Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more than 100 years experience in providing HVAC systems and equipment around the world. Sanyo is a leading manufacturer in the field of high- efficiency absorption chillers. Carrier-Sanyo absorption chillers, produced by Sanyo for Carrier, provide a unique choice of models for all absorption chiller applications. Features The Carrier-Sanyo 16TJ single-effect absorption chillers are designed for cooling applications where low-pressure steam is available as waste heat. They can tie into district steam systems. Carrier-Sanyo absorption chillers allow diversification of critical cooling requirements. Critical cooling loads are met with minimal electrical power input. 16TJ 11-53 Nominal cooling capacity 352-2461 kW SUPER ABSORPTION GB/T-19001-2000 to ISO9001/2000 They allow smaller emergency generators compared to an electrical driven chiller. The units are ozone-safe and CFC-free. Cooling require- ments are met without chlorine-based refrigerants. They reduce the contribution to global warming and minimize the global impact by greatly reducing electricity consumption and production of greenhouse gases. The solution inhibitor has no impact on the environment. An absorption chiller does not utilize a large motor- compressor, and this leads to quiet, vibration-free operation. The use of high-efficiency heat transfer surfaces has reduced the space required for installation of the absorption chiller, resulting in a smaller footprint. Carrier-Sanyo is the industry leader in compact absorption units.

Upload: builiem

Post on 04-Aug-2018

267 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

Single-Effect Steam-Fired Absorption Chillers

The Carrier Corporation has more than 100 years experiencein providing HVAC systems and equipment around the world.Sanyo is a leading manufacturer in the field of high-efficiency absorption chillers. Carrier-Sanyo absorptionchillers, produced by Sanyo for Carrier, provide a uniquechoice of models for all absorption chiller applications.

Features■ The Carrier-Sanyo 16TJ single-effect absorption chillers are

designed for cooling applications where low-pressure steamis available as waste heat.

■ They can tie into district steam systems.■ Carrier-Sanyo absorption chillers allow diversification of

critical cooling requirements. Critical cooling loads are metwith minimal electrical power input.

16TJ 11-53Nominal cooling capacity 352-2461 kW

SUPER ABSORPTION

GB/T-19001-2000 to ISO9001/2000

■ They allow smaller emergency generators compared to anelectrical driven chiller.

■ The units are ozone-safe and CFC-free. Cooling require-ments are met without chlorine-based refrigerants.

■ They reduce the contribution to global warming andminimize the global impact by greatly reducing electricityconsumption and production of greenhouse gases.

■ The solution inhibitor has no impact on the environment.■ An absorption chiller does not utilize a large motor-

compressor, and this leads to quiet, vibration-free operation.■ The use of high-efficiency heat transfer surfaces has reduced

the space required for installation of the absorption chiller,resulting in a smaller footprint.

Carrier-Sanyo is the industry leader in compact absorptionunits.

Page 2: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

Component identification

Nomenclature

16TJ - 11

Unit type: Single-effect, steam-fired absorption chillers

Capacity code

Legend1. Condenser2. Steam inlet3. Generator4. Chilled-water outlet5. Control panel6. Evaporator7. Chilled-water inlet8. Cooling water inlet9. Heat exchanger10. Heat reclaimer11. Absorber

Page 3: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

Figure 1 - Simplified absorption cycle

The absorption cycleThe absorption cooling cycle, like the mechanical vapourcompression refrigeration cycle, utilizes the latent heat ofevaporation of a refrigerant to remove heat from the enteringchilled water. Vapour compression refrigeration systems use achlorine-based refrigerant and a compressor to transport therefrigerant vapour to be condensed in the condenser. Theabsorption cycle, however, uses water as the refrigerant andan absorbent lithium bromide solution to absorb thevaporized refrigerant. Heat is then applied to the solution torelease the refrigerant vapour from the absorbent. Therefrigerant vapour is then condensed in the condenser.The basic single-effect absorption cycle (see Figure 1)

includes generator, condenser, evaporator and absorber withrefrigerant (liquid) and lithium bromide as the workingsolutions. The generator utilizes a heat source (burner, steamor hot water) to vaporize the diluted lithium bromide solution.The water vapour that is released travels to the condenserwhere it is condensed back into a liquid, transferring the heatto the cooling tower water. Once condensed, the liquidrefrigerant is distributed over the evaporator tubes, removingthe heat from the chilled water and vaporizing the liquidrefrigerant. The concentrated lithium bromide solution fromthe generator passes into the absorber, absorbs the refrigerantvapour solution from the evaporator and dilutes itself. Thediluted lithium bromide solution is then pumped back to thegenerator where the cycle is started again.

