ThermalCMP™ Series
thermal flow & level
switches
kayden.com
kayden.com i
CMP™ 100 Thermal Dispersion
Table of Contents
Principle of Operation....................................................................................................... 1
Typical Applications ......................................................................................................... 1
CMP Models – General Purpose .......................................................................................... 2
CMP Specifications ........................................................................................................... 3
CMP Electronics ................................................................................................................ 4
Ordering Legends
CMP 112 Threaded (Liquids) ............................................................................................ 5
CMP 115 Threaded (Inert Gases) ...................................................................................... 6
CMP 122 Sanitary Flanged (Liquids) .................................................................................. 7
CMP 125 Sanitary Flanged (Inert Gases) ............................................................................ 8
Installation Guidelines
Application Considerations - Flow ..................................................................................... 9
Application Principles - Flow, Level, Interface & Temperature................................................. 9
Mounting & Installation Diagrams for Flow ......................................................................... 10
Guidelines for Flow Applications (Liquids, Slurries, Air & Gas)
Mounting the Sensing Element .................................................................................. 11
Sensor Orientation.................................................................................................. 11
Mounting Considerations .......................................................................................... 11
Horizontal Pipe - Side Mount (Ideal) .......................................................................... 12
Horizontal Pipe - Top Mount ..................................................................................... 12
Horizontal Pipe - Bottom Mount................................................................................. 12
Vertical Pipe - Side Mount (Acceptable) ...................................................................... 13
Vertical Pipe - Side Mount - Downward Flow ................................................................ 13
Vertical Pipe - Top & Bottom Mount (Less Desirable) ..................................................... 13
Application Considerations - Level .................................................................................... 14
Application Considerations - Interface ............................................................................... 14
Point Level & Fluids Interface
Mounting Considerations .......................................................................................... 15
Tanks & Vessels - Side Mount (Ideal) ......................................................................... 15
Tanks & Vessels - Top Mount .................................................................................... 15
kayden.comii
Table of Contents Thermal Dispersion
RCM Software, Communication Adapters & Equipment Tags ................................................. 16
Interconnecting Cable for Remote Electronics ..................................................................... 17
Outline Dimensional Drawings
CMP 112 & 115 Threaded ................................................................................................ 18
CMP 122 & 125 Sanitary Flanged ...................................................................................... 18
Customer Notes ................................................................................................................. 19
Thermal Product Group Comparison .................................................................................... 20
Thermal Product Group Overview ....................................................................................... 21
Contact Us, Distributors and Ordering Information ............................................................. 22
kayden.com 1
CMP™ 100 Thermal Dispersion
Principle of Operation – Thermal Dispersion
Kayden switches use proven thermal dispersion technology to create a very accurate, economical and rugged method of
sensing flow, level & interface.
The sensors incorporate two platinum Resistance Temperature Detectors (RTD’s), one RTD measures the actual process
temperature while the other RTD is heated to create a temperature differential.
Flow:
As the process travels over the tip of the sensor, the
increased flow of the process reduces the temperature of
the heated RTD. This reduced temperature difference
between the two RTD’s is monitored by the electronics and
the switch changes state once the set point is reached.
Level:
In a dry to wet application, the fluid surrounds the tip of the
sensor, thus dispersing some of the heat from the heated
RTD. This reduced temperature difference between the two
RTD’s is monitored by the electronics and the switch
changes state once the set point is reached.
Flow:
• Pump Protection – Dry Alarm
• Leak Detection
• Flow Monitoring & Verification
• Tank Overflow Protection
• Monitoring Purge Air Flow
• Drain Line Flow
• Interface Control in Separation Vessels
• Vent Monitoring
Interface:
Interface (Level) Detection
• Separation Vessels, Oil / Pad / Water Knockout tanks
Level:
• Emergency Eye Wash Stations
• Liquids, Air, Inert Gases & Steam
• Slurries
• Interface Detection
• Corrosive Liquids
• General-Purpose Areas
• Interface Control & Level Detection in Settling Vessels
• Chemical Injection/Additive Flow Monitoring
Temperature:
Process Temperature Monitoring
• One relay configurable for process temperature
Typical Applications
GAS VENT
OVERFLOW
INLET
PROCESS TANK
LEAK PROTECTION
HIGH LEVEL
LOW LEVEL
PUMP PROTECTION
Side of Switch
Back of Switch
OVERFLOWTANK
CMP™ Models – General Purpose
kayden.com2
CMP™ 100 Thermal Dispersion
Applications: Flow & Level
The CMP Series for liquids, inert gases, air and slurries. For general-purpose applications. Reliable ‘no moving parts’
stainless steel sensors.
