siemens - reconectadores en vacio en mt

36
www.siemens.com/energy Catalog HG 11.42 · 2008 Medium-Voltage Equipment Selection and Ordering Data

Upload: fedefab2009

Post on 26-Nov-2015

85 views

Category:

Documents


6 download

TRANSCRIPT

  • www.siemens.com/energy

    Catalog HG 11.42 2008

    Medium-Voltage EquipmentSelection and Ordering Data

  • 2 Siemens HG 11.42 2008

    R-HG

    11-1

    72.ti

    f

    2

    Siemens Vacuum Recloser 3AD

  • 21

    3

    4

    3Siemens HG 11.42 2008

    Siemens VacuumRecloser 3AD

    Medium-Voltage EquipmentCatalog HG 11.42 2008

    Siemens AG 2008

    Contents Page

    DescriptionGeneral

    Switch unit

    Controller, protection functions

    Ambient conditions, altitude correction factorand number of operating cycles

    Product range overview and scope of delivery

    56

    7

    9

    13

    14

    Product SelectionOrdering data and configuration example

    Selection of primary ratings

    Selection of controller

    Selection of additional equipment

    1516

    17

    20

    24

    Technical DataElectrical data, dimensions and weights:

    Voltage level 12 kV

    Voltage level 15.5 kV

    Voltage level 27 kV

    Voltage level 38 kV

    27

    28

    28

    29

    29

    AnnexInquiry form

    Configuration instructions

    Configuration aid

    3334

    35

    Siemens Vacuum Recloser 3AD Contents

    Foldout page

  • 4 Siemens HG 11.42 2008

    R-HG

    11-3

    00.ti

    f

    Siemens Vacuum Recloser 3AD

  • 1Siemens HG 11.42 2008 5

    DescriptionContents

    Vacuum recloser with cubicle and controller

    R-HG

    11-3

    01.ti

    f

    Contents Page

    Description

    General

    Switch unit:

    Recloser principle

    Design

    Pole assemblies

    Operating mechanism

    Magnetic actuator

    Mechanical lockout

    Recloser cycle

    Controller:

    User interface

    Protection functions

    Communications

    Protocols

    Metering functions

    Data records

    Software

    Standards

    Ambient conditions

    Altitude correction factor

    Number of operating cycles

    Product range overview

    Scope of delivery

    5

    6

    7

    7

    7

    7

    7

    8

    8

    9

    10

    11

    11

    11

    11

    12

    12

    13

    13

    13

    14

    14

    Siemens Vacuum Recloser 3AD

  • 1Siemens HG 11.42 20086

    Siemens vacuum recloser 3AD

    The switch unit is the primary part of the recloser. It islocated on top of the pole to switch the overhead line.It is permanently exposed to weather and environment.

    As the heart of the recloser, the controller is located in acubicle at the bottom of the pole.

    Switch unit Controller inside the cubicleR-

    HG11

    -302

    .tif

    R-HG

    11-3

    03.ti

    f

    DescriptionGeneral

    3AD vacuum reclosers are outdoor circuit-breakersdesigned for frequent opening and reclosing in case oftemporary faults. They fulfill this task automatically bymonitoring the line and operating autonomously.

    The recloser consists of two main components: Theswitch unit being the circuit-breaker and the controller asprotection and control unit. It is housed inside the controlcubicle.

    Siemens Vacuum Recloser 3AD

  • 1Siemens HG 11.42 2008 7

    Recloser principle

    Reclosers are used in distribution systems of power supplycompanies (utilities). Like circuit-breakers they are capableof switching normal and fault currents. They are equippedwith sensors and a controller being the protection andcontrol device. In case of a line fault, they can break andmake several times, thus avoiding longer network interrup-tions due to temporary faults.

    As outdoor devices they are normally pole-mounted andexposed to environment and weather. A recloser consists oftwo components: The switch unit (circuit-breaker) and thecontroller (inside the control cubicle), both connectedthrough a control cable.

    Design

    Switching operationThe vacuum switching technology, proven and fullydeveloped for more than 30 years, is the basis for thevacuum interrupters.

    Pole assemblies

    Each vacuum interrupter is embedded in an epoxy-resin polemade out of weather-proof cycloalyphatic resin. This enablesa small design as well as resistance against environmentaleffects. The vacuum interrupter is vertically mounted insidethe pole, providing a long service life. Each recloser is equip-ped with an integrated current transformer. For special pro-tection purposes, a resistive voltage sensor can also beincorporated in the pole. The accuracy achieved in this wayis much higher than that of capacitive dividers.

    Operating mechanism

    The pole assemblies of the recloser are directly mounted onthe operating mechanism housing. Besides the completekinematics, it also accommodates the position indicator anda mechanical operations counter. The operating mechanismhousing is made of mild steel with a special coating for out-door applications. Optionally, a stainless-steel housing isavailable.

    The recloser is installed on the pole by means of a polemounting frame. Alternatively, the recloser can be mounteddirectly on a frame for pad-mounting in substations.

    Magnetic actuator

    The recloser is operated by a magnetic actuator enabling therecloser cycle, i.e. the high number of switching operationswithin a short period of time. The actuator is a bi-stablesystem, locked in the end positions by permanent magnets.If not in operation, the magnet coils do not consume anypower. The operating force is transmitted to all three polesthrough a mechanical coupling.

    DescriptionSwitch unit

    Siemens Vacuum Recloser 3AD

    Structure of the switch unit

    Switch unit front view

    Switch unit rear view

    R-HG

    11-3

    04.ti

    fR-

    HG11

    -305

    .tif

  • 1Siemens HG 11.42 20088

    Siemens Vacuum Recloser 3ADDescriptionSwitch unit

    Mechanical lockout

    A mechanical lockout enables tripping independently on thecontroller. If this handle is pulled, the recloser opens and issimultaneously locked out electrically and mechanically. Thehandle stays extended, thus indicating the interlocked state.

    To close the recloser again, the operating rod must first bepushed back to the operation position in order to release thelockout. Then the recloser can be closed electrically via thecontrol.

    Recloser cycle

    In case of a network fault, the recloser opens and reclosesseveral times. In case of temporary faults the automaticreclosing significantly reduces the loss of power supply.The recloser cycle is optimized accordingly:

    The first interruption of a fault is done quickly andinstantaneously, so that even the fuses in the system do notoperate. After approx. 300 ms (user settable), it reclosesback on.

    The second and third interruption has a definite or inverse-time delay. Thus, downstream fuses in the network have thechance to operate and isolate the affected network section,restoring normal operation in the remaining network. Thefollowing dead time is usually 210 s (user settable).

