tuapannguanut, 3911 sisimiut...tuapannguanut, 3911 sisimiut report sisimiut 10.7.2015. 1 foreword...

21
Indoor Air Quality Renovation Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015

Upload: others

Post on 19-Mar-2020

15 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

Indoor Air Quality Renovation Tuapannguanut, 3911 Sisimiut

Report Sisimiut 10.7.2015

Page 2: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

1

Foreword

Winters in the Arctic are very cold and long. When the temperatures are so low, the occupants of

Arctic dwellings stop opening windows to avoid cold draught. Any natural vents get typically sealed

for the same reason. This, together with the lack of mechanical ventilation results in insufficient air

change in majority of the dwellings. Consequently the indoor air quality (IAQ) becomes rather poor

which has a negative effect on the occupants’ health and may also damage the construction due to

mold growth. In this project a state of the art ventilation unit was installed in an old house to study

its performance and any changes of the IAQ. The measurements have shown that the IAQ had

improved significantly. Also the occupants have reported significant increase in their comfort. The

initial costs of the installation would pay off in approximately 14 years thanks to the heat recovery.

All in all the installation of the mechanical ventilation had proved to be an efficient yet economical

solution to an actual indoor air quality problem in Greenland.

Page 3: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

2

1. Introduction

The climate in the Arctic is cold which means that living inside the heated space requires quite some

energy. To avoid large heat losses and cold discomfort, building envelopes are often sealed, which

reduces natural infiltration. Results of previous studies in Sisimiut [1,2] showed, that ventilation

equipment is rare, and when present, it is limited to an exhaust fan in the bathroom (only installed in

63% of households) and wall mounted fresh air valves. Fresh air valves are source of cold draft and

often get sealed by the occupants in order to avoid discomfort. Range hoods are not always installed

(missing in 18% of the households). Limited air change together with a tradition of long lasting

cooking, drying laundry inside and need to bring wet outdoor clothing inside to dry it often leads to

elevated concentrations of moisture. Too high humidity makes a good environment for dust mites to

grow and may also lead to mold growth. Poorly ventilated spaces also experience high concentrations

of other indoor pollutants such as tobacco smoke (34% of respondents to the survey smoke inside),

pollen, carbon monoxide, carbon dioxide or volatile organic compounds.

With respect to the amount of time people spend inside their homes the effect of poor indoor climate

(IC) on occupants’ health and comfort is considerable.

A recent study [2] showed that both existing and new buildings in Greenland suffer from insufficient

ventilation. In fact, the problem is growing with new dwellings as improving building techniques allow

tighter envelopes and properly designed ventilation equipment has not been introduced yet. Therefore

the problem of poor indoor climate is relevant for both existing and new buildings.

Possible solution for improving the indoor climate of a home in energy efficient way is installation of

ventilation unit with heat exchanger. This solution saves energy by reusing heat from the exhaust air

to preheat the fresh supply air. The fresh air is then supplied to rooms at temperature high enough to

avoid draught discomfort.

In the past there have been a lot of negative experiences with these systems as they were mainly

designed for milder climates and were not able to cope with the extreme cold. However, some of the

new modern ventilation units are capable of continuous operation even at very low temperatures in

the Arctic. They can also regulate the air change according to the actual demands of the users which

further reduces the energy consumption.

In December 2014 a Greenlandic housing administration company INI A/S in collaboration with Center

for Arctic Technology at Technical University of Denmark ARTEK installed a state of the art ventilation

unit into one of the city owned apartments in Sisimiut, Greenland. The aim was to study the

functionality of the system under Greenlandic conditions and to introduce the technology to the

community.

The results showed a significant improvement of the indoor climate which was not only measured by

instruments, but also confirmed by the inhabitants of the home. Moreover the system was capable of

operation during the coldest winter with temperatures below -25 °C without breakdowns.

This report describes the system in details and brings results of the experiment.

Page 4: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

3

1.1. Introduction of the home

The home which was a subject of this study is a type row house in Tuapannguanut – Sisimiut built in

80’s (shown in Figure 1). It consists of two floors. In a ground floor there is an entrance, laundry, living

room and kitchen. In the second floor there are two bedrooms and a bathroom (see the floor plans in

Figure 2). The floor area of the home is approximately 70 m2. The house is occupied by a family of 7

people (2 adults and 5 children).

