IEEJ: March 2009 Standards & Labeling System for Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for Standards & Labeling System for Air Air - - conditioning Equipment conditioning Equipment in US, Europe and Japan in US, Europe and Japan The Japan Refrigeration and Air Conditioning Industry Association (JRAIA) Tetsuro Kishimoto, President Sugawara Sakuo, Inspection &Testing Group

Upload: others

Post on 13-Jun-2020

13 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

Standards & Labeling System forAir-conditioning Equipment in US, Europe and Japan

Standards & Labeling System forStandards & Labeling System forAirAir--conditioning Equipment conditioning Equipment in US, Europe and Japanin US, Europe and Japan

The Japan Refrigeration and Air Conditioning Industry Association

(JRAIA)

Tetsuro Kishimoto, President Sugawara Sakuo, Inspection &Testing Group

Page 2: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

1. Introduction

2.Features of Japan’s Energy-saving Standards and Domestic DemandShifting from COP to APFLeading Methods, Energy-saving Standards, and their Effects Labeling

3.American Energy-saving Standards: IPLV

4.Challenges facing the New Energy-saving Standards Energy-saving Capabilities of INV and NON-INV Devices

5. Conclusion

Contents

Page 3: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

Demand for Air ConditionersDemand for Air Conditioners

4,722

5,920

7,081

6,240

5,040

6,717

7,6888,109

7,148

6,5507,019

7,677

6,470

7,570

6,902 7,040

6,469

4,5873,965

3,6523,380

0

2,000

4,000

6,000

8,000

10,000

85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 00 01 02 03 04 05 06 07

Seasonal year (October – September)

Total demand (1,000 units)

Cooling only

HP(Non-INV)

HP(INV)

7,420

Cooling/heating,Inverter,Wall, separate type

Source: Data reported by Mitsubishi Electric Co.

Page 4: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009JapanJapan’’s Energys Energy--saving Standardssaving StandardsCOPCOP →→ APFAPF

COP shows cooling/heating capacity (kW) per 1 kW of power consumption. A higher figure represents higher efficiency of energy consumption and higher energy-saving capability.

(COP:Coefficient of Performance)

APE also shows cooling/heating capacity (kW) per 1 kW of power consumption. It takes into account not only power consumption at rated time but also load conditions such as buildings where air conditioners are used and purpose of use, outside air temperature while cooling or heating, and efficiency of the air conditioner depending on the differing capacities of inverter devices, thus making it possible to evaluate energy consumption performance against utilization.

(APF: Annual Performance Factor)

COP (Coefficient of Performance)

APF (Annual Performance Factor)

( Coefficient of Performance ) (Annual Performance Factor)

Page 5: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

Adopting APF (Annual Performance Factor) Adopting APF (Annual Performance Factor)

EnergyEnergy--consumption Performance (Energyconsumption Performance (Energy--saving law) saving law) COP = (cooling rated COP + heating rated COP) / 2

APF = f (cooling rated COP, cooling median COP, heating rated COP, heating median COP, heating low-temperature COP, duration of outside air temperature)

Calculation methods matching the Japanese lifestyle and local enCalculation methods matching the Japanese lifestyle and local environment! vironment!

Changes in design points through the Changes in design points through the revision of energyrevision of energy--saving standardssaving standards

Life changes in line with change in airLife changes in line with change in air--conditioning capabilityconditioning capability

(Energy(Energy--saving standards appropriate to saving standards appropriate to each locality/environment) each locality/environment)

Page 6: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009 APF (Annual Performance Factor) APF (Annual Performance Factor)

Outside air temperature

Japan/Tokyo Meteorological data

Preset temperature

27℃ for cooling/20℃ for heating

Duration

Cooling 3.6 months June 2 – Sept. 21

Operating hours 18 hours, 6:00 – 24:00

Type of house Average wooden house (facing south)

