DEDICATED PRESSURE SYSTEMS LTD.
Telephone 01372 803 675 Fax 01372 803 678
Email [email protected] �Internet http://www.heatweb.com
�9-19 Manor Green Road, Epsom, Surrey KT19 8RA
Specification 3708-3 Southwark 2 Bed / 1 Bath District Heating Everest
04/12/01 Copies / revised specifications can be obtained via fax / email
Heat Bank System � Everest combination unit � 14 Plate Heat Exchanger (30 ltr/min) � Indirect � 40mm Foam Insulation � Fitted Primary Controls RX1 Programmable Room Thermostat � All fitted controls are wired � Thermostatic Blending Valve 22mm � Backup Immersion Heater � Cased � Supplied with X100 Inhibitor �
� �
2���Plate Heat Exchanger 3���Heat Exchanger Pump 4���Flow Switch 5���Thermostatic Blending Valve, Mixcall III 7���Automatic Air Vent 8���Filling Vent 9���Feed to Ball Valve 10��Isolating Valve 11��Y-Pattern Strainer (supplied loose) 12��Overflow 13��Cold Feed / Expansion 14��Immersion Heater 3kW Incaloy with Stat + Overheat 16��Cold Mains In, 22mm 17��Hot Mains Out, 22mm 18��Drain Cock 19��Flow From Boiler 21��Flow to Primary Coil 22��Return from Primary Coil 33��Danfoss Radio Receiver 34� Danfoss TP5 RF Room Thermostat 35a�Zone Valve - Hot Water 22mm 35b Zone Valve - Heating 22mm (supplied loose) 38��Tamperproof Cylinder Thermostat (with Pocket) 39��White Coated Steel Casing 42� Wiring Centre with Immersion Switch + Fuses 63��Sentinel X100 Corrosion Inhibitor
Unit Code EC-130-3708-3 EC-150-3708-3
Capacity [litres] 130 150
Base Diameter [mm] 450 450
Overall Diameter [mm] 530 530
Height [mm] 1190 1330
The Heat Bank come with a 3 metre power supply lead, to be wired into a switched 16amp spur.� ALL other wiring is completed. The wiring centre [42] includes a 13amp fuse for the immersion heater [14], as well as a 3 amp fuse for controls.� Fuses are
surface (screw-driver) accessible allowing inspection and replacement without removal of the wiring centre cover.� A clearly labeled neon switch is provided for user operation of the immersion heater.� The room thermostat [34] communicates with the unit via a digital RF signal removing the need for wiring.� The room stat
receiver [33] provides the user with manual override / control, should the batteries in the room thermostat fail. The central heating zone valve [35b] actuator is wired into the wiring centre [42], to be installed in pipework by installer.
The hot water zone valve [35a] provides an auxiliary switch that can be used to provide the boiler house with a system
demand signal. �
DEDICATED PRESSURE SYSTEMS LTD.
Telephone 01372 803 675 Fax 01372 803 678
Email [email protected] �Internet http://www.heatweb.com
�9-19 Manor Green Road, Epsom, Surrey KT19 8RA
Specification 3708-4 Southwark 2 Bed / 1 Bath District Heating Everest
25/4/2003
Heat Bank System � Everest combination unit � 14 Plate Heat Exchanger (30 ltr/min) � Indirect � 40mm Foam Insulation � All fitted controls are wired � Thermostatic Blending Valve 22mm � Backup Immersion Heater � Cased � Danfoss RX1 Receiver Back-Plate (wired) Jetseal Ball Valve Supplied with Internal Inhibitor
� �
2���Plate Heat Exchanger L18-14 3���Heat Exchanger Pump 4���Flow Switch 5���Thermostatic Blending Valve, Mixcall III 7���Automatic Air Vent 8���Filling Vent 9���Jetseal Ball Valve 10��Isolating Valve 11��Y-Pattern Strainer (supplied loose) 12��Overflow 13��Cold Feed / Expansion 14��Immersion Heater 3kW Incaloy with Stat + Overheat 16��Cold Mains In, 22mm 17��Hot Mains Out, 22mm 18��Drain Cock 21��Flow to Primary Coil 22��Return from Primary Coil 38��Tamperproof Cylinder Thermostat (with Pocket) 39��White Coated Steel Casing 42� Wiring Centre 43��Back-Plate for Room Stat Receiver
62��Magnetic Scale Inhibitor 3/4"BSP MI
1.5 litres of Corrosion Inhibitor is supplied, already added into the store, following factory testing of the unit.� Should the unit be drained down after initial filling, fresh inhibitor will be required.
Unit Code CEC-130-3708-4
Capacity [litres] 130
Base Diameter [mm] 450
Overall Diameter [mm] 530
Height [mm] 1190
District Heating Everest
DEDICATED PRESSURE SYSTEMS LTD.
