VAM I/O units

Publication version: VIO/en M/A003

User Manual

Page 2: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

Trace back information:Workspace Main version a100Checked in 2016-03-02Skribenta version 4.6.006

Page 3: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

Table of Contents

51 General .....................................................................................51.1 Legal notice ......................................................................51.2 Safety information and password protection ....................

82 Introduction .............................................................................82.1 Purpose ............................................................................82.2 Main properties ................................................................

103 User interface ..........................................................................113.1 VAM 3L fiber sensor I/O unit ............................................123.2 VAM 3LX fiber sensor I/O unit ..........................................133.3 VAM 10L point sensor I/O unit .........................................143.4 VAM 10LD point sensor I/O unit .......................................163.5 VAM 12L point sensor I/O unit .........................................173.6 VAM 12LD point sensor I/O unit .......................................193.7 VAM 4C current I/O unit ...................................................203.8 VAM 4CD current I/O unit ................................................213.9 VAMP 4R trip multiplier relay ...........................................

224 Programming switches ...........................................................224.1 Switches for arc sensor I/O units .....................................244.2 Switches for current I/O units ...........................................

275 Adjusting the overcurrent setting ..........................................

286 BI/BO connection ....................................................................

297 Connections .............................................................................307.1 VAM 3L / VAM 3LX interfaces ..........................................317.2 VAM 10L interfaces ..........................................................327.3 VAM 10LD interfaces .......................................................337.4 VAM 12L interfaces ..........................................................347.5 VAM 12LD interfaces .......................................................357.6 VAM 4C interfaces ...........................................................367.7 VAM 4CD interfaces .........................................................377.8 VAMP 4R interfaces .........................................................

388 I/O Technical data ....................................................................388.1 Connections .....................................................................398.2 Auxiliary power supply .....................................................398.3 Digital inputs ....................................................................408.4 Trip contacts .....................................................................418.5 Disturbance tests .............................................................428.6 Electrical safety tests .......................................................

3VIO/en M/A003

Table of Contents

Page 4: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

428.7 Environmental conditions .................................................428.8 Package ...........................................................................438.9 Casing ..............................................................................

449 Construction ............................................................................449.1 Dimensional drawings ......................................................449.1.1 VAM 3L / 3LX Din rail mounting ..........................459.1.2 VAM 10L Din rail mounting ..................................469.1.3 VAM 10LD Flush mounting .................................479.1.4 VAM 12L Din rail mounting ..................................489.1.5 VAM 12LD Flush mounting .................................499.1.6 VAM 4C Din rail mounting ...................................509.1.7 VAM 4CD Flush mounting ...................................519.1.8 VAMP 4R Din rail mounting .................................529.1.9 VA 1 DA ...............................................................529.1.10 VA 1 EH ...............................................................539.1.11 VYX 001 ..............................................................549.1.12 VYX 002 ..............................................................559.2 I/O unit mounting and wiring ............................................

569.2.1 VAM 10L, VAM 12L, VAM 4C, VAM 3L, VAM

3LX ......................................................................569.2.2 VAM 10LD, VAM 12LD, VAM 4CD ......................569.3 Connecting the VAMP 321 I/O units ................................

569.4 Connecting the secondary circuits of the current

transformers (VAM 4C / VAM 4CD only) ..........................589.5 Connecting the trip circuits of the circuit breakers ...........599.6 Connecting between the central unit and the I/O unit ......609.7 Connecting separate auxiliary supplies ...........................629.8 VAMP 4R .........................................................................639.9 Wiring multiple central units .............................................639.10 Arc sensors ......................................................................649.10.1 VA 1 DA ...............................................................659.10.2 VA 1 EH ...............................................................669.10.3 ARC-SLx .............................................................669.10.4 VA 1 DP ...............................................................

6810 Order information ....................................................................

6911 Glossary ...................................................................................

VIO/en M/A0034

Table of Contents

Page 5: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

1 General

1.1 Legal noticeCopyright

2015 Schneider Electric. All rights reserved.

Disclaimer

No responsibility is assumed by Schneider Electric for anyconsequences arising out of the use of this document. This documentis not intended as an instruction manual for untrained persons. Thisdocument gives instructions on device installation, commissioningand operation. However, the manual cannot cover all conceivablecircumstances or include detailed information on all topics. In theevent of questions or specific problems, do not take any actionwithout proper authorization. Contact Schneider Electric and requestthe necessary information.

Contact information

35 rue Joseph Monier

92506 Rueil-Malmaison

FRANCE

Phone: +33 (0) 1 41 29 70 00

Fax: +33 (0) 1 41 29 71 00

www.schneider-electric.com

1.2 Safety information and passwordprotectionImportant Information

Read these instructions carefully and look at the equipment tobecome familiar with the device before trying to install, operate,service or maintain it. The following special messages may appearthroughout this bulletin or on the equipment to warn of potentialhazards or to call attention to information that clarifies or simplifiesa procedure.

5VIO/en M/A003

1 General

Page 6: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

The addition of either symbol to a “Danger” or “Warning” safety labelindicates that an electrical hazard exists which will result in personalinjury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potentialpersonal injury hazards. Obey all safety messages that follow thissymbol to avoid possible injury or death.

DANGERDANGER indicates an imminently hazardous situation which, ifnot avoided, will result in death or serious injury.

WARNINGWARNING indicates a potentially hazardous situation which, ifnot avoided, can result in death or serious injury.

CAUTIONCAUTION indicates a potentially hazardous situation which, ifnot avoided, can result in minor or moderate injury.

NOTICE

NOTICE is used to address practices not related to physicalinjury.

User qualification

Electrical equipment should be installed, operated, serviced, andmaintained only by trained and qualified personnel. No responsibilityis assumed by Schneider Electric for any consequences arising outof the use of this material. A qualified person is one who has skillsand knowledge related to the construction, installation, and operationof electrical equipment and has received safety training to recognizeand avoid the hazards involved.

Password protection

Use IED's password protection feature in order to protect untrainedperson interacting this device.

VIO/en M/A0036

1 General1.2 Safety information and password protection

Page 7: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

WARNINGWORKING ON ENERGIZED EQUIPMENT

Do not choose lower Personal Protection Equipment whileworking on energized equipment.

Failure to follow these instructions can result in death orserious injury.

7VIO/en M/A003

1.2 Safety information and password protection1 General

Page 8: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

2 Introduction

This User’s Manual contains a functional description of the VAM I/Ounits and technical data.

2.1 PurposeThe main purpose of the VAM I/O units is to detect arc light or shortcircuit current and deliver this information (zone information) to thearc protection central unit and the other VAM I/O units. AdditionallyVAM I/O units can be used for tripping appropriate circuit breakers.

This document is not applicable in North American market.

2.2 Main propertiesArc flash protection system is a modular system consisting of acentral unit, I/O units and arc sensors.

Due to its modularity, the system is suitable for a range of arcprotection applications, from simple systems with one central unitand one I/O unit to more complex solutions comprising several centralunits used for selective arc protection.

The I/O unit VAM 10L / VAM 10LD, VAM 12L / VAM 12LD servesas link between the system’s point sensors and the central unit. EachI/O unit has connections for ten arc sensors, one portable pin sensorand one trip output.

The I/O unit VAM 3L/VAM3LX serves as link between the system’sfibre sensors and the central unit. Each I/O unit has connections forthree arc sensors, one pin sensor and one trip output.

The I/O unit VAM 4C / VAM 4CD serves as link between the system’scurrent inputs and the central unit. Each I/O unit has connections forthree current transformers and one trip output.

The arc sensor VA 1 DA is activated by strong light. The sensortransforms the light information into the current signal, which isforwarded through the I/O unit to the central unit. The arc sensor VA1 EH also operates on the same principle.

The pin sensor VA 1 DP has the same functions as an arc sensorbut can be temporarily connected to an I/O unit. The sensor can befixed to the breast pocket of a technician to improve safety whenworking with live switchgear.

VIO/en M/A0038

2 Introduction

Page 9: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

The door mounted VAM I/O units with the letter D in the typedesignations VAM 10LD, VAM 12LD and VAM 4CD are door mountedversions for the corresponding VAM 10L, VAM 12 L and VAM 4Cunits. The functionality is exactly the same.

9VIO/en M/A003

2.2 Main properties2 Introduction

Page 10: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

3 User interface

Usually, there is no need to touch the front panel during normaloperation, since all the necessary information can be read from thecentral unit display. However, after a new installation or a systemexpand you will need to program certain functions (zone/address,trip output) in the I/O unit.

NOTE: If you unfasten the terminal blocks during installation, remember totighten the fixing screws after installation! Also tighten the screwseven if you did not unfasten the blocks.

VIO/en M/A00310

3 User interface

Page 11: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

3.1 VAM 3L fiber sensor I/O unit

SW1

Addr.

Zone

L+I / L

Latch

L>ext/Int

SENSOR

OK

ACT

TRIP

COM 1 COM 2

ON

COM

CH1 CH2 CH3

SENSOR INPUTS

R1 T1 R2 T2 R3 T3

VAM 3L

X216 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

1

12

3

4

5

6

7

9

10

11

8

2

1

2

3

4

5

6

7

8

OFF ON

Figure 3.1: VAM 3L fiber sensor I/O unit front panel

1. Connection for portable arc sensor (VA 1 DP)

2. Programming switches

3. POWER indicator light, indicates that the supply voltages of eachcomponent are in order.

4. COM indicator light, lit when the central units and I/O units arecommunicating.

5. ERROR indicator light, indicates an internal fault detected by thecomponent’s self-diagnostics. Such faults include faulty arcsensor or changes in the amount of sensors.