CMP 112 & 115 CMP 122 & 125
3kayden.com
CMP™ 100
Applications:
• Flow & Level (Liquids): Models 112 & 122
• Flow (Inert Gases): Models 115 & 125
Process Connections:
• 3/4" MNPT
• Sanitary 1" to 3.5" Tri-Clamp®
Insertion ‘U’ Lengths:
• Imperial:1.2", 2" & 4" (for 112 & 115 Models)2" & 4" (for 122 & 125 Models)
• Metric: 3 cm, 5 cm & 10 cm (for 112 & 115 Models)5 cm & 10 cm (for 122 & 125 Models)
Wetted Material:
• 304/316L Stainless Steel
Temperature Range – Continuous Service:
• Sensor:-40°F to +167°F (-40°C to +65°C)
• Electronics:-40°F to +167°F (-40°C to +65°C)
Operating Pressure - Sensor:
Threaded Style:
• Maximum Working Pressure: 24 MPa (3500 psig) at 70°F (21°C)Derated with temperature
Sanitary Tri-Clamp® Style:
• Maximum Working Pressure: 1723 kPa (250 psig) at 70°F (21°C)
Switch Point Range-Flow:
• Water-based Liquids: 0.01 to 3.0 feet/sec. (0.003 to 0.91 meter/sec.)
• Inert Gases: 0.25 to 125 feet/sec. (0.076 to 38.1 meter/sec.)Standard conditions: 70°F (21°C) at 14.7 psi (1 atm)
Accuracy:
• Flow Service:±5% set point velocity over operating range of ±50°F (±28°C)
• Level Service:±0.50 inches (±1.3 cm)
Response Time:
• Approximately 0.5 to 30 seconds.
Input Power:
• 12-36 VDC
• Consumption: Maximum: 2.4 watts
Heater Power:
• Fixed
Outputs:
• Single SPDT sealed relay rated @ 0.5 amp resistive 36 volts AC/DC
Cable:
• Thermoplastic Polyurethane Jacket (Estane® 58887)
Cable Lengths:
• Imperial: 10', 20', 30', 40' & 50'
• Metric:3.0 m, 6.0 m, 9.1 m, 12.1 m & 15.2 m
Note: Custom cable lengths available upon request.
Warranty:
• Three (3) Years from shipment date from factory (see Terms & Conditions on kayden.com for details)
Thermal Dispersion
CMP™ 100 Specifications
kayden.com4
CMP™ 100 Thermal Dispersion
CMP Electronics
LED Indicator:
Green LED Indicates the relay is energized
Blue LED Indicates power on
Standard Features:
• Solid state electronics
• Relay can be set to energize above or below set point
• Setpoint adjustable with the trim-pot
• Available in Threaded and Sanitary Flanged configurations
Microprocessor Based Electronics
The electronics are epoxy encapsulated within the sensor housing offering a simple operating status display and trim-pot.
Sanitary AssemblyThreaded Assembly
5kayden.com
Thermal DispersionCMP™ 112 Threaded
Flow & Level Switch (Liquids)
© KAYDEN Instruments. All rights reserved. Contents subject to change without notice.
Please refer to kayden.com for current specifications and configurations.
Model Number Legend Doc. #: ML-112-003-000
112 CODE Sensor Operating Temperature Range
• T ‘T’ Type Sensor
• • CODE Material of Construction - Sensor
• • A 316L Stainless Steel
• • • CODE Process Connection - MNPT
• • • D 3/4"
• • • • CODE Insertion ‘U’ Lengths
• • • • 0012 1.2" (3.0 cm)
• • • • 0020 2" (5.0 cm)
• • • • 0040 4" (10.1 cm)
• • • • • CODE Input Power
• • • • • E 12-36 VDC
• • • • • • Electronics
• • • • • • Epoxy Encapsulated within Sensor Housing.
• • • • • • Single SPST sealed relay contact.
• • • • • • • CODE Agency Approvals
• • • • • • • 6 None - Non-hazardous only
• • • • • • • • CODE Language
• • • • • • • • E English
• • • • • • • • • CODE Cable Length
• • • • • • • • • 0100 10' (3.0 m)
• • • • • • • • • 0300 30' (9.1 m)
• • • • • • • • • 0500 50' (15.2 m)
112 T A D 0020 E 6 E 0100
kayden.com6
CMP™ 115 Threaded
Flow Switch (Inert Gases)
© KAYDEN Instruments. All rights reserved. Contents subject to change without notice.
Please refer to kayden.com for current specifications and configurations.
