Location: Engineer: Study Case: SC 7.0.0 Page: 1 SN: 12345678 Filename: 26MW Shagharthang HPP Project: ETAP Contract: Date: 01-02-2012 Revision: Base Config.: Normal Electrical Transient Analyzer Program IEC 60909 Standard 3-Phase Fault Currents Short-Circuit Analysis Short-Circuit Current Based on User-Defined c Factor Total Number of Buses: Swing V-Control Load Total Number of Branches: XFMR2 Reactor Line/Cable Impedance Tie PD XFMR3 Total Number of Machines: Generator Motor Machines Synchronous Synchronous Induction Load Lumped 1 2 9 6 0 1 0 0 4 3 0 0 18 0 12 11 21 Power Grid System Frequency: 50 Hz Unit System: Metric Project Filename: 26MW Shagharthang HPP Output Filename: C:\ETAP 700\26MW Shagharthang HPP\Untitled.SI1

Upload: muzzamilali

Post on 06-Dec-2015

17 views

Category:

Documents


3 download

DESCRIPTION

System Analysis

TRANSCRIPT

Page 1: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 1

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

Electrical Transient Analyzer Program

IEC 60909 Standard

3-Phase Fault Currents

Short-Circuit Analysis

Short-Circuit Current Based on User-Defined c Factor

Total

Number of Buses:

Swing V-Control Load Total

Number of Branches:

XFMR2 Reactor Line/Cable Impedance Tie PDXFMR3 Total

Number of Machines:

Generator Motor Machines

Synchronous Synchronous Induction

Load

Lumped

1 2 9

6 0 1 0 0 4

3 0 0 18 0

12

11

21

Power

Grid

System Frequency: 50 Hz

Unit System: Metric

Project Filename: 26MW Shagharthang HPP

Output Filename: C:\ETAP 700\26MW Shagharthang HPP\Untitled.SI1

Page 2: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 2

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

Adjustments

Transformer Impedance:

Reactor Impedance:

Adjustments

Apply

/Global

Individual

PercentTolerance

Overload Heater Resistance:

Transmission Line Length:

Cable Length:

Temperature Correction

Transmission Line Resistance:

Cable Resistance:

Apply

Adjustments

Individual

/Global Degree C

Individual

Individual

Individual

Individual

Yes

Yes

No

No

No

Yes

Yes

Page 3: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 3

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

Bus Input Data

ID Type

Bus Initial Voltage

%Mag. Ang.Sub-sysBase kVNom. kV

11.000 11.000SWNGBus1 1 100.00 0.00

66.000 66.000LoadBus2 1 100.00 0.00

66.000 66.000LoadBus4 1 100.00 0.00

11.000 11.000Gen.Bus7 1 100.00 0.00

66.000 66.000LoadBus8 1 100.00 0.00

11.000 11.000Gen.Bus13 1 100.00 0.00

66.000 66.000LoadBus14 1 100.00 0.00

66.000 66.000LoadBus15 1 100.00 0.00

66.000 66.000LoadBus16 1 100.00 0.00

11.000 11.000LoadBus17 1 100.00 0.00

11.000 11.000LoadBus22 1 100.00 0.00

11.000 11.000LoadBus24 1 100.00 0.00

12 Buses Total

All voltages reported by ETAP are in % of bus Nominal kV.

Base kV values of buses are calculated and used internally by ETAP .

Page 4: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 4

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

Line/Cable Input Data

ID Library Size #/Phase R

Line/Cable

Ohms or Siemens/1000 m per Conductor (Cable) or per Phase (Line)

Adj. (m) % Tol.

Length

YXT (°C)

Line1 183 1609.3 1 1.24274 75 0 0.0000034 0.49710

Line / Cable resistances are listed at the specified temperatures.

Page 5: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 5

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

2-Winding Transformer Input Data

ID MVA Prim. kV Sec. kV % Z X/R Prim. Sec.

Transformer

% Tol.