6. Connector sockets for the VX001 modular cables

7. LED lights indicating sensor activation

8. Terminals for three fibre sensors

9. Portable arc sensor VA 1 DP connected and operational

10. Portable arc sensor activated

11. I/O unit trip relay activated

12. Terminal block for external communication and BI/O channelsand trip signal

11VIO/en M/A003

3.1 VAM 3L fiber sensor I/O unit3 User interface

Page 12: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

3.2 VAM 3LX fiber sensor I/O unit

SW1

Addr.

Zone

L+I / LLatch

L>ext/Int

SENSOR

OK

ACT

TRIP

COM 1 COM 2

ON

COM

CH1 CH2 CH3

SENSOR INPUTS

R1 T1 R2 T2 R3 T3

VAM 3LX

X216 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

1

12

3

4

5

6

7

9

10

11

8

2

1

2

3

4

5

6

7

8

OFF ON

CH1 CH2 CH3Adj Adj Adj

Min. Max. Min. Max. Min. Max.

13

Figure 3.2: VAM 3LX fiber sensor I/O unit front panel

1. Connection for portable arc sensor (VA 1 DP)

2. Programming switches

3. POWER indicator light, indicates that the supply voltages of eachcomponent are in order.

4. COM indicator light, lit when the central units and I/O units arecommunicating.

5. ERROR indicator light, indicates an internal fault detected by thecomponent’s self-diagnostics. Such faults include faulty arcsensor or changes in the amount of sensors.

6. Connector sockets for the VX001 modular cables

7. LED lights indicating sensor activation

8. Terminals for three fibre sensors

9. Portable arc sensor VA 1 DP connected and operational

10. Portable arc sensor activated

11. I/O unit trip relay activated

12. Terminal block for external communication and BI/O channelsand trip signal

13. Sensitivity adjustments for each fibre sensor channels

VIO/en M/A00312

3 User interface3.2 VAM 3LX fiber sensor I/O unit

Page 13: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

3.3 VAM 10L point sensor I/O unit

SW1

SENSOR

OK

ACT

COM 1 COM 2

ON

COMTRIP

Addr.

Zone

L+I / L

Latch

L> ext/int

SENSOR INPUTS

1 2 3 4 5 6 7 8 9 10

X1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

X212345678910111213141516

VAM 10L

1

12

3

4

5

6

7

9

10

11

8

2

1

2

3

4

5

6

7

8

OFF ON

Figure 3.3: VAM 10L point sensor I/O unit front panel

1. Connection for portable arc sensor (VA 1 DP)

2. Programming switches

3. POWER indicator light, indicates that the supply voltages of eachcomponent are in order.

4. COM indicator light, lit when the central unit and I/O units arecommunicating.

5. ERROR indicator light, indicates an internal fault detected by thecomponent’s self-diagnostics. Such faults include faulty arcsensor or changes in the amount of sensors.

6. Connector sockets for the VX001 modular cables

7. LED lights indicating sensor activation

8. Terminal block for ten arc sensors

9. Portable arc sensor VA 1 DP connected and operational

10. Portable arc sensor activated

11. I/O unit trip relay activated

12. Terminal block for external communication and BI/O channelsand trip signal

13VIO/en M/A003

3.3 VAM 10L point sensor I/O unit3 User interface

Page 14: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

3.4 VAM 10LD point sensor I/O unit

12

8

SW1

SENSOR

OK

ACT

COM 2 COM 1

Addr.

Zone

L/L+I

Latch

L> Int/

Ext

SENSOR INPUTS

X11234567891011121314151617181920

X2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1

69

10

2

12345678

O N

VAM 10LDPoint sensor I/O unit

SENSOR INPUTS

1 2 3 4 5 6 7 8 9 10

7

COM

ON3

4

5ADDRESS NR 10

1. BB FEEDER 7

2. CB FEEDER 7

3. CC FEEDER 7

4. BB FEEDER 8

5. CB FEEDER 8

6. CC FEEDER 8

7. BB FEEDER 9

8. BB FEEDER 9

9. BB FEEDER 9

10. TIE BREAKER ID

TRIP

13

11

BACK PANEL

FRONT PANEL

Figure 3.4: VAM 10LD point sensor I/O unit front and back panel

1. Connection for portable arc sensor (VA 1 DP)

2. Programming switches

3. POWER indicator light, indicates that the supply voltages of eachcomponent are in order.

4. COM indicator light, lit when the central unit and I/O units arecommunicating.

5. ERROR indicator light, indicates an internal fault detected by thecomponent’s self-diagnostics. Such faults include faulty arcsensor or changes in the amount of sensors.

6. Connector sockets for the VX001 modular cables

7. LED lights indicating sensor activation

8. Terminal block for ten arc sensors

VIO/en M/A00314

3 User interface3.4 VAM 10LD point sensor I/O unit

Page 15: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9. Portable arc sensor VA 1 DP connected and operational

10. Portable arc sensor activated

11. I/O unit trip relay activated

12. Terminal block for external communication and BI/O channelsand trip signal

13. Text pocket for sensor specific labels.

15VIO/en M/A003

3.4 VAM 10LD point sensor I/O unit3 User interface

Page 16: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

3.5 VAM 12L point sensor I/O unitVAM 12L is primary design for selective feeder trip applications. Theunit comprises 3 electromechanical trip normally open contacts andone trip alarm change over contact.

The unit has 10 Arc sensor inputs. Tree sensors (of the ten) inputsare dedicated, and are controlling their own trip relay. The unit isideal for selective trip of cable compartment in case of an ARC fault.VAM 12L can selectively handle 3 feeders. The rest of the sensorscan then supervise the busbar and breaker compartments and willoperate in the zone selected by the unit address switches.

SW 1

SENSOR

OK

ACTON

COMTRIP

Addr

Zone

L+I / LLatch

L>ext/int

SENSOR INPUTS

1 2 3 4 5 6 7 8 9 10

X212345678910111213141516

VAM 12L

1

12

3

4

5

6

7

9

10

11

8

2

1

2

3

4

5

6

7

8

OFF ON

COM 1 COM 2

X1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Figure 3.5: VAM 12L point sensor I/O unit fron panel

1. Connection for portable arc sensor (VA 1 DP)

2. Programming switches

3. POWER indicator light, indicates that the supply voltages of eachcomponent are in order.

4. COM indicator light, lit when the central unit and I/O units arecommunicating.

5. ERROR indicator light, indicates an internal fault detected by thecomponent’s self-diagnostics. Such faults include faulty arcsensor or changes in the amount of sensors.

6. Connector sockets for the VX001 modular cables

7. LED lights indicating sensor activation

8. Terminal block for ten arc sensors

9. Portable arc sensor VA 1 DP connected and operational

10. Portable arc sensor activated

11. I/O unit trip relays activated

12. Terminal block for output relay

VIO/en M/A00316

3 User interface3.5 VAM 12L point sensor I/O unit

Page 17: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

3.6 VAM 12LD point sensor I/O unit

12

8

SW1

SENSOR

OK

ACT

COM 2 COM 1

Addr.

Zone

L/L+I

Latch

L> Int/

Ext

SENSOR INPUTS

X11234567891011121314151617181920

X2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1

69

10

2

12345678

O N

VAM 12LDPoint sensor I/O unit

SENSOR INPUTS

1 2 3 4 5 6 7 8 9 10

7

COM

ON3

4

5ADDRESS NR 10

1. BB FEEDER 7

2. CB FEEDER 7

3. CC FEEDER 7

4. BB FEEDER 8

5. CB FEEDER 8

6. CC FEEDER 8

7. BB FEEDER 9

8. BB FEEDER 9

9. BB FEEDER 9

10. TIE BREAKER ID

TRIP

13

11

BACK PANEL

FRONT PANEL

Figure 3.6: VAM 12LD point sensor I/O unit front and back panel

1. Connection for portable arc sensor (VA 1 DP)

2. Programming switches

3. POWER indicator light, indicates that the supply voltages of eachcomponent are in order.

4. COM indicator light, lit when the central unit and I/O units arecommunicating.

5. ERROR indicator light, indicates an internal fault detected by thecomponent’s self-diagnostics. Such faults include faulty arcsensor or changes in the amount of sensors.

6. Connector sockets for the VX001 modular cables

7. LED lights indicating sensor activation

8. Terminal block for ten arc sensors

17VIO/en M/A003

3.6 VAM 12LD point sensor I/O unit3 User interface

Page 18: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9. Portable arc sensor VA 1 DP connected and operational

10. Portable arc sensor activated

11. I/O unit trip relays activated

12. Terminal block for output relays

13. Text pocket for sensor specific labels.

VIO/en M/A00318

3 User interface3.6 VAM 12LD point sensor I/O unit

Page 19: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

3.7 VAM 4C current I/O unit

4.0

2.0

1.0

0.5

0.1

x In

ON

COM

COM 1 COM 2

Addr.

Zone2

Zone1

Zone4

Zone3

SW1

TRIP

VAM 4C

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X2

9 10

8 L1/L3 L2/IoX1

1

12

3

4

5

L1 L2 L3

CURRENT TRANSFORMER

6

11

2

1

2

3

4

5

6

7

8

OFF ON

7

SW2

1A/5A

Latch

I>in

I>out

6

3 1.0

x In

0.055

L1,L3 L2/Io

0.5

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4

ON

13

Figure 3.7: VAM 4C current I/O unit front panel

1. Programming switches

2. POWER indicator light, indicates the supply voltages of eachcomponent are in order.

3. COM indicator light, lit when the central units and I/O units arecommunicating.

4. ERROR indicator light, indicates an internal fault detected by thecomponent’s self-diagnostics. Such faults include faulty currenttransformer or phase current unbalance.

