Smoke and No Mirrors The ACTIONAIR guide to smoke control dampers - Peter Faruqi – National Sales Manager - ACTIONAIR - Swegon

Upload: others

Post on 04-Jul-2020

24 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Smoke and No Mirrors The ACTIONAIR guide to smoke control dampers

- Peter Faruqi – National Sales Manager - ACTIONAIR- Swegon

Page 2: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Introduction to ACTIONAIR

• Our “Smoke and Fire” product line

• Manufactured in the UK for over 45 years

• Market leading fire, smoke & air control products

• All products meet the latest European Standards & Regulations.

• Our on-going research and development ensures our customers expectations and requirements are completely satisfied

• Swegon are here to support from the earliest stages of specification through to installation, commissioning and maintenance of ACTIONAIR products

Page 3: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

How we work…

Knowledge Controls and dampers

Collaboration on site

Safe buildings!

Page 4: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

We are here every step of the way

Delivery Installation & Commissioning

Operation

Selectionsoftware

Wide productchoice

Local Salesand Technical

Teams

Service Organisation

Helpdesk and Support

Specification & Design

Page 5: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Project ReferencesPROJECT REFERENCE LOCATION

• Ten Trinity Square London

• Bridge Theatre London

• Uxmouth Power Station UK

• Aboyne Hospital Aberdeenshire

• St James Hospital Dublin

• Edwardian Hotel London

• Queen Elizabeth Hospital Manchester

• Dalkeith Shopping CentreBournemouth

• Altnagelvin Hospital Derry

• Stansted Airport London

• Liverpool University Liverpool

• Heartlands Hospital Birmingham

• Windsor Office Development London

• Microsoft European H.Q. Dublin

• Great Ormond Street London

• National History Museum London

• Battersea Power Station London

PROJECT REFERENCE LOCATION

• Spire Hospital Manchester

• British Museum London

• One Crown Place Dublin

• John Radcliffe Hospital Oxford

• Finsbury Square (Office Block) London

• Prince Philip Hospital Leeds

• R.A.F. Mildenhall Suffolk

• 140 Aldersgate (Office Block) London

• Queen Elizabeth Hospital Gateshead

• Dexia Luxembourg

• UCC Medical Nursing Cork

• Royal Victory Hospital Belfast

• Western Hospital Scotland

• University Hospital Southampton

• Medway Maritime Hospital Kent

Page 6: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Learning outcomes

• Today we will cover…

• Why smoke control is important

• Overview of Smoke Control Dampers (compared to fire dampers)

• Smoke Control Damper classifications

• Look at strategies and best practice

Page 7: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Key fire and smoke terminology

• Compartmentation is…

• Keeping the fire and smoke limited to one part of a building

• Cause and effect is…

• Which dampers open

• Which dampers close

• Some of these dampers will be fire dampers, some smoke dampers

• Details hot/cold smoke extraction

• The wider cause and effect may include AOVs, fans and fire doors

Page 8: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Why Smoke Control?

Our industry understands better than most that it is not the fire that kills, but smoke.

• Grenfell Tower - shock waves through the building services industry.

• Under the radar … until disaster

Page 9: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

…Smoke is the #1 Killer in UK Fires.

Table Source: Home Office Incident Recording System / https://www.gov.uk/government/collections/fire-statisticsContact: [email protected]

38%

25%

16%

20%Overcome by gas or smokeBurnsBurns and overcome by gas or smokeOther/Unspecified

Page 10: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

The drive towards compliance….

• Product Standard BS EN12101-8

• Classification Standard BS EN13501-4

• Test Standard BS EN1366-10

• First published April 2011

• Widely used in Europe for smoke control

• UK had previously favoured fail-safe closed actuators, part 10 uses drive open/drive closed.

• Post-Grenfell fire, industry re-focusing on standards and applications.

Page 11: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Fire Dampers (MSFD or FD)

Fire damper function is to maintain compartmentation

• Fire dampers to be CE marked to BS EN 15650

• Tested to BS EN 1366-2

• Classified to BS EN 13501-3

Fire Dampers

✓ have thermal release mechanism at 72*C

✓ fail safe-close

✓ have fire resistance in closed position

✓ have known leakage characteristics (determining classification ‘E’ or ‘ES’)

Page 12: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Smoke Control Dampers (MSD)

Smoke control damper function is to contain/maintain an extraction path for smoke.

