Smoke and heat exhaust systemsSafety thanks to certified smoke outlet devices – cost-effective and EN-compliant

Customized

IntelligenceDem Kunden dienen als Programm

The LAMILUX CI philosophy

Customer value is the reason we exist and is the focus of our activities. This requires harmony, identity and a balance between custom-er value and company strategy.

The principles that guide our company's actions and customer relations are set out in LAMILUX's company philosophy:

Customized intelligence – serving the customer is our mission.This requires outstanding performance and leadership in all areas relevant to customers, especially in the role as:

• A quality leader - optimum benefit for customers • A leader in innovation - at the cutting edge of technology • A leader in service - fast, uncomplicated, reliable and friendly • A leader in expertise - optimum sales and technical advisory services • Leader in solving problems - individual, tailor-made solutions

SHEV IN FIRE INCIDENTS – CERTIFIED SMOKE OUTLETS

and create SAFE CONDITIONS.

2

Customized

IntelligenceDem Kunden dienen als Programm

... rescue LIVES

... protect ASSETS and PROPERTY

... reduce BUSINESS RISKS

... provide ADDED VALUE

Experts from fire service associations, the German VdS Schadenverhütung fire protection and safety testing centre and the German Daylight

and Smoke Protection Systems Association agree: only certified smoke outlet devices create safe conditions in the event of fire.

• They are designed as per DIN 18232-2 and tested as per EN 12101-2.

• They prevent rooms from completely filling with smoke.

• They reliably provide a smoke-free layer.

• They contain the fire incident and minimise its consequences.

+ rely on DIN 18232-2 and EN 12101-2 to provide a certified smoke outlet device.

3

SHEV SYSTEMS – ESSENTIAL FOR SURVIVAL

CI SystemSmoke Lift F100

CI SystemSmoke Lift ME

CI SystemSmoke Lift B/S

CI SystemSmoke Lift M

Building system controls

Page 6 Page 10 Page 14 Page 22 Page 26

RESCUE lives: poisonous smoke fumes extracted

PROTECT assets and property: fire service given faster, more targeted access to extinguish fire

REDUCE business risks: less risk of production downtimes and failure to deliver

PROVIDE added value: energy-efficient daylight intake and ventilation function with SHEV systems

Certified smoke ventilation is only safe and efficient if provided by natural smoke and heat exhaust systems (SHEV) which

are designed according to specifications in DIN 18232-2.

These systems use thermal lift to channel smoke, heat and poisonous fumes into the open air. A smoke-free layer forms near the floor when

fresh air flows in, meaning:

• People can quickly escape into the open air.

• Emergency services have the air that they require to extinguish fires and rescue people trapped inside.

The most cost-intelligent solution for

each SHEV surface in the building Product overview

LAMILUX CI Systems and smoke and heat exhaust systems

LAMILUX CI SYSTEMSMOKE LIFT M | Page 22

LAMILUX CI SYSTEMSMOKE LIFT ME | Page 10

LAMILUX CI SYSTEMSmoke Lift B | Page 14

LAMILUX CI SYSTEMSMOKE LIFT SW

LAMILUX CI SYSTEMSmoke Lift B | Page 14

LAMILUX CI SYSTEMSmoke Lift ME DK | Page 12

LAMILUX CI SYSTEMSMOKE LIFT F100 | Page 6

LAMILUX CI SYSTEMAIR INLET DEVICES | Page 24

LAMILUX CI SYSTEMSmoke Lift S | Page 18

LAMILUX CI System

Smoke Lift F100

6Customized

IntelligenceDem Kunden dienen als Programm

LAMILUX CI System Smoke Lift F100VERSATILE AND COST-EFFECTIVE

LAMILUX smoke lifts not only comply with fire service requirements for fast, efficient smoke and heat ventilation. They still

also meet a constructor's need to provide a cost-effective solution.

The LAMILUX CI System Smoke Lift F100 consists of an upstand for a roof mount and a glazed upper section. The SHEV units are much more

than 'off-the-rack' products and offer great diversity and flexibility: our extensive selection of accessories helps us to match LAMILUX Smoke

Lift F100 to individual requirements, customer wishes and structural conditions.