Heating 5.5 monthsOct. 28 – Apr. 14 Room space Room space matching each

machine

Examples of locational constantsSapporo(3.1),Sendai (1.6),Tokyo(1.0),Osaka(1.2),Fukuoka(1.1),Naha(0.6)

Cooling capacity(kW) (appellation) 2.2 2.5 2.8 3.6 4.0

Aggregated cooling/heating capacity (kWh)

4,408 5,010 5,611 7,214 8,015

Cooling capacity(kW) (appellation) 4.5 5.0 5.6 6.3 7.1

Aggregated cooling/heating capacity (kWh)

9,017 10,019 11,222 12,624 14,227

Standards for calculating duration of outside air temperature (JStandards for calculating duration of outside air temperature (Japan) apan)

Aggregated cooling/heating capacity by cooling capacity Aggregated cooling/heating capacity by cooling capacity

Power consumption during seasons = aggregated cooling/heating caPower consumption during seasons = aggregated cooling/heating capacity / APFpacity / APFElectricity cost = power consumption during each season x 22 yenElectricity cost = power consumption during each season x 22 yen x x locationallocational constant constant

Page 7: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

APF (Annual Performance Factor) APF (Annual Performance Factor)

外気温度の発生時間(暖房期間)

0

50

100

150

200

250

300

350

-8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22

外気温度[℃]

発生

時間

[hr]

外気温度の発生時間(冷房期間)

0

50

100

150

200

250

300

22 24 26 28 30 32 34 36 38 40

外気温度[℃]

発生

時間

[hr]

Total heating hoursTotal heating hours==2,889 hrs2,889 hrsΣΣ((duration x difference in temperatureduration x difference in temperature)=)=32,231 32,231

((Room temperature assumed 20Room temperature assumed 20℃℃))

Total cooling hoursTotal cooling hours==1,430 hrs1,430 hrsΣΣ((duration x difference in temperatureduration x difference in temperature)=)=10,13410,134((Room temperature assumed 27 Room temperature assumed 27 ℃℃))

Design point is on Design point is on ““median heatingmedian heating””. .

Duration of outside air temperature (heating season)

Duration of outside air temperature (cooling season)

Dur

atio

n (h

ours

)

Dur

atio

n (h

ours

)

Outside air temperature (℃) Outside air temperature (℃)

Page 8: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

Type of unit Cooling capacity

Baseline energy consumption performance

(COP)

Targeted year

Direct air-blowing, wall type (not including multi types for which an indoor device is controlled in each room)

2.5kW or less 5.272004

Refrigeration year

2.5kW - 3.2 kW 4.90

3.2kW - 4.0 kW 3.65

4.0kW - 7.1 kW 3.17 2007Refrigeration

yearOver 7.1kW 3.10

Primary targets for air conditioner energy-savings

(Excerpts)

Page 9: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009 Changes in distribution of air conditioner performance

2.8 kW cooling capacity class - data from JRAIA

1996 1998 2000 2002 2004 2006

Lowest COPdeviceWeighted average

Highest COP device

Leading target

Page 10: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

Category

Baseline energy consumption performance(APF)

Refrigeration capacity Dimensional categoryCategory

name

3.2 kW or lower

Dimension-defined type A 5.8 (←4.90)

Dimension-free type B 6.6 (←4.90)

3.2 kW - 4.0 kWDimension-defined type C 4.9 (←3.65)

Dimension-free type D 6.0 (←3.65)

Under the heading Dimensional category, “dimension-defined type” refers to indoor devices that are less than 800 mm in width and 295 mm in height.Others are categorized as dimension-free type.

