rp30-5.pdf

Upload: nicholas-garrett

Post on 03-Apr-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 RP30-5.pdf

    1/81

    RP 30-5

    INSTRUMENTATION AND CONTROL

    SELECTION AND USE OF EQUIPMENT

    FOR INSTRUMENT PROTECTION

    SYSTEMS

    November 1993

    Copyright The British Petroleum Company p.l.c.

    http://rpses%20word%20documents/RP30-5.doc
  • 7/28/2019 RP30-5.pdf

    2/81

    Copyright The British Petroleum Company p.l.c.

    All rights reserved. The information contained in this document is

    subject to the terms and conditions of the agreement or contract under

    which the document was supplied to the recipient's organisation. None

    of the information contained in this document shall be disclosed outside

    the recipient's own organisation without the prior written permission ofManager, Standards, BP International Limited, unless the terms of such

    agreement or contract expressly allow.

  • 7/28/2019 RP30-5.pdf

    3/81

  • 7/28/2019 RP30-5.pdf

    4/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE i

    CONTENTS

    Section Page

    FOREWORD................................................................................................................. iii1. INTRODUCTION...................................................................................................... 1

    1.1 Scope.............................................................................................................. 1

    1.2 Application ..................................................................................................... 1

    1.3 Units............................................................................................................... 1

    1.4 Quality Assurance........................................................................................... 2

    2. PROTECTIVE INSTRUMENTATION SYSTEMS................................................. 2

    2.1 General Requirements..................................................................................... 2

    2.2 Choice of Equipment for Protective Systems................................................... 3

    2.3 System Design ................................................................................................ 6

    2.4 Equipment Recommendations ......................................................................... 92.5 Testing............................................................................................................ 13

    2.6 Integrity Assessment ....................................................................................... 14

    2.7 Design Documentation.................................................................................... 16

    3. ALARM SYSTEMS................................................................................................... 18

    3.1 General Requirements..................................................................................... 18

    3.2 Categories of Alarms....................................................................................... 20

    3.3 Measurement Interface.................................................................................... 22

    3.4 Panel Annunciators ......................................................................................... 23

    3.5 VDU Based Annunciators............................................................................... 23

    3.6 Audible Alarms............................................................................................... 253.7 Microprocessor Based Alarm Systems............................................................. 26

    4. FIRE AND GAS DETECTION AND CONTROL SYSTEM.................................. 27

    4.1 General .......................................................................................................... 27

    4.2 Fire and Gas Control Panel Equipment........................................................... 29

    4.3 Annunciation and Display............................................................................... 31

    4.4 Control Actions ............................................................................................. 31

    4.5 Fire Protection System Controls..................................................................... 33

    4.6 Telemetry Systems......................................................................................... 36

    4.7 Field Equipment.............................................................................................. 36

    4.8 Remote Fire and Gas Panels........................................................................... 424.9 Drawings and Documentation ........................................................................ 43

    5. PIPELINE LEAK DETECTION SYSTEMS............................................................ 43

    5.1 Scope.............................................................................................................. 43

    5.2 Requirement for Pipeline Leak Detection ........................................................ 44

    5.3 Design and Selection....................................................................................... 47

    5.4 Operation, Maintenance and Testing ............................................................... 53

    FIGURE 1 - DRAWING SYMBOLS FOR FIRE AND GAS LAYOUTS.................. 55

    FIGURE 2 - TYPICAL FIREPUMP START LOGIC DIAGRAM............................ 57

  • 7/28/2019 RP30-5.pdf

    5/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE ii

    FIGURE 3 - FIRE PUMP CAUSE & EFFECT DIAGRAM....................................... 58

    FIGURE 4 - TYPICAL CONTROL ACTION MATRIX ........................................... 59

    FIGURE 5 - TYPICAL FIRE AND GAS DETECTION SYSTEM BLOCK

    DIAGRAM..................................................................................................................... 61

    APPENDIX A................................................................................................................. 62

    DEFINITIONS AND ABBREVIATIONS............................................................ 62

    APPENDIX B................................................................................................................. 65

    LIST OF REFERENCED DOCUMENTS............................................................ 65

    APPENDIX B1............................................................................................................... 67

    APPLICABLE STANDARDS AND LEGISLATION (UK) FOR FIRE AND

    GAS SYSTEMS................................................................................................... 67

    APPENDIX C................................................................................................................. 69

    TYPICAL FIRE AND GAS VDU PHILOSOPHY ............................................... 69

    C1. GENERAL DESCRIPTION .......................................................................... 69C1.1 Area Mimics................................................................................................ 69

    C1.2 Expanded Mimics........................................................................................ 69

    C1.3 Alarm Banner Area....................................................................................... 70

    C1.4 Bar Chart Displays ....................................................................................... 70

    C1.5 Tabular Switch State Displays (Page Displays) ............................................. 70

    C1.6 Fire Pump/Ring Main Display....................................................................... 71

    C1.7 HVAC Status Displays ................................................................................. 71

    C1.8 Alarm Listings.............................................................................................. 71

    C1.9 Help Displays ............................................................................................... 71

    C1.10 Printer Facilities.......................................................................................... 71C2 ALARM HANDLING..................................................................................... 72

    C3 DISPLAY ACCESS........................................................................................ 72

    C3.1 Direct Access ............................................................................................... 72

    C3.2 Previous/Next Paging ................................................................................... 72

    C3.3 Fast Access .................................................................................................. 73

    C4 DIRECTORY STACK.................................................................................... 73

  • 7/28/2019 RP30-5.pdf

    6/81

  • 7/28/2019 RP30-5.pdf

    7/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE iv

    It is intended to review and update this document at regular intervals, because it is essential to

    maintain BP's commercial advantage from the effective deployment of the rapidly developing

    technology covered by this Practice.

    Application

    'Specification' or 'Approval' actions are indicated by an asterisk (*) preceding a paragraph

    number.

    Text in italics is Commentary. Commentary provides background information which supports

    the requirements of the Recommended Practice, and may discuss alternative options.

    This document may refer to certain local, national or international regulations but the

    responsibility to ensure compliance with legislation and any other statutory requirements lies

    with the user. The user should adapt or supplement this document to ensure compliance for

    the specific application.

    Principal Changes since last Issue

    Principal changes to Sections Issued from March 1991:

    (a) The Practice has been revised to the new format to rationalise the sections and to

    integrate the commentary into the main test.

    (b) The sections have been updated to include references to new standards and reflect

    changes in operating practices.

    (c) Section numbering has been amended to suit the applicable part.

    The cross-references at the end of this foreword show relationships between new documents

    and the old CP 18.

    Feedback and Further Information

    Users are invited to feed back any comments and to detail experiences in the application of

    BP RPSE's, to assist in the process of their continuous improvement.

    For feedback and further information, please contact Standards Group, BP International or

    the Custodian. See Quarterly Status List for contacts.

  • 7/28/2019 RP30-5.pdf

    8/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE v

    LIST OF SECTIONS CROSS REFERENCED TO CP 18

    RP 30-1 TO RP 30-5 CP 18 PARTS AND SECTIONS

    No equivalent in RP 3~X Part 1 (Foreword and Introduction)

    RP 30-1 INSTRUMENTATION AND CONTROL DESIGN AND PRACTICE

    Part 2 Systems, Design and Practice

    Section 1 Introduction E Section 1 Introduction

    Section 2 Control Engineering Principles E Section 2 Control Engineering Principles

    Section 3 Selection of Instrumentation Equipment E Section 3 Selection of Instrumentation

    Equipment

    Section 5 Earthing and Bonding E Section 5 Earthing and Bonding

    Section 6 Instrument Power Supplies E Section 6 Instrument Power Supplies

    Section 7 Instrument Air Systems E Section 7 Instrument Air Systems

    Section 8 Hydraulic Power Systems E Section 8 Hydraulic Power Systems

    Section 9 Control Panels E Section 9 Control Panels

    Section 10 Control Buildings E Section 10 Control Buildings

    Section 11 Instrument Database Systems Section 1I Digital Systems (to RP 30-4, Sect 2)

    + Section 12 Adv. Cntrl Sys. (to RP 30-4, Sect. 5)