SHEV7

How you benefit

LAMILUX CI System Smoke Lift F100

• Tested to DIN EN 12101-2

• Does not strike the roof during test or false signal release

• CO2 cartridges in the heat exhaust unit are not damaged when an

alarm point

is triggered

• Complies with DIN 18234 with no additional work or expense

(see Page 8)

Test parameters as defined by DIN EN 12101-2 and test results

Flow coefficient Cv

Effective aerodynamic opening surface Aw

Functional reliability

Snow load

Low ambient temperature

Wind load

Heat resistance

between 0.60 & 0.75

between 0.6 m² and 3.38 m²

RE 50/1000

+ 10,000 ventilation function openings

SL 500 to 2400

T(-05) T(-10) T(-15)

WL 1500

B300

CO2

bar

24 V 48 V 230 V

230 V

Smoke and heat venti-lation:

Ventilation:

DIN 18234 – EASILY MET WITH LAMILUX

8Customized

IntelligenceDem Kunden dienen als Programm

Heavy surface protection

Sheet steel border

Heat insulation in compliance withDIN 18234-3, 4.1

Upstand with heat-insulatedbase flange and hard PVC connecting rail

ADDITIONAL

EXPENSE

LAMILUX solution

DIN 18234 is an all-important reference for flat roofs since the standard's scope of application has widened considerably over recent years. It has now no longer limited to purely industrial buildings. Moreover, roofs can now also be tested and classified for preventive fire protection with the aim of containing fire spread on roofs.

SHEV9

100/100

100/150

100/200

100/240

100/250

100/300

120/120

120/150

120/180

120/240

120/300

125/125

125/250

150/150

150/180

150/200

150/210

150/240

150/250

150/300

180/180

180/240

180/250

200/200

0.60

0.90

1.30

1.56

1.63

1.95

0.94

1.17

1.40

1.87

2.34

1.02

2.03

1.46

1.76

1.95

2.05

2.34

2.44

2.93

2.11

2.81

2.93

2.60

0.60

0.90

1.30

1.56

1.63

1.95

0.94

1.17

1.40

1.87

2.34

1.02

2.03

1.46

1.76

1.95

2.05

2.34

2.44

2.93

2.11

2.81

2.93

2.60

0.75

1.13

1.50

1.80

1.88

2.25

1.08

1.35

1.62

2.16

2.70

1.17

2.34

1.69

2.03

2.25

2.36

2.70

2.81

3.38

2.43

3.24

3.38

3.00

0.75

1.13

1.50

1.80

1.88

2.25

1.08

1.35

1.62

2.16

2.70

1.17

2.34

1.69

2.03

2.25

2.36

2.70

2.81

3.38

2.43

3.24

3.38

3.00

Aw values (m²)Sloped upstand

Aw values (m²)Sloped upstand

Aw values (m²)Sheer upstandwith spoiler

Aw values (m²)Sheer upstandwith spoiler

CO2 CO2 24V 24V48V 48V230V 230V

10Customized

IntelligenceDem Kunden dienen als Programm

CI System Smoke Lift MEA MODULAR SMOKE AND HEAT VENTILATION SYSTEM

Certified safety – energy efficiency – comfort: with CI System Glass Architecture ME, we have developed a daylight system

that unites these three aspects in a single roof system. Thanks to a combination between numerous innovations, this flat

window with real glazing complies with important safety-relevant requirements:

• CI System Smoke Lift ME meets Building Materials Class A1 requirements and is thus non-flammable.

• Complies with EN 12101-2 as a smoke and heat ventilation system

German federal state building codes sometimes require translucent roofing to be made of non-flammable construction materials. CI System

Glass Architecture ME is classified as a smoke and heat ventilation system in compliance with EN 12101-2 when combined with a 24-volt

drive, for example, and provides fire protection in vulnerable areas of buildings.

