scada – rtu interface
TRANSCRIPT
BY S . GANESH BABU
• A formal definition of SCADA system, as recommended by IEEE, is:
• “A collection of equipment that will provide an operator at a remote location with sufficient information to determine the status of a particular equipment or a process and cause actions to take place regarding that equipment or process without being physically present”.
05/03/23 2s ganesh babu
• A power system consists of devices that generate, transmit, and distribute power.
• Power system automation is the act of automatically controlling the power system via automated processes within computers and intelligent I&C devices.
• It consists of three major processes:• data acquisition, • power system supervision,• and power system control, all, working in a
coordinated automatic fashion.
05/03/23 3s ganesh babu
• Data acquisition refers to;• Collecting data in the form of measured analog
current or voltage values,• The open or closed status of contact points.• Control refers to sending command messages
to a device to operate the I&C (A collection of devices that monitor, control and protect the system is referred as instrumentation and control(I&C) system)and power system devices
05/03/23 4s ganesh babu
Measurement and feeding of various parameters such as : Voltage, Current, power, circuit breaker status, and alarms
needs a supporting sub system. The parameters are fed into the substation telemetry
equipment called RTU ( Remote telemetry unit or remote terminal unit).
Analogs: Bus voltage: source : bus potential transformer. and currents in all feeders and transformers: source –
current transformers.
05/03/23 5s ganesh babu
Power in MW, KVAR, Power factor from LV breaker.
Analogue measurements carried out by Industrial standard transducers with an output of 4 – 20mA and 1 to 5v D.C.
05/03/23 6s ganesh babu
Breaker “ON / OFF” status. Alarms for oil, buch’olz, oil and winding
temperature. OLTC positions for transformers. Capacitor banks. All status inputs calls for voltage free
contact terminals.
05/03/23 7s ganesh babu
Central control room monitors a series of mixture of analog and status inputs the frequency of which is decided by the priorities and fleeting events.
Scanning rate depends on nature of substation parameters.
Voltage rating and type of substation. Non fleeting status and analog would require a
scanning rate 0f 2 to 3 minutes. Fleeting and high priority inputs require a
scanning rate of 5 to 10 secs and is decided based on the following factors.
05/03/23 8s ganesh babu
Importance of the substation to the grid. Voltage rating : Higher the voltage rating, the
more the importance, Cost factor, which decides the type of
communication and the choice of the scan rate. Ex: High Speed TDMA link between central
control center and the substation and its exclusivity.
05/03/23 9s ganesh babu
Automatic Switching Emergency Load shedding Re-routing services for station maintenance Automatic transfer schemes Load sectionalizing Custom, automatic reclosing schemes Automatic service restoration Circuit breaker control and interlocking Feeder automation and fault recovery
05/03/23 10s ganesh babu
Protection and Control• Circuit breaker lockout
• Protective relay interface/interaction
• Dynamic protective relay setting for dynamic station topology
Voltage Regulation Management• Load Tap Changer (LTC) control
• Voltage regulator control
• Capacitor control
05/03/23 11s ganesh babu
Transformer Management• Parameter monitoring and alarming
• Real-time modeling
• Interface to existing transformer monitors Automatic System Diagnostics
• Power apparatus health monitoring
• PLC and communications self monitoring
• Report and alarm on IED self diagnostics
05/03/23 12s ganesh babu
Maintenance and Safety
Kirk Key interlock management
Maintenance ‘Lock-out/Tag-out management
Automatic circuit isolation control
05/03/23 13s ganesh babu
Station MMIs – Graphical User Interface (GUI)
Interface real-time single-line displays Interactive real-time breaker and switch
control display On-line operation and maintenance logs Sequence of events recording IED detail displays Parameter trending displays
05/03/23 14s ganesh babu
Increased reliability, lower costs. Forecasting accurate demand supply
management Faster restoration of power in case of a break
down Better active and reactive power management Reduced maintenance cost, conditioning
monitoring Reduce human influence and errors Assists operator for faster decision making Automated meter reading Easy fault diagnosis
05/03/23 15s ganesh babu
Availability of information Analysis of information Decision making Optimized system operation (competitive
environment) Equipment condition monitoring (ECM) Equipment parameters are automatically
tracked to detect abnormalities. Timely action, Extended life ECM IEDs available Sequence Of Events (SOE) recording
05/03/23 16s ganesh babu
A SCADA system generally consists of a master station and a number of geographically dispersed Remote Terminal Units (RTUs), all interconnected to master station via a variety of communication channels.