    The fourth (optional up to the fifth) interruption is fastagain and serves as a check. This for example utilizes thephysical effect that, when the short-circuit occurs, the linesmove due to the magnetic forces of the current, and foreignobjects are shaken off.

    If the fault still exists, the recloser turns to the lockout andcan only be closed from the operator panel or via SCADA.

    Lock-out handle pushed in(operational position)

    Lock-out handle pulled(open position)

    R-HG

    11-3

    06.ti

    fR-

    HG11

    -307

    .tif

  • 1Siemens HG 11.42 2008 9

    The controller

    The Siemens Argus-M controller is based on the Argus-Mdirectional overcurrent protection relay. These relays provideprotection, control, monitoring, instrumentation and me-tering with integrated input and output logic, data logging& fault reports.

    Communication access to relay functionality is via a frontUSB port for local PC connection or a rear electrical RS485port for remote connection. Additional rear port options areavailable.

    The controller is mounted in the control cubicle. Along withthe controller, this cubicle also contains the auxiliary powersupply with batteries for uninterruptible power supply,electronic boards, fuses, and a general-purpose outlet topower a laptop.

    The controller contains a large number of protectionfunctions (elements) which can be selected or deselectedthrough the menu driven display. These elements can becustomized to the utilities needs by parameters (settings) asdescribed below.

    User interface

    20-character x 4-line backlit LCD

    Menu navigation keys

    3 fixed LEDs

    8 or 16 programmable tri-color LEDs are availableeliminating the need for expensive panel-mounted pilotlights and associated wiring. Each LED is tri-colored (red,green, yellow) allowing for clear indication of the associatedfunctions state.

    12 programmable function keys each with tri-color LED areavailable for implementing scheme control functionality.

    Each function key has an associated tri-color LED (red,green, yellow) allowing for clear indication of the associatedfunctions state.

    DescriptionController

    Siemens Vacuum Recloser 3AD

    Argus-M controller

    Tri-color LEDs and pushbuttonsof the controller

    R-HG

    11-3

    08.ti

    f

    R-HG

    11-3

    09.ti

    f

  • 1Siemens HG 11.42 200810

    DescriptionController

    Siemens Vacuum Recloser 3AD

    Protection functions(in order of ANSI numbering)

    37 Undercurrent

    Each element has settings for pickup level and Definite TimeLag (DTL) delays. Operates if current falls below setting forduration of delay.

    46BC Broken conductor/phase unbalance

    Element has settings for pickup level and DTL delay. With thecircuit-breaker closed, if one or two of the line currents fallbelow setting, this could be due to a broken conductor.

    46NPS Negative phase-sequence overcurrent

    Each element has user settings for pickup level and InverseDefinite Minimum Time Lag (IDMTL) or DTL delay. It operatesif NPS current exceeds setting and delay. NPS current ele-ments can be used to detect unbalances on the system orremote earth faults when a delta-star transformer is incircuit.

    49 Thermal overload

    The thermal algorithm calculates the thermal states from themeasured currents and can be applied to lines, cables andtransformers. Outputs are available for thermal overload andthermal capacity.

    50/51 Phase fault

    50 INST (instantaneous)/DTL (Definite Time Lag) and51 IDMTL (Inverse Definite Minimum Time Lag)/DTL ele-ments provide overcurrent protection, each with indepen-dent settings for pickup current, time-multiplier (51) andtime delays. The user can select IEC or ANSI time currentcharacteristics. The IDMT stage has a user programmablereset characteristic, either DTL or shaped current/time resetcharacteristic to improve grading with electromechanicalprotection.

    50G/51G/50N/51N Earth fault/sensitive earth fault

    Earth-fault current is derived from the residual connection ofthe 3 integrated line CTs. 50 INST/DTL and 51 IDMTL/DTLelements provide overcurrent protection, each with indepen-dent settings for pickup current, time-multiplier (51) andtime delays. The user can select IEC or ANSI time currentcharacteristics. The IDMT stage has a user programmablereset characteristic, either DTL or shaped current/time resetcharacteristic to improve grading with electromechanicalprotection.

    50BF Circuit-breaker fail

    The circuit-breaker fail function is triggered from an internaltrip signal. Line currents are monitored following a trip signaland an output is issued if any current is still detected after aspecified time interval. This can be used to re-trip the CB orto back-trip an upstream CB. A second back-trip time delay isavailable to enable another stage to be utilized if required.

    64H Restricted earth-fault scheme

    The measured earth-fault input may be used in a 64H highimpedance restricted earth-fault scheme. Required externalseries stabilizing resistor and non-linear shunt resistor can besupplied.

    74TC Trip-circuit supervision

    The trip-circuit(s) can be monitored via binary inputs. Trip-circuit failure raises an HMI alarm and output(s).

    81HBL2 Inrush restrain/second harmonic block

    Where second harmonic current is detected (i.e. duringtransformer energization) user selectable elements can beblocked.

    Cold load pickup

    If a circuit-breaker is closed onto a cold load, i.e. one thathas not been powered for a prolonged period, this canimpose a higher than normal load-current demand on thesystem which could exceed normal settings. Theseconditions can exist for an extended period and must not beinterpreted as a fault. To allow optimum setting levels to beapplied for normal operation, the cold load pickup featurewill apply alternative settings for a limited period. The fea-ture resets when either the circuit-breaker has been closedfor a settable period, or if the current has been reducedbeneath a set level for a user set period.

    27/59 Under/overvoltage

    Each element has settings for pickup level, drop-off level andDefinite Time Lag (DTL) delays. It operates if voltage exceedssetting for duration of delay. It can be applied in load shed-ding schemes.

    47 Negative phase-sequence overvoltage

    Each element has settings for pickup level and Definite TimeLag (DTL) delays. It operates if NPS voltage exceeds settingfor duration of delay.

    59N Neutral overvoltage

    Each element has settings for pickup level and Definite TimeLag (DTL) delays. It operates if neutral voltage exceedssetting for duration of delay. Neutral overvoltage can beused to detect earth faults in high impedance earthed orisolated systems.

    60CTS CT supervision

    The CT supervision considers the presence of negativephase-sequence current, without an equivalent level ofnegative phase-sequence voltage, for a user set time as aCT failure. The element has user operate and delay settings.

  • 1Siemens HG 11.42 2008 11

    DescriptionController

    Siemens Vacuum Recloser 3AD

    67/67N Directional control

    Phase-fault, earth-fault and sensitive earth-fault elementscan be directionalized. Each element can be user set toforward, reverse, or non-directional. Directional phase-faultelements are polarized from quadrature voltage. Earth-faultelements can be user set to be polarized from residualvoltage or negative phase-sequence voltage.