SHEV11

Test parameters as defined by DIN EN 12101-2 and test results

Flow coefficient Cv

Effective aerodynamic opening surface Aw

Functional reliability

Snow load

Low ambient temperature

Wind load

Heat resistance

0.57

between 0.38 m² and 0.73 m²

RE 50/1000

+ 10,000 ventilation function openings

SL 500 to 1000

T(00) T(-05) T(-15)

WL 1500

B300

100/100

100/150

120/120

125/125

0.38

0.62

0.59

0.65

0.38

0.62

0.59

0.65

0.45

0.70

0.67

0.73

0.45

0.70

0.67

0.73

Aw values (m²)Sloped upstand

Aw values (m²)Sloped upstand

Aw values (m²)Sheer upstand

Aw values (m²)Sheer upstand

CO2 CO2 24V 24V

How you benefit

LAMILUX CI System Smoke Lift ME

• Building material class A1 (non-flammable)

• Watertight against driving rain (Class E 1200 EN 12208)

• Resistant to high wind

loads (Class C4/B5, EN 12210)

• Permanent fall-through protection system (GSBAU 18)

• Excellent heat-insulation properties

(Ug values of 1.1 to 0.6 W/(m²K) as per EN 673)

• Total energy permeability g between18 and 78 per cent

• Optimum airtightness (Class 4 EN 12207)

• Light transmission Lτ between 19 to 82 per cent available

12Customized

IntelligenceDem Kunden dienen als Programm

CI System Smoke Lift ME DKDOUBLE THE SAFETY

CI System Double Flap ME DK combines a SHEV function (smoke extraction as per EN 12101-2), optimum daylight intake

and natural ventilation in a compact system. This soundproofed daylight element impresses due to its extremely good heat

insulation properties.

CI System Double Flap ME can be supplied in a very large format and thus feature a highly effective, aerodynamic smoke extraction surface.

This daylight system is also designed to incorporate the frequently used fair weather ventilation system. Driven by a pneumatic system or an

electrical motor (24V in compliance with EN 12101-2 or 230V), ventilation flaps can be opened up to an angle of 90°. Intelligent control of the

ventilation function enables users to adjust individual air exchange rates perfectly to their needs.

SHEV13

Test parameters as defined by DIN EN 12101-2 and test results

Flow coefficient Cv

Effective aerodynamic opening surface Aw

Functional reliability

Snow load

Low ambient temperature

Wind load

Heat resistance

0.68

between 0.90 m² and 2.92 m²

RE 50/1000

+ 10,000 ventilation function openings

SL 500 to 1000

T(00) T(-05) T(-15)

WL 1500

B300

120/120

120/180

120/240

125/250

150/150

150/180

150/200

150/210

150/240

150/250

180/180

180/240

180/250

200/200

0.90

1.37

1.84

2.00

1.43

1.73

1.92

2.02

2.32

2.42

2.08

2.80

2.92

2.59

0.90

1.37

1.43

1.73

1.92

2.02

2.08

2.59

Aw values (m²)Sheer upstand

Aw values (m²)Sheer upstand

CO2 24V

How you benefit

LAMILUX CI System Smoke Lift ME DK

• Watertight against driving rain (Class E 1200 EN 12208)

• Resistant to high wind

loads (Class C4/B5, EN 12210)

• Excellent heat-insulation properties

(Ug values of 1.1 to 0.6 W/(m²K) as per EN 673)

• Total energy permeability g between18 and 78 per cent

• Optimum airtightness (Class 4 EN 12207)

• Adverse weather ventilation optional

LAMILUX CI System

Smoke Lift B

14Customized

IntelligenceDem Kunden dienen als Programm

14

LAMILUX CI System Smoke Lift BSMOKE EXHAUST WITH OPTIMUM ENERGY EFFICIENCY

CI System Continuous Rooflight B is equipped with smoke and heat ventilation devices that fulfil all EN 12101-2 require-

ments. Single or double flaps are integrated to provide a smoke and heat exhaust ventilation system and can be activated

to provided normal ventilation or fair weather ventilation.

Energy efficiency: the blower door test demonstrates the optimum airtightness in the continuous rooflight system when flaps are closed.

Safety and stability: open SHEV flaps offer very strong resistance to wind loads, even when they feature large dimensions. This is guaranteed

by spring-loaded, multiple-joint traverses connected directly to the flap structure.

