Smoke and heat exhaust systemsSafety thanks to certified smoke outlet devices – cost-effective and EN-compliant
Customized
IntelligenceDem Kunden dienen als Programm
The LAMILUX CI philosophy
Customer value is the reason we exist and is the focus of our activities. This requires harmony, identity and a balance between custom-er value and company strategy.
The principles that guide our company's actions and customer relations are set out in LAMILUX's company philosophy:
Customized intelligence – serving the customer is our mission.This requires outstanding performance and leadership in all areas relevant to customers, especially in the role as:
• A quality leader - optimum benefit for customers • A leader in innovation - at the cutting edge of technology • A leader in service - fast, uncomplicated, reliable and friendly • A leader in expertise - optimum sales and technical advisory services • Leader in solving problems - individual, tailor-made solutions
SHEV IN FIRE INCIDENTS – CERTIFIED SMOKE OUTLETS
and create SAFE CONDITIONS.
2
Customized
IntelligenceDem Kunden dienen als Programm
... rescue LIVES
... protect ASSETS and PROPERTY
... reduce BUSINESS RISKS
... provide ADDED VALUE
Experts from fire service associations, the German VdS Schadenverhütung fire protection and safety testing centre and the German Daylight
and Smoke Protection Systems Association agree: only certified smoke outlet devices create safe conditions in the event of fire.
• They are designed as per DIN 18232-2 and tested as per EN 12101-2.
• They prevent rooms from completely filling with smoke.
• They reliably provide a smoke-free layer.
• They contain the fire incident and minimise its consequences.
+ rely on DIN 18232-2 and EN 12101-2 to provide a certified smoke outlet device.
3
SHEV SYSTEMS – ESSENTIAL FOR SURVIVAL
CI SystemSmoke Lift F100
CI SystemSmoke Lift ME
CI SystemSmoke Lift B/S
CI SystemSmoke Lift M
Building system controls
Page 6 Page 10 Page 14 Page 22 Page 26
RESCUE lives: poisonous smoke fumes extracted
PROTECT assets and property: fire service given faster, more targeted access to extinguish fire
REDUCE business risks: less risk of production downtimes and failure to deliver
PROVIDE added value: energy-efficient daylight intake and ventilation function with SHEV systems
Certified smoke ventilation is only safe and efficient if provided by natural smoke and heat exhaust systems (SHEV) which
are designed according to specifications in DIN 18232-2.
These systems use thermal lift to channel smoke, heat and poisonous fumes into the open air. A smoke-free layer forms near the floor when
fresh air flows in, meaning:
• People can quickly escape into the open air.
• Emergency services have the air that they require to extinguish fires and rescue people trapped inside.
The most cost-intelligent solution for
each SHEV surface in the building Product overview
LAMILUX CI Systems and smoke and heat exhaust systems
LAMILUX CI SYSTEMSMOKE LIFT M | Page 22
LAMILUX CI SYSTEMSMOKE LIFT ME | Page 10
LAMILUX CI SYSTEMSmoke Lift B | Page 14
LAMILUX CI SYSTEMSMOKE LIFT SW
LAMILUX CI SYSTEMSmoke Lift B | Page 14
LAMILUX CI SYSTEMSmoke Lift ME DK | Page 12
LAMILUX CI SYSTEMSMOKE LIFT F100 | Page 6
LAMILUX CI SYSTEMAIR INLET DEVICES | Page 24
LAMILUX CI SYSTEMSmoke Lift S | Page 18
LAMILUX CI System Smoke Lift F100VERSATILE AND COST-EFFECTIVE
LAMILUX smoke lifts not only comply with fire service requirements for fast, efficient smoke and heat ventilation. They still
also meet a constructor's need to provide a cost-effective solution.
The LAMILUX CI System Smoke Lift F100 consists of an upstand for a roof mount and a glazed upper section. The SHEV units are much more
than 'off-the-rack' products and offer great diversity and flexibility: our extensive selection of accessories helps us to match LAMILUX Smoke
Lift F100 to individual requirements, customer wishes and structural conditions.
