short-circuit current analysis for dfig wind farm

15
energies Article Short-Circuit Current Analysis for DFIG Wind Farm Considering the Action of a Crowbar Yan Hong Yuan ID and Feng Wu * College of Energy and Electrical Engineering, Hohai University, Nanjing 211100, China; [email protected] or [email protected] * Correspondence: [email protected]; Tel.: +1-530-518-7449 Received: 4 January 2018; Accepted: 7 February 2018; Published: 12 February 2018 Abstract: With the increasing capacity of wind farms integrated into the power grid, the short-circuit current analysis for wind farms becomes more and more important. Since the wind turbine is usually integrated into the power grid via power electronic devices, the “crowbar” is installed in the wind turbine to protect the power electronic devices and to improve the fault ride through capability. The impact of the crowbar has to be considered during the short-circuit current analysis for the wind farm. In order to fully analyze the short-circuit current characteristics of a wind farm, the short-circuit currents for a doubly-fed induction generator (DFIG) wind turbine under symmetrical and asymmetrical faults considering the crowbar action characteristic are derived firstly. Then the action situation of the crowbar of a DFIG wind turbine is studied and the action area curve is obtained. Taking the crowbar action, or not, as the grouping criterion, wind turbines in the wind farm are divided into two groups, and the wind farm is aggregated into two equivalent wind turbines. Using the equivalent model, the short-circuit current of a wind farm can be calculated accurately. Finally, simulations are performed in MATLAB/Simulink which is the commercial math software produced by the MathWorks company in Natick, Massachusetts, the United States to verify the proposed short-circuit current calculation method for the DFIG wind farm. Keywords: crowbar; doubly-fed induction generator; short-circuit current; wind farm; wind turbine 1. Introduction With the increasing capacity of wind farms (WF) integrated into the power grid, the impact of WFs on the operation of power grid becomes more and more significant [1]. The short-circuit current of the WF under the system fault is quite different from that of the traditional power plant. The result of the fault analysis and the evaluation of protection action characteristics are affected by imprecise short-circuit current calculations, and it is of great significance to the electric design of the WF. Additionally, a “crowbar” is usually installed in the wind turbine (WT) with a doubly-fed induction generator (DFIG) to increase the fault ride-through capability by limiting the short-circuit current flowing through the power electronic devices under the system fault [24]. Hence, the effect of the crowbar has to be considered in the short-circuit current analysis for the power grid integrated with large-scale WFs. Previously, a great deal of studies have been carried out to study the short-circuit current of WTs with DFIG. The impact factors on the short-circuit current was investigated in [5,6]. The effect of the low-voltage ride-through control strategy on the short-circuit current of WTs with DFIG was analyzed in [7,8]. The short-circuit current of the WT with DFIG protected by a crowbar was also studied in [9,10]. In [9], the sudden short-circuit process was regarded as a superimposition of the steady state operation and the transient state operation provoked by the reverse voltage, stator three-phase short-circuit current expression was obtained by carrying out the Laplace transformation and the Energies 2018, 11, 425; doi:10.3390/en11020425 www.mdpi.com/journal/energies

Upload: others

Post on 15-Nov-2021

14 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Short-Circuit Current Analysis for DFIG Wind Farm

energies

Article

Short-Circuit Current Analysis for DFIG Wind FarmConsidering the Action of a Crowbar

Yan Hong Yuan ID and Feng Wu *

College of Energy and Electrical Engineering, Hohai University, Nanjing 211100, China;[email protected] or [email protected]* Correspondence: [email protected]; Tel.: +1-530-518-7449

Received: 4 January 2018; Accepted: 7 February 2018; Published: 12 February 2018

Abstract: With the increasing capacity of wind farms integrated into the power grid, the short-circuitcurrent analysis for wind farms becomes more and more important. Since the wind turbine isusually integrated into the power grid via power electronic devices, the “crowbar” is installed inthe wind turbine to protect the power electronic devices and to improve the fault ride throughcapability. The impact of the crowbar has to be considered during the short-circuit current analysisfor the wind farm. In order to fully analyze the short-circuit current characteristics of a windfarm, the short-circuit currents for a doubly-fed induction generator (DFIG) wind turbine undersymmetrical and asymmetrical faults considering the crowbar action characteristic are derived firstly.Then the action situation of the crowbar of a DFIG wind turbine is studied and the action area curve isobtained. Taking the crowbar action, or not, as the grouping criterion, wind turbines in the wind farmare divided into two groups, and the wind farm is aggregated into two equivalent wind turbines.Using the equivalent model, the short-circuit current of a wind farm can be calculated accurately.Finally, simulations are performed in MATLAB/Simulink which is the commercial math softwareproduced by the MathWorks company in Natick, Massachusetts, the United States to verify theproposed short-circuit current calculation method for the DFIG wind farm.

Keywords: crowbar; doubly-fed induction generator; short-circuit current; wind farm; wind turbine

1. Introduction

With the increasing capacity of wind farms (WF) integrated into the power grid, the impactof WFs on the operation of power grid becomes more and more significant [1]. The short-circuitcurrent of the WF under the system fault is quite different from that of the traditional power plant.The result of the fault analysis and the evaluation of protection action characteristics are affectedby imprecise short-circuit current calculations, and it is of great significance to the electric design ofthe WF. Additionally, a “crowbar” is usually installed in the wind turbine (WT) with a doubly-fedinduction generator (DFIG) to increase the fault ride-through capability by limiting the short-circuitcurrent flowing through the power electronic devices under the system fault [2–4]. Hence, the effect ofthe crowbar has to be considered in the short-circuit current analysis for the power grid integratedwith large-scale WFs.

Previously, a great deal of studies have been carried out to study the short-circuit current of WTswith DFIG. The impact factors on the short-circuit current was investigated in [5,6]. The effect of thelow-voltage ride-through control strategy on the short-circuit current of WTs with DFIG was analyzedin [7,8]. The short-circuit current of the WT with DFIG protected by a crowbar was also studiedin [9,10]. In [9], the sudden short-circuit process was regarded as a superimposition of the steadystate operation and the transient state operation provoked by the reverse voltage, stator three-phaseshort-circuit current expression was obtained by carrying out the Laplace transformation and the

Energies 2018, 11, 425; doi:10.3390/en11020425 www.mdpi.com/journal/energies

Page 2: Short-Circuit Current Analysis for DFIG Wind Farm

Energies 2018, 11, 425 2 of 15

inverse transformation to the state space equation. The studies mentioned above mainly focused onthe short-circuit current of a single WT with DFIG. Moreover, because the WF usually consists ofhundreds of WTs, the short-circuit current analysis of the WF is more efficient for the operation ofthe power grid, but there are fewer studies on it. A simple DFIG WF equivalent model, which can beused to quantify a WF’s short-circuit current contributions to the grid, was presented in [11], and theamplitude range of short-circuit current supplied by the WF was determined by analyzing the shortcircuit behavior of a DFIG with a crowbar. In [12], the WF was also equivalent to a single WT withDFIG to study the short-circuit current of the WF, where the effect of the crowbar was not considered.However, when the system fault happens, the actions of the crowbars in a WF are very complicated.For example, under a system fault, some of the crowbars would be triggered, while the others wouldnot. In this condition, the detailed actions of the crowbars have to be discussed before the short-circuitcurrent analysis for the WF.

