troubleshooting flowchart
TRANSCRIPT
-
7/27/2019 Troubleshooting Flowchart
1/3
GET bs00date.lst and KIdate.lst
using WS_FTP from NMS
directory
/global/home/rnp/NDr_d
Update files Cell Performance.xls and GSM Performance.xls
Note: GSM Performance.xls will graph trend of CSSR, TCH drop, Blkng etc. of each BSC. Then youll know which BSC needs
immediate attention. Whether problem is due to certain sites only or the whole BSC youd have to confirm from the Cell Perfo rmance.xls
Cell Performance.xls gives statistics of each cell for the whole day with weights added for prioritization purposes.
PROBLEM:LOW CSSR
Call Set-up Success Ratecontributors:
SDCCH Blkng, SDCCH Drop,
TCH Blkng, Ater Congestion
High TCH Blkng:
1. Check history of the cell from the to see if itsreally congested.
Note: Sudden increase in traffic may be caused by a
sector of the site or a different nearby site that was
down so check if they are working normally. Use
MapInfo to check sites surrounding it.
2. Check column tch availability to see if all
nstalled TRXs are working normally.
Note: If certain TRX of the site are blocked by user,
you must confirm from OSS why (is it a new trx to
be added, having problems, or just accidentally
blocked)
High SDCCH Blkng:
1. Check reason for high SDCCH usage. SDCCH is used only
for SMS and location updates.
Very High Location Updates? check parameter MNC and
MCC from the ZEQO. MNC must be 03 and MCC=515.
Check defi ned location ar eas. Must be the same for same
Site ID (1800 and 900). Check which neighbor sites LAC is
different and is causing the location updates. Confirm if this is
really the designed value of LAC. Parameter CRH from ZEQO
may be changed to 10 dB for the site and the neighbor site to
help lessen Location Update.
2. Check configuration. Is it combined (MBCCHC) or separate
(MBCCH at TS0 and SDCCH at TS1)? Change to separate
config to lessen SDCCH blocking. Also the TRX aside from
the MBCCH trx must have an assigned SDCCH at TS1.
3. If it is a 900 cell with an 1800 overlay, if the 1800 is not
congested on the SDCCH, C2 must be activated to bias sdcch
traffic to the 1800 and REO must be set from 6 to 20. The
higher the value the greater the bias.
High SDCCH DROP (check from network doctor ndp166mx_d, the cause of
sdcch drop ABIS, RF, Aif ? Etc.
May be solved simply by restarting the BTS, or replace a hardware part, or retune,
or define or correct definition in the MSC, or change BCSU assignment depending
on the following:
1. Channel failure rate alarm, low mean holding time alarm from the ZEOL, low
traffic and corresponding send buffer overflow alarm in ZAHO for the BCSU of the
TRX involved may be solved by changing BCSU assignment
2. No alarm, no traffic, sudden increase in sdcch drop may be solved by restarting
the site. Just give it a kick.
3. SDCCH drop due to Aif (based from the ndo166mx_d). Site might not be
defined in the MSC. Or wrongly defined (locked in the MSC, wrong CI etc)
4. For sites with more than one t rx and sdcch drop is >50%. And all the traffic goes
only to one trx. Quality is low for that trx which does not carry traffic based from
the cell analyzer (report no. 216 from the Network Doctor, - This may be
interfered or have some hardware fault like wrong wiring, termination or
connection in the back plane, or tx output power, etc
5. Interfered sites may have high sdcch drop. Please check uplink interference from
the zero command. Retune if interfered. If it has 2 TRX and a frequency is hard to
find you may change the site to hopping mode to lessen interference.
6. Transmission problems check disturbance from command ZYMO:ET, 46;
(where 46 is the et number)
7. Check branching table
TROUBLEHOOTING FLOWCHART
Call Congestion at Ater (BSC-MSC Links)
1. Capacity of voice channels at the BSC-MSC link not sufficient. Needs expansion
2. The effect of this is usually felt in all the sites in the BSC
So its important that Ater congestion and signalling link loading between the BSC
and MSC are also monitored.
-
7/27/2019 Troubleshooting Flowchart
2/3
PROBLEM:LOW CCSR
Call Completion Success
Rate
contributors:
TCH Drop
High TCH DROP (check from network doctor ndp163mx_d, the cause of TCH drop ABIS, RF, Aif ? Etc.
