Page 1: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

ThermalCMP™ Series

thermal flow & level

switches

Page 2: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com

Page 3: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com i

CMP™ 100 Thermal Dispersion

Table of Contents

Principle of Operation....................................................................................................... 1

Typical Applications ......................................................................................................... 1

CMP Models – General Purpose .......................................................................................... 2

CMP Specifications ........................................................................................................... 3

CMP Electronics ................................................................................................................ 4

Ordering Legends

CMP 112 Threaded (Liquids) ............................................................................................ 5

CMP 115 Threaded (Inert Gases) ...................................................................................... 6

CMP 122 Sanitary Flanged (Liquids) .................................................................................. 7

CMP 125 Sanitary Flanged (Inert Gases) ............................................................................ 8

Installation Guidelines

Application Considerations - Flow ..................................................................................... 9

Application Principles - Flow, Level, Interface & Temperature................................................. 9

Mounting & Installation Diagrams for Flow ......................................................................... 10

Guidelines for Flow Applications (Liquids, Slurries, Air & Gas)

Mounting the Sensing Element .................................................................................. 11

Sensor Orientation.................................................................................................. 11

Mounting Considerations .......................................................................................... 11

Horizontal Pipe - Side Mount (Ideal) .......................................................................... 12

Horizontal Pipe - Top Mount ..................................................................................... 12

Horizontal Pipe - Bottom Mount................................................................................. 12

Vertical Pipe - Side Mount (Acceptable) ...................................................................... 13

Vertical Pipe - Side Mount - Downward Flow ................................................................ 13

Vertical Pipe - Top & Bottom Mount (Less Desirable) ..................................................... 13

Application Considerations - Level .................................................................................... 14

Application Considerations - Interface ............................................................................... 14

Point Level & Fluids Interface

Mounting Considerations .......................................................................................... 15

Tanks & Vessels - Side Mount (Ideal) ......................................................................... 15

Tanks & Vessels - Top Mount .................................................................................... 15

Page 4: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.comii

Table of Contents Thermal Dispersion

RCM Software, Communication Adapters & Equipment Tags ................................................. 16

Interconnecting Cable for Remote Electronics ..................................................................... 17

Outline Dimensional Drawings

CMP 112 & 115 Threaded ................................................................................................ 18

CMP 122 & 125 Sanitary Flanged ...................................................................................... 18

Customer Notes ................................................................................................................. 19

Thermal Product Group Comparison .................................................................................... 20

Thermal Product Group Overview ....................................................................................... 21

Contact Us, Distributors and Ordering Information ............................................................. 22

Page 5: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com 1

CMP™ 100 Thermal Dispersion

Principle of Operation – Thermal Dispersion

Kayden switches use proven thermal dispersion technology to create a very accurate, economical and rugged method of

sensing flow, level & interface.

The sensors incorporate two platinum Resistance Temperature Detectors (RTD’s), one RTD measures the actual process

temperature while the other RTD is heated to create a temperature differential.

Flow:

As the process travels over the tip of the sensor, the

increased flow of the process reduces the temperature of

the heated RTD. This reduced temperature difference

between the two RTD’s is monitored by the electronics and

the switch changes state once the set point is reached.

Level:

In a dry to wet application, the fluid surrounds the tip of the

sensor, thus dispersing some of the heat from the heated

RTD. This reduced temperature difference between the two

RTD’s is monitored by the electronics and the switch

changes state once the set point is reached.

Flow:

• Pump Protection – Dry Alarm

• Leak Detection

• Flow Monitoring & Verification

• Tank Overflow Protection

• Monitoring Purge Air Flow

• Drain Line Flow

• Interface Control in Separation Vessels

• Vent Monitoring

Interface:

Interface (Level) Detection

• Separation Vessels, Oil / Pad / Water Knockout tanks

Level:

• Emergency Eye Wash Stations

• Liquids, Air, Inert Gases & Steam

• Slurries

• Interface Detection

• Corrosive Liquids

• General-Purpose Areas

• Interface Control & Level Detection in Settling Vessels

• Chemical Injection/Additive Flow Monitoring

Temperature:

Process Temperature Monitoring

• One relay configurable for process temperature

Typical Applications

GAS VENT

OVERFLOW

INLET

PROCESS TANK

LEAK PROTECTION

HIGH LEVEL

LOW LEVEL

PUMP PROTECTION

Side of Switch

Back of Switch

OVERFLOWTANK

Page 6: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

CMP™ Models – General Purpose

kayden.com2

CMP™ 100 Thermal Dispersion

Applications: Flow & Level

The CMP Series for liquids, inert gases, air and slurries. For general-purpose applications. Reliable ‘no moving parts’

stainless steel sensors.