In this paper, a method for the short-circuit current calculation for a DFIG WF under constantpower factor control is proposed. The short-circuit current for the WT with DFIG under symmetricaland asymmetrical grid faults are presented firstly, where the action of Crowbar can be considered.The curve for action area of Crowbar is obtained, based on which the action of each crowbar of the WTin the WF can be decided using the terminal voltage and the input wind speed. Taking the crowbaraction, or not, as the clustering criterion, the WTs in the WF are aggregated into two WTs with DFIG.Using the two-machine equivalent model, the short-circuit current of the WF is calculated. A WFconsisting of 36 WTs which has considered the wake effect and is close to the actual WF is performedin MATLAB/Similink, which is the commercial math software produced by the MathWorks companyin Natick, Massachusetts, the United States and approximates the real-time operating conditions.A comparison is made between the calculated and the simulated short-circuit current of the WF undersymmetrical and asymmetrical fault, respectively. The effectiveness of the proposed short-circuitcurrent calculation method for a DFIG WF is evaluated by the case studies.

2. Short-Circuit Current of WT with DFIG Considering the Action of Crowbar

2.1. Model of WT with DFIG Equipped with a Crowbar

The configuration of the WT with DFIG equipped with a crowbar under constant power factorcontrol is shown in Figure 1.

Energies 2018, 11, x FOR PEER REVIEW 2 of 16

three-phase short-circuit current expression was obtained by carrying out the Laplace

transformation and the inverse transformation to the state space equation. The studies mentioned

above mainly focused on the short-circuit current of a single WT with DFIG. Moreover, because the

WF usually consists of hundreds of WTs, the short-circuit current analysis of the WF is more efficient

for the operation of the power grid, but there are fewer studies on it. A simple DFIG WF equivalent

model, which can be used to quantify a WF’s short-circuit current contributions to the grid, was

presented in [11], and the amplitude range of short-circuit current supplied by the WF was

determined by analyzing the short circuit behavior of a DFIG with a crowbar. In [12], the WF was

also equivalent to a single WT with DFIG to study the short-circuit current of the WF, where the

effect of the crowbar was not considered. However, when the system fault happens, the actions of

the crowbars in a WF are very complicated. For example, under a system fault, some of the crowbars

would be triggered, while the others would not. In this condition, the detailed actions of the

crowbars have to be discussed before the short-circuit current analysis for the WF.

In this paper, a method for the short-circuit current calculation for a DFIG WF under constant

power factor control is proposed. The short-circuit current for the WT with DFIG under symmetrical

and asymmetrical grid faults are presented firstly, where the action of Crowbar can be considered.

The curve for action area of Crowbar is obtained, based on which the action of each crowbar of the

WT in the WF can be decided using the terminal voltage and the input wind speed. Taking the

crowbar action, or not, as the clustering criterion, the WTs in the WF are aggregated into two WTs with

DFIG. Using the two-machine equivalent model, the short-circuit current of the WF is calculated. A

WF consisting of 36 WTs which has considered the wake effect and is close to the actual WF is

performed in MATLAB/Similink, which is the commercial math software produced by the

MathWorks company in Natick, Massachusetts, the United States and approximates the real-time

operating conditions. A comparison is made between the calculated and the simulated short-circuit

current of the WF under symmetrical and asymmetrical fault, respectively. The effectiveness of the

proposed short-circuit current calculation method for a DFIG WF is evaluated by the case studies.

2. Short-Circuit Current of WT with DFIG Considering the Action of Crowbar

2.1. Model of WT with DFIG Equipped with a Crowbar

The configuration of the WT with DFIG equipped with a crowbar under constant power factor

control is shown in Figure 1.

gearbox

power

grid

rotor-side

converter

grid-side

converter

DFIG

Crowbar

Figure 1. Configuration of wind turbine (WT) with doubly-fed induction generator (DFIG) equipped

with a crowbar.

Currently, the commercial WT with DFIG usually adopts the three-phase three-wire system

where there is no zero-sequence component in the short-circuit current. Therefore, according to the

instantaneous symmetrical component theory, the stator and rotor voltage, current and flux vectors

can be decomposed into the corresponding positive and negative sequence vectors in the positive

and reverse rotating synchronous coordinate systems. They are called positive and negative

sequence vectors in the following part of this paper, respectively, and they can be written as:

s sj t j tP N P Ne e

f f f f f , (1)

Figure 1. Configuration of wind turbine (WT) with doubly-fed induction generator (DFIG) equippedwith a crowbar.

Currently, the commercial WT with DFIG usually adopts the three-phase three-wire systemwhere there is no zero-sequence component in the short-circuit current. Therefore, according to theinstantaneous symmetrical component theory, the stator and rotor voltage, current and flux vectorscan be decomposed into the corresponding positive and negative sequence vectors in the positiveand reverse rotating synchronous coordinate systems. They are called positive and negative sequencevectors in the following part of this paper, respectively, and they can be written as:

f = fP + fN = fP+ejωst + fN

−e−jωst, (1)

Page 3: Short-Circuit Current Analysis for DFIG Wind Farm

Energies 2018, 11, 425 3 of 15

where f represents voltage, current or flux vector; the subscript “+” and “−” represent the forwardand reverse synchronous rotating coordinate systems, respectively; the superscript P and N representthe positive and negative sequence components, respectively.

The positive and negative sequence models of WT with DFIG are given by:UP

s,+ = RsIPs,+ +

dΨPs,+

dt + jωsΨPs,+

UPr,+ = RrIP

r,+ +dΨP

r,+dt + j(ωs −ωr)ΨP

r,+ΨP

s,+ = LsIPs,+ + LmIP

s,+ΨP

r,+ = LrIPr,+ + LmIP

r,+

(2)

UN

s,− = RsINs,− +

dΨNs,−

dt − jωsΨNs,−

UNr,− = RrIN

r,− +dΨN

r,−dt − j(ωs + ωr)ΨN

r,−ΨN

s,− = LsINs,− + LmIN

r,−ΨN

r,− = LrINr,− + LmIN

s,−

(3)

where Us, Ur, Is, Ir, Ψs, Ψr are the voltage, current, and flux of the stator and rotor, respectively; Rs,Rr, Ls, Lr are the resistance and inductance of the stator and rotor, respectively; Lm is the mutualinductance of the generator; and ωs and ωr are the electrical angular velocities of the stator androtor, respectively.

The negative sequence component is zero when the system is symmetrical.When the power grid operates normally or the terminal voltage of WT with DFIG equipped with

the crowbar drops slightly, the crowbar will not be triggered and the WT with DFIG is excited by therotor side converter, which is the just like the WT with DFIG equipped without a crowbar. Whenthe power grid fault happens and the terminal voltage drops deeply, the stator and rotor currentsincrease quickly with the decrease of the terminal voltage. Then, the crowbar is activated to preventthe converter from over-current shock and consumes the unbalanced energy in the WT after the systemfault, which improves the fault ride through capability. Hence, the crowbar plays a very importantrole in the WT under the system fault, and it has to be included in the model of the WT with DFIG forthe short-circuit current analysis.

