schedule for the r & m of distribution transformers
TRANSCRIPT
R&M Final 2 5/12/2006 10:50 AM A-1
Schedule for the R & M of Distribution Transformers
Schedule No. Item to be
inspected
Brief description of work
1.
Connections Check for tightness. Replace and refill old/worn out
thimbles where necessary check for Provision of PVC
sleeves insulating beads on the H.T. connectors, &
replace where necessary.
2.
Oil level Check for proper oil level and top up if necessary.
Check for leakage from the drain valve, gaskets and
tank etc. & attend it if required.
3. Breather Inspect silica gel and recondition/replace, if
necessary.
4. Fuses (HT
and LT)
Check for continuity, tightness and proper rating/
size. Replace if necessary.
5. G.O. Switch Check for proper functioning and sparking & adjust
the settings, if required.
6. Diaphragm Check for cracks & replace if required.
Monthly
7.
Bushing and
arcing horns
Check for cracked and broken bushings. Clean or
replace if necessary. Examine and replace damaged
gaskets. Adjust arcing horns for proper gaps and
alignment.
1. Insulation
resistance
Check the I.R.values with 1 KV meggar. Compare the
values with the values at the time of commissioning.
Quarterly
2.
Voltage and
load
checking
Measure voltage and load during peak load conditions
at the transformers and at the tail end of LT feeders.
Measure load during peak load conditions against its
rated capacity. Balance the load on three phases and
initiate action for augmentation, if necessary.
R&M Final 2 5/12/2006 10:50 AM A-2
Schedule No. Item to be
inspected
Brief description of work
3.
Barbed wire
and danger
plate etc.
Check for proper installations and repaint/replace
where ever necessary.
1.
Oil Observe colour of oil, Check water content and
perform crackle test on the oil samples drawn from
the drain off valve. In case the test indicates
deterioration, perform di-electric strength test. In
case of over contamination, the transformer oil should
be replaced and drained out oil should be separately
dehydrated for its reuse.
Keep records of the test results.
Yearly
2.
Earth
testing
(to be done
during driest
part of the
year)
Check for earth resistance in respect of transformer
neutral, metal parts including body and the lightening
arrester. Ensure that this is less than 2 ohms.
Examine the whole earthing system for tightness of
connections and broken/rusted leads etc. Recondition
or replace where ever necessary.
Keep records of the test results.
1. Conservator
tank
Clean the inspection glass for proper visibility. Check
for leakage from the glass fitting.
Check for proper communication of the conservator
with transformer tank by draining some oil through
the drain valve and watching the oil in the gauge glass
to drop.
In case the oil does not drop, investigate and remove
the sludge or other obstruction(s) after dis
assembling the conservator tank. Two yearly
2. Acidity and
sludge
Check for acidity and sludge formation. In case the
acidity is more than 0.5 mg/KOH/gm, of oil then
recondition the oil.
In case the acidity is more than 1.0 mg/KOH/gm,
reclaim the quality of oil with fuller’s earth or action
of inhibitors.
Once
every 5
years
1.
Complete overhauling of the transformer.
R&M Final 2 5/12/2006 10:50 AM A-3
Schedule for the R & M of Power Transformers
Schedule No. Item to be inspected Brief description of work
1. Ambient Temp Note down the temperature and record the
maximum daily ambient temperature.
2.
Winding/Oil Temp Check that temp rise is reasonable. In case
of any abnormal variation, check the cooling
system of T/F. If the same is not found in
order. Shut down the T/F for further
investigation.
Hourly
3. Load/Voltage Check against rated figures. In case of any
variation, check the TPI.
1.
Oil level in transformer Check against transformer oil level/
temperature. Top up with dry oil, if
necessary.
2 Oil level in bushings Check for any oil leakage.
3. Relief Vent diaphragm Check for cracked or broken. Replace if
necessary.
4.
For internal abnormal noise. Check for any abnormal sound or excessive
chattering. Shut down the T/F in case of
abnormal noise, for further investigation.
5 Heaters in Junction Box Check for proper working, if provided.
Replace, if found defective/damaged.
6
External connection
(Leads/Jumpers)
Check visually for tightness and sparking on
jumpers, bushings etc. on complete
darkness. Attend it, if required.
Daily each shift
7
Bus bar and cable boxes and
cables
Check for any damage and signs of
overheating at their joints. Check for
overheating of back covers and attend, if
found excessive heated.
Monthly
1 Dehydrating breather
(i)Check for condition/colour of Silica gel.
Recondition or replace as necessary.
(ii) Ensure for free air passage
(iii) Tight, lid of the breather for air
tightness to avoid entry
(iv) Check oil level in oil cup and make up oil,
if required.
(v) Remove oil from dash pot and pour in
fresh oil where required.