Secondary targets for air conditioner energy-savings

(Excerpts)

Targeted year: 2010

Figures in parentheses show the relevant primary targets

Page 11: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

期間消費電力量  〔 k W h〕

Changes in energy-saving capabilities ofair conditioners

Cooling & heating combined, wall, 2.8 kW cooling capacity, energy-saving typeSource: JRAIA

Power consumption during cooling season Power consumption during heating season

Power consumption during the seasons 〔kWh〕

FY 1995FY 1996FY 1997FY 1998FY 1999FY 2000FY 2001FY 2002FY 2003FY 2004FY 2005FY 2006FY 2007FY 2008

Page 12: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009 Problems with APFProblems with APF

・The COP of inverter air-conditioners has the secondary feature of a convex upper shape

Lines where COP is reduced during low capacity are similar→ Losing touch with actual operation during low capacity

・Capacity ranges greater than rated capacity are estimated according to energy-saving capability at rated times→ Difference in power consumption/consumption current during actual operation (when operating for a short time)

・Outside air temperature is assumed to be the same for rated time and median time → Different from actual usage

・Annual usage is assumed at 9.1 months; daily usage at 18 hours→ Longer than actual usage?

APF (an indicator of actual air conditioner usage in Japan)

s1

Page 13: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

Labeling system for energyLabeling system for energy--saving saving ・Introduced in 2000 by Japanese Industrial Standards (JIS) ・Level of achievement of leading standards to be displayed

→ Useful when users select home appliances

Models attaining the targetModels attaining the target

Models not attaining the target Models not attaining the target

Targeted appliancesTargeted appliances(Leading appliances)

・Air conditioners・Fluorescent lighting fixtures・TVs・Refrigerator・Rice cookers with thermos function・Microwave ovens・DVD recorders

Energy-saving standard achievement ratio

Annual power consumption

Energy-saving standard achievement ratio

Annual power consumption

Targeted year

Targeted year

year

year

Page 14: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

Unified energyUnified energy--saving labelsaving labelRetailers started using the unified energy-saving label in October 2006 as a system for showing energy-saving performance.

・Multistep assessment system to show relative energy-saving performance of marketed appliances by numbers of stars ★

・Standards are reviewed in April every year taking into consideration the energy-saving performance distribution of each type of appliance

Targeted appliances・Air conditioners・Refrigerators・TVs

Page 15: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

AmericaAmerica’’s Energys Energy--saving saving Standards: IPLVStandards: IPLV

IPLVIPLV((Integrated Part Load Value)Integrated Part Load Value)・Set up by ARI(Air conditioning & Refrigeration Institute)

・Seasonal performance coefficient weighted by annual generation frequency using COPs of several different loads and testing conditions

・An indicator similar to APF

・China and European countries are now considering adoption of these standards for evaluating air conditioning performance

Page 16: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

Stepn

Partial load ratio

Air temperature at compressor

intake

1 100% 35 ℃

2 75% 30 ℃

3 50% 25 ℃

4 25% 20 ℃

5 0% 15 ℃

Relationship between Partial Load Ratios and Partial Load Factors

American EnergyAmerican Energy--saving saving Standards: IPLVStandards: IPLV

1.0

2.0

4.0

3.0

0

Per

form

ance

Fa

ctor

IPLV calculation formula with 4 levels of partial load steps

PLV= (PLF1-PLF2)(COP1+COP2) / 2+ (PLF2-PLF3)(COP2+COP3) / 2+ (PLF3-PLF4)(COP3+COP4) / 2+ PLF4・COP4

Test conditions at partial load steps(Chiller)

Par

tial L

oad

Fact

or (P

LF)

Partial Load Ratio (%)

Page 17: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009EnergyEnergy--saving standards suited tosaving standards suited toeach regioneach region

TThe basic idea he basic idea behind APFbehind APF

APF =Heat load at actual usage (cooling/heating times)

Power consumption at actual usage

APF ≠ COP , APF ≠ (H・COP+C・COP)/ 2Representative value of actual heat load ≠ rated point, Power consumption at actual usage ≠ rated point

As a result, in Japan, figures are calculated based on performance (rated, median, and low-temperature) and meteorological data for Tokyo, and difference from Tokyo is adjusted using locational constants.