SHEV15

Test parameters as defined by DIN EN 12101-2 and test results

Flow coefficient Cv

Effective aerodynamic opening surface Aw

Functional reliability

Snow load

Low ambient temperature

Wind load

Heat resistance

between 0.60 & 0.65

between 0.59 m² and 7.40 m²

RE 1000 + 10,000 ventilation function openings

RE 11000

SL 500

T(-5)

WL 1500

B300

CO2

bar

24V 48V 230V

230V

Smoke and heat ventilation:

Ventilation:

How you benefit

LAMILUX CI System Smoke Lift B

• No spreading of flames as DIN 18234 requirements are met

thanks to Linear Burn-through Protection (LBP)

• Thermal release with CO2 - cylinder is not damaged during tests

or due to false alarms

• Excellent heat-insulation values with no thermal bridges

• Suitable as a melt-out roof surface in accordance with DIN 18230

and available as 'hard roofing' upon request; in accordance with

DIN 4102-7, resistant to flying sparks and radiated heat

16Customized

IntelligenceDem Kunden dienen als Programm

Many flap combinations for market-leading

smoke and heat exhaust units

Dimensions never seen before can be achieved in SHEV systems thanks to a new technology. The CI System Smoke Lift B can be integrated

into continuous rooflight structures as a single or double flap in numerous potential combinations to create optimum, building-specific smoke

extraction surfaces. In the event of a fire, flaps are quickly opened by thermal release, thermal and CO2 remote release or electric remote

release. The SHEV flap systems can also be used for ventilation and activated electrically/pneumatically.

CI System Smoke Lift B with a single flap

CI System Smoke Lift B

with symmetric double flap system

16

SHEV17

Smoke Lift BE with single flap

100

TS

125

TS

150

TS

Smoke Lift BA with asymmetric double flap system

175

TS

200

TS

Smoke Lift BD with symmetric double flap system

250

TS

300

TS

TS = tandem-series heat exhaust unit

100

200

420

100

200

420

100

200

420

100

200

420

100

200

420

100

200

420

100

200

420

0.93

1.96

4.01

1.17

2.46

5.04

1.43

3.01

6.17

1.67

3.51

7.20

1.91

4.01

8.22

2.39

5.02

10.28

2.87

6.02

12.34

0.59

1.27

2.53

0.74

1.60

3.18

0.90

1.96

3.83

1.04

2.28

4.68

1.18

2.61

5.43

1.48

3.26

6.37

1.78

3.91

7.40

Free opening surface Ageo in m²

Effective aerodynamic opening surface Aw in m²

18Customized

IntelligenceDem Kunden dienen als Programm

CI System Smoke Lift SA MODULAR SMOKE AND HEAT VENTILATION SYSTEM

If needed, you can equip CI System Continuous Rooflight S with smoke and heat ventilation devices that fulfil EN 12101-2

requirements.

Thermally separated flap systems for smoke and heat exhaust and natural ventilation can be integrated into the extremely stable, thermal

bridge-free structure with span widths up to six metres. They can be fitted into continuous rooflights in a modular system combining different

sized versions, ideally matched to the required smoke exhaust surface

CO2

bar

24V 48V 230V

230V

Smoke and heat ventilation:

Ventilation:

SHEV19

Test parameters as defined by DIN EN 12101-2 and test results

Flow coefficient Cv

Effective aerodynamic opening surface Aw

Functional reliability

Snow load

Low ambient temperature

Wind load

Heat resistance

between 0.60 & 0.65

between 0.32 m² and 5.08 m²

RE 1000 + 10,000 ventilation function openings

RE 11000

SL 500

T(-5)

