system 450™ series modular controls -...

82
1 System 450™ Series Modular Controls Technical Bulletin Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 System 450 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Standard Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 High Input Select and Hybrid Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Reset Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Control Modules and User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Expansion Modules, Module Assemblies, and Outputs . . . . . . . . . . . . . . . . . . . . . . . . 14 Module Assemblies and Output Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Direct and Reverse Control Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Hybrid Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Proportional Plus Integral Control and Integration Constants . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 System 450 Compatible Sensors and Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Standard Control Module Sensors and Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Reset Control Module Sensors and Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Sensor Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 System 450 Standard Control System Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 High Input Signal Selection System Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 System 450 Reset Control System Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Modes of Operation for Reset Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Load Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Detailed Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Designing and Building System 450 Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . 31 System 450™ Series Modular Controls Technical Bulletin Code No. LIT-12011459 Issued February 3, 2011 Supersedes November 19, 2010

Upload: hoangkiet

Post on 20-May-2019

219 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

System 450™ Series Modular ControlsTechnical Bulletin

Code No. LIT-12011459Issued February 3, 2011

Supersedes November 19, 2010

Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

System 450 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Standard Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

High Input Select and Hybrid Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Reset Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Control Modules and User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Expansion Modules, Module Assemblies, and Outputs . . . . . . . . . . . . . . . . . . . . . . . . 14

Module Assemblies and Output Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Direct and Reverse Control Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Hybrid Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Proportional Plus Integral Control and Integration Constants . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

System 450 Compatible Sensors and Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Standard Control Module Sensors and Transducers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Reset Control Module Sensors and Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Sensor Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

System 450 Standard Control System Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

High Input Signal Selection System Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

System 450 Reset Control System Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Modes of Operation for Reset Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Load Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Detailed Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Designing and Building System 450 Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . 31

1System 450™ Series Modular Controls Technical Bulletin

Page 2: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Selecting Input Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Assembling System 450 Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Installing System 450 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Locating System 450 Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Wiring System 450 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Wiring System 450 Sensors and Transducers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Setting up a System 450 Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Determining Output Numbers and Output Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Accessing and Navigating the User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Viewing the System Status Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Accessing the System Setup Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Setting up the Input Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Setting up Standard Control Module Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

Setting up a Relay Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

Setting up an Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

Setting up a Pulse Region Hybrid Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Determining the Integration Constant for an Analog Output . . . . . . . . . . . . . . . . . . . . . . . . 49

Testing the Slowest to Fastest Time Integral to Determine I-C Setting . . . . . . . . . . . . . . . . . . . . 49

Using the Response Time to a Step Change to Determine the I-C Setting . . . . . . . . . . . . . . . . . 50

Setting up Reset Control Module Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Setting up the Temperature or Humidity Reset Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Setting up the Reset Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

Setting up a Standard Relay Output with Unoccupied Setback. . . . . . . . . . . . . . . . . . . . . . 57

Setting up a Standard Analog Output with Unoccupied Setback. . . . . . . . . . . . . . . . . . . . . 61

Setting up a Relay Output with Temperature Reset Control and Unoccupied Setback. . . . 64

Setting up an Analog Output with Reset Setpoint Control and Unoccupied Setback . . . . . 66

Setting Time and Day . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

Setting up an Occupied/Unoccupied Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

Occupied/Unoccupied Setback Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

Relay Output That References an Input Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

System 450™ Series Modular Controls Technical Bulletin2

Page 3: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Analog Output That References an Input Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

Relay Output and Analog Output That Reference the Reset Function . . . . . . . . . . . . . . . . . 70

Multi-stage Cooling That References the Reset Function and Load Balancing Is Set to One 70

Multi-stage Cooling That References the Reset Function and Load Balancing Is Set to One 70

Troubleshooting System 450 Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

Specified Voltage Ranges for Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

Repair Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

C450Cxx Control Modules with Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

C450CxN Control Modules with Relay Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

C450RxN Reset Control Modules with Relay Output . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

C450SxN Analog Output Expansion Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

C450SxN Relay Output Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

C450YNN Power Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

System 450™ Series Modular Controls Technical Bulletin 3

Page 4: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

System 450™ Series Modular Controls Technical Bulletin4

Page 5: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

No.458

549

4-7664-2675

4-7664-2772

4-7664-2802

4-7664-2683

Document IntroductionThe System 450™ Series of modular controls is designed to provide compact, cost-effective, customizable, and accurate digital control for a wide variety of Heating, Ventilating, Air Conditioning, and Refrigeration (HVACR), and commercial/industrial process applications.

This document describes System 450 features and functions, and provides guidelines and instructions for designing, selecting, installing, setting up, and troubleshooting System 450 components and control systems.

This document also provides System 450 Technical Specifications on page 78 and references to System 450 Related Documentation.

Note: In this document, control module refers to the standard System 450 Control Module (C450CxN-1 models), the System 450 Reset Control Module (C450RxN-1 models), or the System 450 Hybrid Analog Output and High Input Signal Selection Control Module (C450CPW-100), unless noted otherwise.

Related DocumentationTable 1 provides references to System 450 related documentation, including input sensor installation instructions. Table 1: Related DocumentationFor More Information On See LIT/PartSystem 450 Series Features, Benefits, Models, and Technical Specifications

System 450 Series Modular Control Product Bulletin

LIT-12011

System 450 Series Features, Benefits, Models, and Technical Specifications

System 450 Series Modular Control Catalog Page

LIT-1900

Installing, Wiring, and Setting up System 450 Control Modules with Relay Output

System 450 Series Control Modules with Relay Outputs Installation Instructions

Part No. 2

Installing, Wiring, and Setting up System 450 Reset Control Modules with Real-Time Clock and Relay Output

System 450 Series Reset Control Modules with Real-Time Clock and Relay Output Installation Instructions

Part No. 2

Installing, Wiring, and Setting up System 450 Control Modules with Hybrid Analog Output and High Input Signal Selection

System 450™ Series Control Module with Hybrid Analog Output and High Input Signal Selection Installation Instructions

Part No. 2

Installing and Wiring System 450 Expansion Modules with Relay Output

System 450 Series Expansion Modules with Relay Outputs Installation Instructions

Part No. 2

5

Page 6: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

4-7664-2691

64-7664-1636

1904-7664-2659

4-9527-7

uickLIT nformation for Setra odel 265.

No.

Installing and Wiring the System 450 Power Module

System 450 Series Power Module Installation Instructions

Part No. 2

Installing and Wiring the A99 Series Temperature Sensors

A99B Series Temperature Sensors Product/Technical Bulletin

LIT-12518Part No. 2

Installing and Wiring the P499 Series Electronic Pressure Transducers

P499 Series Electronic Pressure Transducers Product/Technical Bulletin

LIT-12011Part No. 2

Installing and Wiring the HE-67xx Humidity Sensors and Humidity with Temperature Sensors

TrueRH Series HE-67xx Humidity Element with Temperature Sensor Installation Instructions

Part No. 2

Installing and Wiring Setra Systems Model 265 Differential Pressure Transducers

Setra Systems Model 265 Differential Pressure Transducer Installation Guide

Search QProduct IWeb SiteSystem M

Table 1: Related DocumentationFor More Information On See LIT/Part

6

Page 7: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

System 450 OverviewThe System 450 Series is a family of compact digital electronic control, expansion, and power modules that are easily assembled and set up to provide reliable on/off and proportional control of temperature, pressure, and humidity conditions in a wide variety of HVACR and commercial/industrial process applications.

The System 450 Series is designed to replace System 350 Series and System 27 Series control systems and provides more features and greater flexibility with far fewer model variations. Most System 350 and System 27 modules are designed for single purpose applications (either temperature, pressure, or humidity) and cannot be assembled and configured to control multiple conditions in a controlled system.

The System 450 Series has several model variations; each module is designed to be multi-purpose, adaptable, and completely field configurable for temperature, pressure, and humidity applications. The System 450 Series allows you to build a wide range of inexpensive, compact, durable, and versatile custom control systems that allow you to monitor and control multiple control loops in your controlled system. A single System 450 control system can monitor and control temperature, pressure, and humidity simultaneously.

Note: System 450 modules are not compatible with System 350 or System 27 modules, but you can build all of the System 350 and System 27 control systems and many more with System 450 modules, usually with fewer modules.

The characteristics of the System 450 Series family of controls include:

• a single System 450 control module, which provides the control system User Interface (UI) for setting up, monitoring, and controlling your system and the sensor wiring interface for connecting the input sensors

• one to three input sensors, which connect directly to the control module and provide input signals for monitoring the control loops in your controlled system

• one to ten outputs provided by the control module and expansion modules. Each output provides either on/off control or a proportional analog signal (0–10 VDC or 4–20 mA) to the equipment in your controlled system.

• an optional power module to provide power to the connected control module and expansion modules

See Table 10 on page 74 for a complete list of System 450 modules.

Standard ControlStandard control in the System 450 Series family uses the standard control module (C450CxN-1 models). The standard control module provides:

• Relay (on/off) and analog control of pressure, temperature, and/or humidity applications

• Simultaneous control of pressure, temperature, and humidity

7

Page 8: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

• On/Off stage control

• Proportional plus Integral (PI) control

The standard module does not include reset control, scheduling, or load balancing capabilities. These features are available with the reset control module.

High Input Select and Hybrid Analog OutputThe C450CPW-100 model is a hybrid analog output control module with Liquid Crystal Display (LCD) and four-button touchpad User Interface (UI) that allows you to set up a System 450 control system. This model uses the same hardware and setup screens as the C450CPN-1, but adds two new functions:

• the ability to use the highest of two or three sensor inputs (High Input Signal selection)

• the ability to configure a hybrid Analog Output (AO) to transition between a pulse output and a standard VDC output, depending on the sensor value relative to the proportional band. At low output levels, the pulse output signal provides an average motor speed that is less than the EC motor’s fixed minimum speed.

Note: This model was designed for (but is not limited to) controlling an EC motor. By using temperature, humidity, or pressure sensor inputs, this control can be used for a wide range of applications.

Reset ControlReset control in the System 450 Series family uses the reset control module (C450RxN-1 models). In addition to all the capabilities of the standard control module, the reset control module also provides:

• reset setpoint control of humidity and temperature applications (no pressure control available)

• a real-time clock used to configure temperature or humidity setback based on an occupancy schedule

• load balancing of controlled equipment with relay outputs (equalizes runtime)

To enable reset control of an output, you select a special reference sensor called the Reset Sensor (rES). When you set up an output, you select the rES sensor, which causes the output to use RSP as its setpoint and use Sn-2 as the sensor input to control the process variable. This process is detailed later in Setting up the Reset Setpoint on page 54.

8

Page 9: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Displays a the Outpute Status or een. Outputtermined by (left to right)utput 4.)

whether ancreases asd whether theimum oroperty is aton displayedsetup values).

Green LEDsnsion Modulese or Off.

fault screens, ystem statusess to save go to the

Control Modules and User InterfaceEach System 450 control system requires a single control module. System 450 control modules have a Liquid Crystal Display (LCD) that allows you to monitor the controlled system, along with a four-button touchpad for navigating the control system status and setup screens, and setting the system parameters.

System 450 control modules are available with one or two relay outputs or with one or two analog outputs. You set up all of the relay and analog outputs in your control system in any control module UI.

A control module can also be configured as a simple stand-alone control system when your application requires only one or two relay outputs or one or two analog outputs.

During normal operation, the LCD displays the Main (default) System 450 screens, which automatically scroll through and display the status of the sensors in your control system. You can easily view output status and access the System 450 setup interface from the Main screens. See Accessing and Navigating the User Interface.

The System 450 Output Status screens display the status of each output in the control system. A relay output status is displayed as ON or OFF. An analog output status is displayed as a percentage of the total output signal strength (0–100%).

The setup screens in the System 450 UI enable you to set up the control sensors and all of the outputs in the control system. See Figure 2, Figure 3, Figure 4, Figure 5, and Setting up a System 450 Control System.

Figure 1: System 450 Control Module with Relay Outputs Showing LCD andFour-Button touchpad User Interface

Output (or Sensor) Number:

4

numerical value that identifies(or Sensor) associated with thSetup Value shown on the scrNumbers are automatically dethe outputs' physical positionsin the module assembly. ( = O

Control Ramp Icon: DisplaysAnalog Output increases or dethe sensor input increases, anoutput signal strength is at minmaximum when the sensed prSetpoint. The Control Ramp icis determined by the Output's (SP, EP, Pb, OSET, OSP, OEP

MENU Button: Press to move through thesensor and output setup-start-screens.When moving through the status or setup screens, press to return to the status startscreen or setup start screen.

M

M

Status or Setup Identifier:

or OSP

Displays theunit of measurement, output, sensor number,

setup parameter for the displayed Status orSetup Value. (Setup Identifier represents% Output Signal Strength at Setpoint.)

UP and DOWN Buttons: Press or to selecta different value for any flashing value in theSetup Value field. In the Main/Default (SensorStatus) screen, press and hold both and for 5 seconds to access the Setup Start screens.

Status or Setup Value:

Displays the currentinput status, output status, or setup parametervalue for the displayed input sensor or output.

ParameterValue when the value is flashing.

Press or to adjust the

M

OSP 4

Light-Emitting Diode (LED):on Control Modules and Expawith relays (only) indicate if thassociated Relay Output is On

FIG:sys450_rst_cntrl_m

odul

NEXT Button: In the Main/Depress to scroll through the sscreens. In a setup screen, prthe (flashing) Setup Value andnext setup screen.

9

Page 10: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

e

Figure 2: C450CxN-1 Standard Control Module and C450SxN-1 Expansion ModulStatus and Setup Screen Example (See Also Figure 9.)

10

Page 11: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Setup Screens

Figure 3: C450CPW-100 Control Module and C450SBN-1 Expansion Module Status and Example

11

Page 12: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

sim

ulta

neou

sly

to re

turn

to th

e M

ain

scre

ens.

Figure 4: C450RxN-1 Reset Control Module and C450SxN-1 ExpansionStatus and Setup Screen Example

(See also Figure 14, Figure 29, and Figure 35.)

OU

T O

UT

Mai

nSc

reen

s

Syst

em S

tatu

sSc

reen

s

Sens

or S

etup

Star

t Scr

eens

Res

et S

etpo

int

Setu

p St

art S

cree

nsB

oile

r Wat

er T

empe

ratu

re

Rel

ay O

utpu

t with

RSP

Setu

p St

art S

cree

nsB

oile

r 1 R

eset

- O

n/O

ff

Rel

ay O

utpu

t with

RSP

Se

tup

Star

t Scr

eens

Boile

r 2 R

eset

- O

n/O

ff

Rel

ay O

utpu

t with

RSP

Se

tup

Star

t Scr

eens

B

oile

r 3 R

eset

- O

n/O

ff

Tim

e an

d D

ay C

lock

Setu

p St

art S

cree

ns

Occ

upie

d/U

nocc

upie

dSc

hedu

le S

etup

Star

t Scr

eens

Not

e: A

fter 2

min

utes

of i

nact

ivity

in a

ny s

cree

n,th

e di

spla

y re

turn

s to

the

Mai

n sc

reen

s.

FF

TUE

RS

P

The

Mai

n sc

reen

s au

to-s

crol

ldu

ring

norm

al o

pera

tion.

Pres

s

re

peat

edly

to s

crol

l thr

ough

all M

ain

and

Syst

em S

tatu

s sc

reen

s.

Press repeatedly to scroll through the System Setup Start screens*

*Not

e: In

any

Set

up S

tart

scre

en, P

ress

a

nd

Not

e:re

quire

d on

ly T

ime

and

Day

, and

Occ

upie

d/U

nocc

upie

d S

ched

ule

can

be s

et u

p fo

r any

con

trol

syst

em, b

ut a

re

for c

ontro

l sys

tem

s th

at u

se th

e Se

tbac

k (S

bK) f

eatu

re.

Pres

s

to

scro

ll th

roug

h an

d se

t up

each

occ

upie

d/un

occu

pied

sc

hedu

le s

cree

n.

Pres

s

and

sim

ulta

neou

sly

and

h

old

5 se

cond

s

to g

o to

the

S

enso

r Set

up

Sta

rt sc

reen

.

FIG

:sys

450_

rst_

mnu

_flw

chrt

OFF

T

Stan

dard

Rel

ay O

utpu

t Se

tup

Star

t Scr

eens

Boile

r Circ

ulat

ion

Pum

p - O

n/O

ff

Afte

r you

mak

e a

chan

ge to

a S

etup

Sta

rt sc

reen

, pre

ss

to

sav

e th

e ch

ange

.

To re

set h

ours

(HR

S),

hold

dow

n th

e

k

eyfo

r 5 s

econ

ds.

n

OC

-1A

M

- -

- -

12

Page 13: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Figure 5: C450RBN-1 and C450CQN-1 Control Modules - Chilled Water Reset with Vent Cooling Status and Setup Screen Example

(See also Figure 12, Figure 29, and Figure 36.)

OU

T

Mai

nSc

reen

s

Syst

em S

tatu

sSc

reen

s

Sens

or S

etup

Star

t Scr

eens

Res

et S

etpo

int

Setu

p St

art S

cree

nsC

hille

r Wat

er T

empe

ratu

re

Rel

ay O

utpu

tSe

tup

Star

t Scr

eens

Enab

le V

ent C

oolin

g <

55°F

Ana

log

Out

put w

ith R

SP

Setu

p St

art S

cree

nsC

hille

r Res

et -

Mod

ulat

ing

Valv

e

Ana

log

Out

put w

ith R

SP

Setu

p St

art S

cree

ns

Mod

ulat

e Ve

nt -

Dam

per/C

oolin

g

Tim

e an

d D

ay C

lock

Setu

p St

art S

cree

ns

Occ

upie

d/U

nocc

upie

dSc

hedu

le S

etup

Star

t Scr

eens

Not

e: A

fter 2

min

utes

of

inac

tivity

in a

ny s

cree

n,th

e di

spla

y re

turn

s to

the

Mai

n sc

reen

s.

FF

TUE

The

Mai

n sc

reen

s au

to-s

crol

ldu

ring

norm

al o

pera

tion.

Pre

ss

r

epea

tedl

y to

scr

oll t

hrou

ghal

l Mai

n an

d Sy

stem

Sta

tus

scre

ens.

Press repeatedly to scroll through the System Setup Start screens*

Pre

ss

an

d

si

mul

tane

ousl

y an

d

hol

d 5

seco

nds

to

go

to th

e

Sens

or S

etup

S

tart

scre

en.

FIG

:sys

450_

cwr_

mnu

_flw

chrt

*Not

e: In

any

Set

up S

tart

scre

en, P

ress

a

nd

si

mul

tane

ousl

y to

retu

rn to

the

Mai

n sc

reen

s.

Not

e:re

quire

d on

ly T

ime

and

Day

, and

Occ

upie

d/U

nocc

upie

d S

ched

ule

can

be s

et u

p fo

r any

con

trol

syst

em, b

ut a

re

for c

ontro

l sys

tem

s th

at u

se th

e Se

tbac

k (S

bK) f

eatu

re.

:Pr

ess

t

o sc

roll

thro

ugh

and

set u

pea

ch o

ccup

ied/

unoc

cupi

ed

sche

dule

scr

een.

RSP

F

Afte

r you

mak

e a

chan

ge to

a S

etup

Sta

rt sc

reen

, pre

ss

to

sav

e th

e ch

ange

.

