refrigerators manual 7

67
8/20/2019 Refrigerators Manual 7 http://slidepdf.com/reader/full/refrigerators-manual-7 1/67  Raker Appliance Repair Professionals, Inc. Refrigerators and Freezers Manual 7 Harry D. Raker

Upload: appliance799

Post on 07-Aug-2018

228 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 1/67

 

Raker

Appliance Repair Professionals, Inc. 

Refrigerators and Freezers

Manual 7

Harry D. Raker

Page 2: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 2/67

 

Copyright © 2003 Harry D. Raker

All rights reserved.

ISBN 0-976228-66-1 (Volume 7)ISBN 0-976228-60-2 (27 Volume Set)

Table of Contents

Page 3: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 3/67

 

Manual 7

Refrigerators and Freezers

Introduction ........................................................................................ 1The Freon System and the Evaporator............................................................. 3

The Capillary Tube ...................................................................... 5The Condenser .................................................................................. 9Freon System Refinements................................................................................ 12Leaks and Pressures ........................................................................ 13Restrictions ............................................................... 15Overheated Compressors ................................................................................ 17Inefficient Compressors ............................................................................ 19Burned Out Compressors ................................................................. 20Replacing a Failed Compressor .................................................... 21Refrigeration Temperatures ................................................................. 26Air Flow and Control Settings........................................................................... 28

Understanding Frost-Free systems ................................................................. 33Diagnosing Frost System Failures...................................................................... 38Component By Component................................................................................ 40Defrost Clock Diagnosis .................................................................................... 42

Condenser Fan Motors ..................................................................................... 47Evaporator Fan Motors ...................................................................... 48Door Switches ................................................................................ 50Cold Controls ........................................................................................ 51Door Gaskets ................................................................................... 52Typical Component Layout.................................................................................. 55Typical Wiring Diagram....................................................................................... 56

Sample Flat Rate .............................................................................................. 57Examination ..................................................................................................... 58Examination Answers ......................................................................................... 60

Page 4: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 4/67

 

Refrigerators &

FreezersIntroduction 

instein is featured on the lessoncover for a very good reason. Toa novice, repairing refrigerationsystems seems utterly impossible.

From their point of view, you need to bean Einstein to understand and fix one.

Refrigerators offer no easy clues as towhat is wrong, most of the time they diequietly. Seldom are the moving partsvisible.

A Bottom Freezer from the 60’s

This is great news for us!  It keeps out

the meddlers and Mr. Fix-it types. Weget more work at higher prices.

Refrigeration repair requires very carefulattention to subtle clues. It is moreessential than ever to listen to thecustomer. It is also important todelicately approach refrigerationsystems. Key information can be lostand diagnostic time wasted if the wrongapproach is used. A refrigeration systemis a fragile and easily disturbed.

In this lesson we will learn how a freonsystem works, how to diagnose it , andhow to repair its components.

Fig071_01

A New SubZero Side-By-Side

E

Page 5: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 5/67

 

Refrigerators and Freezers page 2 Copyright © 2008 Harry D. Raker

In some ways, refrigerators are easier torepair than other appliances. Forinstance, they all utilize the exact sameoperating theory. They all operate onfreon gas. Also, a great many parts are

interchangeable between brands andmodels. We don’t have to concernourselves with many different designslike we do on washing machines. Thereare some differences, but they are notdramatic. Brands are so similar that it is possible to be working on a refrigeratorand not even know what brand you arefixing!

In order to properly repair refrigerators,

it is necessary to thoroughly understandhow the freon system works. This, ofcourse, is the heart of the coolingsystem.

 Uncle Harry’s

Story Time

 In the early stages of my appliance

repair career, I was somewhatintimidated by refrigeration systems.

 Back in the 70’s, they seemed mysteriousto me. For years, I refused service callson them and concentrated on laundryequipment. (Oh, the money I must haveturned away.)

Service techs were always talking about"back pressure", "charging","evacuating systems" , "restrictions","dryers". I really didn't know what they

were talking about.

 As luck would have it, about 1979, Ibought an old company, Reliable ServiceCo. Inc. It was a major expansion,doubling the size of my company fromthree to six trucks. Along with the new

company came three service men, and alot of refrigeration work.

 It wasn’t too long before I realized that

the servicemen that came with thecompany were largely incompetent.Very quickly, I was forced to learnrefrigeration. Refrigerators were

 popping up that none of my techs could properly repair.

 As it turned out, the dreadedrefrigeration wasn't so bad after all.Today, I enjoy refrigeration calls. Theyare good moneymakers; they're clean,

and the work is relatively simple.

 It's like learning to swim, you have to jump into the water. Eventually, Ibecame better than any of the men. Thatwas because I understood the freontheory better. 

Page 6: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 6/67

 

Refrigerators and Freezers page 3 Copyright © 2008 Harry D. Raker

The Freon System 

irst, the word "system" refers to the piping that carries the freon around

to various sections of the

refrigerator. It is silver-soldered shutand often referred to as the “sealedsystem.” To understand the sealedsystem, it is necessary to understandfreon gas.

Freon has a number of peculiar properties that make it ideal for a

refrigeration system. It is an odorless,

colorless, non-corrosive, non-

flammable, cheap (it used to be), non-

poisonous gas. It’s most important property is that it turns into a liquid atfairly low pressures. At normal roomtemperatures, 70°F, freon turns from agas into a liquid at about 70 lb. persquare inch. If you buy a can of freon atthe store, it is full of a liquid. The pressure in the tank, is around 70 psi.

Propane is a similar gas. When you buyit for your grill, it also a liquid under

 pressure, You can feel the liquidsloshing around in the tank. Like freonif you exhaust it to the air, it turns into agas.

Have you ever noticed that a propanetank gets frosty when propane is rapidlyexhausted from the tank? Freonoperates much the same way. The lawsof physics dictate that when a liquidevaporates into a gas, it absorbs energy.

Evaporation is a Cooling Process

This is the key to all freon systems.Simple enough! We will trace the freon path through a complete refrigerationcycle, beginning at the evaporator.

The Evaporator 

s liquid freon enters the freezersection of all refrigerators, it boils

from a liquid into a gas and absorbs

heat from the surrounding chamber. The boiling takes place within the

evaporator. The evaporator is a longaluminum coil of tubing that looks verysimilar to a car radiator.

If you shut off the fans and listen, youcan actually hear freon boiling as itenters the swelled section, known as theexpansion bulb, of the evaporator. Youcan hear it trickling and bubbling and

 boiling as it works its way through theevaporator. If you had X-ray eyes andcould see inside the evaporator, youwould see droplets of freon boiling intoa gas. The freon is gradually pumped bythe compressor from the inlet to theoutlet of the evaporator.

The boiling temperature of the freon is15 °F below zero. As it boils, it freezesthe evaporator. A finger will stick

against a cold evaporator

F A

Page 7: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 7/67

 

Refrigerators and Freezers page 4 Copyright © 2008 Harry D. Raker

.

Fig071_02

Page 8: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 8/67

 

Refrigerators and Freezers page 5 Copyright © 2008 Harry D. Raker

The Capillary Tube

o attain correct temperatures, theamount of freon that enters the

evaporator must be carefully

controlled. On large commercialrefrigeration systems the flow controlleris called an “expansion valve.” Ondomestic refrigeration systems acapillary tube controls the flow. Acapillary tube is also known as a“metering device.”

It is a long thin copper tube. Freon backs up at high pressure behind thecapillary waiting to squirt out the hole at

the end. The coiled, tiny ten-foot tuberestricts the flow of freon like the pinhole in the end of a water pistol.Freon squirts out the end of the capillarytube and into the evaporator expansion bulb.

Fig071_03

T

Page 9: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 9/67

 

Refrigerators and Freezers page 6 Copyright © 2008 Harry D. Raker

Freon enters the evaporator as a liquid,evaporates and leaves as a low-pressuregas.

Freon evaporation will drop thetemperature to 15°F below zero on thesurface of the evaporator!

Fig071_04

Page 10: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 10/67

 

Refrigerators and Freezers page 7 Copyright © 2008 Harry D. Raker

Chilled freon gas exits the freezercompartment and travels back to thecompressor.

Consider the following refrigeration

design problem. As freon leaves thefreezer section it is a chilled gas and itmust flow back to the compressor. Inthe summer time, condensate will formon the cool return line. The condensateis much like that which forms on coldwater pipes in the summer. Potentiallythis wet return line can cause rust anddripping down the back of therefrigerator. And sometimes it does!

This problem is prevented in two ways.The first solution we will cover now, thesecond later. Looking on the back of a

refrigerator, there is only one insulatedfreon line. It is the line from theevaporator back to the compressor. It iscovered with black foam rubber to

minimize condensate problems.

 Uncle Harry’s

Trick of the Trade # 92

Identify the freon return line by lookingfor the black insulation. To identify thelines connected to the compressor feelthe two lines that enter and exit. Theinlet line will be cool and the exit ordischarge line will be hot.

Fig071_05

Page 11: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 11/67

 

Refrigerators and Freezers page 8 Copyright © 2008 Harry D. Raker

Cool freon gas returning from theevaporator enters the compressor at alow pressure of 1-2 pounds per squareinch (psi). The compressor pumps the

freon up to about 150-180 lb. psi. Itoperates very much like an aircompressor. Instead of air, arefrigeration compressor compressesgaseous freon.