CMP 112 & 115 CMP 122 & 125

Page 7: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

3kayden.com

CMP™ 100

Applications:

• Flow & Level (Liquids): Models 112 & 122

• Flow (Inert Gases): Models 115 & 125

Process Connections:

• 3/4" MNPT

• Sanitary 1" to 3.5" Tri-Clamp®

Insertion ‘U’ Lengths:

• Imperial:1.2", 2" & 4" (for 112 & 115 Models)2" & 4" (for 122 & 125 Models)

• Metric: 3 cm, 5 cm & 10 cm (for 112 & 115 Models)5 cm & 10 cm (for 122 & 125 Models)

Wetted Material:

• 304/316L Stainless Steel

Temperature Range – Continuous Service:

• Sensor:-40°F to +167°F (-40°C to +65°C)

• Electronics:-40°F to +167°F (-40°C to +65°C)

Operating Pressure - Sensor:

Threaded Style:

• Maximum Working Pressure: 24 MPa (3500 psig) at 70°F (21°C)Derated with temperature

Sanitary Tri-Clamp® Style:

• Maximum Working Pressure: 1723 kPa (250 psig) at 70°F (21°C)

Switch Point Range-Flow:

• Water-based Liquids: 0.01 to 3.0 feet/sec. (0.003 to 0.91 meter/sec.)

• Inert Gases: 0.25 to 125 feet/sec. (0.076 to 38.1 meter/sec.)Standard conditions: 70°F (21°C) at 14.7 psi (1 atm)

Accuracy:

• Flow Service:±5% set point velocity over operating range of ±50°F (±28°C)

• Level Service:±0.50 inches (±1.3 cm)

Response Time:

• Approximately 0.5 to 30 seconds.

Input Power:

• 12-36 VDC

• Consumption: Maximum: 2.4 watts

Heater Power:

• Fixed

Outputs:

• Single SPDT sealed relay rated @ 0.5 amp resistive 36 volts AC/DC

Cable:

• Thermoplastic Polyurethane Jacket (Estane® 58887)

Cable Lengths:

• Imperial: 10', 20', 30', 40' & 50'

• Metric:3.0 m, 6.0 m, 9.1 m, 12.1 m & 15.2 m

Note: Custom cable lengths available upon request.

Warranty:

• Three (3) Years from shipment date from factory (see Terms & Conditions on kayden.com for details)

Thermal Dispersion

CMP™ 100 Specifications

Page 8: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com4

CMP™ 100 Thermal Dispersion

CMP Electronics

LED Indicator:

Green LED Indicates the relay is energized

Blue LED Indicates power on

Standard Features:

• Solid state electronics

• Relay can be set to energize above or below set point

• Setpoint adjustable with the trim-pot

• Available in Threaded and Sanitary Flanged configurations

Microprocessor Based Electronics

The electronics are epoxy encapsulated within the sensor housing offering a simple operating status display and trim-pot.

Sanitary AssemblyThreaded Assembly

Page 9: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

5kayden.com

Thermal DispersionCMP™ 112 Threaded

Flow & Level Switch (Liquids)

© KAYDEN Instruments. All rights reserved. Contents subject to change without notice.

Please refer to kayden.com for current specifications and configurations.

Model Number Legend Doc. #: ML-112-003-000

112 CODE Sensor Operating Temperature Range

• T ‘T’ Type Sensor

• • CODE Material of Construction - Sensor

• • A 316L Stainless Steel

• • • CODE Process Connection - MNPT

• • • D 3/4"

• • • • CODE Insertion ‘U’ Lengths

• • • • 0012 1.2" (3.0 cm)

• • • • 0020 2" (5.0 cm)

• • • • 0040 4" (10.1 cm)

• • • • • CODE Input Power

• • • • • E 12-36 VDC

• • • • • • Electronics

• • • • • • Epoxy Encapsulated within Sensor Housing.

• • • • • • Single SPST sealed relay contact.

• • • • • • • CODE Agency Approvals

• • • • • • • 6 None - Non-hazardous only

• • • • • • • • CODE Language

• • • • • • • • E English

• • • • • • • • • CODE Cable Length

• • • • • • • • • 0100 10' (3.0 m)

• • • • • • • • • 0300 30' (9.1 m)

• • • • • • • • • 0500 50' (15.2 m)

112 T A D 0020 E 6 E 0100

Page 10: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com6

CMP™ 115 Threaded

Flow Switch (Inert Gases)

© KAYDEN Instruments. All rights reserved. Contents subject to change without notice.

Please refer to kayden.com for current specifications and configurations.

