trident 2011

28
Solid Dielectric Switchgear Providing load and fault interrupting switching for systems rated through 38kV, 800A continuous, 12.5 and 16kA symmetrical interrupting Submersible vault designs Dead-front padmount designs Time proven, solid epoxy insulation Modular construction Maintenance-free operation Ease of automation Lazer TM ready CATALOG TS11 November, 2011

Upload: ramlijavier

Post on 29-May-2017

244 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Trident 2011

Solid Dielectric Switchgear

Providing load and fault interrupting switching for systems rated through

38kV, 800A continuous, 12.5 and 16kA symmetrical interrupting

• Submersiblevaultdesigns• Dead-frontpadmountdesigns• Timeproven,solidepoxyinsulation• Modularconstruction• Maintenance-freeoperation• Easeofautomation• LazerTMready

CATALOG TS11November,2011

Page 2: Trident 2011

General FeaturesWorldWide experience and perFormanceSince 1905, G&W has been provid-ing custom electrical products andinnovative solutions to power usersaroundtheworld. Today,G&Wcon-tinues that traditionwitha full lineofsolid dielectric switchgear using theindustry’slatestinsulationtechnology.Tridentswitchgearcombinesthebestsolid dielectric insulation materialswithtimeproven,rugged,andreliableswitchingdesigns.Drawingonmanyyearsoffieldexperienceintheareasof loadbreak switchingand vacuumfault interrupter technology,G&Wof-fers one of the widest selections ofelectrical distribution switchgear intheindustry.

solid dielectric technoloGyTrident switchgear utilizes G&W’stimeproven,submersibleepoxypoly-mer system to fully encapsulate thevacuum interrupters. This systemprovides excellent insulation proper-ties and incorporates a permanentlybonded semi-conductive externalcoating providing a fully shielded,void-free construction. Internalshieldslimittheelectricalstressintheepoxy,thereforeincreasingitselectri-cal integrity. All modules are 100%factory tested for partial discharge.Dual ratio current transformers areencapsulated within each moduleprovidingeither500:1or1000:1pro-tectioncharacteristics.

submersibilitySolid dielectric switchgear is dead-front and fully submersible. Unitshave remained fully operable afterwithstanding years of submersion atdepthsofupto10feet(3m).

maintenance beneFitsSolid dielectric insulation means nomoreroutinemaintenanceaswithoilandairswitchgear.Soliddielectricin-sulation also offers an alternative toSF6insulateddevices.

application FlexibilitySoliddielectricswitchgearofferscom-pact, modular construction. Moduleconfigurations permit elbow styleconnections to be all front mountedor front/backmounteddependingonuserpreference.Thesamesizemod-ulescanfunctionaseitherloadbreakor fault interrupting. Three phaseswitches can be linked together tocreate tailoredmulti-wayswitchcon-figurations. Trident fault interruptersofferawidevarietyofelectronicover-current controls for customized sys-temprotectioncoordination.Automa-tioniseasywhetheritisanautomatictransferschemeorafullyintegrateddistribution automation “Smart Grid”project.

Page 2

p Three phase Trident-S fault interrupters in a submersible vault application.

ideal replacement For oil Fuse cutouts Tridentfaultinterruptersareanidealreplacementforsinglephaseorthreephaseoilfusecutoutsbyofferingthefollowingadvantages:

•Nomorefuselinkstostockorreplace•Maintenance-free,nonflammablesoliddielectricinsulation•Positiveloadbreakoperationandeasyresetoftrippedcircuits•Electroniccontrolsmirrorfuselinkcurves•Easytoautomate•200Awellor600Aseparableconnectorbushing

Fully testedTrident switches are designed andtestedtoapplicablestandardsinclud-ing IEEEC37.74 (IEEEC37.71 andC37.72),IEEE386,IEC60265,IEEE592and IEEE57.12.28. All fault in-terrupter devices must pass reclos-er-class duties as outlined in IEEEC37.60.

INDEXGeneralFeatures.............Page2ThreePhaseDesigns......Page4Multi-WayDesigns...........Page12SinglePhaseDesign.......Page18Accessories/Options........Page21

Page 3: Trident 2011

the Flexibility oF solid dielectric technoloGy

Page 3

operatinG mechanism FlexibilityTrident-SP,SandSTswitchesincor-porate integralsinglephaseor threephase spring-assisted mechanismsfor positive open and close opera-tions. The operating mechanismsarelocatedwithinaweldedstainlesssteel housing, constructed to with-stand continuous submersible envi-ronments. The spring mechanismsoperate thevacuum interrupters,en-capsulatedwithintheepoxymodules,to accomplish load break switchingandfaultinterruptingprotection.Trident-SR switches incorporate aninternal magnetic actuator in placeof the spring-assisted mechanism,providinghighspeedoperation.Themagnetic actuator eliminates theneedforadd-onexternalmotorsandcablingmakingitanidealsolutionforautomatedswitchingapplications. cable entrance Flexibility Cable entrances canbeeither 200Awell or 600A separable connectorbushings for accepting elbow styleconnectors. The rugged epoxy sur-faceminimizestheforcerequiredforremoving elbow connections com-pared to rubber-to-rubber junctions.Different module orientations permitcableentry from the front, side, bot-tomorbackoftheunit.

interrupter control FlexibilityTridentswitchgearoffersavarietyofovercurrent controls including manySchweitzerEngineeringLaboratories(SEL) models for fault interruptingswitches to suitmost any protectionrequirement. All G&W controls areself-powered from the integral cur-rent transformers and offer over 30different Time Current Characteristic(TCC) curve families. Optional fea-tures include inrush protection (coldloadpickup), instantaneous,groundfault, time delay,minimum response

Modular Flexbility

time,andmanualtrippushbuttons.Othersmaybeprogrammedthrougha laptop computer, or with a frontpanel interface. Trident controlsmay be mounted within an externalNEMA4X(IP56)or6P(IP67)enclo-sure,orwithintheswitchmechanismhousing (IP68), eliminating the needfor external cabling. G&W can alsointegrate other manufacturer’s con-trols depending on user preference.

mountinG FlexibilityTridentswitchgearissuitableforsub-mersible vault or padmount installa-tions.Theymaybemountedverticallyorhorizontally,onawallorfloor,andinanyattitude. Thesmall footprint isidealforspacerestrictedapplications.Stainlesssteelmountingbracketsareavailableformaximumcorrosionresis-tance.Parkingstandsareavailable.

Operating Handle FlexibilityVarious styles of operating handlesare available depending upon userpreference. Handlescanbe remov-able or permanently fixed to theswitch. Handles can be straight orangledprovidingthebestmechanicaladvantage for operating personnel.Handles canbe locatedon the frontorsideoftheswitch.Allarehookstickoperable.

automation FlexibilityTrident switchgear is easily adaptedfor automation requirements. Fromsimple remote control through so-phisticated distribution automationschemes,G&Whastheproductsandintegrationexpertisetodothejob.