The laws of physics again intervene:

If a gas is compressed in a

confined space, its temperature

will rise. 

Consequently, the compressor and thegas being compressed and dischargedget hot. Incidentally, this heat is theenergy that was absorbed by the boilingfreon from the food compartments.Almost magically, freon flow hastransferred heat from inside of the box tothe outside! Now the problem is how toget rid of the heat.

Fig071_06Typical Compressor Jammed Under A Refrigerator

Page 12: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 12/67

 

Refrigerators and Freezers page 9 Copyright © 2008 Harry D. Raker

The Condenser 

he hot pressurized gas from thecompressor enters another long

series of steel tubes that are very

similar to the evaporator..

This second series of tubes is called thecondenser. It is positioned eitherunderneath or up the back of therefrigerator. They are always painted black and zigzag back and forth just like

the evaporator. The condenser is used toradiate the heat out of the hot freon.

Fig071_07

T

Page 13: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 13/67

 

Refrigerators and Freezers page 10 Copyright © 2008 Harry D. Raker

Freon as a high-pressure gas enters thecondenser. As the gas makes its waythrough the condenser, it gradually chillsdown and condenses into a liquid. . This

is the exact reverse of what happenedinside the evaporator within the freezer.

Picture the condenser as operatingexactly like cooling coils on amoonshine still. Freon is equivalent tothe moonshine trickling out of the still’scopper coils.

Condensers are made in two differentways, static and fan cooled. A static

condenser uses room air currents to coolthe freon as it flows through the coils. Ifthe coils are folded into a small spacenot enough air will flow to sufficiently

cool the freon. A condenser-cooling fanis necessary. Static condensers are usedon smaller and older refrigerators.

 Newer and more expensive refrigeratorsare larger and generate more heat. Theyall require a condenser-cooling fan.Also, installing the condenser below thefood compartment, allows therefrigerator it to be jammed against thewall or installed in a tight cabinet- (Zeroclearance.) Instead of the hot airflowing up the back wall, it now flowsout the front . Cats love this warm spot.

Fig071_08

Page 14: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 14/67

 

Refrigerators and Freezers page 11 Copyright © 2008 Harry D. Raker

Jamming the condenser into tight

quarters in a boon for the service business. The fan constantly sucks inlint and animal hair clogging thecondenser.

The combination of the compressor andthe condenser is often known as the“condensing unit”. Together theycondense freon from a gas into a warmliquid. A similar pair of components sitsoutside your house. It is called an “air

conditioning condenser” and performsthe same function.

The evaporator for your air conditioner

sits in the furnace chamber.

At the outlet of the condenser, the nowliquid freon has cooled down to roomtemperature. After freon leaves thecondenser, it goes through a filter ordryer to clean out any impurities. Dirtmay come from the compressor oil orany corrosion inside the system. Theoutlet of the dryer is the input to thecapillary tube.

Page 15: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 15/67

 

Refrigerators and Freezers page 12 Copyright © 2008 Harry D. Raker

This is where our story first began andwe have completed one full cycle of thefreon system.

Heat within the freezer compartment was captured by theboiling freon and transferred into heat driven off the

condenser and into the surrounding room.

Fig071_09

An Overview of the Complete Freon System

Page 16: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 16/67

 

Refrigerators and Freezers page 13 Copyright © 2008 Harry D. Raker

Freon System Refinements 

ome bright engineer, realized that ifthe capillary tube is soldered to the

return line from the evaporator, two

 positive things could be accomplished atthe same time.

1. The slightly warm freon making itsway through the capillary tube to theevaporator would get even cooler if itwere snuggled up against the cool freoncoming back from the evaporator.

2. The warm capillary tube helps towarm up the return line slightly resulting

in less chance of condensate.

As mentioned previously that there aretwo methods of preventing condensatefrom forming on the return line from theevaporator. Soldering the capillary tubeto the return line is the second method.

The soldered section of tubing is calledthe “cap and suction” line. If the solder

fails condensate will form on the cap andsuction line.

 Uncle Harry’s

Trick of the Trade # 93A separated cap and suction line can berepaired with plastic cable ties.

This freon sealed system is a very highlyengineered and sophisticated. It is pre-set at the factory to run like a digitalwatch and is not really designed to betampered with. The system is hard-

soldered shut and with rare exceptionhas no access valve. The amount offreon in the system is very carefullyweighed to fractions of an ounce. Thesystem is balanced out, so that freoncoming back from the evaporator is atexactly the right pressure as it enters thecompressor.

Understanding System Problems 

reon systems fail in three ways:

1. A leak and a loss of freon.

2. A restriction or clogging in the lines.

3. Compressor failure.

S

F

Page 17: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 17/67

 

Refrigerators and Freezers page 14 Copyright © 2008 Harry D. Raker

1. Leaks and Pressures within

the Freon system

he freon pressure returning to thecompressor is known as “back

 pressure.” As mentioned before theamount of freon is adjusted to stabilizeat a backpressure of 1-2 psi. If somefreon leaks out the system, the backpressure drops. This is known as a

“short system”. As the compressorkeeps trying to suck freon from the lines,it drops the backpressure into a vacuum.Eventually there is not enough freon toadequately fill and cool the evaporator.

Instead of being evenly frosted, all of thefreon will boil away near the expansion bulb.

Fig071_10

Examples of Partially Frosted Evaporators

T

Page 18: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 18/67

 

Refrigerators and Freezers page 15 Copyright © 2008 Harry D. Raker

Leaks can occur in both the evaporatorand the condenser. Condensers,sometimes, have a loop that sits in thedrain pan underneath the refrigerator.The heat from the hot freon helps to

evaporate the defrost water. In somecases the loop carries compressor oilinstead of freon. For our purposes, itdoesn’t matter.

 Naturally, these loops rust in the water, perforate, and allow the freon to leakout. SubZero refrigerators are knownfor rusted through condenser loops.Water can then get into the system.Water creates havoc in a freon system.

It causes rust inside the steel condenserlines and ice crystals to form at the endof the capillary tube. A systemcontaminated with water is basicallytrashed.

Evaporators are made of aluminum andthe capillary and return lines are copper.Welding two dissimilar metals togetheris extremely difficult. It can only bedone with special welding equipment.

Even though the factories do their best,the junction between the two metalsremains a weak spot. Evaporator leaksusually form at the joints where thecapillary tube or the return line arewelded to the aluminum evaporator.

Human interference is another majorcause of leaks. Sometimes freon linesare damaged during a move. More oftenthey are punctured. In the trade this is

often called “the ice pick trick”. Smallmanual defrost units are the main problem. Customers get impatient withthe defrost process and use an ice pick tochip away accumulated ice. They puncture the exposed evaporator coils.

 Uncle Harry’s

Trick of the Trade # 94

In spite of anything you might hear to

the contrary, there is no reliable

method for repairing a punctured

evaporator. Once an evaporator is punctured it must be replaced.

Fig071_11

Page 19: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 19/67

 

Refrigerators and Freezers page 16 Copyright © 2008 Harry D. Raker

2. Restrictions

nything that blocks the flow offreon is called a “restriction.”

Restriction problems are more

common than leaks. They result in asimilar frost pattern. When the system isrestricted insufficient freon gets to theevaporator and poor cooling results.

Fig071_12

A

Page 20: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 20/67

 

Refrigerators and Freezers page 17 Copyright © 2008 Harry D. Raker

Restrictions usually occur at the inlet oroutlet of the capillary tube.

Any tiny fragments will be sufficient toclog the inlet. The in line dryers arehelpful, but not perfect.

Any moisture in the system will freezewith the freon as it evaporates at theoutlet of the capillary tube. Tiny icecrystals are sufficient to plug up thesmall tube. In fact the dryer’s job is toabsorb water along with dirt.

An overheated or burned out compressorwill create contamination.

By checking temperatures, it is possibleto separate a restriction from a leak. Anempty or dry system will not have anyfreon to pump. Therefore, the condenserwill not be hot. The compressor will be

only warm to the touch; no gas is beingcompressed to generate heat.

Page 21: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 21/67

 

Refrigerators and Freezers page 18 Copyright © 2008 Harry D. Raker

In contrast, the condensing unit of arestricted system will be very hot. The poor compressor will be pumping freoninto a totally blocked condenser. Thegas pressure will reach the compressor

limits of 200-300 psi. The compressorand some or all of the condenser will betoo hot to touch.

 Uncle Harry’s

Trick of the Trade # 95

Develop a habit of feeling all the freonlines as you work. Diagnosis becomes

easier when you know the proper

temperatures of each one.

GE, in recent years, has had atremendous number of problems with itsnew style compressor and condenser.The redesigned units were first sold inthe middle 80’s and are easily identified by brown door gaskets. Apparently,restrictions are frequently occurring in

the condensing system. There have beena great number of failures during and beyond the customary 5-year warranty period.

GE has reacted by extending thewarranty to 10 years on a pro-rata basis.Customers can get a condenserreplacement in the 6th, 7th or 8th yearfor about $200.00. With the extendedwarranty, the repair cost averages about

half the normal price. GE mechanicshave gotten so good, that they can do asystem replacement in less than twohours. This is about half the normaltime. They must get a lot of practice.