2.2. Short-Circuit Current of WT with DFIG When the Crowbar Acts

If the terminal voltage falls deeply, the crowbar will be triggered. According to Equation (1),the stator and rotor currents can be decomposed into positive and negative sequence vectors in thepositive and reverse rotating coordinate systems which can be written as:

Is = IPs,+ ejωst + IN

s,−e−jωst

Ir = IPr,+ ejωst + IN

r,−e−jωst (4)

Therefore, the positive and negative sequence vectors of stator and rotor currents need to becalculated firstly. According to the positive and negative sequence flux in Equations (2) and (3),the relations between stator, rotor currents and fluxes can be obtained as follows:

IPs,+ = Lr

Ls Lr−L2m

ΨPs,+ − Lm

Ls Lr−L2m

ΨPr,+

IPr,+ = − Lm

Ls Lr−L2m

ΨPs,+ + Ls

Ls Lr−L2m

ΨPr,+

INs,− = Lr

Ls Lr−L2m

ΨNs,− − Lm

Ls Lr−L2m

ΨNr,−

INr,− = − Lm

Ls Lr−L2m

ΨNs,− + Ls

Ls Lr−L2m

ΨNr,−

(5)

After the action of the crowbar, the rotor is shorted by the crowbar resistance, and the rotorside resistance is changed to R′r = Rr + Rcb, where Rcb is the crowbar resistance. According to

Page 4: Short-Circuit Current Analysis for DFIG Wind Farm

Energies 2018, 11, 425 4 of 15

Equations (2), (3), and (5), and neglecting the stator resistance, the differential equations of stator androtor flux can be written as:

dΨPs,+

dt + jωsΨPs,+ = UP

s,+dΨN

s,−dt − jωsΨN

s,− = UNs,−

dΨPr,+

dt +(

LsR′rLs Lr−L2

m+ j(ωs −ωr)

)ΨP

r,+ =LmR′rΨP

s,+Ls Lr−L2

mdΨN

r,−dt +

(LsR′r

Ls Lr−L2m− j(ωs + ωr)

)ΨN

r,− =LmR′rΨN

s,−Ls Lr−L2

m

(6)

When the power grid operates under normal condition, the stator flux is constant and the statorvoltage equals to 1 pu. The initial values of the positive and negative sequence components can beobtained as follows:

IPs,+(0) = Is(0)

ΨPs,+(0) = Ψs(0)

ΨPr,+(0) =

LrLm

ΨPs,+(0)−

Ls Lr−L2m

LmIP

s,+(0)IP

r,+(0) = − LmLs Lr−L2

mΨP

s,+(0) +Ls

Ls Lr−L2m

ΨPr,+(0)

ΨNs,−(0) = 0

ΨNr,−(0) = 0

(7)

Substituting Equation (7) into Equations (6), the differential equations can be solved:

ΨPs,+ =

UPs,+

jωs+

(Usjωs− UP

s,+jωs

)e−(jωst+ t

τs )

ΨNs,− = −UN

s,−jωs

+UN

s,−jωs

e−(−jωst+ tτs )

ΨPr,+ =

A1UPs,+

jωs+ B1

(Usjωs− UP

s,+jωs

)e−(jωst+ t

τs ) + C1e−(jωst+jωrt+ tτr )

ΨNr,− = −A2

UNs,−

jωs+ B2

UNs,−

jωse−(−jωst+ t

τs ) + C2ejωst+jωrt− tτr ,

(8)

where τs =(

Ls − L2m/Lr

)/Rs is the time constant of stator, τr =

(Lr − L2

m/Ls)/R′r is

the time constant of rotor, and A1 = LmR′r(jωs+jωr+1/τr)(Ls Lr−L2

m), B1 = LmR′r

(1/τr−1/τs−jωr)(Ls Lr−L2m)

,

C1 = ΨPr.+(0) −

UPr.+(0)

jωs+jωr+1/τr− A1UP

s,+jωs

− B1(Us−UPs,+)

jωs, A2 = − LmR′r

(1/τr−jωs−jωr)(Ls Lr−L2m)

e−jωst,

B2 = LmR′r(1/τr−1/τs−jωr)(Ls Lr−L2

m), and C2 =

A2UNs,−

jωs− B2UN

s,−jωs

.

When the crowbar is triggered, the stator and rotor currents of WT with DFIG can be obtainedby Equations (4), (5), and (8). If the fault is symmetrical, the negative sequence component is zero.The stator and rotor currents can be converted into a three-phase stationary coordinate system throughcoordinate transformation.

2.3. Short-Circuit Current of WT with DFIG When Crowbar Does Not Act

If the terminal voltage falls slightly, the crowbar will not be triggered and the rotor voltage willnot be zero. According to the stator flux in Equations (2) and (3), the positive and negative sequencevectors of stator current can be written as: IP

s,+ =ΨP

s,+Ls− LmIP

r,+Ls

INs,− =

ΨNs,−Ls− LmIN

r,−Ls

.(9)

As shown in Equation (9), the short-circuit current is mainly determined by the stator flux androtor current.

Page 5: Short-Circuit Current Analysis for DFIG Wind Farm

Energies 2018, 11, 425 5 of 15

Since the action of the crowbar has no effect on the stator flux, the stator flux can be written as inaccordance with Equation (8):

ΨPs,+ =

UPs,+

jωs+

(Usjωs− UP

s,+jωs

)e−(jωst+ t

τs )

ΨNs,− = −UN

s,−jωs

+UN

s,−jωs

e−(−jωst+ tτs ).

(10)

During the grid fault, the rotor side converter can keep track of the reference value very well ifthe controller’s closed-loop bandwidth is large enough. The response of the converter is very fast,hence, if the rotor side converter control strategy is constant power factor control, the rotor current canbe approximated to the reference value [13]:

Ir = Ir,re f . (11)

According to Equations (4) and (9)–(11), the stator and rotor currents of WT with DFIG canbe obtained when the crowbar is not triggered. If the fault is symmetrical, the negative sequencecomponent is zero.

2.4. Influence of Crowbar on Short-Circuit Current of WT

Two simulation systems for WTs with DFIG equipped with and without a crowbar are built inMATLAB/Simulink which is the commercial math software produced by the MathWorks company inNatick, Massachusetts, the United States as shown in Figure 1, respectively. The parameters of the WTare listed in Table 1.

Table 1. Parameters of wind turbine (WT) with doubly-fed induction generator (DFIG).

Parameters Values

rated power/MW 1.5rated voltage/V 575

system frequency/HZ 60stator resistance/p.u. 0.023

stator inductance/p.u. 0.18rotor resistance/p.u. 0.016

rotor inductance/p.u. 0.16mutual inductance/p.u. 2.9

rotor speed/p.u. 1.2

The crowbar resistance is 30 ∗ Rr. The wind speed flowing into the WT is 11 m/s. A system faultis applied at the terminal of the WF via a short resistance at t = 0, and the terminal voltage drops to0.5 pu. The short-circuit currents of phase A of these two simulation systems are shown in Figure 2.

From Figure 2, it can be seen that the short-circuit current of the WT equipped with a crowbar isdifferent from that of the WT without a crowbar. Since the terminal voltage drops deeply to 0.5 pu,with a crowbar, the converter can be prevented from over-current shock and the unbalanced energycan be consumed by the crowbar in the WT. However, without a crowbar, the converter may faceover-current shock and the unbalanced energy will affect the power grid. Their impact currents arealso listed in Table 2.

Page 6: Short-Circuit Current Analysis for DFIG Wind Farm

Energies 2018, 11, 425 6 of 15

Energies 2018, 11, x FOR PEER REVIEW 6 of 16

Table 1. Parameters of wind turbine (WT) with doubly-fed induction generator (DFIG).

