    S/N SITE ID ISSUE

    1 PL0009

    Enter current setting at 100A,Modem and Comm config not activated,Exit

    Voltage set at 45V,Battery capacity not inputed on the page,Exit DOD set at

    100%,Fales alarm from Rectifier low volt cable.

    2 PL0020Enter current set at 100A,Modem and Comm config not activated,Exit Voltageset at 44V,Battery capacity not inputed on the page,Exit DOD set at 100%,DG

    Run and on Load not active.

    3 PL0023

    Enter current set at 100A,Modem and Comm config not activated,Exit Voltage

    set at 45V,Battery capacity not inputed on the page,Exit DOD set at

    100%,Inhibit Alarm Clear set at 30 minute,Inhibit Alarm Set at 3 minutes,Mask

    Time setting at 5 minute.

    4 PL0024

    Enter current set at 100A,Modem and Comm config not activated,Exit Voltage

    set at 47V,Battery capacity not inputed on the page,Exit DOD set at 100%,Fan

    Power control not enable.Site presently on on Gen Manual Overide

    5 PL0035Hybrid override enabled.Mask time set at 5minute instead of 0,Emergency fan

    on set point at the same setting with munti AC run.

    6 PL0036

    Rectifier Alarm Active and not changing in state,Hybrid Override active,DG

    runing and DG Loading Alarm not active,BTS/Movenment enabled on hybrid

    suspene config,Hybrid retry set at 60m,Hybrid Inhibit Alarm Clear set at

    60m,Inhidit alarm set at 5m,Hybrid supend delay and mask alarm set at 3 and

    5 minute.

    7 KD0051

    1. Vent power diabled,Exit DOD% set at 100A,Enter current set at

    100A,Battery capacity not entered on the page,Hybrid schedule time put at

    20pm,Comm and Moderm Config not entered.

    8 KD0017DG manual override. On Time Schedule and Off time Schedule wrong.

    Emergency Fan on Set point wrong

    9 KD0029 DG Manual override

    10 PL0007 DG Manual override,fan control checked in hybrid config

  • 7/28/2019 SAM2_analysis(16-10-2012)

    2/6

    11 PL0009 Fan control checked in hybrid config. Site kicked out of hybrid at 48.2V

    12 PL0010DG Manual override,fan control checked in hybrid config, Emergency fan set

    point set at 42C

    13 PL0006Hybrid Override alarm active but doent control hybrid schedule.Enter Voltage

    and Exit DOD set at 100A and 100%.

    14 RV0194Enter Voltage and current set at 48V and 200A,Battery Capacity not

    included,Exit DOD:set at 0,No Rectifier alarms not active.

    15 RV0005

    Rectifier Alarms not active,Aircon control enable for hybrid off time

    period,Mask alarms enabled,delayed time set for 60 minutes.Hybrid time set

    at 9am.

    16 RV0007

    Rectifier alarm not active.Enter current set at 100A,Enter Voltage 48V,Hybrid

    schedule time set at 9pm to 5am.

    17 KT0045Hybrid schedule time set at 19pm,Enter Current 100A ,Exit DOD% set at

    100%,

    18 KD0093Aircon control enable on hybrid time,Enter current set at 100A,Exit DOD% set

    at 100%

    19 KD0070 Enter current set at 100A,enter voltage 48V,Exit DOD set at 100%,

    20 KD0045Rectifier Low Volts alarm comes up once the power goes off for

    hybrid@50V,Enter current,Voltage and DOD set at 100A,48V and 100%.

    21 KN0003

    200A Current probe not enabled,retry Delay set at 60 minutes,Inhibit Alarm

    clear:60minutes ,Inhibit Alarm set:5miutes,hybrid suspended cancel delay:3

    minutes and mask time set at 5 minutes.Exit DOD%:100,Hybrid on time set at

    20pm.

    22 RV0121Mains on load alarms remains unchanged,Enter current and voltage set at

    100A and 48V

    23 PL0018

    Hybrid enter current is too high,DG manual overrride, SAM2 Gen controller

    bad,Humidity/Temperature probe bad,Both Gen run and Gen on load signals

    not terminated

    24 PL0013

    Gen run and Gen onload signal not terminated,DG manual overrride,DG

    startfail,Fan control checked in hybrid config,hybrid exit voltage is below the

    standard value and the firmware is old

  • 7/28/2019 SAM2_analysis(16-10-2012)

