Irrigation System Controller
Users Guide Setup Installation Programming Troubleshooting
v Indoor and Outdoor 6-, 9-, and 12-station Models v
English
Espaol
Franais
-
Getting to Know Your Rain Dial Controller . . . . . . . . . . . . . .23
Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
BatteryInstallationandArmchairProgramming . . . . . . . . . . 4-5
Overview:ControlModuleInterface . . . . . . . . . . . . . . . . . . . . 6-7
Overview:InternalControllerComponents . . . . . . . . . . . . . . 8-9
Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1015
InstallingtheControllerCabinet . . . . . . . . . . . . . . . . . . . . . . . .10
ConnectingtheValveControlWiring . . . . . . . . . . . . . . . . .1011
ConnectingaRainSensor(optional) . . . . . . . . . . . . . . . . . . . .12
ConnectingaRemoteControlUnit(optional) . . . . . . . . . . . . .13
ConnectingtheEarthGroundDevice . . . . . . . . . . . . . . . . . . .14
ConnectingthePowerSource . . . . . . . . . . . . . . . . . . . . . .1517
IndoorModels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
OutdoorModels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1617
ControllerStationTestFeature . . . . . . . . . . . . . . . . . . . . . . . .17
Getting the Most From Your Rain Dial Controller . . . . . . .1819
SampleWateringPlan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
What the Display Indicates . . . . . . . . . . . . . . . . . . . . . . . . . .2021
Basic Programming Procedures . . . . . . . . . . . . . . . . . . . . .2225
SettingtheCurrentTimeandDay . . . . . . . . . . . . . . . . . . . . . .22
SettingtheValveRunTimeDuration . . . . . . . . . . . . . . . . . . .22
SettingtheProgramCycleStartTime(s) . . . . . . . . . . . . . . . . .23
SettingtheProgramWateringDaySchedule . . . . . . .2325
ToSetaWeekdaySchedule: . . . . . . . . . . . . . . . . . . . . . .23
ToSetaSkipDaySchedule: . . . . . . . . . . . . . . . . . . . . . . .24
ToSetanOdd/EvenDateSchedule . . . . . . . . . . . . . .2425
DayExclusionFeature . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
ii
F Table of Contents
-
Special Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2629
RainDelay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
WaterBudget . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2628
ToApplyaBasicWaterBudget: . . . . . . . . . . . . . . . . . . . .27
ToApplyaMonthlyWaterBudget: . . . . . . . . . . . . . . .2728
Stack/Overlap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
StationDelay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
PumpControlDuringStationDelay . . . . . . . . . . . . . . . . . . . .30
PumpControlOption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Diagnostic Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Fuse Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Manual Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3233
Semi-automaticProgramOperation . . . . . . . . . . . . . . . . . . . .32
ManualStationOperation . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Clear Program Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Restore Rain Dial-R to Factory Default Settings . . . . . . . . . .35
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Contact Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
FCC Rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
1
-
F Getting to Know your Rain Dial Controller
To take full advantage of your new Rain Dial-R controller, take a few moments to become familiar with its many features:
Modular design Provideseasyaccesstovalveconnectionter-minalsandbatterystorage .Snap-outdesignenablesthecontrolmoduletobeeasilyremovedforArmchairProgramming .
Remote control ready Built-inRJ-11jackfordirectconnectiontoIrritrolCMR-KITorKSR-KIThandheldremotecontrolsystems .
Non-volatile memory Keepsalluser-definedwateringprogramsstoredinmemoryforseveralyearswithout power!
Super Cap Providesabackuppowersourcetosustaincurrenttimeanddateduringapoweroutagelastingupto24hours .
Battery back-upMaintainscurrenttimeanddateaduringpoweroutagelastinglongerthan24hours .AlsoenablesArmchairProgrammingofthecontrollerpriortoinstallation .
Three independent watering ProgramsEnablesautomaticwateringProgramstobespecificallytailoredforvariousportionsofthelandscape;e .g .,lawns,shrubsandtrees .
Three Start Timesper Program Enablesoperationofeachauto-maticProgramuptothreetimesperscheduledwateringday .
Skip Days schedulingEnableswateringdaystobescheduledbyinterval,rangingfrom1(everyday)to31(onceevery31days) .
Odd/Even date schedulingEnablesawateringdayscheduletobedefinedbyallodd-oreven-numberedcalendardays .
Day Exclusion EnablesspecificweekdaystobeexcludedfromanOdd/EvendateorSkipDayswateringschedule .
Program Stack/Overlap ProvidestheoptiontolimitoperationtooneProgram/stationatatime(Stack),orenableuptothreeProgramsorstationstooperateconcurrently .
Station Test FeatureAconvenienttest-cyclefeatureoperateseachvalvestationinsequenceforaselectedruntimefrom110minutes .Perfect for new installations!
Live programming Enablesprogrammingchangestobemadeatanytimeeven during watering!
2
-
Fully automatic, semi-automatic and manual station operations .
Manual AdvanceEnablesstationsequencetobeadvancedmanuallyduringoperation(manualorautomatic) .
Off or Stop ImmediatelystopsandpreventsallwateringactivitywithoutdisturbingPrograms .
Four places available to quickly remove start timesFourOFFpositionsareprovidedwithinthetimedisplaytoremoveunwantedstarttimes;significantlyreducingtheamountofscrollingrequired .
Rain Delay Enablesautomaticwateringtobepostponedfrom1to9days;thenresumeautomaticallywateringasscheduled .
Water BudgetEnablestheruntimeofallstationswithinaProgramtobescaledupto200%ordownto0%(Off) .Inaddition,aWaterBudgetvaluecanbeappliedtoindividualProgramsbyspecificmonthswhenseasonalwaterbudgetingispreferred .Thisisagreatfeatureforwatersmartapplications .
MV/Pump control by station EnablesautomaticMasterValve/Pumpoperationtobecontrolledbyindividualstations .
Station sequence delayProvidesanadjustabledelayperiodbetweenstationsduringtheoperatingsequencetoaccommodateslow-closingvalvesorarequiredwell-recoveryperiod .
MV/Pump controlduring station delay EnablesMasterValve/Pumpoperationtobeactiveorinactiveduringastationdelayperiod .Rain Dial-R provides the choice!
Built-in circuit protectionHelpsprotectthecontrollerselectroniccomponentsfromdamageduetopowerandnearbylightningsurges .
Diagnostic Circuit Breaker Enablesthecontrollertodetectandbypassanystationwithashortcircuitorfaultysolenoid .DisplaysFUSandthebypassedstationnumberforeasytroubleshooting .
Clear Program Memory EnablesProgrammemorytobeclearedandresetindependentlyofotherPrograms .
Reset to Factory Program Defaults EnablesfactorydefaultProgramsettingstobeeasilyrestoredifrequired .
3
-
F Getting Started
Battery Installation & Armchair Programming
Installinga9Vbattery(user-provided)servestwoimportantfunctions:first,itenablestheRainDial-Rtobefullyprogrammedpriortoinstallation,andsecond,itkeepsthecontrolmodulesynchronizedwithcurrenttimeanddateduringamainpowerinterruptionlastingmorethan24hours .Note: The battery is not capable of operating the sprinkler valves. Main AC power must be applied to the controller to enable operation.
Thecontrolmoduleisdesignedtobeeasilyremovedforcompleteprogramminginamoreconvenientsetting,suchasyourfavoritearmchair .Toremovethecontrolmodule,simplyunplugtheribboncableconnectorfromtheprintedcircuitboard,thencarefullyremovethemodulefromitssnap-inhinges .TheRainDial-Rfeaturesnon-volatilememory,whichkeepstheprogramminginformationintact,evenifthebatterydiesorisdisconnected .
Installing the Battery1 . Openthecontrollerdoor .
2 . Pullthecontrolmoduleopenbygraspingitfromtherightedge(pressthemodulereleasetabontheoutdoormodel) .
3 . Pressdownandoutwardontopofthebatterycompartmentcovertoremove .SeeFigure 1 .
4 . Attachthebatterycliptoa9VAlakalinebattery .
5 . Stowthebatteryintothecompartmentandreinstallthecover .
6 . Thedisplaywillbeginflashing12:00 AM(pressanybuttontohalt) .
Note: To begin setting up a watering Program, refer to Basic Programming Procedures on page 22.
CAUTION: To avoid hazards from improper battery type installation, always replace the battery with the same or equivalent battery type . Always dispose of used batteries properly, as recommended by the battery manufacturer .
4
-
EARTHGROUND
MV/PUMP
7 8 9 10 11 12
1 2 3 4 5 6
24 VACVC
5
Figure 1
9-Volt Alkaline Battery (not included)
Battery Compartment Cover
-
Overview: Control Module Interface
1 - Program Switch Three-positionslideswitchusedtoselectProgramA,BorC
forsetup,programreviewandmanualoperation .
2 - LCD Display High-contrastLCDpaneldisplaysallcontrollerprogramming
andoperatinginformation .
3 - Plus and Minus Buttons Pushbuttonsusedtoincreaseanddecreasedisplayvalues
duringcontrollersetup,programmingandmanualoperations .Adjustsvaluesincrementally(pressandrelease)orbyrapidscrolling(pressandhold) .
4 - Dial A25-positionrotaryswitchusedtoselectstations,starttimes,
wateringdaysandspecialfunctionsforsetup,programmingandmanualoperations .
5 - Manual Button Pushbuttonusedtostartandcontrolmanualoperations
bystation .AlsoservesasaNextbuttontostepforwardthroughvarioussetup,programmingandmanualoperations .
6 - Function Switch Athree-positionslideswitchusedtoselectoneofthree
controllerfunctionmodes: Off or Stop -Stopsallcurrentwateringoperations,and
preventsallautomaticandmanualoperations . Set Programs - Enablesautomaticwateringprogramsetup
valuestobeselectedandchanged . Run or Manual - Normalswitchpositionforallautomaticand
manualwateringoperations .
7 - Semi-Auto Start Button Pushbuttonusedtomanuallystartanautomaticwatering
Program .AlsousedtoinitiatetheStationTestRunoperation .
6
-
7
Figure 2
1
2
3
4
5
6
7
-
Overview: Internal Controller Components
1 - Battery Compartment Snap-incoverprovideseasyaccessto9Valkalinebattery .
2 - Control Module Ribbon Cable Quickdisconnectcablecontrolmodulefromcabinetfor
ArmchairProgrammingorservice .
3 - Earth Ground Terminal Wireconnectionterminalforearthgroundconductor .
4 - Sensor Bypass Switch Switchcontrols(optional)rain/freezesensorinput . 5 - Safety Fuse 2ASlow-blowfuseprotectsagainstshort-circuitoverloadon
the24VACinputpower .
6 - Power Transformer Connection Terminals (24 VAC) Wireconnectionterminalsfor24VACplug-intransformer,
andpowerconnectionpointfor(optional)CMR-KITremote . 7 - Valve Common Terminal (VC) Wireconnectionterminalforthevalve(field)commonwire .
8 - Rain Sensor Terminals (Sensor) Wireconnectionterminalsfor(optional)IrritrolRainSensorTM
modelRS500,RS1000,orRFS1000 .
9 - Sensor Terminal Jumper Sensorterminaljumperwireremovedonlywhenarainor
rain/freezesensorisconnected .)