Rating Z Variation

+ 5% - 5% % Z

Adjusted% Tap Setting

GT1 10.575 11.000 66.000 8.00 18.60 2.50 2.50 -7.0 7.4400 0 0

T2 10.575 11.000 66.000 8.00 18.60 2.50 2.50 -7.0 7.4400 0 0

T5 10.575 11.000 66.000 8.00 18.60 2.50 2.50 -7.0 7.4400 0 0

T6 10.000 66.000 11.000 8.00 15.50 2.50 2.50 -7.0 7.4400 0 0

T8 10.000 66.000 11.000 8.00 15.50 2.50 2.50 -7.0 7.4400 0 0

T10 10.000 66.000 11.000 8.00 15.50 2.50 2.50 -7.0 7.4400 0 0

Page 6: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 6

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

Branch Connections

ID From Bus To Bus R X ZType

CKT/Branch % Impedance, Pos. Seq., 100 MVAbConnected Bus ID

Y

GT1 Bus1 3.78 70.28 70.39Bus42W XFMR

T2 Bus7 3.78 70.28 70.39Bus82W XFMR

T5 Bus13 3.78 70.28 70.39Bus142W XFMR

T6 Bus16 4.79 74.28 74.43Bus172W XFMR

T8 Bus16 4.79 74.28 74.43Bus222W XFMR

T10 Bus16 4.79 74.28 74.43Bus242W XFMR

Line1 Bus15 4.59 1.84 4.95Bus16Line

2SW1 Bus4 Bus2Tie Switch

2SW3 Bus8 Bus2Tie Switch

2SW6 Bus14 Bus2Tie Switch

2SW7 Bus15 Bus2Tie Switch

Page 7: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 7

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

Synchronous Generator Input Data

IDID Type MVA kV RPM R Adj.

Synchronous Generator Rating

% Impedance in Machine Base

Connected Bus

% PF R/X Xd, sat Type

Excitation

Tol.

Xd"

1.000 1000 11.000 10.220Gen1 Hydro 19.00 0.05 155.00 Turbine 130%Bus1 85.00 0.0

1.000 1000 11.000 10.220Gen3 Hydro 19.00 0.05 155.00 Turbine 130%Bus7 85.00 0.0

1.000 1000 11.000 10.220Gen6 Hydro 19.00 0.05 155.00 Turbine 130%Bus13 85.00 0.0

Total Connected Synchronous Generators ( = 3 ) : 30.660 MVA

Page 8: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 8

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

Lumped Load Input Data

IDID kVA kV R R/X"X"

Lumped Load Rating Machine Base

kW kvar

Loading

MTR STAT

% Load

Lumped Load

Connected Bus

Motor Loads

Amp % PF

% Impedance

MW/PP

m Fact.

Lump1 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus17 0.00 2200.0 1496.0 927.1

Lump3 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus17 0.00 2200.0 1496.0 927.1

Lump4 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus17 0.00 2200.0 1496.0 927.1

Lump5 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus17 0.00 2200.0 1496.0 927.1

Lump6 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus17 0.00 2200.0 1496.0 927.1

Lump7 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus17 0.00 2200.0 1496.0 927.1

Lump15 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus22 0.00 2200.0 1496.0 927.1

Lump16 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus22 0.00 2200.0 1496.0 927.1

Lump17 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus22 0.00 2200.0 1496.0 927.1

Lump18 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus22 0.00 2200.0 1496.0 927.1

Lump19 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus22 0.00 2200.0 1496.0 927.1

Lump20 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus22 0.00 2200.0 1496.0 927.1

Lump27 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus24 0.00 2200.0 1496.0 927.1

Lump28 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus24 0.00 2200.0 1496.0 927.1

Lump29 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus24 0.00 2200.0 1496.0 927.1

Lump30 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus24 0.00 2200.0 1496.0 927.1

Lump31 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus24 0.00 2200.0 1496.0 927.1

Lump32 11.000 80 20 85.00 1.66 16.58 1.50 0.10Bus24 0.00 2200.0 1496.0 927.1

Total Connected Lumped Loads ( = 18 ): 39600.0 kVA

Page 9: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 9

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

SHORT-CIRCUIT REPORT

3-Phase fault at bus: Bus1

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

11.000

1.10

20.435

6.008

(User-Defined)

kA Method C

ID MagnitudeRatioRealFrom BusID Imaginary

From Bus To Bus % V kA kA X/R kA

Contribution Voltage & Initial Symmetrical Current (rms)