3. Compressor Failures

ompressors fail in four ways:

1. Overheating, binding and locking

up.

2. The internal valves fail and little or nofreon is pumped. They become“inefficient”.

3. The motor windings short or burn out.

4. They begin making strange noises.

5. External starting and safety devices

fail.

Fig071_13

C

Page 22: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 22/67

 

Refrigerators and Freezers page 19 Copyright © 2008 Harry D. Raker

1. Overheated Compressors 

y far the most common compressorfailure is overheating. All

compressors have a high limit

thermostat mounted on the side. Thethermostat operates exactly like a dryerlimit. It opens when the set temperatureis exceeded. It also opens if thecompressor draws too much current.

The safety emits an audible click and breaks the compressor circuit.Fortunately, overheating is seldom fatal.The cause is often elsewhere and can becorrected. Once the compressor cools

down, it usually resumes normaloperation.

The common cause of overheating is aclogged condenser. Frequent cleaning by the homeowner is needed.

The second most common cause is a blocked or bad condenser fan motor.

Tight compressors 

tight compressor is much like aseized gasoline engine. A bearingor a piston has galled to the shaft or

the piston wall. The unit becomes toohard to turn and overheats or simplylocks. Some failing compressorscontinue to work under normalconditions, but fail on hot days.

Knowledgeable mechanics often call

these “high wattage compressors.” Highwattage refers to the current draw of thecompressor. A dragging compressorwill draw more current ,as it tries to perform its necessary duties. The excesscurrent will generate more heat andeventually cause the overload to

operate. It is possible to spot a highwattage compressor with an Amprobe bycomparing the rated current to that

observed.

Usually, careful observation will providethe same information. Most of the timecompressors are not just half bad, theyare completely shot.

The life of some dragging compressorscan be extended with a “hard start kit.”A hard start kit replaces the startingrelay and limit mounted on the

compressor. It includes a strongcapacitor designed to give thecompressor a jolt, during the first fewseconds of startup.

Hard start kits are successful in onlyabout one-third to one-half the cases.When they work it is almost like amiracle. Instantaneously, a lockedcompressor comes back to life. Keep inmind that that they are not a cure all.

They only buy time in most cases. Some basic problem is still lurking.

B

A

Page 23: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 23/67

 

Refrigerators and Freezers page 20 Copyright © 2008 Harry D. Raker

Fig071_14 Relays and Overloads

Page 24: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 24/67

 

Refrigerators and Freezers page 21 Copyright © 2008 Harry D. Raker

2. An Inefficient Compressor

f a valve fails within the compressor,freon will not be pumped and nocooling will take place. Its external

temperature can identify an inefficientcompressor. The compressor dome willonly be slightly warm, instead of hot tothe touch. Also the discharge line will be at room temperature.

The compressor is not hot because nowork is being done.

A dry system, one without freon, will actthe same way.

 Uncle Harry’s

Trick of the Trade # 96

Detecting a dry or weak compressor

While the refrigerator is running unplugit, and immediately plug it back in. Agood refrigerator will immediately clickoff the overload safety. It will take tento fifteen minutes to restart. A goodcompressor is unable to start up againstthe normal operating head pressure of

150 psi. Time must allowed for the

discharge freon pressure to die down.

A bad compressor or a dry system willdevelop no head pressure. It will restartimmediately.

I

Page 25: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 25/67

 

Refrigerators and Freezers page 22 Copyright © 2008 Harry D. Raker

3. A Burned Out Compressor

 burned out compressor has badinternal wiring. Either thewindings are shorted together or

open circuited. Either case is easy todiagnose.

There are two methods.

One is to remove the connector from theside of the compressor and test theresistance with an ohmmeter. It isnecessary to test between each pair ofterminals. It is also necessary to test fora short between the windings and the

outside dome. Unfortunately, theresistance reading for a good winding is

very low and hard to accurately measure.A short to the dome is easy to find.

Second method:

 Uncle Harry’sTrick of the Trade # 97

The fastest and surest way to diagnose a bad compressor is to hook up a “hardstart kit” and plug it into the troublelight. If the compressor runs, lookelsewhere for the problem. If it doesn’t,you know for sure, the problem isinternal.

Fig071_15

Hard Start Kit Being Installed

A

Page 26: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 26/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker22

4. Strange Noises

he pump within the sealed dome sitson springs. It quietly bounces as it pumps. The springs, and the

external rubber grommets holding thedome in place, are designed to minimizenoise.

As the refrigerator ages, the mountinggrommets get hard, and transmitvibration to the cabinet. Customerssometimes complain of noisycompressors. Either a simpleexplanation, or replacing the rubbermounts is needed.

If one of the internal springs breaks, the

motor tilts within the dome and mayactually hit the side when it shuts off.This banging makes a very distinctrapping sound. Nothing can be done,short of replacing the compressor.Before too long, the sharp rapping will break something inside the dome.

 Uncle Harry’s

Story Time

 I had an old refrigeration mechanic fora short time, prior to his retirement. Acustomer called in during hisemployment and described the broken spring noise. Old Joe said,

“Oh, tell her, she’s got “stopper”.”

 All the young mechanics looked at him. Before long, one took the bait.

“OK, Joe, what’s a “stopper.”

 First he explained where the noise came from. Then, he smiled and said, “Well,

boys, one of these days, it’s going to stop.” 

Replacing a failed compressor

eplacing a bad compressor variesfrom hard to impossible. The best

situation occurs if the compressorquietly dies, and creates nocontamination during its demise.Unfortunately, failures are usually a lotmore dramatic. The more heat and burning involved, the more difficult thereplacement job. When a compressor burns out, massive destruction occursinside the sealed dome.

During the failure process, freon has been continually pumped through the burning motor, spreading debristhroughout the system. Needless to say,the dirt will pile up at the entrance tocapillary tube and clog up. It only takesone tiny speck of dirt to restrict thesystem

Compressor replacement is an art form.

In addition to accepted standards, eachmechanic develops his own style. Allsorts of tricks of the trade have beendevised to replace burned-outcompressors. The difficulty centersaround cleaning out the freon system. Incase of a burnout, the best solution isreplacement all of the systemcomponents, not just the compressor. Itis recommended to replace both theevaporator and condenser too.

T

Page 27: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 27/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker23

If they are not replaced, good techniquerequires that the condenser andevaporator be unsoldered from thesystem and blown out with high-pressuregas. Hopefully, this will blow out any

accumulated debris. The gas is forced infrom the exhaust end of the evaporator.It goes through the capillary backwardsand cleans it.

Often a clean rag is wrapped at the outletto detect any traces of dirt. In the past,freon was the handy ideal cleaning gas.With the new EPA restrictions, this is nolonger allowed. Instead, a can ofnitrogen is used. Once the rag shows no

signs of dirt, the mechanic prays thatthere's no left over debris lodged in thesystem. It is then soldered backtogether.

 Uncle Harry’s

Story Time

Years ago, a customer convinced us toreplace a burned out compressor. Therefrigerator was really too old for the

repair, but they wanted it. Thecompressor was tightly fitted, andoverall a difficult replacement.

 I felt confident in accepting the job, eventhough it was a tough burnout. I had thebest refrigeration mechanic, in

 Baltimore, working for me. Mymechanic had been doing system work for over 30 years.

 After about a week, we got a callback onthe job. The system was restricted. Wecleaned and evacuated it a second time.

Of course, we were even more carefulthan on the first time.

 After about a week, we got anothercallback. It was restricted again.

 Eventually, we were there twelve times. Even a second expert mechanic wasbrought in to try his skills.

We pulled the refrigerator out so manytimes, that the customer claimed that wehad ruined her kitchen floor. Believe itor not, we wound up turning in the floorclaim to our insurance company. They paid to replace it.

We finally gave up on the refrigeratorand refunded most of the money.

 Every mechanic in the company was

affected by that job. It proved, beyond adoubt, just how miserable acontaminated system can be. 

Before reassembly, a new filter dryer isalways installed between the condenserand the capillary. Hopefully it will catchany lingering dirt. A new compressor isinstalled and the system is silver-

soldered back together. There is a thirdtube on all compressors. It is called a

“process tube.” This process tube isused by the factory or field technician togain access to the system.

Once a system has been cleaned andreassembled two further operations musttake place:

1. The air, along with any moisture,must be sucked out.

2. The proper amount of freon must beadded back.

Page 28: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 28/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker24

Air and moisture are evacuated with avacuum pump. A vacuum pump is aspecial compressor designed,specifically, to suck the system downinto a vacuum. Old-time mechanics

used old compressors for a vacuum pump. This is no longer possible underthe new EPA laws. The pump isconnected with special fittings to the process tube. Most good mechanics, letthe pump run for a considerable time.

A minimum is thirty minutes, some let

it run overnight. 

The longer the pump runs, the more

likely it will be that all the moisture willevaporate and be sucked out. Long pumping will not remove dirt, only

moisture. Once the system is as cleanand as dry as possible, freon is added.

This procedure is known as “charging.”Typical refrigerators require 6-8 ounces

of freon, less than a cupful. Again,special equipment is needed toaccurately measure the freon.

In recent years, the EPA has addedanother layer of complexity. It is nownecessary to recover and properlydispose of any excess freon. A systemcannot be simply cut open and exhaustedto the air. The old freon must becollected in the process.