Parameters Values

rated power/MW 1.5

rated voltage/V 575

system frequency/HZ 60

stator resistance/p.u. 0.023

stator inductance/p.u. 0.18

rotor resistance/p.u. 0.016

rotor inductance/p.u. 0.16

mutual inductance/p.u. 2.9

rotor speed/p.u. 1.2

The crowbar resistance is 30*Rr . The wind speed flowing into the WT is 11 m/s. A system fault

is applied at the terminal of the WF via a short resistance at t = 0, and the terminal voltage drops to

0.5 pu. The short-circuit currents of phase A of these two simulation systems are shown in Figure 2.

Figure 2. Short-circuit currents of WTs equipped with a crowbar and without a crowbar.

From Figure 2, it can be seen that the short-circuit current of the WT equipped with a crowbar is

different from that of the WT without a crowbar. Since the terminal voltage drops deeply to 0.5 pu,

with a crowbar, the converter can be prevented from over-current shock and the unbalanced energy

can be consumed by the crowbar in the WT. However, without a crowbar, the converter may face

over-current shock and the unbalanced energy will affect the power grid. Their impact currents are

also listed in Table 2.

Table 2. Impact currents of WTs equipped with and without a crowbar.

WT with Crowbar/pu WT without Crowbar/pu Absolute Error/pu Relative Error/%

Impact current 2.268 2.505 0.237 10.4

From Table 2, it can be seen that the difference of the impact current is larger than 10%, hence,

the effect of the crowbar has to be considered in the short-circuit current analysis.

3. Short-Circuit Current of a DFIG WF Considering Crowbar Operation Characteristics

3.1. Curve for the Action Area of the Crowbar

In a WF, the time-lag effect and wake effect lead to the different input wind speeds flowing into

each WT because of their different locations. Since the WT in the WF operates under different

conditions, its crowbar would have different actions under the system fault. Especially when the

Figure 2. Short-circuit currents of WTs equipped with a crowbar and without a crowbar.

Table 2. Impact currents of WTs equipped with and without a crowbar.

WT with Crowbar/pu WT without Crowbar/pu Absolute Error/pu Relative Error/%

Impact current 2.268 2.505 0.237 10.4

From Table 2, it can be seen that the difference of the impact current is larger than 10%, hence,the effect of the crowbar has to be considered in the short-circuit current analysis.

3. Short-Circuit Current of a DFIG WF Considering Crowbar Operation Characteristics

3.1. Curve for the Action Area of the Crowbar

In a WF, the time-lag effect and wake effect lead to the different input wind speeds flowinginto each WT because of their different locations. Since the WT in the WF operates under differentconditions, its crowbar would have different actions under the system fault. Especially when thesystem fault is not very severe, only part of the crowbars in the WF would be activated, while theothers would not. At this scenario, if the WF is aggregated into one equivalent machine to calculatethe short-circuit current, the errors will be significant.

Therefore, it is necessary to decide the action condition of the crowbar in the WF before thecalculation of the short-circuit current. The crowbar is triggered when the rotor current is greater thanthe current limitation. However, it is difficult to collect the instantaneous rotor current of each WT inthe real WF. It has to be pointed out that the action of the crowbar has a strong relationship with theinput wind speed and the terminal voltage drop [14].

The critical curve of the crowbar action for a single WT under different wind speeds and voltagedrops is drawn by the following steps, as shown in Figure 3:

Step 1: Input the cut-in wind speed to the WT with DFIG, and it remains constant.Step 2: Apply a system fault at the terminal of the WF via a short resistance at t = 0, and the short

resistance is set to 0.Step 3: Simulate the dynamics of the WT.Step 4: Check the status of the crowbar. If the crowbar is triggered, increase the short resistance

by 0.001 Ω and go to step 3; otherwise, go to step 5.Step 5: Write down the current wind speed and the critical terminal voltage.Step 6: If the current wind speed is smaller than the cut-out speed, increase the wind speed by 0.5

m/s and go to step 2; otherwise, go to step 7.Step 7: Stop and draw the curve for the action area of the crowbar using the wind speeds and

their corresponding critical terminal voltages.

Page 7: Short-Circuit Current Analysis for DFIG Wind Farm

Energies 2018, 11, 425 7 of 15

Energies 2018, 11, x FOR PEER REVIEW 7 of 16

system fault is not very severe, only part of the crowbars in the WF would be activated, while the

others would not. At this scenario, if the WF is aggregated into one equivalent machine to calculate

the short-circuit current, the errors will be significant.

Therefore, it is necessary to decide the action condition of the crowbar in the WF before the

calculation of the short-circuit current. The crowbar is triggered when the rotor current is greater

than the current limitation. However, it is difficult to collect the instantaneous rotor current of each

WT in the real WF. It has to be pointed out that the action of the crowbar has a strong relationship

with the input wind speed and the terminal voltage drop [14].

The critical curve of the crowbar action for a single WT under different wind speeds and

voltage drops is drawn by the following steps, as shown in Figure 3:

Step 1: Input the cut-in wind speed to the WT with DFIG, and it remains constant.

Step 2: Apply a system fault at the terminal of the WF via a short resistance at t = 0, and the short

resistance is set to 0.

Step 3: Simulate the dynamics of the WT.

Step 4: Check the status of the crowbar. If the crowbar is triggered, increase the short resistance

by 0.001 Ω and go to step 3; otherwise, go to step 5.

Step 5: Write down the current wind speed and the critical terminal voltage.

Step 6: If the current wind speed is smaller than the cut-out speed, increase the wind speed by

0.5 m/s and go to step 2; otherwise, go to step 7.

Step 7: Stop and draw the curve for the action area of the crowbar using the wind speeds and

their corresponding critical terminal voltages.

Begin

Step 1: Input the cut-in wind speed to the WT with DFIG, and remains constant.

Step 2: Apply a system fault at the terminal of the WF via a short resistance at t=0, and the short resistance is set to 0.

Step 3: Simulate the dynamics of the WT.

Increase the short resistance

by

0.001Ω.

Step 4: Is the Crowbar triggered?

Step 5 : Write down the current wind speed and the critical terminal voltage.

Step 6:Is the current wind speed

smaller than the cut-out speed?

Increase

the wind

speed

by

0.5m/s.

S tep 7 :Stop and Draw the curve for action area of Crowbar using the wind speeds and their corresponding critical terminal voltages.

Yes

No

No

Yes

End.

Figure 3. Flowchart drawing curve for the action area of the crowbar.

Figure 3. Flowchart drawing curve for the action area of the crowbar.

Following the above steps, the critical curve of the crowbar action for the WT with DFIG usedin Section 2 is drawn and shown in Figure 4. As the rated wind speed of the WT is 11 m/s, the pitchangle controller of the WT will abandon the wind when the input wind speed exceeds the rated windspeed, which results the actual effective wind speed is equivalent to or slightly higher than 11 m/s.Therefore, the curve tends to be flat after the inflection point (11, 0.69).

The input wind speed of each WT can be measured and collected since each WT is equipped witha wind speed meter in the real WF. The terminal voltage of each WT is also measured and sent tothe control center of the WF. The input wind speed and the terminal voltage are used to look up theaction area curve. The crowbar would be triggered when the operation point is below the critical line,otherwise it would not be triggered.

If there is more than one type of WT in the DFIG WF, the corresponding curve for the action area of eachtype of crowbar is required. However, the same type of WTs are used in the construction of WFs in general.Other types of WTs may be added during the later expansion processes, but not too many. Therefore,the calculation of the curves will not be too large if there are different kinds of WTs in the DFIG WF.