Bus1 Total 0.00 0.532 -7.912 14.9 7.929

Bus4 Bus1 58.86 0.369 -4.814 13.1 4.829

Gen1 Bus1 100.00 0.163 -3.097 19.0 3.101

Bus16 Bus15 60.06 0.055 -0.494 9.0 0.497

Bus13 Bus14 70.15 0.003 -0.154 49.0 0.154

Bus7 Bus8 70.15 0.003 -0.154 49.0 0.154

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

9.113 0.01 7.606 11.870

7.496 0.02 7.486 10.594

6.129 0.03 7.356 9.575

5.011 0.04 7.173 8.750

4.256 0.05 6.989 8.183

3.507 0.06 6.913 7.752

2.889 0.07 6.838 7.423

2.380 0.08 6.763 7.169

1.961 0.09 6.688 6.970

1.739 0.10 6.614 6.839

0.685 0.15 6.485 6.522

0.270 0.20 6.358 6.363

0.106 0.25 6.231 6.232

0.042 0.30 6.151 6.152

Page 10: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 10

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

3-Phase fault at bus: Bus2

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

66.000

1.10

5.764

0.482

(User-Defined)

kA Method C

ID MagnitudeRatioRealFrom BusID Imaginary

From Bus To Bus % V kA kA X/R kA

Contribution Voltage & Initial Symmetrical Current (rms)

Bus2 Total 0.00 0.232 -2.318 10.0 2.329

Bus16 Bus15 6.20 0.173 -1.194 6.9 1.206

Bus13 Bus14 27.44 0.020 -0.375 18.9 0.375

Bus7 Bus8 27.44 0.020 -0.375 18.9 0.375

Bus1 Bus4 27.44 0.020 -0.375 18.9 0.375

Bus17 Bus16 34.23 0.058 -0.398 6.9 0.402

Bus22 Bus16 34.23 0.058 -0.398 6.9 0.402

Bus24 Bus16 34.23 0.058 -0.398 6.9 0.402

Gen6 Bus13 100.00 0.119 -2.247 18.9 2.251

Gen3 Bus7 100.00 0.119 -2.247 18.9 2.251

Gen1 Bus1 100.00 0.119 -2.247 18.9 2.251

Bus4 Bus2 0.00 0.020 -0.375 18.9 0.375

Bus8 Bus2 0.00 0.020 -0.375 18.9 0.375

Bus14 Bus2 0.00 0.020 -0.375 18.9 0.375

Bus15 Bus2 0.00 0.173 -1.194 6.9 1.206

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

2.439 0.01 2.195 3.281

1.890 0.02 2.146 2.859

1.432 0.03 2.093 2.536

1.084 0.04 1.993 2.269

0.940 0.05 1.897 2.117

0.731 0.06 1.855 1.994

0.569 0.07 1.813 1.901

0.443 0.08 1.773 1.828

0.345 0.09 1.734 1.768

0.342 0.10 1.696 1.730

0.110 0.15 1.623 1.627

Page 11: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 11

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

(Cont.)

3-Phase fault at bus: Bus2

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

66.000

1.10

5.764

0.482

(User-Defined)

kA Method C

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

0.036 0.20 1.552 1.553

0.011 0.25 1.484 1.484

0.004 0.30 1.462 1.462

Page 12: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 12

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

3-Phase fault at bus: Bus4

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

66.000

1.10

5.764

0.482

(User-Defined)

kA Method C

ID MagnitudeRatioRealFrom BusID Imaginary

From Bus To Bus % V kA kA X/R kA

Contribution Voltage & Initial Symmetrical Current (rms)

Bus4 Total 0.00 0.232 -2.318 10.0 2.329

Bus1 Bus4 27.44 0.020 -0.375 18.9 0.375

Bus16 Bus15 6.20 0.173 -1.194 6.9 1.206

Bus13 Bus14 27.44 0.020 -0.375 18.9 0.375

Bus7 Bus8 27.44 0.020 -0.375 18.9 0.375

Gen1 Bus1 100.00 0.119 -2.247 18.9 2.251

Bus17 Bus16 34.23 0.058 -0.398 6.9 0.402

Bus22 Bus16 34.23 0.058 -0.398 6.9 0.402

Bus24 Bus16 34.23 0.058 -0.398 6.9 0.402

Gen6 Bus13 100.00 0.119 -2.247 18.9 2.251

Gen3 Bus7 100.00 0.119 -2.247 18.9 2.251

Bus2 Bus4 0.00 0.212 -1.943 9.1 1.955

Bus8 Bus2 0.00 0.020 -0.375 18.9 0.375

Bus14 Bus2 0.00 0.020 -0.375 18.9 0.375

Bus15 Bus2 0.00 0.173 -1.194 6.9 1.206

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

2.439 0.01 2.195 3.281

1.890 0.02 2.146 2.859

1.432 0.03 2.093 2.536

1.084 0.04 1.993 2.269

0.940 0.05 1.897 2.117

0.731 0.06 1.855 1.994

0.569 0.07 1.813 1.901

0.443 0.08 1.773 1.828

0.345 0.09 1.734 1.768

0.342 0.10 1.696 1.730

0.110 0.15 1.623 1.627

Page 13: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 13

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

(Cont.)