5. Connector sockets for the VX001 modular cables

6. LED lights indicating that I> stage has started

7. Terminals for three current transformers

8. Current transformer programming switches

9. Overcurrent setting knob (IL1, IL3), setting range 0.5 – 6 x IN10. Overcurrent setting knob (IL1, I0), setting range 0.05 – 5 x IN11. I/O unit trip relay activated

12. Terminal block for external communication and BI/O channelsand trip signal

13. Indicator leds for current setting

19VIO/en M/A003

3.7 VAM 4C current I/O unit3 User interface

Page 20: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

3.8 VAM 4CD current I/O unit

12

7

X1123456789101112

X2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

COM 2 COM 15

VAM 4CDCurrent I/O unit

- - - CURRENT TRANSFORMER - - -

L3L2L1

6

COM

ON2

3

4FEEDER: F06

ADDRESS: 33

ZONE: 1 & 2

I> PICK 2 X In-UP:

OTHER I: > EXT ON

14

TRIP 11

BACK PANEL

FRONT PANEL

4.0

2.0

1.0

0.5

0.1

x In

13 SW1 1

Addr.

Zone2

Zone1

Zone4

Zone3

1234567

8O N

L2/Io L1/L3 SW2

8910

Figure 3.8: VAM 4CD current I/O unit front and back panel

1. Programming switches

2. POWER indicator light, indicates the supply voltages of eachcomponent are in order.

3. COM indicator light, lit when the central units and I/O units arecommunicating.

4. ERROR indicator light, indicates an internal fault detected by thecomponent’s self-diagnostics. Such faults include faulty currenttransformer or phase current unbalance.

5. Connector sockets for the VX001 modular cables

6. LED lights indicating that I> stage has started

7. Terminals for three current transformers

8. Current transformer programming switches

VIO/en M/A00320

3 User interface3.8 VAM 4CD current I/O unit

Page 21: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9. Overcurrent setting knob (IL1, IL3), setting range 0.5 – 6 x IN10. Overcurrent setting knob (IL1, I0), setting range 0.05 – 5 x IN11. I/O unit trip relay activated

12. Terminal block for external communication and BI/O channelsand trip signal

13. Indicator leds for current setting

14. Text pocket

3.9 VAMP 4R trip multiplier relay

VAMP 4R

Power

Trip 2

Trip 1

+++ ---TRIP 1

12 11 9 8 6 5 4 3 2 1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

X2

X1

TRIP 2

18...265Vac/dc 24Vdc

INPUTS

NO NC NO NC NO NC NO NC

TRIP GROUP 1 TRIP GROUP 2

NO NCCOM

SF ALARM

OUTPUT

VAMP 4R frontplate

��

Figure 3.9: VAMP 4R trip multiplier relay front panel

1. POWER LED, indicates that the external operating voltage of+24 Vdc is connected.

2. Terminals for external operating voltage (+24 Vdc). Can besupplied by central units or I/O units.

3. Terminals for incoming trip signal (e.g. 24 Vdc from VAM I/O unitbinary output, 2 groups). Control voltage range is 18 – 265Vad/dc.

4. Terminals for outgoing trip signals (8 potential-free contacts, 4normally open, 4 normally closed).

21VIO/en M/A003

3.9 VAMP 4R trip multiplier relay3 User interface

Page 22: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

4 Programming switches

Before system implementation, check the positions of theprogramming switches in accordance with the following basicprinciples:

• Each I/O unit connected to the communication bus has its ownaddress (each I/O unit have an unique address).

• Set the programming switches before connecting the supplyvoltage.

• If you have to change the switch positions once the supplyvoltage has been connected, disconnect the supply voltage tothe unit in question for the duration of the programming andre-configure the system.

• If position of the switch is changed, re-install the system againin the central unit.

4.1 Switches for arc sensor I/O unitsThe programming switches of the I/O units are used to determinethe unit address and trip relay function.

The system accommodates up to 16 units. Eight addresses arereserved for each protection zone:

• Zone 1 addresses 0 – 7• Zone 2 addresses 8 – 15• Zone 3 addresses 16 – 23• Zone 4 addresses 24 – 31

The programming switches have different weight factors. To createan address for the I/O unit, turn switches with different values to theON position and calculate the sum of their weight factors. Thefollowing table shows the weight factors of each programming switch.Table 4.1: Programming switch weight factors, *) VAM 10L / VAM 10LD, VAM12L / VAM 12LD, and VAM 3L / VAM 3LX only

Weight factorSwitch No.

18

27

46

85

164 *)

NOTE: Note the position of the VAM 12LD, VAM 10LD and VAM 4CD dipswitches.

VIO/en M/A00322

4 Programming switches

Page 23: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

SW1

SENSOR

ACT

OK

Addr.

Zone

L / L+I

Latch

L> ext/int

VAM 12LD / VAM 10LD

1

2

3

4

5

6

7

8

OFFON

SW1

Addr.

Zone

L+I / L

Latch

L>ext/Int

SENSOR

OK

ACT

TRIP

VAM 3L / VAM 3LX

1

2

3

4

5

6

7

8

OFF ON

SW1

SENSOR

OK

ACT

TRIP

Addr.

Zone

L+I / L

Latch

L>ext/int

VAM 10L / VAM 12L

1

2

3

4

5

6

7

8

OFF ON

Figure 4.1: Programming switches for VAM 10L, VAM 10LD, VAM 12L, VAM 12LD,VAM 3L and VAM 3LX

VAM 10L / VAM 10LD, VAM 3L / VAM 3LX

Switch 1 determines which light activation activates the arc stage.When the switch position is ON, the arc stage only activates on thelight information provided by the unit's own sensors. In OFF positionthe arc stage activates on the light information received from anyunit in the same protection zone.

Switch 2 determines the trip relay latch. When the switch is in ONposition the trip relay remains engaged after the arc trip until the faultis acknowledged at the central unit’s panel. In the OFF position thetrip relay follows the arc fault.

Switch 3 determines the arc trip criteria. When the switch is in ONposition the trip is based on light information only; in OFF positionboth fault currents exceeding the current limit and light informationare required.

23VIO/en M/A003

4.1 Switches for arc sensor I/O units4 Programming switches

Page 24: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

VAM 12L / VAM 12LD

When the L>ext/int DIP switch is in “L>int” position, the output relaysare only activated by dedicated sensors.

SENSOR 1 activates T1.

SENSOR 2 activates T2.

SENSOR 3 activates T3.

SENSORS 4 to 10 are normally sending light information to systemaccording to zone setting.

If the switch is in “L>ext” position, all output relays are also controlledby the selected zone information. This activation source can be anysensor channel 4 to 10 or from an external I/O unit configured to thesame zone.

4.2 Switches for current I/O unitsThe address range for current I/O units is (32), 33 - 46. Do not useaddress 32, because in this case the current I/O unit operates inCENTRAL UNIT mode and the actual central unit must be set toSUB-UNIT mode. To determine the address of a current I/O unit,add the sum of the weight factors to 32 (for example, programmingswitch values total 7, address of the current I/O unit 32 + 7 = 39).

NOTE: Do not use 32 as the unit address if system have central unit.

Other programming switches have different functions in differentunits, as described below.

VIO/en M/A00324

4 Programming switches4.2 Switches for current I/O units

Page 25: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

VAM 4C / VAM 4CD

Addr.

Zone2

Zone1

Zone4

Zone3

SW1

TRIP

VAM 4C

1

2

3

4

5

6

7

8

OFF ON

SW2

1A/5A

Latch

I>in

I>out

6

3 1.0

x In

0.055

L1,L3 L2/Io

0.5

11 12

1 2 3 4

ON

M

SW2

1A/5A

Latch

I>in

I>out

6

3 1.0

x In

0.055

L1,L3 L2/Io

0.5

11 12

1 2 3 4

ON

VAM 4CD

SW1

Addr.

Zone11

2

3

4

5

6

7

8

OFFON

Zone2

Zone3

Zone4

Figure 4.2: Programming switches of VAM 4C / VAM 4CD

Table 4.2: VAM4C dipswitches weight factorsWeight factorSW NO:

18

27

46

85

25VIO/en M/A003

4.2 Switches for current I/O units4 Programming switches

Page 26: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

Table 4.3: SW1 switch settingsDescriptionDefinitionSwitch

System operating zone 1 (light information)Zone 11

System operating zone 2 (light information)Zone 22

System operating zone 3 (light information)Zone 33

System operating zone 4 (light information)Zone 44

Address weighting coefficient 8Addr5

Address weighting coefficient 4Addr6

Address weighting coefficient 2Addr7

Address weighting coefficient 1Addr8

Table 4.4: SW2 switch settingsDescriptionDefinitionSwitch

Position ”0” (switch down): trip relay is onlyoperational while the protection is activated

Latch1

Position ”1” (switch up): trip relay changesto latching status after trip

Position ”0” (switch down): rated secondarycurrent of the current transformer is 1 A

1A / 5A *2

Position ”1” (switch up): rated secondarycurrent of the current transformer is 5 A

Position ”0” (switch down): unit does nottransmit the current criteria to other units

I> out3

Position ”1” (switch up): unit transmits thecurrent criteria to other units

Position ”0” (switch down): unit does not re-ceive the current criteria from other units

I> in4

Position ”1” (switch up): unit receives thecurrent criteria from other units

*) As in CT

VIO/en M/A00326

4 Programming switches4.2 Switches for current I/O units

Page 27: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

5 Adjusting the overcurrentsetting

The principles for changing the current setting in VAM 4C units arethe same as for the central unit. You can see the estimated currentsetting from the led bar on the right side of the unit.