Model Number Legend Doc. #: ML-115-003-000

Thermal Dispersion

115 CODE Sensor Operating Temperature Range

• T ‘T’ Type Sensor

• • CODE Material of Construction - Sensor

• • A 316L Stainless Steel

• • • CODE Process Connection - MNPT

• • • D 3/4"

• • • • CODE Insertion ‘U’ Lengths

• • • • 0012 1.2" (3.0 cm)

• • • • 0020 2" (5.0 cm)

• • • • 0040 4" (10.1 cm)

• • • • • CODE Input Power

• • • • • E 12-36 VDC

• • • • • • Electronics

• • • • • • Epoxy Encapsulated within Sensor Housing.

• • • • • • Single SPST sealed relay contact.

• • • • • • • CODE Agency Approvals

• • • • • • • 6 None - Non-hazardous only

• • • • • • • • CODE Language

• • • • • • • • E English

• • • • • • • • • CODE Cable Length

• • • • • • • • • 0100 10' (3.0 m)

• • • • • • • • • 0300 30' (9.1 m)

• • • • • • • • • 0500 50' (15.2 m)

115 T A D 0020 E 6 E 0100

Page 11: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com 7

Thermal DispersionCMP™ 122 Sanitary Flanged

Flow & Level Switch (Liquids)

© KAYDEN Instruments. All rights reserved. Contents subject to change without notice.

Please refer to kayden.com for current specifications and configurations.

Model Number Legend Doc. #: ML-122-003-000

122 CODE Sensor Operating Temperature Range

• T ‘T’ Type Sensor

• • CODE Material of Construction - Sensor

• • A6 304/316L Stainless Steel - Sanitary - (3A Compliant)

• • • CODE Process Connection - Tri-Clamp®

• • • E 1"

• • • G 1.5"

• • • H 2"

• • • J 2.5"

• • • K 3"

• • • L 3.5"

• • • • CODE Insertion ‘U’ Lengths

• • • • 0020 2" (5.0 cm)

• • • • 0040 4" (10.1 cm)

• • • • • CODE Input Power

• • • • • E 12-36 VDC

• • • • • • Electronics

• • • • • • Epoxy Encapsulated within Sensor Housing.

• • • • • • Single SPST sealed relay contact.

• • • • • • • CODE Agency Approvals

• • • • • • • 6 None - Non-hazardous only

• • • • • • • • CODE Language

• • • • • • • • E English

• • • • • • • • • CODE Cable Length

• • • • • • • • • 0100 10' (3.0 m)

• • • • • • • • • 0300 30' (9.1 m)

• • • • • • • • • 0500 50' (15.2 m)

122 T A6 G 0020 E 6 E 0100

Page 12: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com8

Thermal DispersionCMP™ 125 Sanitary Flanged

Flow Switch (Inert Gases)

© KAYDEN Instruments. All rights reserved. Contents subject to change without notice.

Please refer to kayden.com for current specifications and configurations.

Model Number Legend Doc. #: ML-125-003-000

125 CODE Sensor Operating Temperature Range

• T ‘T’ Type Sensor

• • CODE Material of Construction - Sensor

• • A6 304/316L Stainless Steel - Sanitary - (3A Compliant)

• • • CODE Process Connection - Tri-Clamp®

• • • E 1"

• • • G 1.5"

• • • H 2"

• • • J 2.5"

• • • K 3"

• • • L 3.5"

• • • • CODE Insertion ‘U’ Lengths

• • • • 0020 2" (5.0 cm)

• • • • 0040 4" (10.1 cm)

• • • • • CODE Input Power

• • • • • E 12-36 VDC

• • • • • • Electronics

• • • • • • Epoxy Encapsulated within Sensor Housing.

• • • • • • Single SPST sealed relay contact.

• • • • • • • CODE Agency Approvals

• • • • • • • 6 None - Non-hazardous only

• • • • • • • • CODE Language

• • • • • • • • E English

• • • • • • • • • CODE Cable Length

• • • • • • • • • 0100 10' (3.0 m)

• • • • • • • • • 0300 30' (9.1 m)

• • • • • • • • • 0500 50' (15.2 m)

125 T A6 G 0020 E 6 E 0100

Page 13: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com 9

Installation Guidelines Thermal Dispersion

Application Considerations - Flow

Flow

Ideal Process Conditions

Liquids:

• Consistent process composition & temperature

• Sufficient straight run flow profile (minimizesturbulence)

• Recommended minimum of 5 pipe diametersfrom any disturbance

Air & Gas:

• Consistent process composition & temperature

• Sufficient straight run flow profile (minimizes turbulence)

• Clean and dry

Slurries:

• Consistent process composition & temperature

• Sufficient straight run flow profile (minimizesturbulence)

Emulsion:

• Consistent process composition & temperature

• Sufficient straight run flow profile (minimizesturbulence)

Undesirable Process Conditions

Liquids:

• Inconsistent process composition or temperature

• Insufficient straight run

• Turbulence

• Aerated fluids

Air & Gas:

• Inconsistent process composition or temperature

• Wet or saturated air/gas

Slurries:

• Inconsistent process composition or temperature

• Insufficient straight run

• Turbulence

• Aerated fluids

Emulsion:

• Inconsistent process composition & temperature

• Insufficient straight run

• Turbulence

• Aerated fluids

Solids:

• Dry granulated processes are NOT good candidates for thermal switches

Application Principles- Flow, Level, Interface & Temperature

4 Consistent process composition

4 Consistent process temperature

4 Clean or dir ty process

4 Liquids

4 Dry air & gas

4 Slurries

4 Emulsion

8 Aerated fluids

8 Large temperature swings

8 Wet or saturated air/gas

8 Solids

8 Sediment covering sensing tip

GAS VENT

OVERFLOW

INLET

PROCESS TANK

LEAK PROTECTION

HIGH LEVEL

LOW LEVEL

PUMP PROTECTION

Side of Switch

Back of Switch

OVERFLOWTANK

Page 14: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com10

Installation Guidelines Thermal Dispersion

Flow

Mounting & Installation Diagrams for Flow

Bends, Elbows, etc.:

Good installation practice requires

sufficient downstream placement of

bends, expansions or reductions.

Valves, etc.:

Good installation practice

requires sufficient downstream

placement from isolation and

control valves - especially if

valves are only partially

opened.

Pumps, Fans & Compressors:

Good installation practice requires

sufficient downstream placement from

pumps, fans and compressors. The

preferred installation point for pump

flow / no-flow detection is on the inlet

side of the pump.

Note: Flow profiles will tend to be smoother as the downstream distance between the bend, elbow, valve, pump,

fan or compressor and the switch increases.

Flow

Flow

Flow

Page 15: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com 11

Installation Guidelines Thermal Dispersion

Flow

Mounting the Sensing Element:

• Ensure the arrows engraved on the sensor are oriented parallel to the process flow

• Liquids & Slurries: When mounted in a tee or section of pipe larger than the normal process pipe, position sensor in a

vertical run of pipe with flow upward. This will prevent air or gas bubbles from becoming trapped around the sensing tip

• Avoid locations where sediment may accumulate and eventually isolate the sensing tip from the process. Situating the

sensing tip in the sediment may prevent the switch from being able to sense any changes in the process as the

sediment will insulate the sensing tip

Sensor Orientation

To optimize the sensor’s performance and interpretation of the processes actions, ensure the sensor is

positioned as outlined below:

Mounting Considerations:

• Where possible mount the sensor in the point of least turbulent flow

• Pumps, fans, valves, or pipe bends of 90° or more may cause turbulence or significant variance in the flow which may

affect the repeatability of the switch. When possible, care should be taken to minimize this possibility. Consult your

local Kayden Representative or Kayden for questions or recommendations

• Ensure the arrows engraved on the sensor are oriented parallel to the process flow

• Liquids & Slurries: When mounted in a tee or section of pipe larger than the normal process pipe, position sensor in a

vertical run of pipe with flow upward, this will prevent entrained air or gas from collecting around the sensing tip

• Avoid locations where sediment may accumulate and eventually isolate the sensing tip from the process

• For pump flow/no-flow detecton the best/preferred installation point is on the inlet side of the pump.

The discharge side may have turbulence, reverse flow and an undeveloped flow profile. These factors may

greatly reduce repeatability and accuracy

Guidelines for Flow Applications (Liquids, Slurries, Air, Gas)

Front View of Sensor

Flow

F

Front View of Sensor

Flow & Level

Sensor Orientation for Horizontal Flow

Sensor Orientation for Vertical Flow

Page 16: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com12

Installation Guidelines Thermal Dispersion

Flow

Horizontal Pipe – Side Mount (Ideal)

Ensure sensing tip is fully inside the pipe wall as a minimum and to the center of the pipe as a maximum. Avoid locations

where sediment may accumulate and isolate the sensing tip from the process.

Horizontal Pipe – Top Mount

Ensure sensing tip is fully inside the pipe wall to a position where it will be constantly and fully exposed to the process in

order for the flow or lack of flow to be recognized at any given time.

Horizontal Pipe – Bottom Mount

Ensure sensing tip is fully inside the pipe wall to a position where it will be constantly covered by the process in order for the

flow or lack of flow to be recognized at any given time. Ensure the process covers the sensing tip – if the sensing tip is

situated near the top of the pipe, the process must be filling the pipe to a level where the sensing tip is covered at all times. A

wide selection of insertion ‘U’ lengths are available starting at 1.2”.