10 - Master Valve/Pump Terminal (MV/Pump) Wireconnectionterminalfor(optional)mastervalveorpump
startrelay .(InstalledsensorterminaljumperwireremovedonlywhenRainSensorconnectionismade .)
11 - Valve Station Terminals Valveconnectionterminalsoneterminalforeachvalve .
(Terminallayoutvariesbymodel12-stationmodelshown .)
12 - Handheld Remote Control Plug-in Port ModularconnectorportrequiredfortheIrritrolhandheld
remotecontrolsystemmodelsCMR-KITorKSR-KIT-K .
8
-
9
1 2 3 4
5
6
7
8
9
1011
Figure 3
12
-
F Installation Procedures
wInstalling the Controller CabinetSelectashelteredlocationfortheindoormodelRainDial-Rsuchasagarageorserviceroom,preferablywithin5'(1 .5m)ofagroundedelectricaloutlet .Foroutdoorcontrollers,choosealocationthatpro-tectsagainstdirectexposuretosunandcontactwithirrigationspray,andisatleast5'(1 .5m)awayfromanymotorizedequipment .
1 . Drivetheprovidedstainlesssteelscrewintoawallstudataconve-nientheight,leaving1/4"(6 .4mm)ofthescrewshaftexposed .
Note: Use screw anchors when installing on drywall or masonry. 2 . Hangthecontrolleronthescrewusingthekeyhole-shapedslot .3 . Tosecurethecontroller,driveoneortwoscrewsthroughthe
lowermountingholes . Note: The lower mounting holes in the Outdoor cabinet have a thin
veneer that is easily pierced when installing the mounting screw during installation.
wConnecting the Valve Control WiringForbestresults,useconnectionwirecablespecificallydesignedforautomaticirrigationsystems .Use18-AWGwireforconnectionsupto800'fromthecontroller,orheavier14-AWG(2 .0mm2)wireforcon-nectionsupto2000' .Aseparatewireforeachvalve(andrelay)con-nectionandatleastonecommon(return)wireisrequired .
Note: If control wire conduit is required, install it at this time. For conduit installation, use the 3/4" (19mm) access hole in the indoor cabinet, or the threaded 1.25" NPT opening in the outdoor cabinet.1 . Routethecontrolwirefromthecontrollerlocationtothevalve(s) .2 . Attachaseparatecontrolwiretoeitherleadofeachvalvesolenoid .3 . Toprovideacommon(return)wire,attachtheremainingleadof
eachvalvesolenoidtoasinglewire . Note: To prevent corrosion and a possible short circuit, use
waterproof wire connectors on all external wire splices. For reference at the controller, note the wire color used for each
valve connection and its corresponding watering zone.
10
-
4 . Routethecablethroughthelargestopeninginthebaseofthecontrollercabinetorthroughconduitifinstalled .Removethecablejackettoexposeabout8"ofwires .Carefullyremove3/8"ofinsulationfromtheendofeachwiretobeconnected .
5 . Secureeachvalvewiretonumberedterminalinthepreferredoperatingsequenceorder .
6 . ConnectthecommonwiretotheterminallabeledVC .7 . Ifapplicable,connectonelegofthemastervalveorpumpstart
relaycontrolwiretotheterminallabeledMV/PUMP,andtheremaininglegtothevalvecommonwire .
Note: The controller does not supply power to operate a pump. The pump start relay must have a nominal coil voltage of 24 VAC, rated at 0.375A maximum.
EARTHGROUND
MV/Pump Sensor
+ -
7 8 9 10 11 12
1 2 3 4 5 6
24 VACVC
11
Figure 4
Sprinkler Control Valves
Common Wire
Pump Start Relay or Master Valve
1
2
3
MV
24V Relay
Master Valve/Pump Terminal
Valve Common Terminal
-
Connecting a Rain Sensor (optional) TheRainDial-RisdesignedtoworkinconjunctionwithIrritrolRainSensormodelsRS500,RS1000orRain/FreezesensorRFS1000torestrictwateringwhenmoistureand/ortemperaturelimitsaremet .Note: If connecting an alternate make of rain sensor, ensure it pro-vides normally-closed switch circuit operation.
IMPORTANT: If a rain sensor is not installed, the sensor terminal jumper wire must remain in place, and the sensor switch must remain in the Bypass position . If either of these conditions are not met, automatic and manual operation will be disabled . 1 . Insertthesensorcablethroughthebottomofthecabinet .
2 . LoosentheSensorterminalsandremovethejumperwire .
3 . RefertotheinstallationinstructionsprovidedwiththeRainSensorandconnectwiresaccordingly .
4 . PlacetheSensorswitchintheActiveposition . Note: When the Rain Sensor is active, all watering
operations will be terminated and SEn (Sensor) will be displayed (in the current time dial position).
EARTHGROUND
MV/Pump Sensor
+ -
7 8 9 10 11 12
1 2 3 4 5 6
24 VACVC
12
Figure 5
Jumper Wire Removed
-
Connecting a Remote Control Unit (optional)TheRainDial-Rcontrollerisremote-readyandisfullycompatiblewithbothIrritrolHandheldRemoteControlmodels:theclose-rangeresidentialmodelKSR-KIT-K,andthelong-rangecommercialmodelCMR-1-KIT .Bothhandheldremotesystemsoffersimilarcontrolfea-tures .Refertotheuserguideprovidedwitheachremotekitforcom-pleteinformation .
Asshownintheillustrationbelow,theKSR-KIT-KreceiverplugassemblysimplyplugsintothereceptacleprovidedinthebackoftheRainDial-Rcontrolmodule .TheCMR-1-KITreceiverplugassemblyalsorequiresconnectiontothe24VACpowerterminals .
Note: The receiver plug assembly of the two remote models look similar, but are not interchangeable.
EARTHGROUND
MV/Pump Sensor
+ -
7 8 9 10 11 12
1 2 3 4 5 6
24 VACVC
13
Figure 6
CMR-CC Receiver Plug for CMR-1-KIT Remote
CA-03 Receiver Plug for KSR-KIT Remote
-
Connecting an Earth Ground DeviceNote: In order for the electrical surge components built into your Rain Dial-R to function properly, the controller must be connected to an earth ground device, such as a copper-clad ground rod or metal water pipe, using solid copper wire. This connection is especially important when the controller is installed in a lightning-prone area .
1 . Connecta1216AWG(2mm21 .3mm2)solid-copperwiretothegrounddeviceandrouteintothecontrollerthroughanaccessopeninginthebaseofthecabinet .
2 . SecurethegroundwiretotheterminallabeledEarthGround .
EARTHGROUND
MV/Pump Sensor
+ -
7 8 9 10 11 12
1 2 3 4 5 6
24 VACVC
Metal Water Pipe
8 (2 .4 m) Copper-clad Ground Rod (in moist soil)
14
Figure 7
-
Connecting the Power Supply - Indoor Models 1 . Routetheplug-intransformercablethroughthesmallhole
providedinthebottomofthecabinet .
2 . Tieaknotinthecabletoprovideastrainrelief,andconnectthewirestotheterminalslabeled24VAC(ineitherorder) .
3 . Closethecontrolmoduleandplugthetransformerintoawalloutlet .Thecontrollerisnowreadytoprogramandoperate .
Note: To immediately test-run the Rain Dial-R irrigation control system, refer to the Controller Station Test Feature on page 17.
EARTHGROUND
MV/Pump Sensor
+ -
7 8 9 10 11 12
1 2 3 4 5 6
24 VACVC
Figure 8
15
Strain-relief Knot
Strain-relief Knot
24 VAC, 30VA Transformer
-
Connecting the Power Source - Outdoor Models
WARNING: All electrical components and connection methods must comply with all applicable national and local electrical codes including installation by qualified person-nel . These codes may require a junction box installed on controllers 1/2" (13mm) NPT nipple and a means in the fixed wiring of disconnecting AC power having a contact separation of at least 0 .120" (3mm) in the line and neutral poles . The connection wire must have insulation rated @ 105 C min .
The controller must be connected to a grounded power source . Do not connect to one phase of a 3-phase power supply used by a pump or other electrical equipment .Prior to connecting controller wiring, verify that power has been turned off at the source by using an AC volt meter .1 . Installa1/2"(13mm)NPTconduitbodytothetransformerthread-
edfitting .Fromtheconduitbody,installelectricalconduitroutingtotheACpowersource(perelectricalcode) .
2 . Pull14AWGthroughtheconduitintotheconduitbody .
3 . Usingtwist-onwireconnectors,attachthematingwiresasshowninFigure 10 .
4 . Closeandsecuretheconduitbodycover .5 . Applypowertothecontrollerandcheckcontrolleroperation .If
thecontrollerisnotoperating,disconnectthepoweratthesourceandhaveaqualifiedelectriciancheckforpossibleshortcircuit .
CAUTION: For maximum protection of the controller electronic components when installed outdoors, always keep the cabinet cover closed and locked whenever possible . Store the cabinet keys in a safe, convenient location .
16
Figure 9
Key
-
Controller Station Test Feature
The controllerStation Test feature enablesyoutoquicklycheckforpropervalvestationoperationafterinitialinstallationorservice .Thetestcycleenablesallvalvestationstooperateinsequenceforatemporaryruntime,adjustablefrom110minutes .
1 . PlacetheFunction switchintheSet ProgramsorRunposition .
2 . TurntheDialtotheSkip Days - Special Functionsposition .
3 . PresstheManualbutton(onetime)toselecttheTestRundisplayasshownatright .
4 . A2-minutetestruntimeissetbydefault .Toadjusttheruntimefrom110minutes,pressthe or button .
5 . PresstheSemi-Autobuttontostartthewateringcycle .Station1willturnon .
6 . TurntheDialtotheCurrent Timeposition .Thedisplaywillindicatethecurrentclocktime(initially12:00PM)andstation1 .
7 . Tomanuallyadvancethroughthestationoperatingsequence,presstheManualbutton .
RD-1200
A-+
B-C-
MANUAL
TodaySun
Mon
Wed
Thu
2
3
4
5
6
7
8
9
1011123
21
PM
SC
HE
DU
LE
STARTTIMES
VA
LV
ER
UN
TIM
ES
17
Figure 10
1 2 3 4 5 6 7 8 9 10 11 12
Equipment Ground to Green or Green/Yellow
Hot or L2 to Black or Brown
Neutral or L1 to White or Blue
Conduit Body
Electrical Conduit
-
F Getting the Most from Your Rain Dial-R Controller What is an Automatic Program Watering Cycle? AnautomaticwateringProgrambeginsatitsearliestassignedstarttimeonascheduledwateringday .ThelowestvalvestationnumberassignedtotheProgram,turnsonandoperatesthesprinklersforthespecifiedruntimeduration .Whenfinished,thenextvalvestationinnumericorder(withanassignedruntimeintheProgram)beginsoperation .TheProgramWateringCyclecontinuesuntilallvalvestationswithanassignedruntimeintheProgramhaveoperated . Why Three Programs? Atypicalresidentiallandscapeincludesvarioussectionsoflawn,shrubs,treesandgroundcover,allofwhichrequirewateringondifferentschedulesforoptimumplanthealthandconservation .Toaccommodatethis,theRainDial-RprovidesthreeindependentwateringPrograms:A,BandC .