SHEV7
How you benefit
LAMILUX CI System Smoke Lift F100
• Tested to DIN EN 12101-2
• Does not strike the roof during test or false signal release
• CO2 cartridges in the heat exhaust unit are not damaged when an
alarm point
is triggered
• Complies with DIN 18234 with no additional work or expense
(see Page 8)
Test parameters as defined by DIN EN 12101-2 and test results
Flow coefficient Cv
Effective aerodynamic opening surface Aw
Functional reliability
Snow load
Low ambient temperature
Wind load
Heat resistance
between 0.60 & 0.75
between 0.6 m² and 3.38 m²
RE 50/1000
+ 10,000 ventilation function openings
SL 500 to 2400
T(-05) T(-10) T(-15)
WL 1500
B300
CO2
bar
24 V 48 V 230 V
230 V
Smoke and heat venti-lation:
Ventilation:
DIN 18234 – EASILY MET WITH LAMILUX
8Customized
IntelligenceDem Kunden dienen als Programm
Heavy surface protection
Sheet steel border
Heat insulation in compliance withDIN 18234-3, 4.1
Upstand with heat-insulatedbase flange and hard PVC connecting rail
ADDITIONAL
EXPENSE
LAMILUX solution
DIN 18234 is an all-important reference for flat roofs since the standard's scope of application has widened considerably over recent years. It has now no longer limited to purely industrial buildings. Moreover, roofs can now also be tested and classified for preventive fire protection with the aim of containing fire spread on roofs.
SHEV9
100/100
100/150
100/200
100/240
100/250
100/300
120/120
120/150
120/180
120/240
120/300
125/125
125/250
150/150
150/180
150/200
150/210
150/240
150/250
150/300
180/180
180/240
180/250
200/200
0.60
0.90
1.30
1.56
1.63
1.95
0.94
1.17
1.40
1.87
2.34
1.02
2.03
1.46
1.76
1.95
2.05
2.34
2.44
2.93
2.11
2.81
2.93
2.60
0.60
0.90
1.30
1.56
1.63
1.95
0.94
1.17
1.40
1.87
2.34
1.02
2.03
1.46
1.76
1.95
2.05
2.34
2.44
2.93
2.11
2.81
2.93
2.60
0.75
1.13
1.50
1.80
1.88
2.25
1.08
1.35
1.62
2.16
2.70
1.17
2.34
1.69
2.03
2.25
2.36
2.70
2.81
3.38
2.43
3.24
3.38
3.00
0.75
1.13
1.50
1.80
1.88
2.25
1.08
1.35
1.62
2.16
2.70
1.17
2.34
1.69
2.03
2.25
2.36
2.70
2.81
3.38
2.43
3.24
3.38
3.00
Aw values (m²)Sloped upstand
Aw values (m²)Sloped upstand
Aw values (m²)Sheer upstandwith spoiler
Aw values (m²)Sheer upstandwith spoiler
CO2 CO2 24V 24V48V 48V230V 230V
10Customized
IntelligenceDem Kunden dienen als Programm
CI System Smoke Lift MEA MODULAR SMOKE AND HEAT VENTILATION SYSTEM
Certified safety – energy efficiency – comfort: with CI System Glass Architecture ME, we have developed a daylight system
that unites these three aspects in a single roof system. Thanks to a combination between numerous innovations, this flat
window with real glazing complies with important safety-relevant requirements:
• CI System Smoke Lift ME meets Building Materials Class A1 requirements and is thus non-flammable.
• Complies with EN 12101-2 as a smoke and heat ventilation system
German federal state building codes sometimes require translucent roofing to be made of non-flammable construction materials. CI System
Glass Architecture ME is classified as a smoke and heat ventilation system in compliance with EN 12101-2 when combined with a 24-volt
drive, for example, and provides fire protection in vulnerable areas of buildings.