HR

S1

To re

set h

ours

(HR

S),

hold

dow

n th

e

k

eyfo

r 5 s

econ

ds.

n

13

Page 14: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

ts

FIG

:sys

450m

od_a

ssm

bly

g) 7t

Expansion Modules, Module Assemblies, and OutputsSystem 450 expansion modules provide additional outputs to expand control systems and meet specific application requirements. A System 450 control system can provide up to ten outputs, which can be any combination of relay and analog outputs. Expansion modules are available with one or two relay outputs, or with two analog outputs. See Table 10 on page 74 for System 450 module information.

Module Assemblies and Output NumbersYou can easily plug System 450 modules together at the 6-pin plugs and jacks located on the sides of the modules’ housings and mount these module assemblies on standard 35 mm DIN rail (recommended) or directly to a hard, even surface. See Mounting for more information.

The control module is always mounted on the left side of the module assembly. If a System 450 power module is used, the power module is always plugged into the right side of the control module. If expansion modules are used, they can be plugged into the assembly in any order on the right side of the power module. See Assembling System 450 Modules for more information.

Each time a System 450 module assembly is powered on, the control module polls all of the modules to identify output type (relay or analog) and then assigns an output number (1 to 9 and 0 = 10) to each output, starting with the control module output on the left. Output numbers are displayed on the control module LCD to identify the output you are viewing as you navigate the system status and setup screens in the UI (Figure 1).

Figure 6 shows a System 450 module assembly example, the module positions, the output types, and the automatically assigned output numbers used in the system set up in the control module UI.

Figure 6: System 450 Module Assembly Example Showing Control, Power, andExpansion Module Positions, Output Positions, and Output Numbers

LC1

LNO

1LN

C1

LC2

LNO

2LN

C2

240VAC

120VAC

LC1

LNO

1

Control Module(C450CCN-1,C450RCN-1)

2 Relay Outputs

ExpansionModule

(C450CQN-1)2 Analog Outpu

Power Module(C450YNN-1)24 VAC Output

ExpansionModule

(C450CQN-1)2 Analog Outputs

ExpansionModule

(C450SBN-1)1 Relay Output

Sensor Terminalsand (Optional)

24 VAC Supply PowerInput Terminals

(Relay)Output 1

(Relay)Output 2

(Analog)Output 3

(Analog) Output 4

(Relay)Output 5

Supply PowerTerminals

AO

2C

OM

AO

1

AO

2C

OM

AO

1

6-Pin ModularPlugs and Jacks

(Analog)Output 6

(AnaloOutpu

14

Page 15: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Relay OutputsRelay outputs provide low and line-voltage on/off control for devices and equipment in your controlled systems. You can set up multiple relay outputs to create a variety of equipment staging configurations.

Each relay output is a Single-Pole, Double-Throw (SPDT) set of dry contacts (Figure 17). The relay terminals do not supply power to your controlled system. See Technical Specifications on page 78 for the relay electrical ratings. See Wiring System 450 Components on page 34 for information on wiring output relays.

A green Light-Emitting Diode (LED) on the relay control and relay expansion module housings (Figure 1) indicates the relay output status.

When a relay output is On:

• the corresponding green LED on the module housing is lit

• the LNO (Line Normally Open) relay contact is closed

• the LNC (Line Normally Closed) relay contact is open

• the corresponding Output Status screen in the UI displays ON

When a relay output is Off:

• the corresponding green LED on the module housing is not lit

• the LNO relay contact is open

• the LNC relay contact is closed

• the corresponding Output Status screen in the UI displays OFF

See Setting up a Relay Output on page 42 for procedures on setting up relay outputs in the System 450 UI.

Control and expansion modules are available with one or two relay outputs. See Table 10 on page 74 for System 450 model information.

Analog OutputsAnalog outputs provide proportional analog signals for devices and equipment in your controlled systems. Each analog output can generate either a 4-20 mA or 0-10 VDC signal. The output signal type is self-selecting; after you connect the analog output to the controlled equipment, the output detects the analog input on the controlled equipment and generates the appropriate analog signal.

You can set up an analog output to generate a direct-acting or reverse-acting proportional output signal. You can also set up the output signal strength to increase or decrease in either the direct-acting or reverse-acting mode. See Direct and Reverse Control Actions on page 16 for more information.

System 450 also provides six integration constants that allow you to set up a proportional plus integral control signal, which can provide more precise setpoint control. See Proportional Plus Integral Control and Integration Constants on page 18 for information on determining the integration constant for an analog output.

15

Page 16: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

For the standard control module, see Setting up an Analog Output on page 44 for procedures on setting up analog outputs in the System 450 UI. For the reset control module, see Setting up a Standard Analog Output with Unoccupied Setback on page 61 or Setting up an Analog Output with Reset Setpoint Control and Unoccupied Setback on page 66.

Control module and expansion module models are available with one or two analog outputs. See Table 10 on page 74 for System 450 model information.

Direct and Reverse Control Actions

An analog output can be set up to provide one of four different control actions, which allow you to match the output signal to the requirements of your control system and the controlled equipment. The proportional output signal can provide direct-acting or reverse acting control. In addition, the output signal can be set up to generate either the minimum or the maximum output signal strength at Setpoint. See Table 2 for more information.

A control ramp icon is displayed on the status screens for all analog outputs in your control system (Figure 1 on page 9). The displayed control ramp icon represents the control action of the analog output signal.

An analog output’s control action and the corresponding control ramp are automatically determined by the values that you select in four analog output setup screens:

• Setpoint value (SP) is the target value that the control system drives toward, and along with the End Point, defines the output proportional band.

• End Point value (EP) is the maximum deviation from the target value. The control system applies maximum output at the EP to drive the process back toward the SP. The SP and EP define the output proportional band.

• Output at Setpoint value (OSP) is the signal level of the analog output when the input sensor is at the setpoint (SP). The OSP is expressed as a percentage (0-100%) of the full scale output.

• Output at Endpoint value (OEP) is the signal level of the analog output when the input sensor is at the endpoint (EP). The OEP is expressed as a percentage (0-100%) of the full scale output.

Table 2 on page 17 shows the four available control ramp icons and describes their corresponding control actions and the setup value relationships required to configure the four control actions. See Figure 23 and Figure 24 for examples.

16

Page 17: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

ships

Hybrid Analog Output

The C450CPW-100 control’s single hybrid Analog Output (AO) (OUTA1) transitions between a pulse output and a standard VDC output, depending on the sensor value relative to the proportional band. At low output levels, the pulse output signal provides an average motor speed that is less than the EC motor’s fixed minimum speed.

Note: This control function is not limited to EC Motor applications.

The Pulse Region Hybrid AO Setup Screens allow the user to select a Period (in seconds) and Level (expressed in %) for the Hybrid AO.

Table 2: System 450 Control Ramps, Analog Output Control Actions, and System Setup Value Relationships

Control Ramp Displayed

Control Action Set the Analog Output Value Relationfor the Desired Control Action and Corresponding Control Ramp

SP < EP

OSP < OEP

SP > EP

OSP < OEP

SP > EP

OSP > OEP

SP < EP

OSP > OEP

Output Minimum at SP

Proport

ional

Band

OEP=100%

OSP=0%SP=50°F EP=60°F

Output Minimum at SP

Proportional

Band

EP=50°F SP=60°F

OEP=100%

OSP=0%

Output Maximum at SP

OSP=100%

OEP=0%EP=50°F SP=60°F

Proport

ional

Band

Output Maximum at SP

SP=50°F EP=60°F

OSP=100%

OEP=0%

Proportional

Band

17

Page 18: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Proportional Plus Integral Control and Integration Constants

In addition to standard proportional control, System 450 provides Proportional plus Integral (PI) control capability. The addition of integral control enables a properly set up analog output to drive a controlled condition closer to the Setpoint target (Figure 8 on page 19).

Standard proportional-only controls continuously adjust the output in proportion to the difference (offset error) between Setpoint value and the sensor value. As the load on the system increases, the offset error increases. A proportional-only control responds to the increased offset error by changing the output signal, which drives the controlled equipment to compensate for the load change (Figure 8 on page 19). Proportional-only control loops are relatively easy to set up and adjust.

Typically, under constant system load, proportional-only control loops do not drive a system to the selected Setpoint. Instead, the controlled system is maintained at a control point within the proportional band (throttling range) between the setpoint and end point. The larger the load on the system, the further the control point drifts from the setpoint. Still, for many applications, proportional-only control is the best choice for analog output control.

Proportional plus Integral (PI) control incorporates a time-integral control action with proportional control action and, if properly set up, a PI control loop can effectively eliminate offset error and enable a controlled system to drive to the target setpoint even under large constant loads (Figure 8). On a properly sized system with predictable loads, PI control can maintain the controlled system very close to the Setpoint value.

A system’s output capacity, the size of the load on the system, and the integration constant selected determine the speed (recovery rate) at which the PI control drives the system to Setpoint.

Figure 7: Pulse Signal with Pulse Level = 25% and Logical Output = 12.5%

18

Page 19: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

PON

LY-P

RO

+I

The integration constant establishes the rate at which the control readjusts the analog output signal. The faster the integration constant, the faster the control readjusts the output signal and the faster the recovery rate of a properly sized and setup loop.

Note: PI control is not suitable for all controlled systems. Improperly applied PI control loops are unstable and can overshoot setpoint, resulting in control loop oscillation. Also, with PI control, the proportional band (throttling range) and the integration constant are interdependent and you must properly set up these values in relation to each other. You must also properly size the system equipment to handle the maximum load. Close observation (over several cycles and under different load condition) is required to properly set up a PI control loop. On a properly sized system, a PI control loop can drive the system condition much closer to Setpoint than proportional-only control.

In addition to a proportional-only setting, System 450 provides six time-integral settings in the Integration Constant Setup screen for matching the analog signal’s response rate to the controlled system’s recovery rate. The seven integration constant settings are shown in Table 7 on page 52.

See Determining the Integration Constant for an Analog Output on page 49 for more information and the procedures for determining an integration constant and testing a PI control loop in your controlled system.

System 450 Compatible Sensors and TransducersSystem 450 control modules are designed to operate with a variety of compatible sensors and transducers.

Figure 8: Proportional Only Control Versus Proportional Plus IntegralControl

Proportional Only Control

Hum

idity

,P

ress

ure,

or

Tem

pera

ture

Integral control adjusts the outputto bring the system condition toSetpoint regardless of system load.

Control point and outputfollows the system load.

Hum

idity

,P

ress

ure,

or

Tem

pera

ture

Offset Error

Offset Error

End Point

ZeroOffsetError

End Point

19

Page 20: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Code 1

alid

xxxx

0R5D-AB

401C

10D-AB

402C

404C

405C

01x

02x

05x

07x

e s P

Sensor Product Type Number1

alid product code

0 A99B-xxx

7 A99B-xxx

0 HE-67Sx-xxxxx

Standard Control Module Sensors and TransducersTable 3 shows the available temperature, humidity, and pressure sensors (with parameter values, value ranges, and product codes) for the C450CxN-1 models.

Reset Control Module Sensors and TransducersTable 4 shows the available temperature and humidity sensors (with parameter values, value ranges, and product codes) for the C450RxN-1 models. The reset module cannot use pressure sensors.

The Sensor Type that an output references automatically determines the controlled condition, unit of measurement, minimum differential, setup value ranges, and the default setup values for the output.

Table 3: Sensor Types, Setup Values, and Product Codes for Standard Control Modules

Sensor Type

Units of Measurement(Condition/Units)

Range of Values

Displayed Resolution Value

Minimum Differential

Displayed Sensor Range

Product Numbers

1. See Table 11, Table 12, Table 13, and Table 14 in Repair Information on page 74 for a complete list of vproduct code numbers and ordering information for System 450 compatible sensors and transducers.

°F °F (Temperature/degrees) -40 to 250 1 1 -46 to 255 A99B-xxx

°C °C (Temperature/degrees) -40 to 121 0.5 0.5 -43 to 124 A99B-xxx

rH % (Humidity/%RH) 10 to 95 1 2 1 to 100 HE-67Sx-x

P 05 INWC (Pressure/in.W.C.) 0.025 to 0.50 0.005 0.025 0 to 0.5 DPT2650-

P 8 bAR (Pressure/bar) -1 to 8 0.05 0.2 -1 to 8 P499RCP-

P 10 INWC (Pressure/in.W.C.) 0.5 to 10 0.05 0.2 0 to 10 DPT2650-

P 15 bAR (Pressure/bar) -1 to 15 0.1 0.2 -1 to 15 P499RCP-

P 30 bAR (Pressure/bar) 0 to 30 0.1 0.4 0 to 30 P499RCP-

P 50 bAR (Pressure/bar) 0 to 50 0.2 0.4 0 to 50 P499RCP-

P100 PSI (Pressure/psi) 0 to 100 0.5 1 0 to 100 P499Rxx-1

P200 PSI (Pressure/psi) 0 to 200 1 1 0 to 200 P499Rxx-1

P500 PSI (Pressure/psi) 90 to 500 1 5 0 to 500 P499Rxx-1

P750 PSI (Pressure/psi) 150 to 750 2 6 0 to 750 P499Rxx-1

Table 4: Sensor Types, Setup Values, and Product Codes for Reset Control ModulesSensor Type

Unit Range of Usable Values

Resolution Increments Value

Minimum Differential or Proportional Band

Effective Sensing Range

Range of Usable Pb/dIFF and SbK Valuesfor RSP

Rangeof UsablOSETValuefor RS

1. See Table 11, Table 12, Table 13, and Table 14 in Repair Information on page 74 for a complete list of vnumbers and ordering information for System 450 compatible sensors and transducers.

°F °F -40 to 250 1 1 -46 to 255 -30 to 30 -30 to 3

°C °C -40 to 121 0.5 0.5 -43 to 124 -17 to 17 -17 to 1

rH % Humidity 10 to 95 1 2 1 to 100 -20 to 20 -30 to 3

20

Page 21: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Note: For a System 450 control system to operate properly, you must wire the correct sensor or transducer model to the correct sensor input terminals on the control module and select the correct Sensor Type in the associated Select Sensor Type screen in the System 450 UI. You must also correctly set the active/passive sensor jumpers or switches on the control module.

See Table 11, Table 12, Table 13, and Table 14 in Repair Information on page 74 for complete product code numbers and ordering information for System 450 compatible sensors and transducers.

See Wiring System 450 Components on page 34 for information on System 450 input sensor wiring terminals on control modules. Refer to the sensor literature referenced in Related Documentation on page 5 for information on installing, wiring, operating, troubleshooting, and replacing System 450 compatible sensors.

See Setting up the Input Sensors on page 40 and Setting up a System 450 Control System on page 37 for information on setting up the Sensor Types in the System 450 control module UI.

See Figure 9, Figure 10, and Figure 13 for more information regarding jumper settings.

Sensor Failures

Both the standard and reset control modules provide sensor failure modes for the output configurations. The Sensor Failure Mode (SNFx) screen in the UI allows you to select whether the output relay is ON or OFF if the referenced input sensor fails or encounters a sensor or wiring failure. For the reset control module, additional conditions are taken into account if the sensor fails; namely, the calculation of RSP, and the Shutdown Low and Shutdown High conditions. Table 5 describes the impact on the state of the outputs, the RSP, and the shutdown condition in response to a failed sensor.

As shown in Table 5, if Sn-1 fails, the Reset Setpoint (RSP) cannot be calculated. In this case, RSP is set equal to the Minimum (MNSP) or Maximum Reset Setpoints (MXSP). The value chosen depends on the type of reset application that you have configured.

If the calculated RSP decreases with an increasing master sensor, then RSP = MXSP when Sn-1 fails. This condition is identified as RSTR > REND (Reset Start > Reset End). See Figure 29.

Table 5: How Sensor Failures Affect the OutputFailed Sensor

Standard Output State

Reset Output State1

1. Using rES sensor.

Reset Setpoint (RSP)

Shutdown High (SdHI)

Shutdown Low (SdLO)

Sn-1 On or Off n/a2

2. Not applicable.

MNSP or MXSP No Shutdown No Shutdown

Sn-2 On or Off On or Off n/a n/a n/a

Sn-3 On or Off n/a n/a n/a n/a

21

Page 22: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

If the calculated RSP increases with an increasing master sensor, then RSP = MNSP when Sn-1 fails. This condition is identified as REND > RSTR (Reset End > Reset Start). See Figure 30.

22

Page 23: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

System 450 Standard Control System ExamplesSystem 450 can provide a wide range of cost-effective, custom control systems. Figure 9 and Figure 10 show examples of System 450 control systems for some representative system applications featuring the standard C450CxN-1 control modules.

Figure 9: System 450 Control System for a Room Heating and Cooling Application with Condenser Fan Speed Control

FIG

:sys

450_

app_

exm

pl

L1L2

L1L2

0-10 VDC or4-20 mA

Analog OutputSignal

L1 L2

AO

2C

OM

AO

1

Sn-1Sn-2Sn-3

Sensor 1:(or removed) sets Sn-1 to Active (Pressure).

Jumper positioned across two pins sets Sn-2 and Sn-3 to Passive (Temperature).Sensors 2 and 3:

Jumper positioned on one pinSn-1Sn-2Sn-3

Jumper Settings

Active/PassiveSensor Jumpers

(See )Jumper Settings

23

Page 24: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

n

L1

L2

L1

L2

reference -3.)

Fig:

sys4

50_w

irng_

exm

pl

Figure 10: System 450 Control System Example for a Clean Room ApplicatioThat Controls Temperature, Pressure, and Humidity Simultaneously

240VAC

120VAC

LC1

LNO

1LN

C1

LC2

LNO

2LN

C2

L1 L2

HE67Sx-x Humdistat(Sensor Sn-3 in Setup UI)

Output 3Output 2

C450CPN-1 C450YNN-1C450SCN-1

Control Module1 Analog

Power Module

ExpansionModule with

2 Relays

ExpansionModule with

2 Relays

C450SCN-1

DPT-2650 Air PressureDifferential Transducer

(Sensor Sn-1 in Setup UI)

EXCOUTCOM

PWRCOMOUT

%RH

(Outputs 4 and 5Sensor Sn

Control RoomTemperature

(Sn-2)

Switch 1 sets Sensor S1(Set to Active/Off)

Switch 2 sets Sensor S2(Set to Passive/On)

Switch 3 sets Sensor S3(Set to Active/Off).

DIP Switches (for Active/Passive Sensors)

Active/PassiveSensor DIP Switches(See )DIP Switches

Output 1

CO

MA

O1

(Output 1 referencesSensor Sn-1.)

L1L2

L1L2

(Outputs 2 and 3 reference Sensor Sn-2.)

LC1

LNO

1LN

C1

LC2

LNO

2LN

C2

Output 5Output 4

32

1 ON

32

1 ON

24

Page 25: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

High Input Signal Selection System ExampleThe C450CPW-100 model has the ability to control an output using the High Input (HI) signal value of two (HI-2) or three (HI-3) sensors.

When you configure Sn-1 and Sn-2 as the same sensor type (temperature, humidity, or pressure), the SENSX screen includes the option of selecting Sn-1, Sn-2, Sn-3, or HI-2. Selecting HI-2 results in the highest input signal of Sn-1 or Sn-2 controlling the analog output.

When you configure Sn-1, Sn-2, and Sn-3 as the same sensor type (temperature, humidity, or pressure), the SENSX screen includes the option of selecting Sn-1, Sn-2, Sn-3, HI-2, or HI-3. Selecting HI-3 results in the highest input signal of Sn-1, Sn-2, or Sn-3 controlling the analog output.

Figure 11: Example System 450 EC Motor Fan Speed Control

25

Page 26: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

ling

System 450 Reset Control System ExamplesSystem 450 provides solutions for custom reset control systems. Figure 12, Figure 13, and Figure 14 show examples of System 450 reset control systems featuring the C450RxN-1 reset control module.