TheexamplebelowshowshowmultipleProgramscanbeusedtoeasilyaccomplishthis:
Program Start Time Valve # Location Run Time Schedule
A (#1)5:00AM 1 FrontLawn 15min. Odd 2 Backyard 15min. Odd 3 SideYard 10min. Odd B (#1)3:00PM 4 Trees(drip) 2hrs. Mon C (#1)4:00AM 5 Garden 5min. SkipDays,1 (#2)7:30PM 5 Garden 5min. SkipDays,1
18
-
Avoid unexpected start times Itispossibletosetasecondstarttimethatbeginsbeforethewateringcyclefromthefirststarttimehasfinished .Whenthishappens,thestartofthesecondcycleisdelayeduntilthefirstiscomplete;sothestarttimemaynotoccurwhenyouexpectit .Inaddition,increasingruntimewiththewaterbudgetfea-turemaycauseanoverlapthatdelaysthenextscheduledstarttime .
Avoid watering on a non-watering day AwateringcyclethatcontinuesbeyondMidnightwillruntocompletionregardlessifthenextdayisscheduledforwatering .
Avoid excessive watering Bydefault,ProgramsA,BandCcanbescheduledtorunconcurrently(overlap) .ThisfeaturecanberestrictedbyselectingtheProgramStackingoption(seepage28) .Starttimesenteredforanyprogramwillbeginautomaticallywhenthattimeoccurs .Usingmultipleprogramsenablesvalvestationstowaterondifferentschedulesortoprovideadditionalwateringifoneprogramisnotenough .Ifyouneedextrawater,usemorethanonestarttimeand/orusetheWaterBudgetfeaturetoincreasethevalvestationruntime .
Avoid Creating a low water pressure condition Starttimesassignedtodifferentprogramsareindependent .Ifyousetidenticaloroverlappingstarttimes,morethanonevalvestationcanrunatthesametime .Thetotalflowmayexceedtheavailablewatersupply .Toavoidthissituation,allowmoretimebetweenstarttimestoreducethenumberofvalvesrunningatonetime,andmakesurethatmultipleProgramsdonothavethesamestarttimes .
Establishing new lawnsHavingshort,multiplewateringcycleseachdayisespeciallyusefulwhenestablishinganewlawn .
Help with electrical problems TheRainDial-RwilldisplaythestationnumberandthewordFUSifashort-circuitonavalvestationisdetected .Thedetectedstationwillbebypassed,allowingtheremainingstationstorunintheProgramwateringcycle .
19
-
F What the Display Indicates
Thefollowingexamplesrepresentthedisplayinformationprovidedtoassistyouwithinthevariousprogramming,setupandoperatingmodes .
Programming Mode (Function Set Programs) Current Time-Displaysthecurrenttimeofday .
Valve Run Times-Displaystheruntimesetforaselectedvalvenumber .Willindicate0159minutes,1 .05 .9hoursorOff .
Start Times-Displaysstarttime(s)assignedtotheselectedProgram .
Today-DisplaysthecurrentdaywithinaWeekdayschedule,e .g .Su,Mo,etc .,orSkip Daysscheduleday(131) .
Schedule-DisplaysONorOFF foreachdayinaWeekdayschedule .WhenusinganOdd/Evenschedule,Odd,EvenorOFFwillbedisplayedforeachstation .WhenusingaSkip Daysschedule,Once Every (0131) willbedisplayed .
Special Functions (Dial Special Functions)
Station Test Cycle-Allactivestationnumberswillbeshownatthetopofthedisplay .T:0110indicatesminutesofruntimeselectedfortestcycle .
Water Budget (Per Program)-Displaysthecur-rentWaterBudget%orOFF .IfaMonthlyWaterBudgetisinuse,( )willbeshown .
Clear Program Memory-CLrindicatestheClearProgramMemoryfunctionisselected .
Well Recovery Time-Indicatesthedelaytime(0059seconds,159minutesor12hours)settooccurbetweenstationsinawateringcycle .
20
1 2 3 4 5 6 7 8 9 10 11 12
-
Pump Operation during Station Delay -IndicatespumpoperationissettoOnorOffduringastationdelayperiodperiod .
Program Stacking/Overlap-IndicatesProgramStacking(1:On)orOverlap(3:On) optionselected .
Odd/Even Schedule -IndicatesOddorEvnscheduleselected .
Calender month -Displaysthecurrentmonth .
Calender month/day -Displaysthecurrentmonthandday .
Year -Displaysthecurrentyear .
Rain Delay-Indicatesnumberofdays(09)settodelayautomaticoperation .
Monthly Water Budget -IndicatesWaterBudgetstatus(On/Off)permonth(112)and%factor(01200orOff)assignedtoeachmonth .(Month,dayandyearmayalsobesetatthistime .)
Run Mode (Function Run) Automatic Mode (Dial Current Time)-Active
valvenumberandcurrenttimeareshown .(Dial Active valve number)-activevalvenumber,currentProgramandremainingruntime .
Note: If Water Budget is active, the adjusted run time will be shown.
Manual Mode-(Dial Active valve number)-Valvenumber,M:andremainingruntimeareshown .
Rain Delay-OF(Off)andthenumberofdaysuntilwateringresumesalternateswiththecurrenttime .
Diagnostic Circuit Breaker-FUS(Fuse)andthebypassedvalvenumber(s)willalternatewiththecurrenttime .
21
-
F Basic Programming Procedures
Setting the Current Time and Day
1 . PlacetheFunction switchintheSet Programs(center)position .
2 . TurntheDialtotheCurrent Timeposition .
3 . Pressthe or buttontosetthecurrenttime(noteAM/PM) .
Note: When using the or button, press and release to adjust in steps, or press and hold to scroll.
4 . TurntheDialtotheTodayposition .
5 . Pressthe or buttontoselectthecurrentday(abbreviation) .
Note: If Odd/Even schedule or Monthly Water Budget is used, the current day of the week is preset and cannot be changed.
6 . ReturntheDialtotheCurrent Timeposition .
7 . ReturntheFunction switchtotheRunposition .
Note: The flashing colon (:) indicates AC power is present. If the colon is not flashing, the controller is operating on battery power only.
Setting the Valve Run Time Duration
EachvalvestationcanhaveanindividualruntimeassignmentineachProgram .Runtimecanbesetfor159minutes(in1-minuteincrements)or15 .9hours(in1/10-hourincrements) .
1 . PlacetheFunction switchintheSet Programs(center)position .
2 . SelectProgramA,BorC .
3 . TurntheDialtoselectthevalve number .
4 . Pressthe or buttontosetthevalveruntimeduration .
5 . Repeatsteps3and4forallvalvestobeassignedtotheselectedProgram .
6 . Repeatsteps25foreachProgramasneeded .
7 . Whenfinished,returntheDialtotheCurrent Timeposition .
8 . PlacetheFunction switchintheRunposition .
22
-
Setting the Program Cycle Start Time(s)EachProgramcanhavethreeseparatestarttimes .Formaturelandscapes,onestarttimeperProgramisgenerallysufficient .Whenestablishinganewlawn,usingtwoorthreestarttimeswithshortvalveruntimescanprovidetheadditionalirrigationrequiredforgrow-in,atareducedratetohelppreventrunoffanderosion .1 . PlacetheFunction switchintheSet Programsposition .2 . SelectProgramA,BorC .3 . TurntheDialtoselectStart Time 1 (2 or 3) .4 . Pressthe or buttontosetthestarttime(noteAM/PM) . Note: To remove a start time, select Off, displayed between
11:5912:00 and 5:596:00 (AM and PM).5 . Repeatsteps3and4tosetadditionalstarttimesforthisProgram .6 . Repeatsteps25foreachProgramasneeded .7 . Whenfinished,returntheDialtotheCurrent Timeposition .8 . ReturntheFunction switchtotheRunposition .
Setting the Program Watering Day Schedule
WateringdayscanbescheduledforeachProgramusingoneofthefollowingmethods: Weekdays-Scheduleswateringforspecificdaysoftheweek . Skip Day-Scheduleswateringdaysbyintervalfrequency;
e .g .,everyday(01),every-other-day(02)etc . Odd/Even Date-ScheduleswateringdaysbasedonOdd-or
Even-numberedcalenderdays .To set a Weekdays Schedule:1 . PlacetheFunction switchintheSet Programsposition .2 . SelectProgramA,BorC .3 . TurntheDialtothedesiredweekdayposition .4 . Pressthe buttontoselecttheday(On),orthe button
removetheday(Off)fromthewateringdayschedule .5 . Repeatsteps3and4toscheduleadditionalweekdaysasneeded .6 . Repeatsteps25foreachProgramasneeded .7 . Whenfinished,returntheDialtotheCurrent Timeposition .8 . ReturntheFunction switchtotheRunposition .
23
-
Note: Each Program can have a Skip Days or an Odd/Even Date watering schedule, but not both. One schedule must be turned off to enable the alternate schedule to be selected.
To Set a Skip Day Schedule:1 . PlacetheFunction switchintheSet Programsposition .
2 . SelectProgramA,BorC .
3 . TurntheDialtotheSkip Days/Special Functions position .
4 . Pressthe / buttonstoselecttheSkip Day interval(0131) days .
Note:To turn Off a Skip Day schedule, press the or button to display OFF.
5 . TurntheDialtotheToday position .
6 . Pressthe / buttonstoselectthecurrentdaywithintheSkipDayintervalschedule .
Note: For example, if you have selected a 3-day schedule, and prefer to have watering start today, select 03. To water tomor-row, select 02. To watering in three days, select 01.
7 . Repeatsteps26foreachProgramasneeded .
8 . Whenfinished,returntheDialtotheCurrent Timeposition .
9 . ReturntheFunction switchtotheRunposition .
To Set an Odd/Even Date Schedule:1 . PlacetheFunction switchintheSet Programsposition .
2 . SelectProgramA,BorC .
3 . TurntheDialtotheSkip Days - Special Functions position .
4 . PresstheManualbutton(seventimes)todisplaydashes( ) .
5 . Pressthe buttontoselectOdd,orthe buttontoselectEven (EVn) .
Note:To turn Off an Odd/Even Date schedule, press the or button to display dashes ( ).
6 . PresstheManualbutton(onetime)toselectthecalendarMonth January(JA)willbedisplayed .
24
-
7 . Pressthe / buttonstoadjustthemonthsetting . JA-January,Fe-February,MR-March,AP-April,My-May,
JN-June,JL-July,AU-August,SE-September,OC-October,nO-November,andDE-December .
8 . PresstheManualbutton(onetime)toselecttheDaysetting .9 . Pressthe / buttonstoselectthecurrentcalendarday .
Example: September 17th would be displayed as S:17.10 .PresstheManualbutton(onetime)toselecttheYearsetting .11 .Pressthe / buttonstoselecttheyear(09 =2009) .
13 .Whenfinished,returntheDialtotheCurrent Timeposition .12 .Repeatsteps210foreachProgramasneeded .14 .ReturntheFunction switchtotheRunposition .Note: When an Odd/Even schedule is used, confirm that the current day of the week is correctly set by turning the Dial to the Today position. If the day of the week is incorrect, adjust the month, day and year settings to properly synchronize the controller. Also note that when using an Odd/Even schedule, watering never occurs on the 31st of any month or February 29th of a leap year.