In nature, IPLV is similar to APFIn nature, IPLV is similar to APF・・Loads are categorized in partsLoads are categorized in parts・・Test condition differs between partial loadsTest condition differs between partial loads

Page 18: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

Desirable energyDesirable energy--saving standards for saving standards for air conditionersair conditioners

1) Applicable both to inverter and non-inverter devices2) Applicable both to cooling regions and cooling/heating regions 3) Performance assessment points and outside air conditions meet international standards 4) Up to three performance assessment points5) Based on regional climate data and average housing 6) Within each region, should be adjusted using locationalconstants etc. 7) Periodically reviewed depending on development of air conditioners

1) Applicable both to inverter and non-inverter devices2) Applicable both to cooling regions and cooling/heating regions 3) Performance assessment points and outside air conditions meet international standards 4) Up to three performance assessment points5) Based on regional climate data and average housing 6) Within each region, should be adjusted using locationalconstants etc. 7) Periodically reviewed depending on development of air conditioners

・COP and SEER are incapable of assessing power consumption during actual use ・New energy-saving standards do not necessarily mean to choose either IPLV or APF・Standards that are reasonable, valid, and suitable for housing/climate/usage of each

country/region are sought

Page 19: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

(100%)(100%)(20%)(20%) (140%)(140%)(50%)(50%)

Comparing Inverter devices with NonComparing Inverter devices with Non--inverter devicesinverter devices

OFFOFF

ONON

Capacity exceeds load so ability to attain room temperature improves

Range of cooling Range of cooling capacity generated capacity generated (kW) (kW)

NonNon--INVINV

devicedevice

INVINVdevicedevice

Required cooling loadRequired cooling load

Room temperature rises when Room temperature rises when coolingcooling

Room temperature Room temperature rising when coolingrising when cooling

Range where room temperature becomes uncontrollable due to of load generation exceeding air conditioning capacity

OFFOFF

ONON

Difficult to assure room temperature control ability due to restriction preventing COMP restart

Competent rangeCompetent range

Maxim

umM

aximum

Rated

Rated

Minim

umM

inimum

Page 20: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

Operation of Inverter device(During sleep, in Nagoya, in 1998) Operation of Inverter deviceOperation of Inverter device(During sleep, in Nagoya, in 1998) (During sleep, in Nagoya, in 1998)

A室(1998年 7月29日~7月30日)

0

5

10

15

20

25

30

35

18:00 21:00 0:00 3:00 6:00 9:00

時   刻

温 

  

度[℃

]

0

500

1000

1500

2000

2500

3000消

費電

力[W

]

吸込温度[℃]

吹出温度[℃]

消費電力[W]

B室(1998年 8月5日~8月6日)

10

15

20

25

30

35

18:00 21:00 0 :00 3 :00 6 :00 9:00

時   刻

温 

  

 度

[℃]

0

100

200

300

400

500

消費

電力

[W]

吸込温度[℃] 吹出温度[℃]

消費電力[W]

General device(Minimum power: 0.9 kW) Test device(Minimum power: 0.5 kW)

TimeTime

A室(1998年 7月29日~7月30日)

20

25

30

35

18:00 21:00 0:00 3:00 6:00 9:00

時   刻

温 

  

度[℃

]

外気温度[℃]

室内空気温度[℃]

設定温度:28[℃](1:30以降29[℃])

B室(1998年 8月5日~8月6日)

20

25

30

35

18:00 21:00 0:00 3:00 6:00 9:00

時   刻

温 

  

 度

[℃]

外気温度[℃]

室内空気平均温度[℃]

設定温度:29[℃](22:40以降30[℃])

Pow

er c

onsu

mpt

ion

(W)

Pow

er c

onsu

mpt

ion

(W)

Temperature of intake air (℃) Temperature of emitted air (℃) Power consumption (W)

Temperature of intake air (℃) Power consumption (W)

Temperature of emitted air (℃)

