transformers and power flow

43
ELECTRICAL POWER TRANSMISSION AND DISTRIBUTION

Upload: nakul-surana

Post on 14-Jun-2015

132 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: Transformers and power flow

ELECTRICAL POWER TRANSMISSION AND

DISTRIBUTION

Page 2: Transformers and power flow

ENS 441/ELT 437 2

Single Phase Transformer

A transformer is an electrical device that is used to raise or lower the voltage (or current) level.

A single-phase transformer has two electrically isolated windings.

The winding that is connected to the electrical power source is called the “primary” winding.

The winding that is used to draw electrical power is called the “secondary” winding.

Syed A Rizvi

Page 3: Transformers and power flow

ENS 441/ELT 437 3

Ideal Transformer

Figure below shows a schematic diagram of an ideal single-phase transformer.

Syed A Rizvi

EP = induced voltage on the primary

side (RMS)

ES = induced voltage on the secondary

side (RMS)

NP = Number of turns on the primary

windings

NS = Number of turns on the secondary

windings

Φm = magnetic flux created by the

source voltage E

Φm

Page 4: Transformers and power flow

ENS 441/ELT 437 4

Ideal Transformer

When the primary winding is connected to an AC power source it produces an instantaneous magnetic flux “Φm(t)” linking the primary as well as secondary windings of the transformer.

The flux linkage induces an instantaneous voltage “Ep(t)” in the primary winding in accordance with the Faraday’s law of electromagnetic induction. That is,

Syed A Rizvi

Page 5: Transformers and power flow

ENS 441/ELT 437 5

Ideal Transformer

Since the voltage applied at the primary is sinusoidal, therefore, the magnetic flux Φm(t) is also sinusoidal and mathematically it can be expressed as

.Therefore,

or

Syed A Rizvi

Page 6: Transformers and power flow

ENS 441/ELT 437 6

Ideal Transformer

Substituting and we get

Above Eq. shows that the induced voltage Ep(t) leads the magnetic flux Φm(t) by 90o. The RMS value of Ep(t), denoted by Ep is given by

or

(1)

Syed A Rizvi

Page 7: Transformers and power flow

ENS 441/ELT 437 7

Ideal Transformer

Since the magnetic flux Φm(t) also links the secondary winding that has Ns turns, the RMS value of the induced voltage at the secondary side of the transformer, denoted by Es is given by

(2)

Comparing Eqs. (1) and (2) yields

or

Syed A Rizvi

Page 8: Transformers and power flow

ENS 441/ELT 437 8

Ideal Transformer

or

or

where, “a” is called the turn ratio of the transformer.

Syed A Rizvi

Page 9: Transformers and power flow

ENS 441/ELT 437 9

Single Phase Transformer

Figure below shows an ideal transformer with a load on the secondary side.

Syed A Rizvi

Page 10: Transformers and power flow

ENS 441/ELT 437 10

Ideal Transformer Under ideal conditions no current flows through the

primary winding and the primary current “IP” is zero when secondary side is open.

When a load is connected to the secondary side, a current, Is, flows out of the secondary windings.

The secondary current, Is, creates a magnetic flux “Φs” in the transformer’s core.

Since the source voltage, E, is unchanged, which mean the flux, Φm, must remain the same as it was before the load was connected.

Therefore, the new flux (Φs) due to the secondary the current, Is, must be countered by an equal and opposite flux. Syed A Rizvi

Page 11: Transformers and power flow

ENS 441/ELT 437 11

Ideal Transformer

The counter flux “Φp” is produced by causing a current, Ip, to flow into the primary windings.

Under ideal conditions, the fluxes Φs and Φp cancel each other and the total flux through the core remains Φm.

Result: Primary and secondary induced voltages (Ep and Es) remain unchanged.

The flow of the primary current, Ip, represents the power transfer from primary side to the secondary side of the transformer to support the load Zs.

Under ideal conditions there is no loss of power during the power transfer from the primary side to the secondary side of the transformer.

Syed A Rizvi

Page 12: Transformers and power flow

ENS 441/ELT 437 12

Ideal TransformerTherefore, the total power, Sp, on the primary side of the transformer must be equal to the total power, Ss, on the secondary side of the transformer, where

and

but Sp = Ss, therefore,

But , therefore,

or

Syed A Rizvi

Page 13: Transformers and power flow

ENS 441/ELT 437 13

Ideal Transformer

The load impedance as seen by the primary side, denoted by Zp, can be given by

but .

Therefore,

Above Eq. shows an important property of the transformer; that is, it can be used to change the effective impedance of any load and thus can also act as an impedance transformer.

Syed A Rizvi

Page 14: Transformers and power flow

ENS 441/ELT 437 14

Ideal Transformer

Using impedance transformation, the impedances on the secondary side can be expressed as the equivalent impedances on the primary side to greatly simplify the circuit analysis involving transformers.

Syed A Rizvi

Page 15: Transformers and power flow

ENS 441/ELT 437 15

Practical Transformer

The ideal transformer is lossless. In a real transformer, however, the

primary current is not zero under no-load condition.