• Spring-assisted or magnetic actuator operation

• Submersible, welded construction

• Operating handle options • Cable entrance options

“C” Module- Front access

“Z” Module- Front/ back access

Page 4: Trident 2011

trident®-s three phase sWitchGearTrident-S threephase,spring-assist-ed switchgear is available for loadbreak or fault interrupting switching.TheTrident-Sisidealforthreephasedistributionswitchingandprotection,aswellasforthreephaseoilfusecut-outandoilswitchgearreplacements.Faultprotectioncanbeprovidedus-ingvacuum interrupterswith integralcurrenttransformersandavarietyofovercurrentcontrols.

Features•15.5,27,or38kV,800A continuouscurrent•12.5kAsymmetricalinterruptingwith16kAavailableat15.5kV•Manualorautomatedoperation•Padmountandvaultdesigns•Verticalorhorizontalmounting•Hookstickoperablewithpermanentorremovablehandles•Submersibleconstruction•Optionalhandlepermitting switchtofunctionasaload breakorfaultinterrupter

p Horizontal mounted fault interrupter in a submersible vault.

p Padmount switch with horizontal mounting and diagonal, spread bushing configuration.

Page 4

p Fault interrupter with wall mounted control box and side mounted operating handle.

Side mounted handles can be positioned with hookstick eye on top or bottom for best mechanical advantage.

Spring-assisted operating mechanism Viewing window u

Closed (red)Open (green)

Drive rod

Vacuum bottle

Encapsulated current transformer

Encapsulated 200A well or 600A seperable connector bushings for elbow connectors

Page 5: Trident 2011

or

or

trident®-s three phase sWitchGear

Page 5

ratinGs

IEEE C37.60 Fault interruptinG dutyPercentofMaximumInterruptingRating

Approx.InterruptingCurrent,Amps

No.ofFault

Interrup-tions

15-20%45-55%90-100%

2,0006,00012,500

445616

Total#ofFaultInterruptions:116

Padmount style, front access, horizontal mountApproximateDimensionsApproximateWeight=700lbs.(318kg)Spreadbushingconfiguation

Enclosuredepth=41”(1035mm)

Vault styleApproximateDimensionsApproximateWeight=200lbs.(91kg)

Configuration “B”withbushingfrontandhandlefrontmounted.

Configuration “A”withbushingfrontandhandlesidemounted.

pTypicalOne-line

TypicalOne-line

Voltage Class (kV) 15 25 35

Maximum(kV) 15.5 27* 38

BILImpulse(kV) 110 125 150

ContinuousCurrent(A) 800 800 800

LoadBreakCurrent(A) 800 800 800

1MinACWithstand

(kV)35 60 70

1MinACWithstanddry(kV)

34 40 50

15MinDCWithstand

(kV)53 78 103

MomentaryCurrent(kA)asym

20 20 20

Fault-Close3-times

(kA)asym20 20 20

FaultInterruptingCurrent(kA)asym

12.5** 12.5 12.5

1SecCurrent(kA)sym 12.5 12.5 12.5

MechanicalOperations 2K 2K 2K

* 29.3kV available** 16kA available

Page 6: Trident 2011

trident®-sr three phase sWitchGear

Page 6

p Vault style Trident-SR with front mounted bushings.

Trident-SR,highspeedmagneticac-tuator (3-1/2 cycles), SCADA readyswitchessimplifytheprocessofauto-matedswitchingandfaultinterruptiononsystemsratedthrough38kV.Theextremelyflexibledesignpermits theuser to customize the best solutionfor theirparticularapplication. Fromremote operation, to fully automateddistributionautomationorSmartGridschemes, theTrident-SR offersmul-tipleapplicationfunctionality,allwithinthe same compact switch footprint.Comparethesefeatures:

Features•15.5,27,or38kV,800Acontinuouscurrent•12.5kAsymmetricalinterrupting•Magneticactuatorforautomatedoperations•Padmountandvaultdesigns•Verticalorhorizontalmounting•Hookstickoperablewithfront mountedhandles.

For load break switching -Therug-ged magnetic actuator is tested toover 10,000 mechanical load breakoperations.

For fault interrupting -AvarietyofSchweitzerEngineering Laborato-ries(SEL)relaysandG&Welectroniccontrolsareavailabletobestmeetthespecific protection needs of the ap-plication. Programmingusinga lap-top computer or built-in LCDdisplayareavailableoptions.G&Wcontrolsare powered by current transform-ershousedwithintheepoxymodule.Otherstylecontrolsarealsoavailable.

For remote operation - Hand heldremoteoperatorsareavailablepermittingpushbuttonoperationfromeitherabovegroundforvaultapplica-tionsorfromacontroladjacenttotheenclosureforpadmountapplications.

Viewing window

Drive rod

vacuum bottle

Encapsulated current transformer and voltage sensing

Manuel trip handle

High speed magnetic actuator

Manuel close handle

Encapsulated 200A well or 600A seperable connector bushings for elbow connectors

Page 7: Trident 2011

trident®-sr three phase sWitchGear

Page 7

SCADA ready automation -Current transformers encapsulatedwithin the epoxy modules provideintegralcurrentsensing.Integralca-pacitively coupled voltage screensprovide three phase analog voltagevaluesforconnectiontoawideselec-tionofrelaysandRTUs.

For Lazer® ready automation - Trident-SR switches are an integralpart ofG&W’spre-engineeredLazercontrolpackagetoprovideautomaticpowerrestoration.UsingSELrelayswithdistributedcapabilitiesandpeer-to-peercommunication,G&W’sLazersolution with Trident switchgear cangreatly simplify the automation pro-cess from small scale through largescalesystemrequirements.

For future Smart Grid - Thinking of automating in the nearfuturebut need switchesnow? Thebuilt-in features and application flex-ibilityoftheTrident-SRcanhelpsim-plifyyourdecision.

Compact, clean design - No add-on motors or linkage. Noexternalcurrent transformersorvolt-agesensorshangingfromelbowcon-nectors.Trident-SRswitchesfeaturebuilt-incomponents.

Maintenance benefits - Solid dielectric insulation eliminatesanyconcernabout liquidorgaseousdielectrics.Thatmeansnomorerou-tineswitchmaintenance.

Submersibility -Solid dielectric switchgear is dead-front and fully submersible. Unitshave remained fully operable afterwithstandinga20footheadofwaterfor20days.

Contact position indicator -Alargeviewingwindowpermitsvisual verification of vacuum con-tact position, either open or close.The position indicator is connecteddirectly to the drive assembly. Inaddition, three different color LEDscanalsobeprovided to verify eitherPowerOK,Tripped,orBlockedposi-tion. LED verification of “open” and

“close”, inaddition to theflag indica-tor,canalsobetwoofthethreeLEDoptions.Anoperationcounterisalsoincluded.

Manual trip handle - A hookstick operable handle per-mits manual opening of the switch.Once opened, the switch is thenblocked from any remote com-mands thereby prohibiting anyclose operation. The open andblocked positions are padlockableproviding true mechanical lockout.

Manual close handle - Ahookstickoperablehandlepermitsmanualclosingofanelectronically tripped or manuallyopenedfaultinterrupter.