Model Number Legend Doc. #: ML-115-003-000
Thermal Dispersion
115 CODE Sensor Operating Temperature Range
• T ‘T’ Type Sensor
• • CODE Material of Construction - Sensor
• • A 316L Stainless Steel
• • • CODE Process Connection - MNPT
• • • D 3/4"
• • • • CODE Insertion ‘U’ Lengths
• • • • 0012 1.2" (3.0 cm)
• • • • 0020 2" (5.0 cm)
• • • • 0040 4" (10.1 cm)
• • • • • CODE Input Power
• • • • • E 12-36 VDC
• • • • • • Electronics
• • • • • • Epoxy Encapsulated within Sensor Housing.
• • • • • • Single SPST sealed relay contact.
• • • • • • • CODE Agency Approvals
• • • • • • • 6 None - Non-hazardous only
• • • • • • • • CODE Language
• • • • • • • • E English
• • • • • • • • • CODE Cable Length
• • • • • • • • • 0100 10' (3.0 m)
• • • • • • • • • 0300 30' (9.1 m)
• • • • • • • • • 0500 50' (15.2 m)
115 T A D 0020 E 6 E 0100
kayden.com 7
Thermal DispersionCMP™ 122 Sanitary Flanged
Flow & Level Switch (Liquids)
© KAYDEN Instruments. All rights reserved. Contents subject to change without notice.
Please refer to kayden.com for current specifications and configurations.
Model Number Legend Doc. #: ML-122-003-000
122 CODE Sensor Operating Temperature Range
• T ‘T’ Type Sensor
• • CODE Material of Construction - Sensor
• • A6 304/316L Stainless Steel - Sanitary - (3A Compliant)
• • • CODE Process Connection - Tri-Clamp®
• • • E 1"
• • • G 1.5"
• • • H 2"
• • • J 2.5"
• • • K 3"
• • • L 3.5"
• • • • CODE Insertion ‘U’ Lengths
• • • • 0020 2" (5.0 cm)
• • • • 0040 4" (10.1 cm)
• • • • • CODE Input Power
• • • • • E 12-36 VDC
• • • • • • Electronics
• • • • • • Epoxy Encapsulated within Sensor Housing.
• • • • • • Single SPST sealed relay contact.
• • • • • • • CODE Agency Approvals
• • • • • • • 6 None - Non-hazardous only
• • • • • • • • CODE Language
• • • • • • • • E English
• • • • • • • • • CODE Cable Length
• • • • • • • • • 0100 10' (3.0 m)
• • • • • • • • • 0300 30' (9.1 m)
• • • • • • • • • 0500 50' (15.2 m)
122 T A6 G 0020 E 6 E 0100
kayden.com8
Thermal DispersionCMP™ 125 Sanitary Flanged
Flow Switch (Inert Gases)
© KAYDEN Instruments. All rights reserved. Contents subject to change without notice.
Please refer to kayden.com for current specifications and configurations.
Model Number Legend Doc. #: ML-125-003-000
125 CODE Sensor Operating Temperature Range
• T ‘T’ Type Sensor
• • CODE Material of Construction - Sensor
• • A6 304/316L Stainless Steel - Sanitary - (3A Compliant)
• • • CODE Process Connection - Tri-Clamp®
• • • E 1"
• • • G 1.5"
• • • H 2"
• • • J 2.5"
• • • K 3"
• • • L 3.5"
• • • • CODE Insertion ‘U’ Lengths
• • • • 0020 2" (5.0 cm)
• • • • 0040 4" (10.1 cm)
• • • • • CODE Input Power
• • • • • E 12-36 VDC
• • • • • • Electronics
• • • • • • Epoxy Encapsulated within Sensor Housing.
• • • • • • Single SPST sealed relay contact.