    + Section 13 Telecommunications (to RP 30-4, Sect. 3

    RP 30-2 INSTRUMENTATION AND CONTROL SELECTION AND USE OF MEASUREMENT INSTRUMENTATION

    Part 3 Measurement

    Section 1 Introduction E Section 1 Introduction

    Section 2 Temperature Measurement E Section 2 Temperature Measurement

    Section 3 Pressure Measurement E Section 3 Pressure Measurement

    Section 4 Liquid Level Measurement E Section 4 Liquid Level Measurement

    Section 5 Flow Measurement E Section 5 Flow Measurement

    Section 6 Storage Tank Measurement E Section 6 Storage Tank Measurement

    Section 7 On Line Analytical Measurement E Section 7 Measurement

    Section 8 Automatic Samplers for Offline E Section 8 Automatic Samplers for Offline Analysis

    Analysis

    Section 9 Weighbridges and Weighscales E + Section 9 Weighing Systems

    Section 10 Environmental Monitoring

    Section 11 Instrumentation for HVAC systems

    Section 12 Drilling Instrumentation

    RP 30-3 INSTRUMENTATION AND CONTROL SELECTION AND USE OF CONTROL AND SHUTOFF VALVESPart 4 Valves and Actuators

    Section 1 Introduction E Section 1 Introduction

    Section 2 Regulating Control Valves E Section 2 Regulating Control Valves

    Section 3 Power Actuated Isolating Valves ESection 3 Power Actuated Isolating Valves

    RP 30-4 INSTRUMENTATION AND CONTROL SELECTION AND USE OF CONTROL AND DATA ACQUISITION SYSTEMS

    Section I Introduction

    Section 2 Digital Systems (new commentary added)

    Section 3 Telecommunications

    Section 4 Subsea Control Systems

    Section 5 + Advanced Control Systems

    RP 30-5 INSTRUMENTATION AND CONTROL SELECTION AND USE OF EQUIPMENT FOR INSTRUMENT PROTECTIONSYSTEMS

    Part 5 Protective Systems

    Section I Introduction E Section I Introduction

    Section 2 Protective Instrument Systems E Section 2 Protective Instrument Systems

    Section 3 Alarm systems E Section 3 Alarm Systems

    Section 4 Fire and Gas Detection and Control E Section 4 Fire and Gas Detection and Control

    Systems Systems

    Section 5 Pipeline Leak Detection E + Section 5 Pipeline Leak Detection

    E- equivalent (not identical)

    +- yet to be published

    http://rp30-4.pdf/http://rp30-4.pdf/http://rp30-4.pdf/http://rp30-4.pdf/http://rp30-4.pdf/http://rp30-4.pdf/http://rp30-4.pdf/
  • 7/28/2019 RP30-5.pdf

    9/81

  • 7/28/2019 RP30-5.pdf

    10/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 2

    1.4 Quali ty Assurance

    Verification of the vendor's quality system is normally part of the pre-qualification

    procedure, and is therefore not specified in the core text of this specification. If

    this is not the case, clauses should be inserted to require the vendor to operate and

    be prepared to demonstrate the quality system to the purchaser. The quality system

    should ensure that the technical and QA requirements specified in the enquiry andpurchase documents are applied to all materials, equipment and services provided

    by sub-contractors and to any free issue materials.

    Further suggestions may be found in the BP Group RPSEs Introductory Volume.

    2. PROTECTIVE INSTRUMENTATION SYSTEMS

    This Section details BP recommendations for instruments, logic

    systems and valves which make up a protective instrumentation system

    and should be read in conjunction with BP Group GS 130-9'Specification for the supply of Shutdown Systems'. Compliance with

    all applicable statutory regulations at the final point of installation is

    mandatory, and shall take precedence over the basis for design covered

    by this Recommended Practice.

    2.1 General Requirements

    * 2.1.1 BP Group RP 30-6 specifies BP process design requirements for

    protective instrumentation systems and the actions to be taken. A

    system shall be provided to meet these requirements. Where the

    requirements of this Recommended Practice conflict with otherdocuments, the matter shall be referred to BP.

    2.1.2 A schedule should be prepared listing all process conditions to be

    monitored by protective systems. It shall define the limits of safe

    operation and protective action to be taken in the event of a

    transgression. The schedule shall list the consequences of failure on

    demand and the application category.

    2.1.3 Failure of the protective instrumentation shall not cause the plant to go

    to an unsafe condition. The effect of failure of any function or group offunctions should be fully analysed and the results of this investigation

    used to determine the design of the protective instrumentation.

    2.1.4 The action on loss of power supply to protective instrumentation

    system shall cause the plant to trip.

    Systems which energise to trip may be considered for certain Category 2

    applications where spurious operation would cause more serious consequences

    than lost production. In such case a study should be carried out to determine the

    following:-

    http://gs130-9.pdf/http://gs130-9.pdf/http://gs130-9.pdf/http://gs130-9.pdf/http://rp30-6.pdf/http://rp30-6.pdf/http://rp30-6.pdf/http://gs130-9.pdf/
  • 7/28/2019 RP30-5.pdf

    11/81

  • 7/28/2019 RP30-5.pdf

    12/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 4

    Where the system, in addition to providing facilities similar to

    those offered by limited variability systems, provide facilities

    similar to those in a mini-computer based real-time system, e.g.

    displays, high level languages and data links.

    (iv) Pneumatic or hydraulic logic systems. These systems are only

    applicable to simple applications.

    (v) Hybrid system comprising more than one of the above.

    Points to be considered in the application of programmable electronic systems

    include:-

    (a) Failure and Failure Modes

    Because a single microprocessor is often used to execute the logic of the

    application, its, or associated component failure will usually result in

    some or all logic being halted, e.g. plant protection may be lost.

    It is unlikely that the mechanism of failure can be predicted and it is also

    possible that a fault may lie unrevealed. To overcome these two

    difficulties, it is necessary to arrange, usually by external equipment, to

    detect failure and take action (usually by forcing plant outputs to a safe

    state). In addition, to reveal dormant faults, it is necessary to test the

    system regularly. It is therefore of the utmost importance to consider the

    outcome of the failure states in plant design.

    In addition to hardware faults, software problems can occur. Software

    failure cannot occur, but software faults can result either from operating

    system software being insufficiently tested to reveal faults, or from the

    application software being unable to cope with a certain plant condition.The danger is that in each case the fault may lie dormant until a particular

    plant condition is reached and the system then 'fails'. Recognition of these

    two possibilities leads to important strategies concerning the selection and

    testing of the system. In the case of faults in the operating system, these

    can be minimised by selecting a manufacturer who has a standard product

    implemented widely in industry. In the case of application software it is

    necessary to apply strict control of the development process and undertake

    verification of each stage. It is also essential to allow adequate time to

    test the functions of the application software, both at the development

    phase and on the actual plant.

    To minimise problems with software full variability systems should be

    avoided. They should only be considered where the complexity ofapplication requires advanced algorithms.

    Some manufacturers offer designs which are fault tolerant and this can be

    of benefit in applications where high integrity is required.

    (b) Modifications

    Because such systems provide flexibility and convenience in configuring

    logic to meet plant requirements, there is a danger that such flexibility

    applied in an uncontrolled fashion can lead to downgrading of plant

    protection following injudicious modification of application software. It is

  • 7/28/2019 RP30-5.pdf

    13/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 5

    therefore important to ensure that access to, and modifications of, the

    application software is closely controlled.

    (c) Overrides and Interlocks

    Where override or interlock facilities are provided by application

    software, a facility should be provided to ensure that the operator andplant manager are aware that the plant is being operated in such a

    fashion. If the application of overrides is not closely monitored, there is a

    danger that plant protection is gradually downgraded.

    Advantages of programmable systems include the following:-

    (i) Space saving

    (ii) Low power

    (iii) Ease of configuration

    (iv) Ease of reconfiguration

    (v) Fault diagnosis

    (vi) Simple interface to computers

    Disadvantages of programmable systems include:-

    (i) Statutory authorities may impose strict requirements for their

    application on any safety related duty.

    (ii) Hardware and software faults (revealed or unrevealed) may result

    in common mode failure and seriously impair functionality.

    Careful selection of vendor and his proposal is essential to

    ensure:-

    - Vendor has a proven experience in the supply of similar

    sized systems.

    - Vendor has established and effective QA system for both

    hardware and software design and implementation; including

    modification procedures.

    - Bought-in hardware and software complies with above.

    (iii) Additional costs can arise in meeting the software QA

    requirements.

    (iv) Such systems can be complex leading to more difficult and time

    consuming fault finding. This can lead to higher cost of training.

    2.2.3 When programmable systems are provided, their failure modes should

    be fully considered. The systems should be designed such that in the

    event of a system failure the plant is not put into an unsafe condition.