Day Exclusion FeatureWhenusingaSkipDaysandOdd/Evendatewateringschedule,wateringwillnotoccuronthesamedaysfromweektoweek .Torestrictwateringonspecificweekdays;e .g .,forscheduledmowingormaintenance,usetheDayExclusionfeatureasfollows:
1 .PlacetheFunction switchintheSet Programsposition .2 . SelectProgramA,BorC .3 . TurntheDialtotheDay tobeexcluded .4 . Pressthe buttondisplayOFF .5 . Repeatsteps3and4toexcludeadditionaldays .6 . ReturntheDialtotheCurrent Time position .7 .ReturntheFunction switchtotheRunposition .
v This completes the basic programming requirements for automatic operation . To utilize the various Rain Dial-R Special Functions, continue on pages 2629 .
25
-
F Special Functions
Rain Delay
TheRain Delay feature enablesautomaticwateringoperationtobesuspendedforaperiodof1to9days;thenresumewateringautomaticallyasscheduled .
1 . PlacetheFunction switchintheSet Programs position .
2 . TurntheDialtotheSkip Days - Special Functionsposition .
3 . PresstheManualbutton(repeatedly)todisplayrd0 (RainDelay=0days) .
4 . Pressthe / buttonstoselectaRainDelayperiodof1to9days .
5 . ReturntheDialtotheCurrent Timeposition .
6 . ReturntheFunction switchtotheRun position .
Note: When the Rain Delay function is active, the display will alternately indicate the current time of day and the number of days remaining until automatic operation resumes. To cancel Rain Delay at any time, decrease Rain Delay setting to 0 days.
Water Budget
TheWater Budgetfeatureenablestheruntimeofallstations,assignedtoaspecificProgram,tobesimultaneouslyadjustedupordownbypercentage .Fromthebaselineof100%,runtimescanbereducedto0%(Off)orincreasedupto200% .
Toreducethepossibilityofover-wateringwhenselectingaWaterBudgetvalueabove100%,theadjustedruntimeisautomaticallycutinhalf,andthewateringcycleruntwice .Forexample,adjustingto200%wouldfirstincreasea20-minutestationruntimeto40min-utes,thensplitthetimeinhalfandruntwowateringcyclesback-to-backwith20minutesduringeachcycle .
Allzoneruntimesareretainedinthetimermemoryandreturnedtotheirsetvaluewhentheseasonadjustisresetto100% .Theonlytimeastationruntimewillappearchangedisduringoperation .
26
-
Foradditionalcontrol,aWaterBudgetfactorcanbeassigneduni-versallytoaProgram,orappliedtoaProgrambyspecificmonthsoftheyearwhenWaterBudgetingbyseasonaldemandispreferred .
Note: Each Program is limited to one Water Budget method at a time. Applying a Water Budget by monthly demand will override a basic Water Budget adjustment value. Conversely, to apply a basic Water Budget, all months must be set at 100%.
To Apply a Basic Water Budget:
1 . TurntheDialtotheSkip Days - Special Functionsposition .
2 . SelectProgramA,BorC .
3 . PlacetheFunction switchintheSet Programs position .
4 . PresstheManualbutton(twice)todisplay100 (%) .
5 . Pressthe or buttontoadjustthe%factor(10%increments) .
Note: Decreasing the Water Budget value beyond 10% to OFF prevents the Program from running automatically.
6 . ReturntheDialtotheCurrent Time position .
7 . ReturntheFunction switchtotheRunposition .
To Apply a Monthly Water Budget:
Note: Applying a monthly Water Budget requires the current date to be set. If an Odd/Even watering schedule has been assigned, the current date was established during the procedure. Steps 111 in the following procedure establishes the current date. To bypass this portion of the procedure, begin at step 12 on page 28.
1 . TurntheDialtotheSkip Days - Special Functionsposition .
2 . SelectProgramA,BorC .
3 . PlacetheFunction switchintheSet Programs position .
4 . PresstheManual buttonrepeatedlytoselect theMonthlyWaterBudgetdisplayasshownatright .
5 . Pressthe buttontoselectON .
27
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
-
6 . PresstheManualbuttononetimetoselectthecalendarMonthsetting .January(JA)willbedisplayed .
7 . Pressthe or buttontoselectthecurrentmonthabbreviation:JA-January(1),Fe-February(2),MR-March(3),AP-April(4),My-May(5),JN-June(6),JL-July(7),AU-August(8),SE-September(9),OC-October(10),nO-November(11)andDE-December(12) .
8 . Withthemonthselected,presstheManual buttononetimetoselecttheDaysetting .
9 . Usethe / buttonstoselectthecurrentcalendarday .For example, April 4 would be displayed as A:04.
10 .PresstheManual buttononetimetoselecttheYearsetting .
11 .Pressthe / buttonstoselectthecurrentyear(09=2009) .
12 .PresstheManual button(asneeded)toselecttheMonthlyWaterBudgetdisplay .1(January)isselectedwithitscurrentWaterBudgetvalue(100%bydefault) .
13 .Tochangethemonthselection,presstheManualbutton .
14 .Pressthe / buttonstoadjustthe%factorin1%incrementsdownorup(Offor10%200%) .
15 .Repeatsteps13and14tosetadditionalmonths .
15 .Whenfinished,returntheDialtotheCurrent Timeposition .
16 .ReturntheFunction switchtotheRunposition .
Stack/Overlap
TheStack/Overlap optiondetermineshowthecontrollerwillmanageconcurrentlyscheduledprogramsormanuallystartedvalvestations .Bydefault,theOverlapoptionisselected,enablingsimultaneousoperationofuptothreeProgramsormanualvalvestations .SelectingtheStackoptionlimitsoperationtoeitheroneautomaticProgramormanualvalvestation .
28
-
Important: The Stack option prevents a scheduled Program or manually
operated valve station from operating until any current opera-tion has been completed or canceled. At midnight, any remaining scheduled Programs stacked in queue will be canceled.
Selecting the Overlap option can cause the electrical and/or hydraulic capacity of your irrigation system to be exceeded. Always plan your watering schedule carefully!
1 . TurntheDialtotheSkip Days - Special Functionsposition .
2 . PlacetheFunction switchintheSet Programs position .
3 . PresstheManualbuttonrepeatedlytodisplay3:On (threeprogramsorstationscanrunconcurrently) .
4 . ToselecttheStackoption,pressthe / buttontochoose1:On .
5 . ReturntheDialtotheCurrent Time position .
6 . ReturntheFunction switchtotheRunposition .
Station Delay
Irrigationsystemsthatutilizeawell-watersourceorhaveslow-closingvalves,mayrequireadelayperiodtooccurbetweencon-secutivestationsduringawateringcycle .TheStationDelayfeatureenablesadelayperiodtobesetfrom1secondto2hours .1 . PlacetheFunction switchintheSet Programsposition .
2 . PlacetheProgramswitchtoselectA,BorC .
3 . TurntheDialtotheSkip Days - Special Functions position .
4 . PresstheManualbuttonrepeatedlytodisplayW:00 (nodelay) .
5 . Pressthe / buttonstosetthedelaytime:0059seconds,0159minutes(MIN)or1 .02 .0hours(HR .) .
Note: Hold the button down to scroll. The display will continuously scroll from seconds to minutes to hours (:00 = no delay time).
6 . ReturntheDialtotheCurrent Time position .
7 . ReturntheFunction switchintheRunposition .
29
-
Pump Control During Station Delay
ThePumpControlfeatureisgenerallyusedinconjunctionwiththeStationDelayfeature,enablingthepump/mastervalvetobeturnedonoroffbetweenconsecutivestationsduringawateringcycle .Forexample,asystemwithslow-closingvalvesmayrequireanauxiliarypumptoremainonthroughoutthewateringcycletoassistvalveclosure .Alternately,asystemutilizingawell-watersupplysourcemayrequiretheauxiliarypumptobeoffwhenanextendeddelayperiodbetweenstationsisrequiredforadequatewell-recoverytime .
1 . PlacetheFunction switchintheSet Programsposition .
2 . PlacetheProgramswitchtoselectA,BorC .
3 . TurntheDialtotheSkip Days - Special Functions position .
4 . PresstheManualbutton(repeatedly)todisplayP:OF (PumpOff) .
5 . Pressthe / buttontotogglebetweenP:OFandP:On
6 . ReturntheDialtotheCurrent Time position .
7 . ReturntheFunction switchintheRunposition .
Pump Control Option
Bydefault,thepumpcontrolcircuitisactivatedsimultaneouslywithanyautomaticormanualvalvestationoperation .Whenpumpoper-ationisnotrequiredforspecificvalvestations;e .g .,dripirrigation,thepumpcontrolcircuitcanbeeasilydisabledasneeded .
Note: The Pump control option applies to the selected valve station regardless of its Program assignment.
1 . PlacetheFunction switchintheSet Programsposition .
2 . TurntheDialtoselecttheappropriatevalvestationnumber .
3 . PresstheManualbutton:P:On(PumpOn)willbedisplayed .
4 . Todisablethepumpcontrolcircuitfromthevalvestation,pressthe buttontodisplayP:OF (PumpOff) .
5 . Repeatsteps24foradditionalvalvestationsasrequired .
6 . ReturntheDialtotheCurrent Time position .
7 . ReturntheFunction switchtotheRunposition . 30
-
F Diagnostic Circuit Breaker
ThepromptFUSandthemalfunctioningvalvestationnumberwillbealternatelydisplayedwiththecurrenttime .Thevalvestationwillbebypassedduringthewateringcycle,enablingallremainingvalvestationstorunasscheduled .WiththeDialsetintheCurrent Time position,pressanybuttontocleartheFUSdisplay .
Important:Determine the cause of the malfunction and take corrective action as necessary . Clearing the display will not resolve the problem .
F Fuse Replacement
Caution: The 2 .0A safety fuse protects the transformer from damage due an excessive current load (short circuit) condition . Locate and eliminate the cause of the problem before replac-ing the fuse . For continued protection against risk of fire, replace only with the same fuse type and rating .
1 . Disconnectpowertothecontroller .2 . Carefullyremovethesafetyfusefromtheterminalboard(see
page9forfuselocation) .
3 . Installanew2 .0Aslow-blowfuse,ensuringthatitisproperlyseatedintheretainingclip .
4 . Reconnectpowertothecontroller .
31
-
F Manual Operations
Semi-automatic Program Operation
Semi-AutomaticProgramoperationenablesanautomaticProgramwateringcycletobestartedmanuallyatanytime .Oncerunning,themanualadvancefeatureenablesyoutostepthroughthepro-grammedstationsequence .
1 . PlacetheFunction switchintheRunposition .
2 . TurntheDialtotheCurrent Time position .
3 . PlacetheProgramswitchtoselectA,BorC .
4 . PresstheSemi-Autobuttontostartthewateringcycle .
Note: Once started, the station sequence can be manually advanced by placing the Dial to Current Time and pressing the Manual button.
Note: The Manual Advance feature applies to all Automatic, Semi-automatic and Station Test watering operations for the selected Program.
Note: To terminate watering operations, place the Function switch momentarily in the OFF or Stop position.
32
-
Manual Station Operation
Manualstation operationprovidesmanualcontrolattheindividualstationlevelandprovidesthefollowingfourcontroloptions:
Station(s)canbeoperatedforaone-timerundurationwithoutalteringthestationssetruntimeinanautomaticProgram .
Operationcanbelimitedtoonlyonestationrunningmanuallyorsettoallowthreestationstorunatthesametime .
Note: Refer to Stack/Overlap Option on page 26 for additional information regarding manual operations.
