startup training – tps3 06

12
Startup Training – TPS3 06

Upload: lakia

Post on 11-Feb-2016

22 views

Category:

Documents


0 download

DESCRIPTION

Startup Training – TPS3 06. Topics Covered. Visual Inspections Verify environmental requirements are met TPS3 06 Diagnostic Operation Test Procedures Fill out Inspection Sheet. Visual Inspections. Neutral and ground bond needs to be visually inspected. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Startup Training – TPS3 06

Startup Training – TPS3 06

Page 2: Startup Training – TPS3 06

Siemens

TPS3Startup Training

2

Topics Covered

Visual Inspections

Verify environmental requirements are met

TPS3 06 Diagnostic Operation

Test Procedures

Fill out Inspection Sheet

Page 3: Startup Training – TPS3 06

Siemens

TPS3Startup Training

3

Visual Inspections

Neutral and ground bond needs to be visually inspected.

If bond is loose, missing, or old, tighten, install, or replace bond. Poor neutral to ground bonds account for 99.9% of all surge protection failures.

Surge protection failure due to poor neutral to ground bond integrity will NOT be warranted!

Refer to page two of the installation manual.

Ground bond broken off

Page 4: Startup Training – TPS3 06

Siemens

TPS3Startup Training

4

Verify Environmental Requirements

This surge protector is designed to operate indoors in an ambient temperature range of -40C (-40F) to +60C (+140F) with a relative humidity of 0% to 95%(non-condensing).

Verify installed environment meets this requirement.

Refer to page two of installation manual.

Refer to Red Warning Tag that is attached to disconnect

Page 5: Startup Training – TPS3 06

Siemens

TPS3Startup Training

5

Startup

Before energizing. Surge protection must remain off until high-potential insulation testing is finished. Refer to page 1 of manual

Once all installation procedures are followed, surge protector can now be energized.

All Siemens TPS3 surge protectors are designed to be virtually maintenance free. Light indicators show protection status. The following slides show different light conditions and what they mean.

Page 6: Startup Training – TPS3 06

Siemens

TPS3Startup Training

6

Normal StatusNormal 100% function suppressor will have three green lights. The service light will not illuminate nor will the audible alarm sound.

Page 7: Startup Training – TPS3 06

Siemens

TPS3Startup Training

7

Testing StatusIf the unit is in “Normal Mode – All green lights”, pressing the “Test” button will cause the red service light to illuminate, the audible alarm to sound, and the dry contacts will change state. Also, the green lights remain illuminated during the test. Once the “Test” button is released, the service light stops illuminating, audible alarm will stop sounding, and the dry contacts will reset. The green phase lights stay illuminated.

Page 8: Startup Training – TPS3 06

Siemens

TPS3Startup Training

8

Fault ConditionIf a fault condition occurs, the audible alarm will sound, the Red Service LED will illuminate and the LED representing the affected phase/s will extinguish, indicating that the unit needs service. Contact a qualified electrician or technician for evaluation.

Page 9: Startup Training – TPS3 06

Siemens

TPS3Startup Training

9

Silence Audible AlarmIf an inoperative condition were to occur, the built-in audible alarm will sound and the red Service LED will illuminate. This indicates that the unit needs evaluation by a qualified electrician or technician. Until a qualified person evaluates the unit, press Alarm Silence to silence the alarm. (The LED above Alarm Silence illuminates when the alarm is deactivated. Normal operation occurs with the Alarm Silence LED extinguished.) The red Service LED will remain illuminated even though the Audible Alarm has been silenced.

Page 10: Startup Training – TPS3 06

Siemens

TPS3Startup Training

10

Abnormal N-G Voltage IndicatorsThis SPD include N-G voltage indicators. If the SPD detects excessive N-G voltage, the Red Service LED will blink and the Audible Alarm will cycle. This condition requires immediate attention as the SPD will fail.

Immediately TURN OFF the SPD, and contact electrician to inspect system grounding.

Page 11: Startup Training – TPS3 06

Siemens

TPS3Startup Training

11

What Causes Abnormal N-G Voltage?

Incorrectly bonded distribution systems damage SPDs. If the XO or N-G bonding jumper is not installed, the electrical system has no reference to ground. It becomes an ungrounded system. Please see previous section regarding SPDs on ungrounded systems. Such systems are known to eventually produce abnormally high L-G voltages.

SPDs will attempt to chase this system-level overvoltage abnormality until the SPD fails. This effect is accelerated on Wye systems where SPDs are designed for grounded systems. (SPDs for ungrounded systems generally have higher MCOV to allow for L-G voltage fluctuations.) Failures of this nature are not defects in the SPDs workmanship or material. This is an installation error and is not covered by warranty.

A differential voltage circuit monitors neutral to ground voltage. When N-G voltage becomes excessive, an amplifier energizes a resistor. Eventually, that resistor will overheat and cause thermally sensitive shrink wrap to shrink around the resistor. This does not occur on transient or instantaneous N-G overvoltages. When the SPD is deenergized, the shrink wrap covered resistor can be accessed by qualified personnel under the display plate cover.

Page 12: Startup Training – TPS3 06

Siemens

TPS3Startup Training

12

Return To Normal StatusOnce damaged modules are replaced, the phase light or lights will return to their green state, and the service light will stop illuminating. Also, the audible alarm will stop sounding. If the audible alarm silence switch was depressed to turn off the alarm, the silence alarm light will remain on. You need to depress the silence switch again to activate the audible alarm and turn of the silence alarm light.