r&t 2007 - machinery room design - jekel

Upload: andres-veliz

Post on 03-Apr-2018

224 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 R&T 2007 - Machinery Room Design - Jekel

    1/10

    Machinery Room DesignMachinery Room DesignRequirements & Best PracticesRequirements & Best Practices

    Todd Jekel, Assistant Director, IRC Feb. 8, 2007Todd Jekel, Assistant Director, IRC Feb. 8, 2007

    2007 IRC

    Standard DefinitionStandard Definition

    z What is a machinery room?

    zASHRAE 15-2004 3 states:

    a space, meeting the requirements of8.11 and 8.12, that is designed tohouse compressors and pressure vessels

    z 8.11 refers to 7.4, which refers to 7.2z 7.2.2.7 states:

    All refrigerant-containing parts in systems exceeding 100HP (74.6 kW) compressor drive power, exceptevaporators used for refrigeration or dehumidification,condensers used for heating, control and pressure-reliefvalves for either, and connecting piping, are locatedeither in a machinery room or outdoors.

    z What is a machinery room?

    zASHRAE 15-2004 3 states:

    a space, meeting the requirements of8.11 and 8.12, that is designed tohouse compressors and pressure vessels

    z 8.11 refers to 7.4, which refers to 7.2z 7.2.2.7 states:

    All refrigerant-containing parts in systems exceeding 100HP (74.6 kW) compressor drive power, exceptevaporators used for refrigeration or dehumidification,condensers used for heating, control and pressure-reliefvalves for either, and connecting piping, are locatedeither in a machinery room or outdoors.

  • 7/28/2019 R&T 2007 - Machinery Room Design - Jekel

    2/10

    2007 IRC

    Standard Definition (cont.)Standard Definition (cont.)

    z What is a machinery room?

    z IIAR 2-1999

    a space that is designed to safely housecompressors, pressure vessels, or associatedrefrigeration equipment

    No further expansion of

    definition within the bodyof the standard

    z What is a machinery room?

    z IIAR 2-1999

    a space that is designed to safely housecompressors, pressure vessels, or associatedrefrigeration equipment

    No further expansion of

    definition within the bodyof the standard

    2007 IRC

    Location & SitingLocation & Siting

    z Location

    z Ideal

    zGround floor with multiple outside walls

    z Easy access for emergency response

    z Often found realities in older systemszNo outside walls due to facility expansion

    z Basement or upper floor location (formerlyallowed)

    z Location

    z Ideal

    zGround floor with multiple outside walls

    z Easy access for emergency response

    z Often found realities in older systemszNo outside walls due to facility expansion

    z Basement or upper floor location (formerlyallowed)

  • 7/28/2019 R&T 2007 - Machinery Room Design - Jekel

    3/10

    2007 IRC

    EgressEgress

    z Egress & Doors

    zASHRAE 15

    z 8.11.2

    ztight-fitting door(s) opening outward, self-closing if theyopen into the building, adequate in number to ensurefreedom for persons to escape in an emergency

    z 8.12(b)

    z Same as 8.11.2 but says fire doors

    z 8.12(d)

    zshall have a door that opens directly to the outside airor through a vestibule equipped with self-closing, tight-fitting doors

    z IIAR 2 6.3.1.5 (same)

    z Egress & Doors

    zASHRAE 15

    z 8.11.2

    ztight-fitting door(s) opening outward, self-closing if theyopen into the building, adequate in number to ensurefreedom for persons to escape in an emergency

    z 8.12(b)

    z Same as 8.11.2 but says fire doors

    z 8.12(d)

    zshall have a door that opens directly to the outside airor through a vestibule equipped with self-closing, tight-fitting doors

    z IIAR 2 6.3.1.5 (same)

    2007 IRC

    Standard RequirementsStandard Requirements

    zAccesszASHRAE 8.11.8 & IIAR6.1.1.1

    z Accessshall be restricted toauthorized personnel. Doors shallbe clearly markedto indicate this

    restriction.

    z PenetrationszASHRAE 15 8.12(f) & IIAR6.3.1.10

    z All pipes piercing the interior walls, ceiling orfloorshall be tightly sealed to the walls,ceiling or floor through which they pass.

    zAccesszASHRAE 8.11.8 & IIAR6.1.1.1

    z Accessshall be restricted toauthorized personnel. Doors shallbe clearly markedto indicate this

    restriction.

    z PenetrationszASHRAE 15 8.12(f) & IIAR6.3.1.10

    z All pipes piercing the interior walls, ceiling orfloorshall be tightly sealed to the walls,ceiling or floor through which they pass.