Avoid locations where sediment may accumulate and eventually isolate the sensing tip from the process.

Guidelines for Flow Applications (Liquids, Slurries, Air, Gas)

4 Liquid

4 Gas

8 Liquid (Partially Full)

4 Liquid

8 Gas

8 Sediment

4 Liquid

4 Gas

4 Liquid

4 Gas

Sensor Positioning, Horizontal Pipe

5% minimum

35% min to 65% max

50%

35% min to 45% max

50% maximum

Horizontal Mounting Vertical Up/DownMounting

Page 17: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com 13

Installation Guidelines Thermal Dispersion

Flow

Vertical Pipe – Side Mount (Acceptable)

Ensure sensing tip is fully inside the pipe wall as a minimum and to the center of the pipe as a maximum.

Note: When installing the switch in vertical piping, Kayden strongly recommends installing thermal switches at a point of

UPWARD process flow to ensure continued total immersion of the sensing tip.

Vertical Pipe – Side Mount – Downward Flow:

• Is only recommended for higher flow rates where the LINE IS KEPT FULL OF LIQUID/SLURRY

• For installation in a vertical gravity flow, the switch must be distant enough from an open outlet that air cavitation does

not affect the sensing tip and cause a false flow signal. A constriction at the outlet avoids this problem

• A waterfall effect will occur in vertical pipe with low flow rates. Also, the process is likely to become substantially

aerated. The switch will interpret the aeration as a substantially lower flow rate and possibly cause a false

low flow alarm

Vertical Pipe – Side Mount – Top & Bottom Mount (Less Desirable)

Positioning the sensor on a corner or elbow is not recommended as the process will be turbulent. The switch may interpret

the turbulence as a constantly changing flow rate and fail to alarm as required.

Vertical Pipe, Flow Up & Down

Guidelines for Flow Applications (Liquids, Slurries, Air, Gas)

8 Liquid

4 Gas

4 Liquid

4 Gas

Page 18: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com14

Installation Guidelines Thermal Dispersion

Application Considerations - Level

Level

Ideal Process Conditions

Liquids:

• Consistent process composition

• Non-turbulent

Slurries:

• Consistent process composition

Emulsion:

• Consistent process composition

Undesirable Process Conditions

Liquids:

• Inconsistent process composition

• Turbulence

• Large temperature swings

Slurries:

• Inconsistent process composition

• Turbulence

• Large temperature swings

Emulsion:

• Inconsistent process composition

• Turbulence

• Large temperature swings

Solids:

• Dry granulated processes are NOT goodcandidates for thermal switches

Application Considerations - Interface

Interface

Ideal Process Conditions

Liquid to Liquid:

• Consistent process composition & temperature

• Non-turbulent applications

• Large differential in thermal conductivities

Air or Gas to Liquid:

• Consistent process composition & temperature

• Non-turbulent applications

• Dry gas

Emulsion:

• Consistent process composition & temperature

• Large differential in thermal conductivities

Undesirable Process Conditions

Liquid to Liquid:

• Inconsistent process composition or temperature

• High aeration

• High turbulence

• Small differential in thermal conductivities

Air or Gas to Liquid:

• Inconsistent process composition or temperature

• High turbulence

Emulsion:

• Inconsistent process composition or temperature

• High aeration

• High turbulence

• Small differential in thermal conductivities

Solids:

• Dry granulated processes are NOT goodcandidates for thermal switches

Page 19: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com 15

Installation Guidelines Thermal Dispersion

Liquid Level

Mounting Considerations:• Where possible mount the sensor in the point of

least turbulence

• Agitators, bubblers, valves, or screens may affect therepeatability of the switch. Note: When possible, care should be taken tominimize this possibility. Consult your local KaydenRepresentative or Kayden for questions orrecommendations

• Ensure the arrows on the sensor are oriented parallelto the process surface

• Keep sensing tip clear of any mixing devices that maycause damage

Tanks and Vessels – Side Mount (Ideal)

Ensure sensing tip is fully inside the tank wall

as a minimum.

Tanks and Vessels – Top Mount

Ensure sensing tip is fully inserted to the desired

sensing point.

Point Level & Fluids Interface

Page 20: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com16

Thermal DispersionAccessories

• Use the RCMS program to change Set Points 1 & 2, adjust Relay

modes, adjust the Start-up Bypass Timer and Set Point Delays, set

the heater to optimize response, lock or unlock the Display Panel

when security and/or settings are critical, visualize the actions of the

process via the graphical display and many other features

• Requires an RS-485 adapter such as the Kayden SCA and acommunication cable

• Provides an additional interface for all CLASSIC 800, CLASSIC 850DIN & BASIC+ 400 models

Part Number: A11-SFT

Stainless Steel Tags

Stainless Steel tags are attached

with stainless steel wire to the switch.