Cable entrance flexibility - Cable entrances canbeeither 200Awell or 600A separable connectorbushings for accepting elbow styleconnectors.In-lineordiagonalspreadversionconfigurationsareavailabletofacilitatecabletraining.

p Contact position indicator with LEDs

p Manual trip handle

p Manual close handle

Voltage Class (kV) 15 25 35

Maximum(kV) 15.5 27* 38

BILImpulse(kV) 110 125 150

ContinuousCurrent(A) 800 800 800

LoadBreakCurrent(A) 800 800 800

1MinACWithstand(kV) 35 60 70

1MinACWithstanddry(kV)

34 40 50

15MinDCWithstand(kV) 53 78 103

MomentaryCurrent(kA)asym

20 20 20

Fault-Close3-times

(kA)asym20 20 20

FaultInterruptingCurrent(kA)asym

12.5 12.5 12.5

1SecCurrent(kA)sym 12.5 12.5 12.5

MechanicalOperations 10K 10K 10K

IEEE C37.60 FAULT INTERRUPTING DUTYPercentofMaximumInterruptingRating

Approx.InterruptingCurrent,Amps

No.ofFault

Interrup-tions

15-20%45-55%90-100%

2,0006,00012,500

445616

Total#ofFaultInterruptions:116

* 29.3kV available

ratinGs

Page 8: Trident 2011

trident®-sr three phase sWitchGear

Padmount, front access, horizontalSpreadbushingconfigurationAp-proximateDimensionsApproximateWeight=1100lbs.(500kg)

Vault style ApproximateDimensions.ApproximateWeight=400lbs.(180kg)

Trident-SR with integral Bypass Switch- ApproximateDimensions.Approx.Weight=900lbs.(408kg)CombinationTrident-SRwithTrident-SswitchpermittingtheTrident-SRanditsrelaytobefullytestedwithoutde-energizingthecircuit.

Options1)200Atapbushingstopowerpotentialtransformersforcontrolpowerorvoltage sensing.2)VariousrelaysavailableinNEMA4,4X, submersible6PandsubmersibleIP68 (20foot,20day)ratings.

t Front access, vault style bypass switch.

73’(1856mm)

50”(1280mm)

Catalognumber:WA13-RE9SLB

Page 8

Depthtoendofhandle=18”(457mm)

pTypicalOne-line

pTypicalOne-line

Depth=41”(1041mm)

or

or

p SEL’s 751A relay makes an ideal solution.

pTypicalOne-line

Page 9: Trident 2011

trident®-st three phase sWitchGear

Page 9

p Trident-ST with individual, single phase operating handles.

Spring-assisted operating mechanism

Encapsulated current transformer

Vacuum bottle

Viewing window

40"(1022mm)

22"(556mm)

Vault styleApproximateDimensions.ApproximateWeight=400lbs.(180kg)

Depthtoendofhandle=27”(690mm)

p Typical One-line

Trident-STthreephase,spring-assist-ed switchgear can provide eitherthree phase or single phase faultprotection.TheTrident-STisidealforthreephasedistributionswitchingandprotection,aswellasforthreephaseoil fuse cutout and oil switchgearreplacements. Fault protection canbe provided using vacuum interrupt-erswithintegralcurrenttransformersandavarietyofovercurrentcontrols.

Features•15.5,27,or29.3kV,630A continuouscurrent•12.5kAsymmetricalinterrupting•Padmountandvaultdesigns•Verticalorhorizontalmounting•Hookstickoperablewith permanentorremovablehandles.•Optional3-phaseexternal gangedlinkagefor3-phase operation

Voltage Class (kV) 15 25

Maximum(kV) 15.5 27*

BILImpulse(kV) 110 125

ContinuousCurrent(A) 630 630

LoadBreakCurrent(A) 630 630

1MinACWithstand(kV) 35 60

1MinACWithstanddry(kV) 34 40

15MinDCWithstand(kV) 53 78

MomentaryCurrent(kA)asym 20 20

Fault-Close3-times(kA)asym 20 20

FaultInterruptingCurrent(kA)asym 12.5 12.5

1SecCurrent(kA)sym 12.5 12.5

MechanicalOperations 2000 2000

PercentofMaximumInterruptingRating

Approx.InterruptingCurrent,Amps

No.ofFault

Interruptions

15-20%45-55%90-100%

2,0006,00012,500

445616

Total#ofFaultInterruptions:116

ratinGs

IEEE C37.60 FAULT INTERRUPTING DUTY

* 29.3kV available

Page 10: Trident 2011

hoW to order trident® three phase sWitchGear

Page 10

Mounting

Configuration*

Voltage Class

Number of Phases

Description Code

Padmount,frontaccess,verticalmount P

Padmount,frontaccess,horizontalmount H

Padmount,front/backaccess,vertical B

Padmount,front/backaccess,horizontal R

Vaultstylewithnon-submersibleelectronics(ifsupplied) V

Vaultstylewithsubmersibleelectronics(ifsupplied) W

Description CodeBushingsfront;sidemountedhandle ABushingsfront;frontmountedhandle BBushingsback;sidemountedhandle CBushingsback;frontmountedhandle D

Description Code

Trident-S S

Trident-ST T

Trident-SR R

Description Code

Loadbreakswitch L

Type1 1

Type2 2

Type3 3

Type4 4

Type7 7

ATScontrol:ATC451 A

Connectorized:SEL351RorSEL651R R

Pre-engineeredcontrol:Relay,RTU,IED E

Provisionsforfutureuse:Junctionbox P

Customertowireandsupplycontrol W

Description Code

Nooptions 0

Auxiliarycontacts 1

Motoractuator(Trident-S only) 2

Stationaryorportable(Trident-S only) orstationaryorhandheldcontrol(Trident-SR only) 3

Voltagesensing 4

Auxiliarycontactsandvoltagesensing(Trident-SR only) 5

Auxiliarycontacts,voltagesensingandstationaryorhandheldcontrol(Trident-SR only) 6

Auxiliarycontactsandstationaryorportable(Trident-S only) orstationaryorhandheldcontrol

(Trident-SR only)7

Voltagesensingandstationaryorhandheldcontrol(Trident-SR only) 8

Customengineered 9

Loadbreak/faultinterrupterswitch A

Bypassswitch B

Groundcutin/cutoutswitch C

Controls, if applicable

Switch Style

Options

kV Code15 125 235 3

Phase CodeThree 3

* Contact your G&W representative for other configurations

Closest to Housing Away from Housing Code

200A 200A 2

200A 600A 3

600A 200A 4

600A 600A 6

hoW to order:Selectfromthevariouscatalogbreakdownchartoptionsbelow.Enterthedesiredselectioninthecorrespond-ingcatalognumberposition.