Room B (August 5 – August 6, 1998)Room A (July 29 – July 30, 1998)

Tem

pera

ture

(℃)

Tem

pera

ture

(℃)

Tem

pera

ture

(℃)

Tem

pera

ture

(℃)

TimeTime

Preset temperature: 28℃ (29℃ after 1:30)

Preset temperature: 29℃ (30℃ after 22:40)Outside air temperature (℃) Room air temperature (℃)

Outside air temperature (℃) Room air temperature (℃)

Room B (August 5 – August 6, 1998)Room A (July 29 – July 30, 1998)

Page 21: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009 Application of new energyApplication of new energy--saving standards saving standards

Assessment of coolingAssessment of cooling--only, cooling/heating, Nononly, cooling/heating, Non--INV, and INV INV, and INV devices is possible using a single set of energydevices is possible using a single set of energy--saving standards saving standards by metering constantby metering constant--speed time of Nonspeed time of Non--INV devices and energyINV devices and energy--saving performance when turning devices on or off. saving performance when turning devices on or off.

1)Simulating operation characteristics caused by changes in outside air at model houses

→ Frequency and running rate under standard conditions

2)Metering energy-saving performance using air enthalpy method

→ Metering performance by running rate

3)Calculating power consumption by realized load → New energy-saving standards

Air conditioning capacity

COP

Inverter

Non-Inv

Page 22: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009 Application of new energyApplication of new energy--saving standards saving standards

Assessment of coolingAssessment of cooling--only, cooling/heating, Nononly, cooling/heating, Non--INV, and INV INV, and INV devices is possible using a single set of energydevices is possible using a single set of energy--saving standards saving standards by metering constantby metering constant--speed time of Nonspeed time of Non--INV devices and energyINV devices and energy--saving performance when turning devices on or off. saving performance when turning devices on or off.

1)Simulating operation characteristics caused by changes in outside air at model houses

→ Frequency and running rate under standard conditions

2)Metering energy-saving performance using air enthalpy method

→ Metering performance by running rate

3)Calculating power consumption by realized load → New energy-saving standards

Air conditioning capacity

COP

Inverter

Non-Inv

Page 23: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

Points to note when conducting Points to note when conducting questionnaire surveyquestionnaire survey

Points to note when conducting questionnaire survey Points to note when conducting questionnaire survey ・・When looking at the insulation ability of houses, etc, show modeWhen looking at the insulation ability of houses, etc, show model house l house

structuresstructures →→ so respondents can choose. so respondents can choose. ・・Specify a room space as an airSpecify a room space as an air--conditioned area (a closed space). conditioned area (a closed space). ・・For data that appears to show unbalanced airFor data that appears to show unbalanced air--conditioning load and conditioning load and

capacity, conduct an additional survey on usage of air conditioncapacity, conduct an additional survey on usage of air conditioners ers and categorize it as unique data with comments (eliminate it froand categorize it as unique data with comments (eliminate it from the m the statistical data). statistical data).

・・Survey heatSurvey heat--generating appliances such as home appliances (estimate generating appliances such as home appliances (estimate types of appliances and amount of generated heat) types of appliances and amount of generated heat)

・・Check amount of clothing at home, and estimate sensation of warmCheck amount of clothing at home, and estimate sensation of warmth. th. →→ (Estimate clothing amount) (Estimate clothing amount) →→ Estimate comfortable temperatureEstimate comfortable temperature

・・Survey behavioral patterns per day/per weekSurvey behavioral patterns per day/per week(at home/not at home, cleaning, washing, relaxation time at home(at home/not at home, cleaning, washing, relaxation time at home, , preparing meals, eatingpreparing meals, eating……) )

Page 24: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

Points to note when conducting Points to note when conducting Metering SurveyMetering Survey

Points to note when conducting Metering Survey No. 1 Points to note when conducting Metering Survey No. 1 1) When measuring temperature, meter outside air temperature, room temperature,

and temperature at air intake of air conditioners. Meter humidity of outside air and in the room if possible.

