the new static var compensator for sps – commissioning results based on the cired2003 conference...

1
` THE NEW STATIC VAR COMPENSATOR FOR SPS – COMMISSIONING RESULTS based on the CIRED2003 conference paper from K. Kahle, J. Pedersen (CERN) and T. Larsson, M. M. Oliveira (ABB) CERN - European Organization for Nuclear Research K. Kahle April 2003 6th ST Workshop, THOIRY Design The new Static Var Compensator for the SPS, CERN Prevessin Background Calculations before installation Measurements after installation Calculated harmonics performance The SVC is an outdoor installation covering an area of about 2500 m 2 . It also includes a prefabricated building for the high voltage thyristor valves, the cooling system and the SVC control system. The remaining space is used for the harmonic filters. The SVC consists of a TCR rated at 150 Mvar and eight harmonic filters tuned to 100, 150, 250, 350, 550, 650 Hz and two damped high-pass filters. The filters generate a total reactive power of 130 Mvar. Calculated harm onic distortion 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 frequency (H z) harm onic distortion (% ) M easured harm onic distortion 0 0.1 0.2 0.3 0.4 0.5 0.6 50 100 150 250 350 550 650 850 950 1150 1250 frequency (H z) harm onic distortion (% ) Measured harmonic performance Measured 18 kV bus voltage Measured load current during a SPS pulse Results of 18 kV voltage calculations: The EMTDC computer simulations modeled the behavior of the SPS power converters, of the Static Var Compensator and of the interaction between them. The main purpose of the Static Var Compensator is to stabilize the 18 kV voltage, therefore the resulting 18 kV network voltage was calculated for a complete SPS pulse. Small variations of the 18 kV voltage were expected at the transition points from the rising slope of the power pulse to the flat top and from the flat top to the pulse descent. Results of 18 kV harmonic measurements: Total Harmonic Distortion 0.74 % no individual harmonic exceeding 0.5 % The measurements correspond closely to the calculated values. Results of 18 kV voltage measurements: The voltage response was recorded and the data post-processed with MATLAB. The comparison of the calculated 18 kV voltage with the measured response shows large similarities. All voltage notches, both up and down, are identical. Only the first notch at t=9 s of the measurement is critical, while the second, larger variation at t=10.5 s has no major significance for the physics performance of the SPS accelerator. Some discrepancies were found in the amplitude of the notches, where the measurements show larger voltage variations than the calculations predicted. Here the computer model needs to be improved in the future. Conclusions Following a long history of SVC projects at CERN since 1974, the new 150 Mvar 18 kV Static Var Compensator was successfully installed and tested in 2002. During the project there was a unique opportunity to compare and verify comprehensive computer studies with the results of extensive measurements. Following the actual performance tests, the correct operation of the SVC, together with the SPS accelerator, was successfully proven over a period of several months. This project also shows the excellent SVC performance, which can be achieved for fast changing rectifier loads, by using conventional TCR technology, combined with passive filtering. Computer calculations: a) active and reactive power b) resulting 18 kV voltage c) TCR susceptance reference d) TCR firing angle e) reactive power from 400 kV network The The SPS electrical network currently consists of: • 3 transformers 400/18 kV • 3 Static Var Compensators (1974, 1976 and 2002) • 2 main groups of SPS power converters The new Static Var Compensator (SVC) was required: • to have a third redundant supply group (3 transformers and 3 SVC’s) • to facilitate the renovation of the two existing Static Var Compensators • to cover the load increase due to the LHC injection tunnels TI2 / TI8. Purpose of the Static Var Compensator (SVC): The electrical current in the SPS magnet is pulsating between zero Ampere and 4500 Ampere every 14 seconds. A Static Var Compensator: • compensates for the reactive power • stabilizes the 18 kV voltage (variation: 14% without SVC, 0.75 % with SVC) • eliminates the harmonics created by the pulsating load (harmonic distortion: 20% without SVC, 0.74 % with SVC) Results of 18 kV harmonic calculations: Total Harmonic Distortion < 0.8 % no individual harmonic exceeding 0.35 % The studies confirmed that eight harmonic filters were needed to achieve the required excellent performance. Existing SVC BEQ1 Existing SVC BEQ3 New SVC BEQ2 SPS SPS Impedance diagram