Figure 12: System 450 Reset Control System Example for a Chiller with Free Coo(See Figure 5, Figure 28, and Figure 29.)

120 VAC

LC1

LNO

1LN

C1

AO

2

CO

M

AO

1

C450RBN-1Reset Control Module

C450SQN-1Expansion Module

Sn-1Sn-2Sn-3

RelayOutput 1

AnalogOutput 2

AnalogOutput 3

Active/Passive Sensor Jumpers(All jumpers positioned across two pins set to Passive.)

Note: In this example, an external power supply is used in place of the C450YNN-1 Power Module.

FIG

:sys

450_

app_

cwr_

vnt

24 VAC100 VA

26

Page 27: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

g

Fig:

sys4

50_w

irng_

natp

ool

Figure 13: System 450 Reset Control System Example for a Natatorium/SwimminPool Zone

LC1

LNO

1LN

C1

LC2

LNO

2LN

C2

240VAC

120VAC

L1L2

L1L2

L1 L2

HE67Sx-x Humidistat (Control Room Humidity)(Sensor Sn-2 in Setup UI)

C450RCN-1 C450YNN-1Control Modulewith 2 Relays

Power Module

ExpansionModule with

1 Analog

C450SPN-1

CO

MA

O1

PWRCOMOUT

%RH

Output 1 references sensor rES.Output 2 references sensor Sn-3 (temperature).

Output 3 referencesSensor Sn-3.

Control RoomTemperature

(Sn-3)

Active/PassiveSensor Jumpers

(See )Jumper Settings

Sn-1Sn-2Sn-3

Sensor 1:sets Sn-1 to Passive (Temperature).

Jumper positioned on one pin(or removed) sets Sn-2 to Active (Humidity).

Jumper positioned across two pinssets Sn-3 to Passive (Temperature).

Sensor 2:

Sensor 3:

Jumper positioned across two pinsSn-1Sn-2Sn-3

Jumper Settings

27

Page 28: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Figure 14: System 450 Reset Control System Example for a Three-Stage Boiler with or without Load Balancing (See Figure 4, Figure 28, and Figure 29.)

LC1

LNO

1LN

C1

LC2

LNO

2LN

C2

240VAC

120VAC

LC1

LNO

1LN

C1

LC2

LNO

2LN

C2

L2L1

L2L1

L2L1

L2L1

L1 L2

C450RCN-1Reset Control Module C450YNN-1

Power Module

C450SCN-1Expansion Module

Sn-1Sn-2Sn-3

RelayOutput 1

RelayOutput 2

RelayOutput 3

RelayOutput 4

Active/Passive Sensor Jumpers(All jumpers set to Passive.)

Note: In 120 VAC applications, L1 must be the Hot lead and L2 must be the Neutral/Common lead.

FIG

:sys

450_

app_

3stg

_bol

r

28

Page 29: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

FIG

:drc

t_cl

g

Modes of Operation for Reset Control ModuleSystem 450 reset control modules and relay output expansion modules can perform temperature and humidity management for multi-stage applications. They can automatically adjust the setpoint to save energy based on readings from the sensor and function settings. Figure 15 shows an example of direct acting control for a cooling application. In a cooling application, you select the direct acting mode of operation by using a positive differential (dIFF) and positive offset (OSET). When the Reset Setpoint (RSP) is reached on a drop in temperature, the normally open relay contacts open, ending the On cycle of Stage 1.

Figure 15: System 450 Direct Acting Mode of Operation Example

OFF to ON

ON to OFF

73

Zone Air Sensor (Sn-2)

Stage 11 OUTR

72 7571 74

Sn‐1

°F

Sn‐2

°F

Sn‐3

‐‐

OFFS1

0 0

OFFS2

0

OFFS3

‐‐  ‐

SENS

70 80

RENd

100 ‐‐

SdHI

55

SdLO

‐‐  ‐

RSET MNSP MXSP RSTR

4

SbK

rES

ONT1

0 0

OFFT1

OFF

SNF1‐‐  ‐

OUTR1 SENS1 dIFF1 OSET1

rES

SENS1

ON

bAL

80

01

rES

ONT3

180 0

OFFT3

OFF

SNF3‐‐  ‐

OUTR3 SENS3 dIFF3 OSET3rES

SENS321

rES

ONT2

60 0

OFFT2

OFF

SNF2‐‐  ‐

OUTR2 SENS2 dIFF2 OSET2rES

SENS211

rES

ONT4240 0

OFFT4

OFF

SNF4‐‐  ‐

OUTR4 SENS4 dIFF4 OSET4

rES

SENS4

31

Stage 2 2OUTR

Stage 3 3OUTR

Stage 4 4OUTR

RSP = °F72

OSET4 dIFF4

Action: Cooling (DA) cutout low, differential Summary of UI Setup Screens:

is above action level; positive value.

OFF

ON

70 7776 7978 80

(MNSP) (MXSP)

°F

RSP

29

Page 30: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Figure 16 shows an example of reverse acting control for a heating application. In a heating application, you select the reverse acting mode of operation by using a negative differential (dIFF) and negative offset (OSET). When the Reset Setpoint (RSP) is reached on a rise of temperature, the normally open relay contacts open, ending the On cycle for Stage 1.

Both Figure 15 and Figure 16 include the setup UI screens that indicate the selections you would make to configure these examples. The system designer must select values that are appropriate for their application.

Figure 16: System 450 Reverse Acting Mode of Operation Example

OFF to ON

ON to OFF

142

Water TempSensor Sn-2

Stage 1 OUTR1

146144

Stage 2 2OUTR

Stage 3 3OUTR

Stage 4 4OUTR

RSP = °F148

Sn‐1

°F

Sn‐2

°F

Sn‐3 OFFS1

0 0

OFFS2

0

OFFS3

‐‐  ‐

SENS

110 180

RENd

0 55

SdHI SdLO

‐‐  ‐

RSET MNSP MXSP RSTR

‐10

SbK

rES

ONT1

0 0

OFFT1

OFF

SNF1‐‐  ‐

OUTR1 SENS1 dIFF1 OSET1

rES

SENS1

ON

bAL

50

0‐4

rES

ONT3

60 0

OFFT3

OFF

SNF3

‐‐  ‐

OUTR3 SENS3 dIFF3 OSET3

rES

SENS3

‐4‐4

rES

ONT2

30 0

OFFT2

OFF

SNF2

‐‐  ‐

OUTR2 SENS2 dIFF2 OSET2

rES

SENS2

‐2‐4

rES

ONT4

90 0

OFFT4

OFF

SNF4

‐‐  ‐

OUTR4 SENS4 dIFF4 OSET4

rES

SENS4

‐6‐4

‐‐

110

OSET4dIFF4

Action: Summary of UI Setup Screens:

Heating  High, differential (RA) cutout  is below action  egative value.level; n

OFF

ON

148 180140 150

(MNSP) (MXSP)

136 138

FIG

:rvrs

_htg

°F

‐‐

RSP

30

Page 31: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Load BalancingThe examples in Figure 15 and Figure 16 also show the use of load balancing. When Load Balancing Mode (bAL) is set to ON, the reset control module starts the stage with the least amount of ON time first. This stage becomes the new Stage 1. The stage with the most amount of ON time starts last. This stage becomes the new Stage 4. The reset control module automatically moves dIFF1 and OSET1 from the old Stage 1 to the new Stage 1, and moves dIFF4 and OSET4 from the old Stage 4 to the new Stage 4. This pattern works the same way for Stages 2 and 3.

Detailed Procedures

Designing and Building System 450 Control SystemsThe variety and flexibility of System 450 modules and sensors allow you to build an almost limitless variety of custom control systems. In fact, for many control systems, different System 450 components can be configured to achieve the same results.

Observe the following guidelines when designing a control system and selecting components:

• Determine the conditions and condition ranges that must be monitored in your application. Up to three sensors can be connected and up to three conditions can be monitored simultaneously. See Table 3 on page 20 and Selecting Input Sensors for more information.

• Determine the number and type (relay or analog) of outputs required to control the equipment in your application. Up to ten outputs can be configured in and controlled by a single System 450 control system.

• Determine the types of control and expansion modules needed to provide the required outputs for your application and the minimum number of modules required to provide those outputs.

Note: Many System 450 control systems can be configured using a different set of module models to build the assembly, but typically there is one configuration that is more cost effective to build than other potential module assembly configurations.

• Determine which control module can fully satisfy the application. For example, select the Reset Control Module (C450RxN-1 models) if you need a reset function, occupied and unoccupied scheduling, energy savings with setback, and/or load balancing.

Selecting Input SensorsIn a System 450 control system, each output references an input sensor that is wired to the control module and set up in the control module UI. Observe the following guidelines when selecting, installing, and setting up sensors for your control system:

31

Page 32: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

• Select only System 450 compatible sensors listed in Table 3 on page 20 or Table 4 on page 20 for your type of control module.

• Select only the sensors that match the desired units of measurement and are designed to operate in the ranges that the control system is intended to monitor and control. (See Table 3 on page 20 or Table 4 on page 20).

• Ensure that the correct sensor is wired properly to the correct input terminals on the control module. (See Wiring System 450 Components on page 34.)

• Ensure that the wire length between the sensors and control module is as short as possible/practical, and ensure that the wiring is properly sized. (Refer to the sensor installation instructions referenced in Related Documentation on page 5 for more information on wiring sensors.)

• Ensure that the correct sensor type is selected in the System 450 UI for each sensor wired to the control module. (See Setting up the Input Sensors on page 40.)

• Ensure that each output references the correct sensor in the System 450 UI. (See Setting up a System 450 Control System on page 37.)

Assembling System 450 Modules

After selecting the System 450 components for your control system, you must assemble the modules. Figure 6 on page 14 shows an example of a System 450 module assembly. Observe the following guidelines when assembling System 450 modules:

• Always locate the control module on the left side of the module assembly.

• Always plug the System 450 power module (when used) into the right side of the control module.

• Plug the expansion modules together, in any order, on the right side of the System 450 power module (or on the right side of the control module when an external 24 VAC power supply is used instead of a System 450 power module). See Wiring System 450 Components on page 34 for information on wiring an optional external 24 VAC supply power to System 450 control systems that do not have a power module. Also, see Figure 12 on page 26 for an example that uses an external power supply.

Installing System 450 Components

Locating System 450 ModulesObserve these guidelines when locating and mounting System 450 modules:

• Ensure that the mounting surface can support the module assembly, DIN rail, mounting hardware, and any (user-supplied) panel or enclosure.

• Mount the modules in a horizontal, upright orientation wherever possible. DIN rail mount is recommended.

• Mount modules directly on only flat and even surfaces.

32

Page 33: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

• Mount the modules in locations free of corrosive vapors and observe the ambient operating conditions in the Technical Specifications on page 78.

• Allow sufficient space for making connections, running wires, and viewing LCD for control status and set up.

• Do not mount the modules on surfaces that are prone to vibration or in locations where strong radio frequency or electromagnetic emissions may cause interference.

• Do not install the modules in airtight enclosures.

• Do not install heat generating devices in an enclosure with the modules that may cause the ambient temperature to exceed 66°C (150°F).

Mounting

Mount System 450 modules on 35 mm DIN rail (recommended) or directly to a flat/even surface.

To mount the modules on DIN rail:

1. Provide a section of 35 mm DIN rail that is longer than the module assembly width, and mount the DIN rail in a suitable location using appropriate mounting hardware/fasteners.

2. Clip the control module on the rail, position the module’s upper DIN rail clips on the top rail, and gently snap the lower clips on to the bottom of the rail.

3. Clip the remaining modules to the right of the control module on to the DIN rail and gently slide and plug the modules together. (If a System 450 power module is used, mount the power module to the right of the control module so that the power module plugs directly into the control module.)

To direct-mount modules to wall surfaces:

1. Plug the modules together, remove the module covers, place the assembly horizontally against a flat even surface in a suitable location, and mark the mounting slot locations on the surface.

2. Install appropriate screw fasteners, leaving screw heads approximately one to two turns away from flush to the surface.

IMPORTANT: When mounting a module assembly on a DIN rail, clip the modules on to the DIN rail individually before gently sliding and plugging the mounted modules together on the DIN rail. Clipping a complete module assembly that is already plugged together on to the DIN rail can damage the 6-pin modular plugs and void any warranties.

IMPORTANT: Mount the module assembly only on a flat, even surface. Mounting the module assembly on an uneven surface can damage the module housings or the 6-pin modular connectors.

33

Page 34: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

3. Place the assembly over screw heads and on the mounting slots, and carefully tighten mount screws.

Refer to the sensor installation instructions referenced in Related Documentation on page 5 for information on locating and mounting System 450 compatible input sensors.

Wiring System 450 ComponentsWhen wiring your System 450 control system, observe the following guidelines and see Figure 17, Figure 18, and Table 6.

Refer to the Technical Specifications table in the module installation instructions referenced in Related Documentation on page 5 for module electrical ratings.

!WARNING: Risk of Electric Shock.Disconnect or isolate all power supplies before making electrical connections. More than one disconnect or isolation may be required to completely de-energize equipment. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.

IMPORTANT: Use copper conductors only. Make all wiring in accordance with local, national, and regional regulations.

IMPORTANT: Do not exceed the System 450 module electrical ratings. Exceeding module electrical ratings can result in permanent damage to the modules and void any warranty.

IMPORTANT: Do not connect supply power to the System 450 modules before checking all wiring connections. Short circuits or improperly connected wires can result in damage to the modules and void any warranty.

34

Page 35: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Figure 17 and Figure 18 show the wiring terminal details for System 450 control modules and expansion modules.

Figure 17: Wiring Terminal Details for System 450 Control and Expansion Modules with Relay Output

System 450Control Module

with Relay Output(C450SxN-1)

Sn2CSn35V

24VC

Sn1C

Common terminals (C)are internallyconnected.

LNC

1LN

O1

LC1

Internal SPDT Relay(Normally Closed Position)

Line-Voltage

(on Relay Control and Expansion Modules)

Relay Output Terminals

Note: Some Control and Expansion module models have two output relaysand a second terminal block labeled LNC2, LNO2, and LC2.

System 450Expansion Modulewith Relay Output

(C450CxN-1)sy

s450

_cnt

rl_ex

pnsn

_wirn

g

Figure 18: Wiring Terminal Details for System 450 Control and Expansion Modules with Analog Outputs

System 450Control Module

with Analog Outputs(C450CQN-1)

System 450Expansion Module

with Analog Outputs(C450SQN-1)

sys4

50_a

nlg_

cntrl

_exp

nsn_

wirn

g

AO

2C

OM

AO

1

AO

2C

OM

AO

1

AO

2C

OM

AO

1

AnalogControlled

Device

AnalogControlled

Device

+

__

+

Low-Voltage

(on Analog Control and Analog Expansion Modules)

Analog Output Terminals

Sn2CSn35V

24VC

Sn1C

Common terminals (C)are internallyconnected.

35

Page 36: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

ed Wire

to 16 AWG2 to 1.5 mm2

to 14 AWG2 to 2.5 mm2

to 16 AWG2 to 1.5 mm2

to 14 AWG2 to 2.5 mm2

Table 6 provides wiring terminal information and required wire size for System 450 control, expansion, and power modules. Table 6: System 450 Wiring Terminal and Wire Size InformationTerminal Block Type (on Module Type)

Terminal Label

Terminal Function RequirSizes

Input Sensor and Low-Voltage Input Power Terminal Block (on all Control Modules)

24V Accepts 24 VAC supply power, when a C450YNN-1 power module is not connected, and provides power terminal for 24 VAC (humidity) sensors.

28 AWG0.08 mm

5V Provides 5 VDC power for active sensors.

Sn-1, Sn-2, Sn-3

Accepts passive or active (0-5 VDC) input signals from sensors.Note: In System 450 reset control systems, Sn-1 is

the Master sensor (typically sensing outdoor air temperature) and Sn-2 is the controlled loop sensor.

C (3 Terminals)

Provides low-voltage common connections for 24 VAC power and passive or active sensors connected to the 5V, Sn1, Sn2, and Sn3 terminals. Note: The three C terminals are connected internally and can be connected to ground in the field.

Line-Voltage Output Relay Terminal Blocks (on Control and Expansion Modules with Relay Output)

LNC1,LNC2

Connects equipment control circuit to the Line-voltage Normally Closed (LNC) contact on the SPDT relay.LNC2 terminals are only on control and expansion modules with two output relays.

28 AWG0.08 mm

LNO1, LNO2

Connects equipment control circuit to the Line-voltage Normally Open (LNO) contact on the SPDT relay.LNO2 terminals are only on control and expansion modules with two output relays.

LC1LC2

Connects line power to the Line-voltage Common (LC) on the SPDT relay.LC2 terminals are only on control and expansion modules with two output relays.

Low-Voltage Analog Output Terminal Block(on Control and Expansion Modules with Analog Outputs)

AO1AO2

In conjunction with the COM terminal, provides a self-detecting analog output signal; either 0-10 VDC or 4-20 mA.

28 AWG0.08 mm

COM In conjunction with the AO1 or AO2 terminal, provides a self-detecting analog output signal; either 0-10 VDC or 4-20 mA.

Line-Voltage Supply Power Terminal Block (on Power Modules)

240 VAC Left terminal is for one 240 VAC supply power lead. 22 AWG0.34 mmNo Label

on the Middle Terminal

Middle terminal is the Common connection for either the 120 VAC or 240 VAC supply power lead.

120 VAC Right terminal is for one 120 VAC supply power lead.

36

Page 37: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Wiring System 450 Sensors and TransducersRefer to the sensor installation instructions referenced in Related Documentation on page 5 for information on wiring System 450 compatible input sensors.

Setting up a System 450 Control SystemAfter assembling the modules, your System 450 control system is ready to connect to power and to be set up in the control module UI.

Note: You can power on and set up a System 450 control system (in the control module UI) before installing the module assembly or wiring the sensors and outputs.

Note: The input sensors must be set up in the System 450 UI before you can set up any of the control system outputs. See Setting up the Input Sensors on page 40 for more information and detailed procedures.

Determining Output Numbers and Output TypesAfter all of the modules in your control system are properly assembled and each time power is supplied to the module assembly, the control module automatically polls all of the modules in the assembly, assigns output numbers, and determines output types and their order in the assembly.

The control module assigns a sequential output number to each output in the module assembly, starting with the output farthest to the left in the control module, which is assigned output number 1. Each output to the right of output 1 is assigned an output number; the numbers are 2 to 9 in order of the output’s physical position, left to right, in the module assembly. Zero (0) is assigned to output 10, if the control system has ten outputs. See Figure 6 on page 14 for an example of output numbers in a module assembly.

The control module also determines if an output is a relay output or an analog output, and generates the appropriate status screens and set up screens in the System 450 UI for each output.

IMPORTANT: The setup information in the control module is retained if the unit experiences a power failure. If power is lost for an extended period of time (for example, 8 hours or more), the time clock setup parameter resets, indicated by dashes shown on the time screen. When this occurs, the occupied and unoccupied function defaults to occupied mode until you re-enter the time.

IMPORTANT: Do not change the module positions after a System 450 control system is assembled, powered, and set up in the System 450 User Interface (UI). System 450 control logic is set up in the UI according to the sensor type, output type, and output number. If you change the module positions in an module assembly that is already set up in the UI, the output numbers and default setup values for the outputs also change, which often requires you to again set up the entire control system in the UI.