WorkswiththeManualAdvancefeaturetomoveupthroughthestationsequence .
1 . PlacetheFunction switchintheRunposition .
2 . TurntheDialtotheStation Number tobemanuallyoperated .
3 . Usethe / buttonstosetamanualoperationruntimerangingfrom1minuteto5 .9hours .
4 . PresstheManual buttontostarttheoperation .
5 . Ifthisistheonlystationtoberunmanually,skipstep6andcontinueatstep7below .
6 . Toaddadditionalstationstothemanualrunoperation,repeatsteps2through4asneeded,thencontinueatstep7 .
Note: Depending upon the Stack/Overlap setting, additional stations selected (beyond the one or three option setting) will register as OFF when entered with the Manual button. However, they will be placed (stacked) in the manual sequence to run.
7 . TurntheDialtotheCurrent Timeposition .
Note: Once started, the station sequence can be manually advanced by pressing the Manual button.
Note: To terminate manual watering operations, place the Function switch momentarily in the OFF or Stop position.
33
-
34
F Clear Program Memory
TheClear ProgramMemoryfeatureenablesyoutosafelycleartheautomaticwateringprogramsettingsdefinedforaspecificProgramwithoutaffectinganyremainingPrograminformation .ThememoryerasefunctionappliesonlytothespecifiedProgram,leavingtheremainingProgramsintact .
Important:The Clear Program function completely erases all user-defined programming information from the selected Program including: start times, run times, and watering day schedule .
Note: To return the Program back to factory default settings, refer to Reset Factory Default Programming on page 35.
1 . PlacetheFunction switchintheSet Programsposition .
2 . PlacetheProgramswitchtoselectA,BorC .
3 . TurntheDialtotheSkip Days - Special Functions position .
4 . PresstheManualbuttonrepeatedlytodisplayCLr (Clear) .
5 . Pressthe buttononetime .Thedisplaywillshowtheprompt:CL?(Clear?) .
6 . Tocompletetheprocess,pressthe buttonagaintodisplaythepromptEnd .
7 . ReturntheDialtotheCurrent Time position .
8 . ReturntheFunction switchtotheRunposition .
-
35
F Restore Rain Dial-R to Factory Default Settings
TheRainDial-Rfactorydefaultsettingsforautomaticprogramoperationareasfollows:CurrentTime:12:00AM .CurrentDay:Sunday .CurrentDate:January1,2008 .ProgramA:Weekdaywateringschedulewithalldaysactive . Onestarttimeat7:00AM . 10-minuteruntimeonallvalvestations .ProgramBandC:Nowateringdays,stationruntimesorstarttimes .SkipDaysandOdd/Evendayschedule:OFF-allPrograms .ExcludeddaysinSkipDaysorOdd/Evenschedule:None .MV/Pumpoperation:ON-allstations .WellRecoveryperiod:00(OFF)-allPrograms .MV/PumpoperationduringWellRecovery:OFF-allPrograms .WaterBudget:100%-allProgramsandmonths .RainDelay:0days .Stack/Overlap:Overlap-3Programsor3manualstations .
To restore factory default settings:1 . PlacetheFunction switchintheSet Programposition .2 . PlacetheProgramswitchtoselectProgramB .4 . Openthebatterycompartmentanddisconnectthebattery .3 . LeavingtheACpowerconnected,carefullyunplugthecontrol
moduleribboncablefromtheterminalBoardsocket .5 . PressandholdtheManualbutton .6 . PlugintheribboncableandreleasetheManualbutton . Note: With the dial in the Current Time position, the display
should now show 12:00 AM. If it does not, repeat the procedure as necessary.
7 . Connectthebattery .8 . Reprogramthecontroller .
-
36
Problem
Displayblank .
Somevalvesdonotoperate .
Novalvesoperate .
Wateringonwrongday .
Currenttimeiswrongandflashing .
FUSandastationnumberalternateswithcurrenttime .
Valvewillnotturnoff(withFunctionSwitch .intheOFFposition) .
SENalternateswithtimeofday .
Possible Cause
Nopower .
Faultyorimpropervalvewireconnections .
Debrisinvalve .
FunctionswitchOFF .
Faultyvalvecommonwireconnection .
Sensorswitchin Activepositionnosensororjumperconnected .
Nostarttimeset .
Wateringdayschedulesetincorrectly .
Powerinterruptionwithoutbatterybackup .
Shortorover-currentonvalvestation .
Valvemalfunction .
Wateringonholdduetosensoroperation .
Correction
Checktransformer/powerconnections,2Afuse,andACpower .
Checkandcorrectallvalvewireconnections .
Inspect,clean/replacevalvesolenoid/plungeranddiaphragm .
SetswitchtoRun .
Check/correctvalvecommonconnection .
SetswitchtoBypassorinstallterminaljumper .
SetProgramstarttime .
Correctwateringdayscheduleasneeded .
Install/replacebattery,resetcurrenttime .
Check/replacevalvesolenoidandsplices .
Inspect,clean/replacevalvesolenoid/plungeranddiaphragm .
Normaloperationforsensor .SetSensorswitchtoBypass .
F Troubleshooting
-
37
F Contact Information
Thetroubleshootingsolutionsareprovidedtohelpresolveproblemsthatmayariseduringsetupand/oroperationoftheRainDial-Rcontroller .
Iftheproblemisnotlistedorcannotberesolvedwiththeprovidedsolutions,contactanauthorizedIrritrolproductexpertforassistanceviaphoneoremail .
U .S ./Canada:
Phone:1-800-634-8873(7:30am4pm,MF,PT)
E-mail:irrigationsupport@irritrol .com
Europe:
Phone:+39-076540191
E-mail:intlirrigationsupport@irritrol .com
Australia:
Phone:+61883003633
E-mail:intlirrigationsupport@irritrol .com
-
F Specifications
Outdoor Models: Input:120VAC60Hz,30VA(Domestic), 230/240VAC,50Hz,30VA(International)Indoor Models: Input(fromplug-intransformer):24VAC,60Hz,30VA (domestic),24VAC,50Hz,30VA(InternationalandAustralian)
All Models: StationOutput:24VACat0 .5A,1 .0A(maximumtotal) MasterValve/PumpStartRelayOutput:24VACat0 .375A 2 .0ASlow-blowFuse BatteryBack-up(time,dayanddate) Operatingtemperaturerange:32Fto140F(0Cto60C)
Caution: The Rain Dial is designed to operate 24 VAC valve solenoids rated at 0 .25A (6 VA) . Total current load during operation must not exceed 1 .0A . A maximum of two solenoids per station terminal may be used if the total station load does not exceed 0 .5A . No more than three solenoids (plus MV/Pump circuit) should operate concurrently . In irrigation systems where multiple controllers are used, each controller must utilize a sepa-rate valve common circuit .FCC Rules - Domestic: ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassBdig-
italdevice,pursuanttoSubpartJofPart15oftheFCCRules .Theselimitsaredesignedtoprovidereasonable
protectionagainstharmfulinterferenceinaresidentialinstallation .Thisequipmentgenerates,usesandcan
radiateradiofrequencyenergyand,ifnotinstalledandusedinaccordancewiththeinstructions,maycause
harmfulinterferencetoradiocommunications .However,thereisnoguaranteethatinterferencewillnotoccur
inaparticularinstallation .Ifthisequipmentdoesharmfulinterferencetoradioortelevisionreception,which
canbedeterminedbyturningtheequipmentoffandon,theuserisencouragedtotrytocorrecttheinterfer-
encebyoneormoreofthefollowingmeasures:
1 . Reorientorrelocatethereceivingantenna .
2 . Increasetheseparationbetweentheequipmentandreceiver .
3 . Connecttheequipmentintoanoutletonacircuitdifferentfromthattowhichthereceiverisconnected .
4 . Consultthedealeroranexperiencedradio/TVtechnicianforhelp .
TheusermayfindthefollowingbookletpreparedbytheFederalCommunicationsCommissionhelpful:
HowToIdentifyandResolveRadio-TVInterferenceProblems .ThisbookletisavailablefromtheU .S .
GovernmentPrintingOffice,Washington,DC20402,stock#004-000-00345-4 .
International:ThisisaCISPR22ClassBproduct .
2008Irritrolwww .irritrol .com FormNumber373-0502Rev .A
-
Controlador de sistemas de riego
Gua del usuario Configuracin Instalacin Programacin Solucin de
problemas
v Modelos para interiores y exteriores de 6, 9 y 12 estaciones v
English
Espaol
Franais
-
Introduccin al controlador Rain Dial . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
Cmo empezar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Instalacindelapilayprogramacindesdecasa . . . . . . . . . . . . . . .4-5
Descripcingeneral:Interfazdelmdulodecontrol . . . . . . . . . . . . . .6-7
Descripcingeneral:Componentesinternosdelcontrolador . . . . . . .8-9
Procedimientos de instalacin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-15
InstalacindelarmariodelControlador . . . . . . . . . . . . . . . . . . . . . . . . 10
Conexindelcableadodecontroldelasvlvulas . . . . . . . . . . . . . .10-11
Conexindeunsensordelluvia(opcional) . . . . . . . . . . . . . . . . . . . . . 12
Conexindeunaunidaddecontrolremoto(opcional) . . . . . . . . . . . . . 13
Conexinaunatomadetierra . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Conexindelsuministroelctrico . . . . . . . . . . . . . . . . . . . . . . . . . . .15-17
Modelosparainteriores . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Modelosparaexteriores . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-17
Pruebadeestaciones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Cmo obtener los mejores resultados de su programador Rain Dial . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-19
Ejemplodeunplanderiego . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Indicaciones en pantalla . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20-21
Procedimientos bsicos de programacin . . . . . . . . . . . . . . . . . . . . .22-25
Ajustedelafechaylahoraactuales . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Ajustedeltiempoderiegodelasvlvulas . . . . . . . . . . . . . . . . . . . . . . 22
Ajustedelashorasdearranquedelosprogramas . . . . . . . . . . . . . . . 23
Ajustedelcalendariodedasderiego . . . . . . . . . . . . . . . . . . . .23-25
ParaprogramaruncalendariodeltipoDasdelasemana: . . . . . . 23
ParaprogramaruncalendariodeltipoSaltarDas: . . . . . . . . . . . . 24
ParaprogramaruncalendariodeltipoDaspares/impares . . . .24-25
Exclusindedas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
ii
FContenido
-
Funciones especiales . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26-29
Suspensintemporalporlluvia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Ajustesporcentuales . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26-28
ParaaplicarunAjusteporcentualbsico: . . . . . . . . . . . . . . . . . . . 27
ParaaplicarunAjusteporcentualmensual: . . . . . . . . . . . . . . . .27-28
Apilamiento/Solapamiento . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Retardoestacin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
ControldelabombaduranteelperiododeRetardoestacin . . . . . . . 30
OpcindeControldelabomba . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Interruptor automtico . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Sustitucin de fusibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Operaciones manuales . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3233
Operacinsemiautomticadeprogramas . . . . . . . . . . . . . . . . . . . . . . 32
Operacinmanualdeestaciones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Borrar la memoria de programas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Restaurar los Ajustes predeterminados de fbrica del Rain Dial-R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Solucin de Problemas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Informacin de contacto . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Especificaciones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Normativa FCC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
1
-
F Introduccin al controlador Rain Dial
Para obtener las mximas ventajas de su nuevo controlador Rain Dial-R, dedique unos momentos a familiarizarse con sus muchas funciones:
Diseo modular Facilitaelaccesoalosterminalesdeconexindelasvlvulasyalcompartimientodelaspilas .Elmdulodecontrolencajaapresinypuederetirarsefcilmenteparalaprogramacin"desdecasa" .