• • • • • • • CODE Agency Approvals
• • • • • • • 6 None - Non-hazardous only
• • • • • • • • CODE Language
• • • • • • • • E English
• • • • • • • • • CODE Cable Length
• • • • • • • • • 0100 10' (3.0 m)
• • • • • • • • • 0300 30' (9.1 m)
• • • • • • • • • 0500 50' (15.2 m)
125 T A6 G 0020 E 6 E 0100
kayden.com 9
Installation Guidelines Thermal Dispersion
Application Considerations - Flow
Flow
Ideal Process Conditions
Liquids:
• Consistent process composition & temperature
• Sufficient straight run flow profile (minimizesturbulence)
• Recommended minimum of 5 pipe diametersfrom any disturbance
Air & Gas:
• Consistent process composition & temperature
• Sufficient straight run flow profile (minimizes turbulence)
• Clean and dry
Slurries:
• Consistent process composition & temperature
• Sufficient straight run flow profile (minimizesturbulence)
Emulsion:
• Consistent process composition & temperature
• Sufficient straight run flow profile (minimizesturbulence)
Undesirable Process Conditions
Liquids:
• Inconsistent process composition or temperature
• Insufficient straight run
• Turbulence
• Aerated fluids
Air & Gas:
• Inconsistent process composition or temperature
• Wet or saturated air/gas
Slurries:
• Inconsistent process composition or temperature
• Insufficient straight run
• Turbulence
• Aerated fluids
Emulsion:
• Inconsistent process composition & temperature
• Insufficient straight run
• Turbulence
• Aerated fluids
Solids:
• Dry granulated processes are NOT good candidates for thermal switches
Application Principles- Flow, Level, Interface & Temperature
4 Consistent process composition
4 Consistent process temperature
4 Clean or dir ty process
4 Liquids
4 Dry air & gas
4 Slurries
4 Emulsion
8 Aerated fluids
8 Large temperature swings
8 Wet or saturated air/gas
8 Solids
8 Sediment covering sensing tip
GAS VENT
OVERFLOW
INLET
PROCESS TANK
LEAK PROTECTION
HIGH LEVEL
LOW LEVEL
PUMP PROTECTION
Side of Switch
Back of Switch
OVERFLOWTANK
kayden.com10
Installation Guidelines Thermal Dispersion
Flow
Mounting & Installation Diagrams for Flow
Bends, Elbows, etc.:
Good installation practice requires
sufficient downstream placement of
bends, expansions or reductions.
Valves, etc.:
Good installation practice
requires sufficient downstream
placement from isolation and
control valves - especially if
valves are only partially
opened.
Pumps, Fans & Compressors:
Good installation practice requires
sufficient downstream placement from
pumps, fans and compressors. The
preferred installation point for pump
flow / no-flow detection is on the inlet
side of the pump.
Note: Flow profiles will tend to be smoother as the downstream distance between the bend, elbow, valve, pump,
fan or compressor and the switch increases.
Flow
Flow
Flow
kayden.com 11
Installation Guidelines Thermal Dispersion
Flow
Mounting the Sensing Element:
• Ensure the arrows engraved on the sensor are oriented parallel to the process flow
• Liquids & Slurries: When mounted in a tee or section of pipe larger than the normal process pipe, position sensor in a
vertical run of pipe with flow upward. This will prevent air or gas bubbles from becoming trapped around the sensing tip
• Avoid locations where sediment may accumulate and eventually isolate the sensing tip from the process. Situating the
sensing tip in the sediment may prevent the switch from being able to sense any changes in the process as the
sediment will insulate the sensing tip
Sensor Orientation
To optimize the sensor’s performance and interpretation of the processes actions, ensure the sensor is
positioned as outlined below:
Mounting Considerations:
• Where possible mount the sensor in the point of least turbulent flow
• Pumps, fans, valves, or pipe bends of 90° or more may cause turbulence or significant variance in the flow which may
affect the repeatability of the switch. When possible, care should be taken to minimize this possibility. Consult your
local Kayden Representative or Kayden for questions or recommendations
• Ensure the arrows engraved on the sensor are oriented parallel to the process flow
• Liquids & Slurries: When mounted in a tee or section of pipe larger than the normal process pipe, position sensor in a
vertical run of pipe with flow upward, this will prevent entrained air or gas from collecting around the sensing tip
• Avoid locations where sediment may accumulate and eventually isolate the sensing tip from the process
• For pump flow/no-flow detecton the best/preferred installation point is on the inlet side of the pump.
The discharge side may have turbulence, reverse flow and an undeveloped flow profile. These factors may
greatly reduce repeatability and accuracy
Guidelines for Flow Applications (Liquids, Slurries, Air, Gas)
Front View of Sensor
Flow
F
Front View of Sensor
Flow & Level
Sensor Orientation for Horizontal Flow
Sensor Orientation for Vertical Flow
kayden.com12
Installation Guidelines Thermal Dispersion
Flow
Horizontal Pipe – Side Mount (Ideal)
Ensure sensing tip is fully inside the pipe wall as a minimum and to the center of the pipe as a maximum. Avoid locations
where sediment may accumulate and isolate the sensing tip from the process.
Horizontal Pipe – Top Mount
Ensure sensing tip is fully inside the pipe wall to a position where it will be constantly and fully exposed to the process in
order for the flow or lack of flow to be recognized at any given time.
Horizontal Pipe – Bottom Mount
Ensure sensing tip is fully inside the pipe wall to a position where it will be constantly covered by the process in order for the
flow or lack of flow to be recognized at any given time. Ensure the process covers the sensing tip – if the sensing tip is
situated near the top of the pipe, the process must be filling the pipe to a level where the sensing tip is covered at all times. A
wide selection of insertion ‘U’ lengths are available starting at 1.2”.