Fig071_17

 

Page 29: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 29/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker25

The fines for improper freon proceduresare up to $25,000.00. A bounty isoffered by the EPA for any leads, whichresult in convictions. They really mean

 business.

 Uncle Harry’s

Story Time

 North of me, in the next county, amechanic was recently caughtexhausting freon. He was doing an afterhour repair on an air-conditioner.Unknown to the mechanic, the customer(a true sweetheart) took a picture of him

and turned him in for a reward. Themechanic was eventually fined$5,000.00. His comment was,

“It’s going to take any awful lot ofmoonlight jobs to pay for that job!”

After the system is properly charged, itis turned on and run until it stabilizes. Aset of refrigeration gauges is connected.Gradually, the “back pressure” can be

checked. It should be 1-2 psi.. Once the pressures check out, the process tube is pinched shut with special “process tube pliers”. The system is then solderedshut.

Some mechanics install and leave aShraeder “tap valve” soldered onto thesystem. A Shraeder “tap valve” allowsfuture testing of freon pressures and

charging if needed. It also leaves a

 potential leak source.

 Uncle Harry’s

Trick of the Trade # 98

Superior mechanics leave no chance forleaks; they solder the system completelyshut. If you decide to do system work,invest in tools to do it right. Use processtube adapters and pinching pliers.

The previous compressor replacement procedure is only a sketchy overview

and is not intended to be complete.Actual system work requires much morestudy, Federal schooling and licensing.

Reviewing, it is obvious that compressorreplacement and system work iscomplex, time consuming and requires aconsiderable investment in equipment.Consequently, the fees that must becharged, exceed $400.00. When an

evaporator or condenser is also replaced,five or six hundred is not unusual.

If a refrigerator is over 10 years old, thedecision is clear-cut. It is not wise for acustomer to spend that much money. Upto five years, the compressor is covered by the factory warranty. Customers thatcomplain to the factory during 6th yearoften get extended factory coverage.

The only manufacturer havingsignificant trouble, in the 5-10 yearrange, is GE. As mentioned, they haveextended the warranty coverage.

Page 30: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 30/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker26

After considering the various factors, thenumber of potential customers dwindlesdown. Desirable systems jobs, the cleanones are in a distinct minority.

But the worst has yet to come.

Even after all the possible precautionsare taken, most of the time problemsarise anyway. The percentage ofcallbacks on systems work is extremelyhigh. System replacement jobs, that lastmore than a year, are the rare exception.

 Uncle Harry’s

Story Time

 Recalling again, my experience when Ibought the Reliable Service Co. Inc., for

 several years, we continued doing system work. It wasn’t too long, before I felt it was a financial black hole. The profits were generally less than normalrepair work, and the callbacks weremuch greater.

 I instructed my men to only accept the

cleanest and most desirable jobs. The system work still was not as profitable asregular work. Eventually, after carefulanalysis, I stopped it altogether. We simply referred any system calls to friends in the business. Of course, we still collected a service charge for

diagnosing the problem.

 I remember, clearly, that my menthought I was crazy. They only saw the

big checks coming in and thought I wasthrowing away very desirable, bigmoney service work.

Of course, they didn’t understand that itwas the accounting that made the workundesirable.

 Even today, fifteen years later, I watchtechnicians that continue to repair systems.

 Everyone that I know doing it, still has

continual problems.

 Another example.

 Just recently, I got a large hospital

account. The head of maintenance toldme about my predecessor. They werecharging $500-600.00 to replaceevaporators, condensers, andcompressors on special built-in kitchenunits. (It was very difficult to replace

the whole unit.) In spite of all the precautions, the sealed system work stilldid not hold up for long. Callbackscaused them to lose the account.

 Uncle Harry’s

Trick of the Trade # 99

Stay away from system work .

Pay attention to your Uncle Harry!

Does it make sense to get involved in allthe expense of equipment, licensing timeand learning time to accomplish aspecialty task? At the present time, a 25LB can of freon costs $700.00 and it jumps every month. The EPA simply ismaking it impossible to economicallyrepair systems.

Page 31: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 31/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker27

  Novices, homeowners, and new studentsseem to think the refrigeration problemsare always freon problems.

It simply isn’t so.

A classic service call:

“I want you to come look at my

“Refrigidaire.” I think it needs some

“frezone.””

Refrigerator Temperatures 

nderstanding normal operating

temperatures is important for quickdiagnosis. Now that the sealed

system is better understood, thetemperature of each section will bereviewed.

Compressor Temperatures

hen everything is operating asdesigned on a forced-aircondenser, the compressor

temperature, will be uncomfortable toyour hand. It's not hot enough to burn,closer to 120 °F. The small outlet line ofthe compressor is hotter yet. It'scarrying the compressed hot freon to thecondenser.

Condenser Temperatures

he inlet to the condenser is of course

the same line two feet away, so it isstill pretty hot; but as the freon loses

heat and condenses into a liquid, itslowly cools down. It gradually reachesclose to room temperature, when it exitsthe condensing unit. Most of thecondenser is warm to the touch.

Capillary and Suction Line

Temperatures

s mentioned before, as the freon

comes out of the condenser, it goesthrough a dryer and into a capillary

tube, The capillary tube is soldered upagainst the line returning from thefreezer. The combined capillary andreturn line will be a little cooler thanroom temperature. Once the suction lineseparates from the capillary tube, it willstill be slightly cool to the touch.

The Freezer Section 

ext is the freezer section where thefreon is evaporating. Thetemperature on the evaporator itself

will be about 10-15 °F below zero. Theair temperature in a stabilized freezerthat has cycled off will be about 12-18°F.

On opening a side-by-side freezer, that isat 10 °F or below, on a humid summerday, fog will roll out like dry ice sittingon a stage set. In order for ice cream to be hard, but still scoopable, thetemperature needs to be in teens. Icecream is still soft between 20-28 °F.

Usually, customers first notice a problem with ice cream or frozen orange juice. Watch out for some new low fatice creams, they need even lowertemperatures to freeze hard.

Automatic icemakers also are anindicator of temperature. The internalcycle thermostat of most icemakers is setat 16 °F. When freezer temperatures arerising, a stalled icemaker is the firstindicator.

U

W

T

A

Page 32: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 32/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker28

 Logically, if the icemaker continues tooperate, the freezer temperature is below16 °F.

The Fresh Food Section

ontinuing on, with the controls inthe freezer and fresh food sectionset in the mid-range, the fresh food

section will stabilize between 36-38 °F.and the freezer will stay below 20 °F.

 Uncle Harry’s

Trick of the Trade # 100

It's very important upon arrival at arefrigeration call, to first test thetemperatures of the freezer and freshfood section.

Testing Temperatures

s soon as you start opening the

doors and looking around, you arelosing valuable information.

Customers often introduce you to a sickrefrigerator by opening the doors. Begentle, close the doors and immediatelytake the operating temperatures. It iscritical to take accurate temperatures before doing anything else. If the doorsare left open for over a minute, theinformation is lost.

Fig071_17

The quickest way to get accuratetemperatures is to test the food itself.First, confirm that one of the liquids in

the fresh food compartment has beenthere overnight. Wash off the tip of yourthermometer and insert it into the liquid.Try to pick an item that was sitting nearthe center of a shelf. Stay away from thedoor and the crispers.

Reclose the door and wait a few minutesuntil the thermometer stabilizes. Readthe temperature. Just laying thethermometer on a shelf in the air should be avoided. Likewise in the freezer, jamthe tip of your thermometer betweenseveral packages of frozen food. Let itsit for several minutes, until it stabilizes.

While you are waiting, talk with thecustomer about the failure. Once thetemperatures are established, proceedwith further diagnosis.

An empty refrigerator can give incorrecttemperature indications. The plastic and

C

A

Page 33: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 33/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker29

air remaining never appear as cold asfood. The air temperature in a freezercan be below zero and the shelves maystill not seem cold to the touch. It isessential to depend on a thermometer.

Air Flow and Control Settings 

nderstanding air flow and propercontrol settings are equally asimportant as the freon system.

 Nearly all of today’s refrigerators haveonly one evaporator. It is in the back orthe bottom of the freezer compartment.On side-by-sides, it's always up the back, and on top freezers, it's either on

the floor of the freezer section, or on the back wall. On the bottom freezermodels, it is on the back wall. Coldfrom this one evaporator must becirculated and controlled throughout therefrigerator.

Fig071_18

U

Page 34: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 34/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker30

 An evaporator fan motor sucks air overthe evaporator and blows it through thevarious pieces of ductwork in the freezerand fresh food section. The bulk of it

stays in the freezer, but about 25% isallowed to flow over into the fresh foodsection.

This division of airflow is controlled bya damper that is set by the customer.The damper control is usually called the“freezer temperature control.”

When the damper is set in a mid-rangethe temperatures stabilize at 15-20°F in

the freezer and 36-38 °F in the freshfood side. The split of the air, keeps adifference of about 20°F between thetwo compartments.

If the damper is set wide open, too muchfreezer air will come into the fresh foodside. The freezer will climb into themiddle and upper twenties, and spotfreezing often occurs in the fresh foodside.

