How Do you Migrate a WinAC MP Project from SIMATIC WinCC flexible 2008 SP3 to SIMATIC WinCC (TIA Portal) V11/V12?

WinCC V11/V12

FAQ April 2013

Question

2 WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren

Version 1.1, Entry ID: 65766912

This document is an entry from the Siemens Industry Online Support. The following Terms of Use apply (www.siemens.com/terms_of_use). The following link takes you directly to the download page of this document. http://support.automation.siemens.com/WW/view/en/65766912 Caution The functions and solutions described in this entry are mainly limited to the realization of the automation task. Please take into account furthermore that corresponding protective measures have to be taken up in the context of Industrial Security when connecting your equipment to other parts of the plant, the enterprise network or the Internet. For more information, please refer to entry ID 50203404. http://support.automation.siemens.com/WW/view/en/50203404

Question How do you migrate a SIMATIC WinAC MP project from SIMATIC WinCC flexible 2008 SP3 to SIMATIC WinCC (TIA Portal) V11/V12?

Answer The instructions and notes listed in this document provide a detailed answer to this question.

Table of Contents

WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren Version 1.1, Entry ID: 65766912 3

Table of Contents 1 Introduction ........................................................................................................ 4 2 Preparing HMI Device for the Migration .......................................................... 5

2.1 Updating operating system................................................................... 5 2.2 Transferring option ............................................................................... 6

3 Migrating a Project ............................................................................................ 7

3.1 Migrating STEP 7 and WinCC flexible project...................................... 7 3.2 Final check of the migrated components ............................................. 9

4 Additional Checks after the Migration ........................................................... 10

4.1 Checking the IP address (HMI device) ............................................... 10 4.2 Checking the standard images in the project library .......................... 11 4.3 Checking the provided system functions ............................................ 13 4.4 Checking the provided HMI tags ........................................................ 14

5 Downloading the Project................................................................................. 15

5.1 Downloading the entire project to the device ..................................... 15 5.2 Transferring HMI project separately ................................................... 20

6 Transferring STEP 7 Program Blocks ........................................................... 21

6.1 Transferring program blocks individually ............................................ 21 6.2 Transferring program blocks completely ............................................ 22

7 Online and Diagnostics ................................................................................... 23

7.1 Establishing online connection ........................................................... 23 7.2 Diagnostic buffer ................................................................................ 24 7.3 Task card “Online tools" ..................................................................... 25

1 Introduction

4 WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren

Version 1.1, Entry ID: 65766912

1 Introduction The following FAQ deal with the migration of SIMATIC WinAC MP projects (SIMATIC WinCC flexible 2008 SP3) to SIMATIC WinCC (TIA Portal) V11 SP2 Update 3 or newer. A migration of SIMATIC WinCC flexible 2008 SP3 projects is only possible from SIMATIC WinCC (TIA Portal) V11 SP2 Update 3.

Note Compatibility The SIMATIC MP377 Daylight 15" Touch operator panel is only supported with WinCC V12!

Objective of the migration After the migration of your SIMATIC WinAC MP project, you no longer edit it with SIMATIC WinCC flexible but with SIMATIC WinCC (TIA Portal).

Requirements and supporting software versions The following requirements must be satisfied and the following software has to be installed:

• All required software versions (TIA Portal, WinCC flexible, STEP 7, etc.) are centrally installed on an engineering station.

Figure 1-1

• The following TIA Portal components are required (min. WinCC Comfort):

Figure 1-2

2 Preparing HMI Device for the Migration

WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren Version 1.1, Entry ID: 65766912 5

2 Preparing HMI Device for the Migration 2.1 Updating operating system

Prerequisite The WinCC project and the WinCC panel settings have to be saved in the system settings of the operator panel via the "Backup/Restore" menu command before updating.

Instruction In order to update the operating system on the operator panel, proceed as follows: 1. Open the TIA Portal. 2. Select the HMI operator panel that is to be updated in the project navigation. 3. In order to update the operating system of the HMI operator panel, select the “Update

operating system" command in "Online > HMI device maintenance”. SIMATIC ProSave opens. The "OS Update" tab is visible.

Figure 2-1

4. Click the “Update OS” button.

The respective files are transferred to the operator panel. The operator panel has to be in transfer mode.

Result The operator panel is automatically restarted once the operator panel is updated. The previously saved device configuration is automatically restored on the operator panel once the operating system has been updated.

Note Automatic update of the operating system

The full configuration (STEP 7 and HMI part) is downloaded via the “Extended download to device” dialog. This process carries out an automatic update of the operating system.