Avoid locations where sediment may accumulate and eventually isolate the sensing tip from the process.
Guidelines for Flow Applications (Liquids, Slurries, Air, Gas)
4 Liquid
4 Gas
8 Liquid (Partially Full)
4 Liquid
8 Gas
8 Sediment
4 Liquid
4 Gas
4 Liquid
4 Gas
Sensor Positioning, Horizontal Pipe
5% minimum
35% min to 65% max
50%
35% min to 45% max
50% maximum
Horizontal Mounting Vertical Up/DownMounting
kayden.com 13
Installation Guidelines Thermal Dispersion
Flow
Vertical Pipe – Side Mount (Acceptable)
Ensure sensing tip is fully inside the pipe wall as a minimum and to the center of the pipe as a maximum.
Note: When installing the switch in vertical piping, Kayden strongly recommends installing thermal switches at a point of
UPWARD process flow to ensure continued total immersion of the sensing tip.
Vertical Pipe – Side Mount – Downward Flow:
• Is only recommended for higher flow rates where the LINE IS KEPT FULL OF LIQUID/SLURRY
• For installation in a vertical gravity flow, the switch must be distant enough from an open outlet that air cavitation does
not affect the sensing tip and cause a false flow signal. A constriction at the outlet avoids this problem
• A waterfall effect will occur in vertical pipe with low flow rates. Also, the process is likely to become substantially
aerated. The switch will interpret the aeration as a substantially lower flow rate and possibly cause a false
low flow alarm
Vertical Pipe – Side Mount – Top & Bottom Mount (Less Desirable)
Positioning the sensor on a corner or elbow is not recommended as the process will be turbulent. The switch may interpret
the turbulence as a constantly changing flow rate and fail to alarm as required.
Vertical Pipe, Flow Up & Down
Guidelines for Flow Applications (Liquids, Slurries, Air, Gas)
8 Liquid
4 Gas
4 Liquid
4 Gas
kayden.com14
Installation Guidelines Thermal Dispersion
Application Considerations - Level
Level
Ideal Process Conditions
Liquids:
• Consistent process composition
• Non-turbulent
Slurries:
• Consistent process composition
Emulsion:
• Consistent process composition
Undesirable Process Conditions
Liquids:
• Inconsistent process composition
• Turbulence
• Large temperature swings
Slurries:
• Inconsistent process composition
• Turbulence
• Large temperature swings
Emulsion:
• Inconsistent process composition
• Turbulence
• Large temperature swings
Solids:
• Dry granulated processes are NOT goodcandidates for thermal switches
Application Considerations - Interface
Interface
Ideal Process Conditions
Liquid to Liquid:
• Consistent process composition & temperature
• Non-turbulent applications
• Large differential in thermal conductivities
Air or Gas to Liquid:
• Consistent process composition & temperature
• Non-turbulent applications
• Dry gas
Emulsion:
• Consistent process composition & temperature
• Large differential in thermal conductivities
Undesirable Process Conditions
Liquid to Liquid:
• Inconsistent process composition or temperature
• High aeration
• High turbulence
• Small differential in thermal conductivities
Air or Gas to Liquid:
• Inconsistent process composition or temperature
• High turbulence
Emulsion:
• Inconsistent process composition or temperature
• High aeration
• High turbulence
• Small differential in thermal conductivities
Solids:
• Dry granulated processes are NOT goodcandidates for thermal switches
kayden.com 15
Installation Guidelines Thermal Dispersion
Liquid Level
Mounting Considerations:• Where possible mount the sensor in the point of
least turbulence
• Agitators, bubblers, valves, or screens may affect therepeatability of the switch. Note: When possible, care should be taken tominimize this possibility. Consult your local KaydenRepresentative or Kayden for questions orrecommendations
• Ensure the arrows on the sensor are oriented parallelto the process surface
• Keep sensing tip clear of any mixing devices that maycause damage
Tanks and Vessels – Side Mount (Ideal)
Ensure sensing tip is fully inside the tank wall
as a minimum.
Tanks and Vessels – Top Mount
Ensure sensing tip is fully inserted to the desired
sensing point.
Point Level & Fluids Interface
kayden.com16
Thermal DispersionAccessories
• Use the RCMS program to change Set Points 1 & 2, adjust Relay
modes, adjust the Start-up Bypass Timer and Set Point Delays, set
the heater to optimize response, lock or unlock the Display Panel
when security and/or settings are critical, visualize the actions of the
process via the graphical display and many other features
• Requires an RS-485 adapter such as the Kayden SCA and acommunication cable
• Provides an additional interface for all CLASSIC 800, CLASSIC 850DIN & BASIC+ 400 models
Part Number: A11-SFT
Stainless Steel Tags
Stainless Steel tags are attached
with stainless steel wire to the switch.