(units: ○.○℃,○○RH%) ・Outside air temperature: Measure at north side of building, which is in the shade

all day. Measure humidity if possible.

・Room temperature: Measure where the temperature is not influenced by air coming from air conditioners, and at places close to inhabitants. Height: For heating: 5 – 10 cm above the floor; for cooling: 1.2 m above the floor

・Temperature at air intake: Set up at air intake of air conditioner where air is moving.

2) Power consumption of air conditioners (unit: W) ・When metering power consumption of air conditioners, sampling intervals

should be 1 minute or less. 3) A questionnaire survey should be implemented.

Page 25: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

Points to note when conducting Points to note when conducting Metering SurveyMetering Survey

Points to note when conducting Metering Survey No. 2 Points to note when conducting Metering Survey No. 2

4) How to estimate heat load 4) How to estimate heat load ・・When measuring the heat load of houses, do so when generated airWhen measuring the heat load of houses, do so when generated air conditioning conditioning

capacity and heat load are balanced. Do not estimate it when thecapacity and heat load are balanced. Do not estimate it when the room temperature is room temperature is within a nonwithin a non--controlled range just after the switch has been turned on. controlled range just after the switch has been turned on. ・・As for generated air conditioning capacity (kWh) at On/Off timesAs for generated air conditioning capacity (kWh) at On/Off times, estimate generation , estimate generation

capacity per hour using Oncapacity per hour using On--time, rated capacity (indicated value), and power time, rated capacity (indicated value), and power consumption. consumption. As for power consumption, calculate power consumption per hour (As for power consumption, calculate power consumption per hour (kWh) using On/Off kWh) using On/Off cycle length and the relevant power consumption. cycle length and the relevant power consumption. ・・As a survey on the preset temperature is necessary, record changAs a survey on the preset temperature is necessary, record changes in preset es in preset temperature during operation. temperature during operation. ・・Another method is to estimate the heat load of houses through inAnother method is to estimate the heat load of houses through information about the formation about the characteristics of houses collected by questionnaire etc. and mecharacteristics of houses collected by questionnaire etc. and measured data such as asured data such as room/outside temperature. room/outside temperature.

Page 26: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009 EnergyEnergy--saving performance saving performance evaluation points evaluation points

1) As for performance evaluation points, the more points you use, the more accurately you can measure power consumption. As COP is featured by upper-convex second-order characteristic, taking test cost into consideration, you should use up to three points.

2) Although inputting the minimum capacity may be a popular method, it makes accurate measurement difficult because minimum capacity is0.2 – 0.5 kW-level. Let’s consider more reasonable methods such as using simulation values.

3) It is desirable to internationally unify, through ISO etc, the capacity ratios and outside environment conditions of performance evaluation points. Each region/country chooses the relevant points out of an internationally unified system.

Page 27: The Japan Refrigeration and Air Conditioning …Air-conditioning Equipment in US, Europe and Japan Standards & Labeling System for AirAir-conditioning Equipment in US, Europe and Japan

IEEJ: March 2009

ConclusionConclusion

・Energy-saving standards for air conditioners should show the direction of their development and reflect people’s lives in the country/region.

・When establishing new energy-saving standards, we should choose neither the US’s IPLV nor Japan’s APF. Rather, we should create new standards that are better suited to each country/region.

・Evaluation test points/test conditions should meet internationally agreed standards, with each country/region being able to choose appropriate ones for their situations.

・ Due to development/test costs, evaluations should test a maximum of three points.

・Fair energy-saving standards and test facilities are needed so that air conditioners can compete fairly in the global market.

・Development of air conditioners entails the development of facilities to test air conditioning performance.

・ Now might be the time when we have to consider new testing technologies that take into consideration high accuracy testing technology for low capacities and a test of the ability to create a certain environment that respects human senses.