    If failure of the shutdown system could cause an unsafe condition,

    other equipment or systems should be provided to ensure that the plant

    is maintained in a safe state.

  • 7/28/2019 RP30-5.pdf

    14/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 6

    A hybrid system using both discrete logic and programmable systems may provide

    the optimum solution. Hybrid systems also have the advantage of diversity and

    reduce the probability of common mode failure.

    2.3 System Design

    2.3.1 Overall design shall comply with BP Group RP 30-1 and the

    requirements of BP GroupRP 30-6.

    API RP 14Cfor offshore applications requires that each safety system comprise two

    levels of protection to prevent or minimise the effects of an equipment failure within

    the process. The two levels of protection should be independent of and in addition

    to the control devices used in normal process operation. The first method of

    protection is normally instrument based, the secondary method is normally by self

    acting devices such as relief valves.

    Where a Category 1 system is used top prevent hazards arising this may be

    adequate acting alone providing:-

    (a) The system used in complies with the requirements for Category 1 system

    as defined in BP GroupRP 30-6.

    (b) A full integrity analysis has shown that an acceptable standard of safety

    has been achieved.

    (c) The effects of common mode failure has been considered in the reliability

    analysis

    2.3.2 For a Category 1 application a single failure during normal operation

    shall not cause the system to fail to perform its intended function.

    2.3.3 For a Category 2A application involving serious commercial or

    environmental loss, multiple sensors, logic and final actuation devices

    should be used unless evaluation of the additional reliability and costs

    against the probability of reducing business loss can be shown to be

    uneconomic or environmentally unacceptable.

    2.3.4 For a Category 2B application the use of single sensor, logic and final

    actuation device is normally considered adequate.

    2.3.5 In voting systems, precautions shall be taken to avoid degradation of

    the protection through common faults in the system.

    Examples of common mode problems include blockage of single pressure tappings,

    blowing of common supply fuses to input channels, or accidental damage to cables

    run on a common cable tray, or along the same route. Separation of individual

    protection channels is normally required.

    2.3.6 Category 1 systems need not comprise of one discrete system of

    sensors, voting systems and valves.

    http://rp30-1.pdf/http://rp30-1.pdf/http://rp30-6.pdf/http://rp30-6.pdf/http://external%20standards%20organisations.pdf/http://external%20standards%20organisations.pdf/http://rp30-6.pdf/http://rp30-6.pdf/http://rp30-6.pdf/http://external%20standards%20organisations.pdf/http://rp30-6.pdf/http://rp30-1.pdf/
  • 7/28/2019 RP30-5.pdf

    15/81

  • 7/28/2019 RP30-5.pdf

    16/81

  • 7/28/2019 RP30-5.pdf

    17/81

  • 7/28/2019 RP30-5.pdf

    18/81

  • 7/28/2019 RP30-5.pdf

    19/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 11

    The operation of motor operated valve actuators shall be controlled by

    d.c. operated interposing relays, integral with the motor starter. The

    d.c. supply voltage shall be derived from the protective system and shall

    be independent of the contactor control supply.

    The reversing starter, interlocking and signalling switches shall beintegral with the actuator.

    When the operation of two or more electrically operated valves has to

    be interlocked, (e.g. in order to ensure that a bypass valve is open

    before the line main valve is permitted to close and vice versa), this

    interlocking shall be done only in the main electrical contactor circuits.

    The design shall ensure that any interlocks are effective in all 'remote'

    and 'local' modes of control.

    Actuators fitted to emergency shutdown valves on critical applicationsinvolving plant safety shall conform with BP Group GS 130-6 and

    should be provided with transducers for measuring on-line

    performance.

    If the actuator does not reach the required position within a

    predetermined time period after action is initiated, a 'valve fault' alarm

    shall warn the operator. The alarm supply shall be independent of the

    actuator supply.

    Performance measurement is particularly important on large valves where the

    actuator design margin may be reduced by wear or fouling.

    2.4.3 Circuit Modules

    Removal of a plug-in module should initiate a shut-down action to/from

    the system for that module position. Alternatively for Category 2b

    applications the system may remain in the untripped state providing

    diagnostics are provided to indicate to the operator that the system is

    no longer active.

    Modules that need to be calibrated, e.g. analogue input modules,

    should have defeat and test facilities that allow in situ calibration by asingle technician.

    The system as a whole, and each type of module, shall be unaffected by

    radio frequency interference, even when doors or covers are removed

    for maintenance.

    * When the modules incorporate self diagnostic circuitry, the choice of

    alarm or trip action to be taken on detection of a fault, shall be subject

    to approval by BP.

    http://gs130-6.pdf/http://gs130-6.pdf/http://gs130-6.pdf/http://gs130-6.pdf/
  • 7/28/2019 RP30-5.pdf

    20/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 12

    Each output module shall control a separately fused supply to each

    associated actuator. The output fuses shall be individually accessible.

    Plug-in modules should be removable under power.

    2.4.4 System Alarms

    Protective systems should have facilities to monitor failure states.

    There should be alarms for system malfunctions, and for the loss of

    power supplies to the logic and external circuits.

    2.4.5 Power Supplies

    Powersupplies for protective systems shall be Class A as defined in BP

    Group RP 12-5.

    Relay systems shall be segregated into functional loops, each supplied

    through a separate switch and fuse.

    On earth-free systems, double pole power switches shall be used.

    Separate power supplies should be used for actuation circuits unless it

    can be shown that the effect of switching transients is unlikely to effect

    input or logic circuits.

    The filter circuits of input modules and logic power supplies will need to be

    considered to establish adequate rejection of transients.

    Batteries shall be capable of maintaining power for logic and actuating

    devices for pre-defined period following a primary power supply

    failure. (Refer to Section 6 of BP Group RP 30-1).

    The pre-defined period will need to be sufficient to allow an orderly

    shutdown of the process. The period will depend on the complexity of

    the process and the available manning. The period should be agreed

    with those responsible for Operations Management.

    The components of the logic power supplies should be so arranged asto permit any one of them to be removed for maintenance while the

    system stays on line, and under power.

    2.5 Testing

    2.5.1 Facilities to enable on-line testing of protective instrument systems

    should be provided unless adequate reliability can be achieved by

    testing during planned shutdowns. On spared equipment, batch or

    cyclic processes, test facilities for use on line are not required provided

    http://rp12-5.pdf/http://rp12-5.pdf/http://rp30-1.pdf/http://rp30-1.pdf/http://rp30-1.pdf/http://rp12-5.pdf/
  • 7/28/2019 RP30-5.pdf

    21/81

  • 7/28/2019 RP30-5.pdf

    22/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 14

    Test facilities which prevent the system fulfilling its intended function

    should be avoided.

    The frequency and method of testing should be those which have been

    shown by reliability analysis to give acceptable integrity.

    2.5.6 Category 2A Systems

    Category 2A systems with multiple sensors, logic and trip valves should

    be tested as for the Category 1 system. For 2A systems using single

    sensors and logic, the testing will be determined by the reliability

    requirements.

    2.5.7 Category 2B Systems

    Testing on line of final actuator devices may not be required. An

    adequate level of integrity may be achieved by testing at plant or spared

    equipment shutdown.

    2.6 Integrity Assessment

    2.6.1 General

    2.6.1.1 The design of the shutdown systems shall be such to ensure the

    necessary integrity is achieved.

    A system can fail to meet its intended function because of random

    hardware failures or systematic failure.

    Random hardware failure result from a variety of normal degradation mechanism

    in the hardware. The failure rate arising from this type of failure may be predicted

    by reliability analysis providing the accurate failure rate and demand rate data is

    available.

    Systematic failures arise due to errors in design, construction or use of the system

    and cause a system to fail under particular combinations of inputs or under some

    environmental conditions. Systematic failures can be due to errors or omissions in

    the system requirements specification or errors in the design, manufacture,

    installation or operation of the hardware or software. The failure rate arising from

    this type of failure cannot be predicted by reliability analysis.

    In the event of the assessment not being carried out by BP it will be necessary prior

    to the start of the study to ensure that the contractor or consultant has the

    necessary procedures, data and skilled resources to carry out the design

    assessment.

    2.6.1.2 For Category 1 or for those Category 2A applications involving major

    environmental risk, a quantified assessment of the system should be

    carried out to ensure compliance with required hazard rate and

  • 7/28/2019 RP30-5.pdf

    23/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 15

    reliability. The study shall be subjected to detail audit by engineers not

    involved in the design process.