Figure 1. Tuapannguanut home

Currently the ventilation consists of fresh air valves in bedrooms and living room, range hood with

exhaust towards outside and two vertical ventilation shafts from bathroom and laundry room (see

Figure 2). The fresh air valves were closed and taped by the occupants (to avoid cold draught).

Page 5: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

4

Figure 2. Tuapannguanut floor plans

1.2. Indoor climate

1.1.1 Carbon dioxide (CO2)

In previous studies it was found that exposures to moderately elevated concentrations of CO2 have

negative effect on human performance, perception of poor IAQ or prevalence of certain health

symptoms (such as irritation of mucous membranes, headaches or tiredness) [3-9]. It is however

believed that these symptoms are caused by various other pollutants whose concentrations rise along

with the CO2 concentration as a result of insufficient ventilation. CO2 is therefore often used as an

indicator of IAQ. Nevertheless a recent study on effects of CO2 on human performance [10] found

correlation between elevated CO2 concentration (above 1000 ppm) and decreased decision-making

performance in controlled environment free of other pollutants.

According to European standard EN 15251 [11] new buildings should have the CO2 concentration

lower than 500 ppm above outdoors for most of the time and existing buildings lower than 800 ppm.

Page 6: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

5

The international ASTM Standard D6245 (based on past studies) suggests indoor CO2 concentrations

lower than 650 ppm above outdoors so at least 80% of the unadapted persons will find the level of

body odor acceptable. The American standard ASHRAE 62.1 [12] recommends 700 ppm above

outdoors as an upper limit for CO2 concentration inside a living space.

With the average outdoor CO2 concentration in Sisimiut 400 ppm, the recommended indoor

concentration according to ASTM Standard D6245 is 1050 ppm, according to ASHRAE 62.1 [12] 1100

ppm and according to EN 15251 [11] 900 ppm for new and 1200 ppm for existing buildings.

1.1.2 Humidity

In numerous studies it has been found that increased levels of indoor humidity may have negative

effects on human health and comfort as they increase the risk of mold growth and concentration of

house-dust mites (HDM) [13-15]. Sundell [13] for example in his study in 30 homes in Stockholm area

found that elevated concentrations of HDM allergen in bedrooms were in correlation with additional

moisture. As well as too high humidity also too low humidity may cause problems. A Finnish study

[16] on the effects of humidification on the office workers had shown that office workers have

reported fewer symptoms (skin irritation, mucous membranes irritation, dryness sensation) when

exposed to environment with air at 30% to 40% relative humidity (RH) than when exposed to air RH

below 30%.

Generally, to minimize as many adverse health effects as possible, the indoor RH should be kept

between 30% and 50% [11].

1.1.3 Temperature

The European standard EN ISO 7730 [18] recommends 20 °C to 24 °C as a winter design temperature

and 23 °C to 26 °C as a summer design temperature in order to keep the amount of dissatisfied

occupants below 10%.

Page 7: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

6

2. Current indoor climate

Before the ventilation unit was installed, the indoor climate was monitored for two days for the

reference.

2.1. Carbon dioxide (CO2)

The measurements showed an overall average CO2 concentration of 2198 ppm in the bedrooms.

During the nights the average CO2 concentration was as high as 3124 ppm in master bedroom and

2977 ppm in a children’s bedroom. Such elevated concentrations of CO2 itself may cause tiredness and

concentration disorders [10]. Moreover, the elevated concentrations of CO2 also confirm that the

ventilation of the space is insufficient and hence concentrations of other pollutants may also be

elevated. Some of these pollutants may even be harmful to human beings (Volatile Organic

Compounds) or cause allergies and asthma (dust mites).

Figure 3. CO2 concentration in the two bedrooms before the installation of ventilation unit

0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

09

:00

11

:00

13

:00

15

:00

17

:00

19

:00

21

:00

23

:00

01

:00

03

:00

05

:00

07

:00

09

:00

11

:00

13

:00

15

:00

17

:00

19

:00

21

:00

23

:00

01

:00

03

:00

05

:00

07

:00

CO

2 -

con

cen

trat

ion

[p

pm

]

Time of the day

Master bedroom Children's bedroom Recommended maximum

Night average (master) Night average (children)

Night (occupied) Night (occupied)

Page 8: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

7

2.2. Relative Humidity

From the results it can be seen that the RH in bedrooms was between 30% - 50% for most of the

time (72% of the monitored period). For the rest of the time the RH was below the recommended

levels.