    81 Under/overfrequency

    Each element has settings for pickup level, drop-off level andDefinite Time Lag (DTL) delays. It operates if frequency ex-ceeds setting for duration of delay. It is typically applied inload shedding schemes.

    79 Auto-reclose

    Each element provides independent phase-fault and earth-fault/sensitive earth-fault sequences of up to 5 trips, i.e.4 reclose attempts before lockout. Auto-reclose sequencecan be user set to be initiated from internal protectionoperation or via binary input from an external protection.Each trip in the sequence can be user set to be either instan-taneous (fast) or delayed. The user can set each reclose(dead) time and the reclaim time.

    Battery and capacitor check (no number)

    Sag/swell detection

    Optional protection functionality

    Sync check

    Fault locator

    Loop automation

    Single-triple operation

    Communications

    Front USB port

    Rear RS485 port

    Optional functions

    Rear fiber optic ports

    IRIG-B ports

    RS232 ports

    Protocols

    IEC 60870-5-103

    Modbus RTU

    DNP 3.0

    Metering functions

    Primary current phases and earth

    Secondary current phases and earth

    Positive phase-sequence (PPS) current

    Negative phase-sequence (NPS) current

    Zero phase-sequence (ZPS) current

    Binary input/output status

    Trip circuit healthy/failure

    Time and date

    Starters

    Fault records

    Event records

    Frequency

    Waveform records

    Circuit-breaker trip counters

    It summation for contact wear

    Direction

    Primary line and phase voltages

    Secondary voltages

    Apparent power and power factor

    Real and reactive power

    W Hr forward and reverse

    VAr Hr forward and reverse

    Historical demand record

    Positive phase-sequence (PPS) voltage

    Negative phase-sequence (NPS) voltage

    Zero phase-sequence (ZPS) voltage

    Data records

    Sequence of event records

    Up to 5000 events can be stored.

    Fault records

    The last 10 fault records are displayed on the HMI, with timeand date of trip, measured quantities and type of fault.

    Disturbance recorder

    The waveform recorder stores analog data for all phases, thestates of protection functions, binary inputs, LEDs and binaryoutputs with pre & post trigger data. A record can be triggeredfrom protection function, binary input or via data communi-cations. The waveform recorder stores up to 10 s data.

    Load profile recording

    A rolling record of demand over the last 24 h is stored. Thedemand is averaged over a user selectable period of time.A rolling record of such demand averages is stored andprovides the demand history. A typical application is torecord 15 min-averages for the last 7 days.

  • 1Siemens HG 11.42 200812

    DescriptionController, standards

    Siemens Vacuum Recloser 3AD

    Software

    Reydisp Evolution

    For communication with the relay via a PC (personalcomputer) a user-friendly software package, ReydispEvolution, is available to allow transfer of relay settings,waveform records, event records, fault data records,instruments/meters and control functions. Reydisp Evolutionis compatible with IEC 60870-5-103.

    Programmable logic

    The user can map binary inputs and protection operatedoutputs to function inhibits, logic inputs, LEDs and/or binaryoutputs. The user can also enter up to 16 equations definingscheme logic using standard functions e.g. timers and/orgates, inverters and counters. Each protection elementoutput can be used for alarm & indication and/or tripping.

    Waveform records analysis

    See figure left

    Quick logic

    The Quick logic feature allows the user to input up to 16logic equations (E1 to E16) in text format. Equations can beentered using Reydisp or at the relay fascia.

    Each logic equation is built up from text representing controlcharacters. Each can be up to 20 characters long.

    Standards

    The recloser conforms to the following standards

    ANSI C37.60 (2003)

    IEC 60255

    IEC 60694 (in future IEC 62271-1)

    Typical Reydisp Evolution screenshot

    R-HG

    11-3

    10.ti

    f

  • 1Siemens HG 11.42 2008 13

    Ambient conditions

    The recloser is designed for the normal operating conditionsdefined in ANSI C37.60. This comprises an ambient tempera-ture from 40 C to +55 C plus solar radiation.

    Altitude correction factor

    The dielectric strength of air insulation decreases withincreasing altitude due to low air density. The rated lightningimpulse withstand voltage values specified in the chapterTechnical Data apply to a site altitude of 1000 m above sealevel. For an altitude above 1000 m, the insulation levelmust be corrected according to the opposite drawing.

    The characteristic shown applies to the rated short-durationpower-frequency withstand voltage and the rated lightningimpulse withstand voltage.

    To select the devices, the following applies:

    U W U0 x KaU Rated withstand voltage under standard reference atmosphere

    U0 Rated withstand voltage requested for the place of installation

    Ka Altitude correction factor according to the opposite diagram

    Example

    For a requested rated lightning impulse withstand voltageof 75 kV at an altitude of 2500 m, an insulation level of90 kV under standard reference atmosphere is required asa minimum:

    90 kV W 75 kV x 1.2

    Number of operating cycles

    The recloser is designed for 10,000 operating cycles atnormal current.

    According to the standard IEEE C37.60, the recloser has beentested for 116 short-circuit breaking operations. The actualnumber of short-circuit breaking operations is higher thanthat, and can be even more than 200 depending on the pa-rameters of the short-circuit current (amplitude, DC compo-nent).

    DescriptionAmbient conditions, altitude correction factor and number of operating cycles

    Siemens Vacuum Recloser 3AD

  • 1Siemens HG 11.42 200814

    DescriptionProduct range overview and scope of delivery

    Siemens Vacuum Recloser 3AD

    Product range overview

    Rated voltage Ratedshort-circuit

    breaking current

    Ratedlightning impulsewithstand voltage

    Rated normal current

    kV kA kV 400 A 630 A 800 A

    12 12.5 95

    15.5 12.5 110

    16 110

    27 12.5 125

    12.5 150

    16 150

    38 12.5 170

    16 170

    Scope of delivery

    Standard equipment Optional available Remarks

    Switch unitOperating mechanism Electrical operating mechanism

    (magnetic actuator)

    Operating mechanismhousing

    Mild steel with outdoor protectioncoating IP 55 with lifting eyesand earthing connection