05/03/23 17s ganesh babu
RTU is the eyes, ears and hands of the Master Station.
In most applications the RTU is the slave of the Master Station, but in some applications the RTU is equipped with internal computational and/or optimizing capabilities.
05/03/23 18s ganesh babu
05/03/23 19s ganesh babu
AVAILABILITY: The availability of the RTU shall
be 0.999 over the 12 month period of maintenance exclusive of communication channel and other purchaser caused down time.
Availability = MTBF / ( MTBF + MTTR)
MTBF = Mean Time between failure
MTTR = Mean Time to repair
05/03/23 20s ganesh babu
RTU consists of:
The protocol processor module Communication module Data processing Module I/O modules for analog inputs Digital input and output RTU signals from transducers, relays, breaker
auxiliary switches, and TVMs. Data transmitted to DCC through
communication media (TDMA and MAR)
05/03/23 21s ganesh babu
Functions of RTU include
Input scanning
Alarm,
And change of state detection.
With high degree of reliability, security and integrity.
05/03/23 22s ganesh babu
The I/O channels are defined based on the need of each substation, and the RTU is configured accordingly.
These modules interface through memory mapping to the micro processor.
The RTU scans analogue and digital data non stop, and stores the analogue information after converting it in its memory.
The RTU’s at each substation are accessed and addressed independently.
The electrical and communication format to the mail port is usually RS 232.
05/03/23 23s ganesh babu
Typical diagnostics and indications provided in the RTU are : Power LED:
Indicates power applied to the base board when switched on. RUN LED:
Indicates healthy operating system. LPAT LED:
Indicates too low voltage on the input side. Watch Dog time out LED. Status LED:
Gives a binary coded output if the system fails a soft ware confidence test.
05/03/23 24s ganesh babu
Diagnostic capability at the I/O module level.
Hardware read back at telecom and output circuit for verification of data at the field connection point.
Verification of memory and certain peripheral chips in operating system.
Communication diagnostics to indicate activity on the receiver and transmitter lines for both main and local ports.
05/03/23 25s ganesh babu
The communication subsystem is the interface between the communication network and the RTU internal logic.
This subsystem receives the messages from the master, interprets the message, initiates action within the RTU, and sends an appropriate response to the master.
05/03/23 26s ganesh babu
PRIMARY COMMUNICATION 64 kbps TDM/TDMA (time division multiple
access operating in 2.3/2.5 GHZ band and the out stations extend to EHV stations.
SECONDARY COMMUNICATION: Is 9.6 KBPS MAR (multiple access
Radio) system operating in 849/943 MHZ band.
Mar remotes are located in all 33/11 kv substations.
05/03/23 27s ganesh babu
05/03/23 28s ganesh babu
The logic subsystem consists of the main microprocessor and the database.
It handles all major processing, time keeping, and control sensing.
It also handles analog-to digital conversions and computation /optimization, if required.
05/03/23 29s ganesh babu
The termination subsystem provides the interface between the RTU logic and external equipment such as the communications lines, primary power source and the substation devices.
These assemblies must be designed to protect the RTU logic from the harsh environment of the station.
05/03/23 30s ganesh babu
The power supply, like the termination subsystem, must meet the various voltage surge standards.
The power supply convenes primary power, usually from the substation battery, to the supply requirements of the other RTUs subsystem.
If a station battery is not available, the unit is normally ordered for ac operation with built-in battery back-up to cover several hours of operation.
Care should be exercised in selecting an ac supply circuit to assure a reliable and stable, noise-fee source.