R&M Final 2 5/12/2006 10:50 AM A-4
Schedule No. Item to be inspected Brief description of work
2
Bushing and gaskets Examine for cracks, Paint and dirt deposits
and gap settings. clean or replace it. Check
gaskets for leakage.
3 Cooler fan and pump
bearings, motors and
operating mechanism
Lubricate bearings, check gear box.
Examine Contacts, Check Manual control and
interlocks. Replace burnt or worn out
contacts or other parts.
4
On load tap changer driving
mechanism
Lubricate bearings, Check gear box oil level
and examine contacts. Clean/Replace burnt
or worn out contacts
5
On load tap changer
automatic control
Check all circuits independently. Check
step by step operation including limit
switches. Attend if found faulty.
6
Insulation resistance Check the I.R.values with 2.5KV rating
meggar. Convert it at 70 0 C and compare
the values with the value taken at the time
of commissioning.
7
Relays alarms, temperature
alarm and their circuits
Examine relays and alarm contacts and their
operation, fuses etc. Check for relays
functioning clean or replace the contacts if
required.
8 Arcing Horns Set the rods for alignment and for proper
gap adjustment.
9 Measuring/Protection CT’s Check for sparking and tightness of
connection and oil level.
10 Remote/Manual Switch Check for proper functioning
11 Fire fighting equipments Examine them and ensure that these are in
order.
12 Bucholtz’s relay Note the oil level in the inspection glass of
Bucholtz’s relay.
1
Oil in T/F and tap changer Check for dielectric strength. Dehydrate
the oil, if necessary. Keep continuous
record of test results.
2 Ventilators Check that air passages are free.
Quarterly
3
Bucholtz’s relay
Check proper operation by loweringthe oil
Monthly
R&M Final 2 5/12/2006 10:50 AM A-5
Schedule No. Item to be inspected Brief description of work
4 Forced cooling system (ii) Megger testing of motors(pumps)
(iii) Checking transformer ground
connections for
tightness.
5 Thermo Syphen Filters
Check for its normal working order.
6
Earth Resistance (i) Check for tightness of earth
connections.
(ii) Measure earth resistance of the (a)
T/F body, neutral and other body
parts, (b) Keep proper record of test
results. (Earth testing to be done
during driest part of the season)
1
On load tap Inspect all moving parts, contacts, brake
shoes, motor etc.clean, adjust or replace as
required.
Half Yearly
2 Oil in T/F Check acidity, PPM & BDV & compare with
standard results.
1
Oil in T/F Check Tan delta,, Sp.Resistively , sludge
contents, DGA test, compare it with
standard results.
2 Oil filled bushing Test oil for dielectric strength Dehydrate
or replace the oil, if necessary.
3 Cable box Check for sealing arrangements for filling
holes. Examine compound for cracks.
4 Surge diverter and gaps Examine for cracks and dirt deposits. Clean
or replace if necessary.
5
Gasket joints Check for tightness of bolts to avoid uneven
pressure. Replace damaged gasket.
6 Pipe connections Check oil pipes valves and plugs for
tightness and proper functioning.
7 Foundations Check for cracks, if any and setting.
Yearly
8 Bushings Test the bushings with a Hipet bushing
tester and compare with previous figures.
Quarterly
R&M Final 2 5/12/2006 10:50 AM A-6
Schedule No. Item to be inspected Brief description of work
9 Temperature indication Pockets holding thermo-meter should be
checked. Oil to be replenished, if required.
10 Dial type oil guage Check pointer for free operation. . Adjust,
if required.
11 Paint work Should be inspected
12
Conservator tank (i) Check for proper communication of
the conservator with T/F tank by
draining some oil through drain off
valve and watching the oil in gauge
glass to drop.
(ii) In case, the oil does not drop,
investigate and remove the sludge or
other obstructions after dis-
assembling the tank.
(iii) Check for leakage of oil from glass
side. Clean the inspection glass.
Yearly or
after
5,000
operations
1
Diverter switches for tap
changer having non-arcing
selector switch
Check for worn out contacts. Filter oil
irrespective of all test. Replace worn out
parts.
1 Oil conservator Internal inspection Clean the conservator
thoroughly
Two years
-
2 Buchholtz relay Mechanical inspection. Adjust floats,
switches etc. if required.
3 years or
after
15,000
operations
1
Non-arcing selection switch
of on load tap changer
General inspection. Replace worn out parts
and filter the oil.
7 to 10
years
1
Overall inspection including lifting of core
and coils
Major overhauls (complete) of
transformers.
Once in 7 years
once in 10 years.
1 3000KVA and below (once in 7 yrs.)
Above 3000KVA (once in 10 yrs.)
Yearly
R&M Final 2 5/12/2006 10:50 AM A-7
Schedule for the R & M of Isolators and Earth Switches.
Schedule No. Item to be
inspected
Brief description of work
1
Insulators
Check for cracked or broken porcelain and
excessive dirt film and to undertake repair of
chipped spots by painting with lacquer such as red
clay paint.