The most accurate way of setting the current limit for the unit is asfollows:

• Turn the potentiometer to the maximum value.

• Feed a test current corresponding to the required setting usinga testing device.

• Lower the setting until the current activation indicator LED of theI/O unit and / or the I>ext indicator LED in VAMP 221 the centralunit are / is lit.

L1/L3 L2/Io

4.0

2.0

1.0

0.5

0.1

x In

POWER

COM

ERROR

COM 1 COM 2

L1 L2 L3

CURRENT TRANSFORMER

Addr.

Zone2

Zone1

Zone4

Zone3

SW1

TRIP

VAM 4C

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X2

X1

VAM4c conn

Figure 5.1: Adjusting the current setting in VAM 4C

27VIO/en M/A003

5 Adjusting the overcurrent setting

Page 28: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

6 BI/BO connection

Each I/O unit also has a BI/O bus. The light I/O units (VAM 10L /VAM 10LD, VAM 12L / VAM 12LD, VAM 3L / VAM 3LX) can transmittrip signal to the central unit or current I/O unit. The current I/O unit(VAM 4C / VAM 4CD) can receive the light information and send thecurrent information either to other I/O units or the multiplying relay.

NOTE: The DI/DO on the VAM units are fast BI/BO signals.

The following DI and DO connections are included in thestandard delivery of VAM 10L and VAM 3L / VAM 3LX:

Zone shift 1(2, 2(1, 3(4, 4(3X2-8DI

X2-7GND

Trip signal, 24 V dcX2-10Trip out

Trip signal earthX2-9GND

The following DI and DO connections are included in thestandard delivery of VAM 4C units:

Light input, 24 – 48 V dcX2-8L>in

Light input earthX2-7GND

Trip signalX2-10Trip out

Trip signal earthGNDGND

NOTE: L>in light input in VAM 4C / VAM 4CD (X2-7 &X2-8) is master lightinput. This means that incoming light zone dip switch settings do notmatter and unit trips when this input is active and there is currentover the set limit.

VIO/en M/A00328

6 BI/BO connection

Page 29: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

7 Connections

Grounding of VAM I/O units must be made according to theConstruction section in the document.

DANGERELECTRICAL SHOCK

Always connect the protective grounding before connecting thepower supply.

Failure to follow these instructions can result in death orserious injury.

29VIO/en M/A003

7 Connections

Page 30: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

7.1 VAM 3L / VAM 3LX interfaces

SW1

Addr.

Zone

L+I / L

Latch

L>ext/int

SENSOR

OK

ACT

TRIP

COM 1 COM 2

POWER

COM

ERROR

CH1 CH2 CH3

SENSOR INPUTS

R1 T1 R2 T2 R3 T3

VAM 3L / 3LX

X216 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

Channel 1Fiber receiver connectionX1-R1:

Fiber transmitter connectionX1-T1:

Channel 2Fiber receiver connectionX1-R2:

Fiber transmitter connectionX1-T2:

Channel 3Fiber receiver connectionX1-R3:

Fiber transmitter connectionX1-T3:

= COM1, COM2

+24V supply from master unit orexternal power supply

X2-1:

GNDX2-2:

Zone information(L>, I>)

CAN-LX2-3:

CAN-HX2-4:

master slave comSerial BX2-5:

Serial AX2-6:

Zone changeDI GNDX2-7:

(1 -> 2; 2 -> 1;DI (24-48Vdc)X2-8:

3 -> 4; 4 -> 3)

Trip signal(DI&DO)

DO GNDX2-9:

DO +24VdcX2-10:

Not in use+ Temp sensorX2-11:

- Temp sensorX2-12:

X2-13:

X2-14:

Trip relay (NO)X2-15:

Trip relay (NO)X2-16:

VIO/en M/A00330

7 Connections7.1 VAM 3L / VAM 3LX interfaces

Page 31: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

7.2 VAM 10L interfaces

SW1

SENSOR

OK

ACT

COM 1 COM 2

POWER

COM

ERROR

TRIP

Addr.

Zone

L+I / L

Latch

L> ext/int

SENSOR INPUTS

1 2 3 4 5 6 7 8 9 10

X1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

X212345678910111213141516

VAM 10L

VAM10L conn

arc sensor channel 1X1-1, 2:

arc sensor channel 2X1-3, 4:

arc sensor channel 3X1-5, 6:

arc sensor channel 4X1-7, 8:

arc sensor channel 5X1-9, 10:

arc sensor channel 6X1-11, 12:

arc sensor channel 7X1-13, 14:

arc sensor channel 8X1-15, 16:

arc sensor channel 9X1-17, 18:

arc sensor channel 10X1-19, 20:

=COM1, COM2

+24V supply from masterunit orexternal power supply

X2-1:

GNDX2-2:

Zone information(L>, I>)

CAN-LX2-3:

CAN-HX2-4:

Master slave comSerial BX2-5:

Serial AX2-6:

Zone changeDI GNDX2-7:

(1 -> 2; 2 ->1;DI (24 – 48Vdc)X2-8:

3 -> 4; 4 -> 3)

Trip signalDO GNDX2-9:

DO +24VdcX2-10:

Not in use+ Temp sensorX2-11:

- Temp sensorX2-12:

X2-13:

X2-14:

Trip relay (NO)X2-15:

Trip relay (NO)X2-16:

31VIO/en M/A003

7.2 VAM 10L interfaces7 Connections

Page 32: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

7.3 VAM 10LD interfaces

SW1

SENSOR

OK

ACT

COM 2 COM 1

Addr.

Zone

L/L+I

Latch

L> Int/

Ext

SENSOR INPUTS

X11234567891011121314151617181920

X2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1234567

8O N

arc sensor channel 1X1-1, 2:

arc sensor channel 2X1-3, 4:

arc sensor channel 3X1-5, 6:

arc sensor channel 4X1-7, 8:

arc sensor channel 5X1-9, 10:

arc sensor channel 6X1-11, 12:

arc sensor channel 7X1-13, 14:

arc sensor channel 8X1-15, 16:

arc sensor channel 9X1-17, 18:

arc sensor channel 10X1-19, 20:

=COM1, COM2

+24V supply from masterunit orexternal power supply

X2-1:

GNDX2-2:

Zone information(L>, I>)

CAN-LX2-3:

CAN-HX2-4:

Master slave comSerial BX2-5:

Serial AX2-6:

Zone changeDI GNDX2-7:

(1 -> 2; 2 ->1;DI (24-48Vdc)X2-8:

3 -> 4; 4 -> 3)

Trip signalDO GNDX2-9:

DO +24VdcX2-10:

Not in use+ Temp sensorX2-11:

- Temp sensorX2-12:

X2-13:

X2-14:

Trip relay (NO)X2-15:

Trip relay (NO)X2-16:

VIO/en M/A00332

7 Connections7.3 VAM 10LD interfaces

Page 33: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

7.4 VAM 12L interfaces

VAM12L conn

SW1

SENSOR

OK

ACT

COM 1 COM 2

POWER

COM

ERROR

TRIP

Addr.

Zone

L+I / L

Latch

L> ext/int

SENSOR INPUTS

1 2 3 4 5 6 7 8 9 10

X1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

X212345678910111213141516

VAM 12L

1

2

3

4

5

6

7

8

OFF ON

arc sensor channel 1X1-1, 2:

arc sensor channel 2X1-3, 4:

arc sensor channel 3X1-5, 6:

arc sensor channel 4X1-7, 8:

arc sensor channel 5X1-9, 10:

arc sensor channel 6X1-11, 12:

arc sensor channel 7X1-13, 14:

arc sensor channel 8X1-15, 16:

arc sensor channel 9X1-17, 18:

arc sensor channel 10X1-19, 20:

+24v supply from masterunit or ex-ternal power supply

X2-1:

GNDX2-2:

X2-3:

Alarm

COMX2-4:

NOX2-5:

NCX2-6:

X2-7:

Trip relay 3 (NO)X2-8:

Trip relay 3 (NO)X2-9:

X2-10:

Trip relay 2 (NO)X2-11:

Trip relay 2 (NO)X2-12:

X2-13:

X2-14:

Trip relay 1 (NO)X2-15:

Trip relay 1 (NO)X2-16:

33VIO/en M/A003

7.4 VAM 12L interfaces7 Connections

Page 34: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

7.5 VAM 12LD interfaces

SW1

SENSOR

OK

ACT

COM 2 COM 1

Addr.

Zone

L/L+I

Latch

L> Int/

Ext

SENSOR INPUTS

X11234567891011121314151617181920

X2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

12345

678

O N

arc sensor channel 1X1-1, 2:

arc sensor channel 2X1-3, 4:

arc sensor channel 3X1-5, 6:

arc sensor channel 4X1-7, 8:

arc sensor channel 5X1-9, 10:

arc sensor channel 6X1-11, 12:

arc sensor channel 7X1-13, 14:

arc sensor channel 8X1-15, 16:

arc sensor channel 9X1-17, 18:

arc sensor channel 10X1-19, 20:

+24v supply from masterunit or ex-ternal power supply

X2-1:

GNDX2-2:

X2-3:

Alarm

COMX2-4:

NOX2-5:

NCX2-6:

X2-7:

Trip relay 3 (NO)X2-8:

Trip relay 3 (NO)X2-9:

X2-10:

Trip relay 2 (NO)X2-11:

Trip relay 2 (NO)X2-12:

X2-13:

X2-14:

Trip relay 1 (NO)X2-15:

Trip relay 1 (NO)X2-16:

VIO/en M/A00334

7 Connections7.5 VAM 12LD interfaces

Page 35: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

7.6 VAM 4C interfaces

L1/L3 L2/Io

4.0

2.0

1.0

0.5

0.1

x In

POWER

COM

ERROR

COM 1 COM 2

L1 L2 L3

CURRENT TRANSFORMER

Addr.