___3-____

1

2

3

4

5

6

7

Bushing Arrangement9

21 3 4 5 6 7 8

Page 11: Trident 2011

Example 3:Fault Interrupter with Integral Bypass Submersiblevaultstyle,15kV,threephase,faultinterrupterwithintegralbypassswitch,sidemountedhandleandall600Abushings.AnSEL-751Acontrolisrequired.The catalog number would be: WA13-RE9 SLB

Example 1:Automated Load Break SwitchVaultstyle,27kV,threephase,loadbreakswitchwithall600Abushings.Afrontmountedhandlewithahandheldcontrolisrequired.The catalog number would be: VB23-RL36

Example 2:Fault Interrupter with SEL351RConnectorized Control and Voltage SensingPadmountstyle,horizontal,frontaccess,spreadbushings,35kV,threephasefaultinterrupterwithall600Abushings.Afrontmountedhandleisrequired.The catalog number would be: HB33-RR06

Page 11

orderinG examples - trident®-s sWitchGear

600A

M

600A

200A

200A

200A

200A

orderinG examples - trident®-sr sWitchGear

600A

600A

600A

600A

orderinG examples - trident®-st sWitchGear

200A

200A

600A

600A

Example 1:Oil Fuse Cutout ReplacementVaultstyle,15kV,threephasefaultinter-rupterwithall200AdeepwellbushingsandaNEMA6PType2overcurrentcontrol.Asidemountedhandleisrequired.The catalog number would be: WA13-S202

Example 2:Automated Load Break SwitchVaultstyle,15kV,threephase,loadbreakswitchwithall600Abushings.AsidemountedmotoractuatorwithNEMA4Xstationarycontrolisrequired.The catalog number would be: VA13-SL36

Example 3:Fault interrupter with three phaseelectronic and manual trip, and three phase manual resetPadmountstyle,35kV,threephasefaultinterrupterwithall200AbushingsandaType7overcurrentcontrol.Asidemountedhandleisrequired.The catalog number would be: PA33-S702

Example 1:Oil Fuse Cutout ReplacementSubmersiblevaultstyle,15kV,threephasefaultinterrupterwithall200AdeepwellbushingsandaType1overcurrentcontrol.Afrontmountedhandleisrequired.The catalog number would be: WB13-T102

Page 12: Trident 2011

trident® multi-Way sWitchGear

p Flexible inter-way bus connection system provides reliable performance in a low profile, compact design.

p Automated padmount switch utilizing magnetic actuators and integral voltage sensing electronics for a high speed automatic transfer application.

Page12

Multi-wayTridentswitchesconsistofindividualthreephasemoduleslinkedtogether througha flexible inter-waybus connection. Design your ownswitch combination to ideally matchyourapplicationrequirements.Buildmultiple ways using the same stylemodules or combine Trident stylesS,ST,SPorSRinwhatevercombi-nationyoudesire. Modulesmaybeeitherfaultinterruptersorloadbreakswitches.

Voltage Class (kV) 15 25

Maximum(kV) 15.5 27*

BILImpulse(kV) 110 125

ContinuousCurrent(A)** 630 630

LoadBreakCurrent(A) 630 630

1MinACWithstand(kV) 35 60

1MinACWithstanddry(kV) 34 40

15MinDCWithstand(kV) 53 78

MomentaryCurrent(kA)asym 20 20

Fault-Close3-times(kA)asym 20 20

FaultInterruptingCurrent(kA)asym 12.5# 12.5

1SecCurrent(kA)sym 12.5 12.5

MechanicalOperations,Trident-S 2000 2000

MechanicalOperations,Trident-SR 10K 10K

*29.3kVavailable**800AavailableusingTrident-Sand Trident-SRonly#16kAavailableusingTrident-Sonly

Features•15.5,27kVand29.3kVmaximumdesignvoltage•12.5kAsymmetricalinterruptingwith16kAavailableat15.5kV•Manual,motoractuatoror magneticactuatoroperation•Padmountandvaultdesigns•Hookstickoperable,eitherpermanentorremovablestylehandle•Automaticsourcetransfer applicationsavailable•IntegralPTforcontrolpower available•Compactconstruction•Allfrontaccessorfront/back accessdesigns

ratinGs

PercentofMaximumInterruptingRating

Approx.InterruptingCurrent,Amps

No.ofFault

Interruptions

15-20%45-55%90-100%

2,0006,00012,500

445616

Total#ofFaultInterruptions:116

IEEE C37.60 FAULT INTERRUPTING DUTY

Page 13: Trident 2011

Page13

65"(1651mm

(1830mm)

(1397mm)

72"

55"

Padmount style, Trident-SR and Trident-ST, front / back accessApproximateDimensions.ApproximateWeight=2600lbs.(1182kg)

Padmount style, Trident-S front accessApproximateDimensions.ApproximateWeight=1800lbs.(817kg)

56"(1412mm)

81"(2064mm) 41"

(1041mm)

Trident-SRside Trident-STside

76"(1930mm)

p Typical One-line

t Typical One-line

Page 14: Trident 2011

Configurations A & C VaultWallMount,SideHandleApproximateWidthofSwitch3Way............................78”(1981mm)4Way............................103”(2616mm)5Way............................128”(3251mm)6Way............................153”(3886mm)ApproximateDepth.......21”(533mm)ApproximateHeight......35”(889mm)

Padmount,SideHandleApproximateWidthofEnclosure3Way............................80”(2032mm)4Way............................105”(2667mm)5Way............................130”(3302mm)6Way............................155”(3937mm)ApproximateDepth.......44”(1118mm)ApproximateHeight......68”(1727mm)

Configurations B & DVaultWallMount,FrontHandleApproximateWidthofSwitch3Way............................66”(1676mm)4Way............................84”(2134mm)5Way............................102”(2591mm)6Way............................120”(3048mm)ApproximateDepth.......21”(533mm)ApproximateHeight......35”(889mm)

Padmount,FrontHandleApproximateWidthofEnclosure3Way............................80”(2032mm)4Way............................98”(2489mm)5Way............................116”(2946mm)6Way............................134”(3404mm)ApproximateDepth.......44”(1118mm)ApproximateHeight......68”(1727mm)

Page14

Photo right: Seven-way vault style Trident-SR switch with front mounted operating handles.

Vault style, Trident-SR front accessApproximateDimensions

Vault and Padmount style, Trident-S front access with front handleApproximateDimensions

trident® multi-Way sWitchGear

54"(1370mm)

172"(4370mm)

34"(864mm)

Vault and Padmount style, Trident-S front access with side handleApproximateDimensions

t Typical One-line

Page 15: Trident 2011

hoW to order - trident® multi-Way sWitchGear

hoW to order:Selectfromthevariouscatalogbreakdownchartoptionsbelow.Enterthedesiredselectioninthecorrespondingcatalognumberposition.