Preparado para el control remoto IncorporaunconectorRJ-11paralaconexindirectadelossistemasdecontrolremotodemanoIrritrolCMR-KIToKSR-KIT .
Memoria no voltil Guardalainformacindelosprogramasderiegoenmemoriaduranteaos sin electricidad!
Super Cap" Unafuentedealimentacinderespaldoquemantienelafechaylahoraactualesdurantehasta24horasencasodeuncortedeenergaelctrica .
Pila de respaldo Mantienelafechaylahoraactualesdurantecortesdeenergaelctricademsde24horas .Asimismo,permiteprogramarelcontroladorantesdeinstalarloconelsistema"ArmchairProgramming" .
Tres programas de riego independientes Permitedisearprogramasderiegoautomticoespecficamenteparadiferenteszonaspaisajsticas,porejemplo,cspedes,arbustosorboles .
Tres horas de arranque por programa Permiteponerenmarchacadaprogramaautomticohastatresvecesencadadaderiegoprogramado .
Programacin Saltar Das Permiteprogramarlosdasderiegoporintervalos,desde1(todoslosdas)a31(unavezcada31das) .
Programacin en das Pares/Impares Permitedefinirunprogramaderiegosolamenteendasparesosolamenteendasimpares .
Exclusin de das PermiteexcluirdasespecficosdeunprogramadedasPares/imparesoSaltarDas .
Apilamiento/Solapamiento de programas Permiterestringirlaoperacinaunasolaestacinounsoloprogramaalavez(apilamiento)ohabilitarhastatresProgramasotresestacionesdeformaconcurrente(solapamiento) .
Funcin Prueba de estaciones Unacmodafuncindeprueba,queponeenmarchacadaestacinsecuencialmenteduranteuntiempoderiegoseleccionado,de1a10minutos .Perfecto para instalaciones nuevas!
Programacin en tiempo real Permitemodificarlaprogramacinencualquiermomentoincluso durante el riego!
2
-
Activacin de estaciones en modo automtico, semiautomtico y manual . Avance manual Permiteavanzarmanualmentelasecuenciadeestaciones
durantelaoperacin(manualoautomtica) .
Desconectado o Stop Detieneinmediatamentetodaactividadderiegosinmodificarlaprogramacin .
Cuatro opciones para eliminar rpidamente horas de arranque Existencuatroposicionesde"Desconectado"enlapantalladehorasdearranque,quepermiteneliminarhorasdearranquenodeseadas,reduciendodeformasignificativalosdesplazamientosnecesarios .
Suspensin temporal por lluvia Permitesuspenderelriegoautomticoduranteunperiodode1a9das,yluegoreanudarautomticamenteelriegoprogramado .
Ajuste porcentual PermiteajustarproporcionalmenteeltiempoderiegodetodaslasestacionesdeunProgramadesde0(desactivado)a200% .Adems,puedeaplicarseunAjusteporcentualaprogramasindividualesenmesesespecficossisedeseaaplicarunajusteporcentualestacional .Setratadeunafuncinmuyinteresantequefavoreceelusointeligentedelagua .
Activar/Desactivar VM/Bomba por estacin PermiteactivarlaVlvulamaestra/Bombaporestacionesindividuales .
Retardo en la secuencia de estaciones Proporcionaunretardoajustableentreestacionesdurantelasecuenciadeactivacinparaajustarsealasnecesidadesdevlvulasdecierrelentooperodosderecuperacindepozos .
Control de VM/Bomba durante el retardo de estacinPermiteactivarodesactivarlaVlvulamaestra/BombaduranteelperiododeRetardoestacin .Rain Dial-R le permite elegir!
Proteccin integrada de circuitosAyudaaprotegerloscomponenteselctricosdelcontroladorcontradaoscausadosporsobrecargaselctricasorayos .
Interruptor automtico Permitequeelprogramadordetecteypaseporaltocualquierestacinquetengauncortocircuitoounsolenoideaveriado .Muestra"FUS"yelnmerodelaestacinafectadaparafacilitarlaidentificacinysolucindelproblema .
Borrar memoria de programa Permiteborrarlamemoriadeunprogramaindividualsinafectaraotrosprogramas .
Restaurar los valores de fbrica Permiterecuperarfcilmentelosparmetrosdeoperacinoriginalesdelafbrica,siesnecesario .
3
-
F Cmo empezar
Instalacin de la pila y programacin desde casa
Lainstalacindelapilade9V(asuministrarporelusuario)tienedosfuncionesimportantes:primero,permitecompletarlaprogramacindeRainDial-Rantesdesuinstalacin,ysegundo,mantieneelmdulodecontrolsincronizadoconlafechayhoraactualesduranteposiblescortesdeenergaelctricademsde24horasdeduracin .Nota: La pila no es capaz de activar las vlvulas de los aspersores. Es necesario conectar el controlador al suministro elctrico de corriente alterna para que pueda activar las vlvulas.Elmdulodecontrolestdiseadoparapoderserextradofcilmente,pudindoseprogramarcompletamenteenunlugarmscmodo,porejemplo,ensusillnfavorito .Pararetirarelmdulodecontrol,simplementedesenchufeelconectordelcableplanodelatarjetadelcircuitoimpreso,luegosepareelmdulocuidadosamentedelasbisagrasapresin .RainDial-Rincorporaunamemorianovoltil,quemantieneintactalainformacindelaprogramacin,inclusosilapilaseagotaoesdesconectada .
Instalacin de la pila1 . Abralapuertadelcontrolador .2 . Abraelmdulodecontrolsujetndoloporelbordederecho(enelmodelo
paraexteriores,presionelapestaadeliberacindelmdulo) .3 . Retirelatapadelcompartimientodelapilapresionandohaciaabajoy
haciafueraenelbordesuperiordelamisma .VerlaFigura 1 .4 . Enchufeelconectorenunapilaalcalinade9V .5 . Coloquelapilaenelcompartimientoyvuelvaacolocarlatapa .6 . Lapantallaempezaraparpadearconelmensaje12:00 AM(pulse
cualquierteclaparadetenerla) . Nota: Para empezar a configurar un Programa de riego, consulte
"Procedimientos de programacin bsicos" en la pgina 22.
CUIDADO: Para evitar los peligros que pueden suponer la instalacin de pilas del tipo incorrecto, cambie la pila siempre por otra del mismo tipo o de un tipo equivalente . Elimine las pilas usadas correctamente, siguiendo las recomendaciones del fabricante de las mismas .
4
-
EARTHGROUND
MV/PUMP
7 8 9 10 11 12
1 2 3 4 5 6
24 VACVC
5
Figura 1
Pila alcalina de 9 voltios (no incluida)
Tapa del compar-timiento de la pila
-
Descripcin general: Interfaz del mdulo de control
1 - Interruptor de Programa Uninterruptordeslizantedetresposicionesqueseutilizapara
seleccionarelprogramaA,BoCparasuconfiguracin,repasodeprogramasuoperacinmanual .
2 - Pantalla LCD ElpanelLCDdealtocontrastemuestratodalainformacinsobrelos
programasysobreelfuncionamientodelcontrolador .
3 - Teclas +/- Estasteclasseutilizanparaaumentaroreducirlosvaloresmostrados
enlapantalladurantelaconfiguracin,laprogramacinylasoperacionesmanuales .Losvaloresseajustandeunoenuno(pulsarysoltar)oenmododeavancerpido(pulsarymantenerpulsado) .
4 - Dial Uninterruptorrotativocon25posiciones,utilizadoparaseleccionar
estaciones,horasdearranque,dasderiegoyfuncionesespecialesdurantelaconfiguracin,laprogramacinylasoperacionesmanuales .
5 - Tecla Manual Seutilizaparainiciarycontrolarlaactivacinmanualdelas
estaciones .Tambinsirvecomotecladeavancedurantediversasoperacionesdeconfiguracin,programacinymanuales .
6 - Interruptor de funcin Uninterruptordeslizantedetresposicionesutilizadoparaseleccionar
entrelostresmodosdefuncionamientodelcontrolador: Off or Stop Detienetodaslasoperacionesderiegoactualmenteen
marcha,eimpidetodaoperacinautomticaomanual . Set Programs Permiteseleccionarymodificarlosvaloresde
configuracindelosprogramasderiego . Run or Manual Laposicinnormaldelinterruptorparatodaslas
operacionesderiegoautomticasymanuales .
7 - Tecla de arranque semiautomtico Seutilizaparaarrancarmanualmenteunprogramaderiego
automtico .SeutilizatambinparainiciarlaPruebadefuncionamientodeestaciones .
6
-
7
Figura 2
1
2
3
4
5
6
7
-
Descripcin general: Componentes internos del controlador
1 - Compartimiento de la pila Latapaapresinofreceunaccesofcilalapilaalcalinade9V .
2 - Cable plano del mdulo de control Permitedesconectarrpidamenteelmdulodecontroldelarmariopara
facilitarlaprogramacindesdecasaoelmantenimiento .
3 - Terminal de puesta a tierra Terminalparalaconexindeuncabledetierra .
4 - Interruptor de anulacin del sensor Interruptorquecontrolalaentradadelsensor(opcional)delluvia/heladas . 5 - Fusible de seguridad Unfusibledefundidolentode2Aqueprotegeelcontroladorcontra
sobrecargasporcortocircuitoenelsuministroelctricode24VCA .
6 - Terminales de conexin del transformador de corriente (24 VCA) Terminalesdeconexinparaloscablesdeltransformadorde24VCA,ypunto
deconexinparalaalimentacindelcontrolremotoopcionalCMR-KIT . 7 - Terminal comn de las vlvulas (VC) Terminalparalaconexindelcablecomn(campo)delasvlvulas .
8 - Terminales del sensor de lluvia (Sensor) TerminalesparalaconexindeloscablesdelRainSensorTMmodelos
RS500,RS1000,oRFS1000deIrritrol(opcionales) .
9 - Puente de los terminales del sensor PuentedelosterminalesdelsensorSeretiranicamenteparaconectar
unsensordelluviaodelluvia/heladas)
10 - Terminal de vlvula maestra/bomba (MV/PUMP) TerminalparalaconexindeloscablesdelaVlvulamaestraoRelde
arranquedebomba(opcional) .(ElpuentedelosterminalesdelsensorseretiranicamenteparaefectuarlaconexindelRainSensor .)
11 - Terminales de vlvulas TerminalesparalaconexindelasvlvulasUnterminalparacada
vlvula .(LadisposicindelosterminalesvarasegnelmodeloElmodeloilustradoeselde12estaciones .)
12 - Conector para el control remoto de mano Controldeconexinmodularparaelsistemadecontrolremotodemano
modelosCMR-KIToKSR-KIT-KdeIrritrol .