    For Category 2A systems involving economic or minor environmental

    risk, the reliability of systems may be qualitatively assessed by

    considering the extent of redundancy applied in the system design.Where the demand rate is assessed as low and the implications of

    failure on demand are not large then this qualitative assessment may be

    adequate. Where a reliability analysis is judged to be unnecessary for a

    Category 2A application the reasons shall be recorded for approval.

    The use of independent audit should be considered optional, but is

    recommended where major economic risk is involved.

    The local operating management or their representative should agree at

    the design stage the level of maintenance and testing work.

    In carrying out the analysis it is important that the following is agreed with those

    responsible for the process and instrument design.

    (a) The risks to be quantified.

    (b) The events leading to the risks i.e. the fault trees.

    (c) The data to be used for failure rates and demand rates.

    (d) Whether operator intervention can be included.

    (e) The assumptions made on which the validity of the results depend.

    (f) The test procedure and test intervals.

    2.6.1.3 The integrity of the system shall be reviewed throughout the duration

    of the design and operational life. The design case for any changes toassociated process, plant design or assumptions used shall include

    review of the categorisation and quantitive basis for the protective

    system design.

    It is common for protective system requirements to be established from preliminary

    process and plant design. It is therefore essential that these be reviewed once the

    design is changed for validation purposes.

    2.6.2 Quality

    The procedures to be used during each stage of the implementationshould be defined in the project specification. Evidence that the

    procedures have been followed should be provided and included in the

    design dossier.

    The design, manufacture, installation and maintenance of protection

    systems should be carried out using an established quality assurance

    system such as ISO 9000 Series. An audit or review of independent

    external audit (such as establishing if certification is confirmed) shall be

    carried out to establish that the necessary procedures are in place and

    are being followed.

    http://external%20standards%20organisations.pdf/http://external%20standards%20organisations.pdf/http://external%20standards%20organisations.pdf/http://external%20standards%20organisations.pdf/
  • 7/28/2019 RP30-5.pdf

    24/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 16

    The level of overall quality achieved determines the likelihood of systematic

    failures. The quality of procedures used in the design process is particularly

    important since errors or omissions in specification will be carried on through

    implementation and are unlikely to be corrected by later work.

    When considering whether particular equipment is suitable for its intended

    purpose, a significant history of satisfactory operation in a similar environment willbe of benefit. Other evidence such as independent test reports should also be

    considered. The above aspects are particularly relevant where systems involving

    software are being used. For Category 1 systems check lists within the British HSE

    PES document may be used.

    Integrity Assessment Summary

    Category Design Quality Design

    Assessment

    1

    2A (Major

    environmental

    risk)

    Confirmation ofcontractor or

    consultant

    design ability

    and resources

    for design

    process and

    quantitative

    assessment

    Confirmation ofcertificationto

    ISO 9000 series

    or full Quality

    system audit.

    (Compliance audit

    if considered

    necessary)

    Full quantitativedesign audit by

    independent

    specialist

    consultant

    2A (Economic

    or minor

    environmental

    risk)

    As 1/2A above As 1/2A above Optional but

    recommended for

    high economic risk

    applications2B Design

    capability audit

    not required

    As 1/2A above General project

    procedures

    acceptable

    2.7 Design Documentation

    2.7.1 Category 1

    A design dossier shall be maintained for each Category 1 application

    and submitted to BP for approval at successive stages in the project.

    It should be recognised that a change in a control system design or philosophy

    could necessitate a corresponding change in the design of protection systems. For

    example:-

    (a) Replacing a system of single control loop integrity by a distributed shared

    loop system.

    (b) Computer optimisation linking control loops in a manner not envisaged in

    the original design.

    (c) Changing control valve trim size.

    http://external%20standards%20organisations.pdf/http://external%20standards%20organisations.pdf/http://external%20standards%20organisations.pdf/http://external%20standards%20organisations.pdf/
  • 7/28/2019 RP30-5.pdf

    25/81

  • 7/28/2019 RP30-5.pdf

    26/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 18

    2.7.1.12 All reasonably foreseeable failures of the distributed control system

    leading to more than one output failing simultaneously. These shall be

    listed together with details of how hazard associated loops have been

    allocated.

    2.7.1.13 Detailed design drawings showing process, electrical pneumatic,hydraulic and power supply arrangements.

    2.7.1.14 Design specifications for all safety critical items.

    2.7.1.15 Details of independent design audit together with associated report.

    2.7.2 Category 2A

    A design dossier shall be maintained for each Category 2A application.

    The contents of the dossier should be similar to that defined above for

    Category 1 system with the following exceptions:-

    2.7.2.1 For systems involving major economic or environmental risk, the full

    results of the cost benefit analysis and associated reliability studies shall

    be included.

    2.7.2.2 Where the consequences of failure do not include major economic or

    environmental risk the completed check list need only include

    information not related to quantitative analysis.

    2.7.3 Category 2B

    Documentation conforming to general agreed project procedures will

    be adequate.

    3. ALARM SYSTEMS

    This Section specifies BP general requirements for alarm systems.

    3.1 General Requirements

    3.1.1 This Section outlines the requirements for alarm systems provided tofacilitate protection of plant and equipment. Fire and gas alarm

    requirements are given in Section 4 of this Recommended Practice.

    3.1.2 Each plant shall be fitted with alarm systems to draw the operator's

    attention to abnormal process conditions or events. Alarm systems

    shall provide audible and visual warnings of abnormal occurrences in

    the process, utilities and plant equipment (e.g. machinery), and shall

    display the alarm status of each point.

  • 7/28/2019 RP30-5.pdf

    27/81

  • 7/28/2019 RP30-5.pdf

    28/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 20

    3.1.7 Power supplies for alarm annunciators shall as a minimum requirement

    be Class B as defined in BP GroupRP 12-5. Power supply should be

    adequate for the peak load imposed by any lamp test facility.

    3.1.8 Replacement of a modular power supply unit should be possible

    without interrupting the operation of the system.

    3.1.9 Termination wiring and labelling shall be in accordance with BP Group

    RP 30-1Section 4.

    3.2 Categories of Alarms

    3.2.1 General Requirements

    The following basic categories of alarms and status indications shall be

    applied:-

    (a) Emergency Trip Action

    A separate alarm for each input channel to the protective safety

    system shall be provided, as detailed in Section 2 of this

    Recommended Practice.

    (b) Urgent Alarm

    A separate alarm shall be provided for each condition which

    requires urgent operator action, including alarms which precedea trip as defined in Section 2 of this Recommended Practice.

    (c) Information

    A condition to be drawn to the attention of the operator but not

    requiring immediate action on his part, e.g. standby pump

    started, or status of a sequence controller.

    Additional categories of alarms may be provided on digital control and

    sequential logic equipment:-

    (a) Minor Process Alarms

    This category includes facilities such as control loop setpoint

    deviation and rate of change of plant variable.

    (b) Sequence or Logic Alarms

    http://rp12-5.pdf/http://rp12-5.pdf/http://rp12-5.pdf/http://rp30-1.pdf/http://rp30-1.pdf/http://rp30-1.pdf/http://rp30-1.pdf/http://rp12-5.pdf/
  • 7/28/2019 RP30-5.pdf

    29/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 21

    This category includes alarms which require logic to define an

    alarm stage, e.g. the failure of a valve to move on command or

    the timeout of an expected action following a command.

    (c) Control and Instrumentation System Equipment Failures

    This category includes all alarms provided to draw the

    operator's attention to failure of an item of equipment, which

    may be failure of an individual measurement loop (e.g. open

    circuit) or failure of a system module such as a multiplexer or

    microprocessor or communications link which potentially

    affects several measurements.

    3.2.2 Location

    The main alarm display shall be located in the appropriate permanently

    manned control centre, integral with or adjacent to the control and

    monitoring equipment, and shall include all alarms requiring the

    attention of the operators stationed there.

    Additional alarms may be provided and located at local level for plant

    requiring full time or occasional operator attendance.

    * When specified by BP, a self-contained alarm system should be

    provided for plant attended full time by a local operator. The system

    may be located in a local control room or adjacent to the plant.

    Plant normally unattended but requiring occasional local operator

    attention (e.g. for start-up, trouble shooting or maintenance operations)

    should be provided with a local self-contained alarm system. Examples

    of this type of plant are, packaged units, major machinery and a satellite

    production facility.

    Alarm repeats of local alarms, individually or in groups, should be

    provided at the control centre. Details shall be included in the schedule

    (see 3.1.4).