    3/6

    25 RV0009 DG Manual override. Gen run and gen on load signals not terminated

    26 AN0002Old SAM2 firmware version installed,current probe not discharging when

    power goes off, battery discharges fast

    27 AN0012old SAM2 firmware version installed,hybrid exit voltage is below the standard,

    hybrid override enabled

    28 AN0069 Old SAM2 firmware DG Manually override

    29 AN0139 old SAM2 firmware version, site battery discharges fast

    30 BY0011DG1 Run and DG on load alarm disconnected, DG manual override,Enter

    voltage and exit voltage values not ok

    31 KD0014Current probe not discharging during hybrid state, site kicks out of hybrid due

    to battery low voltage

    32 KD0025The current probe rating on site is not known, the charging current it displays

    is much

    33 KD0140

    hybrid override checked in both inhibit and suspend column in the hybrid

    config, Hybrid override also checked in the hybrid override box, DG manual

    override,DG1 start fail and the current probe needs checking

  • 7/28/2019 SAM2_analysis(16-10-2012)

    4/6

    RECOMMENDATIONS

    Enter current to be set at 30A,Modem config to be set at 900/1800HZ,Comm config to be set as

    SMS.,Exit Voltage to be set at 46V,Battey capacity to be inputed,Exit DOD to be set at 60%,Low

    Volt alarm cable picked point from the rectifier to be changed due to false alarm send to SAM2

    unit and kicking out site from hybrid.

    Enter current to be set at 30A,Modem config to be set at 900/1800HZ,Comm config to be set at

    SMS.,Exit Voltage to be set at 46V,Battey capacity to be inputed,Exit DOD to be set at 60%,DG

    Run alarm and Gen on Load to be terminated.Site seems to be bypassed as non of the DG

    alarms are active.

    Enter current to be set at 30A,Modem config to be set at 900/1800HZ,Comm config to be set at

    SMS.,Exit Voltage to be set at 46V,Battey capacity to be inputed,Exit DOD to be set at

    60%,Inhibit Alarm Clear set,Inhibit Alarm Set and Mask Time setting to be set at zero.

    Engineer to Log into SAM2,change Enter current to to 30A,Modem config to be set at

    900/1800HZ,Comm config to be set at SMS.,Exit Voltage to be set at 46V,Battey capacity to be

    inputed,Exit DOD to be set at 60%,Uncheck the fan control in the hybrid config

    Hybrid override to be dissabled if SAU not in controll of the Hybrid schedule.,Enter current to be

    change to 50A,Battery capacity to be Inputed.Emergency fan set point time to be set at 38 or 40

    degree.

    Hybrid override to be dissabled if SAU not in controll of the Hybrid schedule.,Rectifier,Gen

    runing and Gen on Load signal to be reterminated.Movenement and Door alarm to be remove

    from Hybrid suspense configuration,Aircon control to be dissable on the hybrid config data

    page,Battery capacity to also be included.Gen 1 emergency stop to be dissabled

    The Enginner should enable Vent Power on Alarm config and Power control on Hybrid config

    page,Exit current to be set at 60%,Battery capacity to be included,Hybrid schedule time to be

    changed from 20.00pm to 18.00pm.

    To resolve the Gen manually override,First put off the DG from AMF, let it rest for a

    minute,start Gen from SAM2,let it load. Put off the Gen from SAM2 observe it for 5mins.If the

    Gen doesn't start simulate hybrid for 30mins.If this doesn't resolve the issue log in to the AMF,

    click on the basic settings and scroll to controller mode and change the status to off. Change the

    On and Off schedule to 18.00 and 6.00.The emergency fan on set point to 35C

    To resolve the Gen manually override,First put off the DG from AMF, let it rest for a

    minute,start Gen from SAM2,let it load. Put off the Gen from SAM2 observe it for 5mins.If the

    Gen doesn't start simulate hybrid for 30mins.If this doesn't resolve the issue log in to the AMF,click on the basic settings and scroll to controller mode and change the status to off

    To resolve the Gen manually override,First put off the DG from AMF, let it rest for a

    minute,start Gen from SAM2,let it load. Put off the Gen from SAM2 observe it for 5mins.If the

    Gen doesn't start simulate hybrid for 30mins.If this doesn't resolve the issue log in to the AMF,

    click on the basic settings and scroll to controller mode and change the status to off. Also

    uncheck the fan control in the hybrid config

  • 7/28/2019 SAM2_analysis(16-10-2012)

    5/6

    unchecked the fan control and also deactivate the rectifier low voltage that pops up at 48.2V

    To resolve the Gen manually override,First put off the DG from AMF, let it rest for a

    minute,start Gen from SAM2,let it load. Put off the Gen from SAM2 observe it for 5mins.If the

    Gen doesn't start simulate hybrid for 30mins.If this doesn't resolve the issue log in to the AMF,

    click on the basic settings and scroll to controller mode and change the status to off. Unchecked

    the fan control in hybrid config and also change the emergency fan setpoint to 35C

    The Engineer should recheck hybrid override cable connections from SAU,Enable hybrid

    override control if hybrid schedule is to be control with SAU.Enter current and exit DOD to be

    30A and 60%.