Energies 2018, 11, x FOR PEER REVIEW 8 of 16

Following the above steps, the critical curve of the crowbar action for the WT with DFIG used in

Section 2 is drawn and shown in Figure 4. As the rated wind speed of the WT is 11 m/s, the pitch

angle controller of the WT will abandon the wind when the input wind speed exceeds the rated

wind speed, which results the actual effective wind speed is equivalent to or slightly higher than 11

m/s. Therefore, the curve tends to be flat after the inflection point (11, 0.69).

The input wind speed of each WT can be measured and collected since each WT is equipped

with a wind speed meter in the real WF. The terminal voltage of each WT is also measured and sent

to the control center of the WF. The input wind speed and the terminal voltage are used to look up

the action area curve. The crowbar would be triggered when the operation point is below the critical

line, otherwise it would not be triggered.

If there is more than one type of WT in the DFIG WF, the corresponding curve for the action

area of each type of crowbar is required. However, the same type of WTs are used in the

construction of WFs in general. Other types of WTs may be added during the later expansion

processes, but not too many. Therefore, the calculation of the curves will not be too large if there are

different kinds of WTs in the DFIG WF.

Figure 4. Curve for action area of the crowbar.

3.2. Short-Circuit Current Calculation of a DFIG WF

Firstly, the equivalent input wind speed is obtained by weighted aggregation of wind speed

cubes. Secondly, the method of transforming the collection network in a WF proposed by [15] is

applied to parallel the collection network, so as to achieve the aggregated equivalence of DFIGs at

any location. Thirdly, the action of each crowbar in a DFIG WF is decided by the method proposed

in Section 3.1. Then, using the crowbar action as a clustering index, the DFIG WF is aggregated to a

two-machine model, as shown in Figure 5, where one equivalent machine represents WTs whose

crowbars are triggered and the other one represents the WTs whose crowbars are not triggered.

Meanwhile, parameters of each equivalent machine are aggregated by the capacity weighted

method. According to (4)–(5) and (8)–(11), the short-circuit currents of the two equivalent WTs with

DFIG can finally be obtained, and the vector sum of them is the short-circuit current of the WF.

Figure 4. Curve for action area of the crowbar.

Page 8: Short-Circuit Current Analysis for DFIG Wind Farm

Energies 2018, 11, 425 8 of 15

3.2. Short-Circuit Current Calculation of a DFIG WF

Firstly, the equivalent input wind speed is obtained by weighted aggregation of wind speedcubes. Secondly, the method of transforming the collection network in a WF proposed by [15] isapplied to parallel the collection network, so as to achieve the aggregated equivalence of DFIGs atany location. Thirdly, the action of each crowbar in a DFIG WF is decided by the method proposedin Section 3.1. Then, using the crowbar action as a clustering index, the DFIG WF is aggregated toa two-machine model, as shown in Figure 5, where one equivalent machine represents WTs whosecrowbars are triggered and the other one represents the WTs whose crowbars are not triggered.Meanwhile, parameters of each equivalent machine are aggregated by the capacity weighted method.According to (4)–(5) and (8)–(11), the short-circuit currents of the two equivalent WTs with DFIG canfinally be obtained, and the vector sum of them is the short-circuit current of the WF.Energies 2018, 11, x FOR PEER REVIEW 9 of 16

PCC

T2

T1 Equivalent DFIG1

Equivalent DFIG2

Figure 5. Equivalent model of DFIG WF (wind farm).

4. Simulation Examples

4.1. Crowbar Actions Simulation

A WF consisting of 36 WTs is built in MATLAB/Simulink which is the commercial math

software produced by the MathWorks company in Natick, Massachusetts, the United States, as

shown in Figure 6. The parameters of each WT with DFIG are listed in Table 1. Considering the wake

effect, the wind speeds flowing into the WT in the WF are listed in Table 3.

PCC

15.7kV/220kVinput wind

Figure 6. Configuration of the DFIG WF.

Table 3. Wind speed distribution in the wind farm (WF).

Number Wind Speed (m/s)

Column 1 Column 2 Column 3 Column 4 Column 5 Column 6

line 1 12 11.8 11.6 11.4 11.2 11.0

line 2 11.8 11.6 11.4 11.2 11.0 10.8

line 3 11.6 11.4 11.2 11.0 10.8 10.6

line 4 11.4 11.2 11.0 10.8 10.6 10.4

line 5 11.2 11.0 10.8 10.6 10.4 10.2

line 6 11.0 10.8 10.6 10.4 10.2 10.0

Applying a system fault at the terminal of the DFIG WF via a short resistance at t = 0, the voltage

drops to 0.68 pu. According to the simulation results, the actions of the crowbars in the WF are shown

in Table 4. The crowbars that were triggered are represented by “+”, while the others are represented

by “−”. From Table 4, it can be seen that 22 crowbars are triggered and the other 14 crowbars are not.

Zeq1

Zeq2

Figure 5. Equivalent model of DFIG WF (wind farm).

4. Simulation Examples

4.1. Crowbar Actions Simulation

A WF consisting of 36 WTs is built in MATLAB/Simulink which is the commercial math softwareproduced by the MathWorks company in Natick, Massachusetts, the United States, as shown inFigure 6. The parameters of each WT with DFIG are listed in Table 1. Considering the wake effect,the wind speeds flowing into the WT in the WF are listed in Table 3.

Energies 2018, 11, x FOR PEER REVIEW 9 of 16

PCC

T2

T1 Equivalent DFIG1

Equivalent DFIG2

Figure 5. Equivalent model of DFIG WF (wind farm).

4. Simulation Examples

4.1. Crowbar Actions Simulation

A WF consisting of 36 WTs is built in MATLAB/Simulink which is the commercial math

software produced by the MathWorks company in Natick, Massachusetts, the United States, as

shown in Figure 6. The parameters of each WT with DFIG are listed in Table 1. Considering the wake

effect, the wind speeds flowing into the WT in the WF are listed in Table 3.

PCC

15.7kV/220kVinput wind

Figure 6. Configuration of the DFIG WF.

Table 3. Wind speed distribution in the wind farm (WF).

Number Wind Speed (m/s)

Column 1 Column 2 Column 3 Column 4 Column 5 Column 6

line 1 12 11.8 11.6 11.4 11.2 11.0

line 2 11.8 11.6 11.4 11.2 11.0 10.8

line 3 11.6 11.4 11.2 11.0 10.8 10.6

line 4 11.4 11.2 11.0 10.8 10.6 10.4

line 5 11.2 11.0 10.8 10.6 10.4 10.2

line 6 11.0 10.8 10.6 10.4 10.2 10.0

Applying a system fault at the terminal of the DFIG WF via a short resistance at t = 0, the voltage

drops to 0.68 pu. According to the simulation results, the actions of the crowbars in the WF are shown

in Table 4. The crowbars that were triggered are represented by “+”, while the others are represented

by “−”. From Table 4, it can be seen that 22 crowbars are triggered and the other 14 crowbars are not.

Zeq1

Zeq2

Figure 6. Configuration of the DFIG WF.

Page 9: Short-Circuit Current Analysis for DFIG Wind Farm

Energies 2018, 11, 425 9 of 15

Table 3. Wind speed distribution in the wind farm (WF).