    When a group alarm repeat is accepted, the action of acceptance should

    reset the transmission system to allow subsequent alarms in that group

    to be brought to the attention of the control centre operator.

    Where remote alarms are also required at the control centre, they are usually taken

    back as a single group, a number of groups, single alarms or a combination of

    these. A single group should be used for areas where a single operator only needs

    to visit the area. A number of groups should be used where there is a need to

    define the specific function from an area, e.g. electrical, instrument, machinery or

    process alarms. Single alarms should be used for critical functions which need

  • 7/28/2019 RP30-5.pdf

    30/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 22

    individual operator attention. The grouping of retransmitted alarm functions

    should be fully discussed and agreed with the end user at the design stage.

    Alarms at each location should be accepted independently.

    The alarm logic units for equipment as 3.1.3 (a), (b) and (c) may becentrally housed or mounted behind each alarm panel. Centrally

    housed alarm logic should be in a free standing, ventilated cabinet,

    preferably with both front and back access. Removable gland plates

    should be furnished for cable access.

    The location of the alarm logic units should minimise interference to the operator

    during maintenance operations and plant modifications. Examples of good

    practice are:-

    (a) Integral logic with back access in a conventional control panel.

    (b) Integral logic with front access in a local control panel.

    (c) Remote logic in an equipment area or room, where provided. This method

    is preferred when the alarm display is integrated into a video based

    console.

    3.3 Measurement Interface

    3.3.1 Alarms derived from analogue measurements are preferred.

    3.3.2 When the alarm input is not otherwise measured and transmitted, direct

    switch sensors may be used.

    Direct sensors should be used only where they are more reliable than the function

    measurement and transmission type and where calibration of the equipment is

    possible. However, the cost of the system should also be considered and this

    balanced against the overall requirements of the application.

    3.3.3 Alarms derived from switches should be closed circuit for normal

    operation and open circuit for the alarm condition.

    3.3.4 Sensors shall have ranges selected for effective response, setting and

    resetting at scheduled values of the alarm and normal conditions.Allowance shall be made for any dead-band in switch operation.

    Overrange protection should be provided where necessary.

    3.3.5 Trip alarms should be provided such that the integrity of the shutdown

    system is unaffected (see Section 2 of this Recommended Practice).

    3.4 Panel Annunciators

    3.4.1 Panel mounted annunciators should consist of engraved illuminated

    windows grouped in accordance with the plant units.

  • 7/28/2019 RP30-5.pdf

    31/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 23

    In selecting annunciator window size or the type of read-out (e.g. illuminated and

    engraved windows or LEDs [light emitting diodes] with side descriptors), the

    distance between the normal operator position and the read-out equipment should

    be considered. The nearer the normal operator position is to the read-out

    equipment, the smaller the read-out equipment needs to be. In most cases, it will be

    necessary for the operator to read the alarm description from the normal operating

    position, although in some cases, with experience, knowledge of the position of thealarm in the group will be sufficient.

    When deciding the grouping of alarms, it is necessary to balance what is available

    from manufacturers with the number of alarms for the relevant process unit and the

    operational requirements. Although the system is usually divided by the process

    unit, to assist operator recognition on a unit with a large number of alarms it may

    be better to split alarm displays into a number of sections rather than have a single

    large display.

    3.4.2 The window illumination shall be provided by two bulbs or their

    equivalent. A power healthy indicator shall also be provided for each

    alarm group.

    3.4.3 The windows should be colour coded according to the following:-

    Emergency Trip Action Magenta

    Urgent Alarm Amber

    Information White

    3.4.4 The window engravings should be of the following form:-

    TAG (e.g. 17 PAH 342)

    LOCATION (e.g. RECYCLE COMPRESSOR DISCHARGE)

    ALARM (e.g. HIGH PRESS)

    The engraving for 'Location' should be a concise but definitive

    description of the point location.

    3.4.5 Connections from the central logic cabinet to the alarm annunciators

    should be made with multicore cables of adequate current capacity

    terminated with plugs and sockets.

    3.5 VDU Based Annunciators

    * 3.5.1 This sub-section defines the functional requirements of VDU based

    alarm systems. The precise scheme for each application shall be subject

    to approval by BP.

    3.5.2 Colour and/or text shall be used to denote the alarm/normal states and

    flashing to denote the unaccepted alarm state.

  • 7/28/2019 RP30-5.pdf

    32/81

  • 7/28/2019 RP30-5.pdf

    33/81

  • 7/28/2019 RP30-5.pdf

    34/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 26

    3.7 Microprocessor Based Alarm Systems

    3.7.1 This sub-section covers the requirements for programmable alarm

    systems as defined in 3.1.3 (b), (c), (d) and (e).

    The functional requirements of sub-sections 3.4 and 3.5, as appropriate,shall be satisfied.

    3.7.2 The effect of common mode failures on alarm scanning and display

    shall be stated by the vendor. Redundancy techniques should be

    employed to minimise the effects of common mode failures within

    equipment and its power supply system. The routing and connection of

    critical alarms should be carried out in a manner which maximises

    overall system availability.

    Where redundant equipment is used, specific attention should be given to areas in

    which common mode failures could occur. For example, in a duplicated multiplex

    system with common switching equipment, a common mode fault could occur in the

    switching equipment and negate the beneficial effects of duplication. Redundant

    equipment should be regularly exercised on-line, preferably on an automatic cyclic

    basis.

    In-built diagnostic facilities should warn the operator of faults in the on-line and

    back-up equipment.

    The designer should ensure that the design is not compromised by external failures,

    such as in the power supply system. Quality of the supply (e.g. voltage stability,

    transients) should be addressed. This is covered in greater detail in BP Group RP

    30-4 Section 2.

    3.7.3 The maximum system response time to a burst of alarms shall be

    specified by the vendor.

    A burst of alarms, sometimes known as a flood of alarms, is a situation where one

    plant event can trigger many subsequent events over a short time period. Bursts of

    alarms which are likely to occur should be established in conjunction with the plant

    designer or end user, as appropriate. Normal and abnormal circumstances should

    be addressed, as should the interactive nature of plants connected to the system.

    The response time of the alarm system should be taken as the time lag in processing

    and displaying any single alarm which is initiated within a burst of alarms. Thislag should not significantly reduce the margin allowed by the plant designer for

    operator action following alarm initiation from the primary sensor.

    3.7.4 Urgent alarm limits shall only be altered under the protection of a key

    (or equivalent) security system. Minor alarm settings, e.g. deviation,

    may be modified by the plant operator.

    3.7.5 All software alarm routines should be provided with an adjustable

    deadband, to minimise oscillation into and out of alarm. Alteration of

  • 7/28/2019 RP30-5.pdf

    35/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 27

    the deadband shall be under the same security protection as for alarm

    limits in 3.7.4.

    * 3.7.6 The time resolution of alarm and event logging shall be subject to

    approval by BP. Recording format should be as 3.5.9. A convenient

    method of distinguishing between alarm and event messages should beprovided on printouts.

    Systems should have the facility to store alarm and event history, with

    printout only on demand. Measures to assure security of information

    on loss of power supply and on equipment failure should be provided.

    3.7.7 The following additional requirements shall apply to alarm systems to

    be operated as an integral part of a proprietary distributed control or

    computer system; as defined in paragraphs 3.1.3 (d) and (e).

    All categories of alarms should be connected to the control system and

    be provided with alarm annunciation and presentation facilities at the

    operator's work station.

    It should be possible to apply alarm facilities to derived plant values.

    The system design should ensure that the operator's control facilities

    are not hampered by processing a burst of alarms.

    See 3.7.3 for definition of 'burst of alarms'. A burst of alarms may overload the

    control system and delay other functions (e.g. key board actions) in addition toalarm response.

    4. FIRE AND GAS DETECTION AND CONTROL SYSTEM

    4.1 General

    4.1.1 The scope and application of fire and gas detection, alarm and control

    systems depends upon the inherent risks associated with the materials

    being processed and the layout and size of the installation. Guidance

    on system application is given in BP Group RP 30-7.

    This Section details BP recommendations for fire, flammable and toxic

    gas detection and control systems equipment, and should be read in

    conjunction with BP Group GS 130-10 'Specification for the supply of

    Fire and Gas Systems'. The recommendations also apply to systems

    supplied as part of self contained package units.