Cooling cycle schematic

Heat sink 1.7 Heat 1.0

12 13 14 15 16 17 18

0 10 20 30 40 50 60 70 80 90 100

0

10

20

30

40

50

60

5

8 10

20

30

40 50

80

100

0%

40%

50%

55%

70%

45%

60%

65%

A B

C D

Tem

per

atur

e of

ref

riger

ant

(°C

)

Legend1. Generator2. Cooling water3. Condenser4. Hot water5. Evaporator6. Chilled water7. Absorber8. Refrigerant pump9. Absorbent pump

10. Heat exchanger11. Cooling water12. Concentrated solution13. Diluted solution14. Liquid solution15. Refrigerant vapour16. Cooling water17. Chilled water18. Hot water

Pre

ssur

e (k

Pa)

Temperature of absorbent (°C)

Legend1. Refrigerant vapour2. Condenser3. Generator4. Cooling water5. Liquid refrigerant6. Concentrated solution7. Heat source8. Cooling water9. Chilled water10. Evaporator11. Absorber12. Absorbent pump

Page 4: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

Chiller featuresExpert self-diagnosis function ■ The expert function is provided to monitor operating

conditions, predict chiller information and maintain stableoperation.

Predictive maintenance information

Graph 1 - Fouling of heat transfer tubes in coolingwater system

Graph 2 - Trend of absorbent concentration

Graph 3 - Vacuum condition monitoring

Legend1. Storage tank2. Diluted solution3. Purge nozzle4. Pd cell5. Pressure sensor

Carrier-Sanyo control system■ The Carrier-Sanyo control system surpasses other

proportional only control systems available today. The digitalPID (proportional plus integral plus derivative) controlmaximizes unit performance by maintaining a ±0.5 Kvariance in leaving chilled-water temperature from thesetpoint. Proportional controls can typically only maintain a±1 K variance from the setpoint. The controller’s innovativedesign also incorporates the ability to start and stop thesystem chilled/hot and cooling water pumps. Duringshutdown these pumps are sequenced to ensure a completedilution cycle.

■ The leaving chilled-water temperature is measured every fiveseconds and steam input is changed according to the gradientof the leaving chilled-water temperature curve. Systemtemperatures, setpoints, and operational records are displayedalong with indicator lights for the chiller and pumps.

■ The Carrier-Sanyo control system offers its users self-diagnostics by constantly monitoring the chiller status andwill automatically shut the chiller down should a fault occur.The cause of shutdown will be retained in the memory andcan be displayed for immediate operator review. Thecontroller’s memory will also retain and display the cause ofthe last three system fault conditions. This method ofretaining fault conditions is extremely useful for maintainingan accurate record of unit performance and fault history.

Display and control board

Figure 2 - Indication lights

Con

cent

rate

d in

dic

ator

Cooling load factor (%)

Maintenance zone at cooling water 31°C

Maintenance zone at cooling water 27°C

Abnormal stop zone

Normal lineat cooling water 31°C

Normal lineat cooling water 27°C

Storage ratio (%)

Normal zone

Noticezone

Maintenance zone

2

3

4

1

5

Foul

ing

fact

or

Cooling load factor (%)

Normal line

Normal line

Notice line

Maintenance lineMaintenance zone

Pre

ssur

e in

crea

se in

dic

ator

at s

tora

ge t

ank

LegendName LED colour

1. Operation indication light Green2. Stop indication light Orange3. Alarm indication light Red4. Remote/local select button with LED Green5. Operation select button with LED Green6. Data display 7 segment LED (red)7. Stand-by indication light Green8. Dilution indication light Green9. Safety circuit indication light Green10. Power indication light OrangeGL*. Purge indication light Green43P*. Purge pump on-off switch43ES*. Emergency stop switch

* On the control panel door, see p.16

CHILLER HEATER

#ABS PUMP

#2ABS PUMP

REF PUMP

PURGE PUMP

STAND BY

DILUTION

SAFETY CIRCUIT

CHILLER ALARM OPERATION

POWER

SET BACK

STOP RUN

REMOTE

LOCALBUZZER STOP

RUNSTOP

Page 5: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

Fast digital PID control■ The introduction of new digital PID control to the J-model

stabilizes the chilled/hot-water temperature with higheraccuracy than the previous E-model. It quickly responds tothe load fluctuation and supplies stable chilled/hot-watertemperature. It is suitable for air-conditioning intelligentbuildings which require sophisticated control.

Saving energy with the inverter (option)■ Balancing the load and flow rate with the absorbent pump’s

inverter control enables efficient and energy-saving operation.As a result, it reduces input energy and electric powerconsumption. Running cost is decreased by 5% compared tonon-inverter control.

Graph 4 - Running cost curve

Notes:1. Chilled-water leaving temperature 7°C constant2. Cooling water entering temperature:

Purge system■ The high-performance purge system maintains the required

operating pressure, preserves chiller performancecharacteristics, minimizes chiller maintenance to one purgeoperation per season (for year-round operation).

Steam valve opening control■ At the start-up the opening angle of the steam control valve is

controlled in three stages, reducing the amount of steam andthe time needed to reach the desired level, compared with theprevious model.

■ Adjusting the opening speed of the steam control valve at thesecond and third stage, it is possible to set up the mostsuitable conditions for the site auxiliary equipment.