05/03/23 31s ganesh babu
In addition, occurrences of noise on the communication channel seeks reinforcements in the form of additional master station and RTU hardware and software design to ensure distortion free signal transfer.
Communication channels limit the speed at which data acquisition and control can be performed, thus affecting the master station man-machine interface and applications software design.
05/03/23 32s ganesh babu
05/03/23 33s ganesh babu
05/03/23 34s ganesh babu
The configurations of communication systems are dictated by the following:
Number of RTUs Number of points at RTUs and required
update rates Location of RTUs Communication facilities available Communication equipment and techniques
available
05/03/23 35s ganesh babu
Block diagram for a one-on-one SCADA system configuration, with a master unit for each remote unit
M R 1
M R2
05/03/23 36s ganesh babu
Block diagram for a star or hub SCADA system configuration, with one master unit for several remotes, but with only one remote on each communication channel.
M
R2
R1 R3R4
05/03/23 37s ganesh babu
Block diagram for a party-line SCADA system configuration, with several remote units on a single communication channel.
M
R1 R2 R3 R4
05/03/23 38s ganesh babu
Block diagram for a SCADA system configuration, combining the characteristics of the star and part-line configurations, with one master and several remotes on each of various communication channels
M
R2
R1
R3
R4
R7
R8
R6
R5
05/03/23 39s ganesh babu
05/03/23 40s ganesh babu
Consists of two marshalling boxes accommodating: One, Interfaces the substation equipments with the
RTU. Accommodates transducers, TVM’s, contactors etc., The other panel holds all other radio and
communication accessories along with RTU. The interfacing work at the substation
includes: Erection of SCADA marshalling panel, either
designed and custom made, or fabricated. Fixing of components and accessories, Wiring and dressing of the wires to be connected to
the components.
05/03/23 41s ganesh babu
Transducer
Input 5 A/1A
Output 4-20 mA
05/03/23 42s ganesh babu
Digital data (on/off) may have alarms attached to one state or the other.
05/03/23 43s ganesh babu
Pulse data (e.g counting revolutions of a meter) is normally accumulated or counted.
05/03/23 44s ganesh babu
05/03/23 45s ganesh babu
05/03/23 46s ganesh babu
05/03/23 47s ganesh babu
05/03/23 48s ganesh babu
05/03/23 49s ganesh babu
05/03/23 50s ganesh babu
05/03/23 51s ganesh babu
Laying of 4 core and 10 core cables from the field/ control room to the panel including formation of cable duct where ever required.
Termination of the leads at appropriate points including crimping of lugs and provision of ferrules.
Providing of Earth connection to the marshalling box from the equi-potential bar.
05/03/23 52s ganesh babu
Ensuring vermin proof cable entry points in the marshalling box with the provision of suitable cable glands.
The components that are housed in the SCADA marshalling box are:
AC current transducer to every feeder to measure Y phase current.
Secure make electronic trivector meter for measurement of TVM parameters at power transformer LV breakers.
Voltage transducers to measure HV and LV voltages.
05/03/23 53s ganesh babu
Position transducers to indicate the tap position.
DC voltage transducers to measure D .C. voltage.
48V DC contactors to initiate close and trip pulse to the breaker.
48V contactors to raise and lower taps on the OLTC.
220/24 V contactors for annunciating buch’olz and temperature alarms for each transformer.
05/03/23 54s ganesh babu
05/03/23 55s ganesh babu
Signal cables shall be of a type and installed in a manner so to reduce common-mode and induced noise to a minimum.
Metallic shields shall be employed on all cables. All grounding of shields and signal circuits shall be at one point only to prevent ground loops, except where double shielded cable is used, in which case the outer shield may be grounded at both ends.
05/03/23 s ganesh babu 56
All terminals and terminal blocks shall be clearly identified.
All connectors, cable harnesses and inter – rack wiring shall be clearly identified so that no ambiguity can occur.
Connector pin numbering shall be identical at each and of the cable.
05/03/23 s ganesh babu 57
Supplies DC voltage to RTU and the contactors which activates the operation of OLTC and breaker operations.
05/03/23 58s ganesh babu