  • 7/28/2019 R&T 2007 - Machinery Room Design - Jekel

    4/10

    2007 IRC

    Standard Reqts (cont.)Standard Reqts (cont.)

    z Building materials

    zASHRAE 8.12(c)

    z Walls, floor, and ceiling shall be tight and ofnon-combustible construction. Walls, floor,and ceiling separating the refrigerationmachinery room from other occupied spacesshall be of at least one-hour fire-resistiveconstruction.

    z Building materials

    zASHRAE 8.12(c)

    z Walls, floor, and ceiling shall be tight and ofnon-combustible construction. Walls, floor,and ceiling separating the refrigerationmachinery room from other occupied spacesshall be of at least one-hour fire-resistiveconstruction.

    2007 IRC

    VentilationVentilation

    z ASHRAE 15 8.11.3-5zvented to the outdoors utilizing mechanical

    ventilation

    zone or more power-driven fans To obtain

    reduced airflow for normal ventilation, multiple ormultispeed fans shall be used. Openings for inletair shall be positioned to avoid recirculation. Airsupply & exhaust ductsshall serve no otherarea. The discharge of air shall be to theoutdoors in such a manner as not to cause anuisance or danger.

    z ASHRAE 15 8.11.3-5zvented to the outdoors utilizing mechanical

    ventilation

    zone or more power-driven fans To obtainreduced airflow for normal ventilation, multiple ormultispeed fans shall be used. Openings for inletair shall be positioned to avoid recirculation. Airsupply & exhaust ductsshall serve no otherarea. The discharge of air shall be to theoutdoors in such a manner as not to cause anuisance or danger.

  • 7/28/2019 R&T 2007 - Machinery Room Design - Jekel

    5/10

  • 7/28/2019 R&T 2007 - Machinery Room Design - Jekel

    6/10

    2007 IRC

    Dampers

    Ventilation LayoutVentilation Layout

    LPRHPRINT

    Dampers

    Recommended Area

    of Exhaust Fan(s)

    FreshAirRoll-up

    Door

    2007 IRC

    Ventilation EquipmentConsiderations

    Ventilation EquipmentConsiderations

    z Consider system effects

    z Balance of system pressuredrop & fan pressure rise

    z Consider location ofexhaust & prevailing weather

    z Recirculation

    z Impact makeup air units?

    z Offsite impacts?

    z Consider system effects

    z Balance of system pressuredrop & fan pressure rise

    z Consider location ofexhaust & prevailing weather

    z Recirculation

    z Impact makeup air units?

    z Offsite impacts?

  • 7/28/2019 R&T 2007 - Machinery Room Design - Jekel

    7/10

    2007 IRC

    Equipment SpecificationEquipment Specification

    z IIAR Bulletin 111z Recommends upblast, high velocity

    exhaust fans

    z Considerz Fans that dilute the

    exhaust with fresh airzOften used for laboratory fume

    hood exhaustsz Wetted media exhaust

    systems (scrubbers)

    z IIAR Bulletin 111z Recommends upblast, high velocity

    exhaust fans

    z Considerz Fans that dilute the

    exhaust with fresh airzOften used for laboratory fume

    hood exhaustsz Wetted media exhaust

    systems (scrubbers)

    2007 IRC

    Emergency ControlsEmergency Controls

    z Emergency ControlszASHRAE 8.12(i)

    z Remote control of themechanical equipment in therefrigerating machinery room

    shall be provided immediately outsidethe machinery room door solely forthe purpose of shutting down theequipment in an emergency.Ventilation fans shall be on a separateelectrical control and have a control switchlocated immediately outside the machineryroom door.

    z Emergency ControlszASHRAE 8.12(i)

    z Remote control of themechanical equipment in therefrigerating machinery room

    shall be provided immediately outsidethe machinery room door solely forthe purpose of shutting down theequipment in an emergency.Ventilation fans shall be on a separateelectrical control and have a control switchlocated immediately outside the machineryroom door.