Reason: Iron losses and magnetizing reactance

Causes of iron loss: Eddy currents Hysteresis losses

Syed A Rizvi

Page 16: Transformers and power flow

ENS 441/ELT 437 16

Practical Transformer

Eddy Current Losses: When time-varying magnetic flux passes

through a solid metallic core, the solid metallic core acts like a bundle of concentric conductors and a voltage is induced in each of these sections of the metallic core.

In a solid metal plate each of these sections would behave like a short-circuited conductor and, therefore, the induce voltages would cause a strong currents which swirl back and forth in the core.

These currents are called eddy currents.

Syed A Rizvi

Page 17: Transformers and power flow

ENS 441/ELT 437 17

Practical Transformer

Syed A Rizvi

Eddy currents are a major source of generating heat in transformers. In a solid metal core these currents can be so strong that they render the core red hot. Solution: Design the core

with thin laminated strips to insulates the strips from each other.

Result: The length of the conducting path is greatly reduced.

Magnitudes of the induced voltages in the core thereby diminishing eddy current losses.

Page 18: Transformers and power flow

ENS 441/ELT 437 18

Practical Transformer

Hysteresis LossesThe magnetic flux is caused by magnetic field strength, H. The resulting flux density, B, in any material is related to the magnetic field strength (H) by the following equation:

where,B = magnetic flux density (weber/m2 or tesla)H = magnetic field strength (A-turns/m)µo = permeability of free space =

µr = relative permeability of the material

The value of µr changes with flux and, therefore, the relationship between B and H is expressed in terms of a B-H curve.

Syed A Rizvi

Page 19: Transformers and power flow

ENS 441/ELT 437 19

Practical TransformerFigure below shows the closed B-H curve called hysteresis loop.

Syed A Rizvi

The area under this curve represents the energy that changes into heat during each cycle (joules per cubic meters).

Iron losses are represented as resistance (Rm) in parallel to the primary terminals of the transformer.

Page 20: Transformers and power flow

ENS 441/ELT 437 20

Practical Transformer Magnetizing Inductance: In order to generate the

magnetic flux Φm, a current must flow through the primary windings.

This current is called magnetizing current and depends on the permeability of the material used to build the core.

Higher permeability means lower magnetic current and vice versa.

Permeability can be represented by a parallel inductance (Xm) to the primary terminal because magnetizing current does not affect the amount of induced voltage.

This inductance is called magnetizing inductance.Syed A Rizvi

Page 21: Transformers and power flow

ENS 441/ELT 437 21

Practical Transformer

Winding Resistance: In a real transformer, the winding of the

transformer have finite resistance that must be taken into account while analyzing or modeling a practical transformer.

Since these winding resistances result in a potential drop when current passes through the windings, they are represented as the series resistors (Rp and RS), both at the primary as well as at the secondary side of the transformer.

Syed A Rizvi

Page 22: Transformers and power flow

ENS 441/ELT 437 22

Practical Transformer

Leakage Flux: In a real transformer some of Φs and Φp does leak

in the air. This flux leakage induces voltages both in the

primary winding and secondary windings, which is counter to the voltages induced by the flux Φm.

It results in a voltage drop both at the primary as well as the secondary side.

Accordingly, the effect of the leakage flux is represented as the series impedances (Xlp and Xls) at the primary as well as the secondary side of the transformer in the model of a practical transformer.

Syed A Rizvi

Page 23: Transformers and power flow

ENS 441/ELT 437 23

Practical Transformer

Figure below shows the complete model of practical transformer that incorporate the iron losses, magnetizing current, primary and secondary winding resistances, and the effect of the leakage flux under load conditions.

Syed A Rizvi

Page 24: Transformers and power flow

ENS 441/ELT 437 24

Practical Transformer

The model of the practical transformer is easier to analyze if the elements on the secondary side are shifted to the primary side as shown in Fig. below.

Syed A Rizvi

Page 25: Transformers and power flow

ENS 441/ELT 437 25

Practical Transformer

No-load Condition:Under no-load condition the secondary is open and, therefore, no current flows through the secondary terminals.

Syed A Rizvi

Page 26: Transformers and power flow

ENS 441/ELT 437 26

Practical Transformer

Full-load Condition:Under the full-load condition and, therefore, we can ignore Rm and Xm and the model for the practical transformer reduces to the one shown below.

Syed A Rizvi

Page 27: Transformers and power flow

ENS 441/ELT 437 27

Practical Transformer

The model of the practical transformer can further be simplified by adding the resistances and inductances as follows:

and

Furthermore, Rlp and Xlp can be represented by the complex impedance Zp as follow:

Syed A Rizvi

Page 28: Transformers and power flow

ENS 441/ELT 437 28

Practical Transformer

Figure below shows the simplified circuit for the practical transformer with full load.

Syed A Rizvi

Page 29: Transformers and power flow

ENS 441/ELT 437 29

Practical Transformer

Example: Specifications of a power transformer are as follows:Compute the full-load Vs, Is, as well as heat dissipation in the transformer using the simplified model. Also, compute Iron losses using the model under no-load condition .