Spot Freezing

 pot freezing occurs for severalreasons.

1. The most common is improperly setcontrols.

2. The second is in infrequent use.When a refrigerator is seldom used, cold

air settles to the bottom. Since the doorsare rarely opened, the compressor andfans seldom come on to circulate the air.Vegetables in the crispers will freeze.Incidentally, crispers are located in the bottom because, it is the coldest area.

3. Too much food blocking the airflow.Cold spots form, if no air circulates.

Controls Set at the Maximum 

f the damper is shut down to the pointof being almost closed, the freezertemperature will get colder and

colder. The reason for this is simple.The cold control that shuts off thecompressor is in the fresh food side.With the damper closed off, very littlecold air comes over to the fresh foodsection to satisfy the cold control. Thecompressor runs and runs trying to

satisfy the cold control.

Many refrigerators fail to operate properly if the controls are set to theextremes. The freezer often drops belowzero, and the fresh food compartmentrises into the 40’s. The system is simplyout of balance.

At the first sign of trouble, customers

always set the controls to the

maximum!

In reacting this way, they have doneabsolutely nothing to solve the root problem. Instead, they often introduce amore problems.

 Uncle Harry’s

Trick of the Trade # 101

Before going on any refrigeration calls

always ask the customer to set bothcontrols back to the middle setting. Itwill eliminate one source of confusion.

S

I

Page 35: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 35/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker31

Example of a very common service call.A customer will complain,

“My refrigerator is too warm. The freezer seems fine.”

It is a common service call to arrive andfind the freezer damper completely shutoff. The refrigerator may be as warm as45 °F. If the freezer is too cold, there isnothing wrong with the refrigerationsystem. The problem is simply one of balancing. There is a problem with thedamper or the airflow.

 Uncle Harry’s

Story Time

 I had a customer call a few years ago

with the temperatures too cold in the freezer and not cold enough in the fresh food section. It was a side-by -siderefrigerator. Her husband was anintelligent engineer. He had already runvarious tests on the damper and haddetermined, that it was functioning asdesigned. He was right. He even

removed the damper from the openingbetween the fresh food section and the freezer and left it off for a day. Nothing seemed to solve the problem. The freezer stayed below zero and the fresh food side stayed in the upper 40’s.

Stumped, the customer called a servicecompany, not mine. An old competitorof mine came out and attempted to fixthe problem. He took the freezer section

all apart. Finally, he put in a defrostclock, re-assembled the refrigerator, andclaimed it fixed.

 In a short time, the problem reappeared.Unhappy with the first technician, thecustomer asked around and got myname. I interrogated her fully and

determined that her husband definitelyknew what he was talking about. It alsowas evident, that my friendly competitorhad been unable to find the problem.

 I told the customer, that there was anairflow problem. I had to empty out the freezer and remove the back wall, inorder to see if I could solve the mystery.Upon inspection, I found a number ofminor problems, but nothing that reallyexplained the gross imbalance between

the freezer and the refrigerator. Ichecked the fan rotation and theductwork. I checked whether the fanblades had been put on backwards. I

checked all of the rare things that I knewof, and still stood there stumped.

 I re-assembled the freezer, closed the

doors, and stood back and said tomyself,

"I'm missing something stupid here, thishas got to be something easy.”

With the freezer door shut and the fresh

 food door open, only a trickle of airwould come out of the 2 x 4" hole thatwas supposed to supply cold air to the fresh food side. No matter what I did,the air would not blow out of that holeas it should.

Standing there in frustrated desperation, I thought about the airflow system andrealized what I was missing. There hadto be a way for the air to get from the

 fresh food side back into the freezer. Ofcourse, the air had to have a return pathto make a complete loop. I had not

checked the return air duct.

 I knelt down and pulled out both crisperdrawers of the refrigerator. Tuckedneatly behind one drawer, I found a box

Page 36: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 36/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker32

of Thomas's English muffins snuggled up perfectly against the return air hole. Itcompletely blocked the air returning from the fresh food side back into the freezer. The problem was solved. 

Simple logic tells you that you can'tcontinually exhaust air from a closedfreezer into the refrigerator, without

returning warm air back to the bottom ofthe evaporator. Everyone had missedthe cause. No one was thinking througheach step of the airflow.

I charged the woman $90.00 for therepair. It took an hour and a half to find

that simple problem. She wasn't veryhappy. Nobody likes to look stupid, and pay a fee in addition.

 Uncle Harry’s

Trick of the Trade # 102

Arriving to find an unpluggedrefrigerator or freezer is a useless servicecall. Always advise customers to either,

leave the unit running, or at least turn iton 24 hours before your arrival.

All refrigeration diagnosis requires thattemperatures be stabilized. Sometimes, problems with defrost systems, don't

appear for several days. This is particularly true in the wintertime, whenthe humidity is low. Frost forms more

slowly on the evaporator.

Some compressors, old Frigidaires forexample, take several hours before thereare any noticeable temperature changes.Trying to diagnose one from a warmstart is a complete waste of time.

By turning on a refrigerator in advancethere is little chance of any damage being done. It merely helps with thediagnosis. The damage is usually donewell before you get the call.

Further Balance Problems

ther problems can disturb thedelicate balance between the freshfood and freezer sections. Believe

it or not, the freon system is very fragile.It doesn't take much to get it out of balance, and to lose proper temperaturecontrol.

Examples

1. A bad light switch

The heat generated by a freezer orrefrigerator light that stays on, when thedoor is closed, will wreak havoc with thetemperature control.

2. A bad door gasket

Any gap over one quarter inch and over6” long will also cause trouble.

3. A partially opened door

A child, or even a parent, leaving thedoor ajar, after stuffing it full ofgroceries will cause rapid frost-up. Itcan even cause the compressor tooverheat.

O

Page 37: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 37/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker33

It is sometimes difficult to separate atrue mechanical failure from oneintroduced by a customer. If a customerleaves the door ajar for two or threehours, it can cause a clog of frost in the

evaporator. Sometimes the defrostsystem is not strong enough to melt outthe frost jam and the problem graduallygets worse and worse.

4. A spill

A customer can spill water from an icetray in a freezer. As the water tricklesdown it can form a frozen bridge of iceacross the evaporator. Again this will

cause a clog in the airflow and frost up.

5. Too Much Inspection

Sometimes, customers gets worriedabout a refrigerator. They continuallycheck by opening the doors. This make

matters much worse. It's the same aschecking an oven by repeatedly openingthe door. Every time the door is opened,the temperatures rise.

Questions to ask the customer, whensolutions are not obvious:

1. When did the problem start?

2. Have they had any parties or strangers

in the house?

3. Have there been any power outages?

Fig071_19

A Ice Bridge From A Leaking Icemaker 

Page 38: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 38/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker34

Understanding Frost-Free

Systems

ow that you have a much betteroverall understanding of the

cooling operation, we can get to thefun and money-making part.

Thank your lucky stars that frost-freerefrigeration came along in the 50's.Along with frost-free came a landslideof continual moneymaking service calls. Nearly all of the current service workinvolves components of the frost-freesystem, rather than those of the freonsystem.

A frost-free system works in the

following way:

The evaporator is a constantly coldsurface sitting in humid air from thehousehold. In six or eight hours, theevaporator will be covered with a layerof crystalline frost. The frost interfereswith the transfer of cold between thecool aluminum coils and the warm,

humid air.

After 24 hours, enough frost builds up torestrict the airflow. After two or threedays, the user will begin to noticetemperature problems.

Some customers, with failed defrostsystems, will actually go to the troubleof defrosting their refrigerator everythree days. Although such a method iseffective, it is a bit troublesome.

Obviously, a system is needed to meltthe frost. On all frost-free systems, thecooling comes from one evaporator. Afan circulates air over the evaporator. A

 portion of that cold air is diverted fromthe freezer section, over into the freshfood section. Through use of a controldamper, a balance of temperature isachieved between the refrigerator andthe freezer.

Page 39: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 39/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker35

Fig071_20

Airflow

Page 40: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 40/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker36

Hot-Gas Defrost 

n the early years of the frost-freedesign, a valve was installed within

the freon system. During the defrost

cycle, hot gas from the compressoroutput, bypassed the condenser, and wasdiverted directly to the evaporator.These systems were called "hot gas

defrost systems". Very few of thesesystems are still in operation.

Electric Heat Defrost and the

Defrost Cycle

oday, the defrost heating is donewith electric heat. An electricheater is built into the evaporator.

Fig071_21

Typical Evaporator Heaters

I

T

Page 41: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 41/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker37

Evaporator heaters are made two ways:

1. Radiant heaters.

A radiant heater is a nichrome element

(like a dryer element) built into atempered glass tube. One, two, and eventhree are used. They operate much like aradiant bathroom floodlight.

2. Calrod Heaters

A calrod heater looks exactly like a bakeor broil oven element. They aredesigned at a lower wattage, just enoughto melt the frost.

Defrost heaters are controlled by thedefrost clock. The clock turns off thecompressor and turns on the heatingsystem every 8 hours, for about 20 min.System defrost times vary from six totwelve hours.

 Uncle Harry’s

Trick of the Trade # 102

A generic 8-hour clock will work onnearly every application.

During the defrost cycle the defrostheater stays on until one of two thingshappen:

1. The clock cycle runs out and restarts

the compressor.