Load factor (%) Temperature (°C)

100 32

50 27

30 25

Graph 5 - Steam valve opening control

Expansion of safe operating zone■ This ensures quick response to rapid changes and maintains

stable operation.■ The safe operating zone is between 19°C and 34°C cooling

water temperature (for a nominal cooling water enteringtemperature of 32°C)

Graph 6 - Safe operating zone chart

Crystallization protection■ A microprocessor monitors the absorbent concentration.

Steam supply is stopped, and the unit is returned to normaloperation, when the concentration is over a certain limit, toprevent the crystallization of absorbent.

Ene

rgy

cons

ump

tion

ratio

(%)

Cooling load factor (%)

Invertercontrol

Non-invertercontrol

Max

imum

inp

ut (%

)

Variable (5-30 minutes)

Tem

per

atur

e (°

C)

Ste

am c

onsu

mp

tion

(%)

Ste

am c

ontr

ol o

pen

ing

ratio

(%)

Steam consumption

Cooling water entering temp.

Chilled-water entering temp.

Time (minutes)

Setting

7°C

Example15 minutes30 minutes

Chilled-water leaving temp.

Hot water control valveopening ratio

Cooling water entering temperature (°C)H = 32°C (variable from 20°C to 33°C)

Page 6: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

Technical dataSingle effect steam-fired absorption chillers

Legend

* In accordance with ARI 560 - 200012.2 —> 6.7°C (Fouling factor = 0.0176 m2 K/kW)29.4 —>38.4°C (Fouling factor = 0.044 m2 K/kW)95.0 —>86.0°C (Fouling factor = 0.0176 m2 K/kW)

Note: For selection outside ARI operating conditions please contact Carrier.

16TJ 11 12 13 14 21 22 23 24 31 32 41 42 51 52 53Cooling capacity kW 352 422 527 633 738 844 985 1125 1266 1407 1582 1758 1969 2215 2461Chilled-water system*Flow rate l/s 151 182 227 273 317 364 425 483 544 606 681 758 847 953 1061Pressure drop kPa 49 51 63 67 59 63 40 44 47 51 41 44 38 51 67Connection (ANSI) inch 4 4 4 4 5 5 6 6 6 6 8 8 8 8 8Retention volume m3 0.12 0.13 0.15 0.17 0.22 0.24 0.28 0.30 0.34 0.36 0.46 0.48 0.65 0.71 0.77Cooling water system**Flow rate l/s 81.8 98.1 123 147 172 196 229 262 817 908 1022 1136 1272 1431 1589Pressure drop kPa 33 36 31 36 31 34 64 69 54 56 59 63 41 54 70Connection (ANSI) inch 5 5 5 5 6 6 8 8 8 8 10 10 12 12 12Retention volume m3 0.35 0.38 0.43 0.48 0.60 0.65 0.73 0.79 0.99 1.06 1.25 1.35 2.03 2.18 2.32Steam system Saturated steam 100 kPaConsumption kg/h 780 940 1170 1410 1640 1880 2190 2500 2810 3120 3510 3900 4370 4920 5460Steam inlet inch 5 5 5 5 6 6 8 8 8 8 8 8 10 10 10Drain outlet inch 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 2 2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2Control valve inch 2 2 2-1/2 2-1/2 2-1/2 3 3 4 4 4 4 4 4 5 5Shutoff valve inch 2 2 2-1/2 2-1/2 2-1/2 3 3 4 4 4 4 4 4 5 5Length (L) mm 2680 2681 3690 3690 3770 3770 4850 4850 4910 4910 4960 4960 5050 5590 6090Width (W) mm 1295 1295 1295 1295 1455 1455 1455 1455 1515 1515 1615 1615 1950 1950 1950Height (H) mm 2215 2215 2215 2215 2350 2350 2350 2350 2620 2620 2870 2870 3200 3200 3200Tube removal space mm 2400 2401 3400 3400 3400 3400 4500 4500 4500 4500 4500 4500 4600 5200 5700Operating weight kg 3800 4000 4900 5100 6200 6500 7600 8000 9800 10200 11800 12300 16900 18300 19600Max. shipping weight kg 3300 3500 4300 4500 5400 5600 6600 6900 8500 8800 10100 10400 14200 15400 16500Shipping method One-piecePower supply 400 V-3 ph-50 HzApparent power kVA 4.3 4.3 4.3 4.3 6.0 6.0 6.1 6.1 7.6 7.6 7.6 7.6 7.6 7.6 7.6Total electric current A 6.5 6.5 6.5 6.5 9.0 9.0 9.1 9.1 11.3 11.3 11.3 11.3 11.3 11.3 11.3No.1 absorbent pump kW 1.1 1.1 1.1 1.1 2.2 2.2 2.2 2.2 3.0 3.0 3.0 3.0 3.0 3.0 3.0

A 3.3 3.3 3.3 3.3 5.8 5.8 5.8 5.8 8.0 8.0 8.0 8.0 8.0 8.0 8.0Refrigerant pump kW 0.2 0.2 0.2 0.2 0.2 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3

A 1.25 1.25 1.25 1.25 1.25 1.25 1.35 1.35 1.35 1.35 1.35 1.35 1.35 1.35 1.35Purge pump kW 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4

