO A074-104

6.2.16 UDP

6.2.16.1 MOTS A076-100

6.2.16.2 MESCO A076-101

6.2.16.3 RFPB/SCHNEIDER A076-102

6.2.16.4 SETRAA/AL-AMAL A076-103

6.2.16.4 ECO A076-104

6.2.17 UPP

6.2.17.1 MOTS A078-100

Page 89: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

6

Page

4

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Manufacturers Literature Page 4

6.2.17.2 MESCO A078-101

6.2.17.3 RFPB/SCHNEIDER A078-102

6.2.17.4 SETRAA/AL-AMAL A078-103

6.2.17.5 ECO A078-104

6.2.18 UPS

6.2.18.1 MOTS/CHLORIDE A079-100

6.2.18.2 LIEBERT/EMERSON A079-101

6.2.18.3 RFPB/CHOLRIDE A079-102

6.2.18.4 SETRA-AL AMAL A079-103

6.2.19 USDP

6.2.19.1 MOTS A080-100

6.2.19.2 MESCO A080-101

6.2.19.3 RFPB/SCHNEIDER A080-102

6.2.19.4 SETRAA/AL-AMAL A080-103

6.2.19.5 ECO A080-104

6.2.20 LRP

6.2.20.1 ABB A082-100

6.2.20.2 HONEYWELL A082-101

6.3 LIGHTING SYSTEM 6.3.1 ALADABRA LIGHTING 6.3.2 ALISON BERGER 6.3.3 ALKCO

6.3.4 ARTEMIDE

6.3.5 AUDREY PENDANT

6.3.6 AXO LIGHT

6.3.7 BEGA

6.3.8 BEGA NARDEEN

6.3.9 BELFER LIGHTING

6.3.10 BOCCI LIGHTING

6.3.11 BOOM (3.7.5)

6.3.12 BRUCK LIGHTING

6.3.13 CEAG

6.3.14 COOPER LIGHTING

6.3.15 CORELITE

6.3.16 CRENSHAW LIGHTING

6.3.17 CSL LIGHTING

6.3.18 DELRAY

6.3.19 DELTA LIGHT

6.3.20 DESIGNPLAN-UK

6.3.21 ECOSTA LIGHTING

6.3.22 ECO-GREEN LIGHTING U.S.A.

6.3.23 EDISON PRICE

Page 90: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

6

Page

5

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Manufacturers Literature Page 5

6.3.24 ERCO

6.3.25 ETAP

6.3.26 EUREKA LIGHTING

6.3.27 EUROFASE LIGHTING

6.3.28 FLOS

6.3.29 FOCAL POINT LIGHTING

6.3.30 FONTES

6.3.31 FOSCARINI LIGHTING

6.3.32 GLASS ILLUMINATIONS

6.3.33 GOCCIA

6.3.34 GVA LIGHTING

6.3.35 HE WILLIAMS LIGHTING

6.3.36 HAMPSTEAD LIGHTING

6.3.37 IGUZZINI 6.3.38 I-LED

6.3.39 INDUSTRIES

6.3.40 KANDIL

6.3.41 KENNAL LIGHTING

6.3.42 KKDC

6.3.43 KURT VERSEN

6.3.44 LAMURRINA

6.3.45 LBL LIGHTING

6.3.46 LIGHTOLIER LIGHTING

6.3.47 LOUIS POULSEN

6.3.48 LUCIFER LIGHTING

6.3.49 MENVIER

6.3.50 MEYER

6.3.51 MOOOI LIGHTING

6.3.52 MP LIGHTING

6.3.53 MURANO DUE

6.3.54 NARDEEN & BEGA SERIES

6.3.55 NEIDHART

6.3.56 NEONCIER

6.3.57 NIPPO

6.3.58 NORLIGHT-PROGETTOLUCE

6.3.59 PARAMOUNT INDUSTRIES

6.3.60 PARANDINA LIGHTING

6.3.61 PEERLESS LIGHTING

6.3.62 PHILIPS

6.3.63 PRISMA

6.3.64 RAMBUSCH

6.3.65 REGGIANI

Page 91: 3- Electrical Maintenance (EM)

OPERATING SYSTEMS AND EQUIPMENT MAINTENANCE

MANUAL

Building Ref

1.2.1

Vol

EM

Sect

6

Page

6

ELECTRICAL HIGH

CURRENT

College of Arts, Humanities & Sciences (West Building)

Manufacturers Literature Page 6

6.3.66 RSA LIGHTING

6.3.67 RZB

6.3.68 SAINT TROPEZ BOUTIQUE

6.3.69 SANTA AND COLE

6.3.70 SAUDI LIGHTING

6.3.71 SELUX

6.3.72 SILL

6.3.73 SIMES

6.3.74 SISTEMALUX

6.3.75 SITECO

6.3.76 SLC

6.3.77 SLIM MAKE

6.3.78 SOLVANTI

6.3.79 STONEGATE DESIGNS

6.3.80 STUDIO LAWRENCE

6.3.81 TARGETTI EXTERIEUR

6.3.82 THORN

6.3.83 TOKISTAR LIGHTING

6.3.84 TOM DIXON

6.3.85 TRANSLITE

6.3.86 TRILUX

6.3.87 VERPAN

6.3.88 VIBIA

6.3.89 WE-EF

6.3.90 ZUMTOBEL

6.4 LOW VOLTAGE SYSTEM/SMALL POWER

6.5 LIGHTNING PROTECTION AND GROUNDING SYSTEM