NumberWind Speed (m/s)

Column 1 Column 2 Column 3 Column 4 Column 5 Column 6

line 1 12 11.8 11.6 11.4 11.2 11.0line 2 11.8 11.6 11.4 11.2 11.0 10.8line 3 11.6 11.4 11.2 11.0 10.8 10.6line 4 11.4 11.2 11.0 10.8 10.6 10.4line 5 11.2 11.0 10.8 10.6 10.4 10.2line 6 11.0 10.8 10.6 10.4 10.2 10.0

Applying a system fault at the terminal of the DFIG WF via a short resistance at t = 0, the voltagedrops to 0.68 pu. According to the simulation results, the actions of the crowbars in the WF are shownin Table 4. The crowbars that were triggered are represented by “+”, while the others are representedby “−”. From Table 4, it can be seen that 22 crowbars are triggered and the other 14 crowbars are not.

Table 4. Simulation results of crowbar actions.

NumberCrowbar Actions

Column 1 Column 2 Column 3 Column 4 Column 5 Column 6

line 1 + + + + + +line 2 + + + + + +line 3 + + + + + −line 4 + + + − − −line 5 + + − − − −line 6 − − − − − −

Using the curve for the action area of the crowbar, the crowbar action conditions for each WTin the WF can also be obtained and listed in Table 5. The result is that 22 crowbars are triggeredand the other 14 crowbars are not, which is very close to that obtained from simulation. In Table 5,three crowbars in WTs have different actions comparing to those in Table 4. It has to be pointed outthat the operation condition of these three WTs are very close to the critical curve. If the interval ofthe wind speed and terminal voltage is decreased further when the curve for the action area of thecrowbar is produced, the accuracy of the decision can be improved.

Table 5. Comparison results of crowbar actions.

NumberCrowbar Actions

Column 1 Column 2 Column 3 Column 4 Column 5 Column 6

line 1 + + + + + +line 2 + + + + + −line 3 + + + + − −line 4 + + + − − −line 5 + + − − − −line 6 + − − − − −

4.2. Asymmetrical Fault Simulation

Applying a phase-phase fault between phase A and phase B at the terminal of the WF via differentshort resistances at t = 0, the voltage drops to 0.2 pu, 0.68 pu, and 0.80 pu, respectively.

When the terminal voltage drops to 0.2 pu, all the crowbars in the WF are triggered; while, whenthe terminal voltage drops to 0.8 pu, all the crowbars are not triggered. In these conditions, the WFcan be equivalent to a single WT with crowbars and without crowbars, respectively, to calculate their

Page 10: Short-Circuit Current Analysis for DFIG Wind Farm

Energies 2018, 11, 425 10 of 15

short-circuit currents. The short-circuit currents are shown in Figure 7a,b, respectively. It can be seenthat the calculation values of the short-circuit current is consistent with those of the simulations.

According to Table 5, only some of the crowbars are triggered when the terminal voltage drops to0.68 pu. Therefore, the WF has to be aggregated to two equivalent WTs to calculate its short-circuitcurrent. The short-circuit currents are shown in Figure 7c. In addition, the WF is also equivalent toa single WT to calculate its short-circuit current and show the difference between these two calculationmethods. It can be seen that when the terminal voltage drops to 0.68 pu, the calculated short-circuitcurrent of the WF which is equivalent to two WTs is closer to the simulation results than that of theWF, which is equivalent to a single WT.Energies 2018, 11, x FOR PEER REVIEW 11 of 16

(a) Terminal voltage drops to 0.2 pu.

(b) Terminal voltage drops to 0.8 pu.

(c) Terminal voltage drops to 0.68 pu.

Figure 7. Comparison of the short-circuit current calculation values and simulation values for a

phase-phase (a and b) fault.

Comparisons of the calculated impact currents and simulated impact currents under different

voltage drops by an asymmetrical fault are shown in Table 6.

Table 6. Comparison of the impact currents under different voltage drops by an asymmetrical fault.

Terminal

Voltage/pu

Impact Current

Simulation Value/pu Calculation Value/pu Absolute Error/pu Relative Error/%

0.8 1.354 1.362 0.008 0.591

0.2 2.328 2.341 0.013 0.558

0.68 (2 WTs) 1.792 1.804 0.012 0.670

0.68 (1 WT) 1.418 1.890 0.098 5.469

From Table 6, it can be seen that the WF can be equivalent to a single WT to calculate its

short-circuit current when all the crowbars are triggered or not, since the error of impact current is

Figure 7. Comparison of the short-circuit current calculation values and simulation values fora phase-phase (a and b) fault.

Page 11: Short-Circuit Current Analysis for DFIG Wind Farm

Energies 2018, 11, 425 11 of 15

Comparisons of the calculated impact currents and simulated impact currents under differentvoltage drops by an asymmetrical fault are shown in Table 6.

Table 6. Comparison of the impact currents under different voltage drops by an asymmetrical fault.

Terminal Voltage/puImpact Current

Simulation Value/pu Calculation Value/pu Absolute Error/pu Relative Error/%

0.8 1.354 1.362 0.008 0.5910.2 2.328 2.341 0.013 0.558

0.68 (2 WTs) 1.792 1.804 0.012 0.6700.68 (1 WT) 1.418 1.890 0.098 5.469

From Table 6, it can be seen that the WF can be equivalent to a single WT to calculate itsshort-circuit current when all the crowbars are triggered or not, since the error of impact currentis very small. However, if only part of the crowbars are triggered, the error of impact current of the WF,which is equivalent to two WTs, is much smaller than that of the WF, which is equivalent to a singleWT. Precise short-circuit current calculations will help the result of the fault analysis and the evaluationof the protection action characteristic.

Based on calculations and simulation results, it can be concluded that this DFIG WF needs to beequivalent to two WTs to calculate its short-circuit current when the terminal voltage dip is between0.61 and 0.71. If not, it can be equivalent to a single WT.

4.3. Symmetrical Fault Simulation

Applying a three-phase fault at the terminal of the DFIG WF via a short resistance at t = 0,the voltage drops to 0.68 pu. The analysis process is the same as the asymmetrical fault, and the WF isequivalent to two WTs to calculate the short-circuit current. The comparison between the calculationvalues and simulation values of the short-circuit current of phase A is shown in Figure 8, and theimpact currents of them are shown in Table 7.

Table 7. Comparison of the impact currents under symmetrical fault.

Simulation Value/pu Calculation Value/pu Absolute Error/pu Relative Error/%

Impact current 2.323 2.340 0.017 0.732

Energies 2018, 11, x FOR PEER REVIEW 12 of 16

very small. However, if only part of the crowbars are triggered, the error of impact current of the

WF, which is equivalent to two WTs, is much smaller than that of the WF, which is equivalent to a

single WT. Precise short-circuit current calculations will help the result of the fault analysis and the

evaluation of the protection action characteristic.

Based on calculations and simulation results, it can be concluded that this DFIG WF needs to be

equivalent to two WTs to calculate its short-circuit current when the terminal voltage dip is between

0.61 and 0.71. If not, it can be equivalent to a single WT.

4.3. Symmetrical Fault Simulation

Applying a three-phase fault at the terminal of the DFIG WF via a short resistance at t = 0, the

voltage drops to 0.68 pu. The analysis process is the same as the asymmetrical fault, and the WF is

equivalent to two WTs to calculate the short-circuit current. The comparison between the calculation

values and simulation values of the short-circuit current of phase A is shown in Figure 8, and the

impact currents of them are shown in Table 7.