Please provide the exact information
to be engraved.
Part Number: A20-0001
Lamacoid Tags
Lamacoid equipment tags are applied
with double sided tape to any product.
Please provide the exact information
to be engraved.
Part Number: A20-0002
Paper Tags
Select paper tags when temporary
labeling is required. Please provide the
exact information.
Part Number: A20-0003
These items can be purchased separately but are required to use the Kayden RCM software.
Kayden RCM Software
Equipment Tags
Communication Cable is used to connect
the SCA (Serial Communication Adapter)
to the switch.
Standard Lengths: 4, 8 & 10 feet.
Part Number: A05-CC-0004 4 feet
A05-CC-0008 8 feet
A05-CC-0010 10 feet
Communication Cable
RS-232 (DB-9) to RS-485 AdapterThe SCA is an RS-232 to RS-485 adapter for Modbus
communication protocol. The SCA derives
power from the Kayden switch.
Part Number: A15-321
USB to RS-232 (DB-9) AdapterAdapts the Kayden SCA to USB for computers
without a serial port.
Part Number: A15-322
Kayden Converters/Adapters - USB to RS-232 & RS-232 to RS-485
kayden.com 17
Thermal DispersionAccessories
General Purpose (Non-hazardous) Cable &Connector Assembly
Assembly includes 2 general purpose cable fittings.
Construction: 8-strand concentric, Class B tinned
copper, .020" PVC insulation, individual and overall
foil shield, color & number coded, drain and Mylar
separator, PVC inner jacket, aluminum interlock
armor, PVC outer jacket.
Voltage Rating: 300 volts
Temperature Rating:
-40°F to +194°F (-40°C to +90°C);
insulation rated @ 221°F (105°C)
Part Number: A06-GP-xxxx (xxxx = length in feet)
Kayden’s cables are used to connect sensors to remote electronics. Kayden offers cables for both hazardous and general
purpose locations. Cables and cable fittings are pre-assembled and fitted at Kayden’s factory to ensure integrity of all
connections.
Flameproof Cable & Connector Assembly
Assembly includes 2 sealed XP cable fittings and
sealing compound.
Construction: 8-strand concentric, Class B tinned
copper, .020" PVC insulation, individual and overall
foil shield, color & number coded, drain and Mylar
separator, PVC inner jacket, aluminum interlock
armor, PVC outer jacket.
Voltage Rating: 300 volts
Temperature Rating:
-40°F to +194°F (-40°C to +90°C);
insulation rated @ 221°F (105°C)
Part Number: A06-XP-xxxx (xxxx = length in feet)
Assembly includes heat shrink with crimp ferrules.
(Strain relief fittings are not included, however are available as an option).
Construction: 8 color coded conductors 20 AWG, shielded cable, PVC jacket.
Voltage Rating: 30 volts RMS
Temperature Rating: -4°F to +176°F (-20°C to +80°C)
Part Number: A05-GP-xxxx (xxxx = length in feet)
Armored Cable
Non-Armored Cable
Interconnecting Cable for Remote Electronics
kayden.com18
Thermal Dispersion
CMP 112, 115, 122, & 125
CMP 112 & 115 Threaded
10' CABLE STANDARD(2.24)
'U' LENGTH
0.883/4" MNPT
(3.04 METERS)
WHITE (+)
BLUE
GREEN - Not Used
BLACK (-)
BROWN
CMP 122 & 125 Sanitary Flanged
0.88
(2.24)
'U' LENGTH
10' CABLE STANDARD
(3.04 METERS)
WHITE (+)
BLUE
GREEN - Not Used
BLACK (-)
BROWN
Outline Dimensional Drawings
kayden.com 19
CMP™ 100 Thermal Dispersion
Notes
kayden.com20
Thermal Product Group Comparison Thermal Dispersion
MODELS
FEATURESCLASSIC™ 800
SeriesBASIC+™ 400Series
CMP™ 100Series
CLASSIC™ 850DIN
Flow1 4 4 4 4
Level2 4 4 4 4Interface - Liquid / Slurry 4 4 4Temperature3 4 4
Process Media
Liquids 4 4 4 4
Air & Gases1 4 4 4 4
Slurries 4 4 4
Interface 4 4 4
Features
4-20 mA Analog Output 4
Temperature Mode3 4 4
Relay Contacts Dual SPDT Single SPST Single SPST Dual SPDT
Start-up Bypass Timer4 4 4 4
Adjustable Set Point Deadbands 4 4
Display Panel Lock-Out5 4 4 4
Remote Communications6 4 4 4
Input Power12-24 VDC; 115-230 VAC, 50-60 Hz 4 4
12-24 VDC 4 (12-36 VDC) 4
Remote Mount Electronics
CSA Approved (Class I, Div. 1) Enclosures 4 4
FM Approved (Class I, Div. 1) Enclosures 4 4
Agency Approvals
CSA - ANSI/UL Class I, Div. 14
Groups B, C & D
4Groups C & D
General Purpose (Non-hazardous)
General Purpose (Non-hazardous)
FM Class I, Div. 14
Groups B, C & D
4Groups C & D
General Purpose (Non-hazardous)
General Purpose (Non-hazardous)
Notes:
1. For low flow rates ( < 1 sfps) in gases, the CLASSIC 800 / 850 is recommended.
2. Point Level: physical location of the probe determines sensing point.
3. Requires Kayden RCMS and the Modbus communications (see note 6 below). Relay 2 may be configured to actuate on process temperaturewhile the switch functions in a traditional Flow or Level application.
4. Adjustable from 0 - 100 seconds, the Start-up Bypass Timer is useful when restarting a pump.
5. The programming buttons on the Display Panel of the switch may be disabled using the Kayden RCMS and the Modbus communications.
6. Modbus RS-485; requires Kayden RCMS (included at no charge upon request), a Serial Communication Adapter (SCA) or USB Adapter andcommunications cable are available.
kayden.com 21
Thermal DispersionThermal Product Group Overview
© KAYDEN Instruments. All rights reserved. Contents subject to change without notice.
Please refer to kayden.com for current specifications and configurations.
CLASSIC™ 800Series BASIC+™ 400 CMP™ 100
Models &Applications
810, 812, 814, 816, 821, 828, 830, 832 & 850
Flow, Level, Interface & Temperature
410, 412, 414, 416, 421, 428, 430 & 432
Flow, Level & Interface
112: Flow & Level(Liquids)115:
Flow (Gas)
122:Flow & Level(Liquids)125:
Flow (Gas)
ProcessConnections
810 & 410: 1/2" to 2" MNPT Threaded821 & 421: 1/4" MNPT Threaded
812 & 412: Flanged814 & 414: Flanged Retractable Packing Gland
816 & 416: 1" MNPT Threaded Retractable Packing Gland 828 & 428: 1" to 3" Sanitary Tri-Clamp®
830 & 430: 3/4" FNPT (In-Line) 832 & 432: Flanged (In-Line) 850 DIN Rail: Available with all Sensor Models & most connection sizes
825: Flanged (MultiPoint)
Sanitary Tri-Clamp®
3/4" MNPT
Insertion ‘U’Lengths
1.2", 2", 3", 4", 6", 9", 12" & 18" Standard (most models)Custom lengths available to 120"
1.2", 2" & 4"
Material ofConstruction: (Sensor)
Remote ElectronicsOption
316L Stainless, Titanium Gr. 2, Hastelloy C-276, Alloy 20, Monel 400, Inconel 600 & Nickel 200821 & 421: 316L Stainless Steel only
830, 832, 430 & 432: 316L Stainless Steel c/w Nickel Braze828 & 428: 304/316L Stainless Steel
AvailableExplosion-proof - Standard
304/316L Stainless Steel
316L Stainless Steel
Input Power
PowerConsumption
850 DIN: 24 VDC
Maximum: 6 watts Maximum: 2.4 wattsMaximum: 4.8 watts
12-36 VDC
Communications RS-485 None
OutputsSingle SPST sealed relay contact 5 amps res. 250 VAC / 30 VDC
Modbus via RS-485.
Single SPST sealed relay contact
0.5 amps res. 36 VAC / VDC
TemperatureCompensation Yes No
AgencyApprovals
General Purpose
Self-Test Automated diagnostics performed on electronics & sensing elements No
OperatingTemperature -Sensor
OperatingTemperature -Electronics
Continuous Use:-55°C to +200°C (-67°F to +392°F)
814, 816, 414 & 416: -40°F to +320°F (-40°C to +160°C)
Continuous Use:-55°C to +65°C (-67°F to +167°F)
Continuous Use:-40°C to +75°C (-40°F to +167°F)
Continuous Use:-40°C to +85°C (-40°F to +185°F)
Two SPDT sealed relay contacts 5 amps res. 230 VAC / 24 VDC
Modbus via RS-485.4-20 mA current loop (except 850 DIN)
NotAvailable
Universal AC & DC
OperatingPressure -Sensor
Maximum Working Pressure:24 MPa (3500 psig) at 21°C (70°F) - Threaded
Flange units per flange rating1723 kPa (250 psig) at 21°C (70°F) - Sanitary flange units
MWP:3.6 MPa (525 psig)
@ 21°C (70°F)
MWP:1723 kPa (250 psig)
@ 21°C (70°F)
KAYDEN® Thermal Product Group Overview
kayden.com22
Thermal DispersionContact Information
Contact Us
Contact us with any inquiries you may have.