2 Blades and
contacts
Check that blades are properly seated in the
contacts..
3 Blades and
latches and
stops
Check that blade latches where provided are
engaged. Weekly
4 Locks and
inter locks
Check that switches are properly locked in the
open or closed position as required by padlocks or
other key type locks or interlocks.
Quarterly 1 Bolts, Nuts &
Jumpers
Check bolts, nuts and jumpers for tightness.
Apply petroleum jelly on male and female contacts.
1 I.R,value and
earth
resistance
Check IR, value with 2.5KV megger and earth
resistance. Check that double earthing is provided.
2 Auxiliary &
limit switches
Check condition of contacts and refinish with fine
file if burnt or corroded. Check contact spring
operating rod and lever. Check closing and opening
position with respect to main switch contacts or
travel or motor mechanism.
Half yearly
3 Manual
operating Rod
To check for proper engagement of emergency
operating handle and further its operation is
smooth and satisfactory.
1 Line & ground Check and tighten line and bus terminal and
operating handle ground connections. Check that
ground cable is not broken.
Annually
2 Blades and
contacts
Operate the isolator several times and see that
the blades are properly aligned to engage.
R&M Final 2 5/12/2006 10:50 AM A-8
Schedule for the R & M of CURRENT/POTENTIAL T/F
Schedule No. Item to be
inspected
Brief description of work
1 Insulator Check for any crack or damage of the porcelain
insulator.
2 Oil Check for oil leakage and oil level
3 Earth
connections
Check that earth connections are properly made
4 Jumpers Nut
Bolts etc.
Check that jumpers, nuts, bolts, clamps are
properly tight and are of proper size.
Monthly
5 Secondary
winding
Check that secondary winding terminal wiring is
properly made and routing is not disturbed. The
connections in the panel are intact.
1 I.R.Value Check I.R.values of primary and secondary
windings with 2.5KV & 500 V rating meggar
respectively.
2 Earth
resistance
Check earth resistance.
Half yearly
3 Secondary
taps
Check secondary taps for tightness to avoid
overheating.
1 Oil test Check dielectric strength of oil and toping of oil.
Yearly
2 Tap setting Check tap setting and adjustment at terminal
beard to see that they agree with diagrams.
R&M Final 2 5/12/2006 10:50 AM A-9
Schedule for the R & M of Lightening Arrestors.
Schedule No. Item to be
inspected
Brief description of work Daily
1
Surge Counter Note and record operation indicator reading
alongwith leakage current.
1 Base & support Usual inspection to detect cracking setting or
shifting of base of supports.
Monthly
2 Surge Monitor Check that surge monitor is properly connected
and is in working order and shows a leakage
current.
1 Jumpers and
clamps
Check jumpers and clamps for tightness.
2 Porcelain
shells and
insulators
Clean porcelain insulators and arrestor unit shells.
Repair chipped spots on porcelain with lacquer
such as red clay paint.
3 Grading rings Check and tighten grading rings on high voltage
arrestors.
Half Yearly
4 Gaps Check external gaps. Smooth off burnt spots and
readjust spacing.
1 Weather
sheds and
hooks
See that weather sheds and hooks of oxide film
arrestors are securely fastened in place, repaint if
necessary.
2 Line and
Ground
connection
Check and tighten line and ground connections.
Check ground lead for corrosion or damage below
ground line. Check ground resistance. See that all
leads are as short and direct as possible.
Annual
3 Operation
tests (Surge
generating
equipment
under
procurement)
To check the general working of lightening
arrestors by M&P Divisions.
R&M Final 2 5/12/2006 10:50 AM A-10
Schedule for the R & M of Batteries and Battery Charger.
Schedule No. Item to be
inspected
Brief description of work
1 Battery room
and ventilation
See that battery room entrance doors are kept
closed and that ventilation to out side air are open
and air is circulated by running of the exhaust fan.
2 Operation Check charging rate hourly. Check and record pilot
cell specific gravity, temperature and floating
voltage.
3 Bulb for dry
rectifier
element
Check for burnt bulb and replace when necessary.
Daily
4 Operations Checking specific gravity and voltage of each cell
of lead acid cells. (before and after charging)
(weekly when trickle charge exists)
Daily(
each
shift)
1 Leakage test Perform leakage test by lamp or voltmeter
method.
Wee
kly 1 Cleaning of terminals, applying Vaseline and topping
up with distilled water. (for lead acid batteries)
1 Cell Jars and
covers
Check for cracked or leaking jars or covers and
replace when necessary. Keep jars and covers
clean.
2 Plates Inspect plates(in case of transparent containers
only) carefully for signs of deterioration due to
improper charging. Note quantity, colour and
texture of sediment.