A 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1Pd cell heater W 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38Control circuit W 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300

Page 7: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

Scope of supply1. Standards met

The units comply with the following standards:• ARI 560-2000• 89/392/EEC (machine directive)• 73/23/EEC (low-voltage directive)• 89/336/EEC (electromagnetic compatibility directive)• 97/23/EC (pressure equipment directive)

2. Absorption chiller, comprising:1. Lower shell

• Evaporator and refrigerant dispersion tray• Absorber and absorbent dispersion tray• Eliminators• Bases

2. Upper shell• Generator• Condenser• Low temperature (LT) generator• Eliminators• Rupture disk mounting flange

3. Heat exchangers

4. Pumps• Absorbent pump with isolating valves• Refrigerant pump with isolating valves• Purge pump

5. Purge unit• Purge tank• Ejector and liquid trap• Piping and various manual valves• Palladium cell with heater

6. Control panel• Controller with data displayLEDs and operation buttons• Inverter for absorbent pump (option)• Circuit breaker• Transformer• Relays and terminal blocks• Purge pump operation switch

7. Locally mounted parts• Temperature sensors• Chilled-water flow switch• Generator pressure switch

8. Interconnecting piping and wiring• Refrigerant and absorbent piping• Internal power and control wiring

9. Initial charge• Absorbent (lithium bromide)• Refrigerant (water)• Inhibitor (lithium molybdate)

10. Painting• Main unit: Rust-preventive paint• Control panel: Finish paint

11. Accessories• Operation manual: One set• Washer (for fixing foundation bolts): One set• Gasket and sealant for rupture disk: One set

3. Factory test1. Check of external dimensions2. Hydraulic pressure test of water headers

Test pressure is 1.5 times of maximum working pressure3. Vacuum-side leak test4. Electric insulation resistance test5. Dielectric breakdown test6. Function test of electric circuit and safety devices

4. Scope of supply of the purchaser1. Building and foundations2. External chilled water, cooling water and steam piping

work including various safety valves, isolation valves,mating flanges, gaskets, bolts and nuts, etc.

3. External wiring and piping for the chillers includingnecessary parts

4. Insulation for the chillers including necessary parts.5. Finish painting of the chillers (if needed)6. Cooling water entering temperature control device7. Cooling water treatment device8. Various temperature/pressure gauges for steam and water

lines.9. Cooling tower(s), chilled-water pump(s) and steam

control valve and steam shut-off valve10. Electric power supply (as specified)11. Supply of chilled water, cooling water, steam and air* at

rated conditions12. Maintenance of the chiller13. Necessary tools, labour and materials for installation and

site test operation14. Any other item not specifically mentioned in the scope of

supply

* If pneumatic hot-water valve control is used

Page 8: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

Scope of orderItem Standard OptionChilled water

Temperature Entering: 12.2°C, leaving: 5°C through 12°C

Leaving: 6.7°C, temperature difference 3 K through 10 K

Flow rate 0.043 l/s x kW. Changes depending on chilled water temperature

difference (min 50%)

Max.working pressure 1034 kPa . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1540 kPa, 2068 kPa

Hydraulic test pressure Max. working pressure x 1.5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Max. working pressure x 1.5

Fouling factor 0.018 m2 K/kW. Max. 0.18 m2 K/kW

Tube material Copper tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Cu Ni tube

Water quality Refer to JRA-GL02E-1994 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Structure of water header Hinged type and epoxy treated . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Manufacturing standard of water header Flanged ANSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Cooling waterTemperature Entering: 29.4°C

Leaving: 38.4°C, entering: 20°C through 33°C

Flow rate 0.065 l/s•kW. Within the water fl ow rare range of each model

Max. working pressure 784 kPa. Max. 1960 kPa . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1540 kPa, 2068 kPa

Hydraulic test pressure Max. working pressure x 1.5

Fouling factor 0.044 m2 K/kW. Max. 0.18 m2 K/kW

Tube material Copper tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Cu Ni tube

Water quality Refer to JRA-GL02E-1994 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Structure of water header Hinged type and epoxy treated . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Manufacturing standard of water header Flanged ANSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

SteamSupply pressure 100 kPa, 50 kPa through 100 kPa, max. 5 K superheat

Specific steam consumption 2.22 kg/h/kW. Changes depend on the specifications.