3-Phase fault at bus: Bus4

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

66.000

1.10

5.764

0.482

(User-Defined)

kA Method C

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

0.036 0.20 1.552 1.553

0.011 0.25 1.484 1.484

0.004 0.30 1.462 1.462

Page 14: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 14

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

3-Phase fault at bus: Bus7

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

11.000

1.10

20.435

6.008

(User-Defined)

kA Method C

ID MagnitudeRatioRealFrom BusID Imaginary

From Bus To Bus % V kA kA X/R kA

Contribution Voltage & Initial Symmetrical Current (rms)

Bus7 Total 0.00 0.532 -7.912 14.9 7.929

Bus8 Bus7 58.86 0.369 -4.814 13.1 4.829

Gen3 Bus7 100.00 0.163 -3.097 19.0 3.101

Bus16 Bus15 60.06 0.055 -0.494 9.0 0.497

Bus13 Bus14 70.15 0.003 -0.154 49.0 0.154

Bus1 Bus4 70.15 0.003 -0.154 49.0 0.154

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

9.113 0.01 7.606 11.870

7.496 0.02 7.486 10.594

6.129 0.03 7.356 9.575

5.011 0.04 7.173 8.750

4.256 0.05 6.989 8.183

3.507 0.06 6.913 7.752

2.889 0.07 6.838 7.423

2.380 0.08 6.763 7.169

1.961 0.09 6.688 6.970

1.739 0.10 6.614 6.839

0.685 0.15 6.485 6.522

0.270 0.20 6.358 6.363

0.106 0.25 6.231 6.232

0.042 0.30 6.151 6.152

Page 15: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 15

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

3-Phase fault at bus: Bus8

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

66.000

1.10

5.764

0.482

(User-Defined)

kA Method C

ID MagnitudeRatioRealFrom BusID Imaginary

From Bus To Bus % V kA kA X/R kA

Contribution Voltage & Initial Symmetrical Current (rms)

Bus8 Total 0.00 0.232 -2.318 10.0 2.329

Bus7 Bus8 27.44 0.020 -0.375 18.9 0.375

Bus16 Bus15 6.20 0.173 -1.194 6.9 1.206

Bus13 Bus14 27.44 0.020 -0.375 18.9 0.375

Bus1 Bus4 27.44 0.020 -0.375 18.9 0.375

Gen3 Bus7 100.00 0.119 -2.247 18.9 2.251

Bus17 Bus16 34.23 0.058 -0.398 6.9 0.402

Bus22 Bus16 34.23 0.058 -0.398 6.9 0.402

Bus24 Bus16 34.23 0.058 -0.398 6.9 0.402

Gen6 Bus13 100.00 0.119 -2.247 18.9 2.251

Gen1 Bus1 100.00 0.119 -2.247 18.9 2.251

Bus4 Bus2 0.00 0.020 -0.375 18.9 0.375

Bus2 Bus8 0.00 0.212 -1.943 9.1 1.955

Bus14 Bus2 0.00 0.020 -0.375 18.9 0.375

Bus15 Bus2 0.00 0.173 -1.194 6.9 1.206

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

2.439 0.01 2.195 3.281

1.890 0.02 2.146 2.859

1.432 0.03 2.093 2.536

1.084 0.04 1.993 2.269

0.940 0.05 1.897 2.117

0.731 0.06 1.855 1.994

0.569 0.07 1.813 1.901

0.443 0.08 1.773 1.828

0.345 0.09 1.734 1.768

0.342 0.10 1.696 1.730

0.110 0.15 1.623 1.627

Page 16: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 16

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

(Cont.)