2. A safety defrost limit switch wired inseries turns it off. The defrost limit ismounted on the evaporator. Defrostlimit thermostats are set between 45°Fand 90°F.

The melted frost trickles off of theevaporator collects in a little drain pan below.

Attached to the evaporator pan is a small

tube that directs the water through theinsulation to a second, larger pan sittingon the very bottom of the refrigerator.The larger pan is a plastic tray that can be removed and cleaned by thehomeowner.

Some drain systems have small heaters built-in to keep the water liquid as ittravels out of the cold area.

All of the components added to achievea frost-free operation are complicatedand prone to failure. They are:

1. The defrost clock

2. Defrost heaters.

3. The defrost limit

4. The drain system.

The Difference between Snow

and Ice 

A novice may think, “What a frivolous

title for a section on diagnosingrefrigerators.” Far from it. The laymanuses the words snow and iceinterchangeably, ignoring the difference between them. Observing the differenceis like a guidepost in refrigerationdiagnosis.

Page 42: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 42/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker38

 

 Uncle Harry’s

Story Time 

 Many times, I've instructed apprentice

 servicemen on the difference between snow and ice. Refrigeration is a subtlebusiness. If technicians ignore the clues,they will never be successful. I have fired many trainees, because theyrepeatedly failed to properly observeconditions on service calls.

As far as refrigeration diagnosis isconcerned, it is not necessary to be aweatherman, but snow or ice form for

different reasons. Snow forms in finecrystals on an evaporator that isconstantly cold with humid air blowing

over it. An evaporator with a defrost problem will plug up with white frost orsnow. The snow is soft enough to sticka screwdriver through.

When operating correctly, defrostheaters come on every eight hours fortwenty minutes and melt all of the snowoff of the evaporator. It turns to waterand dribbles into the evaporator drain pan. Suppose the drain pan outlet isclogged. The water will back up andform a miniature pond.

When the cooling system comes backon, the water will turn to ice. Each

subsequent defrost cycle will form a newlayer .  Now the drain pan is reallyclogged.

Fig071_22

Frozen Drain Pan

Page 43: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 43/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker39

 

 Uncle Harry’s

Trick of the Trade # 103

A turkey baster or battery tester are idealfor thawing frozen drains

Eventually, two things happen:

1. The ice gets thick enough to block theair passages to the evaporator. The air

gets blocked enough to affect thetemperatures on the fresh food side.Also, the evaporator will begin to frostup faster than normal, because no air isflowing over it.

2. The defrost water overflows the drainsystem, and begins to trickle out thedoor onto the floor.

Paying attention to the ice or snow

 pattern is very helpful in diagnosing aclogged drain pan and a defrost heater problem. The presence of the ice tellsyou that the heating system is working.

 Uncle Harry’s

Trick of the Trade # 104

Ice only forms where thawing andrefreezing occur.

If only snow is present, there is reason tosuspect a problem with the heaters or theheating circuit, not the drain system.

In order to form ice anywhere in thefreezer section, some warming must be

going on. Something is melting the frostthat naturally forms. Knowing thisinformation gives you a big clue,guiding you to the correct diagnosis.

Ice and snow that form around theevaporator can exert enough force to break the glass rod heaters and bendcomponents of the evaporator. Recallthat, ice can break up a sidewalk in thewintertime.

A child, innocently leaving open therefrigerator door for a few hours, cancause breakage of the defrost heaters inaddition to simple frost build-up.

Fig071_23

 Uncle Harry’sTrick of the Trade # 105

A piece of copper wire wrapped arounda calrod heater and extended into thedrain works just fine

Page 44: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 44/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker40

Diagnosing Frost System

Failures 

rost -free systems fail in severalways:

1. Frost build-up

2. Ice build-up

3. No cooling

The difficulty in diagnosing refrigerationsystems is that the defining line between problems is seldom clear. One problemwill soon cause others. It is often hard

to find the root problem without carefulinvestigation.

For instance, consider this typicalexample. On a humid summer day, ahomeowner leaves the children with a baby sitter. One of the kids leaves therefrigerator door ajar a few inches. Afew hours later, the baby sitterautomatically closes it. The next day,the homeowner notices that the ice

cream is soft. Something is wrong andshe calls for help.

The service man arrives. He finds a badly defrosted evaporator, and poor

temperatures. The freezer is 25 °Finstead of 15°F and the fresh foodsection is 48°F instead of 38°F. No one, but the absent baby sitter, is aware thatthe door was left open.

Before a good serviceman can draw anyconclusions, he must first run a thoroughtest on the defrost system, the lights, andthe fans. A full understanding of the proper operation is necessary for a

 proper diagnosis. A failure of manyindividual components can cause thesame symptoms.

To reach that level of understanding, wewill study each type of failure and learnhow the system is interconnected and balanced. Then we will study eachcomponent and see how it fits into theoverall picture. Once a fullunderstanding is achieved, it is quick

and easy to accurately diagnose arefrigerator.

F

Page 45: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 45/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker41

1. Frost Build-Up 

rost build-up in a frost-freerefrigerator is the most common

 problem of all. Excess frost can be

caused by an excessive amount of humidair, like the baby sitter example, or lackof heat in the defrost cycle. Poor aircirculation can even cause frost. A highflow of air helps to dry out theevaporator.

Following is a list of the reasons forfrost build-up:

1. Bad defrost clock.

2. Open defrost limit.3. Open defrost heater.4. Door left open.5. Bad door gaskets.6. Bad evaporator fan motor.7. Restricted airflow.

2. Ice Build- Up 

Continual melting and thawing of watercause ice build-up. The source of the

water maybe defrosted snow, spillage, or

the icemaker system.

Following is a list of reasons for ice build-up:

1. Clogged drain pan or drain pan tube.2. Bad drain pan heater.3. Deteriorated insulation around thedrain system.4. A spill.5. A leaking icemaker.

6. A leaking icemaker fill valve.

Fig071_24

Typical Frost-up 

F

Page 46: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 46/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker42

3. No Cooling

The primary reason for no cooling has been covered under compressor

 problems. However, the defrost system

can also be the guilty party. The powerto the compressor flows through thedefrost clock (to be covered shortly). Ifthe clock motor fails during the defrostcycle, it may never turn the compressor back on.

Component by Component

Following are the components of therefrigeration system not covered by our

discussion of the freon system. We willcover their properties, configurations,and failure patterns individually.

1. Defrost clocks and defrost heaters2. Defrost limits3. Evaporator fans4. Door switches

5. Door gaskets6. Cold controls

1. Defrost Clocks and Defrost

Heaters

The defrost clock is a small black boxwith four wires connected to it. Sinceit’s introduction it has gone throughmany design changes and improvements.Overall, the clock’s logic and function

have remained the same.

Fig071_25

Page 47: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 47/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker43

 

Fig071_26

Page 48: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 48/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker44

 Skilled technicians tend to be verycasual about matching exact times tofactory specifications. Most technicianscarry only one clock to fit nearly all

models.

The consensus of opinion is that a littleextra defrost time causes no harm. Thedefrost limit controls the uppertemperature of the evaporator anyway.If a clock comes on a little more oftenthan the original design, so what. Theresult is no different from opening thedoor a few extra times.

Defrost Clock Diagnosis

The following method is the fastest andmost reliable way to diagnosis a frostedup evaporator. First locate the defrostclock. (They're mounted all differentways.) Remove it from it’s housing.

 Uncle Harry’s

Trick of the Trade # 106

Turn the defrost clock over so that youcan see the back of it. Feel the defrostclock motor. Is it warm? The timermotor that runs 24 hours a day. A goodmotor will be warm, unless it’s mountedin the cold compartment.

If it's room temperature and there's nosign of warmth, replace it.

Often the back of the defrost clock has asmall window. Peering through thewindow it is possible to see the armatureof the motor spinning. If you can see themotor through the little window and the

armature has stopped, again you knowthat the clock is bad. In other cases, a

small rotating shaft is visible in thecenter of the advancing knob.

If the defrost clock is warm and there is

no window to confirm that the clockmotor is spinning, then another methodis employed.

By the way all of these tests can be donewhile the refrigerator is still running.Take care not to touch any exposedterminals of the clock to any metal oryour fingers. Most often, the spade endsconnecting the defrost clocks are ininsulated housings.

Turn the clock back over so that you'relooking at the main shaft. With yourfingernails or with a wide-bladedscrewdriver, slowly advance the defrostclock until you can hear it audibly click.The loud click indicates the beginning ofthe defrost cycle. At this point, twothings should happen.

The compressor shuts down and the

defrost cycle begins. Sometimes whenyou try to advance the clock, it'sextremely tight. Again, it’s a bad clock.

Assume that it turns easily, the motor iswarm, and the refrigerator is now in thedefrost cycle. Remember at this point,

the evaporator is badly frosted.

Page 49: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 49/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker45

 

 Uncle Harry’s

Trick of the Trade # 107

Defrost heaters make a noise. Listencarefully for a crackling and faint popping noise as the snow begins tocrack from the heat of the defrostheaters.

Using a penknife or a sharp screwdriver,carefully mark the position of the defrostclock. In ten minutes, it will be possibleto detect if it has advanced.