Please provide the exact information

to be engraved.

Part Number: A20-0001

Lamacoid Tags

Lamacoid equipment tags are applied

with double sided tape to any product.

Please provide the exact information

to be engraved.

Part Number: A20-0002

Paper Tags

Select paper tags when temporary

labeling is required. Please provide the

exact information.

Part Number: A20-0003

These items can be purchased separately but are required to use the Kayden RCM software.

Kayden RCM Software

Equipment Tags

Communication Cable is used to connect

the SCA (Serial Communication Adapter)

to the switch.

Standard Lengths: 4, 8 & 10 feet.

Part Number: A05-CC-0004 4 feet

A05-CC-0008 8 feet

A05-CC-0010 10 feet

Communication Cable

RS-232 (DB-9) to RS-485 AdapterThe SCA is an RS-232 to RS-485 adapter for Modbus

communication protocol. The SCA derives

power from the Kayden switch.

Part Number: A15-321

USB to RS-232 (DB-9) AdapterAdapts the Kayden SCA to USB for computers

without a serial port.

Part Number: A15-322

Kayden Converters/Adapters - USB to RS-232 & RS-232 to RS-485

Page 21: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com 17

Thermal DispersionAccessories

General Purpose (Non-hazardous) Cable &Connector Assembly

Assembly includes 2 general purpose cable fittings.

Construction: 8-strand concentric, Class B tinned

copper, .020" PVC insulation, individual and overall

foil shield, color & number coded, drain and Mylar

separator, PVC inner jacket, aluminum interlock

armor, PVC outer jacket.

Voltage Rating: 300 volts

Temperature Rating:

-40°F to +194°F (-40°C to +90°C);

insulation rated @ 221°F (105°C)

Part Number: A06-GP-xxxx (xxxx = length in feet)

Kayden’s cables are used to connect sensors to remote electronics. Kayden offers cables for both hazardous and general

purpose locations. Cables and cable fittings are pre-assembled and fitted at Kayden’s factory to ensure integrity of all

connections.

Flameproof Cable & Connector Assembly

Assembly includes 2 sealed XP cable fittings and

sealing compound.

Construction: 8-strand concentric, Class B tinned

copper, .020" PVC insulation, individual and overall

foil shield, color & number coded, drain and Mylar

separator, PVC inner jacket, aluminum interlock

armor, PVC outer jacket.

Voltage Rating: 300 volts

Temperature Rating:

-40°F to +194°F (-40°C to +90°C);

insulation rated @ 221°F (105°C)

Part Number: A06-XP-xxxx (xxxx = length in feet)

Assembly includes heat shrink with crimp ferrules.

(Strain relief fittings are not included, however are available as an option).

Construction: 8 color coded conductors 20 AWG, shielded cable, PVC jacket.

Voltage Rating: 30 volts RMS

Temperature Rating: -4°F to +176°F (-20°C to +80°C)

Part Number: A05-GP-xxxx (xxxx = length in feet)

Armored Cable

Non-Armored Cable

Interconnecting Cable for Remote Electronics

Page 22: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com18

Thermal Dispersion

CMP 112, 115, 122, & 125

CMP 112 & 115 Threaded

10' CABLE STANDARD(2.24)

'U' LENGTH

0.883/4" MNPT

(3.04 METERS)

WHITE (+)

BLUE

GREEN - Not Used

BLACK (-)

BROWN

CMP 122 & 125 Sanitary Flanged

0.88

(2.24)

'U' LENGTH

10' CABLE STANDARD

(3.04 METERS)

WHITE (+)

BLUE

GREEN - Not Used

BLACK (-)

BROWN

Outline Dimensional Drawings

Page 23: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com 19

CMP™ 100 Thermal Dispersion

Notes

Page 24: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com20

Thermal Product Group Comparison Thermal Dispersion

MODELS

FEATURESCLASSIC™ 800

SeriesBASIC+™ 400Series

CMP™ 100Series

CLASSIC™ 850DIN

Flow1 4 4 4 4

Level2 4 ­4 4 4Interface - Liquid / Slurry 4 4 4Temperature3 4 4

Process Media

Liquids 4 4 4 4

Air & Gases1 4 4 4 4

Slurries 4 4 4

Interface 4 4 4

Features

4-20 mA Analog Output 4

Temperature Mode3 4 4

Relay Contacts Dual SPDT Single SPST Single SPST Dual SPDT

Start-up Bypass Timer4 4 4 4

Adjustable Set Point Deadbands 4 4

Display Panel Lock-Out5 4 4 4

Remote Communications6 4 4 4

Input Power12-24 VDC; 115-230 VAC, 50-60 Hz 4 4

12-24 VDC 4 (12-36 VDC) 4

Remote Mount Electronics

CSA Approved (Class I, Div. 1) Enclosures 4 4

FM Approved (Class I, Div. 1) Enclosures 4 4

Agency Approvals

CSA - ANSI/UL Class I, Div. 14

Groups B, C & D

4Groups C & D

General Purpose (Non-hazardous)