3-Phase fault at bus: Bus8

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

66.000

1.10

5.764

0.482

(User-Defined)

kA Method C

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

0.036 0.20 1.552 1.553

0.011 0.25 1.484 1.484

0.004 0.30 1.462 1.462

Page 17: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 17

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

3-Phase fault at bus: Bus13

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

11.000

1.10

20.435

6.008

(User-Defined)

kA Method C

ID MagnitudeRatioRealFrom BusID Imaginary

From Bus To Bus % V kA kA X/R kA

Contribution Voltage & Initial Symmetrical Current (rms)

Bus13 Total 0.00 0.532 -7.912 14.9 7.929

Bus14 Bus13 58.86 0.369 -4.814 13.1 4.829

Gen6 Bus13 100.00 0.163 -3.097 19.0 3.101

Bus16 Bus15 60.06 0.055 -0.494 9.0 0.497

Bus7 Bus8 70.15 0.003 -0.154 49.0 0.154

Bus1 Bus4 70.15 0.003 -0.154 49.0 0.154

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

9.113 0.01 7.606 11.870

7.496 0.02 7.486 10.594

6.129 0.03 7.356 9.575

5.011 0.04 7.173 8.750

4.256 0.05 6.989 8.183

3.507 0.06 6.913 7.752

2.889 0.07 6.838 7.423

2.380 0.08 6.763 7.169

1.961 0.09 6.688 6.970

1.739 0.10 6.614 6.839

0.685 0.15 6.485 6.522

0.270 0.20 6.358 6.363

0.106 0.25 6.231 6.232

0.042 0.30 6.151 6.152

Page 18: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 18

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

3-Phase fault at bus: Bus14

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

66.000

1.10

5.764

0.482

(User-Defined)

kA Method C

ID MagnitudeRatioRealFrom BusID Imaginary

From Bus To Bus % V kA kA X/R kA

Contribution Voltage & Initial Symmetrical Current (rms)

Bus14 Total 0.00 0.232 -2.318 10.0 2.329

Bus13 Bus14 27.44 0.020 -0.375 18.9 0.375

Bus16 Bus15 6.20 0.173 -1.194 6.9 1.206

Bus7 Bus8 27.44 0.020 -0.375 18.9 0.375

Bus1 Bus4 27.44 0.020 -0.375 18.9 0.375

Gen6 Bus13 100.00 0.119 -2.247 18.9 2.251

Bus17 Bus16 34.23 0.058 -0.398 6.9 0.402

Bus22 Bus16 34.23 0.058 -0.398 6.9 0.402

Bus24 Bus16 34.23 0.058 -0.398 6.9 0.402

Gen3 Bus7 100.00 0.119 -2.247 18.9 2.251

Gen1 Bus1 100.00 0.119 -2.247 18.9 2.251

Bus4 Bus2 0.00 0.020 -0.375 18.9 0.375

Bus8 Bus2 0.00 0.020 -0.375 18.9 0.375

Bus2 Bus14 0.00 0.212 -1.943 9.1 1.955

Bus15 Bus2 0.00 0.173 -1.194 6.9 1.206

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

2.439 0.01 2.195 3.281

1.890 0.02 2.146 2.859

1.432 0.03 2.093 2.536

1.084 0.04 1.993 2.269

0.940 0.05 1.897 2.117

0.731 0.06 1.855 1.994

0.569 0.07 1.813 1.901

0.443 0.08 1.773 1.828

0.345 0.09 1.734 1.768

0.342 0.10 1.696 1.730

0.110 0.15 1.623 1.627

Page 19: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 19

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

(Cont.)

3-Phase fault at bus: Bus14

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

66.000

1.10

5.764

0.482

(User-Defined)

kA Method C

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

0.036 0.20 1.552 1.553

0.011 0.25 1.484 1.484

0.004 0.30 1.462 1.462

Page 20: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 20

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

3-Phase fault at bus: Bus15

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

66.000

1.10

5.764

0.482

(User-Defined)

kA Method C

ID MagnitudeRatioRealFrom BusID Imaginary

From Bus To Bus % V kA kA X/R kA

Contribution Voltage & Initial Symmetrical Current (rms)