SHEV11
Test parameters as defined by DIN EN 12101-2 and test results
Flow coefficient Cv
Effective aerodynamic opening surface Aw
Functional reliability
Snow load
Low ambient temperature
Wind load
Heat resistance
0.57
between 0.38 m² and 0.73 m²
RE 50/1000
+ 10,000 ventilation function openings
SL 500 to 1000
T(00) T(-05) T(-15)
WL 1500
B300
100/100
100/150
120/120
125/125
0.38
0.62
0.59
0.65
0.38
0.62
0.59
0.65
0.45
0.70
0.67
0.73
0.45
0.70
0.67
0.73
Aw values (m²)Sloped upstand
Aw values (m²)Sloped upstand
Aw values (m²)Sheer upstand
Aw values (m²)Sheer upstand
CO2 CO2 24V 24V
How you benefit
LAMILUX CI System Smoke Lift ME
• Building material class A1 (non-flammable)
• Watertight against driving rain (Class E 1200 EN 12208)
• Resistant to high wind
loads (Class C4/B5, EN 12210)
• Permanent fall-through protection system (GSBAU 18)
• Excellent heat-insulation properties
(Ug values of 1.1 to 0.6 W/(m²K) as per EN 673)
• Total energy permeability g between18 and 78 per cent
• Optimum airtightness (Class 4 EN 12207)
• Light transmission Lτ between 19 to 82 per cent available
12Customized
IntelligenceDem Kunden dienen als Programm
CI System Smoke Lift ME DKDOUBLE THE SAFETY
CI System Double Flap ME DK combines a SHEV function (smoke extraction as per EN 12101-2), optimum daylight intake
and natural ventilation in a compact system. This soundproofed daylight element impresses due to its extremely good heat
insulation properties.
CI System Double Flap ME can be supplied in a very large format and thus feature a highly effective, aerodynamic smoke extraction surface.
This daylight system is also designed to incorporate the frequently used fair weather ventilation system. Driven by a pneumatic system or an
electrical motor (24V in compliance with EN 12101-2 or 230V), ventilation flaps can be opened up to an angle of 90°. Intelligent control of the
ventilation function enables users to adjust individual air exchange rates perfectly to their needs.
SHEV13
Test parameters as defined by DIN EN 12101-2 and test results
Flow coefficient Cv
Effective aerodynamic opening surface Aw
Functional reliability
Snow load
Low ambient temperature
Wind load
Heat resistance
0.68
between 0.90 m² and 2.92 m²
RE 50/1000
+ 10,000 ventilation function openings
SL 500 to 1000
T(00) T(-05) T(-15)
WL 1500
B300
120/120
120/180
120/240
125/250
150/150
150/180
150/200
150/210
150/240
150/250
180/180
180/240
180/250
200/200
0.90
1.37
1.84
2.00
1.43
1.73
1.92
2.02
2.32
2.42
2.08
2.80
2.92
2.59
0.90
1.37
1.43
1.73
1.92
2.02
2.08
2.59
Aw values (m²)Sheer upstand
Aw values (m²)Sheer upstand
CO2 24V
How you benefit
LAMILUX CI System Smoke Lift ME DK
• Watertight against driving rain (Class E 1200 EN 12208)
• Resistant to high wind
loads (Class C4/B5, EN 12210)
• Excellent heat-insulation properties
(Ug values of 1.1 to 0.6 W/(m²K) as per EN 673)
• Total energy permeability g between18 and 78 per cent
• Optimum airtightness (Class 4 EN 12207)
• Adverse weather ventilation optional
LAMILUX CI System Smoke Lift BSMOKE EXHAUST WITH OPTIMUM ENERGY EFFICIENCY
CI System Continuous Rooflight B is equipped with smoke and heat ventilation devices that fulfil all EN 12101-2 require-
ments. Single or double flaps are integrated to provide a smoke and heat exhaust ventilation system and can be activated
to provided normal ventilation or fair weather ventilation.
Energy efficiency: the blower door test demonstrates the optimum airtightness in the continuous rooflight system when flaps are closed.
Safety and stability: open SHEV flaps offer very strong resistance to wind loads, even when they feature large dimensions. This is guaranteed
by spring-loaded, multiple-joint traverses connected directly to the flap structure.