    Stainless steel

    Switching medium Vacuum interrupters

    Insulation Cycloaliphatic epoxy resin/air

    Power supply Auxiliary power input Auxiliary transformer for supplyfrom HV line

    Position indicator OPEN: greenCLOSED: red

    Customer-specific color or inscription

    Operations counter Mechanical in the switch unit;electronical in the controller

    Interlocking Electrical; mechanical lockout

    Configuration Pole mounting and 6 mcontrol cable

    Other cable lengths and/orsubstation frame

    Sensors Integrated current transformers Integrated voltage sensors

    Controller andcontrol cubicleCubicle Mild steel with outdoor protection

    coating IP 65 with lifting eyesand earthing connection

    Stainless steel

    Socket outlet USA version Country-specific design

    Controller size E10 (= 10" width) E12 (= 12" width)

    Number of inputs/outputs for customer use

    5 x BI, 8 x BO12 function keys8 user-definable LEDs

    Additional BI/BO and 12 LEDs

    Temperature range Up to 30 C 40 C

    Control keys 5 navigation keys,12 function keys,2 pushbuttons

    Customer-specific pushbuttons orrotary CLOSE/OPEN switches

    Controller interfaces USB (front), RS485 (rear) RS232, fiber optic, IRIG-B

  • 215Siemens HG 11.42 2008

    Switch unit bottom view

    Control cubicle

    Contents Page

    Product Selection

    Ordering data and configuration example

    Selection of primary ratings:

    Voltage level 12 kV

    Voltage level 15.5 kV

    Voltage level 27 kV

    Voltage level 38 kV

    Selection of controller:

    Recloser configuration

    Current and voltage measuring

    Controller size

    Auxiliary voltage

    Control and sensor cables

    Communication protocols

    Communication interfaces

    Function packages

    Languages and power socket

    Selection of additional equipment

    Accessories and spare parts

    15

    16

    17

    17

    18

    19

    20

    20

    21

    21

    22

    22

    22

    23

    23

    24

    25

    Product SelectionContents

    R-HG

    11-3

    11.ti

    fR-

    HG11

    -312

    .tif

    Siemens Vacuum Recloser 3AD

  • 216 Siemens HG 11.42 2008

    Order number structure

    The vacuum reclosers consist of a primary part as well as of acontroller or secondary part. The relevant data make up the16-digit order number. The primary part covers the mainelectrical data of the circuit-breaker poles. The controller andsecondary part covers all auxiliary devices and the controller,which are necessary for operating and controlling therecloser.

    Order codes

    Individual equipment versions, marked with 9 or Z in the 8th

    to 16th position, are explained more in detail by a 3-digitorder code. Several order codes can be added to the ordernumber in succession and in any sequence.

    Mounting parts and special versions ()

    In case of special versions, - Z is added to the order numberand a descriptive order code follows. If several specialversions are required, the suffix - Z is only listed once.If a requested special version is not in the catalog and cantherefore not be ordered via order code, it has to beidentified with Y 9 9 after consultation. The agreementhereto is made between your responsible sales partner andthe order processing department in our Switchgear Factoryin Berlin.

    Configuration example

    In order to simplify the selection of the correct order numberfor the requested recloser type, you will find a configurationexample on each page of the chapter Equipment Selection.For the selection of the auxiliary voltages, the fixing options,the controller, etc. always the last example of the primarypart was taken over and continued, so that at the end of theequipment selection (page 24) a completely configuredrecloser results as an example.

    On the foldout page we offer a configuring aid.Here you can fill in the order number you havedetermined for your recloser.

    a: alphabetical n: numerical

    Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes

    Order No.: 3 A D n n n n n a a n n n a a n

    Primary part1st position Superior group

    Switching devices

    2nd position Main groupCircuit-breaker

    3rd position SubgroupOutdoor vacuum recloser

    4th to 7th position Basic equipmentDesign and ratingsof the vacuum recloser

    Secondary part8th to 16th position Controller, sensors, cables and

    other necessary data

    Order codesGroup of 3 after the Order No.Format: a n a

    Special versions ()Initiated with -ZGroup of 3 after the Order No.Format: a n n

    Product SelectionOrdering data and configuration example

    Example for Order No.: 3 A D 6 2 3 2

    Order codes:

    Siemens Vacuum Recloser 3AD

  • 217Siemens HG 11.42 2008

    Product SelectionSelection of primary ratings

    12 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz Order No.: 3 A D

    Type

    Ur Up Ud Isc Ir

    kV kV kV kA A

    12 75 42 12.5 630 3 A D 1 1 2 2

    3 A D 3 1 2 2

    3 A D 4 1 2 2

    3 A D 6 1 2 2

    800 3 A D 1 1 2 3

    3 A D 3 1 2 3

    3 A D 4 1 2 3

    3 A D 6 1 2 3

    15.5 kV50/60 Hz

    Ur Up Ud Isc Ir

    kV kV kV kA A

    15.5 110 50 12.5 400 3 A D 1 2 2 1

    3 A D 3 2 2 1

    3 A D 4 2 2 1

    3 A D 6 2 2 1

    630 3 A D 1 2 2 2

    3 A D 3 2 2 2

    3 A D 4 2 2 2

    3 A D 6 2 2 2

    800 3 A D 1 2 2 3

    3 A D 3 2 2 3

    3 A D 4 2 2 3

    3 A D 6 2 2 3

    16 630 3 A D 1 2 3 2

    3 A D 3 2 3 2

    3 A D 4 2 3 2

    3 A D 6 2 3 2

    800 3 A D 1 2 3 3

    3 A D 3 2 3 3

    3 A D 4 2 3 3

    3 A D 6 2 3 3

    Configuration example

    Siemens vacuum recloser 3AD 3 A D

    Rated voltage Ur = 15.5 kV

    Rated lightning impulse withstand voltage Up = 110 kV

    Rated short-duration power-frequency withstand voltage Ud = 50 kV

    Rated short-circuit breaking current Isc = 16 kARated normal current Ir = 630 AType: Three-phase recloser for loop automation 6 2 3 2

    See

    page

    20

    See

    page

    20

    See

    page

    21

    See

    page

    21

    See

    page

    22

    See

    page

    22

    See

    page

    22

    See

    page

    23

    See

    page

    23

    See

    page

    24

    Rate

    dvo

    ltage

    Rate

    dlig

    htni

    ngim

    puls

    ew

    ithst

    and

    volta

    ge

    Rate

    dsh

    ort-

    dura

    tion

    pow

    er-f

    requ

    ency

    with

    stan

    dvo

    ltage

    Rate

    dsh

    ort-

    circ

    uit

    brea

    king

    curr

    ent

    Rate

    dno

    rmal

    curr

    ent

    Sing

    le-p

    hase

    Thre

    e-ph

    ase

    3x

    sing

    le-p

    hase

    /si

    ngle

    -trip

    le

    Thre

    e-ph

    ase

    for

    loop

    auto

    mat

    ion

    Siemens Vacuum Recloser 3AD

    Example for Order No.: 3 A D 6 2 3 2

    Order codes:

  • 218 Siemens HG 11.42 2008

    Product SelectionSelection of primary ratings

    Siemens Vacuum Recloser 3AD

    27 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz Order No.: 3 A D

    Type

    Ur Up Ud Isc Ir

    kV kV kV kA A

    27 125 60 12.5 400 3 A D 1 3 2 1

    3 A D 3 3 2 1

    3 A D 4 3 2 1

    3 A D 6 3 2 1

    630 3 A D 1 3 2 2

    3 A D 3 3 2 2

    3 A D 4 3 2 2

    3 A D 6 3 2 2

    800 3 A D 1 3 2 3

    3 A D 3 3 2 3

    3 A D 4 3 2 3

    3 A D 6 3 2 3

    150 60 12.5 400 3 A D On request

    3 A D On request

    3 A D On request

    3 A D On request

    630 3 A D On request

    3 A D On request

    3 A D On request

    3 A D On request

    800 3 A D On request

    3 A D On request

    3 A D On request

    3 A D On request

    16 630 3 A D On request

    3 A D On request

    3 A D On request

    3 A D On request

    800 3 A D On request

    3 A D On request

    3 A D On request

    3 A D On request

    Configuration example

    Siemens vacuum recloser 3AD 3 A D

    Rated voltage Ur = 27 kV

    Rated lightning impulse withstand voltage Up = 125 kV

    Rated short-duration power-frequency withstand voltage Ud = 60 kV

    Rated short-circuit breaking current Isc = 12.5 kARated normal current Ir = 400 AType: Three-phase 3 3 2 1

    See

    page

    20

    See

    page

    20

    See

    page

    21

    See

    page

    21

    See

    page

    22

    See

    page

    22

    See

    page

    22

    See

    page

    23

    See

    page

    23

    See

    page

    24

    Rate

    dvo

    ltage

    Rate

    dlig

    htni

    ngim

    puls

    ew

    ithst

    and

    volta

    ge

    Rate

    dsh

    ort-

    dura

    tion

    pow

    er-f

    requ

    ency

    with

    stan

    dvo

    ltage

    Rate

    dsh

    ort-

    circ

    uit

    brea

    king

    curr

    ent

    Rate

    dno

    rmal

    curr

    ent

    Sing

    le-p

    hase

    Thre

    e-ph

    ase

    3x

    sing

    le-p

    hase

    /si

    ngle

    -trip

    le

    Thre

    e-ph

    ase

    for

    loop

    auto

    mat

    ion

    Example for Order No.: 3 A D 3 3 2 1

    Order codes:

  • 219Siemens HG 11.42 2008

    Produt SelectionSelection of primary ratings

    Siemens Vacuum Recloser 3AD

    38 kV Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes50/60 Hz Order No.: 3 A D

    Type

    Ur Up Ud Isc Ir

    kV kV kV kA A

    38 170 70 12.5 630 3 A D On request

    3 A D On request

    3 A D On request

    3 A D On request

    800 3 A D On request

    3 A D On request

    3 A D On request

    3 A D On request

    16 630 3 A D On request

    3 A D On request

    3 A D On request

    3 A D On request

    800 3 A D On request

    3 A D On request

    3 A D On request

    3 A D On request

    Configuration example

    Siemens vacuum recloser 3AD 3 A D

    Rated voltage Ur = 38 kV

    Rated lightning impulse withstand voltage Up = 170 kV

    Rated short-duration power-frequency withstand voltage Ud = 70 kV

    Rated short-circuit breaking current Isc = 16 kARated normal current Ir = 800 AType: Single-phase on request

    See

    page

    20

    See

    page

    20

    See

    page

    21

    See

    page

    21

    See

    page

    22

    See

    page

    22

    See

    page

    22

    See

    page

    23

    See

    page

    23

    See

    page

    24

    Rate

    dvo

    ltage

    Rate

    dlig

    htni

    ngim

    puls

    ew

    ithst

    and

    volta

    ge

    Rate

    dsh

    ort-

    dura

    tion

    pow

    er-f

    requ

    ency

    with

    stan

    dvo

    ltage

    Rate

    dsh

    ort-

    circ

    uit

    brea

    king

    curr

    ent

    Rate

    dno

    rmal

    curr

    ent

    Sing

    le-p

    hase

    Thre

    e-ph

    ase

    3x

    sing

    le-p

    hase

    /si

    ngle

    -trip

    le

    Thre

    e-ph

    ase

    for

    loop

    auto

    mat

    ion

    Example for Order No.: 3 A D

    Order codes:

  • 220 Siemens HG 11.42 2008

    8th position Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codesRecloser configuration Order No.: 3 A D

    Recloser for pole mounting 1) incl. cubicle, controller and control cable 1Recloser for substation application incl. cubicle and controller 2Switch unit only (w/o cubicle, controller and control cable) 2) 3 Y 0 0 0 Y Y

    1) Pole mounting according to list of accessories

    2) This option is only possible in the stated order number

    9th positionCurrent and voltage measuring

    Current transformers Voltage sensors

    1 integrated CTper pole

    1 integrated sensorper pole

    (including sensor cables)

    3 x external VTs(to be defined as

    accessories)

    A

    B

    1)

    1)

    1) C

    1) Necessary for recloser type: Three-phase for loop automation

    Configuration example

    Siemens vacuum recloser 3AD 3 A D

    (Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A)Type: Three-phase 3 3 2 1

    Recloser for pole mounting incl. control cubicle and control cable 1

    Current and voltage measuring: current transformers, 1 integrated CT per pole A

    Example for Order No.: 3 A D 3 3 2 1 1 A

    Order codes:

    Options

    See

    page

    21

    See

    page

    21

    See

    page

    22

    See

    page

    22

    See

    page

    22

    See

    page

    23

    See

    page

    23

    See

    page

    24

    Product SelectionSelection of controller

    Siemens Vacuum Recloser 3AD

  • 221Siemens HG 11.42 2008

    10th position Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codesController size Order No.: 3 A D

    E10 E12 12 8 16 13 23 33 43 14 22 30

    For 3-phase and single-phase applications

    A

    B

    C

    D

    E

    For loop automation

    F

    Without controller (refers to switch unit only) Y

    11th positionAuxiliary voltage

    Without auxiliary voltage supply (need for switch unit only) 048 V On request

    60 V On request

    110 V 3220 V 4

    110/120 V 5220/240 V 6

    With auxiliary transformer and rated voltage as below:

    Rated voltage 11 kV 9 With order code T 3 ARated voltage 12 kV 9 With order code T 3 BRated voltage 13.8 kV 9 With order code T 3 CRated voltage 15 kV 9 With order code T 3 D

    Configuration example

    Siemens vacuum recloser 3AD 3 A D

    (Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A)Type: Three-phase 3 3 2 1 1 A

    Controller size: E12, 12 function keys,

    16 tri-color LEDs, 33 binary inputs, 30 binary outputs D

    Auxiliary voltage 110/120 V AC 5

    See

    page

    22

    See

    page

    22

    See

    page

    22

    See

    page

    23

    See

    page

    23

    See

    page

    24

    Product SelectionSelection of controller

    Siemens Vacuum Recloser 3AD

    Example for Order No.: 3 A D 3 3 2 1 1 A D 5

    Order codes:

    DC voltage AC voltage

    Con

    trol

    lers

    ize

    Func

    tion

    keys

    Num

    bero

    ftr

    i-col

    orLE

    Ds

    Num

    bero

    fbin

    ary

    inpu

    ts(p

    artly

    forc

    usto

    mer

    use)

    Num

    bero

    fbin

    ary

    outp

    uts

    (par

    tlyfo

    rcus

    tom

    erus

    e)

  • 222 Siemens HG 11.42 2008

    Product SelectionSelection of controller

    Siemens Vacuum Recloser 3AD

    12th position Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codesControl and sensor cables Order No.: 3 A D

    Without (need for switch unit only) 0Cable length 6 m 1Cable with special length (to be specified in clear text) 9 M 1 Y

    13th positionCommunication protocols

    Without communication protocol (need for switch unit only) 0IEC 60870-5-103 and Modbus RTU 1DNP 3.0 2

    14th positionCommunication interfaces

    A

    B

    C

    D

    E

    Without communication interface (need for switch unit only) Y

    Configuration example

    Siemens vacuum recloser 3AD 3 A D

    (Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A)Type: Three-phase 3 3 2 1 1 A D 5

    Length of control and sensor cable 6 m 1

    Communication protocol IEC 60870-5-103 and Modbus RTU 1

    Communication interfaces 1 x USB, 2 x RS485, 1 x IRIG-B C

    See

    page

    23

    See

    page

    23

    See

    page

    24

    Example for Order No.: 3 A D 3 3 2 1 1 A D 5 1 1 C

    Order codes:

    Options(also comprises sensor cables for external voltage sensors if selected)

    Options

    1x

    USB

    (fro

    nt)

    1x

    RS48

    5(r

    ear)

    2x

    RS48

    5(r

    ear)

    1x

    RS23

    2(r

    ear)

    1x

    IRIG

    -B

    2x

    optic

    al

    STpl

    ug(s

    ingl

    em

    ode)

    STpl

    ug(m

    ultip

    lem

    ode)

  • 223Siemens HG 11.42 2008

    15th position Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codesFunction packages Order No.: 3 A D

    Standard protection and monitoring functions AStandard protection and monitoring functionsplus synchro-check and fault locator CStandard protection and monitoring functionsfor loop automation DStandard protection and monitoring functionsfor loop automation with synchro-check and fault locator EStandard protection and monitoring functionsfor single-triple application FStandard protection and monitoring functionsfor single-triple application with synchro-check and fault locator GWithout protection functions (need for switch unit only) Y

    16th positionLanguages and power socket

    English UK 1American English USA 2Spanish Mexico 3Portuguese Brazil 4Other languages on request 9 R 1 Y

    Configuration example

    Siemens vacuum recloser 3AD 3 A D

    (Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A)Type: Three-phase 3 3 2 1 1 A D 5 1 1 C

    Controller with standard protection and monitoring functions A

    Language of operating instructions and nameplate: English

    Standard of power socket: UK 1

    See

    page

    24

    Language of operating Standard of power socketinstructions and nameplate

    Example for Order No.: 3 A D 3 3 2 1 1 A D 5 1 1 C A 1

    Order codes:

    Options

    Product SelectionSelection of controller

    Siemens Vacuum Recloser 3AD

  • 224 Siemens HG 11.42 2008

    Selection of additional equipment Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codesOrder No.: 3 A D

    Ambient temperature down to 40 C Z A 3 8Seaworthy packing inside Germany Z F 0 2Stainless steel for tank, control cubicle Z T 0 1Radio modem power supply 12 V DC Z T 0 2Serial to Ethernet converter Z T 0 3Pole mounting frame with bracket for surge arrester(source and load side) Z T 2 1Pole mounting frame Siemens design (with bracket for surge arresters, source and load side) Z T 2 2Further non-listed special versions (only after consultation withyour responsible sales partner). Information additionally in clear text Z Y 9 9

    Configuration exampleSiemens vacuum recloser 3AD 3 A DRated voltage Ur = 27 kVRated lightning impulse withstand voltage Up = 125 kVRated short-duration power-frequency withstand voltage Ud = 60 kVRated short-circuit breaking current Isc = 12.5 kARated normal current Ir = 400 AType: Three-phase 3 3 2 1 Recloser for pole mounting incl. control cubicle and control cable 1

    Current and voltage measuring: current transformers, 1 CT integrated per pole A

    Controller size: E12, 12 function keys,

    16 tri-color LEDs, 33 binary inputs, 30 binary outputs D

    Auxiliary voltage 110/120 V AC 5

    Length of control and sensor cable 6 m 1

    Communication protocol IEC 60870-5-103 and Modbus RTU 1

    Communication interfaces 1 x USB, 2 x RS485, 1 x IRIG-B C

    Controller with standard protection and monitoring functions A

    Language of operating instructions and nameplate: English

    Standard of power socket: UK 1

    Seaworthy packing inside Germany Z F 0 2

    Stainless steel for tank, control cubicle Z T 0 1

    Options

    Example for Order No.: 3 A D 3 3 2 1 1 A D 5 1 1 C A 1 Z

    Order codes: F 0 2 + T 0 1

    Product SelectionSelection of additional equipment

    Siemens Vacuum Recloser 3AD

  • 225Siemens HG 11.42 2008

    Accessories and spare parts

    A wide range of spare parts and accessories is available.Please contact your responsible sales partner and the orderprocessing department in our Switchgear Factory in Berlin.