WL 1500

B300

How you benefit

LAMILUX CI System Smoke Lift S

• Suitable as a melt-out surface

• Good heat insulation values

• The ideal solution when the architecture requires a ridged roof

shape

• Thermal release with CO2 - cylinder is not damaged during tests

or due to false alarms

Upper edge of roofx

y

CI System Smoke SE30 with single flap

100

100*

150

150*

200

200*

250

250*

300

300*

CI System Smoke SE45 with single flap

80

80*

120

120*

160

160*

200

200*

240

240*

CI System Smoke SE-SHED60 with single flap

100

100*

150

150*

200

200*

250

250*

300

300*

100

120

100

120

100

120

100

120

100

120

100

120

100

120

100

120

100

120

100

120

100

120

100

120

100

120

100

120

100

120

0.53 m²

0.63 m²

0.82 m²

0.97 m²

1.11 m²

1.31 m²

1.40 m²

1.65 m²

1.69 m²

1.99 m²

0.53 m²

0.63 m²

0.82 m²

0.97 m²

1.11 m²

1.31 m²

1.40 m²

1.65 m²

1.69 m²

1.99 m²

0.53 m²

0.63 m²

0.82 m²

0.97 m²

1.11 m²

1.31 m²

1.40 m²

1.65 m²

1.69 m²

1.99 m²

53

53

82

82

111

111

140

140

169

169

53

53

82

82

111

111

140

140

169

169

53

53

82

82

111

111

140

140

169

169

0.32 m²

0.38 m²

0.49 m²

0.58 m²

0.64 m²

0.76 m²

0.80 m²

0.92 m²

0.95 m²

1.09 m²

0.33 m²

0.38 m²

0.51 m²

0.58 m²

0.67 m²

0.77 m²

0.80 m²

0.94 m²

0.96 m²

1.12 m²

0.32 m²

0.38 m²

0.49 m²

0.58 m²

0.64 m²

0.76 m²

0.80 m²

0.92 m²

0.95 m²

1.09 m²

Opening surface Ageo

Upper edge of roof size

Dimension X Dimension Y Effective aerodynamic opening surface

20Customized

IntelligenceDem Kunden dienen als Programm

CI System Smoke Lift SD30 with double flap system

100

100*

100

100 TS**

150

150*

150

150 TS**

200

200*

200

200 TS**

250

250*

250

250 TS**

300

300*

300 TS**

300* TS**

CI System Smoke Lift SD45 with double flap system

120

120*

120

120 TS**

160

160*

160

160 TS**

200

200*

200

200 TS**

240

240*

240 TS**

240* TS**

* In combination with glazing type PC 32-5 and PC 32-5 + GRP** Tandem-series heat exhaust unit

100

120

200

420

100

120

200

420

100

120

200

420

100

120

200

420

100

120

210

240

100

120

200

420

100

120

200

420

100

120

200

420

100

120

210

240

1.02 m²

1.20 m²

2.09 m²

4.24 m²

1.52 m²

1.79 m²

3.12 m²

6.32 m²

2.02 m²

2.38 m²

4.14 m²

8.40 m²

2.52 m²

2.97 m²

5.17 m²

10.48 m²

3.02 m²

3.56 m²

6.21 m²

7.31 m²

1.22 m²

1.43 m²

2.49 m²

5.05 m²

1.63 m²

1.92 m²

3.33 m²

6.76 m²

2.04 m²

2.40 m²

4.17 m²

8.47 m²

2.45 m²

2.89 m²

5.03 m²

5.92 m²

53

53

53

53

82

85

82

82

111

111

111

111

140

140

140

140

169

169

169

169

82

82

82

82

111

111

111

111

140

140

140

140

169

169

169

169

0.64 m²

0.75 m²

1.27 m²

2.42 m²

0.96 m²

1.11 m²

1.90 m²

3.48 m²

1.25 m²

1.48 m²

2.57 m²

4.96 m²

1.54 m²

1.84 m²

3.21 m²

6.50 m²

1.84 m²

2.21 m²

3.85 m²

4.53 m²

0.94 m²

1.09 m²

1.84 m²

3.54 m²

1.25 m²

1.46 m²

2.47 m²

4.39 m²

1.51 m²

1.68 m²

2.71 m²

5.08 m²

1.71 m²

1.90 m²

3.02 m²

3.49 m²

Opening surface Ageo

Upper edge of roof size

Dimension X Dimension Y Effective aerodynamic opening surface

SHEV21

LAMILUX CI System

Smoke Lift M

14Customized

IntelligenceDem Kunden dienen als Programm

22

LAMILUX CI System Smoke Lift MGREATER SAFETY IN PREVENTIVE FIRE PROTECTION

This smoke and heat exhaust ventilation unit is an ideal flap system for smoke and heat exhaust ventilation in LAMILUX glass roof structures.