Figure 4. Cumulative percentage distribution of RH in bedrooms and bathroom before installation of the ventilation unit

The bathroom relative humidity was generally within the reasonable range except for the shower

period where it increased rapidly. After the spike it took 2 hours for the RH to decrease below 50%.

Figure 5. Bathroom RH

0

10

20

30

40

50

60

70

80

90

100

0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Re

lati

ve h

um

idit

y [%

]

Cumulative percentage

Master bedroom

Children bedroom

Bathroom

72%

0

10

20

30

40

50

60

70

80

09

:00

11

:00

13

:00

15

:00

17

:00

19

:00

21

:00

23

:00

01

:00

03

:00

05

:00

07

:00

09

:00

11

:00

13

:00

15

:00

17

:00

19

:00

21

:00

23

:00

01

:00

03

:00

05

:00

07

:00

Re

lati

ve H

um

idit

y [%

]

Time of the day

2 hours

Page 9: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

8

2.3. Temperature

As seen from the Figure 6, the temperatures were within the recommended range for winter comfort

(20 °C to 24 °C) for the entire test period. The overall average temperature was 21.2 °C.

Figure 6. Cumulative temperatures in bedrooms and bathroom before installation of the ventilation unit

20.0

20.5

21.0

21.5

22.0

22.5

23.0

23.5

24.0

0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Tem

pe

ratu

re [

°C]

Cumulative percentage

Master bedroom

Children bedroom

Bathroom

Page 10: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

9

3. Installation of the ventilation unit

As ventilation aggregate a SWEGON CASA R80 was chosen. The unit has a rotary heat exchanger

which allows a continuous operation down to -30 °C and heat exchange efficiency of up to 86%. The

unit is equipped with an electric after heater. The heater ensures that the air supplied to the rooms is

always at a comfortable temperature (above 18 °C) even during the coldest periods. It was decided to

install the ventilation unit in the laundry room where it would take the least space from the

occupants. See Figure 7 and Figure 8 for the laundry room before and after the installation.

Figure 7. Laundry before the installation

Page 11: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

10

Figure 8. Installed ventilation unit

For the air distribution in the house a Lindab InDomo system was used. The ducts are of small

diameter and go directly from the distribution box in the laundry room (see Figure 9) to each room

without further branching. This system allows easy installation and maintenance (cleaning).

Figure 9. Distribution boxes and ducts to each room

The layout of the ventilation system can be seen in Figure 10. The fresh air is supplied into the two

bedrooms in a first floor and to the living room. The exhausts are placed in a kitchen, bathroom and

laundry. The range hood remained connected directly to outside and was not part of the installation.

Page 12: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

11

Figure 10. Ventilation system layout

The supply air terminals were selected to eliminate noise and to supply the air to the rooms in optimal

direction to avoid any draught discomfort or short circuiting. The supply air terminal and its

connection to the duct are shown in Figure 11 and Figure 12.

Figure 11. Supply air terminal device

Figure 12. Air terminal device connection in a closet

The terminals on the façade have been selected to eliminate the intake of snow and insects (Figure

13). The existing fresh air valves were sealed with mineral wool and polyurethane (see Figure 14) to

avoid cold bridges and moisture damage of the construction.

Figure 13. Fresh air intake

Page 13: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

12

Figure 14. Mineral wool and polyurethane sealing of the fresh air valve

In Figure 15 the thermographic pictures of a fresh air valve are shown before and after insulation. One

can see that the lowest temperature of the valve before sealing was 8.6 °C (outside temperature -12

°C) whereas after the sealing it was above 21.2 °C.

Figure 15. Fresh air valve before (left) and after (right) sealing

The unit is equipped with a controller (Figure 16) which allows the occupants to choose between

three operation modes (see Table 1)

Table 1. Ventilation unit modes

Mode Speed [%] Air flow [m3/h] Air change [h-1]

Away 25 36 0.19

Home 55 120 0.63

Boost 80 180 0.95

Page 14: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

13

The occupants do not have an option of turning the ventilation system completely off at any time.

However, if the users turn the unit into “Away” mode its operation is almost unnoticeable yet there is

still an air change of 0.19 h-1 in the house. In addition to the controller there is a hygrostat (Figure 16)

in the bathroom which turns on the “Boost” mode in case of increased humidity (above 60%) in

bathroom automatically (during showers for example).