1. Channel failure rate alarm, low mean holding time alarm from the ZEOL, low traffic and corresponding send buffer overflow
alarm in ZAHO for the BCSU of the TRX involved may be solved by changing BCSU assignment
2. From the ZAHO command, there is an alarm 2993 BTS and TC Unsynchronization Failure
a. There is error in the branching table. Ex. certain TS of TRX not defined
b. Fault in the BCSU or Ater ( as what happened before and TCH drop were felt in the entire BSC)
c. Faulty TRX or some hardware fault in the BTS
3. Interfered sites may have high sdcch drop. Please check uplink interference from the zero command. Retune if interfered. If it
has 2 TRX and a frequency is hard to find you may change the site to hopping mode to lessen interference.
4. Transmission problems check disturbance from command ZYMO:ET, 46; (where 46 is the et number)
5. Handover failures. Not all handover failures will result to drop calls. However, if the cell is not able pass the call successfully
to another after retries, the signal continues to deteriorate until the call is dropped.
OTHER PROBLEMS:
1. BTS NOT DEFINED IN THE MSC: (command: ZEPO:CI=_,LAC=_; or ZEPO:NO=_; where _ is the cell id)
no call seizures and requests can be made in the BTS, only handover traffic. (totch column of KI has value)
2. WRONG LAC or CELLID of the BTS in the MSC: (command: ZEPO:NO=10254 where 10254 is the cell id)
high sdcch dro. Also no calls can be made
3. VERY POOR UPLINK QUALITY or DOWNLINK QUALITY or SIGNAL STRENGTH
might be due to interference. Or antenna problem. Hardware further check at TRX level
4. Understanding of the different parameters is necessary also in troubleshooting. Since poor performance of a BTS may be just due to some wrong
parameter setting. Here are some from the BTS parameters (ZEQO)
Cell Barred = N PER = 7 hours MCC= 515
PLMN Permitted = 0-7 MNC= 03
5. HIGH HANDOVER FAILURES/ SITE HAVING SAME CELLID as some other sites. CELLID must be unique, if both BTS with the same CELLID are
working this will be a problem already. If one is blocked and the other is working like in the case during cut-over where the BTS is defined
already in the other BSC but blocked by user, this might cause confusion in the system and cause handover failures.
6. CELL HAVING SMALL COVERAGE. Check timing advance statistics. Check hardware, quality and downlink strength
NOTES:
Various network doctor files are available and automatically generated by the NMS for your
troubleshooting. You may view or retrieve it from the FTP \global\home\rnp\NDr_d
ndp150mx_dtotal handover failure per BTS
ndp153mx_dHO failure per BTS for each adjacency
ndp190mx_dinterference per BTS for GSM
ndp190px_dinterference per BTS for DCS
ndp250mx_dCSSR per BTS
ndp163mx_dTCH drop per BTS and cause
ndp166mx_dSDCCH drop per BTS and cause
-
7/27/2019 Troubleshooting Flowchart
3/3
Common commands:
ZEEI:BTS=_ ; ZEEI:BCF=_; to view configuration of site
ZERO:BCF=_; ZERO:BTS=_; to view uplink interference level, number of occupied TS
and channel config
ZEEL:BTS=_; ZEEL:BCF=_; to view number of idle, occupied and blocked SDCCH and TCH
ZEOL:_; (where _ =BCF number)
ZYMO:ET,_; (where _ =ET number) to view transmission stats, counters (if there is disturbances)
ZAHO; to view all the alarm in the BSC
ZEOL; to view current alarms of all the BCFs in the BSC
ZEUO:_; (where _ =BTS number) view power parameters of the BTS
ZEQO:BTS=_:all; (where _ =BTS number) view BTS parameters of the BTS
ZEAO:BTS=_; (where _ =BTS number) view adjacents cells of the BTS
ZEHO:_; (where _ =BTS number) view handover parameters of the BTS
ZEPO:CI=_,LAC=_; or ZEPO:NO=_; (where _ =CELL ID) to view definition at the MSC of the BTS
We hope this document will serve as a guide to your analysis of the sites performance and in your
troubleshooting. This does not give the whole picture of the troubleshooting process, the greater part is learned
from actual experience, analysis and observations, as problems are varied and you may have to try different
creative approaches to pinpoint the problem and find an effective solution. Thank you.
written by:
Norlyn Langub
Performance Team SE-Wireless Access