    Enter Voltage and current to be set at 53V and 30A,Input battery capacity,DOD:60%,rectifier

    alarms to be activated.

    Rectifier alarms to be reterminated,Hybrid seting configuration to be configured with hybrid

    reactivation check list.

    Rectifier alarms to be reterminated,Hybrid seting configuration to be configured with Check list

    guide.

    AC mains fail to be enable or MPF changed,Enter current to be change to 30A,Hybrid schedule

    time to be set at 18pm and 8am,DOD% to 60%

    Aircon control to be disabled,Enter current set at 30A,DOD set at 60%

    Enter current current to be set at 30A,Exit DOD at 60%,Enter Voltage:53V.Battey test can also

    be carried out or rectifier configuration reconfimered if it was properly done.

    Rectifier Low volt alarm to be reterminated,Enter current,voltage and DOD changed to 30A,53V

    and 60%.

    The enginer should Enable the 200A current probe and use the hybrid reactivation check list to

    get recommended hybrid config settings

    Mains on load alarm cable to be reterminated.Enter current and Volatage to be changed to 30A

    and 53V.battery capacity to be entered.

    To resolve the Gen manually override,First put off the DG from AMF, let it rest for a

    minute,start Gen from SAM2,let it load. Put off the Gen from SAM2 observe it for 5mins.If the

    Gen does start simulate hybrid for 30mins.If this doesn't resolve the issue log in to the AMF,

    click on the basic settings and scroll to controller mode and change the status to off,Terminate

    the Gen run and Gen on load signals,Change the humidity/temperature probe lastly, change the

    SAM2 Gen controller.

    Terminate the Gen Run and the Gen on load.;To resolve the Gen manually override,First put off

    the DG from AMF, let it rest for a minute,start Gen from SAM2,let it load. Put off the Gen from

    SAM2 observe it for 5mins.If the Gen does start simulate hybrid for 30mins.If this doesn't

    resolve the issue log in to the AMF, click on the basic settings and scroll to controller mode and

    change the status to off.Uncheck the fan control in the hybrid config, change the hybrid exit

    voltage from 44.0V to 47.0V.Lastly upgrade the firmware to version 2.24

  • 7/28/2019 SAM2_analysis(16-10-2012)

    6/6

    To resolve the Gen manually override,First put off the DG from AMF, let it rest for a

    minute,start Gen from SAM2,let it load. Put off the Gen from SAM2 observe it for 5mins.If the

    Gen does start simulate hybrid for 30mins.If this doesn't resolve the issue log in to the AMF,

    click on the basic settings and scroll to controller mode and change the status to off,Terminate

    the Gen run and Gen on load signals.

    upgrade the firmware to 2.24 version,check the current probe connection and carry out battery

    test using the checklist to ascertain the discharging rateupgrade the firmware to 2.24 version,change the hybrid exit voltage to 46.0V and disable the

    hybrid override

    Upgrade the SAM2 firmware,First put off the DG from AMF, let it rest for a minute,start Gen

    from SAM2,let it load. Put off the Gen from SAM2 observe it for 5mins.If the Gen doesn't start

    simulate hybrid for 30mins.If this doesn't resolve the issue log in to the AMF, click on the basic

    settings and scroll to controller mode and change the status to off. Finally reset the SAM2

    upgrade the firmware and carry-out battery test

    The DG1 Run and DG onload signal cable to be re-terminated.To resolve the Gen manually

    override,First put off the DG from AMF, let it rest for a minute,start Gen from SAM2,let it load.

    Put off the Gen from SAM2 observe it for 5mins.If the Gen doesn't start simulate hybrid for

    30mins.If this doesn't resolve the issue log in to the AMF, click on the basic settings and scroll to

    controller mode and change the status to off

    check current probe connection, change the direction also ensure that the current probe is

    clamp to the right DC power cable( do not clamp both -VE and +VE DC cable

    Engineer to log in to SAM2, go to config data, if the current probe is black (200A) check the box

    then click on set config and get config, if it is blue(500A) uncheck the box and click on set config

    and get config

    First unchecked the hybrid override in both the inhibit and suspend column, change the retry

    delay value to zero , uncheck the hybrid override box and change the HO alarm to zero; confirmif the DG battery is ok and also work on the current probe.Lastly,To resolve the Gen manually

    override,First put off the DG from AMF, let it rest for a minute,start Gen from SAM2,let it load.

    Put off the Gen from SAM2 observe it for 5mins.If the Gen doesn't start simulate hybrid for

    30mins.If this doesn't resolve the issue log in to the AMF, click on the basic settings and scroll to

    controller mode and change the status to off