General Purpose (Non-hazardous)

FM Class I, Div. 14

Groups B, C & D

4Groups C & D

General Purpose (Non-hazardous)

General Purpose (Non-hazardous)

Notes:

1. For low flow rates ( < 1 sfps) in gases, the CLASSIC 800 / 850 is recommended.

2. Point Level: physical location of the probe determines sensing point.

3. Requires Kayden RCMS and the Modbus communications (see note 6 below). Relay 2 may be configured to actuate on process temperaturewhile the switch functions in a traditional Flow or Level application.

4. Adjustable from 0 - 100 seconds, the Start-up Bypass Timer is useful when restarting a pump.

5. The programming buttons on the Display Panel of the switch may be disabled using the Kayden RCMS and the Modbus communications.

6. Modbus RS-485; requires Kayden RCMS (included at no charge upon request), a Serial Communication Adapter (SCA) or USB Adapter andcommunications cable are available.

Page 25: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com 21

Thermal DispersionThermal Product Group Overview

© KAYDEN Instruments. All rights reserved. Contents subject to change without notice.

Please refer to kayden.com for current specifications and configurations.

CLASSIC™ 800Series BASIC+™ 400 CMP™ 100

Models &Applications

810, 812, 814, 816, 821, 828, 830, 832 & 850

Flow, Level, Interface & Temperature

410, 412, 414, 416, 421, 428, 430 & 432

Flow, Level & Interface

112: Flow & Level(Liquids)115:

Flow (Gas)

122:Flow & Level(Liquids)125:

Flow (Gas)

ProcessConnections

810 & 410: 1/2" to 2" MNPT Threaded821 & 421: 1/4" MNPT Threaded

812 & 412: Flanged814 & 414: Flanged Retractable Packing Gland

816 & 416: 1" MNPT Threaded Retractable Packing Gland 828 & 428: 1" to 3" Sanitary Tri-Clamp®

830 & 430: 3/4" FNPT (In-Line) 832 & 432: Flanged (In-Line) 850 DIN Rail: Available with all Sensor Models & most connection sizes

825: Flanged (MultiPoint)

Sanitary Tri-Clamp®

3/4" MNPT

Insertion ‘U’Lengths

1.2", 2", 3", 4", 6", 9", 12" & 18" Standard (most models)Custom lengths available to 120"

1.2", 2" & 4"

Material ofConstruction: (Sensor)

Remote ElectronicsOption

316L Stainless, Titanium Gr. 2, Hastelloy C-276, Alloy 20, Monel 400, Inconel 600 & Nickel 200821 & 421: 316L Stainless Steel only

830, 832, 430 & 432: 316L Stainless Steel c/w Nickel Braze828 & 428: 304/316L Stainless Steel

AvailableExplosion-proof - Standard

304/316L Stainless Steel

316L Stainless Steel

Input Power

PowerConsumption

850 DIN: 24 VDC

Maximum: 6 watts Maximum: 2.4 wattsMaximum: 4.8 watts

12-36 VDC

Communications RS-485 None

OutputsSingle SPST sealed relay contact 5 amps res. 250 VAC / 30 VDC

Modbus via RS-485.

Single SPST sealed relay contact

0.5 amps res. 36 VAC / VDC

TemperatureCompensation Yes No

AgencyApprovals

General Purpose

Self-Test Automated diagnostics performed on electronics & sensing elements No

OperatingTemperature -Sensor

OperatingTemperature -Electronics

Continuous Use:-55°C to +200°C (-67°F to +392°F)

814, 816, 414 & 416: -40°F to +320°F (-40°C to +160°C)

Continuous Use:-55°C to +65°C (-67°F to +167°F)

Continuous Use:-40°C to +75°C (-40°F to +167°F)

Continuous Use:-40°C to +85°C (-40°F to +185°F)

Two SPDT sealed relay contacts 5 amps res. 230 VAC / 24 VDC

Modbus via RS-485.4-20 mA current loop (except 850 DIN)

NotAvailable

Universal AC & DC

OperatingPressure -Sensor

Maximum Working Pressure:24 MPa (3500 psig) at 21°C (70°F) - Threaded

Flange units per flange rating1723 kPa (250 psig) at 21°C (70°F) - Sanitary flange units

MWP:3.6 MPa (525 psig)

@ 21°C (70°F)

MWP:1723 kPa (250 psig)

@ 21°C (70°F)

KAYDEN® Thermal Product Group Overview

Page 26: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com22

Thermal DispersionContact Information

Contact Us

Contact us with any inquiries you may have.