Figure 16. Ventilation unit controller (left) and hygrostat

Page 15: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

14

4. Indoor climate after the installation

After installation of the ventilation unit the indoor climate was monitored for four months to see any

possible changes. A period of two days was selected and compared with the state before installation.

4.1. Carbon dioxide

It can be seen from Figure 17 and Figure 18 that the CO2 concentration has decreased significantly after the installation of the ventilation unit. The night time average concentration decreased from 3124 ppm to 1420 ppm in a master bedroom and from 2977 ppm to 1520 ppm in a children’s bedroom. Although the CO2 concentration is still higher than the recommended value, the difference is marginal when compared to the original state and can be mitigated by adjusting the ventilation unit to supply more air into the bedrooms.

Figure 17. CO2 concentration in master bedroom before and after installation of the ventilation unit

0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

09

:00

11

:00

13

:00

15

:00

17

:00

19

:00

21

:00

23

:00

01

:00

03

:00

05

:00

07

:00

09

:00

11

:00

13

:00

15

:00

17

:00

19

:00

21

:00

23

:00

01

:00

03

:00

05

:00

07

:00

CO

2 -

con

cen

trat

ion

[p

pm

]

Time of the day

Before installation After installation Recommended maximum

Night average before Night average after

Night (occupied) Night (occupied)

Page 16: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

15

Figure 18. CO2 concentration in children’s bedroom before and after installation of the ventilation unit

4.2. Relative Humidity

The average relative humidity has (as expected) decreased after the installation. However, as it can be

seen from the Figure 19 the amount of time when the RH is within the recommended range had

actually increased from 72% to 77%. That is due to moisture recovery effect of the rotary heat

exchanger.

0

500

1000

1500

2000

2500

3000

3500

4000

45000

9:0

0

11

:00

13

:00

15

:00

17

:00

19

:00

21

:00

23

:00

01

:00

03

:00

05

:00

07

:00

09

:00

11

:00

13

:00

15

:00

17

:00

19

:00

21

:00

23

:00

01

:00

03

:00

05

:00

07

:00

CO

2 -

con

cen

trat

ion

[p

pm

]

Title

Before installation After installation Recommended maximum

Night average before Night average after

Night (occupied) Night (occupied)

Page 17: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

16

Figure 19. Relative humidity in bedrooms after installation of the ventilation system

RH in the bathroom has also decreased. Additionally the time the RH was above 50% during and after

shower was significantly shortened (from 1 hour 55 minutes to 27 minutes) thanks to the boost

function of the ventilation unit (see Figure 20).

Figure 20. Relative humidity in Bathroom during shower before and after installation of the ventilation system

0

10

20

30

40

50

60

0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Re

lati

ve h

um

idit

y [%

]

Cumulative percentage

Before installation

After installation

Average before

Average after77%

0

10

20

30

40

50

60

70

80

90

00:00 00:10 00:20 00:30 00:40 00:50 01:00 01:10 01:20 01:30 01:40 01:50 02:00

Re

lati

ve h

um

idit

y [%

]

Time

RH - after installation RH - before installation

1h55min

27min

Page 18: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

17

4.3. Temperature

Although the temperature of the outside air was below -20 °C, the temperature of the air supplied to

the rooms was above 18 °C all the time.

Figure 21. Temperature of the outside and supply air

-30

-25

-20

-15

-10

-5

0

5

10

15

20

25

00

:00

04

:00

08

:00

12

:00

16

:00

20

:00

00

:00

04

:00

08

:00

12

:00

16

:00

20

:00

Tem

pe

ratu

re [

°C]

Time

Outside temperature

Supply air temperature

Page 19: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

18

5. Economy

The costs of the unit including installation were approximately 62,000 DKK. The average power

consumption of the unit was 80 W which yields the annual electricity consumption of 700 kWh (1,150

DKK). Additionally the annual heat loss related to ventilation is about 1260 kWh (1,010 DKK)

It is difficult to estimate the annual savings as the home was not properly ventilated before the

installation.

However, assuming a proper ventilation of the home the annual costs related to natural ventilation

without heat recovery would be approximately 6,700 DKK. With ventilation unit installed these costs

are 2,160 DKK (1,010 DKK for heat and 1,150 DKK for electricity). The ventilation unit will hence save

around 4,540 DKK per year which gives a simple return of investment of less than 14 years.