Bus15 Total 0.00 0.232 -2.318 10.0 2.329

Bus16 Bus15 6.20 0.173 -1.194 6.9 1.206

Bus13 Bus14 27.44 0.020 -0.375 18.9 0.375

Bus7 Bus8 27.44 0.020 -0.375 18.9 0.375

Bus1 Bus4 27.44 0.020 -0.375 18.9 0.375

Bus17 Bus16 34.23 0.058 -0.398 6.9 0.402

Bus22 Bus16 34.23 0.058 -0.398 6.9 0.402

Bus24 Bus16 34.23 0.058 -0.398 6.9 0.402

Gen6 Bus13 100.00 0.119 -2.247 18.9 2.251

Gen3 Bus7 100.00 0.119 -2.247 18.9 2.251

Gen1 Bus1 100.00 0.119 -2.247 18.9 2.251

Bus4 Bus2 0.00 0.020 -0.375 18.9 0.375

Bus8 Bus2 0.00 0.020 -0.375 18.9 0.375

Bus14 Bus2 0.00 0.020 -0.375 18.9 0.375

Bus2 Bus15 0.00 0.059 -1.124 18.9 1.125

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

2.439 0.01 2.195 3.281

1.890 0.02 2.146 2.859

1.432 0.03 2.093 2.536

1.084 0.04 1.993 2.269

0.940 0.05 1.897 2.117

0.731 0.06 1.855 1.994

0.569 0.07 1.813 1.901

0.443 0.08 1.773 1.828

0.345 0.09 1.734 1.768

0.342 0.10 1.696 1.730

0.110 0.15 1.623 1.627

Page 21: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 21

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

(Cont.)

3-Phase fault at bus: Bus15

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

66.000

1.10

5.764

0.482

(User-Defined)

kA Method C

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

0.036 0.20 1.552 1.553

0.011 0.25 1.484 1.484

0.004 0.30 1.462 1.462

Page 22: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 22

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

3-Phase fault at bus: Bus16

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

66.000

1.10

5.808

1.097

(User-Defined)

kA Method C

ID MagnitudeRatioRealFrom BusID Imaginary

From Bus To Bus % V kA kA X/R kA

Contribution Voltage & Initial Symmetrical Current (rms)

Bus16 Total 0.00 0.224 -2.329 10.4 2.340

Bus15 Bus16 5.64 0.114 -1.091 9.6 1.097

Bus17 Bus16 32.05 0.037 -0.413 11.3 0.414

Bus22 Bus16 32.05 0.037 -0.413 11.3 0.414

Bus24 Bus16 32.05 0.037 -0.413 11.3 0.414

Bus13 Bus14 29.57 0.038 -0.364 9.6 0.366

Bus7 Bus8 29.57 0.038 -0.364 9.6 0.366

Bus1 Bus4 29.57 0.038 -0.364 9.6 0.366

Lump1 Bus17 100.00 0.037 -0.413 11.3 0.414

Lump3 Bus17 100.00 0.037 -0.413 11.3 0.414

Lump4 Bus17 100.00 0.037 -0.413 11.3 0.414

Lump5 Bus17 100.00 0.037 -0.413 11.3 0.414

Lump6 Bus17 100.00 0.037 -0.413 11.3 0.414

Lump7 Bus17 100.00 0.037 -0.413 11.3 0.414

Lump15 Bus22 100.00 0.037 -0.413 11.3 0.414

Lump16 Bus22 100.00 0.037 -0.413 11.3 0.414

Lump17 Bus22 100.00 0.037 -0.413 11.3 0.414

Lump18 Bus22 100.00 0.037 -0.413 11.3 0.414

Lump19 Bus22 100.00 0.037 -0.413 11.3 0.414

Lump20 Bus22 100.00 0.037 -0.413 11.3 0.414

Lump27 Bus24 100.00 0.037 -0.413 11.3 0.414

Lump28 Bus24 100.00 0.037 -0.413 11.3 0.414

Lump29 Bus24 100.00 0.037 -0.413 11.3 0.414

Lump30 Bus24 100.00 0.037 -0.413 11.3 0.414

Lump31 Bus24 100.00 0.037 -0.413 11.3 0.414

Lump32 Bus24 100.00 0.037 -0.413 11.3 0.414

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

Page 23: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 23

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

(Cont.)

3-Phase fault at bus: Bus16

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

66.000

1.10

5.808

1.097

(User-Defined)

kA Method C

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

2.449 0.01 2.202 3.293

1.814 0.02 2.152 2.815

1.343 0.03 2.099 2.492

0.995 0.04 1.994 2.228

0.740 0.05 1.893 2.033

0.548 0.06 1.849 1.928

0.406 0.07 1.805 1.850

0.301 0.08 1.763 1.789

0.223 0.09 1.722 1.736

0.167 0.10 1.682 1.690

0.037 0.15 1.605 1.606

0.008 0.20 1.531 1.531

0.002 0.25 1.459 1.459

0.000 0.30 1.438 1.438

Page 24: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 24

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

3-Phase fault at bus: Bus17

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

11.000

1.10

20.820

3.562

(User-Defined)

kA Method C

ID MagnitudeRatioRealFrom BusID Imaginary

From Bus To Bus % V kA kA X/R kA

Contribution Voltage & Initial Symmetrical Current (rms)