3 Separators See that the separators remain in place and are
keeping the plates properly spaced(in case of
transparent containers only)
4 Electrolyte Check electrolyte level and add distilled water
when required.
5 Acid and
distilled water
storage
See that enough distilled water and acid are kept
in storage to meet current needs. Check
containers for cleanliness.
6 Operation Check and record specific gravity and voltage of
each cell.
Monthly
7 Transformer
or reactor
Check general condition and operating temperature
of transformer or reactor used in bulb or dry type
rectifiers.
R&M Final 2 5/12/2006 10:50 AM A-11
Schedule No. Item to be
inspected
Brief description of work
Quar
terly
1 Connections Checking all connections of charger and battery
for tightness.
1 Discharging
and charging
cycle
This is required to be carried out as prescribed by
the manufacturer in order to prolong the life of
the battery.
2 Bulb or dry
rectifier
element
See the copper oxide or selenium rectifier
elements are not operating too hot, this will
shorten their life. Half yearly
3 Rheostat Check that sliding mechanism of the rheostat is in
order and clean the sliding contacts, if required.
Check contact heating and spring pressure.
1 Battery room
and ventilation
Check metallic structures/parts located in the
room for corrosion and clean and paint as
necessary, check ventilation system fan etc. for
proper operation to make sure that no explosive
gases are being accumulated in the battery room
due to excessive gassing or poor ventilation.
2 Base or rack Inspect concretes base or wooden racks for
deterioration. Repair and repaint with acid
resistant paint as necessary.
3 Case pad Check base pad of sheet rubber, or other material
for deterioration from acid or other causes.
4 Inter cell
connectors
and terminals
Clean acid corrosion from connectors and
terminals should be lead coated. Tighten terminals
and apply petroleum jelly for exposed surface.
5 Hydrometer
and thermo
meter
Check condition of hydrometer and thermometers
used for daily and monthly readings against spare
units held in reserve.
6 Sink funnel
and filters
See that the sink, funnels, fillers and other
distilled water and acid handling facilities kept
clean and in good useable conditions.
7 Water still Check still for proper operation, adequacy and
purity of distilled water delivered. See that
equipment is kept clean
Annual
8 Complete overhauling of the battery. (as
recommended by manufacturer)
R&M Final 2 5/12/2006 10:50 AM A-12
Schedule for the R & M of Oil and Air Circuit Breakers.
Schedule No. Item to be
inspected
Brief description of work
1 General
cleanliness
Examine that switchgear premises doors, circuit
breaker etc. for general cleanliness.
2 Oil Check oil leakage, if so level be also ascertained.
3 Tank Check for temperature by touch and for any
unusual noise and smell.
4 Alarms and
lamp indication
circuit etc.
Test the alarm circuit for continuity and lighting
circuit and earthing system.
5 Draining and blowing down of main air receivers,
checking all air pressures and air conditioning flow
meters.
6 Safety aids Check safety aids for proper operation/condition.
7 Load Check for load conditions on 3 phases, adjust relay
setting. If necessary.
Daily
8 Indicating and
measuring
instruments
Check, indicating and measuring instruments for
correct reading and being in proper working order.
1 Auxiliary
fuses
Check that auxiliary fuses are in tact.
2 Oil level and
gauges
Check oil level in gauges of the tank/poles/oil
filled bushing. Replenish oil if found below normal.
3 Bushing or
insulators
Check for chipped or broken insulator, excessive
dirt film.
4 Closing
solenoid of air
cylinder,
motor or
spring
Visual inspection to see that equipment is in
operating conditions Drain condensation from air
cylinder.
5 Latch and trip
mechanism
Visual(or otherwise)inspection to see that
mechanism is in operating condition.
6 Tripping
solenoid
Visual inspection to see that solenoid trip device is
in operating condition.
Weekly
7 Cabinet lights
and heaters
Check cabinet heaters and see that they are in
service during cold weather. Replace burnt out
lamps.
R&M Final 2 5/12/2006 10:50 AM A-13
Schedule No. Item to be
inspected
Brief description of work
8 Power supplies
and wiring
See that all power control circuit switches are
closed
9 Breathers and
vents
Check for external obstructions to breathers and
vents and condition of silica gel.
1 Nuts, bolts &
Jumpers etc.
Check whether nuts and bolts are tight and
jumpers are properly connected.
2 Drain plug Check that drain plug is tight.
Monthly
3 Operation
counter
Observe and record reading of operation counter.
1 Local remote
operation
Check that breaker can be operated locally and in
remote control operation.
2 Exhaust pipes Check and clean the exhaust pipes.
3 Dash pot Check the working of dash pot.
4 Shutter
mechanism and
trolley
alignment for
11KV breakers
To check for proper working of shutter mechanism
and to verify the alignment of trolley.
5
Manual
operating
device
Check that manual operating lever or jack is kept
on hand and is in visible condition. See that
breaker is closable with it.