Zone2

Zone1

Zone4

Zone3

SW1

TRIP

VAM 4C

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X2

X1

VAM4c conn

Current input IL1X1-1, 3:

Current input IL2 / IoX1-5, 7:

Current input IL3X1-9, 11:

= COM1, COM2

+24V supply from master unit orexternal power supply

X2-1:

GNDX2-2:

Zone information(L>, I>)

CAN-LX2-3:

CAN-HX2-4:

master slave comSerial BX2-5:

Serial AX2-6:

L>DI GNDX2-7:

DI (24-48Vdc)X2-8:

TRIPDO GNDX2-9:

DO +24VdcX2-10:

X2-11:

X2-12:

X2-13:

X2-14:

Trip relay (NO)X2-15:

Trip relay (NO)X2-16:

35VIO/en M/A003

7.6 VAM 4C interfaces7 Connections

Page 36: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

7.7 VAM 4CD interfaces

X1123456789101112

X2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

COM 2 COM 1

4.0

2.0

1.0

0.5

0.1

x In

SW1

Addr.

Zone2

Zone1

Zone4

Zone3

12

34

567

8O N

L2/Io L1/L3 SW2

Current input IL1X1-1, 3:

Current input IL2 / IoX1-5, 7:

Current input IL3X1-9, 11:

= COM1, COM2

+24V supply from master unit orexternal power supply

X2-1:

GNDX2-2:

Zone information(L>, I>)

CAN-LX2-3:

CAN-HX2-4:

master slave comSerial BX2-5:

Serial AX2-6:

L>DI GNDX2-7:

DI (24-48Vdc)X2-8:

TRIPDO GNDX2-9:

DO +24VdcX2-10:

X2-11:

X2-12:

X2-13:

X2-14:

Trip relay (NO)X2-15:

Trip relay (NO)X2-16:

VIO/en M/A00336

7 Connections7.7 VAM 4CD interfaces

Page 37: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

7.8 VAMP 4R interfaces

VAMP 4R

Power

Trip 2

Trip 1

+++ ---TRIP 1

12 11 9 8 6 5 4 3 2 1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

X2

X1

TRIP 2

18 - 265Vac/dc 24Vdc

INPUTS

NO NC NO NC NO NC NO NC

TRIP GROUP 1 TRIP GROUP 2

NO NCCOM

SF ALARM

OUTPUT

1

233

4

Trip relay (NO), Trip group 1.X1-1, 2:

Trip relay (NC), Trip group 1.X1-3, 4:

Trip relay (NO), Trip group 1.X1-5, 6:

Trip relay (NC), Trip group 1.X1-7, 8:

Trip relay (NO), Trip group 2.X1-9, 10:

Trip relay (NC), Trip group 2.X1-11, 12:

Trip relay (NO), Trip group 2.X1-13, 14:

Trip relay (NC), Trip group 2.X1-15, 16:

X1-17:

SF Alarm relay

NOX1-18:

COMX1-19:

NCX1-20:

Aux voltage supply +24VdcX2-1:

GNDX2-2:

Aux voltage supply +24VdcX2-3:

GNDX2-4:

Aux voltage supply +24VdcX2-5:

GNDX2-6:

X2-7:

Trip group 2.TRIP 2. Input 18 – 265Vac/dcX2-8:

TRIP 2. Input 18 – 265Vac/dcX2-9:

X2-10:

Trip group 1.TRIP 1. Input 18 – 265Vac/dcX2-11:

TRIP 1. Input 18 – 265Vac/dcX2-12:

37VIO/en M/A003

7.8 VAMP 4R interfaces7 Connections

Page 38: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

8 I/O Technical data

8.1 ConnectionsTable 8.1: VAM 3L

3 fibre loop sensors (type ARC-SLx)Sensor connections

1 portable arc sensor (type VA 1 DP)

Table 8.2: VAM 3LX3 fibre loop sensors (type ARC-SLx)Sensor connections

- sensitivity adjust range compared to 3L

0.5 (max) – 1.5 (min)

1 portable arc sensor (type VA 1 DP)

Table 8.3: VAM 10L, VAM 10LD, VAM 12L, VAM 12LD10 arc sensors (type VA 1 DA or VA 1 EH)Sensor connections

1 portable arc sensor (type VA 1 DP)

Cross-section area of wireTerminal:

Maximum 2.5 mm2 (13 – 14 AWG)- MSTB2.5 - 5.08

Minimum 1.5 mm2 (15 – 16 AWG)

Table 8.4: VAM 4C, VAM 4CD1 or 5 A (optional) 50/60HzRated current L1 / L3

0 – 6 A (0 – 6*IN [IN =1A]);- current measuring zone

0 – 30 A (0 – 6* IN [IN =5A])- thermal withstand capability

300 A (for 1s)- power consumption

100 A (for 10s)

20 A (continuous)

<0.3 VA

1 or 5 A (optional) 50/60HzRated current L2 / I0

0 – 6 A (0 – 6*IN [IN =1A]);- current measuring zone

0 – 30 A (0 – 6* IN [IN =5A])- thermal withstand capability

300 A (for 1s)- power consumption

100 A (for 10s)

20 A (continuous)

<0.3 VA

Cross-section area of wireTerminal:

Maximum 4 mm2 (11 – 12 AWG)- single or multi-strand wire

Minimum 2.5 mm2 (13 – 14 AWG)

VIO/en M/A00338

8 I/O Technical data

Page 39: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

8.2 Auxiliary power supplyTable 8.5: VAM 10L, VAM 10LD, VAM 12L, VAM 12LD, VAM 4C, VAM 4CD,VAM 3L, VAM 3LX

24 V dcRated voltage UAUX

< 1 W (in normal mode)Power consumption

< 1.5 W (output relays activated)

-Terminal:

Cross-section area of wire- MSTB2.5 - 5.08

Maximum 2.5 mm2 (13 – 14 AWG)( RJ 45 when supply from central unit)

Minimum 1.5 mm2 (15 – 16 AWG)

Table 8.6: VAMP 4R24 V dcRated voltage UAUX

20 mA stbyCurrent consumption

80 mA- one relay group activated

180 mA- both relay groups activated

Table 8.7: VA 1 DA, VA 1 EH, VA 1 DP12 V dc (from I/O unit)Rated voltage UAUX

< 35 mW (in normal mode)Power consumption

< 450 mW (activated)

8.3 Digital inputsNo digital inputs available in VAM 12L and VAM 12LDTable 8.8: VAM 10L, VAM 10LD, VAM 3L, VAM 3LX

1 pcs I> inNumber of inputs

1 arc fault trip out

24 – 48 V dc (BIO in)Internal operating voltage

24 V dc (BIO out)

5 mALoad capacity (max.)

Cross-section area of wireTerminal:

Maximum 2.5 mm2 (13 – 14 AWG)- MSTB2.5 - 5.08

Minimum 1.5 mm2 (15 – 16 AWG)

39VIO/en M/A003

8.2 Auxiliary power supply8 I/O Technical data

Page 40: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

Table 8.9: VAM 4C1 pcs L> in

1 pcs I> out

Number of inputs

24 – 48 V dc (BIO in)

24 V dc (BIO out)

Internal operating voltage

5 mALoad capacity (max.)

Cross-section area of wire

Maximum 2.5 mm2 (13 – 14 AWG)

Minimum 1.5 mm2 (15 – 16 AWG)

Terminal:

- MSTB2.5 - 5.08

Table 8.10: VAMP 4R18 – 265 V ac/dcOperating voltage

2 mACurrent consumption

8.4 Trip contactsTable 8.11: VAM 10L, VAM 10LD, VAM 12L, VAM 12LD, VAM 4C, VAM 4CD,VAM 3L, VAM 3LX

1 closing contact (relay T1)Number of contacts

for VAM 10L, VAM 10LD, VAM 4C,VAM 4CD, VAM 3L, VAM 3LX

3 closing contacts (relay T1)Number of contacts

for VAM 12L, VAM 12LD

250 V ac/dcRated voltage

5 AContinuous withstand capacity

30 AMake and carry for 0.5s

15 AMake and carry for 3s

Breaking capacity, dc(L/R=40 ms)

1 AAt 48 V dc:

0.44 AAt 110 V dc:

0.22 AAt 220 V dc:

AgNi 90/10Relay material

Cross-section area of wireTerminal:

Maximum 2.5 mm2 (13 – 14 AWG)- MSTB2.5 - 5.08

Minimum 1.5 mm2 (15 – 16 AWG)

VIO/en M/A00340

8 I/O Technical data8.4 Trip contacts

Page 41: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

Table 8.12: VAMP 4R250V ac/dc4N/O / 4N/C rated voltage

< 10 msOperation time (typical)

5 AContinuous withstand capacity

30 A

15 A

Make and carry for 0.5s

Make and carry for 3s

N/O breaking capacity dc

(L/R=40ms)

1 AAt 48 V dc

0.44 AAt 110 V dc

0.22 AAt 220 V dc

AgNi 90/10Contact material

Cross-section area of wire

Maximum 2.5 mm2 (13 – 14 AWG)

Minimum 1.5 mm2 (15 – 16 AWG)

Terminal:

- MSTB2.5 - 5.08

8.5 Disturbance testsTable 8.13: Disturbance tests

Test valueStandard & Test class / levelTest

EN 61000-6-4 / IEC 60255-26Emission

0.01 – 30 MHzEN 55011, Class A / IEC 60255-25- Conducted

30 – 1000 MHzEN 55011, Class A / IEC 60255-25- Emitted

EN 61000-6-2 / IEC 60255-26Immunity

±2.5kVp CM, ±1.0kVp DMIEC 60255-22-1- 1Mhz damped oscillatory wave

8 kV contact, 15 kV airEN 61000-4-2 Level 4 / IEC 60255-22-2 Class4

- Static discharge (ESD)

80 - 2700 MHz, 10 V/mEN 61000-4-3 Level 3 / IEC 60255-22-3- Emitted HF field

4 kV, 5/50 ns, 5 kHzEN 61000-4-4 Level 4 / IEC 60255-22-4 ClassA

- Fast transients (EFT)

2 kV, 1.2/50 µs, CMEN 61000-4-5 Level 3 / IEC 60255-22-5- Surge

1 kV, 1.2/50 µs, DM

0.15 - 80 MHz, 10 VemfEN 61000-4-6 Level 3 / IEC 60255-22-6- Conducted HF field

300A/m (continuous), 1000A/m 1-3s

EN 61000-4-8- Power-frequency magnetic field

1000A/m, 1.2/50 µsEN 61000-4-9 Level 5- Pulse magnetic field

41VIO/en M/A003

8.5 Disturbance tests8 I/O Technical data

Page 42: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

8.6 Electrical safety testsTable 8.14: Electrical safety tests

Test valueStandard & Test class / levelTest

5 kV, 1.2/50 ms, 0.5 JEN 60255-5, Class III- Impulse voltage withstand

2 kV, 50 HzEN 60255-5, Class III- Dielectric test

EN 60255-5- Insulation resistance

EN 60255-27- Protective bonding resistance

8.7 Environmental conditionsTable 8.15: Environmental conditions

-10 – 55°C (14 – 131°F)Operating temperature range

-

Transport and storage temperature range

-40 – 70°C (-40 – 158°F)- VAM I/O units

-40 – 85°C (-40 – 185°F)- ARC SLm, VA 1 xx sensors

-

< 75% (1 year, average)Relative air humidity

< 90% (30 days per year, condensation notallowed)

2000 m (6561.68 ft)Maximum operating altitude

8.8 PackageTable 8.16: Package

-Dimensions (WxHxD)

157 x 92 x 25 mm / 6.18 x 3.62 x 0.98 inVAMP 4R, VAM 10L, VAM 4C, VAM 3L,VAM 3LX

-Weight (unit, box and user instructions)

0.62 kg (1.369 lb)VAMP 4R, VAM 10L, VAM 4C, VAM 3L,VAM 3LX

VIO/en M/A00342

8 I/O Technical data8.6 Electrical safety tests

Page 43: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

8.9 CasingTable 8.17: VAM 10L, VAM 4C, VAMP 4R, VAM 3L, VAM 3LX

IP21Housing class (IEC 60529)

NEMA 1Housing class (NEMA)

Open typeHousing class (UL 508)

157 x 92 x 25 mm / 6.18 x 3.62 x 0.98 inDimensions (W x H x D)

1 mm (0.039 in) steel plateMaterial

0.52 kg (1.148 lb)Weight

RAL 7032 (housing) / RAL 70035 (back plate)Colour code

Table 8.18: VAM 10LD, VAM 12LD, VAM 4CDIP64Housing class (IEC 60529)

Front: NEMA 2Housing class (NEMA)

Rear: NEMA 1

Front: Open typeHousing class (UL 508)

Rear: Open type

185 x 120 x 25 mm / 7.28 x 4.72 x 0.98 inDimensions (W x H x D)

1 mm (0.039 in) steel plateMaterial

0.60 kg (1.325 lb)Weight

RAL 7032 (housing) / RAL 70035 (back plate)Colour code

Table 8.19: VA 1 DA, VA 1 EH, VA 1 DPIP21Housing class (IEC 60529)

NEMA 1Housing class (NEMA)

Open typeHousing class (UL 508)

25 x 55 x 14 mm (VA 1 DA)Dimensions (W x H x D)

Φ11 x 62 mm (VA 1 EH)

Φ40 x 7 mm (VA 1 DP)

PlasticMaterial

0.01 kgWeight

VA 1 DA and VA 1 EH: 6 m or 20 mCable length

VA 1 DP: 5 m

43VIO/en M/A003

8.9 Casing8 I/O Technical data

Page 44: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9 Construction

9.1 Dimensional drawings

9.1.1 VAM 3L / 3LX Din rail mounting

mm

in

VAM 3L / 3LX

VAM 3L / 3LX

V A M 3 L / 3 L X

VAM 3L / 3LX

112

4.41

92

3.62

157

6.18

25

0.98

35mm /1.38 in

VAM 3L/3LX DIN RAIL MOUNTING

T max. 0.5-0.6 N•m

4.4-5.3 lb-in

ON

ON

ON

ON

L>ext/Int

L>ext/Int

L>ext/Int

L>ext/Int

VIO/en M/A00344

9 Construction

Page 45: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.1.2 VAM 10L Din rail mounting

35mm /1.38 in

112

4.41

92

3.62

157

6.18

25

0.98

mm

in

VAM 10L DIN RAIL MOUNTING

EN 50022

T max. 0.5-0.6 N•m

4.4-5.3 lb-in

ON

ONON

ON

45VIO/en M/A003

9.1 Dimensional drawings9 Construction

Page 46: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.1.3 VAM 10LD Flush mounting

27.6 1.09

90 3.54

185

7.28

120

4.72

VAM 10LD FLUSH MOUNTING

mm

in

92

3.62

ø4.5

0.18

1.0-100.04- 0.4

170

6.69

157

6.18

105

4.13

T max. 0.5-0.6 N•m

4.4-5.3 lb-in

Min. 2.5 mm2 / Ø0.06 in (#12 - #14 AWG)

Ground screw terminal

ON

ON

ON

VIO/en M/A00346

9 Construction9.1 Dimensional drawings

Page 47: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.1.4 VAM 12L Din rail mounting

112

4.41

92

3.62

157

6.18

25

0.98

mm

in

35mm /1.38 in

VAM 12L DIN RAIL MOUNTING

EN 50022

T max. 0.5-0.6 N•m

4.4-5.3 lb-in

ON

ON

ON

ON

47VIO/en M/A003

9.1 Dimensional drawings9 Construction

Page 48: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.1.5 VAM 12LD Flush mounting

27.6 1.09

90 3.54

185

7.28

120

4.72

VAM 12LD FLUSH MOUNTING

mm

in

92

3.62

ø4.5

0.18

1.0-100.04- 0.4

170

6.69

157

6.18

105

4.13

T max. 0.5-0.6 N•m

4.4-5.3 lb-in

Min. 2.5 mm2 / Ø0.06 in (#12 - #14 AWG)

Ground screw terminal

ON

ON

ON

VIO/en M/A00348

9 Construction9.1 Dimensional drawings

Page 49: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.1.6 VAM 4C Din rail mounting

112

4.41

92

3.62

157

6.18

25

0.98

mm

in

35mm /1.38 in

VAM 4C DIN RAIL MOUNTING

EN 50022

T max. 0.5-0.6 N•m

4.4-5.3 lb-inON

ON

ON

ON

49VIO/en M/A003

9.1 Dimensional drawings9 Construction

Page 50: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.1.7 VAM 4CD Flush mounting

27.6 1.09

90 3.54

185

7.28

120

4.72

VAM 4CD FLUSH MOUNTING

mm

in

92

3.62

ø4.5

0.18

1.0-100.04- 0.4

170

6.69

157

6.18

105

4.13

T max. 0.5-0.6 N•m

4.4-5.3 lb-in

Min. 2.5 mm2 / Ø0.06 in (#12 - #14 AWG)

Ground screw terminal

ON

ON

ON

VIO/en M/A00350

9 Construction9.1 Dimensional drawings

Page 51: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.1.8 VAMP 4R Din rail mounting

35mm /1.38 in

112

4.41

92

3.62

157

6.18

mm

in

25

0.98

VAMP 4R DIN RAIL MOUNTING

EN 50022

T max. 0.5-0.6 N•m

4.4-5.3 lb-in

18 - 265 Vac/dc

18 - 265 Vac/dc

18 - 265 Vac/dc

51VIO/en M/A003

9.1 Dimensional drawings9 Construction

Page 52: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.1.9 VA 1 DA

14

0.55

VA1DA_mittakuva

22.2

0.83

mm

in

10

0.39

46.4

1.83

20

0.79

25

0.98

8

0.31

4.2

0.17

9.1.10 VA 1 EH

VA1EH_mittakuva

mm

in

62

2.44

11

0.43

VIO/en M/A00352

9 Construction9.1 Dimensional drawings

Page 53: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.1.11 VYX 001

mm

in50

1.9715

0.59

7

0.28

50

1.97

15

0.59

51

2.025

0.98

59

2.32

42

1.65

2.5

0.1

10

0.39

53VIO/en M/A003

9.1 Dimensional drawings9 Construction

Page 54: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.1.12 VYX 002

30

1.18

15

0.59

15

0.59

mm

in

30

1.18

10

0.39

59

2.32

3

0.12

VIO/en M/A00354

9 Construction9.1 Dimensional drawings

Page 55: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.2 I/O unit mounting and wiring

CAUTIONRead this User's Manual carefully before undertaking anyinstallation or wiring work.

Safety instructions

Always observe the national electrical safety regulations whenworking under live conditions. The unit manufacturer is not liable fordamage due to incorrect working methods or failure to observe safetyinstructions.