SHEV15
Test parameters as defined by DIN EN 12101-2 and test results
Flow coefficient Cv
Effective aerodynamic opening surface Aw
Functional reliability
Snow load
Low ambient temperature
Wind load
Heat resistance
between 0.60 & 0.65
between 0.59 m² and 7.40 m²
RE 1000 + 10,000 ventilation function openings
RE 11000
SL 500
T(-5)
WL 1500
B300
CO2
bar
24V 48V 230V
230V
Smoke and heat ventilation:
Ventilation:
How you benefit
LAMILUX CI System Smoke Lift B
• No spreading of flames as DIN 18234 requirements are met
thanks to Linear Burn-through Protection (LBP)
• Thermal release with CO2 - cylinder is not damaged during tests
or due to false alarms
• Excellent heat-insulation values with no thermal bridges
• Suitable as a melt-out roof surface in accordance with DIN 18230
and available as 'hard roofing' upon request; in accordance with
DIN 4102-7, resistant to flying sparks and radiated heat
16Customized
IntelligenceDem Kunden dienen als Programm
Many flap combinations for market-leading
smoke and heat exhaust units
Dimensions never seen before can be achieved in SHEV systems thanks to a new technology. The CI System Smoke Lift B can be integrated
into continuous rooflight structures as a single or double flap in numerous potential combinations to create optimum, building-specific smoke
extraction surfaces. In the event of a fire, flaps are quickly opened by thermal release, thermal and CO2 remote release or electric remote
release. The SHEV flap systems can also be used for ventilation and activated electrically/pneumatically.
CI System Smoke Lift B with a single flap
CI System Smoke Lift B
with symmetric double flap system
16
SHEV17
Smoke Lift BE with single flap
100
TS
125
TS
150
TS
Smoke Lift BA with asymmetric double flap system
175
TS
200
TS
Smoke Lift BD with symmetric double flap system
250
TS
300
TS
TS = tandem-series heat exhaust unit
100
200
420
100
200
420
100
200
420
100
200
420
100
200
420
100
200
420
100
200
420
0.93
1.96
4.01
1.17
2.46
5.04
1.43
3.01
6.17
1.67
3.51
7.20
1.91
4.01
8.22
2.39
5.02
10.28
2.87
6.02
12.34
0.59
1.27
2.53
0.74
1.60
3.18
0.90
1.96
3.83
1.04
2.28
4.68
1.18
2.61
5.43
1.48
3.26
6.37
1.78
3.91
7.40
Free opening surface Ageo in m²
Effective aerodynamic opening surface Aw in m²
18Customized
IntelligenceDem Kunden dienen als Programm
CI System Smoke Lift SA MODULAR SMOKE AND HEAT VENTILATION SYSTEM
If needed, you can equip CI System Continuous Rooflight S with smoke and heat ventilation devices that fulfil EN 12101-2
requirements.