6 Latch and trip
mechanism
Observe mechanism during general tripping
operations to see that every thing is in working
order. Check pins, bearings and latch for wear,
binding and misalignment. Clean and lubricate the
moving parts. Check latch carefully to see that it
is not becoming worn so as to unlatch from
vibration or stick or fail to trip. Tighten bolts and
screws.
7 Tripping
solenoid
Observe operation during electrical tripping. See
that full energy, snappy action of plunger is
obtained. Check plunger for sticking in guide Check
oil and insulation resistance.
Quarterly
8
Check and adjust oil level in jacks.
Weekly
R&M Final 2 5/12/2006 10:50 AM A-14
Schedule No. Item to be
inspected
Brief description of work
9 Indicating and
measuring
instruments
Check for satisfactory operation, adjust where
necessary
1 IR values Check IR value in ON and OFF positions between
contacts in off position. Check IR value of control
cable with 500V megger.
2 Earth
resistance
Check earth resistance of body.
3 Slow closing
test
This test may be conducted and also check that all
the three contacts are made simultaneously.
4 Adjustment of
gap (for
MOCB)& other
type to check
the prescribed
items by the
manufacturer
The gap may be checked and adjusted to the
required value.
5 Wiring
connections
Check and tighten wiring connection at terminal
points. Inspect wiring for open circuit, short
circuit and damaged insulation.
6 Aux.Switches Check condition of contacts and refinish with fine
file if burnt or corroded. Check contact springs,
operating rods and levers. Check closing and
operating position with respect to main contacts
while breaker is slowly closed and opened manually.
7 Control and
protection
chamber of
11KV switch
To check for alignment of front door
opening/closing for loose fitting, loose wiring of
opening in 11KV switchgear.
8 Insulated,
jumpers CT
and PT in 11KV
switchgear
To check for tightness of connections, proper
insulation and proper geometry.
Half yearly
9 11KV cable
connections
Check for overheating and proper connection and
insulation.
Quarte
rly
R&M Final 2 5/12/2006 10:50 AM A-15
Schedule No. Item to be
inspected
Brief description of work
1 Foundation Check foundation for cracks and settings.
Settings of the breaker tank may break bushings
or cause misalignment of contacts or bindings of
operating mechanism.
2 Oil valves and
plugs
Check condition of paint. Inspect oil valves and
plugs. Flush out oil and clean the oil
tank/quenching chambers.
3 Oil levels and
gauges
Clean dirty gauge glasses and connections into
tank. Drain out and replace bushing oil if found
dirty or discoloured.
4 Breathers and
Vents
Check to see that screens and baffles in vents or
breathers are not obstructed or broken.
5 Panels and
cabinets
Check air circuit breaker or other panels of
insulating material for cracks and cleanliness.
Check condition of enclosing cabinets including
hinges, latches, locks door gaskets and paint.
6 Bushings or
insulators
Clean porcelain with water, chloroethene or other
suitable cleaner. Repair chipped spots by painting
with lacquer such as red clay paint. Inspect
gaskets for leaks, tighten bolts. Check insulation
resistance with contacts closed and (Tan delta for
condenser type). Check oil sample from bottom of
bushing for dielectric strength and moisture.
Replace or replenish oil if necessary. Check and
clean interior at least once every five years.
7 Main terminals
and ground
connections
Tighten all nuts and ground connections. Refinish
joint mating surface, if they have been
overheated. Inspect ground cable to see that it is
not loose or broken.
8 Main contacts Remove the tanks or drain out oil, so that the
contacts can be inspected, dress contacts, if
rough with a fine file. Check contacts voltage drop
with millivolt meter after inspecting reasonable
current. Frequency of contact maintenance should
be based on numbers and severity of faults
interrupted, rather than a definite period. Check
adjustment of gap when required.
Annual
9 Contact
pressure
spring
Check for loss of temperature damage or other
deterioration.
R&M Final 2 5/12/2006 10:50 AM A-16
Schedule No. Item to be
inspected
Brief description of work
10 Flexible shunt Check flexible shunts of contact hinges for
overheating or damages. Tighten connections.
11 Magnetic, air
or oil below
out devices
Check arc-rupturing blow out coils, magnetic
cirlcuit arc chutes, de ion grids, oil blasts or other
interrupters for proper operations.
12 Cross heads Check contact cross head for misalignment breaks
bends or looseness on lift rods.
13 Lift rods and
guides
Check contacts for lift rods or brakes, weakening
or wrapping and pulling out at ends. Checks
adequacy of guides.
14 Operating
rods shafts
and bell cranks
Check for loose locknuts, set screws, keys, bearing
bent rods or twisted shafts etc. clean moving
parts of rust, dirt and accumulated grease and oil,
wash out bearings, pivots and gears with
chloreethene or other suitable cleaner and
operate breaker several times to work out dirt and
old lubricant. Lubricate with new grease or oil.