Telephone 01372 803 675 Fax 01372 803 678
Email [email protected] �Internet http://www.heatweb.com
�9-19 Manor Green Road, Epsom, Surrey KT19 8RA
Specification 4675-1 No.2 Neckinger Estate, Southwark
11/06/03
Heat Bank System � Everest combination unit � 28 Plate Heat Exchanger (45+ ltr/min) � Indirect � 40mm Foam Insulation � High duty primary coil � S-Plan primary controls � Twin Cylinder Thermostat Arrangement DO NOT USE � Fitted programmer � All fitted controls are wired � Thermostatic Blending Valve, Heatguard 22mm � 28mm Primaries � LWC1 Wiring Centre � Backup Immersion Heater � Cased �
�
2���Plate Heat Exchanger 3���Heat Exchanger Pump 4���Flow Switch 5���Thermostatic Blending Valve, RWC Heatguard 22mm 7���Automatic Air Vent 8���Filling Vent 9���Store Filling Point 9���Feed to Ball Valve 10��Isolating Valve 11��Y-Pattern Strainer (supplied loose) 12��Overflow 13��Cold Feed / Expansion 14��Immersion Heater 3kW Incaloy with Stat 16��Cold Mains In, 22mm 17��Hot Mains Out, 22mm 18��Drain Cock 19��Flow From Boiler 28mm 21��Flow to Primary Coil 22��Return from Primary Coil 23��Flow to Heating 28mm 25��By-Pass Connection 22mm 29��Primary Coil Balancing Valve 33��Programmer Danfoss CP715 34� Room Thermostat (supplied loose) 35a�Two Port Zone Valve - Hot Water 22mm 35b�Two Port Zone Valve - Heating 28mm 38��Cylinder Thermostat (with Immersion Pocket)
Unit Code CEC-210-4675-1 CEC-300-4675-1
Capacity [litres] 210 300
Base Diameter [mm] 450 500
Overall Diameter [mm] 530 580
Height [mm] 1720 1900
Everest Heat Bank, Indirect S-Plan
DEDICATED PRESSURE SYSTEMS LTD.
Telephone 01372 803 675 Fax 01372 803 678
Email [email protected] �Internet http://www.heatweb.com
�9-19 Manor Green Road, Epsom, Surrey KT19 8RA
Specification 4388-2 London Borough of Southwark Under Worktop Xcel Heat Bank GXV100
11/04/02
Xcel Heat Bank System � 28 Plate Heat Exchanger (45+ ltr/min) � Directly heated from remote source � 40mm Foam Insulation � GX-Plan primary controls � Fitted Primary Controls Cased �
�
2���Plate Heat Exchanger, L18-28 3���Heat Exchanger Pump, UPS15/50 4���Flow Switch 5�� Thermostatic Blending Valve (1",� pre-set to 8 ��Vent, 3/4"FI (Blanked) 11��Y-Pattern Strainer (supplied loose) 13��Cold Feed / Expansion, 3/4"FI (Blanked) 15� Immersion Heater 3kW with 2 stats 16��Cold Mains In, 22mm 17��Hot Mains Out, 22mm 18��Drain Cock 19��Flow From Boiler, 22mm 20��Return to Boiler, 22mm 23��Flow to Heating Circuit, 22mm 24��Return from Heating Circuit, 22mm 27��Primary Pump, UPS 15/50 34 Room Thermostat 38��Cylinder Thermostat (Tamperproof,� pre-set to 75°C) 39��White Coated Steel Casing 41��Primary Blending Valve Heatguard UF (Pre-set to 4)
42��Terminal Box WB12 with relay
The GX100 Heat Bank provides both mains pressure, temperature controlled, hot water, at up to 40 litres per minute, and 10 bar pressure.� The store also provides fully pumped central heating.The store is very small, capable of hiding under a kitchen worktop, and has very low standing heat losses.� It can however, deliver a full bath in under 4 minutes, with hot water to spare, and follow up with another bath within 15 minutes of the first.� Also, radiators can be brought up to full temperature in under a minute of
turning the heating on.
Mechanical installation consists of simple push fit-pipework connections, and the only site wiring required is connection to the mains electrical supply, boiler and room thermostat.� Being a fully vented thermal store, the system can be installed by installers not qualified to install unvented systems.� As standard, the store is on 24hrs a day, with the room thermostat being the only control the householder need use.� A backup 3kW immersion heater provides backup central heating and hot water in case of boiler failure.� All components are tamperproof.
Unit Code CXC-100-4388-2
Capacity [litres] 100
Base Diameter [mm] 400
Overall Diameter [mm] 480
Height [mm] 850
DEDICATED PRESSURE SYSTEMS LTD.