    To minimise spares holdings and maintenance every effort should be made to

    ensure the package unit equipment (specially the detectors) offered is the same as

    that used in the main F&G system.

    http://rp30-7.pdf/http://rp30-7.pdf/http://gs130-10.pdf/http://gs130-10.pdf/http://gs130-10.pdf/http://rp30-7.pdf/http://gs130-10.pdf/
  • 7/28/2019 RP30-5.pdf

    36/81

  • 7/28/2019 RP30-5.pdf

    37/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 29

    energising and re-energising of the logic circuitry will not cause accidental

    initiation of normally de-energised control actions.

    For Intrinsically Safe circuits utilising Zener barriers both the positive line and the

    negative return line should have separate barriers even if the negative lines are

    tied to earth at the power supply. Use of a single barrier on the positive side only,

    runs the risk of the signal return by-passing the negative return to the power supplyvia the IS earth. Galvanically isolated barriers are the preferred approach.

    4.1.5 The Fire and Gas System shall be designed and installed to facilitate in-

    service testing, maintenance, calibration and repair. Due regard shall be

    made for safety of personnel and access of equipment.

    4.2 Fire and Gas Control Panel Equipment

    4.2.1 All FGCP's and annunciation displays should preferably be located in a

    non-hazardous area such as a control or equipment room.

    The equipment should be suitable for use in the environment in which it

    is located. In controlled environments, account must be taken of the

    possible loss of heating and ventilation under abnormal conditions.

    Points which require particular attention during the assembly of the fire and gas

    panels include:-

    (a) Where front access only panels are used, withdrawal facilities shall be

    provided to enable easy access to termination's etc. The withdrawal

    facility shall provide self support of the equipment when withdrawn from

    the panel and any flexible cabling shall be adequately guarded againstscuffing, kinking, and undue tension.

    (b) Visibility of indications. Visibility of panel modules and their indicators is

    necessary as well as the annunciation of displays. If the panel has doors

    for protection of modules or to prevent unauthorised access, the doors

    shall be provided with see through panels.

    (c) Cooling and ventilation of the panel should be designed to cope with the

    heat generated by a fully equipped panel, even if supplied with 25% spare

    capacity. Where panels are fitted with ventilation systems for cooling

    purposes the air intakes shall be protected with suitable dust filters, and

    fan failure alarms should be provided.

    4.2.2 The FGCP should be designed with spare capacity to allow for any

    known future requirements and also a contingency allowance for design

    development changes.

    The purchase of a fire and gas system is frequently committed before detector and

    control action requirements are fully defined. This can result in considerable

    growth. Under these circumstances, it is prudent to allow a larger than normal

    capacity for expansion and typically 25% may be considered.

  • 7/28/2019 RP30-5.pdf

    38/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 30

    4.2.3 All incoming detector field circuitry shall interface with modules which

    must be compatible with the field sensors.

    Flammable gas detector interface modules must have sufficient gain adjustment for

    doubling the LEL% sensitivity to methane plus any subsequent deterioration in the

    detector during its normal lifetime.

    4.2.4 The system should provide the following:-

    (a) Monitoring of all components of the detection circuit up to and

    including the last sensing element, and shall generate a fault

    signal in the event of any malfunctions.

    (b) Lamp test facilities.

    (c) Latching alarm to ensure short duration alarms are captured.

    Facilities should be provided for remote latch reset where localreset is impractical (e.g. unmanned installations). An alarm

    indication shall override fault indication.

    At the remote control point alarm acceptance should silence the sounder

    and steady the indications at the local panel as well as silencing the

    sounder and steadying indications at the remote control point itself.

    (d) Supervisory facilities to enable the failure of any power supply,

    fuse, etc., to be quickly identified and located.

    Compliance with the British Standards listed in Appendix B is not a statutoryrequirement and their guidance is open to some interpretation depending on the

    installation. The following presents some areas where deviations or points of

    contention may occur and interpretations that should be acceptable:-

    (a) The onset of a detectable level of the hazardous condition at the detector

    and annunciation at the CCR shall not exceed 8 seconds.

    (b) The initiation of a manual call point and annunciation at the CCR shall

    not exceed 3 seconds.

    (c) In the case of flame detectors, which are more likely to operate

    simultaneously, the alarm response should not be prevented.

    (d) The lack of short circuit detection in fire detection loops is acceptable

    provided that a short circuit fault producing an alarm condition is an

    acceptable operating mode.

    4.2.5 The number of circuits connected to individual input/interface modules

    should be such that failure of that module does not significantly reduce

    the level of protection provided for the facility.

  • 7/28/2019 RP30-5.pdf

    39/81

  • 7/28/2019 RP30-5.pdf

    40/81

  • 7/28/2019 RP30-5.pdf

    41/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 33

    For electronic data processing computer rooms, there is greater risk of external

    fire due to paper debris from print outs etc. The consequence of loss of data in the

    event of a fire situation can be quite important.

    A fine water spray arrangement is currently preferred to quench any fire external

    to the computer equipment. It is essential that the consequence to the equipment,

    as a result of initiation of such extinguishant be investigated and agreement soughtfrom the equipment vendor. The design of the system should be such to avoid

    ingress of extinguishant into the cabinets.

    The computing equipment should be shut down on detection of problems from

    detectors located in the room and inside the cabinets. The shutdown should be

    after a time delay to allow for back up of current data.

    4.5.1 Fire Water Pumps

    4.5.1.1 All types of fire water pumps shall be provided with the means to

    manually stop and start the machine locally. Only the start facility is

    required from the FGCP. Additional fire pump start push-buttons at

    selected remote locations should be provide where there is any risk of

    loss of access to the pump locations during incident situations.

    Additional remote start facilities can be provided dependent on plant layout and

    operating procedures. Typically an onshore facility will have an on-site fire

    fighting unit with it's own control point (e.g. fire station). In this instance remote

    start facilities would be provided at the central control room and the fire fighting

    control point.

    Under confirmed combustible gas conditions in the duty fire pump room, control

    logic should be provided to prevent the fire pump from starting, and enable thestart of the stand-by fire pump. Lockable means shall be provide for over-riding

    this trip.

    4.5.1.2 Duty/standby selection should be provided at the FGCP with adequate

    indication to allow the operator to determine the operational status of

    each pump.

    Automatic duty pump start-up should be initiated from the FGCP by

    one of the following:-

    (a) Deluge discharge pressure high.

    (b) Sprinkler flow switch high.

    (c) Confirmed fire detection.

    (d) Main pump failure to start or low fire main pressure.

    The design of the pump control system should be such that automatic

    duty pump start-up does not induce excessive pressure surges on fire

    monitors and fire hoses.

  • 7/28/2019 RP30-5.pdf

    42/81

  • 7/28/2019 RP30-5.pdf

    43/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 35

    (e) One or more sets of four lamp visual warning clusters, at each

    entrance to the protected area, showing the status of CO2 or

    other gaseous total flood system and its controls. Audible

    warning 'on discharge' klaxons or sirens should also be

    provided. It should be audible throughout the area protected by

    the extinguishing medium and should provide sufficientwarning, typically 15 secs, prior to release of extinguishant to

    enable personnel to safely evacuate the area and for dampers to

    close.

    Where visual warning lamps are used on offshore installations,

    consideration should be given to using extinguishant status lamps as

    follows:-

    System manual - lamp colour green

    System auto - lamp colour amber

    System discharged - lamp colour red

    System electrically isolated - lamp colour white.

    Each indicator shall have a twin lamp arrangement.

    (f) Main and reserve systems where provided should have manual

    selection on the skid and an electrical key switch at the FGCP.

    Extinguishant systems may be provided with stand-by systems which

    should be manual initiation only. The intention of these arrangements is

    to allow quick return to normal operation after a discharge of

    extinguishant. The stand-by should not be considered as 'second shotfacility' and any remote change-over facilities should preferably be

    avoided, or if required be interlocked with key switches.

    (g) All extinguishant isolating valves should be monitored via limit

    or proximity switches to indicate they are fully open.

    4.5.3.2 Deluge system solenoid valves should operate by venting the air

    holding the deluge valve closed. Each deluge system should be fitted

    with a low pressure switch for remote indication of loss of vent air.

    Each sprinkler system branch should be fitted with a flow switch toindicate the operation of the system.

    Deluge systems may be provided with the facility to stop deluge remotely at the

    control point on offshore installations on a fire area basis. Where manual control

    of the deluge is required for fire control purposes which uses water curtains and/or

    sub-divides deluge systems within fire areas, consideration may be given to

    grouping deluge controls in a Deluge Control Panel.