15 Closing
solenoid air
cylinder,
meter or
spring
Observe mechanism during several operations to
see that every thing is in proper working order.
Check solenoid plunger for sticking in guides.
Check coil resistance and insulation resistance.
Dismantle air cylinder and clean and lubricate.
Check spring for proper tension and closing energy.
16 Solenoid
valves
Check for condition of valve, and refit as
necessary. See that moving parts are free to
operate. Check resistance and insulation
resistance of solenoid coil.
17 Operation
counter
Check that the operation counter is properly
registering the breaker operations.
18 Position
indicator
Check that position indicator is properly
registering the breaker operations.
19 Dashpots Check for proper setting and adjust as necessary.
Clean out and replenish liquid in liquid dashpot.
20 Mechanism
cabinets
Check condition of metal and hardware. Repaint as
necessary. See that door gaskets are tight and
properly dust and vermin proof.
Annual
21 Power supply
and wiring
Inspect fuses of circuit breakers in all power and
control supply circuits, check in insulation
resistance of wiring with devices connected.
R&M Final 2 5/12/2006 10:50 AM A-17
Schedule No. Item to be
inspected
Brief description of work
22 Oil dielectric
test and
acidity test
dependent on
actual tripping
Check dielectric strength of the insulating oil in
the main tanks and oil filled bushings. Oil should
be filtered or replaced if dielectric strength is
found to below 25 KV, or if there is a noticeable
amount of carbon in suspension on the bottom of
the tanks. Also check ratio and phase angle
adjustments, the acidity of the oil.
23 Operation Some breakers particularly those carrying high
values of current have a tendency to develop
contact heating if left closed for long periods.
Operating and closing the breakers several times
at intervals, as system operation permit, may
alleviate the heating by wiping the oxide from the
contact surfaces, as well as demonstrate that the
breaker is in operating condition.
24 Bushing
current
transformers
and potential
devices
Check tap setting and adjustments at terminal
board to see that they agree with diagrams. Check
insulations resistance of wiring with devices
connected. Check of potential devices if changes
have been made in secondary connection and
burden. Tighten connections, including potential
devices top into bushing.
1 Testing of oil in oil filled bushings
2 Cleaning blast tube intemally and checking clamping
down nuts.
Once in two
years
3 Overhaul and checking efficiency of main
compressor.
Five yearly
1 Complete overhaul of the O.C.B.
(The period can be changed depending upon the lead
cycle of the equipment and manufactures
recommendations).
Annually
R&M Final 2 5/12/2006 10:50 AM A-18
Schedule for the R & M of H.T. Lines (33 KV & 11 KV including G.O. Switches)
Schedule No. Item to be
inspected
Brief description of work
1 Poles
i) Steel
ii) Wood
iii) Cement
Check for the following in case of all the 3 types of
poles:
i) Damages/broken poles or for ground level
erosion and corrosions where the pole is not
capable of safely supporting its load.
ii) Bowed or leaning poles due to improper guying
or overloading.
iii) Unauthorized attachments such as fencing,
aerial wires etc.
iv) Poles which are very much exposed to
hitting/striking of animals and bumping and
scrapping by vehicles
v) If the pole Number plate is still distinct
vi) Check the condition of foundation and attend
it, if necessary.
vii) Examine if pole requires painting/creeseting
of ascue in case of steel/wood poles.
2 Stays Check for the following:
i) Correct direction and proper angle of the stay
ii) Loose broken or any other damage done to
stays
iii) Whether stay insulator is intact/whether stay
is properly earthed
iv) If stay rods are corroded. Attend the same
if required.
Quarterly
3 Cross arms and
pole top steel
works
Check for the following:
i) If the cross-arms/clamps/knee bracings
has/have slipped.
ii) Bending of cross arms due to uneven tension
iii) Excessive rusting of the cross arms bracings
etc.
iv) Cracked or splitting or the wooden cross-
arms.
v) Loose or damaged bracings. Attend the same,
if required.
R&M Final 2 5/12/2006 10:50 AM A-19
Schedule No. Item to be
inspected
Brief description of work
4 Insulators and
fittings
Check for the following:
i) Broken or chipped procelain flashover marks
ii) Tilted insulators
iii) Excessive deposit of dust/salt/coal and other
pollution clean the same.
Excessive rusting of fittings, replace the same, if
required.