___-______....___

Configuration*

Voltage Class

Number of Phases

Way 2 Last Way

Description Code

Bushingsfront;sidemountedhandle A

Bushingsfront;frontmountedhandle B

Bushingsback;sidemountedhandle C

Bushingsback;frontmountedhandle D

Description Code

Trident-S S

Trident-ST T

Trident-SR R

Trident-SP P

Description Code

Loadbreakswitch L

Unswitchedway U

Type1 1

Type2 2

Type3 3

Type4 4

Type7 7

ATScontrol:ATC451 A

Connectorized:SEL351RorSEL651R R

Pre-engineeredcontrol:Relay,RTU,IED E

Provisionsforfutureuse:Junctionbox P

Customertowireandsupplycontrol W

Switch Style

Options

kV Code

15 1

25 2

Mounting Controls, if applicable

* Contact your G&W representative for other configurationsDescription Code

Nooptions 0

Auxiliarycontacts 1

Motoractuator(Trident-S only) 2

Stationaryorportable(Trident-S only) orstationaryorhandheldcontrol(Trident-SR only) 3

Voltagesensing(Trident-SR only) 4

Auxiliarycontactsandvoltagesensing(Trident-SR only) 5

Auxiliarycontacts,voltagesensingandstationaryorhandheldcontrol(Trident-SR only) 6

Auxiliarycontactsandstationaryorportable(Trident-S only) or

stationaryorhandheldcontrol(Trident-SR only)7

Voltagesensingandstationaryorhandheldcontrol(Trident-SR only) 8

Customengineered 9

Loadbreak/faultinterrupterswitch A

Groundcutin/cutoutswitch C

BusTieSwitch T

Description Code

Padmount,frontaccess,verticalmount P

Padmount,front/backaccess,vertical B

Vaultstylewithnon-submersibleelectronics(ifsupplied) V

Vaultstylewithsubmersibleelectronics(ifsupplied) W

21 3 4 5 6 7

1

2

3

4

5

6

7

Way 1

Phase Code

Single 1

Three 3

Page15

Page 16: Trident 2011

Example 1:3-Way Load Break with Auto Source TransferVaultstyle,25kVswitch.Ways1and3areloadbreakswitcheswithmagneticactuatorsandvolt-agesensingfortheautotransferandhave600Abush-ings.Way2isafaultinterrupterandhas200Abush-ings.FaultinterruptercontrolstobeType7.Allwaystohavesidemountedoperatingmechanisms/handles.ANEMA6PratedATC451controlused.The catalog number would be: WA23-RA4 S70 RA4.

Example 2:Bus Tie Switch with Two Unswitched WaysVaultstyle,15kV,threephase,loadbreakswitchwithtwounswitchedwaysandall600Abushings.Sidemountedhandlesarerequired.The catalog number would be: WA13-U00 SL0 SLT SL0 U00

Example 3:3-Way Combination Load Break and Fault Interrupter SwitchPadmountstyle,25kV,3-wayswitchwithtwo600Aloadbreakswitchmodules(ways1and3)andone200Afaultinterrupter(way2).FaultinterruptercontrolstobeType3.Switchoperatorstobefrontmountedwithallbushingsouttheback.The catalog number would be: PC23-SL0 S30 SL0.

orderinG examples - trident® multi-Way sWitchGear

600A 200A 600A600A 200A 600A

p Four-way front access, padmount Trident-S.

p Automated multi-way, Trident-S in a submersible vault installation.

600A 600A600A 600A

Page16

Page 17: Trident 2011

p Three-way, submersible vault, automatic transfer switch including submersible G&W ATC451 control.

Submersible Application Example

Installation shows a 3-way switch, frame mounted so the unit faces upward with side operating handles hookstick operable from above ground. The location is subject to complete submer-sion for extended periods of time. The yellow cable is con-nected to a laptop computer permitting programming of the overcurrent protection parameters for the switch.

Page17

Page 18: Trident 2011

Trident-SP single phase, spring-assisted switchgear is availablefor load break or fault interruptingswitching. The compact units areideal for switching residential loopsand for oil fuse cutout replace-ments. Fault protection can beprovided using vacuum interrupt-ers with integral current transform-ers and a variety of overcurrentcontrols.

Features •15.5,27,or29.3kV,630A continuouscurrent•12.5kAsymmetricalinterrupting•Padmountandvaultdesigns•Verticalorhorizontalmounting•Largeviewingwindowssimplify visualidentificationofopen (green)orclosed(red)vacuum contactposition.Theposition indicatorisconnecteddirectlyto thedriveassembly.•Hookstickoperable,permanent mountedoperatinghandles•Submersibleswitchconstruction•Submersiblecontrolsavailable•Manualoperation

ideal replacement For oil Fuse cutoutsTridentfaultinterruptersofferthefollowingadvantages:•Nomorefuselinkstostockor replace•Maintenance-free,nonflammable soliddielectricinsulation•Safe,positiveloadbreak operationandeasyresetof trippedcircuits•Electroniccontrolsmirrorfuse linkcurves•Compactfootprintforeasy changeout•Submersibleconstruction•200Awellor600Aseparable connectorbushings

trident®-sp sinGle phase sWitchGear

Page18

Spring-assisted operating mechanism

Vacuum bottle

Viewing window - Closed (red), Open (green)

Encapsulated 200A well or 600A separable connector bushings for elbow connectors

Voltage Class (kV) 15 25

Maximum(kV) 15.5 27*

BILImpulse(kV) 110 125

ContinuousCurrent(A) 630 630

LoadBreakCurrent(A) 630 630

1MinACWithstand(kV) 34 40

1MinACWithstanddry(kV) 53 78

15MinDCWithstand(kV) 53 78

MomentaryCurrent(kA)asym 20 20

Fault-Close3-times(kA)asym 20 20

FaultInterruptingCurrent(kA)asym 12.5 12.5

1SecCurrent(kA)sym 12.5 12.5

MechanicalOperations 2000 2000

PercentofMaximumInterruptingRating

Approx.InterruptingCurrent,Amps

No.ofFault

Interruptions

15-20%45-55%90-100%

2,0006,00012,500

445616

Total#ofFaultInterruptions:116

ratinGs

IEEE C37.60 FAULT INTERRUPTING DUTY

* 29.3kV available

Page 19: Trident 2011

Vault styleApproximateDimensionsApproximateWeight=75lbs.(34kg)

35.0"(889mm)

12.0"(305mm)

12.3"(312mm)

Configuration ‘A’withfrontmountedbushings.

24"(610mm)

38"(965mm)

FLIP TOP ENCLOSUREELECTRONIC CONTROL

30"(762mm)

31"(787mm)

Padmount style ApproximateDimensionsApproximateWeight=150lbs.(68kg)

Page19

orderinG examplesExample 1:Oil Fuse Cutout ReplacementVaultstyle,15kV,singlephasefaultinterrupter.ThefaultprotectionschemerequirestheoilfusecutoutTimeCurrentCharacteristic(TCC)curveandasinglephasesetting(Type7).All200Adeepwell,frontpositionedbushings.The catalog number would be: WA11-P702

Example 2:Load Break SwitchVaultstyle,25kV,singlephaseloadbreakswitchwithall200Adeepwellfrontpositionedbush-ings.The catalog number would be: VA21-PL02

200A

200A

200A

200A

p Submersible, subsurface installation permitting hookstick operation from above ground.

or

1.6"(41mm)

7.5"(191mm)

10.0"(254mm)

or

t Typical One-line

Typical One-line u

Page 20: Trident 2011

hoW to order - trident®-sp sinGle phase sWitchGear

Mounting

Configuration*

Voltage Class

Number of Phases

Description CodeBushingsfront;sidemountedhandle ABushingsback;sidemountedhandle C

Description Code

Trident-SPsinglephase P

Description Code

Loadbreakswitch L

Type1 1

Type3 3

Type4 4

Type7 7

Description Code

Nooptions 0

Auxiliarycontacts 1

Controls, if applicable

Switch Style

Options

kV Code15 125 2

Phase CodeSingle 1

* Contact your G&W representative for other configurations

Closest to Housing Away from Housing Code

200A 200A 2

200A 600A 3

600A 200A 4

600A 600A 6

Bushing Arrangement

hoW to order:Selectfromthevariouscatalogbreakdownchartoptionsbelow.Enterthedesiredselectioninthecorrespond-ingcatalognumberposition.