With the clock set in defrost, currentshould be flowing through the defrostheater. Other than the sound, there areseveral ways to confirm, if in fact, thedefrost heater is operating.

Fig071_27

Using an Amprobe to Test for Defrost

Current 

1. In radiant heat models with glass tubeheaters, it is possible to see the red glow.Turn off any lighting and look into theevaporator. Any sign of a red glowconfirms that the defrost limit and the

defrost heater circuit are intact.

2. A second method is to jerk therefrigerator plug out of the socket.Watch for a medium-sized blue arc asthe current flow to the heater circuit iscut off. A tiny spark indicates only thatthe lighting circuit has been cut off.

3. A third option is to pull the defrostwire off of the defrost timer and look for

an arc.

4. Last but not least. Use an Amprobeand clamp it around the defrost heaterlead. There should be several amperesof current flowing.

Page 50: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 50/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker46

If, after performing one of these quicktests, you have determined that nocurrent is flowing through the heatersystem, then either the defrost heater orthe defrost limit is bad. In most cases

the defrost heater is the culprit.

If the defrost system does begin to heatup, you have confirmed that the heatingsystem is okay. The only componentcontrolling the heat is the clock.

Conclusion, the clock must not beadvancing, as designed, and turning onthe heat.

In review, observe the procedure that isused. Separate the problem into twosections:

1. Is the defrost clock bad?

2. Is the heater circuit bad?If the heater circuit is bad, it's time toquote the customer. There's no need totry to separate the diagnosis between thedefrost limit and the defrost heater.Replace both items. The bulk of thework, and therefore the price, is in thelabor. The hard part is getting the unittotally defrosted.

Defrosting an evaporator can take up toan hour. It requires the use of lots of hotwater, a blow dryer (heat gun) or both..Customers must put their food in afreezer chest while you work.

Fig071_28

Page 51: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 51/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker47

Servicemen don't like to either spend alltheir time defrosting or require thecustomer to put the food elsewhere andturn off the refrigerator for a day. Slow

defrosting requires a second trip for parts installation. Better customerrelations are built doing the job quicklywithout inconveniencing the customer.

Fig071_29

Speed Defrosting a GE

 Uncle Harry’s

Trick of the Trade # 108

Speed Defrosting

First, thaw out the area where the heatersgo, install the heaters while the unit isstill frosted up, and turn on the defrostcycle, while you're manually defrostingthe rest of it. In doing so, you're gettingthe benefit of a heat gun, in addition tothe defrost heat from the built-in radiantheaters.

 Note: Keep heat away from the defrost

limit until the very end. It will break thedefrost heater circuit as soon as it warmsup.

Page 52: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 52/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker48

 At any time during the discussion did weunplug the refrigerator? No. Sometimesit is just difficult, and risky to pull arefrigerator out from the wall. It may be

on a spongy linoleum floor or ceramicfloor. The fresh food section is usuallychock full of heavy food items. It is notnecessary to unplug it.

Special plastic skids are available to prevent floor damage

However, care must be exercised indisconnecting and re-connecting theheater. There may be 110 VAC on theheater wiring. The cautious move is to

check between the heater connectionsand the metal case before touching thewiring and working on the heater circuit.The safest method is to use insulated pliers to make the final connection andassume that the wire ends are hot.

 Notice that the diagnosis of the defrostsystem does not require removing anyfood from the freezer. It can be doneremotely by making a few tests at the

defrost clock. The last thing you want todo is take all the food out of the freezerand put it back twice. You want to be prepared to properly fix it, when youdecide to take it apart.

Fig071_30

Moving a Heavy Refrigerator 

Page 53: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 53/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker48

Condenser Fan Motors

ustomers frequently will use the phrase,

"My refrigerator has been “hummingand clicking” and now my food isbeginning to thaw out."

The “humming and clicking” sequenceis a telltale sign of either an overheatedor damaged compressor. The condenser-cooling fan, which circulates the air overthe compressor, can often be theresponsible party. A blocked or badcondenser fan motor will cause the

compressor to overheat. This conditionis commonplace in the summertimewhen the temperatures are high and theusage on the refrigerator is alsoabnormally high.

Fig071_31

A Bad Condenser Fan Motor

Cleaning a condenser is easilyaccomplished with a vacuum cleanerusing a long, skinny tool or using aspecial condenser cleaning brush. It'scommon to find all sorts of debris

 jamming a condenser fan motor. It isalso common to find a stuck condenserfan motor. (A lot of endplay on the shaftof the condenser fan motor is normal.)

One condenser fan motor will fit nearlyevery refrigerator. The only exception isSub-Zero. There are two problemschanging condenser fan motors

1. It's really hot. It is easy to fry your

hands on the side of the compressor.

2. The working area is dirty and verytight. Replacement requires a stubby5/16” and 1/4" nut driver in order toremove the mounting brackets.

C

Page 54: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 54/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker48

Evaporator Fan Motors 

ost of the time, evaporator fanmotors give plenty of warning

 before they fail. They start to

chirp like a bird. The chirp eventually becomes constant; finally the customercan't stand it anymore. Sometimes thehomeowner will put oil on the fan. Itdoesn’t fix it; in about a week the noisewill return.

Sometimes, the fan motor just quietlydies or binds up. Also, the fan motor canget lodged in ice from a spill or lodgedin frost from frost-up. Often, thawingout the housing in which the fan blade

sits will allow the evaporator fan motorto come back to life.

On side-by-side refrigerators, theevaporator fan motor is always mountedon top of the evaporator. It sucks airacross the evaporator and blows it outthe top and over into the fresh foodsection

Fig071_32

M

Page 55: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 55/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker49

 The diagnosis is simple if the fan motoris noisy. Replace it! Things can be alittle more difficult if the fan motor issimply stopped. Make sure that you

have the door switches depressed whenyou're testing an evaporator fan motor.

Sometimes, when you suspect that thefan motor's bad, the only sure method isto empty out the freezer enough to getthe cover off. It is necessary to get tothe fan motor itself. . Test to see if youhave 110 VAC at the fan motorterminals. If power is present, the motoris obviously bad. Often, a bound fan

motor will be too hot to touch.

Fig071_34

Old and New Fan Motors

(Note matching shaded poles)

However, if the fan motor is cold,disconnect the leads to the fan motor,apply 110 VAC to it from a test cord.Make sure that it is, in fact dead, and

that you don't have a problem elsewhere.

In replacing fan motor attention must be paid to the fan rotation. Universalreplacement motors may need to bereversed. Remember the discussion ofshaded pole motors back underelectricity.

Kits of fan motors are available that fitnearly every refrigerator.

Page 56: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 56/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker50

Door Switches

oor switches on the refrigerator andfreezer perform two functions.They turn off the lights and turn on

the fans. Sometimes, they also disablethe icemaker and disable the power tothe circuits, which supply ice and waterin the door. Often, a door switch will bevisibly stuck, bent, or broken. These areeasy to figure out. Once in a while youwill find a switch that appears to begood, but it is in fact faulty.

A bad door switch can cause veryembarrassing problems. It is wise to

operate the door switches manually earlyin a diagnosis check, it only takes a

second. There is nothing worse thantaking a whole freezer apart to check afan motor, only to find a simple doorswitch problem.

Fig071_35

Changing a Door Switch 

On some refrigerators, it's hard to bypassa switch. Some are difficult to get it outof the housing. They are tightly snappedin. If a switch is suspect, dig it out, andshort it out to test it.

Overall, fan and light door switches area minor source of problems. A smallstock of switches will cover most needs.

D

Page 57: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 57/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker51

Cold Controls 

he cold control is the thermostat thatcontrols power to the compressor

and is manually set by the

temperature control knob. A coldcontrol is a capillary tube device with asensing probe that dangles intorefrigerator air. The probe is usually upat the top of the refrigerator and is anair-sensing device.

Overall, cold controls are highly reliableand rarely a source of service calls.

Technicians that replace a lot of cold

controls usually don't know what they

are doing.

Once in a while you might find one thatwon’t turn the refrigerator to turn on.First make sure the unit is not in thedefrost mode.

Fig071_36

Typical Cold Control

 Uncle Harry’s

Trick of the Trade # 109

"The Knuckle Sandwich Diagnosis".

A sharp rap with the knuckles on thecontrol knob of the cold control willoften pop a refrigerator back into life.

A bad cold control represents less than1% of the failures on refrigerators. Coldcontrols never seem to drift off intemperature control.

They are either shorted and never

open or open-circuited and never

close, nothing in between.

T

Page 58: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 58/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker52

Door Gaskets 

eplacing a door gasket on arefrigerator or a freezer is one of

the most difficult jobs in the field of

home appliance repair. Customers perceive it as being very simple, but infact it is very difficult. It is necessary to 

charge for at least an hours time wheninstalling a door gasket.

When does a door gasket needreplacing? As a door gasket gets old, therubber hardens, cracks, splits and tears,and the gasket, particularly down at the bottom, will begin to come apart.

Discoloration and mildew spots on thegasket don't really hurt the seal. They just look bad. For a gasket to actuallycause a problem with the refrigeration, itneeds to be gapped 1/4" or more over anentire corner of the door at least halfway along the bottom. There has to beenough of an opening for a reasonableamount of air flow both in and out.

