SMOKE GUARD www.smokecontrol.com.au Unit 5, 52 Holker St, Silverwater NSW 2128 T : 1300 665 471 F : (02) 9648 1791 E : [email protected] 1 of 7 V5.0 GENERAL The Smoke Guard System introduces a new and exciting way of reducing the effects of vertical smoke movement in buildings. The System was designed by an Architect to provide a cost effective, aesthetically pleasing and space saving alternative to smoke proof lift lobbies and lift pressurisation systems. The System is designed to activate in the early stages of a fire by the operation of a smoke detector, deploying a flexible magnetic temperature resistant smoke containment screen over the lift landing door opening. The design is simple, cost effective and is ideal for heritage building upgrades, retrofit applications and where fire stairs open into a lift lobby and lifts connect multiple smoke compartments in multi-storey hospitals and aged care buildings. Both the Model 400 and 600 Smoke Guard Systems have been tested to AS/NZS 1530 Part 7 for ambient and medium temperature smoke leakage and are an ideal alternative solution to the prescriptive (deemed-to- satisfy) requirements of our building codes. A COST EFFECTIVE, AESTHETICALLY PLEASING, SPACE SAVING ALTERNATIVE TO SMOKE PROOF LOBBIES, AND LIFT SHAFT PRESSURISATION KEY FEATURES Designed for access and egress for disabled and children Only curtain system available that can be operated without any special skills or knowledge Virtually invisible in non-fire mode Increases nett lettable space Tested in accordance with AS/ NZS 1530 Part 7 for smoke leakage performance Ideal for use where lift doors open directly into fire escape stairs Ideal for basement car parks in lieu of Smoke lobbies Simple, reliable and operational performance easily quantified S S MOKE MOKE CONTAINMENT CONTAINMENT S S CREENS CREENS (FOR LIFT DOORS AND OTHER OPENINGS IN SMOKE WALLS)

Upload: others

Post on 13-Mar-2020

4 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months

SM

OK

E G

UA

RD

www.smokecontrol.com.au Unit 5, 52 Holker St, Silverwater NSW 2128

T : 1300 665 471 F : (02) 9648 1791

E : [email protected]

1 of 7 V5.0

GENERAL The Smoke Guard System introduces a new and exciting way of reducing the effects of vertical smoke movement in buildings. The System was designed by an Architect to provide a cost effective, aesthetically pleasing and space saving alternative to smoke proof lift lobbies and lift pressurisation systems. The System is designed to activate in the early stages of a fire by the operation of a smoke detector, deploying a flexible magnetic temperature resistant smoke containment screen over the lift landing door opening. The design is simple, cost effective and is ideal for heritage building upgrades, retrofit applications and where fire stairs open into a lift lobby and lifts connect multiple smoke compartments in multi-storey hospitals and aged care buildings. Both the Model 400 and 600 Smoke Guard Systems have been tested to AS/NZS 1530 Part 7 for ambient and medium temperature smoke leakage and are an ideal alternative solution to the prescriptive (deemed-to-satisfy) requirements of our building codes.

A COST EFFECTIVE, AESTHETICALLY PLEASING,

SPACE SAVING ALTERNATIVE

TO SMOKE PROOF LOBBIES,

AND LIFT SHAFT PRESSURISATION

KEY FEATURES • Designed for access and egress

for disabled and children

• Only curtain system available that can be operated without any special skills or knowledge

• Virtually invisible in non-fire mode

• Increases nett lettable space

• Tested in accordance with AS/NZS 1530 Part 7 for smoke leakage performance

• Ideal for use where lift doors open directly into fire escape stairs

• Ideal for basement car parks in lieu of Smoke lobbies

• Simple, reliable and operational performance easily quantified

SSMOKEMOKE CONTAINMENTCONTAINMENT SSCREENSCREENS (FOR LIFT DOORS AND OTHER OPENINGS IN SMOKE WALLS)

Page 2: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months

SM

OK

E G

UA

RD

www.smokecontrol.com.au Unit 5, 52 Holker St, Silverwater NSW 2128

T : 1300 665 471 F : (02) 9648 1791

E : [email protected]