Max. working pressure 146 kPa . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Hydraulic test pressure Max. working pressure x 1.5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Tube material 9/1 Copper nickel tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Steam quality Refer to JIS-B-8223 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Manufacturing standard of water header Flanged ANSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

ElectricityPower supply 400 V - 3 phase - 50 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Contact the Carrier-Sanyo representative

(Voltage control within ±10%, frequency control within ±5%)

Shipment One section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Multi shipment

ControlSafety functions Refrigerant temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Cooling water flow switch

Chilled-water freeze protection

Chilled-water flow switch

Cooling water temperature

HT generator temperature

HT generator pressure

HT generator solution level

Exhaust gas temperature

Crystallization protection

Motor protection

Capacity control Digital PID control by chilled-water temperature . . . . . . . . . . . . . . . .Inverter control of #1 absorbent pump

Parts Selected by Carrier-Sanyo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Control panelPainting Munsell 5Y-7/1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Indication lights Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Stop

Alarm

Display LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

External terminals Operation indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

(Volt-free normally open contact) Stop indication

Alarm indication

Answer back indication

Cooling mode indication

Structure Indoor type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Parts Selected by Carrier-Sanyo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Electrical wiring and pipingWire: 600 V polyvinyl grade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

chloride-insulated wires

Pipe: Plicatube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

(flexible metal conduits)

Insulation conditionPlace Indoor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Ambient temperature 5°C through 40°C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .No option

Ambient humidity Relative humidity: max 90% at 45°C . . . . . . . . . . . . . . . . . . . . . . . . .No option

Atomosphere Be sure the following are not present . . . . . . . . . . . . . . . . . . . . . . . . .No option

- Corrosive gas

- Explosive gas

- Poisonous gas

Page 9: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

NOTE: The drawings shown on the following pages are for the standard number of passes. For applications outside the nominalconditions of this catalogue, computer selection software can automatically select the most appropriate number of passes.

Pass Arrangement

16TJ Evaporator Absorber Condenser

Minimum Standard Maximum Minimum Standard Maximum Minimum Standard Maximum

11 2 4 6 2 3 4 1 2 2

12 2 4 6 2 3 4 1 2 2

13 2 3 4 2 2 3 1 1 2

14 2 3 4 2 2 3 1 1 2

21 2 3 4 2 2 3 1 1 2

22 2 3 4 2 2 3 1 1 2

23 2 2 4 2 2 3 1 1 2

24 2 2 4 2 2 3 1 1 2

31 2 2 4 2 2 3 1 1 2

32 2 2 4 2 2 3 1 1 2

41 2 2 4 2 2 3 1 1 2

42 2 2 4 2 2 3 1 1 2

51 2 2 4 2 2 3 1 1 2

52 2 2 4 2 2 3 1 1 2

53 2 2 4 2 2 3 1 1 2

Page 10: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

NOTES1. Dimensions (L), (W), (H) are for a standard machine.

The dimensions are changed by parts added. 2. indicates the position of anchor bolts.3. Clearance space must be available at the front and rear of the

chiller.4. All external water piping must be provided with welded ANSI

150 LB flanges by the customer.5. indicates the position of the power supply connection on the

control panel (diameter 35 mm)6. Installation clearance:

Ends 1000 mmTop 200 mmOthers 500 mm

Dimensional drawings, mm16TJ 11 through 16TJ 12

170

22

26

R60

0

20

81

18

96

63

5

23

01

29

0

780

2400

145

800

00

2680(L)

20

01

80

23

10

20

76

2085

785

0

0

19002193

22

15

(H)

2125

300

1295(W)

91

08

82

19

0

25

0

1995

1263

923

595

1410

0

0

0

33

0

18

5

170

63

5

R60

0

31

46

780

29

16

145

800

29

87

0

0

0

30

96

18

0

3690(L)

2085

785

32

71

31

16

20

0 0

0

19002193

22

15

(H)

300

91

08

82

25

0

1410

19

0

2125

1995

1263

923

595

1295(W)

0

0

0

16TJ 13 through 16TJ 14

NOTE: Dimensions are for guidance only.Always refer to the certified drawings supplied upon request when designing aninstallation.

Steam inlet(5 inch)Cooling wateroutlet (5 inch)

Chilled wateroutlet (4 inch)

Chilled water inlet(4 inch)

Cooling waterinlet (5 inch)

Rupture disk(2 inch)

Drain outlet(1-1/2 inch)

Steam inlet Drain outletCooling wateroutlet

Cooling water inletChilled water in/out

Wire connectionØ35 hole

Tube removal

Steam inlet(5 inch)Cooling wateroutlet (5 inch)

Chilled wateroutlet (4 inch)

Chilled waterinlet (4 inch)Cooling waterinlet (5 inch)

Rupture disk(2 inch)

Drain outlet(1-1/2 inch)

Steam inlet Drain outlet Chilled water inletCooling water outlet

Cooling water inletChilled water outlet

Wire connectionØ35 hole

Tube removal

Page 11: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

NOTES1. Dimensions (L), (W), (H) are for a standard machine.

The dimensions are changed by parts added. 2. indicates the position of anchor bolts.3. Clearance space must be available at the front and rear of the

chiller.4. All external water piping must be provided with welded ANSI

150 LB flanges by the customer.5. indicates the position of the power supply connection on the

control panel (diameter 35 mm)6. Installation clearance:

Ends 1000 mmTop 200 mmOthers 500 mm

2350(H)

41

89

38

86

33

12

11

60

35

5

21

0

0

270

R60

0

220

9261000

125

04

35

4

41

04

2255

835

22

0

4850(L)

0

25

0

0

1900

2328

300

2295

10

90

28

5

1510

1455(W)

2135

1333

1019

605

25

0

10

65

0

0

0

16TJ 23 through 16TJ 24

16TJ 21 through 16TJ 22

2350(H)

31

41

29

62

28

66

71

0

35

5

21

0

0

270

R60

0

22

9261000

125 00

22

0

3770(L)

2255

835

0

30

84

31

03

23

7 0

1900

2328

300

1510

1455(W)

28

5

10

90

25

0

2295

2135

1346

1006

605

0

10

65 0

0

NOTE: Dimensions are for guidance only.Always refer to the certified drawings supplied upon request when designing aninstallation.