Fig071_37

A Bad Door Gasket 

Very often what appears to be a baddoor gasket is really only a twisted door.People pulling the handle hundreds oftimes get the door twisted out of shape.Holding your foot or your knee against

one portion of the door and pulling onthe other portion can correct doordistortion. By working gently with yourarms, you can straighten the twists andget the door gasket to seat evenly.

In many cases, gaskets are in need ofcleaning rather than replacement. Driedliquids on the gasket will cause it totwist and stick.

Door hinges, particularly at the top willcome loose and the door will sagslightly. Sometimes the bottom of theinner liner will rub against the plasticinterior of the refrigerator. This willmake the door hard to close and twist thedoor as the customer forces it closed.

R

Page 59: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 59/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker53

Replacing a Door Gasket

f the gasket is torn or deteriorated beyond cleaning or adjustment, then

replace it. With the door still hinged

in place, never remove all the screws atthe same time. This is the laymanmethod. If all the screws are removed atone time, the door will sag and lose itsshape and you're in deep trouble. Usethe following procedures:

The technique to use for installing thedoor gasket is fairly simple, at least itmay sound fairly simple. Actually thereis no way to make it easy.

The new gasket comes all folded up inthe box with creases and wrinklesthroughout. In the wintertime, a stiffgasket that has been folded up for acouple of years can be a tough repair.

Even in warmer weather, it's a good ideato unfold the gasket in advance of the job. Time will remove some of thewrinkles. Even a tub of hot or warmwater is useful to soften up the rubberand eliminate wrinkles.

Some technicians prefer to empty thedoor, remove it from the refrigerator,and lay the door panel flat on theground. This is one style.

Fig071_38

Replacing a Door Gasket

I

Page 60: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 60/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker54

 

 Uncle Harry’s

Trick of the Trade # 110

Personally, I prefer to remove 1/4 of thegasket at a time or 25% of the screws.Install the new gasket on the loosecorner. Repeat the procedure on eachcorner. In doing so, work your wayaround the door, without ever having thedoor lose its shape. The integrity of thedoor is dependent on the liner and thedoorframe being bolted together tocreate a solid box.

Once the gasket is installed the fun begins. In about two thirds of the cases,the new gasket will not evenly seat. Biggaps will be visible between the gasketand the jamb.

“Oh great, now I’m in real trouble.”

Use the following tricks to mold it:

1. Smear Vaseline on the front surface ofthe door gasket, where it hits thedoorjamb. The Vaseline will cause thegasket to stick, once it's held up againstthe doorjamb. This will encourage it tore-form itself and hold against the jamb.

2. Apply heat from a hair dryer to thegasket. This will soften up the seal andhelp it re-form into the proper shape.

3. Work the gasket with your fingers tostretch it and encourage it into thecorrect shape.

4. Push or pull on the door to get it toconform to the straight shape of the jamb.

Molded inside the door gasket rubber isa very weak magnetic strip that over a period of time will pull the rubber up

against the metal doorjamb of therefrigerator. Eventually the magnet willgive the gasket that snug feeling thatyou're familiar with.

Sometimes it's necessary to quit afterdoing the best you can and pray thatover the period of the next few days, thegasket will seat itself against therefrigerator door jamb.

Some brands, like Admirals, have verylarge, cross-section gaskets and it's verydifficult to get them seated properly thefirst time. The percentages of callbacksto re-adjust are around 30%. Accept itand charge accordingly.

Page 61: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 61/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker55

Fig071_39

Typical Component Layout 

Page 62: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 62/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker56

Fig071_40

Typical Wiring Diagram

Page 63: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 63/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker57

Sample Flat Rate

ollowing is  Uncle Harry’s   suggested pricing for typical refrigeration repairs. A

complete set of flat rates is in the Flat Rate Book.

Refrigerators Flat Rate Guide

Description of the Job Price1)  Melt out ice and unplug drain line $115.00

2)  Clean condenser 72.00

3) 

Replace condenser fan motor (WX4X990) 155.004)  Replace evaporator fan motor, various 155.00

5)  Replace defrost clock and defrost unit 160.00

6)  Replace defrost limit 145.00

7)  Replace defrost heater & limit 165.00

8)  Replace cold control 145.00

9)  Replace door switch (fan & light) 98.00

10)Install new door seal (add $85.00 for second seal) 155.00

11)Replace door cams 125.00

12)Install hard start kit 145.00

13)Replace compressor (advise against it) 400.00+

14)

15)

F

Page 64: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 64/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker58

Examination

Manual 7

Refrigerators & Freezers 

(Note: More than one answer maybe correct.)

1. Refrigeration repairs areA. usually obvious.B. like washers and dryers.C. very subtle.D. easy for homeowners.

2. Before your start any repair work on arefrigeratorA. wash your hands.B. take the temperatures.C. pull out the refrigerator.D. eat lunch.

3. When liquids evaporate theyA. cool off.B. generate heat.C. change into a gas.

D. disappear.

4. Freon inside an evaporator isA. a warm gas.B. a cool gas.C. under a low pressure.D. a mixture of liquid and gas.

5. The capillary tubeA. controls the flow of freon.B. clogs with ice and dirt.C. is about 12” long.

D. is in the sealed system.

6. Replacing a refrigerator door sealA. is recommended for even tiny air leaks.B. takes only a few minutes.C. involves taking the seal off all at once.D. is much more difficult than it appears.

7. A bad defrost limitA. can create frost like a bad heater.B. should be replaced with a new heater.C. can be tested at room temperature.D. A & C.

8. Sealed system workA. is an easy way to make money.B. can be done with your eyes closed.C. is worse than the plague.D. requires a large investment.

9. A cap and suction lineA. transfers heat between the two lines.B. is soldered.C. can cause condensate.D. A, B, & C.

10. Evaporator fan motorsA. often make noise, when they fail.B. are shaded pole motors.C. can be reversed.D. are hard to stock

Page 65: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 65/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker59

11. Partial frost patterns indicate

A. a restriction.B. a short system.C. money for you.D. a trashed refrigerator.

12. Water in a sealed systemA. can be easily removed.B. is serious contamination.C. means a major expense.D. causes rust.

13. A hard start kitA. is a temporary fix.B. is used to test compressors.C. rarely works.D. is helpful for testing.

14. Closing a damper controlA. will warm up the freezer.B. will not hurt anything.C. will raise the fresh food temperatures.D. will unbalance the system.

15. A defrost heaterA. can be tested with an ohmmeter.B. melts out accumulated frost.C. is about 12” long.D. is in the sealed system.

16. Defrost clocksA. are largely interchangeable.B. must be exact.C. are easy to find.D. control the freon pressure.

17. The difference between ice and snowA. is critical to diagnosis.B. is a silly statement.C. is important in the winter.D. all of the above.

18. Major frost build-up can be caused byA. an open door.B. a short system.C. a bad defrost limit.D. a bad defrost clock.

19. Ice build-up can be caused byA. a bad defrost clock.B. a separated cap and suction line.C. a clogged drain.D. A, B, & C.

20. A bad defrost clock can be determinedA. by the noise they make, when they fail.B. with your hand.C. with an Amprobe.D. without instruments

Extra credit: Why is system repair discouraged by Uncle Harry?

 ________________________________________________________________________  __________________________________________________________________

Page 66: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 66/67

 

Refrigerators and Freezers Rev. 08/03 

Copyright © 2008 Harry D. Raker60

 

Examination Answers

Manual 7

Refrigerators and Freezers 

1. C. Refrigeration repairs requireexperience and attention to details.

2. B. Do not lose accurate temperaturereadings by opening doors while

talking to the customer. Take thetemperature first.

3. A & C.

4. C & D.

5. A, B & D. The tiny cross section ofthe capillary tube in the sealedsystem can clog with any debris.

6. D. Replacing a refrigerator door sealis difficult and time consuming. It isoften hard to get adjusted.

7. A & B. A defrost limit cannot be

tested at room temperature. Theywill only close at their set points of50-90 degrees F.

8. C & D. The new EPA regulations andthe cost of doing sealed systemrepairs make for far are more troublethan it is worth.

9. D. Failure of the solder joint betweenthe cap and the suction line reduces

the heating transfer between the twolines causing condensation and evenfrost.

Page 67: Refrigerators Manual 7

8/20/2019 Refrigerators Manual 7

http://slidepdf.com/reader/full/refrigerators-manual-7 67/67

 

10 A, B & C. Evaporator fan motorsoften squeal when they fail.Replacement motors can be reversedto fit either rotation.

11. A, B & D.

12. B & C. A sealed systemcontaminated with water can seldom be repaired.

13. A, B & D. In some cases, a hardstart kit is a long-term repair, butmost often the compressor is nearingthe end of its useful life.

14. C & D.15. A & B.

16. A. Defrost clocks are mounted inmany locations. They can bedifficult to find.

17. A & C. C. has nothing whatever to

do with appliances, but nevertheless,it is true.

18. A, C & D.

19. C A bad defrost system results inthe buildup of snow rather than ice.

20. A, B, C & D. There are variousmethods for determining a baddefrost clock and they are all

effective.

Extra Credit (worth 5 points):

Knowledge, licensing, high investment andregulatory requirements all combine todiscourage any new company from gettinginvolved in freon system repair .