2 of 7 V5.0

Description International studies show up to 65% of vertical smoke movement in a building is via the lift shaft. The Smoke Guard System (SGS) is an automatic smoke containment screen designed to reduce the movement of smoke beyond the fire floor via lift shafts thereby maintaining an adequate level of visibility and reducing the effects of toxic smoke to assist occupants in exiting a building in a fire — or prolong the tenability conditions until assistance arrives. The System incorporates a unique flexible magnetic temperature resistant translucent screen contained in a steel housing. This housing is typically mounted above a lift landing door and concealed within a suspended ceiling or bulkhead. Operation On the receipt of an alarm signal the system deploys, rolling down the face of the lift door opening. A flexible magnet seals against the 430 grade magnetic stainless steel auxiliary rails (or magnetic architrave of the lift door frame if available). If occupants wish to pass through the smoke barrier, a rewind switch located on both sides of the screen approximately 1000mm from the ground can be activated. The smoke containment screen is designed to completely rewind into the housing, hold for 4-5 seconds allowing the occupant to escape, and redeploy to re-establish the smoke barrier.

SSMOKEMOKE CONTAINMENTCONTAINMENT SCREENSSCREENS (FOR LIFT DOORS AND OPENINGS IN SMOKE WALLS)

READY The Smoke Guard System ( S G S ) i s contained in a metal housing mounted above the lift door on the lobby side of the lift shaft.

ALARM T h e S G S au tomat i ca l l y deploys when s m o k e i s detected by the smoke detector in front of the lift door.

DEPLOY When deployed t h e S G S m a g n e t i c a l l y attaches to the ferrous metal lift door frame or auxiliary rails p rov id ing a virtually air tight seal without interfering with the lift door.

Screen rewind switch

Page 3: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months

SM

OK

E G

UA

RD

www.smokecontrol.com.au Unit 5, 52 Holker St, Silverwater NSW 2128

T : 1300 665 471 F : (02) 9648 1791

E : [email protected]

3 of 7 V5.0

Operation cont... On resetting of the alarm a rewind motor automatically rewinds the screen back into the concealed void, and on the Model 400, closing the housing door behind it. The SGS has been specifically designed to be operated “without any special skills or knowledge” as required by US codes to cover most occupant types. It is the only system available on the market today with this feature. The SGS offers optional cove seals at the floor level to further reduce both the rate of smoke leakage and to protect lift operation from the effects of water due to activated sprinklers and fire fighting activities.

Cove seals installed at floor level

Fail safe The Model 400 (M400) System is fail safe, deploying on disruption of primary power (240V). However, built in protection from minor power interruptions or failures with an 8-10 second delay assists in avoiding most nuisance deploys. The System may also be connected to an emergency power supply. Battery back-up The Model 600 (M600) System is supplied with a battery back up system that will hold the unit up for 8-10 days in case of a power failure. If, within this time a fire is detected, the system will deploy as required.

Thermal Patch Each SGS is supplied with a thermal patch located on the inside of the housing door that changes colour on exposure to temperatures around 93 0C. If the SGS is installed in a building where a fire has occurred and the thermal patch colour is unchanged, the system is suitable for re-use. However, if the patch changes colour (or there is obvious physical damage) the system may need replacement. Translucent screen The SGS is the only system available with a translucent screen allowing occupants in the lift, such as fire fighters for example, to survey the environment on the other side of the lift to ensure it is safe to enter. Disabled egress Traditional smoke curtain systems that incorporate side guides can potentially trap occupants inside the lift. Able body people can lift the curtain and climb under, however this is not possible for people with mobility disabilities. The SGS does not discriminate against people with disabilities and can be operate without any special skills or knowledge.

SSMOKEMOKE CONTAINMENTCONTAINMENT SCREENSSCREENS (FOR LIFT DOORS AND OPENINGS IN SMOKE WALLS)

Page 4: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months

SM

OK

E G

UA

RD

www.smokecontrol.com.au Unit 5, 52 Holker St, Silverwater NSW 2128

T : 1300 665 471 F : (02) 9648 1791

E : [email protected]