Description Code

Padmount,frontaccess,verticalmount P

Padmount,frontaccess,horizontalmount H

Padmount,front/backaccess,vertical B

Padmount,front/backaccess,horizontal R

Vaultstylewithnon-submersibleelectronics(ifsupplied) V

Vaultstylewithsubmersibleelectronics(ifsupplied) W

___1-P___21 3 4 5 6 7 8

1

2

3

4

5

6

7

8

Page20

Page 21: Trident 2011

G&W interrupter overcurrent controlsTheovercurrentcontrolmonitorsthecurrentandsendsatripsignalwhichopensthevacuuminterruptersandinterruptsthefaultcurrent.G&Wcontrolsareself-poweredfromthecurrenttransformerslocatedinsidethesoliddielectricmodule.Optionalremotetrippingisavailable.G&Walsooffersothermanufacturer’scon-trols,suchasSELrelays,dependingontheapplication.

StandardcontrolenclosuresareNEMA4X(IP56)rated.OptionalsubmersibleenclosuresareNEMA6P(IP67)rated.TheType7ismountedinsidetheswitch’smechanismhousingandhasanIP68rating.

G&W control optionsType 1controlsoperatethree,singlephasevacuuminterruptingmechanisms.TheType1canbefieldsetforeithersinglephaseorthreephasetripmode.Itisusedonswitcheswitheithersinglephaseresetorthreephasereset.Wheninthethreephasemode,allthreephasestripiftheselectedtriplevelofanyindividualphaseisreached.Triplevelselectionscanbemadeunderloadorno-loadconditionswithcurrentrangesin12selectablelevels.Tworangesofminimumtripsettingsareavailable,15to300ampsand30to600amps.Eachunitispre-programmedwith30TimeCurrentCharacteristic(TCC)curves.Thecurveselectioncanbesetorchangedatanytime.

An8poledipswitchallowstheusertochoosetheTCCcurvethatbestmatchestheirindividualcoordina-tionrequirements.Alabel,locatedontheinsideofthelid,providesakeyforthedipswitchsettings.Thecontrolcanbefactorypresettomeettheuser’srequirements.Asprotec-tionorcoordinationrequirementschange,settingscaneasilybechangedinthefield.Depressingthemanualtripbuttonwhenthecontrol

ispoweredupelectronicallytripsallthreephasesofthevacuuminterrupt-er.Eachcontrolalsoincludes“LastCauseofTrip”LEDs.TheseLEDsindicatewhichphaseexperiencedanovercurrentcondition,orthatthecon-trolwasgivenanexternalormanualtripcommand.

Type 2controlsofferfeaturessimilartoType1withthefollowingadditionalfeatures:-Threephaseprotectiononly-Minimumtripsetforallthree phaseswithoneselectorswitch-Adjustablephasetimedelay-Groundfault(phaseimbalance) withseparateadjustabletime delayselectorswitchforprotection oflargethreephasemotorsor transformers.Thegroundtrip levelisrepresentedasapercent oftheminimumtriplevel.-Instantaneoustripandinrush restraintfeatures

Type 3controlsofferfeaturessimilartoType2andmoreincluding:-Singlephaseorthreephasetrip-Vacuumfluorescentdisplay-Keypadoperationforprogramming parametersandretrievingstatus ofcurrentvalues-Adjustablephasetimedelay-Groundfaulttrip-Inrushrestraint-Phaseidentificationandmagnitude offaultindication-Readoutofreal-timecurrentvalues-Selectableinstantaneoustrip-Selectableminimumresponsetime-RS232orRS485serialinterface-Laptopprogrammingkitavailable

Type 4 controlsprovidethesamefeaturesasType3controls;however,thereisnokeypadpanel,displayscreen,ormanualtripbutton.Thecontrolisprogrammedusingalap-topcomputer.Alaptopprogrammingkitisavailable.

control options

p Type 1 control

p Type 2 control

p Type 3 control

p Type 4 control

Page21

Page 22: Trident 2011

control options

Type 7 controlsprovidethesamefeaturesasType4controls,exceptthatthecontrolsaremountedinternaltotheswitchmechanismhousing,eliminatingtheneedforaseparatecontrolenclosureandassociatedcabling.Thecontrolisprogrammedusingalaptopcomputer.Alaptopprogrammingkitisavailable.Singleandthreephaseversionsareavailable.

laptop proGramminG KitFor Type 3, Type 4 or Type 7 Providessoftwareandcableconnectiontoaportablelaptopcom-puterforprogrammingorretrievingfaultinterruptercontrolinformation.OnecableconnectstotheUSBportofthecomputerandtheothercon-nectstothecontrolbox(Type3or4)ormechanismhousing(Type7).

CatalogNumberforType3:ForUSBports:..............LPK7-Type3

CatalogNumberforType4and7:ForUSBports:..............LPK7-USB

compatible relaysBesidesG&W’sinterruptercontrols,variousotherrelayscanbeusedwithTridentswitchgearincludingSchweitzer’smodelSELFalcon,SEL-351R,SEL-651R,SEL-501,SEL-551,SEL-351SandSEL-751A.

remote operation For trident-sMotor ActuatorsForspring-assistedswitches,motoractuatorsarerequiredforremoteoperation.Actuatorsareexternallymountedtoeachswitchoperator.Ifcontrolsarespecified,theactua-torsarehardwiredwith25feetofcable.Padmountdesignsmayhavecablescuttolengthtofitwithintheenclosure.Ifnocontrolisspecified,theactuatorissuppliedwithamalethreadedconnectorforusewithpor-tablecontrols.Actuatorsarehousedwithinapainted,stainlesssteelenclosuresuitableforsubmersibleapplications.

Stationary ControlsSinglewayandmulti-waystationarycontrolsareavailableforbothloadbreakswitchesandfaultinterrupters.Controlscanbeacombinationofswitchandfaultinterrupterways,asrequired.ControlsaredesignedforSCADAinterface.

p Type 7 control board mounted inside the mechanism housing.

p Schweitzer’s SEL-751A control is one of many control options.

Page22

p Stationary Control

p Laptop Connector Cable

Page 23: Trident 2011

Portable ControlsForapplicationswhereACpowerisnotavailableattheswitchsiteoriftheflexibilityofmovingthecontroltodifferentlocationsisdesired,por-tablecontrolsareideal.Thecontrolishousedinanaluminumcarry-ingcasewithhandleandweighsapproximately12lbs.(5.5kg).A120VACcableissuppliedtochargethebatteries.Themaximumcontroltomotoractuatordistanceis50feet(15m).TheUniversalcontrolcanbeusedonbothloadbreakandfaultinterrupterswitches.

remote operation

For trident-srTrident-SRswitchgearalreadyincorporatesaninternal,highspeedmagneticactuatorandisSCADAreadybydesign.Noexternalactua-torsrequiredforremoteoperation.Variouscontroloptionsareavail-able.