Thermally separated flap systems for smoke and heat exhaust and natural ventilation can be integrated into the extremely stable, thermal
bridge-free structure with span widths up to six metres. They can be fitted into continuous rooflights in a modular system combining different
sized versions, ideally matched to the required smoke exhaust surface
CO2
bar
24V 48V 230V
230V
Smoke and heat ventilation:
Ventilation:
SHEV19
Test parameters as defined by DIN EN 12101-2 and test results
Flow coefficient Cv
Effective aerodynamic opening surface Aw
Functional reliability
Snow load
Low ambient temperature
Wind load
Heat resistance
between 0.60 & 0.65
between 0.32 m² and 5.08 m²
RE 1000 + 10,000 ventilation function openings
RE 11000
SL 500
T(-5)
WL 1500
B300
How you benefit
LAMILUX CI System Smoke Lift S
• Suitable as a melt-out surface
• Good heat insulation values
• The ideal solution when the architecture requires a ridged roof
shape
• Thermal release with CO2 - cylinder is not damaged during tests
or due to false alarms
Upper edge of roofx
y
CI System Smoke SE30 with single flap
100
100*
150
150*
200
200*
250
250*
300
300*
CI System Smoke SE45 with single flap
80
80*
120
120*
160
160*
200
200*
240
240*
CI System Smoke SE-SHED60 with single flap
100
100*
150
150*
200
200*
250
250*
300
300*
100
120
100
120
100
120
100
120
100
120
100
120
100
120
100
120
100
120
100
120
100
120
100
120
100
120
100
120
100
120
0.53 m²
0.63 m²
0.82 m²
0.97 m²
1.11 m²
1.31 m²
1.40 m²
1.65 m²
1.69 m²
1.99 m²
0.53 m²
0.63 m²
0.82 m²
0.97 m²
1.11 m²
1.31 m²
1.40 m²
1.65 m²
1.69 m²
1.99 m²
0.53 m²
0.63 m²
0.82 m²
0.97 m²
1.11 m²
1.31 m²
1.40 m²
1.65 m²
1.69 m²
1.99 m²
53
53
82
82
111
111
140
140
169
169
53
53
82
82
111
111
140
140
169
169
53
53
82
82
111
111
140
140
169
169
0.32 m²
0.38 m²
0.49 m²
0.58 m²
0.64 m²
0.76 m²
0.80 m²
0.92 m²
0.95 m²
1.09 m²
0.33 m²
0.38 m²
0.51 m²
0.58 m²
0.67 m²
0.77 m²
0.80 m²
0.94 m²
0.96 m²
1.12 m²
0.32 m²
0.38 m²
0.49 m²
0.58 m²
0.64 m²
0.76 m²
0.80 m²
0.92 m²
0.95 m²
1.09 m²
Opening surface Ageo
Upper edge of roof size
Dimension X Dimension Y Effective aerodynamic opening surface
20Customized
IntelligenceDem Kunden dienen als Programm
CI System Smoke Lift SD30 with double flap system
100
100*
100
100 TS**
150
150*
150
150 TS**
200
200*
200
200 TS**
250
250*
250
250 TS**
300
300*
300 TS**
300* TS**
CI System Smoke Lift SD45 with double flap system
120
120*
120
120 TS**
160
160*
160
160 TS**
200
200*
200
200 TS**
240
240*
240 TS**
240* TS**
* In combination with glazing type PC 32-5 and PC 32-5 + GRP** Tandem-series heat exhaust unit
100
120
200
420
100
120
200
420
100
120
200
420
100
120
200
420
100
120
210
240
100
120
200
420
100
120
200
420
100
120
200
420
100
120
210
240
1.02 m²
1.20 m²
2.09 m²
4.24 m²
1.52 m²
1.79 m²
3.12 m²
6.32 m²
2.02 m²
2.38 m²
4.14 m²
8.40 m²
2.52 m²
2.97 m²
5.17 m²
10.48 m²
3.02 m²
3.56 m²
6.21 m²
7.31 m²
1.22 m²
1.43 m²
2.49 m²
5.05 m²
1.63 m²
1.92 m²
3.33 m²
6.76 m²
2.04 m²
2.40 m²
4.17 m²
8.47 m²
2.45 m²
2.89 m²
5.03 m²
5.92 m²
53
53
53
53
82
85
82
82
111
111
111
111
140
140
140
140
169
169
169
169
82
82
82
82
111
111
111
111
140
140
140
140
169
169
169
169
0.64 m²
0.75 m²
1.27 m²
2.42 m²
0.96 m²
1.11 m²
1.90 m²
3.48 m²
1.25 m²
1.48 m²
2.57 m²
4.96 m²
1.54 m²
1.84 m²
3.21 m²
6.50 m²
1.84 m²
2.21 m²
3.85 m²
4.53 m²
0.94 m²
1.09 m²
1.84 m²
3.54 m²
1.25 m²
1.46 m²
2.47 m²
4.39 m²
1.51 m²
1.68 m²
2.71 m²
5.08 m²
1.71 m²
1.90 m²
3.02 m²
3.49 m²
Opening surface Ageo
Upper edge of roof size
Dimension X Dimension Y Effective aerodynamic opening surface
SHEV21
LAMILUX CI System Smoke Lift MGREATER SAFETY IN PREVENTIVE FIRE PROTECTION
This smoke and heat exhaust ventilation unit is an ideal flap system for smoke and heat exhaust ventilation in LAMILUX glass roof structures.