Telephone 01372 803 675
Fax 01372 803 678
Email [email protected]
Internet http://www.heatweb.com
SPECIFICATION 3755-1 London Borough of Southwark STS Energy Management
09/05/01
210 litre Grade 3 Cylinder (max 1 bar)
Indirect BS 28mm Coil
Finned 6m Solar Coil
40mm Foam Insulation
Danfoss Y-Plan Controls
PCB Primary Wiring Centre
Fitted Primary Pump, 5m head
Fitted Solar Controls
Resol Delta Pro Solar Controller
All fitted controls are wired
HWS Thermostatic Blending Valve
Backup Immersion Heater � �
1���Cold Feed 22mm
2�� Hot Water Services 22mm
3�� HWS Thermostatic Blending Valve
4�� Isolating Valve
7���Automatic Air Vent
8���Vent
13� Drain Cock
14��Immersion Heater 3kW Incaloy with Stat
19��Flow From Boiler
21��Flow to Primary Coil
22��Return to Boiler
23��Flow to Heating Circuit
26��Primary Pump UPS 15/50
29��Primary Coil Balancing Valve
33� Danfoss Programmer CP715
38��Danfoss Cylinder Thermostat�
35��Danfoss Three Port Mid Position Valve
36� Danfoss RF Radio Rom Thermostat
37� Danfoss RX1 RF Receiver Unit
38� Automatic By-Pass Valve
39��White Coated Steel Casing
42��Wiring Centre
48��Check Valve
49��Solar Drain Point
50��Solar Pump� UPS 15/50
51��Flow from Solar Panels
52��Return to Solar Panels
53��Resol Solar Controller
54� Flow Meter
73��Sensor Points
80��Solar Filling Point
81��Dosing Pot Connection
Unit Code ECON-3755-1
Capacity [litres] 210
Base Diameter [mm] 450
Overall Diameter [mm] 520
Height [mm] 1550
DEDICATED PRESSURE SYSTEMS LTD.
Telephone 01372 803 675 Fax 01372 803 678
Email [email protected] �Internet http://www.heatweb.com
R/O Shops, 9-19 Manor Green Road, Epsom, Surrey KT19 8RA
SPECIFICATION 2023-2 Wicken Engineering / Slough Borough Council
20/4/01 �
Stowaway advanced Heat Bank System Manual Fill - No Overflows 40mm Foam Insulation with Casing HWS Heat Exchanger (100kW)� HWS Blending Valve� Primary Heat Exchanger (14kW peak) � Directly Pumped Heating Circuit �
Fitted Primary Pumps All fitted controls are wired � Low Water Level Indicator� Blanked Immersion Heater boss � Coated Steel Casing, with Film Cover Heat Meter, Class C with Impeller� Differential Pressure Control�
1���Integral Expansion Vessel�(18 ltr) 2a� HWS�Plate Heat Exchanger 2b�Primary Plate Heat Exchanger 3���Heat Exchanger Pump UPS 15/50 4���Flow Switch 5���Thermostatic Blending Valve 6���Manual Air Vent 7�� Automatic Air Vent 8���Integral Overflow Chamber 9���System Filling Point 11��Y-Pattern Strainer (supplied loose) 14� Blanked Immersion Boss 2 1/4" 16��Cold Mains In, 22mm 17��Hot Mains Out, 22mm 18��Drain Cock 23��Flow to Heating Circuit 24��Return from Heating Circuit 25� Primary Flow� 26� Primary Return� 27��Primary HX Pump UPS 15/60 28��Heating Circuit Pump UPS 15/60 29� Primary Isolating Valve 30� Motorised 2-Port Valve 33� Programmer 34� Room Thermostat (supplied loose) 38� Cylinder Thermostat� 39��White Coated Steel Casing 40��Tight Fitting Lid 41� Primary Blending Valve 42��Wiring Centre 54��Filling Loop (disconnect after use) 55��Water Level Switch 65��Manual Water Level Test and Drain 70� Flow Meter 71� Class C Heat Meter 72� Temperature Sensors 73� Differential Pressure Control Valve 74� Pressure Sensing Points
�
Unit Code SC-130-2023
Capacity [litres] 130
Base Diameter [mm] 400
Overall Diameter [mm] 480
Height [mm] 1500
����
The use of a Primary Plate Heat Exchanger isolates the District Primaries from the Property Primaries, preventing cross-contamination, and allowing effective dosing of individual systems.
A Mains Water Isolating Lever Valve must be fitted within the cylinder cupboard, in clear view and easily accessible. A Strainer (supplied loose) must also be fitted, down stream of the isolating valve, to protect the flow switch [4].
The Wiring Centre [42] is fitted with a neon which indicates when the unit needs topping-up. It is also fitted with a relay to prevent the Heat Exchanger Pump [3] from activating - there will be no hot water available until the unit is topped up manually, using the filling loop [8].