SEL-751A Relay ControlSchweitzer’s751ArelaymakesanidealcontrolpackagefortheTrident-SR.Therelayincludesvoltageandcurrentinputswhichgreatlysimpli-fiesanydatamonitoringcapabil-ityavailablewiththevoltageandcurrentsensingsuppliedwiththeTrident-SR.Thisswitchandcontrolpackageoffersremotepowerstatusfrominsidetheswitchandremoteopen/blockstatusthroughthecon-trol.

Stationary ControlsApushbuttoncontrolisavailablepermittinglocalonsiteorremoteSCADAoperationoftheswitch.Thecontrolishardwiredintotheswitchandhousedwithinasubmersible,polycarbonateenclosureapproxi-mately6”Wx10”H.Standardcon-trolcableis25feet.Othercablelengthsareavailableupto100feet.

The24VDCcontrolcanbepow-eredbythe120VACsuppliedtotheswitchorfromaseparateACsourcedirectlytothecontrol.

Hand Held ControlsAhandheldcontrolisidealforundergroundvaultapplicationspermittingswitchoperationfromaboveground.Thecontrolcableishardwiredintotheswitchandusesathreadedconnectorforattachmenttothecontrol.Thepolycarbonatecon-trolboxisapproximately7”Wx4”H.The24VDCcontrolispoweredbytheswitch.

Page23

p Hand held controls permit switch operation from outside the vault.

p Stationary controls permit either local or remote SCADA operation.

control options

Page 24: Trident 2011

automatic transFer

ATC 451G&WATC451automatictrans-fercontrolsareavailableforG&WTridentswitchgearthrough38kV.Switchescanbevault(dryorsub-mersible)orpadmountstyles.Thetwoincomingsourcewayscanbelocatedinoneswitch,orintwoseparateswitchesforaddedredundancy.Manualswitchescanberetrofittedinthefield.Standardtransfertimesarewithin8-10seconds.

FeaturesUses SEL-451 relay-G&W’sATC451controlutilizesthefieldprovenSchweitzerSEL-451relayforitsprotectionlogicandprogrammingscheme.

Plug and play construction-TheATC451ispre-programmedandpackagedwithallrequiredcomponentstosimplifyinstallationandmaximizereliableperformance.VariousstylesofNEMAenclosuresareavailabledependingontheapplication.

Overcurrent protection for up to two fault interrupting ways-TheATC451caneliminatetheneedforseparatevacuuminterruptercontrols.Dependingonuserpreferenceandsystemprotectionschemes,variousstylesofseparateinterruptercontrolsareavailable.

SCADA ready-EachATC451comesstandardwithseveralserialportsforcommunicationtoSCADAsystems.MultipleprotocolsareavailableincludingDNP3.0(standard),MirroredBits(standard),andIEC61850(option).Ethernetorfiberopticportsforcommunicationsarealsoavailableoptions.

Lazer® ready -TheSCADAreadycapabilitysimplifiestherequirementsforcommunicationtootherintelligentfielddevicesforautomaticpowerrestorationschemes.ThissimplifiestheintegrationoftheATCintoany

G&Wpre-engineeredLazerautoma-tionsystemwhereautomatictransferisrequired.

Generator source capability-The451canbeprogrammedtopermitastandbygeneratortobeusedinsteadofasecondutilitysource.

Bus tie configurations-TheATC451canbeusedwithabus-tieswitchpermittingautomatictransferwheretheloadisnormallybalancedbetweentwosources.

User friendly controls-Largepushbuttonsareclearlylabeledandprovideeasycontrolcommandsfromthefrontpanel.

Sequence of event recorder-EachATC451includesaSequenceofEventsRecorderwhichwillrecordthelast1000entries,includingset-tingchanges,powerups,andselect-ablelogicelements.

Flexible voltage sensing options -Integralvoltagesensingbushingsareavailablewhicheliminatetheneedforcumbersomeadd-ondevic-es.Thebushingsare600Arated,fullysubmersible,andprovideoneanalogoutputperphaseandonedigitaloutputperwayforvoltagemonitoring.Elbowmountedsensorsandpotentialtransformersarealsoavailable.

p The ATC 451 is laptop programmable.

p Close up of operating panel

control options

Page24

Page 25: Trident 2011

control options

lazer® distribution automation

G&W’sLazerDistributionAutomationsolutionisapre-engineeredpackagewhichperformsautomaticfaultdetec-tion,isolationandrestoration(FDIR)operationsonoverheadandunder-grounddistributionsystems.G&Wusesover100yearsofindustryexperi-encetomatchtheproperswitchgear,controls,andcommunicationdevicesfortheapplication.ForaLazersolu-tion,G&WprimarilyusesSchweitzerEngineeringLaboratoriesintelligentrelays,oneoftheindustry’smostrespectedsuppliers.Othermanufac-turer’srelaysareavailableonrequest.

ALazerdistributionautomationpack-ageconsistsofG&W’smediumvolt-ageswitchingdevices,oneormoreprotectiverelays,communication,andtheintegrationknowledgetomakeitallworktogether.Thesepackagedsystemscanbeusedforcriticalloadapplicationsasbasicastworeclos-ersperformingatransferonvoltagelossorascomplicatedasanetworkedswitch/SCADAsystemwithloadflowmanagementcapabilities.

FeaturesDistributed and Centralized IntelligenceG&Wprovidesthreeconfigurationoptionsthatcanbeselectedtomatchalmostanyapplication.

Peer-to-peer-Forhighspeedtransfersandrestoration,distributedintelligenceandpeer-to-peercommunicationusingprotocolslikeSELMirroredBits®allowforrestorationtimethatcanbemea-suredincycles.Allprotectionandres-torationlogicisstoredintheindividualrelays.Thisoptionisperfectforhighreliability,closedloopcircuits.

Distributed control-Thisconfigura-tionisaccomplishedusingacontrolliketheSEL3354orRTACcomput-ingplatformthatcommunicatestotheintelligentrelaysinthesystem.Thesedevicescanbemountedontheswitchesoratacentrallocationsuchasasubstation.Alloftherelaysareresponsibleforcircuitprotectionand

communicatingtheirstatusbacktothecentralcontrolthroughopenprotocolslikeDNP3.0.

Central control-Thisconfigurationisidealforlargernetworkcircuitswhereadvancedcapabilitiesarerequired.ItiscontrolledbySCADAorDMSsoftwarethatoffersunparalleledmonitoringandcontrol.G&WusessoftwarefromSurvalentTechnologylikeSmartVU™.Thissoftwareoffersauser-friendlyinterfaceaswellastheadvancedcapabilitytohandleauto-maticloadflowadjustmentsandnet-workmanagement.