Telephone Fax(403) 253-1423 (403) 253-1460 Local & International

E-Mail [email protected] kayden.com

Hours Monday – Friday 8:00 a.m. – 5:00 p.m. MST

Mailing Address 3368 – 114th Avenue S.E., Calgary, Alberta, Canada T2Z 3V6

Contact a Local Distributor

DistributorsVisit kayden.com to find a local Distributor near you. Kayden Distributors provide local inventory, technical support

and service.

Kayden 60-Day 100% Satisfaction Guarantee

Standard Products

Standard Products are eligible for the 60-Day 100% Satisfaction Guarantee. If you purchased new Standard Products

from Kayden or an Authorized Kayden Distributor, you may return them to the place of purchase up to 60 days from the

date of invoice for a refund or credit of the product purchase price provided the quantity of Products does not exceed

twenty-five units (nominal restocking fee apply to only those quantities exceeding twenty-five units).

Custom Products

Custom Products are not eligible for this guarantee as they are manufactured specifically to the customers’ individual and

unique requirements. Ship returns prepaid. Please note the refund or credit will not include any charges for special

documentation, special equipment, special service, special approvals, drawings, certificates, equipment tags, set points, flow

curves, x-rays, dye penetration tests, opened software, shipping or insurance shown on your invoice. View the Return Policy in

detail at kayden.com.

Kayden offers the following:

• 60 calendar days from the date of invoice.

• Up to twenty-five (25) Standard Products of any type or combination per order. Should the customer, for any reason, be

unsatisfied with any or all of the Products, he/she may return any or all of them for a full refund.

Visit kayden.com to view the Kayden 60-Day 100% Satisfaction Guarantee in detail.

Warranty

Three (3) Years from shipment date from factory (see Terms & Conditions on kayden.com for details).

Ordering Information

5 Ways to Place an Order:

Your Local Distributor

Visit www.kayden.com to find a local Distributor near you.

Telephone Kayden Fax Kayden Email Kayden

(403) 253-1423 (403) 253-1460 Local & International [email protected]

Mail Kayden

3368 – 114th Avenue S.E., Calgary, Alberta, Canada T2Z 3V6

Page 27: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very

kayden.com

This document and other information from Kayden/ Telematic and its authorized distributors, provides product and/or system options for

further investigation by users having technical expertise. It is important that you analyze all aspects of your application and review the

information concerning the product or system in the current catalog located online at kayden.com.

Copyright 1994 – 2009 Kayden Instruments (a line of products manufactured by Telematic Controls Inc.). All rights reserved.

® ™, KAYDEN, CLASSIC, BASIC, CMP, RCM, RCMS, Remote Control & Monitoring Software, SCA, Helping the World Switch, and

Flow Switch Innovation are trademarks, the property of Kayden Instruments/Telematic Controls Inc.

Tri-Clamp® is a registered trademark of Alfa Laval Inc.

Estane® is a registered trademark of Lubrizol Corporation

Hastelloy® is a registered trademark of Haynes International, Inc.

Inconel®, Incoloy® Alloy 20, Monel® are registered trademarks of Special Metals Corporation

Kayden products are protected by Canadian and International patents.

This catalog is for informational purposes only.

The information contained herein is believed to be reliable, but no representations, guarantees or warranties of any kind are made as to

its accuracy, suitability for particular applications or the results to be obtained therefrom. The information is based on laboratory work

with small-scale equipment and does not necessarily indicate end product performance. Because of the variations in methods,

conditions and equipment used commercially in applying these products, no warranties or guarantees are made as to the suitability of

the products for the application(s) disclosed. Full-scale testing and end product performance are the responsibility of the user. Kayden

Instruments/Telematic Controls Inc. shall not be liable for and the customer assumes all risk and liability of any use of handling of any

product beyond Kayden Instruments/Telematic Controls Inc. direct control. THE SELLER MAKES NO WARRANTIES, EXPRESS OR

IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A

PARTICULAR PURPOSE. Nothing contained herein is to be considered as permission, recommendation, nor as an inducement to

practice any patented invention without permission of the patent owner.

Page 28: thermal flow & level switches · CMP ™100 Thermal Dispersion Principle of Operation – Thermal Dispersion Kayden switches use proven thermal dispersion technology to create a very