The correct handling of the unit under all mounting and operatingconditions forms the foundation for its safe use.

CAUTIONAny separately marked notes and warnings must be observed.

The wiring work must be performed according to nationalstandards and any requirements specified by the customer.

Do not connect the auxiliary supply voltage until the installationhas been completed.

Before installation

Before installation, make sure the environmental conditions complywith the requirements specified in Chapter 7.

CAUTIONThe unit contains components liable to damage if exposed to anelectrostatic discharge (ESD). Do not open the unit unless youhave taken appropriate protective measures against ESD.

The manufacturer cannot guarantee operational safety inenvironments that do not satisfy the specified environmentalconditions.

55VIO/en M/A003

9.2 I/O unit mounting and wiring9 Construction

Page 56: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.2.1 VAM 10L, VAM 12L, VAM 4C, VAM 3L, VAM 3LXThe units are designed for mounting on a DIN rail. Mount the unitson the rail in such a way that the indicator lights on the front panelare visible and the sensor wiring can be made as easily as possible.

9.2.2 VAM 10LD, VAM 12LD, VAM 4CDThe units are designed for mounting on a door. Hence all indicatorsare clearly visible in normal operation.

9.3 Connecting the VAMP 321 I/O unitsThe I/O units can be connected to the components listed below:

• Enclosure current transformer secondary circuits (VAM 4C andVAM 4CD I/O units only)

• Circuit breaker trip circuits

• External auxiliary supply circuits

• Connections to the VAMP 321 central unit or other I/O units (datacommunication and auxiliary supply)

• Connections to other central units or detection relays (digitalinput (DI) or digital output (DO) bus)

9.4 Connecting the secondary circuits of thecurrent transformers (VAM 4C / VAM4CD only)Connect the secondary circuits of the current transformers to thefollowing screw connectors:

• X1-1, X1-3 (L1)

• X1-5, X1-7 (L2/I0)

• X1-9, X1-11 (L3)

The arc protection system can also be single or two-phase connected.Three-phase connection is nevertheless recommended for optimaloperating speed.

VIO/en M/A00356

9 Construction9.3 Connecting the VAMP 321 I/O units

Page 57: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

DANGERHAZARD OF ELECTRICAL SHOCK

Do not open the secondary circuit of a live current transformer.

Disconnecting the secondary circuit of a live current transformermay cause dangerous overvoltages.

Failure to follow these instructions will result in death orserious injury.

NOTE: The current measuring channels L1 and L3 must be used inconnection with two-phase current measuring. Single-phase currentor ground fault current must always be connected to the currentmeasuring channel L2/I0; otherwise, an unbalance error will occur.

The specified operating time can only be guaranteed for three-phasecurrent measurement and with the proper voltage supply to all systemcomponents, minimum allowed auxiliary voltage is 21.6 Vdc.

The VAM 4C overcurrent unbalance alarm settings recognizes if thetwo-phase or three-phase monitoring is being used based on theconnections made to the unit and the overcurrent limits set for eachconnection. The two-phase connection monitoring is triggered whenthe L2/I0 connection overcurrent limit differs from the L1/L3 overcurrentlimit settings by 90% or more. This is because in the event two-phasemonitoring is used, the L2/I0 connection is the connection used tomonitor the ground current.

Therefore, the current limit set for the L2/I0 connection should reflectlimits associated with anticipated ground currents. The remainingL1/L3 currents should be balanced, and overcurrent settings for theL1/L3 connection should be reflected as such. The two-phasemonitoring mode is also referred to as “ground-fault mode.”

The three-phase monitoring is triggered when the L2/I0 and L1/L3overcurrent limit settings are similar, reflecting that each phase isunderstood to be in balance with the other two phases.

If detected, the system gives an unbalance alarm after a 10-seconddelay time. The alarm does not affect other operations of the arcdetection system.

The phase discontinuity settings are non-adjustable since all thesetting values have been programmed in the current-monitoring unit.

57VIO/en M/A003

9.4 Connecting the secondary circuits of the current transformers(VAM 4C / VAM 4CD only)

9 Construction

Page 58: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.5 Connecting the trip circuits of the circuitbreakersConnect the circuit breaker’s trip circuit to the following pins:

TRIP1: X2-15, X2-16

For example, in the event of an arc fault, the output contact will closeat specified time when three-phase current measurement is used.

The output trip relay of the light I/O units (VAM 10L and VAM 3 L)operates during faults in its own zone. In the current I/O unit (VAM4 C), select the protection zone controlling the I/O unit using theprogramming switches.

If several trips are required, the multiplying relay VAMP 4R can beused. If VAMP 4R is used, make sure that proper voltage supply isconnected to device.

VIO/en M/A00358

9 Construction9.5 Connecting the trip circuits of the circuit breakers

Page 59: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.6 Connecting between the central unit andthe I/O unitConnect the central unit to the I/O units with a modular cable of typeVX001. Themodular cable carries all information between the centralunit and I/O units, including data in serial form, arc fault messagesand operating supply to the I/O units.

• Connect the VX001 cable to the arc I/O COM interface of thecentral units.

• Connect the cable to COM1 or COM2 on the first I/O unit.

• Route the cable from COM1 or COM2 on the first I/O unit toCOM1 or COM2 in the next unit, etc.

All the COM1 and COM2 interfaces are identical, i.e. the cable canalways be connected to either interface. The maximum total lengthof the modular cable, taking into account all the I/O units connectedto the central unit, is 100 m.

NOTE: Use only star connection for I/O units. Maximum single bus cablelength is 30 meters.

CAUTIONHAZARD OF EQUIPMENT DAMAGE

Do not connect modular cables closed loop.

Failure to follow these instructions can result in personalinjury or equipment damage.

59VIO/en M/A003

9.6 Connecting between the central unit and the I/O unit9 Construction

Page 60: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.7 Connecting separate auxiliary suppliesWhen routing modular cables over long distances (30 meters ofmodular cabling) or when the system contains more than 4 I/O unitsyou should preferably use a separate auxiliary +24Vdc voltage supplywith output monitoring along with the modular bus cabling.

Recommended types of power supplies with output monitoring:

1. Phaseo ABL4RSM24035 (3.5A @ 24Vdc)

2. Phaseo ABL4RSM24050 (5A @ 24Vdc)

3. or any equivalent type of power supply with above functionality

NOTE: Use of power supplies without voltage monitoring is notrecommended.

Connect the auxiliary supply to the 24 V terminals of the last I/O unit.Use at least 1.5mm2 (AWG 16) size twisted pair cable.

NOTE: It is recommended to use external wiring to connect auxiliary supplyto all units.

Pay particular attention to the polarity of the wire and cableconnections.

Additional power supply cabling is recommended, min. 1.5 mm2 (AWG16)

Power supply cabling, min. 1.5 mm2 (AWG 16)

Modular Arc I/O bus cable

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

X2

OK

ACT

TRIP

6

7

910

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

78

910

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

89

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

+

24Vdc

~−

ON

F1

F2

OK

Vamp 300

OI

Figure 9.1: External power supply wiring

VIO/en M/A00360

9 Construction9.7 Connecting separate auxiliary supplies

Page 61: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

7

910

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

78

910

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

7

910

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

78

10

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

78

910

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

78

910

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

7

910

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

78

910

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

+

+

24Vdc

24Vdc

~−

~−

ON

F1

F2

OK

Vamp 300

OI

Two branch design, length of cabling must not exceed 100 m combine total in both branches.

Figure 9.2: Protection system wiring configuration

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

X2

OK

ACT

TRIP

4

5

78

10

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

78

910

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

78

10

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

78

910

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

ON

F1

F2

OK

Vamp 300

OI

If four or less I/O units are used, total cable length is below 30 m. No power supply is needed.

Figure 9.3: Small protection system wiring configuration, one branch design

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

6

7

910

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

78

910

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

78

910

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

X1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

VAM 10L

POWER

COM

ERROR

COM 1

COM 2

12

3

SENSOR INPUTS

X2

OK

ACT

TRIP

4

5

6

78

910

1 2

3 4

5 6

7 8

ON

L>ext/int

Latch

L+I/L

Zone

Addr.

SW1 SENSOR

X1

1 2 3 4 5 6 7 8 9 10 11 12 13 1

4 15 1

6 17 18 19 20

+

24Vdc

~−

ON

F1

F2

OK

Vamp 300

OI

Systems having more than four I/O units must be equipped with separate auxiliary supply.

Figure 9.4: Protection system wiring configuration, one branch design

61VIO/en M/A003

9.7 Connecting separate auxiliary supplies9 Construction

Page 62: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.8 VAMP 4R

VAMP 4R

12 11 9 8 6 5 4 3 2 1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 19 20 18

:X2

X1:

+-+-+-

+ 2 4 Vdc18 - 265V ad/dc

Group 1 Group 2 Self

super vision

alar m

Figure 9.5: VAMP 4R block diagram

The multiplying relay VAMP 4R can be used when additional tripoutputs are needed.

VAMP 4R comprises 4 N/O contacts and 4 N/C contacts. They aredivided into two separate groups which can be independentlycontrolled by e.g. the binary output of the I/O units or the central unit.

• Attach the VAMP 4R unit to a DIN rail.

• Connect the auxiliary voltage ( +24V ) to terminal X2-1 (+) andX2-2 (-). Terminals X2-3 and X2-5 are parallel inputs to X2-1(+).Terminals X2-4 and X2-6 are parallel inputs to X2-2(1). Theauxiliary voltage ( +24V ) can be supplied from the central unitor nearest slave ( X2-1 (+), X2-2 (-)).