37

Page 38: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Accessing and Navigating the User InterfaceSystem 450 control modules feature a backlit LCD and a four-button touchpad UI for monitoring system status and setting up the sensors and outputs in your control system. Figure 1 on page 9 describes the System 450 UI features and functions.

During normal operation, the System 450 control module LCD displays the Main System Status screens. These sensor status screens scroll automatically and provide real-time status of the conditions sensed at the input sensors.

Figure 2 on page 10 shows an example of a System 450 UI screen flow.

Viewing the System Status Screens

From the Main (Sensor Status) screens, you can scroll through and view your system’s status.

To scroll and view your control system status screens while the control module LCD is displaying a Main (Sensor Status) screen, press (repeatedly) to scroll through and display the Sensor Status screens and the Output Status screens for all sensors and outputs set up in your control system (Figure 19). The Sensor or Output Status screen that is being viewed remains visible for 2 minutes before it times out and begins to autoscroll through the sensors again. You will be able to monitor one sensor that is changing quickly during system setup or operation.

Accessing the System Setup Screens

From the Main sensor status screens, you can also access the Sensor Setup Start screen and the Output Setup Start screens.

• From the Sensor Setup Start screen, you can set up all of the sensors for your control system. See Setting up the Input Sensors on page 40 for procedures on setting up the input sensors.

• From the Output Setup Start screens, you can set up each output point in your control system. See Setting up a Relay Output on page 42 and Setting up an Analog Output on page 44 for procedure on setting up outputs.

Figure 19: Main (Sensor Status) Screens and Output Status Screens Example

Main Screen(Sensor 1 Status)

OUT3°F2

Input Sensor 1Status

232 psi

During normal operation, the display automatically scrolls throughthe Sensor Status screens for all sensors set up in the UI.

After a 2 minute pause in setup or status screen, the displayreturns to the Main (Sensor Status) screens.

anyPress to scroll throughSensor Status screens and

Output Status screens.

Fig:

sys4

50U

I_sy

s_st

ats°F2

38

Page 39: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

To access and navigate the System 450 Setup Start screens:

1. In the Main (Sensor Status) screen, press and simultaneously and hold for 5 seconds. The Sensor Setup Start (SENS) screen appears (Figure 20).

2. Press (repeatedly) to scroll through and access the Output Setup Start (OUTXx) screens for all of the outputs in your control system.

Note: All Setup Start screens have four blinking dashes in the setup value fields (Figure 20). You cannot select values for the setup value fields in the Setup Start screens.

3. Depending on the Setup Start screen that is displayed, press :

• in the Sensor Setup Start (SENS) screen to go the Select Sensor 1 Type (Sn-1) screen and set up the sensors in your control system. See Setting up the Input Sensors for procedures on setting up the sensors.

Figure 20: Accessing the Setup Start Screens in the System 450 UI

Sensor SetupStart

SENS

Relay OutputSetup Start

OUTR1

Output Relay 1

OUTA3

OutputAnalog Setup Start

Analog Output 3

232 PSI

Sensor StatusDisplayed

Main Screen

Relay OutputSetup Start

OUTR2

Output Relay 2

Press and hold + for 5 seconds

to access the Setup Start screens.

Press to scroll through the Sensor Setup Start screensand all of the Analog and Relay Output Setup Start screens. Press in the Sensor Setup Start screen to scroll through the Sensor Setup screens.

Press in any Output Setup Start screen to scroll throughthat output's set up screens. Press + simultaneously in any Setup Start screen toreturn to the Main Screen.

M

M

M

M

Up to 10 outputscan be connected,set up, and viewed.

M

Sensor Setup Screens

Output 1 Relay Setup Screens

Output 2 Relay Setup Screens

Output 3 Analog Setup ScreensFi

g:sy

s450

UI_

sys_

stup

- - -

- --

- --

- - -

M

39

Page 40: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

• in any Output Setup Start (OUTXx) screen to go to the first output setup screen for the output. (See Setting up a Relay Output or Setting up an Analog Output for the procedures for setting up outputs.)

Note: You must set up the input sensors in the System 450 UI before you can set up the outputs in the UI. See Setting up the Input Sensors.

Setting up the Input SensorsTo set up the input sensors in your System 450 control system, you must select the correct Sensor Type for each sensor. You can also select a temperature offset value for any temperature sensor that is set up in your control system.

The Sensor Type you select for an input sensor automatically determines the condition type, unit of measurement, minimum differential, setup value ranges, and default setup values for each output in your control system that references the input sensor.

The standard control modules:

• support temperature, pressure, and humidity sensors

• support configuration of Sn-1, Sn-2, and Sn-3 for any supported sensor type

The reset control modules:

• support temperature and humidity sensors, but not pressure sensors

• require configuration of Sn-1 as a temperature sensor, but support configuration of Sn-2 and Sn-3 as either temperature or humidity sensors

• require configuration of Sn-1 as the master sensor for generating the reset setpoint and require configuration of Sn-2 as the supply (or controlled) temperature or humidity sensor. (Typically, Sn-1 is the outdoor air temperature sensor; see Figure 28).

Note: For a System 450 control system to operate properly, you must wire the correct sensor or transducer model to the correct sensor input terminals on the control module, and select the correct Sensor Type in the associated Select Sensor Type screen in the System 450 UI. You must also correctly set the active/passive sensor jumpers or switches on the control module. See Figure 9, Figure 10, and Figure 13 for more information.

See Table 3 on page 20 (standard control module) or Table 4 on page 20 (reset control module) for System 450 Sensor Types and their associated values and settings.

See Table 11, Table 12, Table 13, and Table 14 in Repair Information on page 74 for complete product code numbers and ordering information for System 450 compatible sensors and transducers.

System 450 allows you to select an offset for each temperature sensor in your control system. Whenever you select the °F or °C Sensor Type for a sensor, a Select Temperature Offset screen appears after the Select Sensor 3 Type screen for each temperature sensor in your control system. The selections are:

40

Page 41: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

• Sensor Type °F, which enables an offset of up to +/- 5°F in 1 degree increments.

• Sensor Type °C, which enables an offset of up to +/- 2.5°C in 0.5 degree increments.

The temperature offset adjusts the displayed temperature value by the offset value. For example, if the displayed value is 72(°F) without an offset, a -2(°F) offset adjusts the displayed value to 70(°F).

To set up the Sensor Type for the input sensors and the temperature offset for a temperature sensor:

1. Access the System 450 UI and navigate to the Sensor Setup Start (SENS) screen (Figure 21).

2. In the Sensor Setup Start (SENS) screen, press to go to the next screen.

3. In the Select Sensor 1 Type (Sn-1) screen, press or to scroll through the Sensor Types. When the desired Sensor Type is displayed (blinking), press to save the Sensor Type selection and go to the Select Sensor 2 Type screen.

4. Repeat Step 3 in the Select Sensor 2 Type (Sn-2) screen and Select Sensor 3 Type (Sn-3) screen if your control system uses a second or third input sensor.

After you have selected the correct Sensor Type for each sensor in your control system, the input sensors are set up in the UI and can be referenced by the outputs that you set up in the system.

5. If a temperature Sensor Type (°F or °C) is selected for a sensor in your control system, a Select Temperature Offset (OFFSx) screen is displayed after the Select Sensor 3 Type (Sn-3) screen (for each temperature sensor in your control system). Select the desired temperature offset by pressing or . Press to save the offset value and go to the next screen.

6. After all of the sensors are set up:

Figure 21: Sensor Setup Start, Select Sensor Type,and Select Temperature Offset Screens

Setup StartScreens

SENS

Select Sensor 1Type

Select Sensor 2Type

Select Sensor 3Type

Sensor Setup Start

P500 °F

Sensor Type (-40 to 250ºF)

ºF No Sensor TypeSelected

M

M

Scroll throughSetup Start Screens

SelectTemperature (only)

Offset Degrees

-2OFFS2Sn-3Sn-1 Sn-2

Note: Whenever you select the

a screen appears after the screen for each temperature sensor in your control system. Select the desired temperature offset for a temperature sensor by pressing or .

Select Temperature Offset Select Sensor 3 TypeºF ºC or Sensor Type for a sensor (Sn-1, Sn-2, or Sn-3),

Fig:

sys4

50U

I_se

nsr_

stup

- -- – – – –

41

Page 42: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

• Press to go to the Sensor Setup Start (SENS) screen; then press to scroll through the output setup start screens and set up the outputs in your control system. (See Setting up Standard Control Module Outputs on page 42 or Setting up Reset Control Module Outputs on page 52 for procedures on setting up outputs for your type of control module.)

• Allow the UI to remain dormant for 2 minutes and the Main screen will begin to autoscroll. You may also return to the Main screen by pressing and simultaneously while a Setup Start screen is displayed.

Setting up Standard Control Module OutputsAfter setting up the input sensors for your System 450 standard control system, you can reference them as you set up the outputs. If you have the reset control module, see Setting up Reset Control Module Outputs on page 52.

Setting up a Relay Output

Relay Outputs provide single and multiple stage on/off control to controlled equipment. When you supply power to a module assembly, the control module polls all of the connected modules, detects any relay outputs, and then assigns an output number and enables a Relay Output Setup Start (OUTRx) screen for each relay output detected (Figure 22 on page 43). See Relay Outputs on page 15 for more information.

Note: The condition (temperature, pressure, or humidity), unit of measurement, minimum differential value, default setup values, condition value ranges available in the output setup screens are determined by the Sensor Type of the input sensor that you select for the output. See Table 3 on page 20 for more information on Sensor Types and their associated values and ranges.

The Relay ON (ONx) screen and Relay OFF (OFFx) screen allow you to select the condition values at which the relay turns On and turns Off. The first time you access the Relay ON (ONx) and Relay OFF (OFFx) screens, the default ON and OFF values appear.

Selecting an ON value less than the OFF value (ON < OFF) turns the relay On when the condition value decreases (which is the typical heating mode in temperature applications and referred to as reverse-acting on/off control).

Selecting an ON value greater than the OFF value (ON > OFF) turns the relay On when the condition value increases (which is the typical cooling mode in temperature applications and referred to as direct-acting on/off control).

The minimum differential value for the condition is determined by the Sensor Type of the input sensor that an output references. The minimum differential is fixed and is automatically enforced in the setup UI when you select ON and OFF values; the condition values within the minimum differential range are not available to select.

M

42

Page 43: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

The Minimum Relay ON Time and Minimum Relay OFF Time screens provide anti-short-cycling control for system equipment by allowing you to delay the shutdown or start-up for up to 300 seconds (5 minutes) after the ON or OFF value is reached.

The Sensor Failure Mode screen allows you to select whether the output relay is On or Off if the referenced input sensor encounters a sensor or wiring failure.

To set up a relay output:

1. Access the System 450 UI and navigate to the desired Relay Output Setup Start (OUTRx) screen (Figure 22). (See Accessing and Navigating the User Interface on page 38.)

2. In the Select Relay Output Setup Start (OUTRx) screen, press to go to the Select Input Sensor (SENsx) screen. (The Select Input Sensor screen does not appear here if the input sensor is already selected for this output. In that case, go to the next step.) Press or to select the input sensor (Sn-1, Sn-2, or Sn-3) that the output references. Press to save the sensor selection and go to the next screen.

3. In the Select Relay ON Value (ONx) screen, press or to select the temperature, pressure, or humidity value at which the relay turns On. Press to save the ON value and go to the next screen.

4. In the Select Relay OFF Value (OFFx) screen, press or to select the temperature, pressure, or humidity value at which the relay turns Off. Press to save the OFF value and go to the next screen.

Figure 22: Relay Output Setup Start Screen and Setup Screen Flow

43

Page 44: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

5. In the Select Minimum Relay ON Time (ONTx) screen, press or to select the minimum number of seconds that the relay stays On after the Relay ON value is reached. Press to save the Minimum ON value and go to the next screen.

6. In the Select Minimum Relay OFF Time (OFFTx) screen, press or to select the minimum number of seconds that the relay stays Off after the Relay OFF value is reached. Press to save the Minimum OFF value and go to the next screen.

7. In the Select Sensor Failure Mode (SNFx) screen, press or to select whether the output relay stays On or Off when a sensor failure is detected. Press to save the Sensor Failure Mode value and go to the next screen.

8. In the Edit Input Sensor screen:

• If the displayed input sensor (Sn-1, Sn-2, or Sn-3) is the correct input sensor for the output relay, the output set up is complete. Press to go to the Relay Output Setup Start screen.

• If the displayed input sensor (Sn-1, Sn-2, or Sn-3) is not the correct input sensor for the output relay, press or to select the correct input sensor. Press to save the new input sensor selection and go to the Relay Output Setup Start screen. Press again to go to the Relay ON Value screen and repeat Step 3 through Step 8 for the new input sensor.

The relay output is set up and saved in the control module. If you need to set up the next output, press to navigate to the next Output Setup Start screen. If you have completed the control system set up, press and simultaneously to return to the Main screens.

Setting up an Analog OutputAnalog Outputs provide proportional analog control signals to controlled equipment based on the sensed conditions. When you supply power to a module assembly, the control module polls all of the connected modules, detects any analog outputs, and then assigns an output number and enables an Analog Output Setup Start screen for each analog output detected (Figure 25 on page 46). See Analog Outputs on page 15 for more information.

Note: The condition (temperature, pressure, or humidity), unit of measurement, minimum differential value, default setup values, condition value ranges available in the output setup screens are determined by the Sensor Type of the input sensor that you select for the output. See Table 3 on page 20 for more information on Sensor Types and their associated values and ranges.

The Setpoint (SP) and End Point (EP) screens allow you to set up a proportional band (or throttling range) for the control loops in your controlled system. The Output at Setpoint (OSP) and Output at End Point (OEP) screens allow you to select the output signal strength (as a percentage of the total signal strength range) that an analog output sends to the controlled equipment at Setpoint and End Point.

M

44

Page 45: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

The relationship between these four setup values (SP, EP, OSP, and OEP) determines the analog output’s proportional control action, which is indicated on the control module LCD by the control ramp indicator. See Direct and Reverse Control Actions on page 16 for more information.

The Integration Constant (I-C) screen allows you to select an integration constant for the analog signal. Selecting an integration constant other than 0 enables proportional plus integral control action, which in many applications can drive the condition closer to Setpoint (than proportional-only control action). See Proportional Plus Integral Control and Integration Constants on page 18 for more information. See Determining the Integration Constant for an Analog Output on page 49 for procedures on determining and testing integration constants.

The Sensor Failure Mode (SNFx) screen allows you to select whether the analog output signal is Off (corresponding to the lowest output capacity) or On (corresponding to the highest output capacity) when a sensor failure is detected.

Figure 23: Relationship between Setpoint, End Point, Output at Setpoint, and Output at End Point for an Analog Output That Controls Room Heating

Sys

tem

Out

put

0%

100%

Condition ValueLess Greater65°F

10% OSP

OEP

SP

EP70°F

Sensor Type = = 70 ( ) = 65 ( ) > = 10 (%) = 100 (%)

SPEPSP EPOSPOEP

°F

°F°F

ProportionalBand

Fig:

sys4

50_c

ntrl_

rmp_

1

Figure 24: Relationship between Setpoint, End Point, Output at Setpoint, and Output at End Point for an Analog Output That Controls Condenser Fan Speed

45

Page 46: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

To set up an analog output:

1. Access the System 450 UI and navigate to the desired Analog Output Setup Start screen (Figure 25). (See Accessing and Navigating the User Interface on page 38.)

2. In the Analog Output Setup Start (OUTAx) screen, press to go to the Select Input Sensor (SENsx) screen. (The Select Input Sensor screen does not appear here if the input sensor is already selected for this output. In that case, go to the next step.) Press or to select the input sensor (Sn-1, Sn-2, or Sn-3) that the output references. Press to save the sensor selection and go to the Select Setpoint Value screen.

3. In the Select Setpoint Value (SPx) screen, press or to select the Setpoint value. (The controlled system drives towards Setpoint and away from End point, which together define the proportional band for the analog output.) Press

to save the Setpoint value and go to the next screen.

4. In the Select End Point Value (EPx) screen, press or to select the End Point value. (The controlled system operates between Setpoint and End point, which together define the proportional band for the analog output.) Press to save the End Point value and go to the next screen.

Figure 25: Analog Output Setup Start Screen and Setup Screen Flow

46

Page 47: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

5. In the Select Output Signal Strength at Setpoint (OSPx) screen, press or to select the value in percent of the output signal strength (0-100%),

corresponding to the lowest output capacity, when the sensor is at the Setpoint (SPx). Press to save the displayed OSP value and go to the next screen.

6. In the Select Output Signal Strength at End Point (OEPx) screen, press or to select the value in percent of the output signal strength (0-100%),

corresponding to the highest output capacity, when the sensor is at the End point (EPx). Press to save the displayed OEP value and go to the next screen.

7. In the Select Integration Constant (I-Cx) screen, press or to select the I-C value for the analog output. (See Determining the Integration Constant for an Analog Output for more information.) Press to save the displayed I-C value and go to the next screen.

8. In the Select Sensor Failure Mode (SNFx) screen, press or to select whether the analog output signal is to be set to its On or Off value when a failure of the referenced input sensor is detected. With regard to sensor failures and analog outputs, the On value is the OEP value. The Off value is the OSP value. Press to save the displayed SNF value and go to the next screen.

9. In the Edit Input Sensor (Sensx) screen you can change the input sensor that the output currently references:

• If the displayed input sensor (Sn-1, Sn-2, or Sn-3) is the correct input sensor for the output relay, the output setup is complete. Press to go to the Analog Output Setup Start screen.

• If the displayed input sensor (Sn-1, Sn-2, or Sn-3) is not the correct input sensor for the output relay, press or to select the correct input sensor. Press to save the new input sensor selection and go to the Analog Setpoint Value screen. Repeat Step 3 through Step 8 for the new input sensor.

10. Press to return to the Analog Output Setup Start (OUTAx) screen.

The analog output is set up and saved in the control module.

• If the controller has a hybrid analog output, press to navigate to the Pulse Region Hybrid AO Setup Screens.

• If the controller does not have a hybrid analog output, press to navigate to the next Output Setup Start screen.

• If you have completed the control system setup, press and simultaneously to return to the Main screens.

M

47

Page 48: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Setting up a Pulse Region Hybrid Analog Output

To set up the Pulse Region of a Hybrid Analog Output:

1. From the Pulse Region Hybrid AO Setup Start Screen for Analog Output 1, press to go to this output’s Pulse Output Level Selection Screen.

Note: Only OUTA1 is capable of generating the Pulse-AO. Additional AO expansion modules provide a standard 0-10 VDC output signal.

2. In the Pulse Output Level Selection Screen, set the Pulse Output Level to a value higher than required for the EC Motor to run. If the motor requires a minimum speed reference of 2 VDC before it will run, set the Pulse Level higher than 2.5 VDC (25%). Press or to select this Output’s Pulse Output Level value. Press to save your Pulse Output Level value selection and go to the Pulse Period Selection Screen.

Note: Screen example shows the Pulse Output Level set to 25%. Range is 0 to 100%. Set the Pulse Output Level to 0% to disable the pulse output. Set the Pulse Output Level to 100% to use the pulse output over the entire 0-10 V output range.

3. In the Pulse Period Selection Screen, press or to select this output’s Pulse Period value. Press to save your Pulse Period value selection and go to the Pulse Region Hybrid AO Setup Start Screen.

Note: Screen example shows the Pulse Period set for 2 seconds. Range is 1 to 30 seconds.