2 Preparing HMI Device for the Migration

6 WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren

Version 1.1, Entry ID: 65766912

2.2 Transferring option

Instruction To be able to transfer the WinAC MP 2008 (WinAC MP V4.1.1) option to the operator panel after updating the operating system, proceed as follows: 1. Open the TIA Portal. 2. Select the respective HMI operator panel in the project navigation. 3. Select the “Options" command in the “Online > HMI device maintenance” menu.

SIMATIC ProSave opens. The “Options" tab is visible. Figure 2-2

4. Select the respective option in the “Available options” box. 5. Transfer the option to the “Installed options” box with the help of the arrow button.

Note Comparing the transfer The options transfer can be compared with the options transfer in WinCC flexible.

3 Migrating a Project

WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren Version 1.1, Entry ID: 65766912 7

3 Migrating a Project 3.1 Migrating STEP 7 and WinCC flexible project

Instruction In order to migrate a STEP 7 project (with HMI project) to the TIA Portal, proceed as follows: 1. Open the TIA Portal. 2. Select the portal view. Figure 3-1

3. Select the "Migrate project" action. 4. To be able to accept the old WinAC MP hardware configuration to the TIA Portal,

enable the “Include hardware configuration” option box. Note If you are using WinCC V11 SP2, the “Exclude hardware configuration" option box has to be disabled in order to transfer the old WinAC MP hardware configuration to the TIA Portal.

5. In order to start the migration, click the “Migrate” button. The project is created and migrated.

Figure 3-2

3 Migrating a Project

8 WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren

Version 1.1, Entry ID: 65766912

Result The following message is displayed after a successful migration. Figure 3-3

Confirm the message with the "OK" button. Detail of the migration process can be viewed via the migration protocol. The protocol includes e.g. information on the number of tags and S7 station names.

3 Migrating a Project

WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren Version 1.1, Entry ID: 65766912 9

3.2 Final check of the migrated components

After successful project migration, you should check the following subcomponents for their completeness in the TIA Portal project:

• HMI components Figure 3-4

• WinAC MP components

Figure 3-5

4 Additional Checks after the Migration

10 WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren

Version 1.1, Entry ID: 65766912

4 Additional Checks after the Migration 4.1 Checking the IP address (HMI device) After checking all subcomponents, you can change the IP address of the respective HMI device and if required, change it. Select the respective device in the device view, in order to display the IP address in the inspection window. Figure 4-1

4 Additional Checks after the Migration

WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren Version 1.1, Entry ID: 65766912 11

4.2 Checking the standard images in the project library

The transferred option WinAC MP 2008 in chapter “Transferring option” (page 10) offers you two preconfigured standard images in WinCC V11 SP2, as was already the case with WinCC flexible:

● WinAC_MP_Home

Figure 4-2

4 Additional Checks after the Migration

12 WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren

Version 1.1, Entry ID: 65766912

● WinAC_MP_Tuning

Figure 4-3

The preconfigured standard images are stored in a global library. The provided images are already switched with internal tags and respective WinAC MP system functions. The "WinAC_MP_Tags" copy template is additionally available to you in WinCC V11 SP2. Figure 4-4

This copy template (WinAC_MP_Tags) is required, since the existing tag connections are not supported because of moving the preconfigured WinAC MP standard images to the respective TIA Portal project. They have to be moved separately first to a newly created tag table. The preconfigured WinAC MP standard images (Home Screen and Tuning Screen) are provided with internal tags by being moved to the new tag table. Due to this, all already existing WinAC MP system functions are supported.

4 Additional Checks after the Migration

WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren Version 1.1, Entry ID: 65766912 13

4.3 Checking the provided system functions

The WinAC MP system functions provided in the TIA Portal are already switched or connected with the two preconfigured WinAC MP images. Figure 4-5

4 Additional Checks after the Migration

14 WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren

Version 1.1, Entry ID: 65766912

4.4 Checking the provided HMI tags

The internally provided tags for WinAC MP in the TIA Portal are already internally switched or connected with the two preconfigured WinAC MP images. Figure 4-6

5 Downloading the Project

WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren Version 1.1, Entry ID: 65766912 15

5 Downloading the Project 5.1 Downloading the entire project to the device

Introduction After checking or adjusting the IP address, the complete software and hardware configuration (here: WinAC MP configuration and HMI project) can be loaded to the device. In this example, the fastest way is described. The hardware configuration of WinAC MP 2008 and the software components used (HMI project) are transferred via a download process to the HMI device.

Prerequisite ● The following transfer settings have to be made on the HMI device:

– Channel 2: Ethernet – Enable Channel “enabled" – Remote Control “enabled"

● The project was migrated. ● The project data is consistent. ● The device to be loaded is available via online access. ● The additional settings and the IP address of the respective HMI device have been

checked. ● The TIA Portal is open. ● The project view is open.