Bus17 Total 0.00 0.724 -8.268 11.4 8.299

Bus16 Bus17 59.84 0.360 -4.628 12.9 4.642

Lump1 Bus17 100.00 0.061 -0.607 10.0 0.610

Lump3 Bus17 100.00 0.061 -0.607 10.0 0.610

Lump4 Bus17 100.00 0.061 -0.607 10.0 0.610

Lump5 Bus17 100.00 0.061 -0.607 10.0 0.610

Lump6 Bus17 100.00 0.061 -0.607 10.0 0.610

Lump7 Bus17 100.00 0.061 -0.607 10.0 0.610

Bus15 Bus16 60.86 0.037 -0.439 11.8 0.441

Bus22 Bus16 72.72 0.011 -0.166 14.5 0.166

Bus24 Bus16 72.72 0.011 -0.166 14.5 0.166

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

8.922 0.01 7.814 11.860

6.802 0.02 7.634 10.225

5.179 0.03 7.449 9.072

3.942 0.04 7.019 8.050

3.033 0.05 6.618 7.280

2.314 0.06 6.429 6.833

1.765 0.07 6.247 6.492

1.347 0.08 6.072 6.219

1.027 0.09 5.903 5.992

0.802 0.10 5.741 5.797

0.209 0.15 5.427 5.431

0.055 0.20 5.131 5.131

0.014 0.25 4.853 4.853

0.004 0.30 4.828 4.828

Page 25: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 25

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

3-Phase fault at bus: Bus22

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

11.000

1.10

20.820

3.562

(User-Defined)

kA Method C

ID MagnitudeRatioRealFrom BusID Imaginary

From Bus To Bus % V kA kA X/R kA

Contribution Voltage & Initial Symmetrical Current (rms)

Bus22 Total 0.00 0.724 -8.268 11.4 8.299

Bus16 Bus22 59.84 0.360 -4.628 12.9 4.642

Lump15 Bus22 100.00 0.061 -0.607 10.0 0.610

Lump16 Bus22 100.00 0.061 -0.607 10.0 0.610

Lump17 Bus22 100.00 0.061 -0.607 10.0 0.610

Lump18 Bus22 100.00 0.061 -0.607 10.0 0.610

Lump19 Bus22 100.00 0.061 -0.607 10.0 0.610

Lump20 Bus22 100.00 0.061 -0.607 10.0 0.610

Bus15 Bus16 60.86 0.037 -0.439 11.8 0.441

Bus17 Bus16 72.72 0.011 -0.166 14.5 0.166

Bus24 Bus16 72.72 0.011 -0.166 14.5 0.166

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

8.922 0.01 7.814 11.860

6.802 0.02 7.634 10.225

5.179 0.03 7.449 9.072

3.942 0.04 7.019 8.050

3.033 0.05 6.618 7.280

2.314 0.06 6.429 6.833

1.765 0.07 6.247 6.492

1.347 0.08 6.072 6.219

1.027 0.09 5.903 5.992

0.802 0.10 5.741 5.797

0.209 0.15 5.427 5.431

0.055 0.20 5.131 5.131

0.014 0.25 4.853 4.853

0.004 0.30 4.828 4.828

Page 26: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 26

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

3-Phase fault at bus: Bus24

kA rms

Nominal kV

Voltage c Factor

Peak Value

Steady State

=

=

=

=

11.000

1.10

20.820

3.562

(User-Defined)

kA Method C

ID MagnitudeRatioRealFrom BusID Imaginary

From Bus To Bus % V kA kA X/R kA

Contribution Voltage & Initial Symmetrical Current (rms)

Bus24 Total 0.00 0.724 -8.268 11.4 8.299

Bus16 Bus24 59.84 0.360 -4.628 12.9 4.642

Lump27 Bus24 100.00 0.061 -0.607 10.0 0.610

Lump28 Bus24 100.00 0.061 -0.607 10.0 0.610

Lump29 Bus24 100.00 0.061 -0.607 10.0 0.610

Lump30 Bus24 100.00 0.061 -0.607 10.0 0.610

Lump31 Bus24 100.00 0.061 -0.607 10.0 0.610

Lump32 Bus24 100.00 0.061 -0.607 10.0 0.610

Bus15 Bus16 60.86 0.037 -0.439 11.8 0.441

Bus17 Bus16 72.72 0.011 -0.166 14.5 0.166

Bus22 Bus16 72.72 0.011 -0.166 14.5 0.166

Breaking and DC Fault Current (kA)