Figure 26: Pulse Region Hybrid AO Setup Start Screen

48

Page 49: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Determining the Integration Constant for an Analog OutputThe default Integration Constant (I-C) setting for analog outputs is 0 (zero) or no integration constant. An I-C setting of 0 provides a proportional-only analog signal. Many applications do not require you to change this default setting. See Proportional Plus Integral Control and Integration Constants on page 18 for more information.

If you want to apply proportional plus integral to a control loop in your controlled system, here are two methods of determining the best I-C setting for the analog output that controls the loop.

Note: Both of the following methods for determining an I-C setting require you to install, set up, and operate the control loop in your controlled system under a variety of typical load conditions and observe the response to load changes and different I-C settings.

Testing the Slowest to Fastest Time Integral to Determine I-C Setting

One method of determining the best I-C setting for a control loop is to observe the controlled system’s operation at the slowest time integral (I-C setting of 1) and then increase the I-C setting one step at a time to determine the best setting.

To determine the best I-C setting for an analog output by testing slowest to fastest time integral:

1. Set up the System 450 control loop for proportional-only control (I-C setting of 0 [zero]), power the controlled system on under typical/steady load conditions, and allow the system to stabilize at a control point somewhere in the proportional band between the Setpoint and End Point values.

2. After the controlled system has stabilized at a control point, set the integration constant to the slowest time integral (I-C setting of 1) and observe the control point to see if it stabilizes closer to the selected Setpoint.

• If the control point overshoots the Setpoint, go to Step 3.

• If the control point stabilizes closer to Setpoint but does not overshoot Setpoint, set the integration constant to the next (faster) time integral and then observe the control point to see if it stabilizes closer to the selected Setpoint.

If the control point does not overshoot Setpoint at new I-C setting, continue to increase the setting and observe the system until the control point overshoots the Setpoint, then go to Step 3.

3. When the control point overshoots Setpoint, continue to observe the control point:

• If the control point drifts past Setpoint, reverses, and then drifts back towards Setpoint and stabilizes at or near Setpoint, go to Step 4.

49

Page 50: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

• If the control point drives significantly beyond Setpoints, then reverses quickly, drives back past Setpoint, and continues oscillating significantly above and below Setpoint, reset the I-C setting to the previous (slower) time integral and go to Step 4.

4. When the control point stabilizes near Setpoint or drifts slightly above and below Setpoint, operate the control loop under a variety of load conditions, including the maximum load condition:

• If the control point drives past Setpoint and begins to oscillate significantly above and below Setpoint, reset the I-C setting to the previous (slower) time integral and repeat Step 3.

• If the control point drifts to or past Setpoint and stabilizes near Setpoint, the current I-C setting for your control loop is correct.

Continue to observe the controlled system until you are sure that the system control point stabilizes somewhere near Setpoint and does not oscillate under all load conditions.

Using the Response Time to a Step Change to Determine the I-C Setting

Another method for determining the best I-C setting for a System 450 control loop is to temporarily create a step change that shifts the proportional band in your controlled system away from the original/desired proportional band. To do so, measure the (first response) time it takes for your controlled system to drive to and stabilize at the shifted control point. Then shift (step change) the proportional band back to original and measure the (second response) time that it takes to return to the original control point.

You need a digital voltmeter set to VDC to perform this procedure.

To determine the best I-C setting for a control loop using:

1. Set up the System 450 analog output for proportional-only control (I-C setting of 0 [zero]), power your controlled system on, operate the system under steady load conditions, and allow the control loop to stabilize at a control point within the proportional band between the selected Setpoint and End Point values.

2. Connect a digital volt-meter across the analog output terminals to measure VDC signal strength changes. Measure and record the signal strength voltage at this (original) stable control point.

3. Change the Setpoint and End Point values to shift (step change) the proportional band 25% away from the original proportional band; the VDC signal rises (or drops) immediately and significantly in response to the proportional band shift. Begin timing the response (to the first step change) at this voltage rise (or drop).

50

Page 51: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Note: The direction of the voltage changes (rise or drop) depends on whether the analog output is set up as a direct-acting or reverse-acting output signal. These instructions refer to the room heating application example shown in Figure 27.

4. Observe the system response and record the time it takes for the measured voltage to drive to and stabilize at the shifted control point in the shifted proportional band. (Typically the shifted control point voltage is slightly higher [or lower] than the original control point voltage.)

5. With the controlled system stabilized at the shifted control point, return (second step change) the Setpoint and End Point values back to the original proportional band. The signal VDC drops (or rises) immediately and significantly in response to the proportional band shift back to original. Begin timing the response (to the second step change) at this voltage drop (or rise).

6. Observe the system response and record the time it takes for the measured voltage to drive back to and stabilize at original control point (voltage) in the original proportional band.

Figure 27: Graph Showing Temporary Proportional Band and Control Point Shifts Used to Measure Response Time in a Heating Application

66°FSP

EP

70°F

ProportionalBand

67°F

Shift

ed E

P

71°F

Shift

ed S

P

0%

100%

ShiftedControl Point

Measure the (first response) time that it takes for the controlled system to drive from the original control pointto the shifted control point and then measure the ( ) time for the system to drive fromthe shifted control point back to the original control point. Use the slower response to determine the proper I-C.

second response

10 VDC

0 VDC

Ana

log

Out

put V

olta

ge

Sys

tem

Out

put

OriginalControl Point

Condition Value(and Time)

VDCRise

Fig:

sys4

50_c

ntrl_

pont

_shf

t

51

Page 52: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Note: In many applications, the response time away from the original control point to the shifted control point is different from the response time of the shifted control point back to the original control point, depending on a variety of factors such as system load and system output. Choose the slower of the two measured response times to determine the I-C setting for your application.

7. Use the slower of the two measured response times and the following table to determine which integration constant (I-C setting) to set on the control and test first.

8. Set the integration constant to the determined I-C setting. Operate and observe the controlled system at a variety of load conditions to determine if the system is stable at the determined I-C setting over the entire output range of the controlled system.

Setting up Reset Control Module OutputsAfter setting up the input sensors for your System 450 reset control system, you can reference them as you set up the reset setpoint and/or outputs. This section also explains how to set the time, day, and schedule. If you have the standard control module, see Setting up Standard Control Module Outputs on page 42.

Setting up the Temperature or Humidity Reset Setpoint

System 450 reset control modules allow you to set up outputs in your control system with temperature or humidity reset control capability.

The temperature or humidity reset control uses an algorithm to calculate and adjust (reset) the setpoint for a temperature or humidity control loop based on changes in ambient outdoor temperature or other uncontrolled condition temperature.

Figure 28 on page 53 shows an example of a simple temperature reset control application used to control either boiler or chiller supply-water temperature. Figure 12, Figure 13, and Figure 14 also show reset control applications.

Table 7: Response Times, Reset Rates, and Integration ConstantsSlowest Measured Response Time for Control Point Shift

Select This Integration Constant (I-C) Value for the Analog Output

Estimated Total Reset Rate for Integration Constant

N/A 0 No reset rate

10 to 15 minutes 1 1 hour (3,600 seconds)

6 to 10 minutes 2 30 minutes (1,800 seconds)

3 to 6 minutes 3 15 minutes (900 seconds)

1 to 3 minutes 4 5 minutes (300 seconds)

30 to 60 seconds 5 2 minutes (120 seconds)

10 to 30 seconds 6 1 minute (60 seconds)

52

Page 53: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

When the ambient or uncontrolled temperature (sensed at the master sensor [Sn-1]), rises or lowers, the reset control module calculates a proportional adjustment that lowers or raises the supply-water temperature control setpoint (Reset Setpoint [RSP]). A second sensor (Sn-2) senses the supply loop/output temperature. The reset control calculates and generates the output signal response that is required to drive the supply/output temperature to the reset setpoint temperature (RSP).

Reset control logic regulates a supply temperature or humidity based on outdoor air temperature to allow proper capacity of the supply to heat, cool, dehumidify, or humidify the desired space or environment. Common temperature reset applications are boiler-water temperature reset based on ambient outdoor air temperature, and chilled-water temperature reset based on outdoor air temperature. You can also apply temperature reset to Variable Air Volume (VAV) zone temperature control systems and a variety of other temperature and humidity control applications.

System 450 reset control modules allow you to set up a wide variety of temperature reset control systems. To set up a System 450 temperature reset control system you must do following:

1. Set up the master temperature sensor (Sn-1 in the System 450 UI). See Setting up a System 450 Control System on page 37 for information and procedures.

2. Set up the output/supply temperature sensor (Sn-2 in the System 450 UI). See Setting up a System 450 Control System on page 37 for information and procedures.

3. Set up the Reset Setpoint (RSP) using the Reset Sensor (rES in the System 450 reset control module UI). See the following information and procedures.

Figure 28: Example Boiler or Chilled Water Temperature Reset Application

FIG

:BCW

S _R

st

MasterTemperature

Sensor(Sn-1)

Supply WaterTemperature

Sensor(Sn-2)

Controlled Equipment (Boiler or Chiller)

Supply Water

Return Water

Relay or Analog Temperature ResetControl Signal to Boiler or Chiller

Temperature ResetControl

Control resets supply watertemperature setpoint based on the temperature sensedat Master Sensor.

Controlled equipment cycles or modulatesbased on reset setpoint and the sensedsupply water temperature.

53

Page 54: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

ller Water eters

re

re

point

d 110°F. int is 110°F..

45°F. int is 45°F.F.

ater Supply

Water Supply

FIG

:sys4

50_R

SP_s

tp

n Sn-1

e]

ture

ture

e]

one air78°F.mperature

perature

FIG

:CW

S _R

st

Setting up the Reset Setpoint

In the System 450 reset control module UI, the Reset Setpoint is defined by the:

• Minimum Reset Setpoint (MNSP) value and the Maximum Reset Setpoint (MXSP) value

• Reset Setpoint Start Temperature (RSTR) value and the Reset Setpoint End Temperature (RENd) value

Figure 29 and Figure 30 illustrate the relationship between the temperature sensed at the master sensor and the reset setpoint temperature.

Figure 29: Example Reset Setpoint Applications for Boiler Water Supply and ChiSupply Showing the Relationships between the Reset Setpoint Setup Param

(See Figure 5 and Figure 31 for implementation details.)

MNSP11045

MXSP180

RSTR50

RENd 0

= Minimum Reset Setpoint ( [°F] BWS Temperature) (

= Maximum Reset Setpoint ( [

= Reset Setpoint Start Temperatu ( [

= Reset Setpoint End Temperatu ( [

[°F] CWS Temperature)

°F] BWS Temperature)( [°F] CWS Temperature)

°F] Outdoor Air for BWS)( [°F] Outdoor Air for CWS)

°F] Outdoor Air for BWS) ( [°F] Outdoor Air for CWS)

= Calculated (Floating) Reset Set

From 0 to 50°F outdoor air, the (BWS) setpoint is reset between 180 anAbove 50°F outdoor air, the BWS setpoBelow 0°F outdoor air, the BWS is 180°F

From 75 to 95°F outdoor air, the (CWS) setpoint is reset between 60 andAbove 95°F outdoor air, the CWS setpoBelow 75°F outdoor air, the CWS is 60°

60

95

75

RSP

Boiler W

Chiller

Tem

pera

ture

at S

n-2

(at S

uppl

y W

ater

Sen

sor)

Temperature at Sn-1 (Master Sensor/Outdoor Air)

MXSP180 (°F) BWS60 (°F) CWS

MNSP110 (°F) BWS45 (°F) CWS

RENd0 (°F) for BWS

75 (°F) for CWS

RSTR50 (°F) for BWS95 (°F) for CWS

HIGHERLOWER

HIGHER

Res

et S

etpo

int

Ran

ge

Outdoor TemperatureReset Control Range

RSP

Figure 30: Graph Showing an Example of Zone Air Temperature Reset Based oOutdoor Air Temperature

MNSP

MXSP

RSTR

REND

= Minimum Reset Setpoint [72 (°F) Zone Air Temperatur

= Maximum Reset Setpoint [78

= Reset Setpoint Start Tempera [80

= Reset Setpoint End Tempera [100

(°F) Zone Air Temperatur

(°F) Outdoor Air]

(°F) Outdoor Air]

• Between 80 and 100°F outdoor air, ztemperature is reset between 72 and • Above 100°F outdoor air, zone air tesetpoint is 78°F.• Below 80°F outdoor air, zone air temsetpoint is 72°F.Temperature at Sn-1 (Master Sensor/Outdoor Air)

MXSP78 (°F)

MNSP72 (°F)

REND100 (°F)

RSTR80 (°F)

HigherLower

Higher

Res

et S

etpo

int

Ran

ge

Ambient TemperatureReset Control Range

RSP

Tem

pera

ture

at S

n-2

(Zon

e Ai

r Sen

sor)

54

Page 55: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

The temperature reset setpoint is adjusted (proportionally) over the defined setpoint range by entering the ambient/uncontrolled temperature values that you want to correspond with the MNSP and MXSP values. Two values are available:

• Reset setpoint Start temperature (RSTR): ambient/uncontrolled temperature value (sensed at the master sensor) that corresponds with the Minimum Setpoint value (MNSP).

• Reset setpoint End temperature (RENd): ambient/uncontrolled temperature value (sensed at the master sensor) that you want to correspond with the Maximum Setpoint (MXSP).

You can also set up temperature limits to turn outputs Off at specified high and/or low temperatures. Two values are available:

• Shutdown High temperature value (SdHI): turns the referenced outputs off when the temperature sensed at the master sensor increases to the Shutdown High temperature value; thereby, MNSP is not maintained. As Figure 29 indicates, you can set a SdHI temperature greater than RSTR.

• Shutdown Low temperature value (SdLO): turns the referenced outputs off when the temperature sensed at the master sensor decreases to the Shutdown Low temperature value; thereby, MNSP is not maintained. As Figure 30 indicates, a VAV zone air temperature reset application can use a SdLO valve.

And lastly, you can set up an unoccupied setback value and/or select load balancing.

• Setback (SbK): positive or negative value that is added to the setpoint during the unoccupied period to provide for energy savings. The unoccupied Setback value (RSP + SbK) is referenced during all scheduled unoccupied times. To use the Setback feature in your control system, you must also set up the time and day of week. See Setting Time and Day. For a weekly occupied/unoccupied schedule, see Setting up an Occupied/Unoccupied Schedule.

• Load Balancing (bAL): On (enabled) or Off (disabled) are the selections. If you select On, load balancing is used to distribute runtime between pieces of equipment. The output that has the lowest runtime hours is the next one to be turned on, whereas the output with the highest runtime hours is the next one to be turned off. Load Balancing is not available for analog outputs.

To set up the Reset Setpoint (RSP):

1. Power the reset control module assembly On.

2. Press and hold and simultaneously for 5 seconds. The Sensor Setup Start (SENS) screen appears.

3. Press once to go to the Reset Setpoint Setup Start (RSET) screen (Figure 31).

Note: You cannot select values in any System 450 Setup Start screens.

M

55

Page 56: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

4. Press to go to the next screen (Figure 31).

5. In the Select Minimum Reset Setpoint (MNSP) screen, press or repeatedly to scroll through and select the minimum reset setpoint value. Then press to save the MNSP value and go to the next screen (Figure 31).

6. In the Select Maximum Reset Setpoint (MXSP) screen, press or repeatedly to scroll through and select the maximum reset setpoint value. Then press to save the MXSP value and go to the next screen (Figure 31).

7. In the Select Reset Setpoint Start Temperature (RSTR) screen, press or repeatedly to scroll through and select the desired start value for the reset

temperature range sensed at the master sensor. Then press to save the selected reset start temperature value and go to the next screen (Figure 31).

8. In the Select Reset Setpoint End Temperature (RENd) screen, press or repeatedly to scroll through and select the desired end value for the reset temperature range sensed at the master sensor. Then press to save the selected reset end temperature value and go to the next screen (Figure 31).

9. In the Select Shutdown High Temperature (SdHI) screen, press or repeatedly to scroll through and select the Shutdown High temperature value. (For many applications, you can keep this set to --.) Then press to save the selected shutdown high temperature value and go to the next screen (Figure 31).

Note: When the uncontrolled temperature, sensed at the master sensor, rises above the Shutdown High temperature (see Figure 29), all of the outputs in the control system that reference the Reset Setpoint sensor (rES) turn Off; thereby MNSP is not maintained.

Figure 31: Reset Setpoint Setup Screens

56

Page 57: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

10. In the Select Shutdown Low Temperature (SdLO) screen, press or repeatedly to scroll through and select the shutdown low temperature value. (For many applications, you can keep this set to --.) Then press to save the selected shutdown low temperature value and go to the next screen (Figure 31).

Note: When the uncontrolled temperature, sensed at the master sensor, drops below the Shutdown Low temperature (see Figure 30), all of the outputs in the control system that reference the Reset Setpoint sensor (rES) turn Off; thereby, MNSP is not maintained.

11. In the Select Unoccupied Setback (SbK) screen, press or repeatedly to scroll through and select the Setback value for the output. Then press to save the selected setback value and go to the next screen.

Note: If you select a Setback value, all of the outputs that reference the Reset sensor (rES) use the selected setback value according the occupied/unoccupied setback schedule you set up for the control system. During unoccupied time periods, the setback is added to RSP, with the restriction that RSP never exceed MXSP, nor be less than MNSP. See Setting up an Occupied/Unoccupied Schedule on page 69 for more information.

12. In the Select Load Balancing Mode (bAL) screen, press or to select either On or Off. Then press to save the load balancing mode selection and return to the Reset Setpoint Setup Start (RSET) screen (Figure 31).

The Reset Setpoint sensor is now set up and can be selected in the Sensor Selection screens as you set up the outputs in your System 450 reset control system.

Setting up a Standard Relay Output with Unoccupied Setback

System 450 reset control modules allow you to set up Relay Outputs with a setback temperature or humidity value that is applied during the unoccupied times of the weekly occupied/unoccupied schedule.

Note: System 450 outputs apply setback values only during the unoccupied times of the control system’s occupied/unoccupied schedule. You must also set up a weekly occupied/unoccupied schedule for the control system to apply an unoccupied setback value to an output. See Setting up an Occupied/Unoccupied Schedule on page 69 for more information on setting up a weekly occupied/unoccupied schedule.

Relay Outputs provide single and multiple stage on/off control to controlled equipment. When you supply power to a module assembly, the control module polls all of the connected modules, detects any relay outputs, and then assigns an output number and enables a Relay Output Setup Start (OUTRx) screen for each relay output detected (Figure 22 on page 43). See Relay Outputs on page 15 for more information.

57

Page 58: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Note: The condition (temperature or humidity), unit of measurement, minimum differential value, default setup values, condition value ranges available in the output setup screens are determined by the Sensor Type of the input sensor that you select for the output. See Table 4 on page 20 for more information on Sensor Types and their associated values and ranges.

The Relay ON (ONx) screen and Relay OFF (OFFx) screen allow you to select the condition values at which the relay turns On and turns Off. The first time you access the Relay ON (ONx) and Relay OFF (OFFx) screens, the default ON and OFF values appear.

Selecting an ON value less than the OFF value (ON < OFF) turns the relay On when the condition value decreases (which is the typical heating mode in temperature applications and referred to as reverse-acting on/off control).

Selecting an ON value greater than the OFF value (ON > OFF) turns the relay On when the condition value increases (which is the typical cooling mode in temperature applications and referred to as direct-acting on/off control).

The minimum differential value for the condition is determined by the Sensor Type of the input sensor that an output references. The minimum differential is fixed and is automatically enforced in the setup UI when you select ON and OFF values; the condition values within the minimum differential range are not available to select.