Upload: rolf-bond

Post on 17-Jan-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

THE NEW STATIC VAR COMPENSATOR FOR SPS COMMISSIONING RESULTS based on the CIRED2003 conference paper from K. Kahle, J. Pedersen (CERN) and T. Larsson, M. M. Oliveira (ABB) CERN - European Organization for Nuclear Research K. Kahle April 20036th ST Workshop, THOIRY Design The new Static Var Compensator for the SPS, CERN Prevessin Background Calculations before installation Measurements after installation Calculated harmonics performance The SVC is an outdoor installation covering an area of about 2500 m 2. It also includes a prefabricated building for the high voltage thyristor valves, the cooling system and the SVC control system. The remaining space is used for the harmonic filters. The SVC consists of a TCR rated at 150 Mvar and eight harmonic filters tuned to 100, 150, 250, 350, 550, 650 Hz and two damped high-pass filters. The filters generate a total reactive power of 130 Mvar. Measured harmonic performance Measured 18 kV bus voltage Measured load current during a SPS pulse Results of 18 kV voltage calculations: The EMTDC computer simulations modeled the behavior of the SPS power converters, of the Static Var Compensator and of the interaction between them. The main purpose of the Static Var Compensator is to stabilize the 18 kV voltage, therefore the resulting 18 kV network voltage was calculated for a complete SPS pulse. Small variations of the 18 kV voltage were expected at the transition points from the rising slope of the power pulse to the flat top and from the flat top to the pulse descent. Results of 18 kV harmonic measurements: Total Harmonic Distortion 0.74 % no individual harmonic exceeding 0.5 % The measurements correspond closely to the calculated values. Results of 18 kV voltage measurements: The voltage response was recorded and the data post-processed with MATLAB. The comparison of the calculated 18 kV voltage with the measured response shows large similarities. All voltage notches, both up and down, are identical. Only the first notch at t=9 s of the measurement is critical, while the second, larger variation at t=10.5 s has no major significance for the physics performance of the SPS accelerator. Some discrepancies were found in the amplitude of the notches, where the measurements show larger voltage variations than the calculations predicted. Here the computer model needs to be improved in the future. Conclusions Following a long history of SVC projects at CERN since 1974, the new 150 Mvar 18 kV Static Var Compensator was successfully installed and tested in During the project there was a unique opportunity to compare and verify comprehensive computer studies with the results of extensive measurements. Following the actual performance tests, the correct operation of the SVC, together with the SPS accelerator, was successfully proven over a period of several months. This project also shows the excellent SVC performance, which can be achieved for fast changing rectifier loads, by using conventional TCR technology, combined with passive filtering. Computer calculations: a) active and reactive power b) resulting 18 kV voltage c) TCR susceptance reference d) TCR firing angle e) reactive power from 400 kV network The The SPS electrical network currently consists of: 3 transformers 400/18 kV 3 Static Var Compensators (1974, 1976 and 2002) 2 main groups of SPS power converters The new Static Var Compensator (SVC) was required: to have a third redundant supply group (3 transformers and 3 SVCs) to facilitate the renovation of the two existing Static Var Compensators to cover the load increase due to the LHC injection tunnels TI2 / TI8. Purpose of the Static Var Compensator (SVC): The electrical current in the SPS magnet is pulsating between zero Ampere and 4500 Ampere every 14 seconds. A Static Var Compensator: compensates for the reactive power stabilizes the 18 kV voltage (variation: 14% without SVC, 0.75 % with SVC) eliminates the harmonics created by the pulsating load (harmonic distortion: 20% without SVC, 0.74 % with SVC) Results of 18 kV harmonic calculations: Total Harmonic Distortion < 0.8 % no individual harmonic exceeding 0.35 % The studies confirmed that eight harmonic filters were needed to achieve the required excellent performance. Existing SVC BEQ1Existing SVC BEQ3 New SVC BEQ2 SPS Impedance diagram Simplified layout of the SPS electrical network Layout of the SVC