The unit is fitted with a Mixcall III Thermostatic Blending Valve, to control the hot water temperature, and prevent scalding.� The graph shows the pressure drop across the valve for various hot water flow rates.� The Valve is adjustable from 27°C to 67°C, and has a lockable head.
The unit is fitted with an Integral Overflow Chamber [8], which traps small volumes of water discharged as a result of overfilling. Water in the chamber can be drained off via the Overfill Drain Cock [66]. The unit MUST be watched during filling as excessive overfilling will result in over-spill onto the floor.
It is advised that the mains water is tested for hardness. In areas of hard water, we advise the use of a scale inhibitor.
It is important that SENTINEL X100 Inhibitor is used to protect the Heat Bank.� Use 1 litre per 100 litres of stored water. A suitable anti-freeze, such as X500, should also be added when there is a chance that the unit will be left filled and unheated in freezing conditions.
DEDICATED PRESSURE SYSTEMS LTD.
Telephone 01372 803 675 Fax 01372 803 678
Email [email protected] �Internet http://www.heatweb.com
�9-19 Manor Green Road, Epsom, Surrey KT19 8RA
Specification 5116-1 Wicken Engineering
24/09/02
Heating Distribution Board � �
�
�
1� Quarter-Turn Ball Valve 2� 3/4" Ply Backboard 3� Y-Pattern Strainer 4� Grundfoss 15-60 Pump
5� Two-Port Motorised Valve 6� Lockshield Valve By-Pass 7� Wiring Centre 8� STROMAX-GM Circuit Regulating Valve 3/4"
�
DEDICATED PRESSURE SYSTEMS LTD.
Telephone 01372 803 675Fax 01372 803 678
Email [email protected]
�Internet http://www.heatweb.com
�
17� Manor Green Road, Epsom, Surrey KT19 8RA Company No.: 2963502� V.A.T. No.: 644221955
DPS Ref: 16181
PANDORA CENTRAL BOILER APPLICATIONSample of letter to customer regarding design options.
This Design will: 1. Obtain an 85-55°C drop on primaries for heating, with a fixed flow rate giving 9kW input. 2. Deliver thermostatically controlled mains pressure domestic hot water at up to 24 l/min @ 6 bar. 3. Deliver central heating with a 30 litre buffer, giving rapid initial heat-up. 4. Provide 3kW electric backup to both hot water and optionally heating. 5. Requires no discharge, with store/heating system manually filled. 6� Requires no annual maintenance. �
As we cannot vary the flow to match low load heating, it is not possible to maintain a low return temperature, UNLESS the heating is separated from the input using some storage as a buffer.
The basic idea is that the primaries are only opened for recovery once the bottom 30 litres of the store has dropped below 55°C (as detected by the upper thermostat).� The primaries are then opened to recover the 50°C water up to 75°C. Once the 30 litres has been circulated through and has reached 70°C the lower thermostat turns off the primaries. (the lower stat needs to be set between 55°C and 70°C - say 65°C).
At full load the radiator flow/rtn will be 75/50°C.� Bottom section will circulate once only.� Primaries will open, and if gradually the lower section will reheat as most heat is going straight to central heating.
At low load the initial radiator flow may be 75/40°C. The flow rate will be much lower so it will take a while for the lower 30 litres to be circulated. Once the primaries open, the lower section may recover 40/70°C and recovery will stop. the heating will now continue at say 70/45°C... and the cycle continues. At all times the primary return temperatures should be at or below the desired maximum of 55°C.
Another way of saying same thing...
We are trying to cool down the primaries to below 55°C. Because there is a set primary flow rate, it is not possible to cool the primaries enough at low heating loads unless... We run the heating off stored heat until we have a reservoir of water cool enough to run and cool the primaries to 55°C.
You cannot even do this with a distribution board, unless you are allowed to reduce the primary flow rate to match load using a thermostatic valve.� The thermostatic valves required to get a set point over 65°C are the Danfoss AVTB valve and the motorised valve still used for tight shut-off.
I have shown a motorised two port valve on the primaries. I assume one must be required, and we can fit and wire if needed. Also a room thermostat as this completes the necessary controls (unless a timer is also needed).
The immersion heater can be lowered into the bottom section if you would like backup electric central heating. In the position shown it will be hot water only.
My selection of heat exchange is our largest stock unit the M18-30. This size gets the htg rtn to within 3°C of primary rtn.� Cheaper heat exchangers are available if this temp difference can be increased. Software gives following:
Only issue is flow rate. I believe to make use of any available Grundfos pump,� the flow rate is too low so a by-pass will be required around the pump, to put is somewhere on the curve. This can be a lockshield valve, an auto-by-pass or fixed orifice.� Also, it may be worth having a Tacometer flow gauge on the store flow through the heat exchanger to allow visual indication and setting of flow rate.