8
-
9
1 2 3 4
5
6
7
8
9
1011
Figura 3
12
-
F Procedimientos de instalacin
wInstalacin del armario del ControladorSeleccioneunlugarprotegidoparalainstalacindelmodeloparainterioresdelRainDial-R,comoporejemploungarajeocuartodemquinas,preferentementeamenosde5'(1,5m)deunatomadecorrienteelctricacontomadetierra .Paramodelosdeexteriores,seleccioneunlugarquelosprotejacontralaexposicindirectaalaluzsolaryelcontactoconelaguaderiegopulverizada,queestaunadistanciamnimade5'(1,5m)decualquierequipoconmotor .1 . Atornilleeltornillodeaceroinoxidablesuministradoenunmontantedepareda
unaalturacmoda,dejandoexpuestoaproximadamente1/4"(6,4mm)deltornillo . Nota: Utilice anclajes de tornillo para la instalacin sobre paredes de cartn-yeso
o de obra. 2 . Cuelgueelprogramadoreneltornillousandolaranuraenformadebocallave .3 . Sujeteelprogramadorconunoodostornilloscolocadosenlostaladrosde
montajeinferiores . Nota: Los taladros de montaje inferiores del armario para exteriores estn
obturados por una lmina fina de plstico que se penetra fcilmente al instalar el tornillo de montaje.
wConexin del cableado de control de las vlvulasParaobtenerlosmejoresresultados,utilicecabledeconexindiseadoespecficamenteparasistemasderiegoautomtico .Utilicecablede18AWGparadistanciasdehasta800'delcontrolador,ocablemsgruesode14AWG(2,0mm2)
paradistanciasdehasta2000' .Serequiereuncableindividualparacadavlvula(yrel)yalmenosuncablecomn(retorno) .Nota: Si es necesario instalar conductos para el cableado, instlelos ahora. Para la instalacin de conductos, utilice el taladro de acceso de 3/4" (19 mm) del armario para interiores, o el orificio roscado de 1,25 "NPT del armario para exteriores. 1 . Tiendaelcabledecontroldesdeelcontroladorhastalasvlvulas .2 . Conecteuncabledecontrolindividualacualquieradeloscablesdelsolenoidede
cadavlvula .3 . Conecteelotrocabledelsolenoidedecadavlvulaauncableindividualpara
formaruncablecomn(deretorno) . Nota: Para evitar la corrosin y posibles cortocircuitos, utilice conectores de cable
impermeables en todos los empalmes exteriores. Anote el color del hilo utilizado para cada vlvula as como su zona de riego
correspondiente para su referencia al hacer las conexiones en el controlador.10
-
4 . Paseelcablealinteriordelprogramadoratravsdelaaberturamayordelabasedelarmariodelcontroladoroatravsdelconducto,siseinstal .Retirelacubiertadelcableparadejarexpuestoaproximadamente8"deloshilos .Retirecuidadosamente3/8"deaislamientodelextremodecadahiloquesevaaconectar .
5 . Conecteelcabledecadavlvulaalterminalnumeradoenelordensecuencialpreferidoparasuoperacin .
6 . ConecteelcablecomnalterminalmarcadoVC .7 . Ensucaso,conecteunhilodelcabledecontroldelavlvulamaestraodelrelde
arranquedebombaalterminalmarcado"MV/PUMP",yelotrohiloalcablecomndelasvlvulas .
Nota: El controlador no suministra la potencia necesaria para activar una bomba. El rel de arranque de la bomba debe tener una tensin de bobina nominal de 24 VCA, con una potencia mxima de 0,375 A.
EARTHGROUND
MV/Pump Sensor
+ -
7 8 9 10 11 12
1 2 3 4 5 6
24 VACVC
11
Figura 4
Vlvulas de control de los aspersores
Hilo comn
Rel de arranque de bomba o vlvula maestra
1
2
3
MV
Rel 24 V
Terminal de vlvula maestra/bomba
Terminal comn de las vlvulas
-
Conexin de un sensor de lluvia (opcional) ElRainDial-RestdiseadoparafuncionarconjuntamenteconelRainSensormodelosRS500,RS1000oelsensordelluvia/heladaRFS1000deIrritrolpararestringirelriegocuandosecumplendeterminadoslmitesdehumedady/otemperatura .Nota: Si va a conectar otra marca de sensor de lluvia, asegrese de que sea compatible con un circuito de interruptor normalmente cerrado.
IMPORTANTE: Si no se instala un sensor de lluvia, deje conectado el cable puente en los terminales del sensor y el interruptor Sensor en la posicin "Bypass . Si no se cumple alguna de estas dos condiciones, la operacin automtica y manual estar desactivada . 1 . Introduzcaelcabledelsensorporlaparteinferiordelarmario .
2 . Aflojelosterminalesdelsensoryretireelcablepuente .
3 . Consultelasinstruccionesdeinstalacinsuministradasconelsensordelluvia,yconecteloscablessegnlasinstrucciones .
4 . PongaelinterruptorSensorenlaposicinActive . Nota: Cuando el sensor de lluvia est activado, se
suspenden todas las operaciones de riego y se muestra SEn (Sensor) (en la posicin Current Time del Dial).
EARTHGROUND
MV/Pump Sensor
+ -
7 8 9 10 11 12
1 2 3 4 5 6
24 VACVC
12
Figura 5
Sin cable puente
-
Conexin de una unidad de control remoto (opcional)ElcontroladorRainDial-RestpreparadoparaelcontrolremotoyestotalmentecompatibleconambosmodelosdecontrolremotodemanoIrritrol:elmodeloresidencialdecortoalcanceKSR-KIT-K,yelmodelocomercialdelargoalcanceCMR-1-KIT .Ambossistemasdemanoofrecenfuncionessimilaresdecontrolremoto .Laguadelusuariosuministradaconcadacontrolremotocontieneinformacincompleta .
Segnsemuestraenlailustracinsiguiente,laclavijadelreceptorKSR-KIT-KseenchufasimplementeenelconectordelapartetraseradelmdulodecontroldelRainDial-R .ElreceptordelCMR-1-KITtambindebeconectarsealosterminalesde24VCA .
Nota: Los receptores/clavijas de ambos modelos de control remoto son parecidos, pero no son intercambiables.
EARTHGROUND
MV/Pump Sensor
+ -
7 8 9 10 11 12
1 2 3 4 5 6
24 VACVC
13
Figura 6
Conector CMR-CC del control remoto CMR-1-KIT
Conector CA-03 del control remoto KSR-KIT .
-
Conexin a una toma de tierraNota: Para que los componentes de proteccin contra sobrecargas de su Rain Dial-R funcionen correctamente, el controlador debe conectarse a un dispositivo de tierra, como por ejemplo una pica de tierra revestida de cobre o una tubera de agua metlica, usando cable de cobre macizo. Esta conexin es especialmente importante cuando se instala el controlador en una zona propensa a rayos .
1 . Conecteuncabledecobremacizode1216AWG(2mm21,3mm2)aldispositivodetierrayllveloalcontroladoratravsdelaaberturadelabasedelarmario .
2 . ConecteelcabledetierraalterminalmarcadoEarthGround .
EARTHGROUND
MV/Pump Sensor
+ -
7 8 9 10 11 12
1 2 3 4 5 6
24 VACVC
Tubera de agua metlica
Pica de tierra de 2,4 m revestida de cobre (en suelo hm-edo)
14
Figura 7
-
Conexin del suministro elctrico Modelos para interiores 1 . Introduzcaelcabledeltransformadorexternoatravsdeltaladropequeo
provistoenlaparteinferiordelarmario .
2 . Hagaunnudoenelcableparaprotegerlocontratirones,yconecteloscablesalosterminalesmarcados"24VCA"(encualquierorden) .
3 . Cierreelmdulodecontrolyenchufeeltransformadorenunatomadecorriente .Elcontroladorestpreparadoparasuprogramacnyuso .
Nota: Para hacer una prueba inmediata del sistema de control de riego Rain Dial-R, consulte "Prueba de funcionamiento de estaciones" en la pgina 17.
EARTHGROUND
MV/Pump Sensor
+ -
7 8 9 10 11 12
1 2 3 4 5 6
24 VACVC
Figura 8
15
Nudo de segu-ridad
Nudo de seguridad
Transformador de 24 VCA, 30VA
-
Conexin del suministro elctrico Modelos para exteriores
ADVERTENCIA: Todos los componentes elctricos y mtodos de conexin deben cumplir la normativa nacional y local aplicable sobre instalaciones elctricas, incluyendo la instalacin por personal cualificado . Estas normas pueden exigir la instalacin de una caja de empalmes en el conector NPT de 1/2" (13 mm) del controlador y algn medio de desconectar el suministro elctrico CA en el cableado fijo, con una separacin entre contactos de al menos 0,120" (3 mm) en los polos de fase y neutro . El cable de conexin debe contar con aislamiento resistente a 105 C como mnimo .
El controlador debe conectarse a una toma de corriente con tierra . No lo conecte a una fase de un suministro elctrico trifsico usado por una bomba u otro equipo elctrico .Antes de conectar los cables del controlador, compruebe que la electricidad ha sido desconectada en la toma de corriente, usando un voltmetro de corriente alterna .1 . Conecteunregistrodeconductode1/2"(13mm)NPTalconectorroscado
deltransformador .Desdeelregistrodeconducto,instaleelconductoelctricohastalatomadecorrienteelctricaCA(deacuerdoconlanormativasobreinstalacioneselctricas) .
2 . Pasecablede14AWGatravsdelconductohastaelregistro .3 . Usandoconectoresdecable,conecteloscablessegnsemuestraenla
Figura 10 .4 . Cierreyafianceelregistrodelconducto .5 . Enciendaelsuministroelctricodelcontroladorycompruebeelfuncionamiento
delcontrolador .Sielcontroladornofunciona,desconecteelsuministroelctricoensuorigenyhagaqueuninstaladorelctricocualificadocompruebesihayalgnposiblecortocircuito .
CUIDADO: Para asegurar la mxima proteccin de los componentes electrnicos del controlador cuando est instalado en el exterior, mantenga siempre cerrada la cubierta del armario, con llave siempre que sea posible . Guarde las llaves del armario en un lugar seguro y de fcil acceso .
16
Figura 9
Llave
-
Prueba de estaciones
LafuncinPrueba de estacionesdelcontroladorlepermitecomprobarrpidamenteelfuncionamientocorrectodelasvlvulasdespusdelainstalacininicialodecualquiermantenimiento .Elciclodepruebaactivatodaslasvlvulassecuencialmenteduranteuntiempoderiegoprovisional,ajustablede1-10minutos .
1 . PongaelinterruptordeFuncinenlaposicinSet ProgramsoRun .2 . GireelDialalaposicinSkip DaysSpecial Functions .3 . PulselateclaManualunavezparaseleccionarla
pantalladepruebadeladerecha .
4 . Pordefecto,eltiempodefuncionamientodelapruebaesde2minutos .Paraajustareltiempoderiegoentre1y10minutos,pulselatecla o .
5 . PulselateclaSemi-Autoparaarrancarelcicloderiego .SeactivarlaEstacin1 .
6 . GireelDialalaposicinCurrent Time .Lapantallaindicarlahoraactualdelreloj(inicialmentelas12:00PM)ylaestacin1 .
7 . Paraavanzarmanualmenteporlasecuenciadeestaciones,pulselateclaManual .