It can be easily installed at angles between 0° to 90°.
SHEV23
Test parameters as defined by DIN EN 12101-2 and test results
Flow coefficient Cv
Effective aerodynamic opening surface Aw
Functional reliability
Snow load
Low ambient temperature
Wind load
Heat resistance
between 0.56 & 0.70
between 0.14 m² and 6.00 m²
RE 50/1000
+ 10,000 ventilation function openings
SL 500 to SL 1000
T(00) T(-05) T(-15)
WL 1500
B300
CO2
bar
24 V 48 V 230V
230V
Smoke and heat ventilation:
Ventilation:
How you benefit
LAMILUX CI System Smoke Lift M
• Flap widths and heights can be freely selected up to 2.50
m, covering a maximum flap size of 3.00 m² with real glazing,
or up to 3.50 m² with polycarbonate glazing
• Complies with European standard EN 12101-2 for smoke and
heat evacuation systems
• Selection of drive systems - pneumatic or 24 volt electric
version
• Perfectly suited for retrofitting to older roof structures as it can
be integrated into other systems
LAMILUX CI System G-Air
LAMILUX CI System B-Air
OPTIMUM EFFICIENCY
SHEV25
Material
Extruded, thermally separated aluminium profiles
Sizes
Width: up to 1,800 mm without centre post
1,801 – 2,400 mm with centre post
Height: 300 mm and above
Louver slats
Aluminium panel (Ug = 1.0 to 1.3 W/m²K)
Insulating glass (Ug = 0.7 to 1.1 W/m²K)
Drives
Pneumatic cylinder
24 V electric motor
Material
Aluminium
Sizes
Width: 600 - 2400 mm
Length (height): 720 - 2920 mm
Louver slats
Aluminium, single- or double-skinned, thermally insulated
Polycarbonate opal or transparent
Insulation glass
Drives
Pneumatic cylinder
24 V electric motor
LAMILUX building control systemsSAFE – ENERGY-EFFICIENT – CONVENIENT
Safety, energy efficiency and comfort in a building are largely determined by building control systems. They are the key to
sustainable, value-based future construction.
LAMILUX provides project planning and equips buildings with complex building control systems featuring networked functions. As a specialist
company with many years' experience in both large and small projects, we provide intelligent controls and automation for fire safety, energy
efficiency and building comfort.
Plan - Network - Automate
From small control solutions through to complex building automation systems in large projects, LAMILUX offers all services from a single
source, including trade contracting. It reliably provides everything from planning and design concepts for electric or pneumatic control systems
and components through to their installation, initial operation and maintenance.
14Customized
IntelligenceDem Kunden dienen als Programm
26
Control with our systems
• Smoke and heat exhaust systems
• Flap systems for natural ventilation
• Solar protection and light guidance
• Sensor-activated electric lighting switches
• Temperature-sensitive switches on climate control units
and benefit from smart networking building safety, energy
efficiency and building comfort.
SHEV27
Smoke removal openings for stairwaysNON-SYSTEM CONNECTED – ELECTRIC
Many European countries have special regulations for stairways. In most cases, smoke must be removed from stairways
using electrically controlled, mains-independent systems. That is why LAMILUX supplies smoke removal openings special-
ly designed for stairways, although they may also be fitted in any type of building or structure.
Our standard set comprises:
• 1 electric motor with a 500 mm stroke, 24 V, disconnection under load
• 1 control unit for a maximum of two motors with control connectors for SHEVS
and ventilation buttons, and various peripherals such as smoke alarms,
thermal alarms or wind and rain sensors
• 2 SHEV control switches with visual display, surface mounted
• 1 flush-mounted fan button for 55 mm switch box
• Single item deliveries and upgrades are possible
14Customized
IntelligenceDem Kunden dienen als Programm
28
Renovation of SHEV systems
A SINGLE PARTNER FOR MANY THINGS INSTEAD OF MANY PARTNERS
When smoke and heat exhaust systems start to age, customer advisory services and a professional renovation are often not
only expensive, but also involve a great deal of work. Not if you work with LAMILUX, however.