    Product SelectionAccessories and spare parts

    Siemens Vacuum Recloser 3AD

    Note:For any request regarding spare parts,subsequent deliveries, etc. the followingdetails are necessary: Type designation Serial No. Design code Year of manufacture

    Data on the nameplate

  • 26 Siemens HG 11.42 2008

    Siemens Vacuum Recloser 3AD

    R-HG

    11-3

    13.ti

    f

  • 27Siemens HG 11.42 2008

    3

    Switch unit driver - discarge switch for the capacitor

    Controller with protective cap

    Contents Page

    Technical Data

    Electrical data, dimensions and weights:

    Voltage level 12 kV

    Voltage level 15.5 kV

    Voltage level 27 kV

    Voltage level 38 kV

    27

    28

    28

    29

    29

    Technical DataContents

    R-HG

    11-3

    14.ti

    fR-

    HG11

    -315

    .tif

    Siemens Vacuum Recloser 3AD

  • 28 Siemens HG 11.42 2008

    3

    Technical DataElectrical data, dimensions and weights

    12 kV50/60 Hz

    Ir tk Isc Ima Up Ud

    A s kA kA kV kV mV mm mm mm kg A A

    3AD122 630 3 12.5 31.5 75 42 24 810 312 287 142 2 10

    3AD123 800 3 12.5 31.5 75 42 24 810 312 287 142 2 10

    15.5 kV50/60 Hz Ir tk Isc Ima Up Ud

    A s kA kA kV kV mV mm mm mm kg A A

    3AD221 400 3 12.5 31.5 110 50 24 810 312 287 142 2 10

    3AD222 630 3 12.5 31.5 110 50 24 810 312 287 142 2 10

    3AD223 800 3 12.5 31.5 110 50 24 810 312 287 142 2 10

    3AD232 630 3 16 40 110 50 24 810 312 287 142 2 10

    3AD233 800 3 16 40 110 50 24 810 312 287 142 2 10

    Rat

    edn

    orm

    alcu

    rren

    t

    Rate

    dop

    erat

    ing

    sequ

    ence

    :O-0

    .2s

    -CO

    -2s

    -CO

    -2s

    -CO

    (-30

    s-C

    O)

    -Loc

    k-ou

    t

    Rate

    ddu

    ratio

    nof

    shor

    t-ci

    rcui

    t

    Rate

    dsh

    ort-

    circ

    uitb

    reak

    ing

    curr

    ent

    Rate

    dsh

    ort-

    circ

    uitm

    akin

    gcu

    rren

    t

    Rate

    dlig

    htni

    ngim

    puls

    ew

    ithst

    and

    volta

    ge

    Rate

    dsh

    ort-

    dura

    tion

    pow

    er-f

    requ

    ency

    with

    stan

    dvo

    ltage

    Vol

    tage

    drop

    Ube

    twee

    nco

    nnec

    tions

    Cre

    epag

    edi

    stan

    ce,p

    hase

    -to-

    eart

    h

    Cle

    aran

    ce,

    phas

    e-to

    -pha

    se

    Min

    imum

    clea

    ranc

    e,ph

    ase-

    to-e

    arth

    Wei

    ght

    Line

    char

    ging

    curr

    ent

    Cab

    lech

    argi

    ngcu

    rren

    t

    Siemens Vacuum Recloser 3AD

    Order No.

  • 29Siemens HG 11.42 2008

    3

    27 kV50/60 Hz

    Ir tk Isc Ima Up Ud

    A s kA kA kV kV mV mm mm mm kg A A

    3AD321 400 3 12.5 31.5 125 60 24 810 312 287 142 5 25

    3AD322 630 3 12.5 31.5 125 60 24 810 312 287 142 5 25

    3AD323 800 3 12.5 31.5 125 60 24 810 312 287 142 5 25

    3AD ... 400 3 12.5 31.5 150 60 On request 5 25

    3AD 630 3 12.5 31.5 150 60 On request 5 25

    3AD 800 3 12.5 31.5 150 60 On request 5 25

    3AD 630 3 16 40 150 60 On request 5 25

    3AD 800 3 16 40 150 60 On request 5 25

    38 kV50/60 Hz Ir tk Isc Ima Up Ud

    A s kA kA kV kV mV mm mm mm kg A A

    3AD 630 3 12.5 31.5 170 70 On request 5 40

    3AD 800 3 12.5 31.5 170 70 On request 5 40

    3AD 630 3 16 40 170 70 On request 5 40

    3AD 800 3 16 40 170 70 On request 5 40

    Technical DataElectrical data, dimensions and weights

    Siemens Vacuum Recloser 3AD

    Rat

    edn

    orm

    alcu

    rren

    t

    Rate

    dop

    erat

    ing

    sequ

    ence

    :O-0

    .2s

    -CO

    -2s

    -CO

    -2s

    -CO

    (-30

    s-C

    O)

    -Loc

    k-ou

    t

    Rate

    ddu

    ratio

    nof

    shor

    t-ci

    rcui

    t

    Rate

    dsh

    ort-

    circ

    uitb

    reak

    ing

    curr

    ent

    Rate

    dsh

    ort-

    circ

    uitm

    akin

    gcu

    rren

    t

    Rate

    dlig

    htni

    ngim

    puls

    ew

    ithst

    and

    volta

    ge

    Rate

    dsh

    ort-

    dura

    tion

    pow

    er-f

    requ

    ency

    with

    stan

    dvo

    ltage

    Vol

    tage

    drop

    Ube

    twee

    nco

    nnec

    tions

    Cre

    epag

    edi

    stan

    ce,p

    hase

    -to-

    eart

    h

    Cle

    aran

    ce,

    phas

    e-to

    -pha

    se

    Min

    imum

    clea

    ranc

    e,ph

    ase-

    to-e

    arth

    Wei

    ght

    Line

    char

    ging

    curr

    ent

    Cab

    lech

    argi

    ngcu

    rren

    t

    Order No.

  • 30 Siemens HG 11.42 2008

    3

    Mabild 1

    Mabild 2

    Dimension drawings

    Dimensions of control cubicle

    Technical DataDimension drawings

    Siemens Vacuum Recloser 3AD

    Dimensions of switch unit

  • 31Siemens HG 11.42 2008

    3

    Technical DataDimension drawings

    Siemens Vacuum Recloser 3AD

    Mabild 2

    Dimension drawings

    Dimensions of switch unit with pole mounting frame

  • 32 Siemens HG 11.42 2008

    R-HG

    11-1

    81.ti

    f

    Siemens Vacuum Recloser 3AD

  • 33Siemens HG 11.42 2008

    4

    Contents Page

    Annex

    Inquiry form

    Configuration instructions

    Configuration aid

    33

    34

    35

    AnnexContents

    Foldout page

    Siemens Vacuum Recloser 3AD

    Switchgear Factory in Berlin, Germany

    R-HG

    11-1

    80.e

    ps

  • 34 Siemens HG 11.42 2008

    4

    AnnexInquiry form

    Inquiry concerning

    Siemens vacuumrecloser 3AD

    Please

    Submit an offer Call us Visit us

    Your address

    Company

    Dept.