Table 7. Comparison of the impact currents under symmetrical fault.

Simulation Value/pu Calculation Value/pu Absolute Error/pu Relative Error/%

Impact current 2.323 2.340 0.017 0.732

Figure 8. Comparison of the short-circuit current calculation values and simulation values for a

three-phase fault.

From Figure 8 and Table 7, it can be seen that the calculation values of short-circuit current

under a symmetrical fault are also consistent with those of the simulation results.

4.4. Fault Simulation in Digsilent

A DFIG WF consisting of 64 WTs connected to the IEEE 39 bus system at BUS33 is performed in

Digsilent. The IEEE 39 bus system is shown in Figure 9. The parameters of each WT with DFIG are

listed in Table 8. Considering the wake effect, the wind speeds flowing into the WT in the WF are

listed in Table 9. The curve for action area of the crowbar is drawn in Figure 10.

Figure 8. Comparison of the short-circuit current calculation values and simulation values fora three-phase fault.

Page 12: Short-Circuit Current Analysis for DFIG Wind Farm

Energies 2018, 11, 425 12 of 15

From Figure 8 and Table 7, it can be seen that the calculation values of short-circuit current undera symmetrical fault are also consistent with those of the simulation results.

4.4. Fault Simulation in Digsilent

A DFIG WF consisting of 64 WTs connected to the IEEE 39 bus system at BUS33 is performedin Digsilent. The IEEE 39 bus system is shown in Figure 9. The parameters of each WT with DFIGare listed in Table 8. Considering the wake effect, the wind speeds flowing into the WT in the WF arelisted in Table 9. The curve for action area of the crowbar is drawn in Figure 10.Energies 2018, 11, x FOR PEER REVIEW 13 of 16

30

39

1

2

25

37

29

17

26

9

3

38

16

5

4

18

27

28

3624

35

22

21

20

34

23

19

33

10

11

13

14

15

831

126

32

7

DFIG WF

G G

G

G G G

G

G

G

Figure 9. IEEE 39 bus system.

Table 8. Parameters of WT with DFIG.

Parameters Values

Rated power/MW 2

Rated voltage/V 575

System frequency/HZ 60

Stator resistance/p.u. 0.01

Stator inductance/p.u. 0.1

Rotor resistance/p.u. 0.01

Rotor inductance/p.u. 0.1

Mutual inductance/p.u. 3.5

Rotor speed/p.u. 1.2

Table 9. Wind speed distribution in the WF.

Number Wind Speed (m/s)

Column 1 Column 2 Column 3 Column 4 Column 5 Column 6 Column 7 Column 8

line 1 12.4 12.2 12.0 11.8 11.6 11.4 11.2 11.0

line 2 12.2 12.0 11.8 11.6 11.4 11.2 11.0 10.8

line 3 12.0 11.8 11.6 11.4 11.2 11.0 10.8 10.6

line 4 11.8 11.6 11.4 11.2 11.0 10.8 10.6 10.4

line 5 11.6 11.4 11.2 11.0 10.8 10.6 10.4 10.2

line 6 11.4 11.2 11.0 10.8 10.6 10.4 10.2 10.0

line 7 11.2 11.0 10.8 10.6 10.4 10.2 10.0 9.8

line 8 11.0 10.8 10.6 10.4 10.2 10.0 9.8 9.6

Figure 9. IEEE 39 bus system.

Table 8. Parameters of WT with DFIG.

Parameters Values

Rated power/MW 2Rated voltage/V 575

System frequency/HZ 60Stator resistance/p.u. 0.01

Stator inductance/p.u. 0.1Rotor resistance/p.u. 0.01

Rotor inductance/p.u. 0.1Mutual inductance/p.u. 3.5

Rotor speed/p.u. 1.2

Table 9. Wind speed distribution in the WF.

NumberWind Speed (m/s)

Column 1 Column 2 Column 3 Column 4 Column 5 Column 6 Column 7 Column 8

line 1 12.4 12.2 12.0 11.8 11.6 11.4 11.2 11.0line 2 12.2 12.0 11.8 11.6 11.4 11.2 11.0 10.8line 3 12.0 11.8 11.6 11.4 11.2 11.0 10.8 10.6line 4 11.8 11.6 11.4 11.2 11.0 10.8 10.6 10.4line 5 11.6 11.4 11.2 11.0 10.8 10.6 10.4 10.2line 6 11.4 11.2 11.0 10.8 10.6 10.4 10.2 10.0line 7 11.2 11.0 10.8 10.6 10.4 10.2 10.0 9.8line 8 11.0 10.8 10.6 10.4 10.2 10.0 9.8 9.6

Page 13: Short-Circuit Current Analysis for DFIG Wind Farm

Energies 2018, 11, 425 13 of 15Energies 2018, 11, x FOR PEER REVIEW 14 of 16

Figure 10. Curve for action area of the crowbar.

Applying a phase-phase fault between phase A and phase B at the terminal of the DFIG WF via

a short resistance at t = 10 s, the voltage drops to 0.55 pu. Using the curve for the action area of the

crowbar in Figure 10, the result is that 66 crowbars are triggered and the other 15 crowbars are not,

and the WF is equivalent to two WTs to calculate the short-circuit current. The comparison between

the calculation values and simulation values of the short-circuit current is shown in Figure 11, and

the impact currents of them is shown in Table 10.

Figure 11. Comparison of the short-circuit current calculation values and simulation values for a

phase-phase (a and b) fault.

Table 10. Comparison of the impact currents under symmetrical fault.

Simulation Value/pu Calculation Value/pu Absolute Error/pu Relative Error/%

Impact current 3.308 3.413 0.105 3.174

From Figure 11 and Table 10, it can be seen that the calculation values of the short-circuit

current are consistent with those of the simulation results.

5. Conclusions

A short-circuit current calculation method for the WF has been proposed in this paper, which

has considered the action of a crowbar and is suitable under both symmetrical and asymmetrical

grid faults. The simulation is conducted in MATLAB/Simulink, which is the commercial math

software produced by the MathWorks company in Natick, Massachusetts, the United States and

approximates the real-time operating conditions. Based on the short-circuit current analysis of the

Figure 10. Curve for action area of the crowbar.

Applying a phase-phase fault between phase A and phase B at the terminal of the DFIG WFvia a short resistance at t = 10 s, the voltage drops to 0.55 pu. Using the curve for the action area of thecrowbar in Figure 10, the result is that 66 crowbars are triggered and the other 15 crowbars are not,and the WF is equivalent to two WTs to calculate the short-circuit current. The comparison betweenthe calculation values and simulation values of the short-circuit current is shown in Figure 11, and theimpact currents of them is shown in Table 10.

Energies 2018, 11, x FOR PEER REVIEW 14 of 16

Figure 10. Curve for action area of the crowbar.

Applying a phase-phase fault between phase A and phase B at the terminal of the DFIG WF via

a short resistance at t = 10 s, the voltage drops to 0.55 pu. Using the curve for the action area of the

crowbar in Figure 10, the result is that 66 crowbars are triggered and the other 15 crowbars are not,

and the WF is equivalent to two WTs to calculate the short-circuit current. The comparison between

the calculation values and simulation values of the short-circuit current is shown in Figure 11, and

the impact currents of them is shown in Table 10.

Figure 11. Comparison of the short-circuit current calculation values and simulation values for a

phase-phase (a and b) fault.