Telephone Fax(403) 253-1423 (403) 253-1460 Local & International
E-Mail [email protected] kayden.com
Hours Monday – Friday 8:00 a.m. – 5:00 p.m. MST
Mailing Address 3368 – 114th Avenue S.E., Calgary, Alberta, Canada T2Z 3V6
Contact a Local Distributor
DistributorsVisit kayden.com to find a local Distributor near you. Kayden Distributors provide local inventory, technical support
and service.
Kayden 60-Day 100% Satisfaction Guarantee
Standard Products
Standard Products are eligible for the 60-Day 100% Satisfaction Guarantee. If you purchased new Standard Products
from Kayden or an Authorized Kayden Distributor, you may return them to the place of purchase up to 60 days from the
date of invoice for a refund or credit of the product purchase price provided the quantity of Products does not exceed
twenty-five units (nominal restocking fee apply to only those quantities exceeding twenty-five units).
Custom Products
Custom Products are not eligible for this guarantee as they are manufactured specifically to the customers’ individual and
unique requirements. Ship returns prepaid. Please note the refund or credit will not include any charges for special
documentation, special equipment, special service, special approvals, drawings, certificates, equipment tags, set points, flow
curves, x-rays, dye penetration tests, opened software, shipping or insurance shown on your invoice. View the Return Policy in
detail at kayden.com.
Kayden offers the following:
• 60 calendar days from the date of invoice.
• Up to twenty-five (25) Standard Products of any type or combination per order. Should the customer, for any reason, be
unsatisfied with any or all of the Products, he/she may return any or all of them for a full refund.
Visit kayden.com to view the Kayden 60-Day 100% Satisfaction Guarantee in detail.
Warranty
Three (3) Years from shipment date from factory (see Terms & Conditions on kayden.com for details).
Ordering Information
5 Ways to Place an Order:
Your Local Distributor
Visit www.kayden.com to find a local Distributor near you.
Telephone Kayden Fax Kayden Email Kayden
(403) 253-1423 (403) 253-1460 Local & International [email protected]
Mail Kayden
3368 – 114th Avenue S.E., Calgary, Alberta, Canada T2Z 3V6
kayden.com
This document and other information from Kayden/ Telematic and its authorized distributors, provides product and/or system options for
further investigation by users having technical expertise. It is important that you analyze all aspects of your application and review the
information concerning the product or system in the current catalog located online at kayden.com.
Copyright 1994 – 2009 Kayden Instruments (a line of products manufactured by Telematic Controls Inc.). All rights reserved.
® ™, KAYDEN, CLASSIC, BASIC, CMP, RCM, RCMS, Remote Control & Monitoring Software, SCA, Helping the World Switch, and
Flow Switch Innovation are trademarks, the property of Kayden Instruments/Telematic Controls Inc.
Tri-Clamp® is a registered trademark of Alfa Laval Inc.
Estane® is a registered trademark of Lubrizol Corporation
Hastelloy® is a registered trademark of Haynes International, Inc.
Inconel®, Incoloy® Alloy 20, Monel® are registered trademarks of Special Metals Corporation
Kayden products are protected by Canadian and International patents.
This catalog is for informational purposes only.
The information contained herein is believed to be reliable, but no representations, guarantees or warranties of any kind are made as to
its accuracy, suitability for particular applications or the results to be obtained therefrom. The information is based on laboratory work
with small-scale equipment and does not necessarily indicate end product performance. Because of the variations in methods,
conditions and equipment used commercially in applying these products, no warranties or guarantees are made as to the suitability of
the products for the application(s) disclosed. Full-scale testing and end product performance are the responsibility of the user. Kayden
Instruments/Telematic Controls Inc. shall not be liable for and the customer assumes all risk and liability of any use of handling of any
product beyond Kayden Instruments/Telematic Controls Inc. direct control. THE SELLER MAKES NO WARRANTIES, EXPRESS OR
IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE. Nothing contained herein is to be considered as permission, recommendation, nor as an inducement to
practice any patented invention without permission of the patent owner.
For more information about the CMP 100 Series or any of Kayden’s other products, or to learn more
about Kayden, please visit us at www.kayden.com