The Minimum Relay ON Time and Minimum Relay OFF Time screens provide anti-short-cycling control for system equipment by allowing you to delay the shutdown or start-up for up to 300 seconds (5 minutes) after the ON or OFF value is reached.

To set up a standard Relay Output with Unoccupied Setback:

1. Power the reset control module assembly On.

2. Press and hold and simultaneously for 5 seconds. The Sensor Setup Start (SENS) screen appears.

58

Page 59: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

3. Press repeatedly to go to a Relay Output Setup Start screen (Figure 32).

4. In the Relay Output Setup Start (OUTRx) screen, press . The Select Input Sensor screen does not appear if an input sensor is already selected for the output. Then go to Step 6.

5. In the Select Input Sensor (SENSx) screen, press or to select the input sensor (Sn-1, Sn-2, Sn-3, or rES) that the output references. If sensor rES is selected, see Setting up a Relay Output with Temperature Reset Control and Unoccupied Setback on page 64. Press to save the sensor selection (Sn-1, Sn-2, or Sn-3) and go to the next screen.

6. In the Select Relay ON Value (ONx) screen, press or to select the temperature value at which the relay turns On. Press to save the ON value and go to the next screen.

7. In the Relay OFF Value (OFFx) screen, press or to select the temperature value at which the relay turns Off. Press to save the OFF value and go to the next screen.

8. In the Minimum Relay ON Time (ONTx) screen, press or to select the minimum number of seconds that the relay stays On after the Relay ON value is reached. Press to save the Minimum ON value and go to the next screen.

9. In the Minimum Relay OFF Time (OFFTx) screen, press or to select the minimum number of seconds that the relay stays Off after the Relay OFF value is reached. Press to save the Minimum OFF value and go to the next screen.

M

Figure 32: Relay Output with Unoccupied Setback Setup Screens

FIG

:sys

450U

I_rly

out_

unoc

c_se

tbk_

stup

4

Select Unoccupied

SetbackValue

UnoccupiedSetback is 4ºF

M

M

System/OutputSetup Screens

59

Page 60: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

10. In the unoccupied Setback (SbKx) screen, press or to select the temperature or humidity setback value that is added to the Relay ON value and Relay OFF values during unoccupied times (see example in Figure 33). The setback may be a positive or negative value. The occupied and unoccupied times are set up in the system’s weekly occupied/unoccupied schedule. To use the Setback feature in your control system, you must also set up the time and day of week. See Setting Time and Day. For a weekly occupied/unoccupied schedule, see Setting up an Occupied/Unoccupied Schedule. Press to save the Unoccupied Setback value and go to the next screen.

11. In the Sensor Failure Mode (SNFx) screen, press or to select whether the output relay stays On or Off when a sensor failure is detected. Press to save the Sensor Failure Mode value and go to the next screen.

12. In the Edit Input Sensor screen:

• If the displayed input sensor (Sn-1, Sn-2, or Sn-3) is the correct input sensor for the output relay, the output setup is complete. Press to go to the Relay Output Setup Start screen.

Figure 33: Occupied and Unoccupied Modes Example

OFF to ON

ON to OFF

OccupiedMode

Zone AirSensor Sn-2

UnoccupiedMode

Description:

Summary of UI Setup Screens:

In this example, occupied mode is controlled by the parameters entered on the OUTR1 Relay OutputSetup screen (see Figure 28). When Sn‐2 climbs to 78°F, OUTR1 turns ON and remains ON until the temperature falls to 75°F. The parameters entered in the schedule, along with the current time, determine the occupied/unoccupied mode. As shown, Day 1 OC‐1 (Occupied) is set to 8:00 AM and UN‐1 (Unoccupied) is set to 8:00 PM. These same parameters are entered for each day of the 7 day schedule. The SbK1 parameter is set to 4°F as indicated in Figure 28. During occupied time from 8:00 AM to 8:00 PM, zone temperature ON and OFF points are 78°F and 75°F (respectively).During unoccupied time, zone temperature ON and OFF points are 82°F and 79°F (respectively).

OFF

ON

FIG

:occ

_uno

cc

7776 7975 7874 8180 8382 °F

Output 1

Output 1

OC‐1AM

8:00

UN‐1PM

8:00

OC‐2AM UN‐2PM

8:00

OC‐7AM

8:00

UN‐7PM

–  ‐

SCHE

8:00

Day 1 Day 2 Day 7

OFF to ON

ON to OFF

8:00

60

Page 61: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

• If the displayed input sensor (Sn-1, Sn-2, or Sn-3) is not the correct input sensor for the output relay, press or to select the correct input sensor. Press to save the new input sensor selection and go to the Relay Output Setup Start screen. Press again to go to the Relay ON Value screen and repeat Step 5 through Step 12 for the new input sensor.

The relay output with setback is set up and saved in the reset control module. To navigate to the next Output Setup Start screen, press . If you have completed the control system setup, press and simultaneously to return to the Main screens.

Setting up a Standard Analog Output with Unoccupied Setback

System 450 reset control modules allow you to set up a standard analog output to provide proportional analog control signals to controlled equipment based on the sensed conditions. When you supply power to a module assembly, the control module polls all of the connected modules, detects any analog outputs, and then assigns an output number and enables an Analog Output Setup Start screen for each analog output detected (Figure 25 on page 46). See Analog Outputs on page 15 for more information.

Note: The condition (temperature or humidity), unit of measurement, minimum differential value, default setup values, condition value ranges available in the output setup screens are determined by the Sensor Type of the input sensor that you select for the output. See Table 3 on page 20 for more information on Sensor Types and their associated values and ranges.

The Setpoint (SPx) and End Point (EPx) screens allow you to set up a proportional band (or throttling range) for the control loops in your controlled system. The Output at Setpoint (OSPx) and Output at End Point (OEPx) screens allow you to select the output signal strength (as a percentage of the total signal strength range) that an analog output sends to the controlled equipment at Setpoint and End Point.

The relationship between these four setup values (SP, EP, OSP, and OEP) determines the analog output’s proportional control action, which is indicated on the control module LCD by the control ramp indicator. See Direct and Reverse Control Actions on page 16 for more information.

The unoccupied Setback (SbKx) screen allows you to specify a positive or negative value that is added to the setpoint during the unoccupied period to provide for energy savings. The unoccupied Setback value (SP + SbK and EP + SbK) is referenced during all scheduled unoccupied times. To use the Setback feature in your control system, you must also set up the time and day of week. See Setting Time and Day. For a weekly occupied/unoccupied schedule, see Setting up an Occupied/Unoccupied Schedule.

M

61

Page 62: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

The Integration Constant (I-Cx) screen allows you to select an integration constant for the analog signal. Selecting an integration constant other than 0 enables proportional plus integral control action, which in many applications can drive the condition closer to Setpoint (than proportional-only control action). See Proportional Plus Integral Control and Integration Constants on page 18 for more information. See Determining the Integration Constant for an Analog Output on page 49 for procedures on determining and testing integration constants.

The Sensor Failure Mode (SNFx) screen allows you to select whether the analog output signal will be set to its On or Off value when a failure of the referenced input sensor is detected. The On value is the OEP value. The Off value is the OSP value.

To set up a standard analog output with unoccupied setback:

1. Power the reset control module assembly On.

2. Press and hold and simultaneously for 5 seconds. The Sensor Setup Start (SENSx) screen appears.

3. Press repeatedly to go to the Analog Output Setup Start screen (Figure 34).

4. In the Analog Output Setup Start (OUTAx) screen, press . The Select Input Sensor (SENS) screen does not appear if an input sensor is already selected. If already selected, go to Step 6.

5. In the Select Input Sensor (SENSx) screen, press or to select Sn-x. Press to save the sensor selection and go to the next screen.

M

Figure 34: Analog Output with Unoccupied Setback Setup Screens

62

Page 63: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

6. In the Select Setpoint (SPx) screen, press or to select the control setpoint for OUTA-x. Press to save the setpoint value and go to the next screen.

7. In the Select End Point (EPx) screen, press or to select the desired end point value. Press to save the end point value and go to the next screen.

8. In the Select Output Signal Strength at Setpoint (OSPx) screen, press or to select the value in percent of the output signal strength (0-100%),

corresponding to the lowest output capacity, when the sensor is at the Setpoint (SPx). Press to save the OSP value and go to the next screen.

9. In the Select Output Signal Strength at End Point (OEPx) screen, press or to select the value in percent of the output signal strength (0-100%),

corresponding to the highest output capacity, when the sensor is at the End point (EPx). Press to save the OEP value and go to the next screen.

10. In the unoccupied Setback Temperature (SbKx) screen, press or to select the temperature or humidity setback value that is added to the SP value (SP+SbK) and EP value (EP+SbK) to calculate a setback proportional band that this output references during the unoccupied times. The occupied and unoccupied times are set up in the system’s weekly occupied/unoccupied schedule. Press to save the Unoccupied Setback value and go to the next screen.

11. In the Integration Constant (I-Cx) screen, press or to select an integration constant to provide proportional plus integral control for the analog output. Initially, select the I-C value of 0 (zero) for no integration constant. To help you select an appropriate constant value, see Determining the Integration Constant for an Analog Output on page 49. Press to save the integration constant and go to the next screen.

12. In the Sensor Failure Mode (SNFx) screen, press or to select whether the analog output signal is set to its On or Off value when a sensor failure is detected. The On value is the OEP value. The Off value is the OSP value. Press

to save the sensor failure mode value and go to the next screen. See Sensor Failures on page 21 for more information.

13. In the Edit Sensor Selection (SENSx) screen, press or to change the sensor that this output references (only if required). Then press to go to the output’s setup start screen.

Note: If you change the sensor that an output references to a sensor with a different Sensor Type, the default setup values for the output also change, which requires you to once again set up the output.

The analog output with reset control is set up and saved in the reset control module. To navigate to the next Output Setup Start screen, press . If you have completed the control system setup, press and simultaneously to return to the Main screens.

M

63

Page 64: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Note: If the TIME and SCHE Setup screens have been programmed, unoccupied setback (using the Sbk value in the RSET Setup screens) automatically occurs on all relays and analog outputs using the RES sensor.

Setting up a Relay Output with Temperature Reset Control and Unoccupied Setback

System 450 reset control modules allow you to set up outputs controlled by a temperature or humidity reset setpoint. See Setting up the Temperature or Humidity Reset Setpoint on page 52 for information on setting up the Reset Setpoint on System 450 reset control modules.

Relay outputs with reset control reference the Reset Setpoint (RSP) to control the on/off output signal. In cases where the offset (OSET) is 0 at the Reset Setpoint value, the output relay is On. The output relay turns Off at the Reset Setpoint plus the Differential from Reset Setpoint value.

To set up a relay output with temperature reset control and unoccupied setback:

1. Power the reset control module assembly On.

2. Press and hold and simultaneously for 5 seconds. The Sensor Setup Start screen appears.

3. Press repeatedly to go to an Relay Output Setup Start (OUTRx) screen (Figure 35).

4. In the Relay Output Setup Start (OUTRx) screen, press . The Select Input Sensor (SENS) screen does not appear if an input sensor is already selected. If already selected, go to Step 6.

5. In the Select Input Sensor (SENSx) screen, press or to select rES to enable reset control. Press to save the rES selection and go to the next screen.

M

Figure 35: Relay Output with Temperature Reset Control Setup Screens

FIG

:sys4

50U

I_rly

out_

tmp_

rset

_stu

p

M

M

System/OutputSetup Screens

5

64

Page 65: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

6. In the Select Differential from Reset Setpoint (dIFFx) screen, press or to scroll to and select the desired differential from the reset setpoint. Press to save the differential value and go to the next screen.

Note: The Differential from Reset Setpoint value defines the range between relay On and relay Off. The differential from reset setpoint can be a positive or negative value. A positive differential provides direct acting control, whereas a negative differential provides reverse acting control. See Figure 15 and Figure 16 for examples.

7. In the Select Temperature Offset (OSETx) screen, press or to scroll to and select the desired temperature (only) offset value. Press to save the temperature offset value and go to the next screen.

Note: The temperature offset value is applied to the entire reset setpoint range (reset setpoint through differential from reset setpoint value).

8. In the Select Minimum Relay ON Time (ONTx) screen, press or to select the minimum number of seconds that the relay stays On after the Relay ON value is reached. Press to save the minimum On-time value and go to the next screen.

9. In the Select Minimum Relay OFF Time (OFFTx) screen, press or to select the minimum number of seconds that the relay stays Off after the Relay OFF value is reached. Press to save the minimum Off-time value and go to the next screen.

10. In the Select Sensor Failure Mode (SNFx) screen, press or to select whether the output relay stays On or Off when a sensor failure is detected. Press to save the Sensor Failure Mode value and go to the next screen.

11. In the Edit Input Sensor (SENSx) screen:

• If the displayed input sensor is rES, the output set up is complete. Press to go to the Relay Output Setup Start screen.

• If the displayed input sensor is not rES, press or to select rES. Press to save the new rES input sensor selection and go to the Relay Output

Setup Start screen. Press again to go to the Select Input Sensor screen and repeat Step 5 through Step 11 for the new rES input sensor.

The relay output with reset is set up and saved in the reset control module. To navigate to the next Output Setup Start screen, press . If you have completed the control system setup, press and simultaneously to return to the Main screens.

Note: If the TIME and SCHE Setup screens have been programmed, unoccupied setback (using the Sbk value in the RSET Setup screens) automatically occurs on all relays and analog outputs using the RES sensor.

M

65

Page 66: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Setting up an Analog Output with Reset Setpoint Control and Unoccupied Setback

System 450 reset control modules allow you to set up analog outputs controlled by a reset setpoint. See Setting up the Temperature or Humidity Reset Setpoint on page 52 for information on setting up the Reset Setpoint on System 450 reset control modules.

Analog outputs with reset control reference the Reset Setpoint (RSP) to control the output signal strength.

To set up an analog output with temperature reset control and unoccupied setback:

1. Power the reset control module assembly On.

2. Press and hold and simultaneously for 5 seconds. The Sensor Setup Start (SENSx) screen appears.

3. Press repeatedly to go to the Analog Output Setup Start screen (Figure 36).

4. In the Analog Output Setup Start (OUTAx) screen, press . The Select Input Sensor (SENS) screen does not appear if an input sensor is already selected. If already selected, go to Step 6.

5. In the Select Input Sensor (SENSx) screen, press several times to select rES to enable reset control. Press to save the sensor selection and go to the next screen.

6. In the Select Proportional Band (Pbx) screen, press or to select the proportional band for the sensor. Press to save the value and go to the next screen.

M

Figure 36: Analog Output with Temperature Reset Control Setup Screens

66

Page 67: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

7. In the Select Temperature Offset (OSETx) screen, press or to select the desired temperature (only) offset value. Press to save the temperature offset value and go to the next screen.

8. In the Select Output Signal Strength at Setpoint (OSPx) screen, press or to select the strength of the signal that the output generates when the sensed

condition is at its setpoint (RSP + OSETx). The signal strength range is 0 to 100 (%). Press to save the percentage value and go to the next screen.

9. In the Select Output Signal Strength at End Point (OEPx) screen, press or to select the strength of the signal that the output generates when the sensed condition is at its End Point value (RSP + Pbx + OSETx). The signal strength range is 0 to 100 (%). Press to save the percentage value and go to the next screen.

10. In the Select Integration Constant (I-Cx) screen, press or to select an integration constant to provide proportional plus integral control for the analog output. Initially, select the I-C value of 0 (zero) for no integration constant. To help you select an appropriate constant value, see Determining the Integration Constant for an Analog Output on page 49. Press to save the integration constant and go to the next screen.

11. In the Select Sensor Failure Mode (SNFx) screen, press or to select whether the analog output signal is to be set to its On or Off value when a sensor failure is detected. The On value is the OEP value. The Off value is the OSP value. Press to save the sensor failure mode value and go to the next screen.

12. In the Select Edit Sensor Selection screen, press or to change the sensor that this output references (only if required). Then press to go to the output’s setup start screen.

Note: If you change the sensor that an output references to a sensor with a different Sensor Type, the default setup values for the output also change, which requires you to once again set up the output.

The analog output with reset control is set up and saved in the reset control module. To navigate to the next Output Setup Start screen, press . If you have completed the control system setup, press and simultaneously to return to the Main screens.

Note: If the TIME and SCHE Setup screens have been programmed, unoccupied setback (using the Sbk value in the RSET Setup screens) automatically occurs on all relays and analog outputs using the RES sensor.

M

67

Page 68: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Setting Time and DaySystem 450 reset control modules include a real-time clock that allows you to control outputs based on time of day and day of week. A typical control scenario enables a setback temperature (or humidity) based on the time or day when the controlled space is occupied and unoccupied. Before you can set up an occupied/unoccupied schedule, you must set the real time clock to the proper time and day of week.

To set the current time and day on a System 450 Reset Control Module:

1. Power the reset control module assembly On.

2. Press and hold and simultaneously for 5 seconds. The Sensor Setup Start screen appears.

3. Press repeatedly until the Time and Day Setup Start screen appears (Figure 37).

4. In the Time and Day Setup Start screen, press to go to the next screen.

5. In the Clock Setup screen, press the:

• to select the 24 hour clock display

• to select the 12 hour (AM/PM) clock display

6. Press to save your Clock Setup selection and go to the next screen.

7. In the Set Time screen, press or repeatedly to scroll (in 1-minute increments) to the desired time of day setting.

Note: Pressing and holding or allows you to scroll through the time values in 15-minute increments.

8. Press to save your time of day selection and go to the next screen.

9. In the Set Day screen, press or repeatedly to scroll to the desired day value.

Note: A Set Day value of 1 is Monday, 2 is Tuesday, 3 is Wednesday, and so on to 7, which is the Set Day value for Sunday. See Figure 38.

10. Press to save your Set Day selection and return to the Time and Day Setup Start screen.

M

Figure 37: Reset Control’s Time and Day Setup Screens

FIG

:sys

450U

I_rs

t_tm

e_stu

p.de

sTime and DaySetup Start Screen

Clock SetupScreen

Time SetupScreen

Day SetupScreen

12 Hour ClockSelected

Time Set to 12:15 PM

Day 1 (Monday)Selected

TIME- - -

68

Page 69: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

4:00

UN 6PM

12:00

OC 7AM

:

UN 7AM

Sunday

Day 7

aturday

Day 6

16:00

UN 6

:

OC 7

0:00

UN 7

n will run

UnoccupiedMode

for the entire day

occupied

Mode

ccupied

mode

09:15

06:00

12:00

18:00

Unoccupied

Mode

upiedMode

ht 9:15AM

piedMode

M 4:00PM

upiedMode

Midnight

edule r)

Setting up an Occupied/Unoccupied ScheduleSystem 450 reset control modules allow you to enable a temperature or humidity setback value according to an occupied/unoccupied schedule on some or all of the outputs in your reset control system. To specify setback for a heating system, enter a negative number for SbK. To specify setup for a cooling system, enter a positive number for SbK.

You can set up a weekly occupied/unoccupied schedule by setting up an occupied and unoccupied time for each day of the week. (1 = Monday, 2 = Tuesday, and so on to 7 = Sunday.) Occupied/unoccupied times are set in 15-minute increments.

Occupied/Unoccupied Setback Modes

Relay Output That References an Input Sensor

See Figure 32. During the occupied time, ON = 78°F (25.5°C) and OFF = 75°F (24°C). During the unoccupied times with SbK = 4F° (2C°), ON changes from 78°F (25.5°C) to 82°F (27.5°C), and OFF changes from 75°F (24°C) to 79°F (26°C).