Syed A Rizvi

Sn (KVA) Enp (V) Ens

(V)

Inp

(A)

Ins (A) Rp

(Ω)

1000 69000 6900 14.5 145 27.2Rs (Ω) Xlp (Ω) Xls (Ω) Xm (Ω) Rm (Ω) Io (A)

0.25 151 1.5 505000 432000 0.210

Page 30: Transformers and power flow

ENS 441/ELT 437 30

Practical Transformer

Solution: Let’s assume it’s a pure resistive load and full-load secondary voltage is the same as Vns and full-load secondary current is the same as Ins. Now we can calculate the load resistance, RL, as follows:

The turn ratio is given by

Now we can compute Rep and Xep

Syed A Rizvi

Page 31: Transformers and power flow

ENS 441/ELT 437 31

Practical Transformer

The resistance shifted to primary, RLp, is given by

Now we can compute the total impedance of the model, ZTp, as follows

Now we can compute primary current, Ip, primary voltage, Ep, secondary current, Is, and secondary voltage, Es as follows

Syed A Rizvi

Page 32: Transformers and power flow

ENS 441/ELT 437 32

Practical Transformer

Now we can compute the heat loss due to the load as follows

Finally, we’ll compute iron losses at no load and at full load as follows

Syed A Rizvi

Page 33: Transformers and power flow

ENS 441/ELT 437 33

Practical Transformer

Total power loss at full load = 10.69 + 10.74 = 21.43 KW.

This power loss produces significant amount of heat that must be removed from the transformer to avoid any damage to transformer.

Syed A Rizvi

Page 34: Transformers and power flow

ENS 441/ELT 437 34

Practical Transformer

There are a number of techniques that are used in the transformers to remove heat.

Through natural circulation of air (type AA),

Through forced air circulation (type AFA), Oil-immersed self-cooled (OA), Oil immersed self-cooled/forced air cooled

(type OA/FA) to name a few.

Syed A Rizvi

Page 35: Transformers and power flow

ENS 441/ELT 437 35

Practical Transformer

Figure below show the front view of an OA/FA type power transformer.

Syed A Rizvi

Page 36: Transformers and power flow

ENS 441/ELT 437 36

Practical Transformer

Syed A Rizvi

Figure next shows the rear view of the same transformer where cooling fans can be seen which remove heat from the transformer through forced air circulation.

A transformer is called a “step-down” transformer if the secondary voltage, ES, is lower than the primary voltage, EP. On the hand, if the secondary voltage is higher than the primary voltage, it is called a “step-up” transformer.

Page 37: Transformers and power flow

ENS 441/ELT 437 37

Practical Transformer

Terminal Marking on Power Transformers: In power transformers, the high voltage

(HV) terminals are marked by symbols H1 and H2.

The low voltage (LV) terminal are marked by symbols X1 and X2.

These terminals are mounted on the transformer tank in a way that they either have additive polarity or they have subtractive polarity.

Syed A Rizvi

Page 38: Transformers and power flow

ENS 441/ELT 437 38

Practical Transformer

Figure below shows the terminal marking and polarity of the power transformers. It is imperative to know the correct

polarity of the transformers if you are connecting them in

Syed A Rizvi

parallel or configuring a 3-phase transformer bank using single phase transformers.

Page 39: Transformers and power flow

ENS 441/ELT 437 39

Practical Transformer

Voltage Regulation:

Voltage regulation is measure of variation in the secondary voltage from no-load to full-load condition when the primary voltage is kept constant.

Voltage regulation is expressed in percent (%) and is defined by the following equation

Syed A Rizvi

Page 40: Transformers and power flow

ENS 441/ELT 437 40

Power in AC Systems

In AC systems the power is divided into three different categories:Apparent Power: It is the product of the voltage and complex

conjugate of the current and is expressed in “volt-amperes” or VA.

If the current I = IR + j IX then the conjugate of I, denoted by I*, is given by I*= IR – j IX. The apparent power, PA, is given by

Syed A Rizvi

Page 41: Transformers and power flow

ENS 441/ELT 437 41

Power in AC Systems

Real Power: The real power (PR) is the power utilized

by a user and is expressed in watts (W). When the apparent power is expressed in

rectangular form, the real part of the apparent power is the real power.

The real power always flows from the source to the user.

Syed A Rizvi

Page 42: Transformers and power flow

ENS 441/ELT 437 42

Power in AC Systems

Reactive Power: The reactive power (PX) is needed to

establish magnetic field in inductors. Electric field in a capacitor acts as a

source of reactive power. Reactive power can be supplied as well

as absorbed by an electric power source. It means that the reactive power can flow from the source to the circuit or from the circuit to the source.

Syed A Rizvi

Page 43: Transformers and power flow

ENS 441/ELT 437 43

Power in AC Systems

When the reactive power flows from the source to the circuit it is considered “positive” reactive power.

However, it is considered “negative” reactive power when it flows from the circuit to the source.

Mathematically, the apparent power (PA), the real power (PR), and the reactive power (PX) are related as follow:

Syed A Rizvi