• The CE marked to BS EN 12101-8

• Tested to BS EN 1366-2 and BS EN1366-10

• Classified to BS EN 13501-4

Smoke control dampers:

✓Drive to open or closed position < 60 seconds

✓Maintain their position – non-fail safe

✓ Have known leakage characteristics

✓Maintain free area in open position at standard or elevated temperatures

Page 13: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Typical Application

Closed

Open

Fire resistant walls

Single compartment

Multi compartment

Multi compartment

Basement levels

Extract fan

Page 14: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Typical classification

E90(vew i↔o)S1000C10000AAmulti

• E90 = “integrity” fulfilled 90 minutes

• vew= installation in/on the duct running through vertical supporting construction

• i↔o = i – fire from inner to outer side, o – fire from outer to inner side

• S = tightnes against smoke spread – penetration < 200 m3/(hm2)

• 1000 = test by 1000 Pa pressure differential

• C10 000 = 10 000 cycles test open – close before fire test

• AA = automatic activation

• Multi = multi compartment usage

Page 15: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

E

EI

120

90

60

30

Cmod

C10000

C300

Hod

How

Hodw

I -> O

O <- I

I <->O

*S

*S = (200m3/h/m2

1500 (500)

1000 (300)

500 (150)

Ved

Vew

Vedw

MA

AA

Multi

Single

Hot

E 120 Vedw Hodw I<->O S 1500 Cmod Hot400/30 MA multi

E = Integrity (30,60,90,120)

I = Insulation rating (30,60,90,120

Classification Breakdown

Page 16: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

E

EI

120

90

60

30

Cmod

C10000

C300

Hod

How

Hodw

I -> O

O <- I

I <->O

*S

*S = (200m3/h/m2

1500 (500)

1000 (300)

500 (150)

Ved

Vew

Vedw

MA

AA

Multi

Single

Hot

E 120 Vedw Hodw I<->O S 1500 Cmod Hot400/30 MA multi

Ve = Vertical (d=duct w=wall dw=duct and wall)

Ho = Horizontal (d=duct w=wall dw=duct and wall)

Classification Breakdown

Page 17: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

E

EI

120

90

60

30

Cmod

C10000

C300

Hod

How

Hodw

I -> O

O <- I

I <->O

*S

*S = (200m3/h/m2

1500 (500)

1000 (300)

500 (150)

Ved

Vew

Vedw

MA

AA

Multi

Single

Hot

E 120 Vedw Hodw I<->O S 1500 Cmod Hot400/30 MA multi

“i→o”, “i ←o” and “i ↔o”,

Indicates that the performance criteria are satisfied from inside to outside (fire inside), outside to inside (fire

outside) or both, respectively.

Classification Breakdown

Page 18: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

E

EI

120

90

60

30

Cmod

C10000

C300

Hod

How

Hodw

I -> O

O <- I

I <->O

*S

*S = (200m3/h/m2

1500 (500)

1000 (300)

500 (150)

Ved

Vew

Vedw

MA

AA

Multi

Single

Hot

E 120 Vedw Hodw I<->O S 1500 Cmod Hot400/30 MA multi

S = Smoke leakage

Classification Breakdown

Page 19: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

E

EI

120

90

60

30

Cmod

C10000

C300

Hod

How

Hodw

I -> O

O <- I

I <->O

*S

*S = (200m3/h/m2

1500 (500)

1000 (300)

500 (150)

Ved

Vew

Vedw

MA

AA

Multi

Single

Hot

E 120 Vedw Hodw I<->O S 1500 Cmod Hot400/30 MA multi

“500”, “1 000” or “1 500” = Pressure level selected for a negative pressure during the test.

Classification Breakdown

Page 20: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

E

EI

120

90

60

30

Cmod

C10000

C300

Hod

How

Hodw

I -> O

O <- I

I <->O

*S

*S = (200m3/h/m2

1500 (500)

1000 (300)

500 (150)

Ved

Vew

Vedw

MA

AA

Multi

Single

Hot

E 120 Vedw Hodw I<->O S 1500 Cmod Hot400/30 MA multi

“C300”, “C10000” or “Cmod” indicates the suitability of the damper for use in smoke control only systems,

combined smoke control and environmental systems, or modulating dampers used in combined smoke

control and environmental systems, respectively.

Classification Breakdown

Page 21: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

E

EI

120

90

60

30

Cmod

C10000

C300

Hod

How

Hodw

I -> O

O <- I

I <->O

*S

*S = (200m3/h/m2

1500 (500)

1000 (300)

500 (150)

Ved

Vew

Vedw

MA

AA

Multi

Single

Hot

E 120 Vedw Hodw I<->O S 1500 Cmod Hot400/30 MA multi

We will now look at the last three parts of the classification in more detail!

Classification Breakdown

Page 22: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Hot 400/30

The test to achieve this part of the classification involves cycling the damper whilst the damper is under elevated temperature

• The test is 60 minutes long

• The damper is cycled every 150 seconds for the first 30 minutes rising from ambient to 400 degrees within 7 minutes.

• After 30 minutes the damper is to remains open for the duration of the test and the time temperature curve goes back to the standard time temperature curve. (38 minutes - 877°C, ending at 60 minutes - 945°C)

• Passing only the Hot400/30 test does NOT mean a damper is 1366-10

Page 23: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

AA / MA

Typically we use AA dampers in the UK for cold smoke clearance…

• AA Smoke control system with automatic activation smoke control system (smoke and heat exhaust ventilation type or pressure differential type), that operates automatically on receipt of a smoke or fire alarm without any manual action/intervention NOTE systems with an attended control room classed as an automatic system.

• MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put into manual operation, on detection smoke or fire. This is instigated with human intervention leading to a sequence of automatic actions.

• For most applications, we recommend using an AA system with dedicated damper control panel

Page 24: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Multi / Single

Single compartment smoke control damper :

“smoke control dampers for use in single

compartment areas, which may be associated with

smoke control duct tested according to EN1366-9

and/or may be installed in an external wall, floor or

roof [ceiling]“

Multi compartment fire resisting smoke control

damper: “smoke control dampers for use in multi

compartment areas, which may be associated with

smoke control duct tested according to EN1366-8

and/or may be installed within or on the face of a

fire compartment structure"

Closed

Open

Single compartment

Single compartment

Multi compartment

Multi compartment

Fire resistant walls

Extract

Page 25: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Typical basement smoke extract example

• Application is for smoke clearance from a basement –common in central London.

• Controlled by dedicated panel which will control the behavior of the damper

• Provide route for extracting smoke

Closed

Open

Fire resistant walls

Extract

A B

C D

EF

Damper Control Panel

Page 26: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

• Activity: Label suitable damper, single/mutli, AA or MA?

• A: SINGLE

• B: MULTI

• C: MULTI

• D: MULTI

• E: MULTI

• F: SINGLEClosed

Open

Fire resistant walls

Extract

A B

C D

EF

Damper Control Panel

Typical basement smoke extract example

Page 27: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

• Activity: Label suitable damper, single/mutli, AA or MA?

• Dampers should be of AA type activation

Closed

Open

Fire resistant walls

Extract

A B

C D

EF

Damper Control Panel

Typical basement smoke extract example

Page 28: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

• The rules governing which dampers open/close and how they are controlled is detailed in the cause and effect…

• In the event of a fire here…

• Which dampers should open/close?

Closed

Open

Fire resistant walls

Extract

A B

C D

EF

Damper Control Panel

Typical basement smoke extract example

Page 29: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Closed

Open

Fire resistant walls

Extract

A B

C D

EF

Damper Control Panel

Typical basement smoke extract example

• The rules governing which dampers open/close and how they are controlled is detailed in the cause and effect…

• In the event of a fire here…

• Which dampers should open/close?

Page 30: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Cause and effect

• The building is divided into zones

Page 31: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Cause and effect

• These zones are normally then mapped into a spreadsheet –which is used by all parties to ensure a joined-up controls strategy across fire alarm, damper, AHU/extract fans and the BMS

• Used by panel manufacturer to add controls logic to the panel

Page 32: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Controls

• Life safety product, with a <10s reaction time

• Thermal protection of devices and networks is paramount in event of fire

• There are numerous devices involved in the actuation of dampers

• Damper

• SDI decoder interface

• Cabling

• Damper Control Panel

• Benefits of using a dedicated damper control panel manufacturer

• Capable of complex ‘Cause and Effect’

• Integration into BMS systems

• Scheduled damper testing and status alerts

Page 33: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put
Page 34: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put
Page 35: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put
Page 36: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put
Page 37: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put
Page 38: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put
Page 39: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put
Page 40: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put
Page 41: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put
Page 42: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put
Page 43: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put
Page 44: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put
Page 45: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put
Page 46: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put
Page 47: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put
Page 48: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

BESA DW145 Guidelines

• Important aspects of FSD installations including

• Responsibility of all parties involved in the overall sequence from system specification through to compliant installation.

• Emphasis is placed on all parties to work as a team.

• DW145 indicates particular responsibilities that are allocated on a project specific basis.

Page 49: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

RIBA Plan of Works Stages – how can we apply this to Smoke Control

RIBA Stage 2 -concept design

Building designed into

zones - engage specialist

manufacturer

RIBA Stage 3 -developed

design

Draft cause and effect

strategy for dampers

RIBA Stage 4 -Detailed design

Specify correct dampers

according to cause and

effect

RIBA Stage 5 –Construction

Engage with building

control and specialists on

site

RIBA Stage 6 -Handover

Utilise specialist

manufacturers to support

commissioning

Page 50: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Conclusion

• Design your cause and effect early to outline cause and effect –then specify dampers, controls and actuators accordingly

• Take note of the ductwork specification 1366-8

• Smoke control is about providing a path for extracting smoke

• Recommended you use a dedicated controls system

• Make sure you use Multi Compartment vs Single Compartment dampers correctly

• A joined up approach – start to finish – key to executing the strategy

Page 51: Smoke and No Mirrors · • MA Smoke control system with manual intervention smoke control system (smoke and heat exhaust ventilation type or pressurization type), that will be put

Any Questions?