sm1 module of analog inputssee also: export department: tel: +48 68 45 75 139/ 276/ 305/ 386 fax:...

2
Export department: Tel: +48 68 45 75 139/ 276/ 305/ 386 Fax: +48 68 32 54 091 e-mail: [email protected] LUMEL S.A. ul. Słubicka 1 65-127 Zielona Góra POLAND WWW.LUMEL.COM.PL SM1 module of analog inputs GALVANIC ISOLATION: INPUTS: OUTPUTS: FEATURES: Conversion of standard signals and temperature into RS485 / Modbus in 2 channels • Programmable measurement characterisc • Fixing on a TS35 rail • Mathemacal funcons realized between channels and on channels. MOD BUS RS 485 E�ample of application 8 x binary output SCADA Program LPConfig Linear charact. 0...20 mA 4...20 mA 0...10 V RS 485 Supply RS 232 RS 485 E�ternal features Overall dimensions 22.5 x 120 x 100 mm Weight < 0.3 kg with packing Protecon grade IP40 from terminal side: IP20 Digital interface Interface type Transmission protocol Modes Baud rate RS-485 Modbus RTU 8N2,8E1,8O1,8N1 2400; 4800; 9600; 19.2 k; 38.4 k; 57.6 k; 115 k bit/s Modbus ASCII 8N1, 7E1, 7O1 Inputs Input type Range Error Temperature -200...850 o C 0.2% Current 0/4...20 mA 0.2% Voltage 0...10 V 0.2% Resistance 0...400 Ω 0.2% Outputs Output type Properes Remarks Digital interface RS-485 Modbus ASCII/RTU HMI

Upload: others

Post on 15-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SM1 module of analog inputsSee AlSo: Export department: Tel: +48 68 45 75 139/ 276/ 305/ 386 Fax: +48 68 32 54 091 e-mail: export@lumel.com.pl LUMEL S.A. ul. Słubicka 1 65-127 Zielona

Export department:Tel: +48 68 45 75 139/ 276/ 305/ 386Fax: +48 68 32 54 091e-mail: [email protected]

LUMEL S.A.ul. Słubicka 165-127 Zielona GóraPOLANDWWW.LUMEL.COM.PL

SM1 module of analog inputs

GAlVANIC ISolATIoN:

INPUTS:

oUTPUTS:

FeATUReS:• Conversion of standard signals and temperature into RS485 / Modbus

in 2 channels

• Programmable measurement characteristi c

• Fixing on a TS35 rail

• Mathemati cal functi ons realized between channels and on channels.

MODBUS

RS485

E�ample of application

8 x binary output

SCADA

ProgramLPConfig

Linear charact.

0...20mA

4...20mA

0...10 V

RS485Supply

RS232

RS485

E�ternal features Overall dimensions 22.5 x 120 x 100 mmWeight < 0.3 kg with packingProtecti on grade IP40 from terminal side: IP20

Digital interfaceInterface type Transmission protocol Modes Baud rate

RS-485Modbus RTU 8N2,8E1,8O1,8N1 2400; 4800; 9600; 19.2 k;

38.4 k; 57.6 k; 115 k bit/sModbus ASCII 8N1, 7E1, 7O1

InputsInput type Range ErrorTemperature -200...850 o C 0.2%Current 0/4...20 mA 0.2%Voltage 0...10 V 0.2%Resistance 0...400 Ω 0.2%

OutputsOutput type Properti es Remarks

Digital interface RS-485 Modbus ASCII/RTU

HMI

Page 2: SM1 module of analog inputsSee AlSo: Export department: Tel: +48 68 45 75 139/ 276/ 305/ 386 Fax: +48 68 32 54 091 e-mail: export@lumel.com.pl LUMEL S.A. ul. Słubicka 1 65-127 Zielona

See AlSo:

Export department:Tel: +48 68 45 75 139/ 276/ 305/ 386Fax: +48 68 32 54 091e-mail: [email protected]

LUMEL S.A.ul. Słubicka 165-127 Zielona GóraPOLANDWWW.LUMEL.COM.PL

Connection diagrams

SM1 module of analog inputs

For more information about LUMEL's

products please visit our website:

www.lumel.com.pl

OUR OFFER

www.lumel.com.pl

SM1-19A

MT058 panel

Programmable controller SMC

Free LPConfig software

* after agreeing with the manufacturer

Supply

Input signals

SM1module

Converter RS-232/RS-485

PC computer

PC computer with a RS-485 card

RS-232 socketSM1 module

PC computer

Connection way of input signals

Input 1 Input 2 Input 1 Input 2Input 1 Input 2 Input 1 Input 2

Conn

ectio

n w

ay

Measured signal

2 voltage inputs 2 current inputs 1 voltage input, 1 current input

2 Pt100 inputs or measurement of resistance up to 400 Ω

Connection way of external signals

Connection way of the RS-485 interface

Connection way of the RS-232 interface

OrderingModule of analog inputs - SM1 XX X XInput signal :

2 voltage inputs 0...10 V 00

2 current inputs 0/4...20 mA 01

1 voltage input + 1 current input 0...10 V+0/4...20 mA 02

2 resistance inputs or Pt100 Pt100 or resistance < 400 Ω 03

Supply:85...253 V a.c./d.c. 120...50 V a.c./d.c. 2

Acceptance tests:without additional quality inspection requirements 8with an extra quality inspection certificate 7

acc. to customer’s requests * X

Ordering example:

The code SM1 - 01 1 8 means:SM1 - module of SM1 type 01 - 2 current inputs: 0/4...20 mA 1 - supply: 85...253 V a.c./d.c. 8 - without additional quality inspection requirements

Rated operating conditions

Supply voltage 85...253 V a.c./d.c. (40...400 Hz) or d.c.20...50 V a.c./d.c. (40...400 Hz) or d.c.

Input power: ≤ 4 VA

Temperature ambient: -10...23...55°CRelative humidity < 95%Operating position on a TS35 railExternal magnetic field < 400 A/m

Safety and compability requirementsElectromagnetic compatibility

Noise immunity acc. to EN 61000-6-2 Noise emissions acc. to EN 61000-6-4

Isolation between circuits acc. to EN 61010-1Pollution level 2Installation category III

Maximum phase-to-earth operating voltage Supply: 300 V, input 50 V,Output: 50 V

Altitude a.s.l. 2000 m

Connection way of external signals