Quarterly
R&M Final 2 5/12/2006 10:50 AM A-20
Schedule No. Item to be
inspected
Brief description of work
5 Conductors and
earthwire
Check for the following:
i) Examine, if securely tied to the
insulator/pole/cross-arms.
ii) Proper sag, set right the same, if required.
iii) Proximity of trees and other objects including
building etc.
iv) Sufficient clearance between conductors and
earthwire and also from the ground.
v) Sufficient clearance from other
electric/telephone lines passing along below or
above it.
vi) Earthwire is properly supported
vii) All the line guards are intact and installed
where necessary
viii) If joints in the jumpers and conductors
appear all right
ix) Broken conductors strands
x) Nicking near insulator neck/or near conductor
clamps
xi) Bindings wire has not become lose and open
xii) Midspan joints have not cracked.
xiii) All joints and jumpers of aluminum conductors
have proper clamps/jointing sleeves. Setright
the same, if required.
Quarterly
6 Jumpers and
other line
accessories
Check for the following:
i) Proper supporting and jointing two ends of the
jumpers with suitable clamps.
ii) Sufficient clearance between jumpers on the
3-phases
iii) Sufficient clearance of jumpers from metal
iv) Provision of proper insulation of jumpers
v) Signs of over-heating and burnings on jumpers
and other fittings.
vi) Loose/defective clamps jointing sleeves, bolts
and nuts, and other fittings.
R&M Final 2 5/12/2006 10:50 AM A-21
Schedule No. Item to be
inspected
Brief description of work
7 GO switches Check for the following:
i) For smooth operation
ii) Evidence of over-heating burning,
crossing/pitting on the switch contacts.
iii) Broken on damaged insulators
iv) Proper and tight earth connection
v) Fuse links for continuity, tightness of
connections and correct rating
vi) Proper locking arrangement
vii) Proper alignment of switch contacts
viii) Proper and complete fitting of male contacts
into the female one.
ix) Arcing horns are intact. Attend the same,
wherever reauired.
8 Lightening
arrestors
Check for the following:
i) Broken/damaged porcelain
ii) Broken and tight. Line and earth connections
iii) External indication of fused/spark-over
arrestors
9 11KV cable and
cable box
Check for the following:
i) Proper supporting of the cable and cable
boxes
ii) Damaged insulators
iii) Oil and compound leaks and that the cable box
is properly topped up with the compound
iv) Proper earthing
v) Overall condition of the cable and joint.
Quarterly
10 Earthing
system
Check for tight and intact earth connections for all
metal works of the line.
R&M Final 2 5/12/2006 10:50 AM A-22
Schedule No. Item to be
inspected
Brief description of work
Half yearly
1 Jumpers and
line
accessories
i) Check for broken or burnt strands of the
jumpers and replace, where necessary.
ii) Check for proper material and size of the
jumpers for the given conductors.
iii) Check for loose connections and signs of over-
heating specially on copper to alumimium
connections
iv) Check for crewaing or jumbling of wires and
jumpers of the Tee-off points and adjust
where necessary.
v) Check for general condition of other line
accessories such as different clamps, jointing
sleeves and other fittings etc. Readjust and
replace where necessary.
vi) Replace the binding wire joints of jumpers by
proper clamps.
vii) Check for the condition of sleeves over the
jumpers and replace, where necessary.
R&M Final 2 5/12/2006 10:50 AM A-23
Schedule No. Item to be
inspected
Brief description of work
2 G.O.
switch(with
fuse unit)
i) Cleanliness: clean all dust and other deposits
with neat and dry cloths.
ii) Switch contacts:
1. Check for alignment, adequate contact
pressure and smooth operation and adjust,
where necessary
2. Examine for burning,over-heating or other
damages. Recondition or replace, where
necessary.
iii) Insulator:
1. Check for cracks. Clipping and other
defects, replace, where necessary.
2. Remove dirt, coal and other pollutions by
wiping with soft cloth. Use acidic solution,
if the deposit has set hard.
iv) Arcing horns: Check if these are intact and
replace if damaged/burnt.
Mechanism: clean, examine and renew worn out
parts. Reduplicate and check for correct operation.
vi) Fuse unit: replace old fuses with new ones of
right type and capacity and proper length
vii) Main connections and Earthing: Proceed as
described under separate heading of jumpers and
earthing devices.
viii) General: Check all hardware and tighten, if
needed
Half- Yearly
R&M Final 2 5/12/2006 10:50 AM A-24
Schedule No. Item to be
inspected
Brief description of work
Half Yearly
3 Tree trimming
and bird's
nests etc.
i) Cut off the trees branches where necessary
to maintain a minimum clearance of 1.8m on
each side of the line
ii) Remove all dead wood.
iii) Remove all bird's nests.
(once before the monsoons or earlier, if necessary)
Annually
1 Poles
1) Steel
2) Wood
3) Cement
The instructions given below are concerned to the 3
types of poles:
i) Replace the damaged/broken poles.
ii) Straighten/make vertically leaning poles by
proper giving
iii) Shift the position of poles exposed to
accidents due to their being near or in
common way.
iv) Reprint the pole No.plate , if defaced
v) Pack and consolidate the foundation soil where
disturbed or erased
vi) Steel poles: Examine for signs of rust, clean
off with wire brush and apply double coat of
suitable paint, where required over a primer
base.
vii) Wood pole:
1. Examine for decay of wood and
creosetting/ascuer treatment may be
done where required.