  • 7/28/2019 R&T 2007 - Machinery Room Design - Jekel

    8/10

    2007 IRC

    Ammonia DetectionAmmonia Detection

    zASHRAE 8.11.2.1 exempts ammonia butrequires continuous ventilation at the emergencyamount (8.12(h))

    z Despite this exemption, the use of ammonia detectorsis common

    z Consider using ammonia detectors for bothpersonnel &property protection

    z Personnelz Low level: Audible & Visual Alarms & Ventilation Control

    z Property

    z High level: Machinery Room Shutdown

    z ASHRAE 8.11.2.1 exempts ammonia butrequires continuous ventilation at the emergencyamount (8.12(h))

    z Despite this exemption, the use of ammonia detectorsis common

    z Consider using ammonia detectors for bothpersonnel &property protection

    z Personnelz Low level: Audible & Visual Alarms & Ventilation Control

    z Property

    z High level: Machinery Room Shutdown

    2007 IRC

    Electrical ShutdownElectrical Shutdown

    z Removes power from all non-classified electricalequipment during high ammonia concentrations

    z motors, motor control centers, floats, switches, etc.

    z Why? It reduces likelihood of deflagrations in the event

    of a non-ventilatable releasez Consider what equipment should be operational during

    an emergency situation & specify that equipment with theappropriate classification (NEC Class 1, Div. 2)

    z ventilation fans, emergency lighting, alarms, other equipment

    z Removes power from all non-classified electricalequipment during high ammonia concentrations

    z motors, motor control centers, floats, switches, etc.

    z Why? It reduces likelihood of deflagrations in the event

    of a non-ventilatable releasez Consider what equipment should be operational during

    an emergency situation & specify that equipment with theappropriate classification (NEC Class 1, Div. 2)

    z ventilation fans, emergency lighting, alarms, other equipment

  • 7/28/2019 R&T 2007 - Machinery Room Design - Jekel

    9/10

    2007 IRC

    Safety SystemsSafety Systems

    z Eye-wash & Shower Station

    z Located outside exit door and anotherrecommended inside machinery room(IIAR 2 6.3.1.4 )

    z Consider what you would needIF you need to use it!

    z Temperature appropriate for

    15 minute de-con shower

    zDrench hose

    z Change of clothes

    z Eye-wash & Shower Station

    z Located outside exit door and anotherrecommended inside machinery room(IIAR 2 6.3.1.4 )

    z Consider what you would needIF you need to use it!

    z Temperature appropriate for

    15 minute de-con shower

    zDrench hose

    z Change of clothes

    2007 IRC

    Safety Systems (cont.)Safety Systems (cont.)

    z Passive containment forrecirculators/vessels

    z diking

    z drain to temporary holding tank

    z Tie ammonia detection and fire protectionalarms into auto-paging system

    z Machinery room secured 24/7 with keycard access

    z Passive containment forrecirculators/vessels

    z diking

    z drain to temporary holding tank

    z Tie ammonia detection and fire protectionalarms into auto-paging system

    z Machinery room secured 24/7 with keycard access

  • 7/28/2019 R&T 2007 - Machinery Room Design - Jekel

    10/10

    2007 IRC

    ConclusionsConclusions

    z Familiarize yourself with the minimumrequirements

    z Consider moving beyond minimums

    z Emergency shutdown

    z Spill containment

    z Pseudo-classified space

    z Familiarize yourself with the minimumrequirements

    z Consider moving beyond minimums

    z Emergency shutdown

    z Spill containment

    z Pseudo-classified space

    Questions?Questions?