TD (S) Ib sym Idc

Based on Total Bus Fault Current

Ib asym

8.922 0.01 7.814 11.860

6.802 0.02 7.634 10.225

5.179 0.03 7.449 9.072

3.942 0.04 7.019 8.050

3.033 0.05 6.618 7.280

2.314 0.06 6.429 6.833

1.765 0.07 6.247 6.492

1.347 0.08 6.072 6.219

1.027 0.09 5.903 5.992

0.802 0.10 5.741 5.797

0.209 0.15 5.427 5.431

0.055 0.20 5.131 5.131

0.014 0.25 4.853 4.853

0.004 0.30 4.828 4.828

Page 27: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 27

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

Short-Circuit Summary Report

3-Phase Fault Currents

ID Ib sym Ib asymipI"kIb asymPeakTypeIDkV

Device Capacity (kA)

Idc

DeviceBus Short-Circuit Current (kA)

Ib sym Idc Ik

Making

Bus1 Bus1 Bus 7.929 20.435 6.008 11.000

6.951GCB1 CB 80.000 13.123 7.929 20.435 3.863 11.000 34.124 31.500 7.952

Bus2 Bus2 Bus 2.329 5.764 0.482 66.000

Bus4 Bus4 Bus 2.329 5.764 0.482 66.000

1.876CB4 CB 80.000 13.123 2.329 5.764 0.829 66.000 34.124 31.500 2.051

Bus7 Bus7 Bus 7.929 20.435 6.008 11.000

6.951CB7 CB 80.000 13.123 7.929 20.435 3.863 11.000 34.124 31.500 7.952

Bus8 Bus8 Bus 2.329 5.764 0.482 66.000

1.876CB8 CB 80.000 13.123 2.329 5.764 0.829 66.000 34.124 31.500 2.051

Bus13 Bus13 Bus 7.929 20.435 6.008 11.000

6.951CB13 CB 80.000 13.123 7.929 20.435 3.863 11.000 34.124 31.500 7.952

Bus14 Bus14 Bus 2.329 5.764 0.482 66.000

1.876CB14 CB 80.000 13.123 2.329 5.764 0.829 66.000 34.124 31.500 2.051

Bus15 Bus15 Bus 2.329 5.764 0.482 66.000

Bus16 Bus16 Bus 2.340 5.808 1.097 66.000

1.871CB17 CB 63.000 10.415 2.340 5.808 0.637 66.000 27.083 25.000 1.976

1.871CB29 CB 63.000 10.415 2.340 5.808 0.637 66.000 27.083 25.000 1.976

1.871CB25 CB 63.000 10.415 2.340 5.808 0.637 66.000 27.083 25.000 1.976

Bus17 Bus17 Bus 8.299 20.820 3.562 11.000

7.814CB21 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB31 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB33 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB34 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB35 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB37 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB36 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

Bus22 Bus22 Bus 8.299 20.820 3.562 11.000

7.814CB45 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB46 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB47 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB48 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB49 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB50 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB24 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

Bus24 Bus24 Bus 8.299 20.820 3.562 11.000

Page 28: System Analysis

Location:

Engineer:Study Case: SC

7.0.0

Page: 28

SN: 12345678

Filename: 26MW Shagharthang HPP

Project: ETAP

Contract:

Date: 01-02-2012

Revision: Base

Config.: Normal

3-Phase Fault Currents

ID Ib sym Ib asymipI"kIb asymPeakTypeIDkV

Device Capacity (kA)

Idc

DeviceBus Short-Circuit Current (kA)

Ib sym Idc Ik

Making

7.814Bus24 CB57 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB58 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB59 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB60 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB61 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB62 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

7.814CB28 CB 0.000 28.310 8.299 20.820 8.922* 11.000 37.769 25.000 11.860

ip is calculated using method C

Ib does not include decay of non-terminal faulted indunction motors

Ik is the maximum steady state fault current

Idc is based on X/R from Method C and Ib as specified above

LV CB duty determined based on service rating.

Total through current is used for device duty.

* Indicates a device with calculated duty exceeding the device capability.

# Indicates a device with calculated duty exceeding the device marginal limit . ( 95 % times device capability)