  • 7/28/2019 RP30-5.pdf

    44/81

  • 7/28/2019 RP30-5.pdf

    45/81

  • 7/28/2019 RP30-5.pdf

    46/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 38

    Ultra Violet Flame Detectors should. Built-in test facilities should be

    provided for checking the detector on line.

    It should be noted that UV detectors are particularly susceptible to smoke and oil

    deposits on the lenses causing loss of sensitivity. Optical integrity should consist of

    a UV source mounted such that the UV radiation path includes the detector lenses.

    Ultra violet detectors should be used in areas where a fire is not likely to generate

    smoke. Ultra violet detectors should only be used in combination with smoke or

    heat detectors.

    4.7.1.6 Infrared Flame Detectors

    Infrared Flame Detectors should respond to radiation equivalent to the

    CO2 absorption band. They should be solar blind and their response to

    other sources of radiation should be minimised. Built-in test facilities

    should be provided for checking the detector on line.

    Point type smoke and heat detectors are not suitable for open areas and fire

    detection coverage should be by optical flame fire detectors with IR detectors the

    preferred choice for hydrocarbon areas. Areas covered by optical flame detectors

    in certain instances may be supplemented with smoke (beam type) or heat (fusible

    loop, linear).

    The smoke and heat detection used in combination with optical flame detectors

    should be selective in approach and is intended to provide firstly for other control

    actions beyond those initiated by the early detection of fire by the flame detectors,

    and secondly in certain circumstances to supplement the optical detection. For

    example:-

    (a) In well bays the optical detectors are intended for detection of fires at

    their initial stages and initiate appropriate alarms and control actions

    (release of deluge) without necessarily shutting down the wells. This

    protection will be inadequate for sudden large fires due to catastrophic

    failures which may threaten the platform structure itself. The addition of

    temperature type detectors (such as fusible loops) is provided to initiate,

    say, down-hole well shut-off valves.

    (b) In areas where the fire can result in large quantities of smoke which can

    accumulate or gravitate to predictable locations, beam type smoke

    detectors should be used as a supplement to the optical flame detection.

    In congested areas it may not be possible to cover a risk area fully with

    optical detectors. Linear heat detectors should be used to supplement the

    optical flame detection.

    (c) An alternative means of heat detection is the frangible bulb or fusible link

    used with fire protection systems.

    The infrared (IR) flame detectors should be on separate circuits from the heat or

    smoke detectors and independently initiate any control actions.

    4.7.1.7 Combined Ultra Violet/Infrared Flame Detectors

  • 7/28/2019 RP30-5.pdf

    47/81

  • 7/28/2019 RP30-5.pdf

    48/81

  • 7/28/2019 RP30-5.pdf

    49/81

  • 7/28/2019 RP30-5.pdf

    50/81

  • 7/28/2019 RP30-5.pdf

    51/81

  • 7/28/2019 RP30-5.pdf

    52/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 44

    This document is not intended to cover those checks for pipeline leaks

    such as visual inspection by line walking and overflying. Hand held and

    aircraft mounted equipment for detecting the presence of hydrocarbons

    or other substances are also excluded from this document.

    5.2 Requirement for Pipeline Leak Detection

    5.2.1 Regulatory and Legislative Framework

    There is little in the way of national or international legislation

    concerning the provision of pipeline leak detection systems, or the

    capabilities of such systems. It is likely that more specific guidance will

    be given in the next few years but this is unlikely to be of a prescriptive

    or legislative nature. The USA is the exception to this where it is

    expected that prescriptive legislation will be introduced.

    Whereas, in general, the provision of leak detection is unlikely to be the

    subject of prescriptive legislation, there is likely to be an increasing

    demand on operators to demonstrate that all reasonable precautions are

    being taken to avoid and mitigate the effects of any possible

    environmental hazards.

    In the UK, offshore pipelines are covered by legislative requirements relating to the

    provision of leak detection, but only in the general sense. Onshore pipelines have

    no specific leak detection requirements, although a leak detection system might

    form part of a particular pipeline's safety notice. The nature of any system to be

    installed and operated would normally be agreed with the appropriate local

    regulatory authority prior to the granting of a pipeline operating licence. Section

    5.3 provides guidance in selecting the most appropriate technology.

    UK law currently requires the developer of any project likely to affect the

    environment to undertake an environmental impact assessment and to provide 'a

    description of the measures envisaged in order to avoid, reduce and if possible,

    remedy the significant adverse effects'.

    5.2.2 Risk Assessment

    If not prescribed by legislation, the requirement for pipeline leak

    detection will be determined by risk management considerations.

    An environmental risk assessment should be carried out for eachpipeline system. The depth and complexity of the assessment will be

    very much dependant on the particular pipeline. The factors which will

    influence the environmental risk assessment will include:-

    - the environmental sensitivity of the areas affected by the

    pipeline routing (e.g. areas of special scientific interest,

    proximity of shorelines, rivers and water courses, density of

    human population)

  • 7/28/2019 RP30-5.pdf

    53/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 45

    - the fluid carried by the pipeline

    - the likely causes of pipeline leakage. Causes of pipeline leakage

    can be divided into five main categories:-

    - internal and external corrosion- third party damage- operational error- natural hazards- mechanical failure

    An examination of the likely causes of failure will provide an indication

    of the most likely leak (hole) sizes and hence leakage rates.

    The potential risk to the environment and the potential for financial loss

    are closely linked. The financial risk associated with pipeline leakage

    arises from:-

    - value of lost line contents

    - clean-up costs associated with loss of line contents

    - the possibility of a large scale clean-up operation hindering the

    repair and re-instatement of the pipeline system.

    - temporary or permanent loss of pipeline operating licence

    - damages or fines imposed by criminal or civil courts

    - loss of Company image as an environmentally concerned

    operator, thereby impeding future applications for operating

    licences.

    In the case of liquid carrying pipelines the most environmentally sensitive routings

    would include subsea and those close to shorelines, rivers and water courses. In a

    marine or river environment, a relatively small quantity of liquid hydrocarbon will

    be spread over a great area and can potentially cause a disproportionately large

    amount of damage. Clean up costs for this type of spill can therefore be

    considerable, making preventative and loss limiting measures cost effective. Toxiceffects from the release of unstabilised sour crudes also requires consideration if

    the pipeline is routed in proximity to populated areas. This hazard is discussed

    under gas transportation below.

    Leakage of chemicals, particularly those soluble or miscible with water, once

    released into marine or river environments are virtually impossible to recover. In

    this case the clean up costs arise from the necessity to neutralise as far as possible

    the harmful effects of the released chemicals. Additionally the claims for damages

    arising out of pollution to water supplies are potentially very large. Against this

    potential liability, preventative and loss limiting measures might be seen as cost

    effective as well as being environmentally desirable. The toxic effects from

  • 7/28/2019 RP30-5.pdf

    54/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 46

    chemicals released into the atmosphere also require consideration if the pipeline is

    routed in proximity to human population.

    The pipeline organisation CONCAWE maintains statistics of pipeline operation

    including reported spillage's. These statistics are broken down into a number of

    pipeline classifications and can therefore be used as a basis for estimating the

    likelihood of leakage from various causes on a particular pipeline.

    *Leakage's from hydrocarbon gas transportation pipelines have much smaller

    potential for environmental pollution than leakage's from liquid carrying lines.

    The environmental effects are limited to the release of greenhouse gases into the

    atmosphere. Further, the quantities of gases involved are likely to be relatively

    small compared to releases from natural sources. The main problems associated

    with leakage from a hydrocarbon gas line are those of high levels of radiation from

    an ignited leak, and the toxic effects of impurities in the gas. The potential risks

    associated with leakage of sour gas (H2S) in proximity to human population are

    considerable. In this case the automatic leak detection system might also require

    the executive ability to shutdown, isolate and possibly de-pressurise the pipeline.

    In the case of long pipelines the ability to isolate sections in sensitive areas mightalso be required.

    5.2.3 Performance Targets for Pipeline Leak Detection

    A performance target for the leak detection system should be set, based

    on the conclusions of the environmental risk assessment discussed in

    the previous section.

    The performance target should aim, where practical, to reduce the

    impact of the risks identified to a level capable of gaining wide

    acceptance. The performance target should in any case significantlyreduce the impact of the risks identified. Once a performance target is

    theoretically established an analysis of the potential technology in terms

    of Leak Detection Systems can be carried out. If the performance

    target derived from the risk assessment is known to be unachievable in

    practical terms then a Leak Detection System based on the 'best

    available technology' should be specified.