Steam inlet(6 inch)Cooling wateroutlet (6 inch)

Chilled wateroutlet (5 inch)

Chilled waterinlet (5 inch)

Cooling waterinlet (6 inch)

Rupture disk(2 inch)

Drain outlet(1-1/2 inch)

Steam inlet Drain outlet Chilled water inletCooling water outlet

Cooling water inletChilled water outlet

Wire connectionØ35 hole

Tube removal

Steam inlet(6 inch)Cooling wateroutlet (6 inch)

Chilled wateroutlet (5 inch)

Chilled waterinlet (5 inch)Cooling waterinlet (6 inch)

Rupture disk(4 inch)

Drain outlet(1-1/2 inch)

Steam inlet Drain outlet Cooling water outletCooling water inletChilled water in/out

Wire connection Ø35 hole

Tube removal

Page 12: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

16TJ 31 through 16TJ 32

2620(H)

41

64

38

36

26

0

11

35

45

8

33

15

280

1022

R600

65

105

1100

0

0

0

41

05

27

0

43

54

4910(L)

2500

815

0

27

5

0

1900

2595

300

2544

33

5

1660

1515(W)

2365

1476

1066

611

11

56

26

0

11

70

0 0

0

NOTE: Dimensions are for guidance only.Always refer to the certified drawings supplied upon request when designing aninstallation.

38

36

46

84

68

26

0

41

64

33

15

11

35

0

275

R60

0

120

1150

0

1036

500

43

29

41

05

30

12

69

4960(L)

2750

840

0

0

1900

2870(H)

2844

1810

300

2805

1615(W)

35

0

12

21

27

5

2595

1613

1142

577

12

55

0 0

0

16TJ 41 through 16TJ 42

Steam inlet(8 inch)Cooling wateroutlet (8 inch)

Chilled wateroutlet (6 inch)Chilled waterinlet (6 inch)Cooling waterinlet (8 inch)

Rupture disk(3 inch)

Drain outlet(2 inch)

Steam inlet Drain outlet

Cooling wateroutlet

Chilled waterin/out

Cooling water inlet

Wire connectionØ35 hole

Tube removal

Steam inlet(10 inch)Cooling wateroutlet (10 inch)

Chilled wateroutlet (8 inch)

Chilled waterinlet (8 inch)

Cooling waterinlet (10 inch)

Rupture disk(3 inch)

Drain outlet(2-1/2 inch)

Steam inlet Drain outlet Cooling water outletCooling water inletChilled water in/out

Wire connectionØ35 hole

Tube removal

NOTES1. Dimensions (L), (W), (H) are for a standard machine.

The dimensions are changed by parts added. 2. indicates the position of anchor bolts.3. Clearance space must be available at the front and rear of the

chiller.4. All external water piping must be provided with welded ANSI

150 LB flanges by the customer.5. indicates the position of the power supply connection on the

control panel (diameter 35 mm)6. Installation clearance:

Ends 1000 mmTop 200 mmOthers 500 mm

Page 13: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

13

16TJ 51 through 16TJ 53

AB C

450

52

3

R60

0

1410

13

0

32

5

10

20

173

32

72

1600

20

0

00

3099

L

FE

900

37

0

0

0

1900

3200(H)

1950(W)

3139

300

25

0

43

5

2010

17

01

2925

1760

1170

651

0 0

0

3158

D

NOTE: Dimensions are for guidance only.Always refer to the certified drawings supplied upon request when designing aninstallation.

Steam inlet(10 inch)Cooling wateroutlet (12 inch)

Chilled wateroutlet (9 inch)

Chilled water inlet(9 inch)Cooling waterinlet (12 inch)

Rupture disk(3 inch)

Drain outlet(2-1/2 inch)

Steam inlet Drain outlet Cooling water outletChilled water in/outCooling water inlet

Wire connectionØ35 hole

Tube removal

16TJ A B C D E F L51 3706 3836 4136 4600 4078 4336 505052 4248 4378 4678 5250 4623 4878 559053 4746 4876 5176 5700 5121 5378 6090

NOTES1. Dimensions (L), (W), (H) are for a standard machine.