Analog Output That References an Input Sensor

See Figure 34. During the occupied time, SP = 74°F (23.5°C) and EP = 78°F (25.5°C). During the unoccupied times with SbK = 5F° (2.5C°), the SP changes from 74°F (23.5°C) to 79°F (26°C), and EP changes from 78°F (25.5°C) to 83°F (28°C).

SCHE

7:45

OC 1AM

5:30

UN 1PM

7:45

OC 2AM

5:30

UN 2PM

7:45

OC 3AM

5:30

UN 3PM

7:45

OC 4AM

5:30

UN 4PM

7:45

OC 5AM

4:00

UN 5PM

9:15

OC 6AM

Monday

Day 1

Tuesday

Day 2

Wednesday

Day 3

Thursday

Day 4

Friday

Day 5

S

SCHE

7: 45

OC 1

17: 30

UN 1

7:45

OC 2

17:30

UN 2

7:45

OC 3

17:30

UN 3

7:45

OC 4

17:30

UN 4

7:45

OC 5

16:00

UN 5

9:15

OC 6

SbKx must be entered and a 12 Hour Clock OR 24 Hour Clock must be set up before Occupied/Unoccupied functio

17:30

Unoccupied

Mode

Occupied

mode

17:30

Unoccupied

Mode

Occupied

mode

17:30

Unoccupied

Mode

Occupied

mode

16:00

Unoccupied

Mode

Occupied

mode

16:00

Un

O07:45 07:45 07:45 07:45

Weekly Occupied / Unoccupied Schedule

00:00

6:00

12:00

18:00

24 Hour Clock

12:00

3:00

6:00

9:00

12 Hour Clock

UnoccupiedMode

Midnight 7:45AM

OccupiedMode

7:45AM to 5:30PM

UnoccupiedMode

5:30PM Midnight

17:30

07:45

UnoccupiedMode

Midnight 7:45AM

OccupiedMode

7:45AM to 5:30PM

UnoccupiedMode

5:30PM Midnight

UnoccupiedMode

Midnight 7:45AM

OccupiedMode

7:45AM 5:30PM

UnoccupiedMode

5:30PM Midnight

UnoccupiedMode

Midnight 7:45AM

OccupiedMode

7:45AM 5:30PM

UnoccupiedMode

5:30PM Midnight

UnoccupiedMode

Midnight 7:45AM

OccupiedMode

7:45AM 4:00PM

UnoccupiedMode

4:00PM Midnight

Unocc

Midnig

Occu

9:15A

Unocc

4:00PM

Occupied

mode

Unoccupied

Mode

Figure 38: Example System 450 Weekly Occupied/Unoccupied SchShowing Occupied and Unoccupied Setup Values (12 Hr or 24 H

69

Page 70: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

Relay Output and Analog Output That Reference the Reset Function

See Figure 29 and Figure 30. During the occupied time, the RSP is calculated as shown. See Figure 39; during the unoccupied time with the SbK = -15F° (-8.5C°), the water supply RSP temperature decreases by 15F° (8.5C°).

Multi-stage Cooling That References the Reset Function and Load Balancing Is Set to One

See Figure 15. During the occupied time, the RSP = 72°F (22.5°C). During the unoccupied times with SbK = 4F° (2C°), the RSP changes from 72°F (22.5°C) to 76°F (24.5°C). The load balancing feature is not affected in its function as a result of Occupied/Unoccupied modes.

Multi-stage Cooling That References the Reset Function and Load Balancing Is Set to One

See Figure 16. During the occupied times the RSP = 148°F (64.5°C). During the unoccupied times with SbK = -10F° (-5.5C°), the RSP changes from 148°F (64.5°C) to 138°F (59°C). The load balancing feature is not affected in its function as a result of Occupied/Unoccupied modes.

When you set up an Occupied/Unoccupied schedule on System 450 reset control system, the outputs respond as follows:

• During an Occupied time mode of operation, the outputs are controlled according to the setup values entered for the output (for example, ON, OFF, RSP, dIFF, OSET).

• During an Unoccupied time mode of operation:

• On a standard controller with relay and analog outputs, the setback value (SbKx) entered for each output is added to the relay output ON and OFF values, or added to the analog output setpoint (SP) and end point (EP) values. The UI does not show these new calculated unoccupied values.

• On a reset controller with relay and analog outputs, the setback value (SbKx) entered in the RSET Setup Start screen is added to the calculated RSP to create the new calculated RSP, which includes the setback value.

70

Page 71: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

t

rature

rature

)

)

S)

)

0 and 110°F. etpoint is 110°F.80°F.

et Setpoint

ler Water Supply

FIG

:sys

450_

bwt_

rst_

stbk

_rm

p

Note: The RSP with added setback cannot go below MNSP or above MXSP. See Figure 39.

Note: A negative Setback Temperature (SbK) value subtracts from the ON and OFF values and functions as an unoccupied setback condition in heating mode. A positive Setback Temperature (SbK) value adds to the ON and OFF values and functions as an unoccupied setup condition in the cooling mode. In addition, the unoccupied setback value is subtracted from or is added to the calculated RSP value to create an Unoccupied Reset Setpoint, which is displayed as the RSP value in the UI during scheduled unoccupied times.

Note: To enable the occupied/unoccupied control function for an output, you need to set up an occupied/unoccupied schedule and enter a Setback value (other than 0) for the output. If you do not enter a positive or negative Setback (SbK) value for an output (default is 0), the output controls its signal according to the occupied setting values during both the occupied and unoccupied time periods.

When you set up an Occupied/Unoccupied schedule, consider the following:

• Typically, Day-1 represents Monday, Day-2 represents Tuesday, Day-3 is Wednesday, and so on to Day-7, which represents Sunday (in a typical weekly schedule).

• Occupied/unoccupied time intervals are 15 minutes apart. Press or repeatedly to scroll through the time of day in 15-minute intervals. You can also press and hold or to quickly scroll through the time of day intervals.

• If an entire day needs to be unoccupied, set OC-x to -- and set UN-x to 12:00 AM or 0:00 (where x is the day number). If the entire day needs to be occupied, set OC-x to 12:00 AM or 0:00 and set UN-x to --.

Note: If OC-x time = UN-x time, then the entire day is set as occupied.

Figure 39: Boiler Water Supply Reset Setpoint with a 15°F Setback

Tem

pera

ture

at S

n-2

(at S

uppl

y W

ater

Sen

sor)

Temperature at Sn-1 (Master Sensor/Outdoor Air)

MXSP180 (°F) BWS

MNSP110 (°F) BWS

RENd0 (°F) BWS

RSTR50 (°F) BWS

Actual RSP

MNSP = Minimum Reset Setpoint110

MXSP = Maximum Reset Setpoin180

RSTR = Reset Range Start Tempe50

RENd = Reset Range End Tempe0

( [°F] BWS Temperature

( [

( [

( [

°F] BWS Temperature

°F] Outdoor Air for BW

°F] Outdoor Air for BWS

From 0 to 50°F outdoor air, the (BWS) setpoint is reset between 18Above 50°F outdoor air, the BWS sBelow 0°F outdoor air, the BWS is 1

RSP = Calculated (Floating) Res

Boi

15 (°F) Setback

25 (°F)

New reset schedule when setback is enabled duringunoccupied times.

71

Page 72: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

reens

FIG

:sys4

50U

I_oc

c-un

oc_s

ch_s

tup.

desDay-7

occupiedtup Screen

:

cupied Time2:00 AM

To set up an occupied/unoccupied schedule:

1. Power the reset control module assembly On.

2. Press and hold and simultaneously for 5 seconds. The Sensor Setup Start (SENS) screen appears.

3. Press repeatedly until the Schedule Setup Start (SCHE) screen appears.

4. In the Schedule Setup Start (SCHE) screen, press to go to the next screen.

5. In the Day-1 Occupied Time (OC-1xM) screen, press or to scroll to and select the occupied start time for the Day-1 of the week. Then press to save the occupied time and go to the next screen.

6. In the Day-1 Unoccupied Time (UN-1xM) screen, press or to scroll to and select the unoccupied start time for the Day-1 of the week. Then press to save the unoccupied time and go to the next screen.

7. In the Day-2 Occupied Time (OC-2xM) screen, press or to scroll to and select the occupied start time for the Day-1 of the week. Then press to save the occupied time and go to the next screen.

8. In the Day-2 Unoccupied Time (UN-2xM) screen, press or to scroll to and select the unoccupied start time for the Day-1 of the week. Then press to save the unoccupied time and go to the Day-2 Occupied Time screen.

9. Repeat Step 7 and Step 8 for the remaining 5 days of the week, until you return to the Schedule Setup Start screen.

10. Press to return to the Status Display screen.

The weekly occupied/unoccupied schedule for your System 450 control system is entered and saved.

M

Figure 40: Example of Weekly Occupied/Unoccupied Schedule Setup Sc

Occupied-Unoccupied

Schedule Setup Start Screen

Day-1Occupied

Setup Screen

Day-1Unoccupied

Setup Screen

Day-2Occupied

Setup Screen

Day-2Unoccupied

Setup Screen

-- - :745 :PM

:745AM

M

M Unoccupied Time5:30 PM

Unoccupied Time5:30 PM

Occupied Time7:45 AM

Occupied Time7:45 PM

PM

:745AM PM

:915AM

Day-5Occupied

Setup Screen

Day-5Unoccupied

Setup Screen

Day-6Occupied

Setup Screen

Day-6Unoccupied

Setup Screen

Unoccupied Time4:00 PM

Unoccupied Time4:00 PM

Occupied Time7:45 AM

Occupied Time9:15 AM

Day 3 and Day 4 set up the same as Day 1 and Day 2.Back to StatusDisplay

:

Day-7Occupied

Setup ScreenUn

Se

Occupied TimeNone

Unoc1

----

M

72

Page 73: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

f sensor wiring and oltage between the

S3) and the low-al (with the sensor r the sensor’s he sensor wiring and d, replace the sensor

the +5 VDC (5V) common (C) ltage range is +4.8 to oltage is out of range, ltage. (See the

e is in range, remove 5V terminal and 5V and any C ill out of range,

.8 to +5.2 VDC), at a time to ausing the voltage

nsor and recheck the

the C450 power age must be between 0 VAC terminals, or at the 240 VAC control system is

VAC power supply, n 20 and 30 VAC.

.

Troubleshooting System 450 Control SystemsSystem 450 control modules display error messages when the module detects a sensor, sensor wiring, sensor power, or power supply failure.

Table 8 shows the System 450 error messages that may be displayed, and provides possible causes for the error messages and the solutions for remedying the errors.

Specified Voltage Ranges for SensorsTable 9 provides the specified operating voltage range for System 450 sensors. To determine if a sensor is operating in the specified range, measure the voltage between the sensor’s terminal connections at the System 450 control module (the S1, S2, or S3 terminal and one of the C terminals).

If the voltage is out of the specified range, check the sensor wiring for shorted or open circuits. Repair or replace wiring as needed. If the wiring appears to be in good condition, replace the sensor and retest the voltage and operation.

Table 8: System 450 Control System Error MessagesError Screen Problem/Symptom Possible Cause Solution

Sensor failure is detected and < SNF > is displayed (instead of a value).

Outputs that reference the failed sensor are operating in the Sensor Failure Modes selected for the Output at setup.

Sensor, sensor wiring, or sensor connections may have failed to open or close.

Check and verify integrity oconnections. Measure the vsensor terminal (S1, S2, orvoltage common (C) terminconnected). See Table 9 foexpected voltage range. If tsensor connections are gooand recheck the voltage.

Sensor power drops below 4.75 VDC and < Err 5V > is displayed (instead of a value).

All Outputs are Off.

The +5 VDC output is out of the specified range; the output may be shorted to ground at the wiring or an active humidity or pressure sensor may have failed.

Check the voltage betweenterminal and any one of theterminals. The specified vo+5.2 VDC. If the specified vcheck the primary supply vosolution that follows.)If the primary supply voltagall wiring connection to the check the voltage between terminal. If the voltage is streplace the control module.If the voltage is in range (+4reconnect each sensor onedetermine which sensor is cdrop. Replace the faulty seoutput voltage.

Supply power failure is detected and < Err PWR > is displayed (instead of a value).

All Outputs are Off.

Supply power failure; supply voltage too low voltage or too high.

Check the supply voltage tomodule. The measured volt100 and 130 VAC at the 12between 200 and 260 VACterminals. If the System 450powered by an external 24 the voltage must be betweeBring the supply into range

73

Page 74: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

al (S1, S2,

one relay output

two relay outputs

one analog output

ptional High Input ect primarily used

ides two analog

t; provides one

t; provides two

ay) for SPDT

lays) for SPDT

mA self-selecting

mA self-selecting

AC supply power

Repair InformationTable 10 provides ordering information for the currently available System 450 Series modules.

Table 11, Table 12, Table 13, and Table 14 provide ordering information for the System 450 compatible sensors and transducers. For more information on installing System 450 compatible sensors and transducers, see Related Documentation on page 5

Table 9: Specified Voltage Ranges between Sensor TerminalsConnected Sensor Specified Voltage Range

Measured between a Sensor Terminor S3) and a Common Terminal (C)

A99B Type Temperature Sensors 0.24 to 0.67 VDC

HE-67xx Humidity Sensor 0.35 to 5.0 VDC

DPT2650 Low-Pressure Differential Sensor 0.35 to 5.0 VDC

P499 Series Electronic Pressure Transducer 0.5 to 4.5 VDC

Table 10: System 450 Modules and Accessories Ordering Information (Part 1 of 2)

Product Code Number

Product Description

C450CBN-1C Control Module1 with LCD, Four-Button Touchpad UI, and Relay Output; provides (SPDT line-voltage relay) for SPDT control.

C450CCN-1C Control Module1 with LCD, Four-Button Touchpad UI, and Relay Output; provides (SPDT line-voltage relays) for SPDT control.

C450CPN-1C Control Module1 with LCD, Four-Button Touchpad UI, and Analog Output; provides(0–10 VDC or 4–20 mA self-selecting signal) for proportional control.

C450CPW-100C Control Module1 with LCD, Four-Button Touchpad UI, Hybrid Analog Output and OSignal Select; provides one hybrid analog output and optional high input signal selfor EC motor control.

C450CQN-1C Control Module1 with LCD and Four-Button Touchpad UI, and Analog Output; provoutputs (0–10 VDC or 4–20 mA self-selecting signals) for proportional control.

C450RBN-1C Reset Control Module1 with LCD, Four-Button Touchpad UI, and SPDT relay outpuSPDT output relay.

C450RCN-1C Reset Control Module1 with LCD, Four-Button Touchpad UI, and SPDT relay outpuSPDT output relays.

C450SBN-1C Relay Output Expansion Module; provides one relay output (SPDT line-voltage relcontrol.

C450SCN-1C Relay Output Expansion Module; provides two relay outputs (SPDT line-voltage recontrol.

C450SPN-1C Analog Output Expansion Module; provides one analog output (0–10 VDC or 4–20signal) for proportional control.

C450SQN-1C Analog Output Expansion Module; provides two analog outputs (0–10 VDC or 4–20signals) for proportional control.

C450YNN-1C Power Module; provides 24 V to System 450 Module Assembly; 120 VAC or 240 Vinput terminals.

BKT287-1R DIN Rail; 12 in. (0.30 m) long

BKT287-2R DIN Rail; 39-1/3 in. (1 m) long

74

Page 75: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

3/4 in.

ft

t

or sensor)

BKT287-3R DIN Rail; 24 in. (0.61 m) long

BKT287-4R DIN Rail; 14 in. (0.36 m) long

PLT344-1R DIN Rail End Clamps (2 clamps)

1. All System 450 control modules can control both relay and analog outputs in a control system.

Table 11: System 450 Compatible A99B Temperature Sensors and Accessories Ordering Information

Product Code Number

Product Description

A99BA-200C PTC Silicon Sensor with Shielded Cable; Cable length (2 m) 6-1/2 ftSensor Temperature Range: -40 to 120°C (-40 to 250°F)Cable Jacket Temperature Range: -40 to 100°C (-40 to 212°F)

A99BB-25C PTC Silicon Sensor with PVC Cable; Cable length (0.25 m) 9-3/4 in.Sensor Temperature Range: -40 to 120°C (-40 to 250°F)Cable Jacket Temperature Range: -40 to 100°C (-40 to 212°F)

A99BB-200C PTC Silicon Sensor with PVC Cable; Cable length (2 m) 6-1/2 ftSensor Temperature Range: -40 to 120°C (-40 to 250°F)Cable Jacket Temperature Range:-40 to 100°C (-40 to 212°F)

A99BB-300C PTC Silicon Sensor with PVC Cable; Cable length (3 m) 9-3/4 ftSensor Temperature Range: -40 to 120°C (-40 to 250°F)Cable Jacket Temperature Range:-40 to 100°C (-40 to 212°F)

A99BB-500C PTC Silicon Sensor with PVC Cable; Cable length (5 m) 16-3/8 ftSensor Temperature Range: -40 to 120°C (-40 to 250°F)Cable Jacket Temperature Range: -40 to 100°C (-40 to 212°F)

A99BB-600C PTC Silicon Sensor with PVC Cable; Cable length (6 m) 19-1/2 ftSensor Temperature Range: -40 to 120°C (-40 to 250°F)Cable Jacket Temperature Range: -40 to 100°C (-40 to 212°F)

A99BC-25C PTC Silicon Sensor with High Temperature Silicon Cable; Cable length (0.25 m) 9-Sensor Temperature Range: -40 to 120°C (-40 to 250°F)Cable jacket rated for full sensor temperature range.

A99BC-300C PTC Silicon Sensor with High Temperature Silicon Cable; Cable length (3 m) 9-3/4Sensor Temperature Range: -40 to 120°C (-40 to 250°F)Cable jacket rated for full sensor temperature range.

A99BC-1500C PTC Silicon Sensor with High Temperature Silicon Cable; Cable length (15 m) 49 fSensor Temperature Range: -40 to 120°C (-40 to 250°F)Cable jacket rated for full sensor temperature range.

BOX10A-600R PVC enclosure for A99 sensor; includes wire nuts and conduit connector (for outdo

WEL11A-601R Immersion well for A99 sensor liquid sensing applications

A99-CLP-1 Mounting clip for A99 temperature sensor

ADP11A-600R Conduit adaptor, 1/2 in. snap-fit EMT conduit adaptor (box of 10)

TE-6001-1 Duct mounting hardware with handy box for A99 sensor

TE-6001-11 Duct mounting hardware without handy box for A99 sensor

SHL10A-603R Sun Shield (for use with outside A99 sensors in sunny locations)

Table 10: System 450 Modules and Accessories Ordering Information (Part 2 of 2)

Product Code Number

Product Description

75

Page 76: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

arately.

arately.

arately.

arately.

le

Style

d arately.

read .

le

lications); 1/4 in. A-PKD3 type wire

pplications); 1/4 in. 3-200C wire

le

Style

d arately.

Table 12: System 450 Compatible HE67S3 Type Humidity Sensors with Integral A99B Temperature Sensor Ordering Information

Product Code Number

Product Description

HE-67S3-0N0BT Wall Mount Humidity Sensor with A99B Type Temperature Sensor: 10 to 95% RH;-40 to 121°C (-40 to 250°F)

HE-67S3-0N00P Duct Mount Humidity Sensor with A99B Type Temperature Sensor: 10 to 95% RH;-40 to 121°C (-40 to 250°F)

Table 13: System 450 Compatible Low Pressure Differential Transducer Ordering Information

Product Code Number

Product Description

DPT2650-0R5D-AB Low Pressure Differential Transducer: 0 to 0.5 in. W.C.