Table 10. Comparison of the impact currents under symmetrical fault.

Simulation Value/pu Calculation Value/pu Absolute Error/pu Relative Error/%

Impact current 3.308 3.413 0.105 3.174

From Figure 11 and Table 10, it can be seen that the calculation values of the short-circuit

current are consistent with those of the simulation results.

5. Conclusions

A short-circuit current calculation method for the WF has been proposed in this paper, which

has considered the action of a crowbar and is suitable under both symmetrical and asymmetrical

grid faults. The simulation is conducted in MATLAB/Simulink, which is the commercial math

software produced by the MathWorks company in Natick, Massachusetts, the United States and

approximates the real-time operating conditions. Based on the short-circuit current analysis of the

Figure 11. Comparison of the short-circuit current calculation values and simulation values fora phase-phase (a and b) fault.

Table 10. Comparison of the impact currents under symmetrical fault.

Simulation Value/pu Calculation Value/pu Absolute Error/pu Relative Error/%

Impact current 3.308 3.413 0.105 3.174

From Figure 11 and Table 10, it can be seen that the calculation values of the short-circuit currentare consistent with those of the simulation results.

5. Conclusions

A short-circuit current calculation method for the WF has been proposed in this paper, which hasconsidered the action of a crowbar and is suitable under both symmetrical and asymmetrical gridfaults. The simulation is conducted in MATLAB/Simulink, which is the commercial math software

Page 14: Short-Circuit Current Analysis for DFIG Wind Farm

Energies 2018, 11, 425 14 of 15

produced by the MathWorks company in Natick, Massachusetts, the United States and approximatesthe real-time operating conditions. Based on the short-circuit current analysis of the WT with andwithout the crowbar, the crowbar has a significant impact on the short-circuit current of the WT.The simulation results of a WF has demonstrated that only some of the crowbars were triggered undera certain grid fault. Hence, the action condition of the crowbar has been studied to obtain the curvefor the action area of the crowbar, which is very useful to decide whether the crowbars are triggered.A two-machine equivalent model has been proposed to calculate the short-circuit current of the WF.The calculated short-circuit currents have been compared with those simulated, and they are closewith each other. The proposed method is effective to calculate the short-circuit current of the DFIG WFeven when there are different kinds of WTs in the WF, which is meaningful for further analysis for theinfluence of the DFIG WF on the fault analysis, protection action characteristics, and electric design ofthe WF. Analysis on an actual WF with different kinds of WTs is one of our future research directions.

Acknowledgments: This work was supported in part by National Science Foundation of China undergrant no. 51422701. This article is funded by the National Science Foundation of China: 51422701 and China‘111’ project of ‘Renewable Energy and Smart Grid’: B14022. The founding sponsors had an important role in thedesign of the study; in the collection, analyses, and interpretation of data; in the writing of the manuscript, and inthe decision to publish the results.

Author Contributions: Feng Wu conceived and designed the experiments; Yan Hong Yuan performed theexperiments; Feng Wu and Yan Hong Yuan analyzed the data; Feng Wu contributed analysis tools; Yan Hong Yuanand Feng Wu wrote the paper.

Conflicts of Interest: The authors declare no conflict of interest.

References

1. Sun, S.; Liu, F.; Xue, S.; Zeng, F. Review on wind power development in China: Current situation andimprovement strategies to realize future development. Renew. Sustain. Energy Rev. 2015, 45, 589–599.[CrossRef]

2. Gao, F.; Xue, A.C.; Li, P.; Yan, Y.T.; Yang, Y. Research on the improvement of LVRT ability of an actualDFIG-type wind farm with Crowbar and SVG. In Proceedings of the International Conference on RenewablePower Generation IET, London, UK, 21–23 September 2016.

3. Lopez, J.; Gubia, E.; Olea, E.; Ruiz, J.; Marroyo, L. Ride Through of Wind Turbines with Doubly Fed InductionGenerator Under Symmetrical Voltage Dips. IEEE Trans. Ind. Electron. 2009, 56, 4246–4254. [CrossRef]

4. Wang, S.Y.; Yu, D.R.; Foley, A.; Zhu, L.Z.; Li, K.; Yu, J.L. Flexible fault ride through strategy for wind farmclusters in power systems with high wind power penetration. Energy Convers. Manag. 2015, 93, 239–248.[CrossRef]

5. Rahim, M.; Parniani, M. Grid-fault ride-through analysis and control of wind turbines with doubly fedinduction generators. Electr. Power Syst. Res. 2010, 80, 184–195. [CrossRef]

6. EI-Naggar, A.; Erlich, I. Fault Current Contribution Analysis of Doubly Fed Induction Generator-BasedWind Turbines. IEEE Trans. Energy Convers. 2015, 30, 874–882. [CrossRef]

7. Yin, J.; Bi, T.; Xue, A.; Yang, Q. Study on short-circuit current and fault analysis method of hybrid wind farmwith low voltage ride-through control strategy. Trans. China Electrotech. Soc. 2015, 39, 60–62.

8. Bi, T.S.; Liu, S.M.; Xue, A.C.; Yang, Q.X. Fault analysis of doubly fed induction generator wind turbines withlow-voltage ride-through capability. Power Syst. Prot. Control 2013, 41, 26–31.

9. Zhang, J.H.; Chen, X.Y.; Wang, B.; Wang, P.; Liu, H.M. Three-phase short circuit analysis of DFIG-based windgeneration and the crowbar biggest resistance setting. In Proceedings of the International Conference onSustainable Power Generation and Supply, Nanjing, China, 6–7 April 2009.

10. Wen, G.; Chen, Y.; Zhong, Z.; Kang, Y. Dynamic voltage and current assignment strategies of nine-switch-converter-based DFIG wind power system for low-voltage ride-through (LVRT) under symmetricalgrid voltage dip. IEEE Trans. Ind. Appl. 2016, 52, 3422–3434. [CrossRef]

11. Cui, Y.; Yan, G.G.; Jiang, D.W.; Mu, G.; Zhou, Z.Q.; Wang, X.B.; Li, Q. DFIG-based wind farm equivalentmodel for power system short circuit current calculation. In Proceedings of the International Conference onSustainable Power Generation and Supply, Nanjing, China, 6–7 April 2009.

Page 15: Short-Circuit Current Analysis for DFIG Wind Farm

Energies 2018, 11, 425 15 of 15

12. Wessels, C.; Gebhardt, F.; Fuchs, F.W. Fault ride-through of a DFIG wind turbine using a dynamic voltagerestorer during symmetrical and asymmetrical grid faults. IEEE Trans. Power Electron. 2011, 26, 807–815.[CrossRef]

13. Harnefors, L.; Nee, H.P. Model-based current control of AC machines using the internal model controlmethod. IEEE Trans. Ind. Appl. 1995, 34, 133–141. [CrossRef]

14. Gao, Y.; Jin, Y.; Ju, P.; Zhou, Q. Dynamic equivalence of wind farm composed of double fed inductiongenerators considering operation characteristic of crowbar. Power Syst. Technol. 2015, 29, 1427–1436.

15. Jin, Y.Q.; Huang, Y.; Ju, P.; Pan, X.P. Collector network transformation methods for wind farm aggregatedmodeling. Power Syst. Prot. Control 2012, 40, 34–41.

© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open accessarticle distributed under the terms and conditions of the Creative Commons Attribution(CC BY) license (http://creativecommons.org/licenses/by/4.0/).