The dimensions are changed by parts added. 2. indicates the position of anchor bolts.3. Clearance space must be available at the front and rear of the

chiller.4. All external water piping must be provided with welded ANSI

150 LB flanges by the customer.5. indicates the position of the power supply connection on the

control panel (diameter 35 mm)6. Installation clearance:

Ends 1000 mmTop 200 mmOthers 500 mm

Page 14: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

14

Foundation dimensions, mm

NOTES:1. The machine base has ø50-mm hole for the anchor bolt.2. The anchor bolt should be fixed as shown in the detail

drawing.Washer should be welded to the base (see Fig. 4)3. There should be a drain channel around the foundation.

4. The floor surface should be made waterproof to facilitatemaintenance work.

5. The surface of the foundation should be made flat.6. Anchor bolts and nuts are to be supplied by customer.

15

0A BB

D

C

EF

G

J

K

AABB

150A

GEF

C

AA

BBK

D

Figure 3 - 16TJ-11 through 16TJ-42 Figure 5 - 16TJ-51 through 16TJ-53

Figure 4 - Details of weld

Table 1 - Dimensional data

Nut

WeldWasher

Base

A = 150 mm and more

16TJ Weight, kg Dimensions, mmAA + BB AA BB A B C D E F G J K

11 3800 1900 1900 1890 -- 175 360 800 150 1100 160 900

12 4000 2000 2000 1890 -- 175 360 800 150 1100 160 900

13 4900 2450 2450 2916 -- 175 360 800 150 1100 160 900

14 5100 2550 2550 2916 -- 175 360 800 150 1100 160 900

21 6200 3100 3100 2866 -- 200 400 1000 150 1300 200 1100

22 6500 3250 3250 2866 -- 200 400 1000 150 1300 200 1100

23 7600 3800 3800 3886 -- 200 400 1000 150 1300 200 1100

24 8000 4000 4000 3886 -- 200 400 1000 150 1300 200 1100

31 9800 4900 4900 3836 -- 225 450 1100 150 1400 250 1200

32 10200 5100 5100 3836 -- 225 450 1100 150 1400 250 1200

41 11800 5900 5900 3836 -- 225 450 1150 150 1450 250 1250

42 12300 6150 6150 3836 -- 225 450 1150 150 1450 250 1250

51 16900 8450 8450 3706 130 190 510 1600 180 1960 250 1700

52 18300 9150 9150 4248 130 190 510 1600 180 1960 250 1700

53 19600 9800 9800 4746 130 190 510 1600 180 1960 250 1700

Page 15: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

15

Control panel dimensions, mm

Start/stop sequence of auxiliary equipment

A

GL43P

43ES

A

16

00

30

0

12

0

70

80

16TJ-11 through16TJ-53

Power supplyØA ( ØB)

Remote controlØ22

Start

Stop

Start signal

Stop signal

Chilled water pump operates

Cooling water pumpoperates and thencooling tower fan

operates

Cooling water pumpstops and cooling tower

fan stopsChilled-water pump stops Chiller stops completely

Stop air conditioners

Machine operates

Diluted operation starts

Operate air conditioners

Page 16: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

Field wiringFigure 6 - Typical electrical field connection diagram - hot water-fired absorption chillers (LJ)

Chiller co

ntrol p

anel

TE

RM

INA

LS

TR

IPS

ON

TH

EC

ON

TR

OL

PAN

EL

PRE-ALARM SIGNAL

REMOTE CHECK SIGNAL

FOR OPERATION INDICATION

FOR STOP INDICATION

FOR ALARM INDICATION

RUN/STOP SIGNALFOR CHILLED WATER PUMP

RUN/STOP SIGNALFOR COOLING WATER PUMP

RUN/STOP SIGNALFOR COOLING TOWER FAN

FEEDBACK SIGNAL

FOR DILUTION INDICATION

RUN/STOP SIGNALFOR VENTILATION FAN

FOR COOLING INDICATION

FOR HEATING INDICATION

FOR ALARM BUZZER

CHILLED/HOT-WATER PUMP INTERLOCK

COOLING WATER PUMP INTERLOCK

RE

MO

TE

SIG

NA

LC

hiller can be op

erated b

y the following five signal typ

es.(1)

Volt-free normally op

en contact (a) for start & stop

(24 V d

.c. 10 mA

):W

ire terminal 324 and

323, connect 170 and 326.

(2)Volt-free norm

ally open contact (a) for start (24 V

d.c. 10 m

A):

Wire term

inal 324 and 325, connect 170 and

326.Volt-free norm

ally open contact (a) for stop

(24 V d

.c. 10 mA

):W

ire terminal 325 and

323.(3)

Volt-free normally op

en contact (a) for start (24 V d

.c. 10 mA

):W

ire terminal 324 and

325, connect 170 and 326.

Volt-free normally closed

contact (b) for stop

(24 V d

.c. 10 mA

):W

ire terminal 325 and

323.(4)

Continuous signal of 24 V

a.c./d.c. for start &

stop (initial setting):

Wire term

inal 324 and 326 (these term

inals are non-polarized

)(5)

Pulse signal of 24 V

a.c./d.c. for start:

Wire term

inal 324 and 326 (these term

inals are non-polarized

.)P

ulse signal of 24 V a.c./d

.c for stop:

Wire term

inal 325 and 326 (these term

inals are non-polarized

.)