6. Conclusion

The experiment showed that the poor indoor climate of the house can be significantly improved in an

energy efficient way. The investment into the system would pay back in less than 14 years. Because

the system helps to reduce high humidity it can also be looked at as prevention against mold.

Consequently there are also savings related to mold renovation which were not included in the

calculations.

Page 20: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

19

References

[1] M Kotol, M Kotol, Survey of occupant behaviour, energy use and indoor air quality in Greenlandic dwellings, (2012).

[2] M Kotol, C Rode, G Clausen, TR Nielsen. Indoor environment in bedrooms in 79 Greenlandic households, Build.Environ. 81 (2014) 29-36.

[3] P Wargocki, DP Wyon, J Sundell, G Clausen, PO Fanger. The effects of outdoor air supply rate in an office on perceived air quality, Sick Building Syndrome (SBS) symptoms and productivity, Indoor Air-International Journal of Indoor Air Quality and Climate. 10 (2000) 222-236.

[4] CA Erdmann, MG Apte. Mucous membrane and lower respiratory building related symptoms in relation to indoor carbon dioxide concentrations in the 100-building BASE dataset, Indoor Air. 14 (2004) 127-134.

[5] OA Seppanen, WJ Fisk, MJ Mendell. Association of ventilation rates and CO2 concentrations with health and other responses in commercial and institutional buildings, Indoor Air-International Journal of Indoor Air Quality and Climate. 9 (1999) 226-252.

[6] P Wargocki, DP Wyon. Providing better thermal and air quality conditions in school classrooms would be cost-effective, Build.Environ. 59 (2013) 581-589.

[7] RJ Shaughnessy, U Haverinen-Shaughnessy, A Nevalainen, D Moschandreas, A preliminary study on the association between ventilation rates in classrooms and student performance, Indoor Air. 16 (2006) 465-468.

[8] JS Park, CH Yoon. The effects of outdoor air supply rate on work performance during 8-h work period, Indoor Air. 21 (2011) 284-290.

[9] D Wyon. The effects of indoor air quality on performance and productivity, Indoor Air. 14 (2004) 92-101.

[10] U Satish, MJ Mendell, K Shekhar, T Hotchi, D Sullivan, S Streufert, et al. Is CO2 an Indoor Pollutant? Direct Effects of Low-to-Moderate CO2 Concentrations on Human Decision-Making Performance, Environ.Health Perspect. 120 (2012) 1671-1677.

[11] Dansk Standard, DS/EN 15251 - Indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal environment, lighting and accoustics, Dansk Standard, Charlottenlund, 2007.

[12] American Society of Heating, Refrigerating and Air-Conditioning Engineers, Ventilation for acceptable indoor air quality, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, Ga., 2004.

[13] J Sundell, M Wickman, G Pershagen, SL Nordvall. Ventilation in Homes Infested by House-Dust Mites, Allergy. 50 (1995) 106-112.

[14] I Pirhonen, A Nevalainen, T Husman, J Pekkanen. Home dampness, moulds and their influence on respiratory infections and symptoms in adults in Finland, Eur.Resp.J. 9 (1996) 2618-2622.

Page 21: Tuapannguanut, 3911 Sisimiut...Tuapannguanut, 3911 Sisimiut Report Sisimiut 10.7.2015. 1 Foreword Winters in the Arctic are very cold and long. When the temperatures are so low, the

20

[15] CG Bornehag, J Sundell, L Hagerhed-Engman, T Sigsgaard. Association between ventilation rates in 390 Swedish homes and allergic symptoms in children, Indoor Air. 15 (2005) 275-280.

[16] L Reinikainen, J Jaakkola, O Seppanen. The Effect of Air Humidification on Symptoms and Perception of Indoor Air-Quality in Office Workers - a 6-Period Cross-Over Trial, Arch.Environ.Health. 47 (1992) 8-15.

[17] PT Ninomura, R Bhargava. Heat recovery ventilators in multifamily residences in the arctic, ASHRAE Trans. 101 (1995) 961-966.

[18] Ergonomi inden for termisk miljø - Analytisk bestemmelse og fortolkning af termisk komfort ved beregning af PMV- og PPD- indekser og lokale termiske komfortkriterier = Ergonomics of the thermal environment - Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria, 2 udg ed., Dansk Standard, Charlottenlund, 2006.