2. Examine for burning of wood at hardware
attachments points and recondition, where
necessary.
viii) Cement Pole: No. detailed maintenance
required.
R&M Final 2 5/12/2006 10:50 AM A-25
Schedule No. Item to be
inspected
Brief description of work
2 Stays i) Tighten the loose stays.
ii) Replace the broken/damaged stays and stay
bows
iii) Replace the broken stay
insulator/recondition the Earth
iv) Provide sufficient barbed wire/cattle guards
on the stay to avoid rubbing of cattles
3 Cross arms i) Replace the broken/splitted/cracked/bent
cross arms by new ones.
ii) Bring in position the slipped cross
arms/clamps/bracings.
iii) Paint the steel cross arms and bracings etc. If
excessively rusted.
Annually
R&M Final 2 5/12/2006 10:50 AM A-26
Schedule No. Item to be
inspected
Brief description of work
4 Insulators and
fittings
i) Clean and check for cracked/chipped and
punctured insulators. Replace, where
necessary.
ii) Examine for the surface contamination and
remove it by wiping with a soft cloth (do not
use cotton waste). If the deposit has set
hard, a weak acidic solution may be used.
The insulators be checked twice a year preferably
or before and after (monsoons)
5 Conductors and
earthwires
i) Tighten loose bindings and replace damaged
ones.
ii) Examine for corrosion at the joints of
conductors and insulators. Clean and renew,
where necessary.
iii) Examine closely for broken strands
particularly at the clamps and insulators due
to vibration and repair, where necessary.
iv) Examine general condition of the conductor
and earthwires i.e. for kinks, crushed spots
over/under tensioning, etc., and recondition,
where necessary.
v) Examine for any loose/cracked joints of
conductors in the midspan and recondition
where necessary.
vi) Examine for any loose/cracked joints slipping
of conductors from the clamps. Tighten all
clamps and fittings.
Annually
6 Lightening
arrestor
i) Clean and examine insulators for cracks or
flashover. Replace, where necessary.
ii) Perform impulse voltage spark over test and
leakage current test to know the condition of
the arrester; replace in case of
unsatisfactory results.
iii) Keep records of test results.
iv) Check and tighten all line connections and
earth leads.
R&M Final 2 5/12/2006 10:50 AM A-27
Schedule No. Item to be
inspected
Brief description of work
7 11KV cable and
cable boxes
i) Clean and examine for damaged bushings.
ii) Check for compound level, if there is leakage.
iii) Perform insulation resistance test,
recondition or replace, where necessary.
iv) Keep continuous records of insulation
resistance.
8 Earthing
System
Replace all broken earth leads and tighten others.
Measure earth resistance of various earths with
earth. Tester. In case of low values, recondition
them.
9 Anti-climbing
devices and
danger plates
etc.
Recondition the anti-climbing devices such as barbed
wire, locks, etc., paint and reprint the danger plated
if defaced.
Annually
R&M Final 2 5/12/2006 10:50 AM A-28
Schedule for the R & M of L.T. Line
Schedule No. Item to be
inspected
Brief description of work Four Monthly 1 Poles stays
Cross-arm
conductors
Insulator
Connectors
Cable boxes
etc.
Same as recommended for these items under
schedule of H.T. Lines (Whether cobwebs, kite
strings etc., hanging on the conductor.
M onthly
2 L.T.Switch Check for the following:
i) If the switch with cover is intact.
ii) If the cable/switch running hot.
iii) Broken cut-outs.
iv) Signs of over-heating/burning on contacts.
v) Proper size of fuse wire.
vi) Safety from rain water etc.
Half Yearly
3 L.T.Switch i) Check lead on the L.T. circuit and replace
the L.T. cable/L.T. switch by higher
capacity one, where necessary.
ii) Replace the damaged L,T.cable with new one
of right capacity.
iii) Examine the switch for smooth operation.
iv) Replace the burnt/cracked cut-outs.
v) Recondition the switch contacts.
vi) Replace the old fuses with new ones of right
capacity.
vii) Tighten all connections.
viii) Ensure that the inlet of the cable into the
switch is plugged with plastic compound to
avoid entry of rain water. Refill, where
necessary.
ix) Clean off the cob web and other nests, etc.,
from the inside of the switch.
R&M Final 2 5/12/2006 10:50 AM A-29
Schedule No. Item to be
inspected
Brief description of work
One to two-yearly
4 (a) Poles
(b) Stays
(c) Cross-
arms
(d) Conductor
(e) Insulator
(f) Connector
(g) Cable
boxes etc.
Same as recommended for these items under
Schedule for H.T.Lines.