Protection and ControlAwidevarietyofprogrammablefeaturesareavailableforprotectionincludinguptoeightindependentsettinggroupswhichoffermultiplelayersofprotection.Advancedcom-municationassistedtrippingschemes,suchasPermissiveOverreachingTransferTrip(POTT)andDirectionalComparisonBlocking(DCB)canbeemployedtoofferextremelyhighspeedfaultisolationonclosedloopsystems.Thesetrippingschemescanbebackeduptomaintainprotectiononfailureofbreakersorcommunication.

CommunicationFlexiblecommunicationandopenprotocolsarecriticalforintegratingtoexistingSmartGridsandexpandingtohandlefutureneeds.Lazersolutionsofferflexiblecommunicationusinghardwiredconnections,fiberopticcable,orarangeofwirelesstechnolo-giesonRS232,RS485,andEthernetports.Someofthedifferentpro-

tocolsavailableare:•DNP3.0•SELMirroredBits(proprietary)•IEC61850withGOOSEmessaging

a smart Grid componentASmartGridconsistsofallpointsinapowernetworkcommunicatingtoautomaticallymakedecisions.Thegoalistomaximizethereliabilityandefficiencyofthenetworkwhilegiv-ingindividualconsumerscontrolovertheirconsumption.SomeofthebasictechnologiesareSCADA,automaticreconfigurationandrestoration,AMR/AMI(meterreading)software,smartmeters,andrenewableenergyintegra-tion.

G&W’sLazerDistributionAutomationsolutionsarepartofthe5kVto38kVnetworksinaSmartGridandfunc-tiontoautomaticallyrestorefaultedlinesorcircuitsthathavelostvoltage.Auto-mationwillimproveadistributionsysteminthefollowingways:

Improved reliability and metrics-Quicklyisolatefaultsandrestorepowertoasmanycustomersaspos-sible.

Improved operational efficiency-Knowingdetailedinformationwithinthedistributionsystemallowscrewstoquicklyidentifythelocationoffaultsandknowthestatusoffielddevices.

Safety-Multiplelevelsoflockoutsandremoteswitchingfromoutsideofenclosedspacesimprovessafetyforoperators.

p Padmount switch with SEL controls.

Page25

Page 26: Trident 2011

Page26

Junction boxForauxiliarycontactsandremotepower/remotetripconnections.IncludesNEMA4X(IP56)enclosurewithterminalstripconnectionsforterminatinguptofoursetsofauxiliarycontactsorfourcontrolsforremotepower/remotetrip.Key interlocKsKeyinterlocksareavailabletoassuresafecoordinationofequipment.Switchescanbespecifiedwithkeylocksfactoryinstalled.Specifylockingschemewhenordering,eitherlockinopenorlockinclosedposition.Forkeylockstobecoordinatedwithotherequipment,othermanufacturer’sinfor-mationmustbeprovided.

Ground luGsBronze,eyeboltstylegroundlugsareavailablefor4/0maximumconductorcable.

FramesBolted,galvanizedmountingframesareavailableforverticalmountingofvaultstyleswitchesprovidinga24”distancefromthegroundtothecenterofthebottombushing.Othersizeframesareavailable.ConsultyourG&Wrepresentativeforavail-ability.

parKinG standsUnpaintedstainlesssteelpark-ingstandsareavailableforeachentranceposition.Parkingstandscanbedesignedtosupportmechan-icaldeadbreakdevicesforvisiblebreakrequirements.ConsultyourG&Wrepresentativewithspecificrequirements.

spread bushinGsAdiagonalbushingconfigurationisavailablewhichincreasesthedistancebetweenthebushingstofacilitatecabletrainingifrequired.

operatinG handlesAnangledstainlesssteelhandlewithhookstickoperableeyeisavail-ableforpermanentattachmenttoeachswitchoperator.Thehandlecanbepositionedupordowntopro-videforoptimumoperatingleverage.Ifaremovablehandleisdesired,abronzehandlewithhookstickeyeisprovidedwhichpositionsoverthehexnutoftheswitchoperator.Onehandleisprovidedperswitch.

p Junction Box

p Key Interlock

p Ground lug

p Permanently attached hookstick operating handle

p Diagonal bushing arrangement with parking stands

p Removable hookstick operating handle

options

Page 27: Trident 2011

p Side mounted motor actuator

p Ground Cut In / Cut Out Selector Switch

p Load Break / Fault Interrupter Selector Switch

p Front mounted motor actuator

options

load breaK / Fault interrupter selector sWitchFaultinterruptingswitchesaresup-pliedwithanexternaloperatingleverwhich,whenoperated,disablesallovercurrentprotectionwhilestillper-mittingloadbreakswitching.Thispermitstheusertoperformemer-gencyswitchingtoreconfigureloadswithouttheworryofpossibleinad-vertenttrippingcausedbytemporaryovercurrentswhichmightotherwisehappeniftheovercurrentcontrolswerestillactivated.Thisoptionelim-inatestheneedforrelaytechnicianstotemporarilychangetheprotectionscheme.Theswitchleversarepad-lockableandoperablebyhookstickorrope.

Ground cut in / cut out selector sWitchForfaultinterruptingswitchesincorporatinggroundfaultprotec-tion.Switchesaresuppliedwithanexternaloperatingleverwhich,whenoperated,disablesallgroundfaultprotectionwhilestillpermittingloadbreakswitching.Thispermitstheusertoperformemergencyswitch-ingtoreconfigureloadswithouttheworryofpossibleinadvertenttrippingcausedbytemporarycurrentimbal-anceswhichmightotherwisehappeniftheovercurrentcontrolswerestillactivated.Thisoptioneliminatestheneedforrelaytechnicianstotempo-rarilychangetheprotectionscheme.Theswitchleversarepadlockableandoperablebyhookstickorrope.

motor actuator Automationbeginswiththeaddi-tionofmotoractuatorstoamanualswitch.Theseactuatorscanbefac-toryinstalledfornewequipmentorretrofittedtoswitchgearinstalledinthefield.TheyarehousedinaNEMA6Penclosureforsubmersibleinstallations.

auxiliary contactsAuxiliarycontactsaremountedinter-naltothemechanismhousingtoprovideremoteindicationofswitchcontactposition.OnenormallyopenandonenormallyclosedformCcontactisprovided.Junctionboxeswithterminalstripconnectionsforuptofourauxiliarycontactsareavail-able.

Page27

Page 28: Trident 2011

The Flexibility of Solid Dielectric Technology ... G&W offers a variety of epoxy encapsulated products including:

Solid Dielectric Viper® Reclosers• To38kV,12.5kAinterrupting• Overheadandpadmountdesigns• Maintenance-freeoperation• WorkwithSELcontrols

Other Solid Dielectric Products• Multiplepointjunctionbarsand• Encapsulatedcurrentlimitingfuses• Distributioncabletransitionjoints• Varietyofcableentrancebushings

G&W ELECTRIC CO.3500W.127thStreetBlueIsland,ILUSA60406(708)388-5010Fax:(708)388-0755Website:www.gwelec.comISO14001:2004Registered

©November,2011 PrintedinUSA

SHANGHAI G&W ELECTRIC LTD.No.8Lane1505,ZuChongZhiRoad,ZhangJiang,Pudong,Shanghai,China201210+86-21-5895-8648,Fax:+86-21-5895-6829,Website:www.gwelec.com.cn