4 of 7 V5.0

Reliability The SGS is less complex than pressurisation systems providing an increase in system reliability. The system has also been cycle tested in excess of 2000 continuous open and close cycles without failure. The system is also ideal as an alternative to smoke-proof lobbies and is less likely to be chocked open like smoke doors for example, also increasing system reliability. Installation In line with Smoke Controls mission to provide customers with reliable solutions, the SGS is installed by our fully trained and approved installer network. Preparation for installation generally requires sufficient head and side room clearance, provision for 240 Volt primary power and a smoke alarm signal with a normally closed relay for the Model 400 and normally open relay for the Model 600. Please contact our office for a detailed scope of works for the Model 400 & 600. Verification of performance Unlike complex pressurization systems that may take weeks or even months to successfully commission the Smoke Guard System is easily commissioned as soon as power is available. In addition, the system is not susceptible to being chocked open like smoke doors in smoke lobbies or re-commissioning due to internal refurbishments or fit outs like pressurisation systems. Maintenance Annual maintenance and verification of system operation should be conducted by our trained personnel in strict accordance with document numbers 402, Rev 03 and 602, Rev 13 for the Model 400 and 600 respectively. Contact us for details.

Sizes Both models are made to order following site measurement. Typical lead time is 8 weeks. For larger openings please refer to Fiberseal smoke containment screen data sheets in Section 2 of the catalogue or contact us for more information. Project specification “An automatic smoke containment screen, complete with a screen mounted rewind switch and housing door closing device, capable of automatically rewinding completely into an overhead housing shall be installed above each of the designated lift door openings. The system shall be tested in accordance with AS/NZS1530 Part 7 to provide a leakage rate of no more than 51 m3/hr at 25 Pa and 2000C. Or 31m3/hr when corrected to standard temperature and pressure. The smoke containment screen shall be translucent and shall provide a Group 1 classification under the requirements of BCA clause C1.10a when tested to AS/NZS3837. The system shall be Smoke Guard Model 400/600 [specify which]. Note: To accommodate the Smoke Guard System; 1. Refer to system data sheets for required

clearances. 2. Lift control and indicator panels shall

not be installed in the architrave face of the lift door frame.

3. Lift control and indicator panels shall not protrude more than 12mm from the face of the wall.

4. Decorative wall cladding to provide sufficient clearance for auxiliary rails.

SSMOKEMOKE CONTAINMENTCONTAINMENT SCREENSSCREENS (FOR LIFT DOORS AND OTHER OPENINGS IN SMOKE WALLS)

Page 5: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months

SM

OK

E G

UA

RD

www.smokecontrol.com.au Unit 5, 52 Holker St, Silverwater NSW 2128

T : 1300 665 471 F : (02) 9648 1791

E : [email protected]

5 of 7 V5.0

Technical details It is now commonly accepted that smoke movement beyond the fire floor can contribute significantly to injury and death in a fire. Typical lift doors can contribute up to 65% of the total vertical movement of smoke to floors above the fire floors1

Other statistics2 show that over 75% of the deaths and injuries in fires are due to the smoke not the fire. A report by Hughes Associates3 provides a hypothetical example of the effectiveness of reducing the smoke leakage through lift doors. The report states; “….the leakage area of the elevator (lift) doors is the primary factor in allowing smoke to migrate to upper floors in a building. If the leakage area of the elevator (lift) doors is controlled to reduced levels then a three fold increase in visibility can be attained on the upper floors of a typical multi-story building regardless of whether the building was sprinklered or not.” The Smoke Guard System is the ideal solution for Fire Safety Engineers to significantly increase the visibility and reduce the amount of toxic smoke in the upper levels of multi-storey buildings to provide quantifiable, easily verifiable egress time for occupants. The applications for Smoke Guard are always increasing. Please do not hesitate to contact us to discuss the potential for the SGS for your unique project.

Resistance to smoke leakage: Although the gaps around the perimeter of lift doors seem relatively small, these gaps are significantly large in terms of smoke leakage. For a typical lift door this leakage can be in excess of 12m3/min per square metre of lift door opening aided by stack, wind and piston effects. Protecting the lift door opening with the SGS reduces this leakage to less than 0.3m3/min per square metre of lift door opening. Resistance to stack, wind & piston effects: Stack and wind effects can overcome pressurisation systems. It is often difficult to design these systems for all potential weather conditions. The Smoke Guard System forms a physical barrier in front of the lift door and has been tested to show that it can withstand pressures up to 75Pa. Chemical resistance: The barrier film used in the Smoke Guard System is resistant to chemical attack. These properties have resulted in various projects in the semiconductor and pharmaceutical industry.

1. Tamura & Shaw, “Air leakage data for the design of Elevator and Stair Shaft pressurizations systems” ASHRAE transactions. Note: This study does not specifically state this figure, however, using the data from actual building tests provided in the study, this result can be calculated.