TO P

OW

ER

SO

UR

CE

UL:208 V

/460 V - 3 p

h - 60 Hz

CE

: 400 V - 3 p

h - 50H

zC

E: O

VE

RV

OLTA

GE

CATE

GO

RY

III24 V

d.c. 10 m

AC

E:O

VE

RV

OLTA

GE

CATE

GO

RY

II

FIELD

-SU

PP

LIED

PAN

EL

(1)(2)

(3)(4)

(5)continuous

pulse

pulse

continuousp

ulse

FIELD

-WIR

ING

CO

NN

EC

TION

(1)P

rovide p

ower sup

ply w

iring and earthing

Connect w

ire betw

een chiller control panel and

earth on site.The chiller has a circuit b

eaker. Please connect p

ower sup

ply cab

le to the terminal b

lock provid

ed.

Earthing resistance: S

hould b

e determ

ined from

local regulations.E

arthing cable: annealed

copp

er wire (p

lease use a cable of the sam

e cross section as the pow

ersup

ply cab

le).

TER

MIN

AL

STR

IPS

ON

THE

CO

NTR

OL

PAN

EL

Page 17: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

17

Typical piping diagram

NOTE: In order to prevent freezing of the chilled water ensure continued operation of the primary and secondary chilled-waterpumps during dilution cycle operation of the chillers.

HC C

F

R

T

16

P

TP

TP

TP

P

P F

T P F

MV

7

6 8

3

4

5

13

17

10

20

1912

15

18

9

2

1

11

14

General remarks on piping1. Work outside the area surrounded by this line shall be

undertaken at the expense of the owner.2. For pipe connections and diameters refer to the dimensional

drawings and specification tables.3. Steam pressure at the inlet of the machine cannot exceed 146

kPa. Please refer to the diagram to install a pressure reliefvalve near the chiller to release pressure above 146 kPa. Therelief valve should be piped to the outdoors.

4. Even if a reducing valve is not required, a strainer, pressuregauge and drain trap should be provided for each machinenear the steam inlet.

5. The back pressure of the steam drain outlet pipe should becontrolled below 19.6 kPa.

6. Determine the location of the chilled and cooling waterpumps with due consideration of the pump’s hydrostatic head.The machine should not be subject to a pressure larger than1034 kPa at any water headers.

7. Cooling water minimum entering control has to be supplied(please refer to the Installation Manual).

8. Provide a thermometer and a pressure gauge at the coolingwater and chilled water outlet and inlet.

9. Provide an air vent valve in each of the chilled and coolingwater lines at a point higher than the header for chilled waterand cooling water.

10. Drain pipes from the evaporator and absorber should be pipedto the drain channel.

11. Provide a blow-down valve in the cooling water line for waterquality control.

12. All external water piping is to be designed for maximum unitwater-side pressure (to cover any options used).

13. Be sure to provide a shutoff valve to prevent steam flow intothe chiller during shut-down.In case two or more chillers are installed, provide anautomatic shutoff valve.

14. Be sure to design the location of the cooling tower to preventcontamination of cooling water by exhaust gas from flues.

15. If required, fit the rupture disk on the chiller according to therupture disk manual.

16. Separate chilled and cooling water pumps should preferablybe provided for each chiller.

17. Provide an expansion tank in the chilled-water line.18. There should be sufficiently large clearance for easy access to

the evaporator, absorber and condenser, to facilitateinspection and cleaning work.

Thermometer Pressure gauge Flow meter Water pump Strainer Stop valve Shutoff valve Thermostat

Legend1. Main steam piping2. Reducing valve3. Air conditioner4. Chilled-water pump (primary)5. Chilled-water pump (secondary)6. Supply header7. Bypass valve

8. Return header9. To drain channel10. Cooling water pump11. Check valve12. Safety valve13. Steam control valve14. Steam shutoff valve15. Blow-down valve

16. Minimum tank capacity 1 m317. To boiler18. Bypass valve19. Water supply20. Cooling water thermostat

Page 18: Single-Effect Steam-Fired Absorption Chillers - Acareacare.eu/CarrierCD/Litt/11614_PSD_10_05.pdf · Single-Effect Steam-Fired Absorption Chillers The Carrier Corporation has more

Before operating the unit■ Before operating the unit be sure to read the operation manual

carefully.■ Installation should conform to all applicable local codes and

regulations.

During the installation■ Read the installation manual carefully before offloading and

installing the unit.■ All work must be carried out be qualified personnel to

prevent injuries and damage to the equipment.■ Waterproof the unit foundation and provide a drain channel to

prevent water damage to the surrounding equipment.■ Provide adequate space around the unit for maintenance work

to ensure safe working conditions.

Maintenance■ In addition to daily inspection periodical maintenance is

required. Insufficient or incorrect maintenance may causefire, electric shock and injuries.

■ Please consult your local service office for further guidance.

Avoiding hazardous places■ Keep the units away from dangerous inflammable substances

such as gasoline, thinner and combustible gases, as these mayresult in a fire.

Safety considerations