    Name

    Street

    Postal code/city

    Phone

    Fax

    E-mail

    Siemens AG

    Dept.

    Name

    Street

    Postal code/city

    Fax

    Technical dataOther values

    Rated voltage 12 kV

    27 kV

    15.5 kV

    38 kV _ _ _ kV

    Rated lightning impulse

    withstand voltage

    75 kV

    150 kV

    110 kV

    170 kV

    125 kV

    _ _ _ kV

    Rated short-duration

    power-frequency

    withstand voltage

    42 kV

    60 kV

    50 kV

    70 kV _ _ _ kV

    Rated short-circuit

    breaking current

    12.5 kA 16 kA _ _ _ kA

    Rated normal current 400 A 630 A 800 A _ _ _ A

    Secondary equipment

    For possible combinations see pages 20 to 23

    Recloser configuration Recloser for

    pole mounting

    Without control

    cubicle

    Made of

    stainless steel

    Others

    Application in

    substation

    Current and voltage sensing Integrated current

    transformers

    Integrated voltage

    sensors

    External voltage

    transformers

    Controller equipment 4 binary inputs

    34 binary inputs

    9 binary outputs

    _ _ _

    14 binary inputs

    17 binary outputs

    24 binary inputs

    25 binary outputs

    Auxiliary voltage _ _ _ V DC _ _ _ V AC, _ _ _ Hz

    Control and sensor cable Without 6 m _ _ _ m

    Communication interfaces USB

    Optical

    RS485

    IRIG-B

    RS232

    Function packages additional

    to standard functions

    Synchronizing and

    synchro-check

    Loop automation

    Fault locating

    Single-triple

    Please copy, fill in and return to yourSiemens partner

    Application and other requirements

    Please check off _ _ _ Please fill in

    Siemens Vacuum Recloser 3AD

  • You prefer to configure your Siemens vacuum recloser 3AD on your own?Please follow the steps for configuration and enter the order number in the configuration aid.Alternatively you can also use your prompted online configurator under www.siemens.com/energy

    Instruction for configuration of the Siemens vacuum recloser 3AD

    1st step: Definition of the primary part (see pages 17 to 19)

    Please specify the following ratings: Possible options:

    Rated voltage (Ur) Ur: 12 kV to 38 kVRated lightning impulse withstand voltage (Up) Up: 75 kV to 170 kVRated short-duration power-frequency withstand voltage (Ud) Ud: 42 kV to 70 kVRated short-circuit breaking current (Isc) Isc: 12.5 kA and 16 kARated normal current (Ir) Ir: 400 A to 800 A

    These ratings define the positions 4 to 7 of the order number.

    2nd step: Definition of the secondary equipment (see pages 20 to 23)

    Please specify the following equipment features: Possible options:

    Recloser configuration(position 8)

    Recloser incl. control cubicle and cables, recloser without control cubicleand cables, recloser for transformer substation, retrofit recloser

    Sensors(position 9)

    Integrated current transformers, integrated voltage transformers,external voltage transformers

    Controller(position 10)

    Housing size, number of function keys and three-color LEDs,number of available binary inputs and outputs

    Auxiliary voltage(position 11)

    Voltages from 48 V DC to 240 V AC

    Cable length of control and sensor cable(position 12)

    Standard length 6 m, special lengths possible

    Communication protocol(position 13)

    IEC 60870-5-103 and Modbus RTU, DNP 3.0

    Communication interfaces(position 14)

    USB, RS485, RS232, IRIG-B, optical, ST plug

    Functions of the controller(position 15)

    Standard protection and monitoring functions,synchronizing and synchro-check, fault location

    Language of operating instructions and nameplate(position 16)

    English, American English, Spanish and Portuguese

    These equipment features define the positions 8 to 16 of the order number.

    3rd step: Do you have any further requirements concerning the equipment? (Please refer to page 24)

    Should you still need more options than the possible special equipment like country-specific mains sockets,weather resistance down to 40 C, stainless-steel design, etc. please contact your responsible sales partner.

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

    Z

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    3 A D

    + + + +

    + + + +

    For configuration of yourSiemens vacuum recloser 3AD

    35Siemens HG 11.42 2008

    S

    e

    e

    p

    a

    g

    e

    2

    0

    S

    e

    e

    p

    a

    g

    e

    2

    0

    S

    e

    e

    p

    a

    g

    e

    2

    1

    S

    e

    e

    p

    a

    g

    e

    2

    1

    S

    e

    e

    p

    a

    g

    e

    2

    2

    S

    e

    e

    p

    a

    g

    e

    2

    2

    S

    e

    e

    p

    a

    g

    e

    2

    2

    S

    e

    e

    p

    a

    g

    e

    2

    3

    S

    e

    e

    p

    a

    g

    e

    2

    3

    S

    e

    e

    p

    a

    g

    e

    2

    4

    S

    e

    e

    p

    a

    g

    e

    1

    7

    t

    o

    S

    e

    e

    p

    a

    g

    e

    1

    9

  • For questions concerning PowerTransmission and Distribution:You can contact our Customer SupportCenter 24 hours a day, 365 days a year.Tel.: +49 180/524 70 00Fax: +49 180/524 24 71(Charges depending on provider)E-Mail: [email protected]/energy-support

    Siemens AGEnergy SectorMedium Voltage DivisionNonnendammallee 10413623 BerlinGermany

    www.siemens.com/energy

    Subject to change without noticeOrder No. E50001-K1511-A421-A1-7600Printed in GermanyDispo 31601KG 03.08 1.0 36 En103063 6101/6519

    The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.The required features should therefore be specified in each individual case at the time of closing the contract.

    R

    -

    H

    G

    1

    1

    -

    1

    8

    2

    .

    t

    i

    f

    If not stated otherwise on the individual pages of this catalog,we reserve the right to include modifications, especially regardingthe stated values, dimensions and weights.Drawings are not binding. All product designations used aretrademarks or product names of Siemens AG or other suppliers.If not stated otherwise, all dimensions in this catalog are givenin mm.

    Responsible for

    Technical contents: General editing:Siemens AG, Dept. PTD M C PPM Siemens AG, Dept. PTD CC MBerlin Erlangen