Customer advisory services, tailored solutions, including control technology, and all work involved in the upgrade from a single source: On
request, LAMILUX will handle the entire renovation package for you. We start with an initial survey to establish what the existing system
contains, if the existing conditions comply with new statutory regulations and what the most cost-effective solution would be. We then draw
up a design concept, arrange demolition and waste disposal, implement safety measures to protect your employees and assets, and install
the system in close cooperation with established partners in the roof building sector. Our specialists are responsible for installing the complex
control technology.
SHEV29
SHEV systems must workFAILING TO MAINTAIN MAKES YOU LIABLE
Smoke and heat ventilation system owners are required by law to perform all necessary measures to ensure that people are
protected against danger in the event of a fire. If you do not maintain your SHEV system, you may be in breach of building
safety regulations, DIN 18232, state directives and other directly or indirectly applicable laws.
If you maintain your SHEV system on a regular basis, you will not only minimise the risk of damage and injury considerably, but also liability
risk.
Inadequate maintenance will also make you liable.
According to VdS guidelines, servicing can only be carried out by companies which can provide a promise from the SHEV system installer
to deliver original replacement parts.
Customized
IntelligenceDem Kunden dienen als Programm
You are involved in the construction of a new building or renovation of an old one and wish to make things safer with preventive fire protection
based on SHEV systems. We will gladly provide you with a consultation related to your project. We will assist you with project-specific planning
and correct SHEV system dimensioning and find tailor-made, building-specific solutions together with you.
The sheer numbers of rules, regulations and directives in preventive fire protection for buildings is daunting, especially where they relate to
smoke and heat ventilation. But what help do industrial standards, industrial guidelines or building codes offer with planning and installing
SHEV systems? What character does a statutory regulation have? What is an interpretable provision or simply a flexible guideline?
Our training programme will provide you with a way through the maze of regulations and their interpretation. This programme is aimed at our
customers and building services planners, on the one hand, and public agencies and fire services on the other.
Benefit from our practical experience
We offer guidance through the maze of regulations
PROJECT-RELATED CONSULTATION
TRAINING ON SHEVS AND PREVENTIVE FIRE PROTECTION
1430
SHEV open only SHEV open onlyVentilation function
SHEV open/closeVentilation function
SHEV open/closeFair weather ventilation
Pneumatic SHEV:
Electric SHEV:
Pneumatic SHEV:
Electric SHEV:
Pneumatic SHEV:
Electric SHEV:
Pneumatic SHEV:
Electric SHEV:
SHEV
SHEV open/close
Pneumatic SHEV:
Electric SHEV:
31
The technical data printed in this brochure was accurate when this brochure went to press and is subject to change without notice. Our technical specifications are based on calculations and supplier information or have been determined by independent testing authorities within the scope of applicable standards. Thermal transmission coefficients for our composite glazing were calculated using the finite element method with reference values as per DIN EN 673 for insulated glass. Based on empirical values and specific characteristics of the composites, a temperature vector of 15 K was defined as the vector between the outer surfaces of the material. Functional values refer to test specimens and the dimensions used in testing only. We cannot provide any further guarantees of technical values. This particularly applies to changes in installation locations or if dimensions are re-measured on site.
ROOFLIGHT DOME F100GLASS ELEMENT F
CONTINUOUS ROOFLIGHT B
LIGHT PANEL
GLASS ARCHITECTURE PR 60
AIR INLET DEVICES
CONTINUOUS ROOFLIGHT S
BUILDING UPGRADES
SMOKE AND HEAT EXHAUSTVENTILATION SYSTEMS
PHOTOVOLTAIC SYSTEMSBUILDING CONTROL SYSTEMS
FIBRE-REINFORCED COMPOSITES