It can be easily installed at angles between 0° to 90°.

SHEV23

Test parameters as defined by DIN EN 12101-2 and test results

Flow coefficient Cv

Effective aerodynamic opening surface Aw

Functional reliability

Snow load

Low ambient temperature

Wind load

Heat resistance

between 0.56 & 0.70

between 0.14 m² and 6.00 m²

RE 50/1000

+ 10,000 ventilation function openings

SL 500 to SL 1000

T(00) T(-05) T(-15)

WL 1500

B300

CO2

bar

24 V 48 V 230V

230V

Smoke and heat ventilation:

Ventilation:

How you benefit

LAMILUX CI System Smoke Lift M

• Flap widths and heights can be freely selected up to 2.50

m, covering a maximum flap size of 3.00 m² with real glazing,

or up to 3.50 m² with polycarbonate glazing

• Complies with European standard EN 12101-2 for smoke and

heat evacuation systems

• Selection of drive systems - pneumatic or 24 volt electric

version

• Perfectly suited for retrofitting to older roof structures as it can

be integrated into other systems

LAMILUX CI System

Air inlet devices

14Customized

IntelligenceDem Kunden dienen als Programm

24

LAMILUX CI System G-Air

LAMILUX CI System B-Air

OPTIMUM EFFICIENCY

SHEV25

Material

Extruded, thermally separated aluminium profiles

Sizes

Width: up to 1,800 mm without centre post

1,801 – 2,400 mm with centre post

Height: 300 mm and above

Louver slats

Aluminium panel (Ug = 1.0 to 1.3 W/m²K)

Insulating glass (Ug = 0.7 to 1.1 W/m²K)

Drives

Pneumatic cylinder

24 V electric motor

Material

Aluminium

Sizes

Width: 600 - 2400 mm

Length (height): 720 - 2920 mm

Louver slats

Aluminium, single- or double-skinned, thermally insulated

Polycarbonate opal or transparent

Insulation glass

Drives

Pneumatic cylinder

24 V electric motor

LAMILUX building control systemsSAFE – ENERGY-EFFICIENT – CONVENIENT

Safety, energy efficiency and comfort in a building are largely determined by building control systems. They are the key to

sustainable, value-based future construction.

LAMILUX provides project planning and equips buildings with complex building control systems featuring networked functions. As a specialist

company with many years' experience in both large and small projects, we provide intelligent controls and automation for fire safety, energy

efficiency and building comfort.

Plan - Network - Automate

From small control solutions through to complex building automation systems in large projects, LAMILUX offers all services from a single

source, including trade contracting. It reliably provides everything from planning and design concepts for electric or pneumatic control systems

and components through to their installation, initial operation and maintenance.

14Customized

IntelligenceDem Kunden dienen als Programm

26

Control with our systems

• Smoke and heat exhaust systems

• Flap systems for natural ventilation

• Solar protection and light guidance

• Sensor-activated electric lighting switches

• Temperature-sensitive switches on climate control units

and benefit from smart networking building safety, energy

efficiency and building comfort.

SHEV27

Smoke removal openings for stairwaysNON-SYSTEM CONNECTED – ELECTRIC

Many European countries have special regulations for stairways. In most cases, smoke must be removed from stairways

using electrically controlled, mains-independent systems. That is why LAMILUX supplies smoke removal openings special-

ly designed for stairways, although they may also be fitted in any type of building or structure.

Our standard set comprises:

• 1 electric motor with a 500 mm stroke, 24 V, disconnection under load

• 1 control unit for a maximum of two motors with control connectors for SHEVS

and ventilation buttons, and various peripherals such as smoke alarms,

thermal alarms or wind and rain sensors

• 2 SHEV control switches with visual display, surface mounted

• 1 flush-mounted fan button for 55 mm switch box

• Single item deliveries and upgrades are possible

14Customized

IntelligenceDem Kunden dienen als Programm

28

Renovation of SHEV systems

A SINGLE PARTNER FOR MANY THINGS INSTEAD OF MANY PARTNERS

When smoke and heat exhaust systems start to age, customer advisory services and a professional renovation are often not

only expensive, but also involve a great deal of work. Not if you work with LAMILUX, however.