• Connect the required signal (18-265 V ad/dc) to the trip controlinputs.

• Input “TRIP 1” ( X2-11, X2-12 ) is controlling the trip group 1.Input “TRIP 2” ( X2-8, X2-9 ) is controlling the trip group 2.

• There are 2xN/C + 2xN/O contacts per trip group.

If necessary, input TRIP 1 and 2 can be connected in parallel. Thenall trip relays will operate simultaneously.

VIO/en M/A00362

9 Construction9.8 VAMP 4R

Page 63: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.9 Wiring multiple central unitsA maximum of 16 I/O units and/or central units in ‘slave’ mode canbe connected to one communication bus. In this case, the units canoperate on a maximum of four protection zones (depending on theirprogramming switches). The light and current signals given by theI/O units, including address information, are transferred to eachcentral unit.

If more than one central unit is to be connected to the samecommunication bus, one central unit must be in central unit modeand the other central units in sub-unit mode.

In applications with multiple central units the central units can beinterconnected also via BI/O connections (binary input/output). Inthis case, each part of the system can control four protection zonesper system communication bus. In this case, arc and overcurrentinformation is transferred between the central units without addressinformation.

NOTE: When configurating Vamp 221 arc protection system with multiplecentral units, disconnect I/O-units from central units in slave modeduring their installation procedure.

9.10 Arc sensorsMount the sensors on the switchgear in such a way that they coverthe protection zone as completely as possible. The line of sight mustbe free between the sensor and the supervised area.

If point sensors are used in open compartments (such as bus-barsections), there should be a sensor approximately every 5 meters.Due to the wide detection range of the sensors and the light reflectioninside the switchgear, the mounting position is not critical.

Connecting sensors VA 1 DA and VA 1 EH to the I/O units

The sensors are delivered with 6-metre standard cables or 20-metreshielded cables (to be specified in the order).

After mounting the sensors, connect them to the I/O units as follows:

• Draw the wire to the nearest I/O unit using the shortest routepossible and cut it to a suitable length.

• Connect the arc sensors to the screw terminals X1-1…20. Thepolarity of the arc sensor cables is not critical.

Connecting the ARC-SLx sensors to the I/O units

The sensors are delivered in standard lengths (to be specified in theorder) equipped with terminals compatible with VAM 3L units.

63VIO/en M/A003

9.9 Wiring multiple central units9 Construction

Page 64: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

After mounting the sensors, connect them to the I/O units as follows:

• Draw each end of the sensor to the I/O unit and carefully form aloop of the extra fibre.

NOTE: Do not shorten the extra sensor fibre unless you have appropriateterminal connectors.

• Connect the arc sensors to plug-in terminals X1-R1, T1…R3,T3. While the polarity of the arc sensors is not critical, you mustconnect each end of the fibre to the same channels.

NOTE: Check that the sensor positioning has not changed during shippingand commissioning.

Use a separate VAMPArc Flash Protection Testing Manual for testingtesting each sensor during commissioning.

9.10.1 VA 1 DAYou can be install the arc sensor onto the switchgear wall from theoutside. Press the active part of the sensor through the 10-mm holein the wall and fix it using a 4-mm screw.

VA1DA_asennus

Figure 9.6: Mounting the arc sensor VA 1 DA

1. Active part of the sensor

2. Cable clamp

3. Fastening screw 4x15 mm

4. Cable of sensorVIO/en M/A00364

9 Construction9.10 Arc sensors

Page 65: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

You can also surface mount the sensor to the wall using the mountingplates VYX01 or VYX02, available as additional parts.

NOTE: The sensor must not be exposed to direct sunlight or other stronglight. Do not mount the sensor directly under a light source.

Figure 9.8: Sensitivity of the arc sensorVA 1 DA

Figure 9.7: Arc sensor VA 1 DA

9.10.2 VA 1 EHYou can be install the arc sensor onto the switchgear wall from theoutside. Press the active part of the sensor through the 10.5-mmhole in the wall.

You can also surface mount the sensor. To do this, push the sensorinto a plastic mounting tube and fix it with heat shrink tubing.

NOTE: The sensor must not be exposed to direct sunlight or other stronglight. Do not mount the sensor directly under a light source.

Figure 9.9: Arc sensor VA 1 EH

65VIO/en M/A003

9.10 Arc sensors9 Construction

Page 66: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

9.10.3 ARC-SLxARC-SLx is an fibre sensor that can be mounted on the switchgearto monitor several compartments simultaneously (various bus-barcompartmets, etc.).

The fibre must not touch any live parts of the switchgear or other hotcomponents, since too high temperatures may destroy the fibre.

When mounting the sensor on the switchgear, ensure that thebending radius is long enough (min. 50 mm) and that it is safe fromthe sharp edges of the switchgear.

NOTE: The sensor must not be exposed to direct sunlight or other stronglight. Do not mount the sensor directly under a light source.

To avoid false tripping, cover any unused channels of the I/O unit.

Figure 9.10: ARC-SLx

9.10.4 VA 1 DPThe portable pin sensor can be temporarily connected to the I/Ounits. It is used to improve safety when working with live switchgear,for example, Attach the sensor close to the working area, for examplein the breast pocket of the maintenance man.

A pin sensor operates in the same way as a fixed arc sensor. Theonly difference is free mobility within the limits of the connectingcable.

Figure 9.11: Pin sensor VA 1 DP

VIO/en M/A00366

9 Construction9.10 Arc sensors

Page 67: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

NOTE: To avoid faulty tripping, disconnect the pin sensor from the systemimmediately after use.

DANGERHAZARDOFELECTRICSHOCK, ELECTRICARCORBURNS

Ensure that trip signal will control main breaker in case of Arcflash incident!

Failure to follow these instructions will result in death orserious injury.

67VIO/en M/A003

9.10 Arc sensors9 Construction

Page 68: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

10 Order information

NoteDescriptionOrder code

3 fibre loops, 1 trip relayFibre sensor I/O unit (VAMP221 and 321)VAM 3L

3 fibre loops, 1 trip relay, adjustable sensitivityFibre sensor I/O unit (VAMP221 and 321)VAM 3LX

3 current inputs, 1 trip relayCurrent I/O unit (VAMP221 and 321)VAM 4C

3 current inputs, 1 trip relay, flush mountingCurrent I/O unit (VAMP221 and 321)VAM 4CD

10 sensor inputs, 1 trip relayPoint sensor I/O unit (VAMP221 and 321)VAM 10L

10 sensor inputs, 1 trip relay, flush mountingPoint sensor I/O unit (VAMP221 and 321)VAM 10LD

10 sensor inputs, 3 trip relaysPoint sensor I/O unit (VAMP221 and 321)VAM 12L

10 sensor inputs, 3 trip relays, flush mountingPoint sensor I/O unit (VAMP221 and 321)VAM 12LD

4 x NO, 4 x NC, 2 groupsTrip multiplier relayVAMP 4R

Cable length 6mArc SensorVA 1 DA-6

Cable length 20mArc SensorVA 1 DA-20

Cable length 6mArc Sensor, shieldedVA 1 DA-6s

Cable length 20mArc Sensor, shieldedVA 1 DA-20s

Cable length 6mArc Sensor, halogen freeVA 1 DA-6-HF

Cable length 20mArc Sensor, halogen freeVA 1 DA-20-HF

Cable length 6mArc Sensor (Pipe type)VA 1 EH-6

Cable length 20mArc Sensor (Pipe type)VA 1 EH-20

Cable length 5mArc Sensor, shielded (metal pipe)VA 1 DV-5

Cable length 10mArc Sensor, shielded (metal pipe)VA 1 DV-10

Cable length 15mArc Sensor, shielded (metal pipe)VA 1 DV-15

Cable length 5mPortable Arc SensorVA 1 DP-5

Cable length 5mPortable Arc SensorVA 1 DP-5D

x = fiber length (1Fibre sensor, 8 000 lxARC SLm-x

Max one joint per fibreFibre joint SLS-1SLS-1

Preferred Cable Lengths (2Modular Cable VAM - VAM ( xx = Cable length [m] )VX001-xx

Cable length 5mExtension cable for VA1DP-5DVX031-5

Cable length 3mUSB programming cable (VAMPSET)VX052-3

Cable length 3mVAMP 300/321 profibus cableVX072

Z-shapedSurface Mounting Plate for SensorsVYX 001

L-shapedSurface Mounting Plate for SensorsVYX 002

U-shapedSurface Mounting Plate for VA 1 DV SensorVYX 628

Height 45mmProjection for 300-seriesVYX 695

Max. distance 1 kmFibre optic Interface Module (plastic - plastic)VSE001PP

RS485 Interface ModuleVSE002

Profibus DP fieldbus option boardVPA 3CG

VIO/en M/A00368

10 Order information

Page 69: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

11 Glossary

DescriptionTerm

Binary inputBI

Binary outputBO

Stores information about the IED settings, events andfault logs.

Document file

Field-programmable gate arrayFPGA

Human-machine interfaceHMI

Intelligent electronic deviceIED

Liquid crystal displayLCD

Light-emitting diodeLED

IED front panel with display and push-buttonsLocal HMI

Personal computerPC

Configuration tool for VAMP protection devicesVAMPSET

69VIO/en M/A003

11 Glossary

Page 70: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal
Page 71: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal
Page 72: UserManual - Schneider Electricms.schneider-electric.be/Main/Vamp/notices/VIO_EN_M.pdf · 2016-03-24 · Theadditionofeithersymboltoa“Danger”or“Warning”safetylabel indicatesthatanelectricalhazardexistswhichwillresultinpersonal

2016