RD-1200
A-+
B-C-
MANUAL
TodaySun
Mon
Wed
Thu
2
3
4
5
6
7
8
9
1011123
21
PM
SC
HE
DU
LE
STARTTIMES
VA
LV
ER
UN
TIM
ES
17
Figura 10
1 2 3 4 5 6 7 8 9 10 11 12
Tierra a Verde o Verde/Amarillo
Fase o L2 a Negro o Marrn
Neutro o L1 a Blanco o Azul
Registro de conducto
Conducto elctrico
-
F Cmo obtener los mejores resultados de su controlador Rain Dial-R Qu es un ciclo automtico de riego programado? Unprogramaderiegoautomticoempiezaalaprimerahoradearranqueasignadaenundaderiegoprogramado .LavlvulaconelnmeromsbajoasignadaalProgramaseactivayhacefuncionarlosaspersoresduranteeltiempoderiegoespecificado .Cuandotermine,lasiguientevlvulaenordennumrico(quetengauntiempoderiegoasignadoenelprograma)empiezaafuncionar .ElcicloderiegoprogramadocontinahastaquesehayanactivadotodaslasvlvulasquetenganasignadountiempoderiegoenelPrograma . Por qu tres programas? Unpaisajeresidencialtpicoincluyediferentesseccionesdecsped,arbustos,rbolesyvegetacindesuelo,todaslascualesnecesitanregarseusandoprogramasdiferentesparamantenerlasaluddelasplantasyunaconservacinptima .Paralograresto,elRainDial-Rofrecetresprogramasderiegoindependientes:A,ByC .Elejemplosiguientemuestracmopuedenutilizarsemltiplesprogramasparaobteneresteresultadoconfacilidad: Programa Hora de inicio Vlvula N Ubicacin Tiempo de riego Calendario
A (N1)5:00AM 1 Cspeddelantero15min. Impar 2 Jardntrasero 15min. Impar 3 Jardnlateral 10min. Impar B (N1)3:00PM 4 rboles(goteo) 2h Lun C (N1)4:00AM 5 Jardn 5min. SaltarDas,1 (N2)7:30PM 5 Jardn 5min. SaltarDas,1
18
-
Evite horas de arranque inesperadas Esposibleprogramarunasegundahoradearranquequeempieceantesdequesehayaacabadoelciclodelaprimerahoradearranque .Siestoocurre,sedemoraelarranquedelsegundociclohastaquesehayacompletadoelprimero,demaneraquelahoradearranquepuedenocoincidirconlahoraesperada .Adems,unaumentodeltiempoderiegodebidoalafuncindeajusteporcentualpuedecausarunsolapamientoqueretrasalasiguientehoradearranqueprogramada .
Evite regar en un da no de riego Uncicloderiegoquecontinamsalldelamedianochesecompletarsintenerencuentasieldasiguienteesundaderiegoprogramado .
Evite regar en exceso Pordefecto,losprogramasA,B,yCpuedenprogramarseparaestaractivadosdeformaconcurrente(solapamiento) .EstecomportamientopuederestringirseseleccionandolaopcinApilamientodeprogramas(verpgina28) .Sihayhorasdearranqueintroducidasencualquierprograma,seiniciarnciclosderiegoautomticamenteaesashoras .Elusodemltiplesprogramaspermitequelasdiferentesestacionesdevlvulasrieguenconcalendariosdiferentes,opermiteaplicarunriegosuplementariosinobastaunsoloprograma .Sinecesitariegoadicional,utilicemsdeunahoradearranqueoutilicelafuncindeAjusteporcentualparaaumentareltiempoderiegodeunaestacindeterminada .
Evite crear una condicin de baja presin del agua Lashorasdearranqueasignadasadiferentesprogramassonindependientesentres .Siustedestablecehorasdearranqueidnticasosolapadas,puedeactivarsemsdeunavlvulaalmismotiempo .Elcaudaltotalpuedesuperarelsuministrodeaguadisponible .Paraevitarestasituacin,dejemstiempoentrehorasdearranqueparareducirelnmerodevlvulasenfuncionamientoencadamomento,yasegresedenoasignarlamismahoradearranqueamltiplesprogramas .
Arraigamiento de csped nuevo Esespecialmentetilestablecermltiplesciclosderiegocortoscadadaduranteelarraigamientodeuncspednuevo .
Ayuda con problemas elctricos ElRainDial-RmuestraelNmerodeestacinylapalabraFUSsisedetectauncortocircuitoenunavlvula .Sesaltarlaestacinencuestin,permitiendolaactivacindelasdemsestacionesdelcicloderiegoprogramado .
19
-
F Indicaciones en pantalla
Lossiguientesejemplosmuestranlainformacinproporcionadaenpantallaparaayudarleenlosdiferentesmodosdeprogramacin,configuracinyoperacin .
Modo Programacin (Funcin Set Programs)
Current Time(Horaactual)muestralahoraactual .
Valve Run Times(Tiemposderiegodelasvlvulas)muestraeltiempoderiegodelnmerodevlvulaseleccionado .Indica0159minutos,1,05,9horasuOff(desactivada) .
Start times(Horasdearranque)muestralashorasdearranqueasignadasalprogramaseleccionado .
Today(Hoy)muestraelDaActualdeuncalendarioDas de la semana,porejemploSu,Mo,(domingo,lunes)etc .,oeldaprogramadodeuncalendarioSaltar das(131) .
ScheduleMuestraONuOFFparacadadadeuncalendarioDas de la semana .CuandoseutilizauncalendarioPar/Impar,semuestraOdd(Impar),Even(Par)uOFF(Desactivado)paracadaestacin .CuandoseutilizauncalendarioSaltar das,semuestraOnce every (0131)(Unavezcada01-31) .
Funciones especiales (Dial Special Functions)
Ciclo de prueba de estacionessemuestranlosnmerosdetodaslasestacionesactivasenlapartesuperiordelapantalla .T:0110indicaenminutoseltiempoderiegoseleccionadoparaelciclodepruebas .
Ajuste porcentual (por programa)muestraelAjusteporcentualactual,uOFF(Desactivado) .SiseestutilizandounAjusteporcentualmensual,semuestra( ) .
Borrar memoria de programaCLrindicaqueestseleccionadalafuncinClearMemory(Borrarmemoria) .
Tiempo de recuperacin de pozoindicalademora(0059segundos,159minutoso1-2horas)entreestacionesenuncicloderiego .
20
1 2 3 4 5 6 7 8 9 10 11 12
-
Activacin de bomba durante Retardo estacin indicasilaactivacindelabombaestenOn(activada)uOff(desactivada)duranteelperiododeretardoentreestaciones .
Apilamiento/solapamiento de programasIndicasiestseleccionadoApilamiento(1:On)oSolapamiento(3:On) deprogramas .
Calendario Par/Impar IndicasiestseleccionadoelcalendarioOdd(impar)oEvn(par) .
Mes Muestraelmesactual .
Mes/da Muestraelmesyeldaactuales .
Ao Muestraelaoactual .
Suspensin temporal por lluviaIndicaelnmerodedas(09)desuspensindelaoperacinautomtica .
Ajuste porcentual mensual Indicaelestadodeajusteporcentual(On/Off)pormes(112)yelporcentaje(01200uOff)asignadoacadames .(Tambinpuedenajustarseahoraelmes,dayao .)
Modo de funcionamiento (Funcin Run) Modo automtico (Dial Hora Actual)Muestraelnmerode
lavlvulaactivaylahoraactual .(Dial Nmero de la vlvula activa)nmerodelavlvulaactiva,programaactualytiempoderiegorestante .
Nota: Si est activado Ajuste porcentual, se muestra el tiempo de riego ajustado.
Modo manual (Dial Nmero de vlvula activa)-semuestraelnmerodevlvula,M:yeltiempoderiegorestante .
Suspensin temporal por lluvia semuestraOF(desactivado)yelnmerodedasrestanteshastaquesereanudeelriego,alternandoconlahoraactual .
Interruptor automtico semuestra"FUS"yelnmerodelaestacinafectada,alternandoconlahoraactual .
21
-
F Procedimientos bsicos de programacin
Ajuste de la fecha y la hora actuales
1 . PongaelinterruptordeFuncinenlaposicinSet Programs(centro) .
2 . GireelDialalaposicinCurrent Time .
3 . Pulselatecla o paraestablecerlahoraactual(Nota:AM/PM) .
Nota: Al usar la tecla o , pulse y suelte la tecla para ajustar el valor en pasos, o pulse y mantenga pulsada la tecla para desplazarse rpidamente.
4 . GireelDialalaposicinToday .
5 . Pulselatecla o paraseleccionareldaactual(abreviatura) .
Nota: Si se utiliza un calendario de das Pares/Impares o Ajuste porcentual mensual, el da actual de la semana est preestablecido y no puede modificarse.
6 . GireelDialalaposicinCurrent Time .
7 . PongaelinterruptordeFuncinenlaposicinRun .
Nota: El signo de dos puntos (:) parpadeante indica la presencia de corriente alterna. Si el signo no parpadea, el controlador est funcionando con la pila solamente.
Ajuste del tiempo de riego de las vlvulas
Cadaestacinpuedetenerasignadountiempoderiegoindividualencadaprograma .Eltiempoderiegopuedeajustarsede159minutos(enincrementosde1minuto),ode15,9horas(enincrementosde1/10dehora) .
1 . PongaelinterruptordeFuncinenlaposicinSet Programs(centro) .
2 . SeleccioneelProgramaA,BoC .
3 . GireelDialparaseleccionarelnmerodelavlvulaaajustar .
4 . Pulselatecla o paraestablecerlahoradeiniciodeltiempoderiegodelavlvula .
5 . Repitalospasos3y4paratodaslasvlvulasquevayanaasignarsealprogramaseleccionado .
6 . Repitalospasos2-5paracadaprograma,segnseanecesario .
7 . Cuandotermine,gireelDialalaposicinCurrent Time(Horaactual) .
8 . PongaelinterruptordeFuncinenlaposicinRun .22
-
Ajuste de las horas de arranque de los programas
Cadaprogramapuedetenertreshorasdearranqueindependientes .Parapaisajesmaduros,unasolahoradearranqueporprogramasuelesersuficiente .Sielcspedesnuevo,elusodedosotreshorasdearranquecontiemposderiegocortospuedeproporcionarelriegoadicionalnecesarioparaelarraigamiento,concaudalesmenoresparaayudaraevitarescorrentasyerosin .1 . PongaelinterruptordeFuncinenlaposicinSet Programs .2 . SeleccioneelProgramaA,BoC .3 . GireelDialaStart Time1,2o3(Horadearranque1,2,3) .4 . Pulselatecla o paraestablecerlahoradearranque(Nota:AM/PM) . Nota: Para eliminar un tiempo de inicio, seleccione Off, situado entre
11.5912.00 y 5.59 6.00 (AM y PM).5 . Repitalospasos3y4paraajustarmshorasdearranqueparaestePrograma .6 . Repitalospasos2-5paracadaprograma,segnseanecesario .7 . Cuandotermine,gireelDialalaposicinCurrent Time(Horaactual) .8 . PongaelinterruptordeFuncinenlaposicinRun .
Ajuste del calendario de das de riego
PuedenprogramarsedasderiegoparacadaPrograma,usandounodelosmtodossiguientes: Das de la semanaProgramaelriegoendasespecficosdelasemana . Saltar dasProgramalosdasderiegoporintervalos,porejemplocadada
(01),dasalternos(02),etc . Da Par/ImparProgramalosdasderiegoenlosdasParesoImpares .Para