Customer advisory services, tailored solutions, including control technology, and all work involved in the upgrade from a single source: On

request, LAMILUX will handle the entire renovation package for you. We start with an initial survey to establish what the existing system

contains, if the existing conditions comply with new statutory regulations and what the most cost-effective solution would be. We then draw

up a design concept, arrange demolition and waste disposal, implement safety measures to protect your employees and assets, and install

the system in close cooperation with established partners in the roof building sector. Our specialists are responsible for installing the complex

control technology.

SHEV29

SHEV systems must workFAILING TO MAINTAIN MAKES YOU LIABLE

Smoke and heat ventilation system owners are required by law to perform all necessary measures to ensure that people are

protected against danger in the event of a fire. If you do not maintain your SHEV system, you may be in breach of building

safety regulations, DIN 18232, state directives and other directly or indirectly applicable laws.

If you maintain your SHEV system on a regular basis, you will not only minimise the risk of damage and injury considerably, but also liability

risk.

Inadequate maintenance will also make you liable.

According to VdS guidelines, servicing can only be carried out by companies which can provide a promise from the SHEV system installer

to deliver original replacement parts.

Customized

IntelligenceDem Kunden dienen als Programm

You are involved in the construction of a new building or renovation of an old one and wish to make things safer with preventive fire protection

based on SHEV systems. We will gladly provide you with a consultation related to your project. We will assist you with project-specific planning

and correct SHEV system dimensioning and find tailor-made, building-specific solutions together with you.

The sheer numbers of rules, regulations and directives in preventive fire protection for buildings is daunting, especially where they relate to

smoke and heat ventilation. But what help do industrial standards, industrial guidelines or building codes offer with planning and installing

SHEV systems? What character does a statutory regulation have? What is an interpretable provision or simply a flexible guideline?

Our training programme will provide you with a way through the maze of regulations and their interpretation. This programme is aimed at our

customers and building services planners, on the one hand, and public agencies and fire services on the other.

Benefit from our practical experience

We offer guidance through the maze of regulations

PROJECT-RELATED CONSULTATION

TRAINING ON SHEVS AND PREVENTIVE FIRE PROTECTION

1430

SHEV open only SHEV open onlyVentilation function

SHEV open/closeVentilation function

SHEV open/closeFair weather ventilation

Pneumatic SHEV:

Electric SHEV:

Pneumatic SHEV:

Electric SHEV:

Pneumatic SHEV:

Electric SHEV:

Pneumatic SHEV:

Electric SHEV:

SHEV

SHEV open/close

Pneumatic SHEV:

Electric SHEV:

31

The technical data printed in this brochure was accurate when this brochure went to press and is subject to change without notice. Our technical specifications are based on calculations and supplier information or have been determined by independent testing authorities within the scope of applicable standards. Thermal transmission coefficients for our composite glazing were calculated using the finite element method with reference values as per DIN EN 673 for insulated glass. Based on empirical values and specific characteristics of the composites, a temperature vector of 15 K was defined as the vector between the outer surfaces of the material. Functional values refer to test specimens and the dimensions used in testing only. We cannot provide any further guarantees of technical values. This particularly applies to changes in installation locations or if dimensions are re-measured on site.

ROOFLIGHT DOME F100GLASS ELEMENT F

CONTINUOUS ROOFLIGHT B

LIGHT PANEL

GLASS ARCHITECTURE PR 60

AIR INLET DEVICES

CONTINUOUS ROOFLIGHT S

BUILDING UPGRADES

SMOKE AND HEAT EXHAUSTVENTILATION SYSTEMS

PHOTOVOLTAIC SYSTEMSBUILDING CONTROL SYSTEMS

FIBRE-REINFORCED COMPOSITES