    The following could form part of a performance target, either singularly

    or in combination.

    - minimum detectable leakage rate or sensitivity

    - speed of response (possibly as function of leakage rate)

    - maximum acceptable false alarm rate

    As an example, if the major risk identified was thermal radiation from a leaking gas

    or LPG line, then the performance target should comprise a minimum detectable

    leakage rate. With the surrounding vessels and structures designed to withstand

    say a 10 kw jet fire, then the minimum detectable leakage rate should be the

    flowrate equivalent of the 10 kw fire.

  • 7/28/2019 RP30-5.pdf

    55/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 47

    As a further example, if the major risk identified was leakage of crude oil into

    coastal waters, then the performance target would probably comprise a speed of

    response as a function of leakage rate. If the oil spill response facilities were

    capable of containing say a 10 tonne oil spill under typical conditions, then a

    measure of the required speed of response for the leak detection system would be

    30 minutes for a 20 tonne/hr leak and 2 minutes for a 300 tonne/hr leak.

    5.3 Design and Selection

    5.3.1 General Criteria

    The design and selection of an automatic leak detection system will be

    influenced by the following:-

    - The performance target for the leak detection system. The

    setting of a performance target is discussed in the previous

    section.

    - The capabilities of the available leak detection systems in

    meeting the performance target, given the nature and operating

    conditions of the particular pipeline. Outlines of well

    established and developmental systems for leak detection are

    provided later in this section.

    - The availability of existing facilities (or the requirement for

    facilities in the case of a new pipeline) which could form part of

    a leak detection system. An example of this would be meteringequipment installed for fiscal purposes.

    - Existing integrity checking techniques carried out on the

    pipeline (inventory balances based on tank gauging for

    example). The selected leak detection method should be

    complimentary to any existing techniques by providing

    increased sensitivity or speed of response.

    The number of alarms produced by a leak detection system that indicate

    a genuine leak will be few in number. Indeed if appropriate pipeline

    integrity measures are taken, zero genuine leak alarms could be hopedfor over the lifetime of the system. Therefore, in order to maintain the

    credibility of a leak detection system the spurious or false alarm rate

    needs to be maintained at a suitably low level. A system with a high

    false alarm rate will tend to be discounted and not provide the intended

    protection.

    The design and selection of a leak detection system is very much

    dependent on the individual characteristics and circumstances of a

    particular pipeline. However the following outlines of automatic leak

  • 7/28/2019 RP30-5.pdf

    56/81

  • 7/28/2019 RP30-5.pdf

    57/81

  • 7/28/2019 RP30-5.pdf

    58/81

  • 7/28/2019 RP30-5.pdf

    59/81

  • 7/28/2019 RP30-5.pdf

    60/81

  • 7/28/2019 RP30-5.pdf

    61/81

  • 7/28/2019 RP30-5.pdf

    62/81

  • 7/28/2019 RP30-5.pdf

    63/81

  • 7/28/2019 RP30-5.pdf

    64/81

  • 7/28/2019 RP30-5.pdf

    65/81

  • 7/28/2019 RP30-5.pdf

    66/81

  • 7/28/2019 RP30-5.pdf

    67/81

  • 7/28/2019 RP30-5.pdf

    68/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 60

  • 7/28/2019 RP30-5.pdf

    69/81

  • 7/28/2019 RP30-5.pdf

    70/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 62

    APPENDIX A

    DEFINITIONS AND ABBREVIATIONS

    Definitions

    Standardised definitions may be found in the BP Group RPSEs Introductory Volume.

    The following general definitions are applicable to all Parts of this Recommended Practice:-

    contract: the agreement or order between the purchaser and

    the vendor (however made) for the execution of the

    works including the conditions, specification and

    drawings (if any) annexed thereto and such

    schedules as are referred to therein.

    cost of ownership: the life cost of a system including initial supply

    contract value, installation cost, ongoing support

    costs (e.g. spares, maintenance and service charges).

    Ex: electrical apparatus protected to meet hazard

    classification in accordance withBS 5345.

    works: all equipment to be provided and work to be carried

    out by the vendor under the contract.

    The following definitions apply to Part 4 of this Recommended Practice:-

    addressable system: a system in which analogue or digital signals from

    each head (detector or manual callpoint) are

    individually identified at the control panel.

    addressable head module: the control panel mounted unit in an addressable

    detection system interfacing with the field equipment

    via a data highway, handling alarm and fault

    detection functions. Also know as an Addressable

    Loop Interface Module (ALIM).

    circuit: the most precise identification in a hard-wired

    detection system of the location of an alarm within

    the fire area.

    control action: an output from the control panel that can initiate

    extinguishant discharge, request ESD action, stop

    fans and close fire dampers etc. Control actions are

    divided into two groups per fire area for inhibit

    functions:-

    http://external%20standards%20organisations.pdf/http://external%20standards%20organisations.pdf/http://external%20standards%20organisations.pdf/
  • 7/28/2019 RP30-5.pdf

    71/81

  • 7/28/2019 RP30-5.pdf

    72/81

  • 7/28/2019 RP30-5.pdf

    73/81

  • 7/28/2019 RP30-5.pdf

    74/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 66

    BP GroupRP 32-6 Inspection and Testing of In-Service Instrumentation

    (replaces BP CP 52)

    BP GroupRP 44-1 Overpressure Protection Systems

    (replaces BP CP 14)

    BP GroupGS 112-2 Electric Motor Operated Valve Actuators for

    Intermittent Operation of Isolation Valves

    (replaces BP Std 152)

    BP GroupGS 130-6 Actuators for Shut-Off Valves

    BP GroupGS 130-9 Specification for the Supply of Shutdown Systems

    BP Group GS 130-10 Specification for the Supply of Fire and Gas Systems

    http://rp32-6.pdf/http://rp32-6.pdf/http://rp44-1.pdf/http://rp44-1.pdf/http://gs112-2.pdf/http://gs112-2.pdf/http://gs130-6.pdf/http://gs130-6.pdf/http://gs130-9.pdf/http://gs130-9.pdf/http://gs130-10.pdf/http://gs130-10.pdf/http://gs130-9.pdf/http://gs130-6.pdf/http://gs112-2.pdf/http://rp44-1.pdf/http://rp32-6.pdf/
  • 7/28/2019 RP30-5.pdf

    75/81

  • 7/28/2019 RP30-5.pdf

    76/81

  • 7/28/2019 RP30-5.pdf

    77/81

  • 7/28/2019 RP30-5.pdf

    78/81

  • 7/28/2019 RP30-5.pdf

    79/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 71

    C1.7 HVAC Status Displays

    Separate mimic displays shall show the status of each HVAC system in

    a single line diagram format.

    C1.8 Alarm Listings

    Standard alarm listings shall be available, detailing tag number, alarm

    type, location and time, on a rolling alarm principle. Each line shall be

    tagged, and shall indicate the time of occurrence.

    Alarm text shall be shown red flashing until accepted, changing to non

    flashing indication.

    Fault and inhibit text shall be shown yellow flashing until accepted,

    changing to non flashing indication.

    Status text shall be shown in white with the above accept facilities.

    There shall be two alarm listings, one 'current' showing fire, gas,

    manual call point and fault. A second alarm listing shall be available for

    historical records and maybe sorted for display on either a device type

    basis and/or a time period basis via the directory.

    The historical alarm listing shall be capable of listing all events and

    operator actions. Storage capacity shall be capable of holding on filethe last 2500 events.

    C1.9 Help Displays

    The system vendor shall incorporate any required 'help' actions

    applicable to his system.

    C1.10 Printer Facilities

    All alarms received into the system shall be available on hard copy from

    the printer on demand. Each entry shall comprise a full line identical tothe historical alarm listing display. Events to be logged shall include

    the following:-

    Incoming alarms and faults

    Output actions

    Inhibits

    Alarm accepts

    Alarm resets

    System faults

  • 7/28/2019 RP30-5.pdf

    80/81

    RP 30-5INSTRUMENTATION AND CONTROL - SELECTION AND USE

    OF EQUIPMENT FOR INSTRUMENT PROTECTION SYSTEMS

    PAGE 72

    C2 ALARM HANDLING

    For both Area and Expanded Mimics, the sensor symbols which are not in alarm are

    presented green on black. This way, shape recognition is possible, but the symboldoes not attract attention.

    Whenever a sensor goes into alarm the status indication at base of display area shall

    start flashing and the audible alarm will sound. It is now p