DPT2650-10D-AB Low Pressure Differential Transducer: 0 to 10 in. W.C.

Table 14: System 450 Compatible P499 Series Electronic Pressure Transducer and WHA-PKD3 Wire Harness Ordering Information (Part 1 of 2)

Product Code Number

Product Description

P499RCP-401C Electronic Pressure Transducer: -1 to 8 bar; 1/4 in. SAE 45° Flare Internal Thread (7/16-20 UNF) with Depressor (Style 47). Order WHA-PKD3 type wire harness sep

P499RCP-402C Electronic Pressure Transducer: -1 to 15 bar; 1/4 in. SAE 45° Flare Internal Thread(7/16-20 UNF) with Depressor (Style 47). Order WHA-PKD3 type wire harness sep

P499RCP-404C Electronic Pressure Transducer: 0 to 30 bar; 1/4 in. SAE 45° Flare Internal Thread(7/16-20 UNF) with Depressor (Style 47). Order WHA-PKD3 type wire harness sep

P499RCP-405C Electronic Pressure Transducer: 0 to 50 bar; 1/4 in. SAE 45° Flare Internal Thread(7/16-20 UNF) with Depressor (Style 47). Order WHA-PKD3 type wire harness sep

P499RAP-101C Electronic Pressure Transducer: 0 to 100 psig; 1/8 in.-27 NPT External Thread StyOrder a WHA-PKD3 type wire harness separately.

P499RAP-101K Electronic Pressure Transducer Kit: 0 to 100 psig; 1/8 in.-27 NPT External Thread WHA-PKD3-200C wire harness included.

P499RCP-101C Electronic Pressure Transducer: 0 to 100 psig; 1/4 in. SAE 45° Flare Internal Threa(7/16-20 UNF) with Depressor (Style 47). Order WHA-PKD3 type wire harness sep

P499RCP-101K Electronic Pressure Transducer Kit: 0 to 100 psig; 1/4 in. SAE 45° Flare Internal Th(7/16-20 UNF) with Depressor (Style 47). WHA-PKD3-200C wire harness included

P499RAP-102C Electronic Pressure Transducer: 0 to 200 psig; 1/8 in.-27 NPT External Thread StyOrder a WHA-PKD3 type wire harness separately.

P499RCPS102C Electronic Pressure Transducer: 0 to 200 psis (sealed for wet and freeze/thaw appSAE 45° Flare Internal Thread (7/16-20 UNF) with Depressor (Style 47). Order WHharness separately.

P499RCPS102K Electronic Pressure Transducer Kit: 0 to 200 psis (sealed for wet and freeze/thaw aSAE 45° Flare Internal Thread (7/16-20 UNF) with Depressor (Style 47). WHA-PKDharness included.

P499RAP-105C Electronic Pressure Transducer: 0 to 500 psig; 1/8 in.-27 NPT External Thread StyOrder WHA-PKD3 type wire harness separately.

P499RAP-105K Electronic Pressure Transducer Kit: 0 to 500 psig; 1/8 in.-27 NPT External Thread WHA-PKD3-200C wire harness included.

P499RCP-105C Electronic Pressure Transducer: 0 to 500 psig; 1/4 in. SAE 45° Flare Internal Threa(7/16-20 UNF) with Depressor (Style 47). Order WHA-PKD3 type wire harness sep

76

Page 77: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

read .

le

Style

d arately.

read .

ft) cable

cable

ft) cable

P499RCP-105K Electronic Pressure Transducer Kit: 0 to 500 psig; 1/4 in. SAE 45° Flare Internal Th(7/16-20 UNF) with Depressor (Style 47). WHA-PKD3-200C wire harness included

P499RAP-107C Electronic Pressure Transducer: 0 to 750 psig; 1/8 in.-27 NPT External Thread StyOrder WHA-PKD3 type wire harness separately.

P499RAP-107K Electronic Pressure Transducer Kit: 0 to 750 psig; 1/8 in.-27 NPT External Thread WHA-PKD3-200C wire harness included.

P499RCP-107C Electronic Pressure Transducer: 0 to 750 psig; 1/4 in. SAE 45° Flare Internal Threa(7/16-20 UNF) with Depressor (Style 47). Order WHA-PKD3 type wire harness sep

P499RCP-107K Electronic Pressure Transducer Kit: 0 to 750 psig; 1/4 in. SAE 45° Flare Internal Th(7/16-20 UNF) with Depressor (Style 47). WHA-PKD3-200C wire harness included

WHA-PDK3-200C Plug and 3-Wire Harness for P499 Electronic Pressure Transducers: 2.0 m (6-1/2

WHA-PDK3-400C Plug and 3-Wire Harness for P499 Electronic Pressure Transducers: 4.0 m (13 ft)

WHA-PDK3-600C Plug and 3-Wire Harness for P499 Electronic Pressure Transducers: 6.0 m (19-5/8

Table 14: System 450 Compatible P499 Series Electronic Pressure Transducer and WHA-PKD3 Wire Harness Ordering Information (Part 2 of 2)

Product Code Number

Product Description

77

Page 78: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

and operating

Input Signal

2 (North America)

puts;

C (85°F)

C (85°F)

ensor

mpedance greater e as intended with

mpedances less nded with Current

closure suitable for

Compliant to

its

t is in compliance EC).

and operating

2 (North America)

Technical Specifications C450Cxx Control Modules with Analog OutputProduct C450Cxx: System 450 Control Module models are sensing controls

controls with LCD, four-button touchpad, and analog outputC450CPN-1: Control Module with one analog outputC450CPW-100: Control Module with Hybrid Analog Output and HighSelectionC450CQN-1: Control Module with two analog outputs

Supply Power C450YNN-1 Power Supply Module or24 (20–30) VAC Safety Extra-Low Voltage (SELV) (Europe) or Class50/60 Hz, 10 VA minimum

Ambient Operating Conditions Temperature: -40 to 66°C (-40 to 150°F) when using 0–10 VDC out -40 to 40°C (-40 to 104°F) when using 4–20 mA outputsHumidity: Up to 95% RH noncondensing; Maximum Dew Point 29°

Ambient Shipping and Storage Conditions

Temperature: -40 to 80°C (-40 to 176°F)Humidity: Up to 95% RH noncondensing; Maximum Dew Point 29°

Input Signal 0–5 VDC; 1,035 ohm at 25°C (77°F) for an A99 PTC Temperature S

Analog Output Voltage Mode (0–10 VDC):10 VDC maximum output voltage10 mA maximum output currentRequires an external load of 1,000 ohm or moreThe AO operates in Voltage Mode when connected to devices with ithan 1,000 ohm. Devices that drop below 1,000 ohm may not operatVoltage Mode applications.

Current Mode (4–20 mA):Requires an external load between 0–300 ohmThe AO operates in Current Mode when connected to devices with ithan 300 ohm. Devices that exceed 300 ohm may not operate as inteMode applications.

Analog Input Accuracy Resolution: 14 bit

Control Construction Independently-mounted control, surface mounted with Lexan 950 enDIN rail mounting or direct mounting to a hard, even surface.

Dimensions (H x W x D) 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.)

Weight C450CPN-1: 195 g (0.43 lb)C450CPW-100: 195 g (0.43 lb)C450CQN-1: 195 g (0.43 lb)

Compliance North America: cULus Listed; UL 60730, File E27734, Vol. 1; FCC CFR47, Part 15, Subpart B, Class BIndustry Canada (IC) Compliant to Canadian ICES-003, Class B lim

Europe: CE Mark - Johnson Controls Inc., declares that this producwith Low Voltage Directive (2006/95/EC); EMC Directive (2004/108/RoHS Directive (2002/95/EC); WEEE Directive (2002/96/EC).

Australia: Mark: C-Tick Compliant (N1813)

C450CxN Control Modules with Relay Output (Part 1 of 2)Product C450Cxx: System 450 Control Module models are sensing controls

controls with LCD, four-button touchpad, and On/Off relay outputC450CBN-1: Control Module with one SPDT output relayC450CCN-1: Control Module with two SPDT output relays

Supply Power C450YNN-1 Power Supply Module or24 (20-30) VAC Safety Extra-Low Voltage (SELV) (Europe) or Class50/60 Hz, 10 VA minimum

78

Page 79: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

puts;

C (85°F)

C (85°F)

ensor

AC

closure suitable for

Compliant to

its

t is in compliance EC).

trols and operating

A99BC-25

A99BC-25

(North America)

(85°F)

(85°F)

nsor

AC

Ambient Operating Conditions Temperature: -40 to 66°C (-40 to 150°F) when using 0–10 VDC out-40 to 40°C (-40 to 104°F) when using 4–20 mA outputsHumidity: Up to 95% RH noncondensing; Maximum Dew Point 29°

Ambient Shipping and Storage Conditions

Temperature: -40 to 80°C (-40 to 176°F)Humidity: Up to 95% RH noncondensing; Maximum Dew Point 29°

Input Signal 0–5 VDC, 1,035 ohm at 25°C (77°F) for an A99 PTC Temperature S

Output Relay Contacts General: 1/2 HP at 120/240 VAC, SPDT

Specific: AC Motor Ratings 120 VAC 208/240 V AC Full-load Amperes: 9.8 A 4.9 A AC Locked-Rotor Amperes: 58.8 A 29.4 A _____________________________________ 10 Amperes AC Non-inductive at 24/240 VAC Pilot Duty: 125 VA at 24/240 VAC

Analog Input Accuracy Resolution: 14 bit

Control Construction Independently-mounted control, surface mounted with Lexan 950 enDIN rail mounting or direct mounting to a hard, even surface.

Dimensions (H x W x D) 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.)

Weight C450CBN-1: 209 g (0.46 lb)C450CCN-1: 222 g (0.49 lb)

Compliance North America: cULus Listed; UL 60730, File E27734, Vol. 1; FCC CFR47, Part 15, Subpart B, Class BIndustry Canada (IC) Compliant to Canadian ICES-003, Class B lim

Europe: CE Mark - Johnson Controls Inc., declares that this producwith Low Voltage Directive (2006/95/EC); EMC Directive (2004/108/RoHS Directive (2002/95/EC); WEEE Directive (2002/96/EC).

Australia: Mark: C-Tick Compliant (N1813)

C450RxN Reset Control Modules with Relay Output (Part 1 of 2)Product C450RxN: System 450 Reset Control Module models are sensing con

controls with LCD, four-button touchpad, and On/Off relay output.C450RBN-1: Reset Control Module with one SPDT output relay, one temperature sensor, and one A99BC-300 temperature sensorC450RCN-1: Reset Control Module with two SPDT output relays, onetemperature sensor, and one A99BC-300 temperature sensor

Supply Power C450YNN-1 Power Supply Module or24 (20-30) VAC Safety Extra-Low Voltage (SELV) (Europe) or Class 250/60 Hz, 10 VA minimum

Ambient Operating Conditions Temperature: -40 to 66°C (-40 to 150°F)Humidity: Up to 95% RH noncondensing; Maximum Dew Point 29°C

Ambient Shipping and Storage Conditions

Temperature: -40 to 80°C (-40 to 176°F)Humidity: Up to 95% RH noncondensing; Maximum Dew Point 29°C

Input Signal 0–5 VDC, 1,035 ohm at 25°C (77°F) for an A99 PTC Temperature Se

Output Relay Contacts General: 1/2 HP at 120/240 VAC, SPDT

Specific: AC Motor Ratings 120 VAC 208/240 V AC Full-load Amperes: 9.8 A 4.9 A AC Locked-Rotor Amperes: 58.8 A 29.4 A _____________________________________ 10 Amperes AC Non-inductive at 24/240 VAC Pilot Duty: 125 VA at 24/240 VAC

Clock Accuracy ±4 minutes per year

Clock Backup Power 12 hours (capacitor reserve)

Setback Events one occupied and one unoccupied event per day; 7 day schedule

C450CxN Control Modules with Relay Output (Part 2 of 2)

79

Page 80: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

losure suitable for

mpliant to CFR47,

is in compliance C).

(North America)

uts;

(85°F)

(85°F)

pedance greater as intended with

edances less than with Current Mode

losure suitable for

mpliant to CFR47,

is in compliance C).

Analog Input Accuracy Resolution: 14 bit

Control Construction Independently-mounted control, surface mounted with Lexan 950 encDIN rail mounting or direct mounting to a hard, even surface.

Dimensions (H x W x D) 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.)

Weight C450RBN-1: 209 g (0.46 lb)C450RCN-1: 222 g (0.49 lb)

Compliance North America: cULus Listed; UL 60730, File E27734, Vol. 1; FCC CoPart 15, Subpart B, Class BIndustry Canada (IC) Compliant to Canadian ICES-003, Class B limits

Europe: CE Mark - Johnson Controls Inc., declares that this product with Low Voltage Directive (2006/95/EC); EMC Directive (2004/108/ERoHS Directive (2002/95/EC); WEEE Directive (2002/96/EC).

Australia: Mark: C-Tick Compliant (N1813)

C450SxN Analog Output Expansion ModulesProduct C450SPN-1: System 450 Expansion Module with one Analog output

C450SQN-1: System 450 Expansion Module with two Analog outputs

Supply Power C450YNN-1 Power Supply Module or24 (20-30) VAC Safety Extra-Low Voltage (SELV) (Europe) or Class 250/60 Hz, 10 VA minimum

Ambient Operating Conditions Temperature: -40 to 66°C (-40 to 150°F) when using 0–10 VDC outp-40 to 40°C (-40 to 104°F) when using 4–20 mA outputsHumidity: Up to 95% RH noncondensing; Maximum Dew Point 29°C

Ambient Shipping and Storage Conditions

Temperature: -40 to 80°C (-40 to 176°F)Humidity: Up to 95% RH noncondensing; Maximum Dew Point 29°C

Analog Output Voltage Mode (0–10 VDC):10 VDC maximum output voltage10 mA maximum output currentRequires an external load of 1,000 ohm or moreThe AO operates in Voltage Mode when connected to devices with imthan 1,000 ohm. Devices that drop below 1,000 ohm may not operateVoltage Mode applications.

Current Mode (4–20 mA):Requires an external load between 0–300 ohmThe AO operates in Current Mode when connected to devices with imp300 ohm. Devices that exceed 300 ohm may not operate as intended applications.

Control Construction Independently-mounted control, surface mounted with Lexan 950 encDIN rail mounting or direct mounting to a hard, even surface.

Dimensions (H x W x D) 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.)

Weight C450SPN-1: 150 g (0.33 lb)C450SQN-1: 150 g (0.33 lb)

Compliance North America: cULus Listed; UL 60730, File E27734, Vol. 1; FCC CoPart 15, Subpart B, Class BIndustry Canada (IC) Compliant to Canadian ICES-003, Class B limits

Europe: CE Mark - Johnson Controls Inc., declares that this product with Low Voltage Directive (2006/95/EC); EMC Directive (2004/108/ERoHS Directive (2002/95/EC); WEEE Directive (2002/96/EC).

Australia: Mark: C-Tick Compliant (N1813)

C450RxN Reset Control Modules with Relay Output (Part 2 of 2)

80

Page 81: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

laylays

(North America)

(85°F)

(85°F)

losure suitable for

ompliant to

is in compliance C).

down to 24 VAC

(85°F)

(85°F)

losure suitable for

ompliant to

is in compliance C).

C450SxN Relay Output Expansion ModulesProduct C450SBN-1: System 450 Expansion Module with one SPDT output re

C450SCN-1: System 450 Expansion Module with two SPDT output re

Supply Power C450YNN-1 Power Supply Module or24 (20-30) VAC Safety Extra-Low Voltage (SELV) (Europe) or Class 250/60 Hz, 10 VA minimum

Ambient Operating Conditions Temperature: -40 to 66°C (-40 to 150°F)Humidity: Up to 95% RH noncondensing; Maximum Dew Point 29°C

Ambient Shipping and Storage Conditions

Temperature: -40 to 80°C (-40 to 176°F)Humidity: Up to 95% RH noncondensing; Maximum Dew Point 29°C

Output Relay Contacts General: 1/2 HP at 120/240 VAC, SPDT

Specific: AC Motor Ratings 120 VAC 208/240 VAC AC Full-load Amperes: 9.8 A 4.9 A AC Locked-Rotor Amperes: 58.8 A 29.4 A _____________________________________ 10 Amperes AC Non-inductive at 24/240 VAC Pilot Duty: 125 VA at 24/240 VAC

Control Construction Independently-mounted control, surface mounted with Lexan 950 encDIN rail mounting or direct mounting to a hard, even surface.

Dimensions (H x W x D) 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.)

Weight C450SBN-1: 172 g (0.38 lb)C450SCN-1: 186 g (0.41 lb)

Compliance North America: cULus Listed; UL 60730, File E27734, Vol. 1; FCC CCFR47, Part 15, Subpart B, Class BIndustry Canada (IC) Compliant to Canadian ICES-003, Class B limits

Europe: CE Mark - Johnson Controls Inc., declares that this product with Low Voltage Directive (2006/95/EC); EMC Directive (2004/108/ERoHS Directive (2002/95/EC); WEEE Directive (2002/96/EC).

Australia: Mark: C-Tick Compliant (N1813)

C450YNN Power ModuleProduct C450YNN-1: System 450 Power Supply Module; 120 or 240 VAC step

Class 2 (North America) or SELV (Europe)

Supply Power 110/120 VAC or 220/240 VAC at 50/60 Hz (100 mA maximum)

Secondary Power 24 VAC, 10 VA

Ambient Operating Conditions Temperature: -40 to 66°C (-40 to 150°F)Humidity: Up to 95% RH noncondensing; Maximum Dew Point 29°C

Ambient Shipping and Storage Conditions

Temperature: -40 to 80°C (-40 to 176°F)Humidity: Up to 95% RH noncondensing; Maximum Dew Point 29°C

Control Construction Independently-mounted control, surface mounted with Lexan 950 encDIN rail mounting or direct mounting to a hard, even surface.

Dimensions (H x W x D) 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.)

Weight C450YNN-1: 390 g (0.86 lb)

Compliance North America: cULus Listed; UL 60730, File E27734, Vol. 1; FCC CCFR47, Part 15, Subpart B, Class BIndustry Canada (IC) Compliant to Canadian ICES-003, Class B limits

Europe: CE Mark - Johnson Controls Inc., declares that this product with Low Voltage Directive (2006/95/EC); EMC Directive (2004/108/ERoHS Directive (2002/95/EC); WEEE Directive (2002/96/EC).

Australia: Mark: C-Tick Compliant (N1813)

81

Page 82: System 450™ Series Modular Controls - ControlTrendscontroltrends.org/wp-content/uploads/2011/03/johnson-controls-450-tech-buillent.pdf · System 450™ Series Modular Controls Technical

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult Johnson Controls application Engineering at (414) 524-5535. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.United States Emissions ComplianceThis equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: - Reorient or relocate the receiving antenna. - Increase the separation between the equipment and receiver. - Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. - Consult the dealer or an experienced radio/TV technician for help.Canadian Emissions ComplianceThis Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.Cet appareil numérique de la Classe (B) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Published in U.S.A. www.johnsoncontrols.com

82

Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.All othermarks herein are the marks of their respective owners. © 2011 Johnson Controls, Inc.

Building Efficiency507 E. Michigan Street, Milwaukee, WI 53202