2. Berl, and Halpin “Human Fatalities from Unwanted Fires” Johns Hopkins APL Technical Digest Vol. 1, No. 2. Another related reference is – Hall, Dr. John, “Burns, Toxic Gases, and other hazards associated with fires: Deaths and Injuries in Fire and Non Fire Situations”, Feb. 2000, NFPA.

3. Beitel, Wakelin & Beyler, Hughes Associates, “Analysis of Smoke Movement in a Building via Elevator Shafts” prepared for the Smoke Safety Council, March 2000

SSMOKEMOKE CONTAINMENTCONTAINMENT SCREENSSCREENS (FOR LIFT DOORS AND OPENINGS IN SMOKE WALLS)

Page 6: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months

SM

OK

E G

UA

RD

www.smokecontrol.com.au Unit 5, 52 Holker St, Silverwater NSW 2128

T : 1300 665 471 F : (02) 9648 1791

E : [email protected]

6 of 7 V5.0

Barrier to water penetration: In multi-storey buildings the Fire Services may choose to use the lift to reach the levels below a fire floor to avoid carrying heavy fire fighting equipment up many floors. Fire fighting activities and water from an activated sprinkler may render lifts unusable. Independent test on the Model 600 Smoke Guard System, complete with cove seals, has shown to significantly reduce the amount of water penetration into the lift.

Water leakage test on standard lift door opening at 76mm water.

This may create valuable time in which the Fire Services can use the lifts to rescue occupants and get closer to the staging area to commence fire fighting activities.

Smoke Guard System deployed— 76mm of water in reservoir.

Smoke Guard Deployed—Leakage significantly reduced at 78mm water

Test reports Extensive testing has already been conducted on the Smoke Guard System and is ongoing. Please do not hesitate to contact us for copies of test reports and for the latest test information. Current tests include: • AS/NZS1530 Part 7 • AS/NZS3837—BCA Group 1 • UL1784 • ASTM E84 • Chemical resistance • Water penetration Technical support We provide an excellent technical support service free of charge from design through to installation and commissioning. Please do not hesitate to contact us for a no-obligation discussion on the various options for your project requirements. Information given in this publication is given to the best of our knowledge and in good faith. Smoke Control is not responsible if recipients of test reports, assessments or literature misinterpret the contents and wrongly use products based on those misinterpretations. No liability is accepted for error omissions in this document. Smoke Control reserves the right to change specification without notice.

SSMOKEMOKE CONTAINMENTCONTAINMENT SCREENSSCREENS (FOR LIFT DOORS AND OTHER OPENINGS IN SMOKE WALLS)

Page 7: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months

SM

OK

E G

UA

RD

www.smokecontrol.com.au Unit 5, 52 Holker St, Silverwater NSW 2128

T : 1300 665 471 F : (02) 9648 1791

E : [email protected]

7 of 7 V5.0

SM

OK

E G

UA

RD

Design Drawings DWG # Description SCD-M400-000 Model 400 system components SCD-M400-001 High mount (magnetic frame) SCD-M400-002 High mount (magnetic auxiliary rails) SCD-M400-003 Head mount (magnetic frame) SCD-M400-004 Head mount (magnetic auxiliary rails) SCD-M400-005 Protection of openings in smoke walls SCD-M400-006 Landing elevation and section details SCD-M600-000 Model 600 system components SCD-M600 -001 High mount (magnetic frame) SCD-M400-002 High mount (magnetic auxiliary rails) SCD-M400-003 Head mount (magnetic frame) SCD-M400-004 Head mount (magnetic auxiliary rails) SCD-M600-005 Landing elevation, section details

SSMOKEMOKE CONTAINMENTCONTAINMENT SCREENSSCREENS (FOR LIFT DOORS AND OPENINGS IN SMOKE WALLS)

Page 8: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 9: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 10: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 11: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 12: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 13: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 14: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 15: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 16: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 17: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 18: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 19: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 20: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 21: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 22: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 23: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 24: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 25: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 26: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 27: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 28: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months
Page 29: SMOKE CONTAINMENT SCREENS CREENSsmokecontrol.com.au/wp-content/uploads/2015/06/Smoke... · 2015-10-01 · Unlike complex pressurization systems that may take weeks or even months