5 Downloading the Project

16 WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren

Version 1.1, Entry ID: 65766912

Instruction In order to load the project to the device, proceed as follows. 1. Select the device in the project navigation. Figure 5-1

2. Right click the selected element.

The context menu opens. Figure 5-2

3. Select the “All” option in the context menu in the “Load to device" submenu.

–If you have not yet established an online connection, the “Extended download to device" dialog opens and you first of all you have to select the interfaces via which you would like to create the online connection to the device.

5 Downloading the Project

WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren Version 1.1, Entry ID: 65766912 17

The hardware configuration of WinAC MP 2008 has to be loaded via the PG/PC interface "PN/IE”. Figure 5-3

5 Downloading the Project

18 WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren

Version 1.1, Entry ID: 65766912

–If you have already created an online connection, the “Load preview" dialog opens. In this dialog, you will be shown messages and actions required for loading. All project-specific data in the target device is deleted. All predefined modules (here: the WinAC MP) are centrally stopped or prepared for the download process. If you enable the “Overwrite all" option box, all already existing configuration data is overwritten in the target system (HMI device)! Figure 5-4

4. Click the “Load" or “Finish” button.

Result The selected project data is loaded to the device. A repeated input of the individual parameters or values is no longer necessary. The transfer path to the HMI device is permanently stored for other transfer processes in the system. The WinAC MP device is restarted. Afterwards the device is in RUN mode. Figure 5-5

5 Downloading the Project

WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren Version 1.1, Entry ID: 65766912 19

The loading process should be completed successfully. Based on the output compiler messages, warnings can be acquired fast and can be further processed. Figure 5-6

5 Downloading the Project

20 WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren

Version 1.1, Entry ID: 65766912

5.2 Transferring HMI project separately

Instruction In order to transfer the HMI project separately to the HMI device after the changes, proceed as follows: 1. Open the TIA Portal. 2 Open the project view. 3. Select the respective HMI device in the project navigation by right clicking it. Figure 5-7

4. Select the “Download to device > Software” command in the context menu.

Result All changes are subsequently transferred to the HMI device.

6 Transferring STEP 7 Program Blocks

WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren Version 1.1, Entry ID: 65766912 21

6 Transferring STEP 7 Program Blocks 6.1 Transferring program blocks individually

Introduction In this example, a data block 1 is newly added and transferred to the HMI device.

Instruction In order to add STEP 7 blocks and to load to the HMI device, proceed as follows: 1. Open the TIA Portal. 2 Open the project view. 3. Select the respective STEP 7 block in the project navigation by right clicking it. 4. Select the “Download to device > Software” command in the context menu.

Result The preview for loading is displayed. Additional information is displayed in this dialog, such as blocks that are not available online. Figure 6-1

6 Transferring STEP 7 Program Blocks

22 WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren

Version 1.1, Entry ID: 65766912

6.2 Transferring program blocks completely

Instruction In order to transfer all STEP 7 program blocks in one download process, proceed as follows: 1. Open the TIA Portal. 2 Open the project view. 3. Select the respective WinAC MP device in the project navigation by right clicking it. Figure 6-2

4. Select the “Download to device > Software (all blocks)” command in the context menu.

Result You have successfully migrated your WinAC MP project to TIA Portal V11 and transferred it to the HMI device.

7 Online and Diagnostics

WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren Version 1.1, Entry ID: 65766912 23

7 Online and Diagnostics 7.1 Establishing online connection

Introduction The TIA Portal provides different diagnostic possibilities. With the “Online & diagnostics” action in the project navigation, you can call different diagnostic information from the overall system with the help of an online connection.

Instruction In order to determine diagnostic information, proceed as follows: 1. Open the TIA Portal. 2 Open the project view. 3. Open the respective device folder in the project navigation. 4. Select the “Online & diagnostics" action. The “Online accesses” dialog opens on the

desktop. Figure 7-1

5. Set the interface parameters. 6. In order to start an online connection, select the “Go online” button.

Result Once the online connection is established, you have different diagnostic options.

7 Online and Diagnostics

24 WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren

Version 1.1, Entry ID: 65766912

7.2 Diagnostic buffer

The diagnostic buffer is used as log file for the occurred diagnostic events. They are entered in the sequence of their occurrence, where the latest event is displayed on top. Further information and functions, such as, e.g. performance data of the currently used WinAC MP, setting the time, memory etc. can be additionally polled here. Figure 7-2

7 Online and Diagnostics

WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren Version 1.1, Entry ID: 65766912 25

7.3 Task card “Online tools"

In the “Online tools" task card you can read out the current diagnostics information and transfer commands to the modules. Figure 7-3 Figure 7-4 Figure 7-5