punim diplome, bashkim statovci

Upload: sara-norman

Post on 04-Apr-2018

1.032 views

Category:

Documents


63 download

TRANSCRIPT

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    1/70

    UNIVERSITETI I PRISHTINS

    FAKULTETI I INXHINIERIS ELEKTRIKE DHE KOMPJUTERIKE

    PUNIM DIPLOMETema: TS. 220/35/10(20) kV PODUJEV , MUNDSIA E KALIMIT NGA

    220/35/10(20) kV N AT 110/20 kV

    Mentori: Kandidati:

    Dr.Sc. Isuf KRASNIQI Bashkim STATOVCI

    Prishtin, 2011

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    2/70

    Punim Diplome

    Prmbajtja:

    HYRJE .......................................................................................................................... 4

    KAPITULLI 1

    1.1Nj historik i shkurtr i sistemit energjetik n Kosov.............................................6

    1.2 Mihjet siprfaqsore.................................................................................................7

    1.3 Termocentralet .........................................................................................................9

    1.3.1 Termocentrali Kosova A.........................................................................9

    1.3.2 Termocentrali Kosova B.......................................................................10

    1.4 Skema teknologjike e sistemit prodhues.................................................................12

    1.5 Hidrocentralet ........................................................................................................12

    1.6 Burimet e riprtrishme (turbinat me er).13

    KAPITULLI 2

    2.1 Rrjeti i transmisionit i Republiks s Kosovs......................................................14

    2.1.1 Historiku i rrjetit t transmisionit............................................................15

    2.1.2 Kapacitetet aktuale t rrjetit t transmisionit............................................18

    2.1.2.1 Kapaciteti i linjave t transmisionit............................................18

    2.1.2.2 Kapaciteti i linjave te shprndarjes.............................................18

    2.1.2.3 Kapacitetet transformuese..........................................................19

    2.2 Linjat interkonektive..............................................................................................21

    2.3 Nnstacionet elektrike ............................................................................................23

    KAPITULLI 3

    3.1 TS 220/35/10(20) kV Podujev..............................................................................24

    3.2Pamja e ndrtimit , dhe elementet kryesore te nj stacioni transformator-ik.........25

    3.3 Transformatort .....................................................................................................29

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    3/70

    Punim Diplome

    KAPITULLI 4

    4.1 Transformatort n TS 220/35/10(20) kV n Podujev......................................... 30

    4.2 elsat automatik ................................................................................................. 34

    4.3 elsat me gaz SF6 ............................................................................................... 35

    4.4 elsat ndars ajror .............................................................................................. 37

    4.5 Sistemi pr furnizim t pandrprer-UPS ............................................................. 38

    4.5.1 Ndarja e UPS-ve sipas fuqis ................................................................. 38

    4.5.2 Ridrejtuesit .............................................................................................. 39

    4.2.3 Baterit .................................................................................................... 39

    4.2.4 Invrtort ................................................................................................. 40

    KAPITULLI 5

    5.1 Transformatort e tensionit ................................................................................... 42

    5.1.1 Konstruktimi i transformatort e tensionit .............................................. 42

    5.2 Transformatort rrymor ........................................................................................ 435.3 Transformatort e kombinuar ............................................................................... 44

    5.3.1 Konstruktimi i transformatorve t kombinuar ...................................... 44

    KAPITULLI 6

    6.1 Mbrojtja .................................................................................................................46

    6.1.1 Mbrojtja e transformatorve n TS 220/35/10(20) kV Podujev

    me Rele Siemens SIPROTEC..................................................................46

    6.1.2 Mbrojtja termike e transformatorve........................................................48

    6.1.3 Mbrojtja Distanciale ................................................................................49

    6.1.4 Mbrojtja Diferenciale ...............................................................................49

    KAPITULLI 7

    7.1 Mbrojtja nga mbitensionet .....................................................................................51

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    4/70

    Punim Diplome

    7.1.1 Mbrojtja nga mbitensionet e jashtme (atmosferike) ................................51

    7.1.2 Rrufepritsit .............................................................................................51

    7.1.2.1 Realizimi i rrufepritsit n TS 220/35/10(20)kV, Podujev................. 52

    7.1.3 Pruesit mbrojts ....................................................................................53

    7.1.3.1 Pruesi mbrojts n TS 220/35/10 kV, Podujev.....................53

    7.1.4 Sferat mbrojtse .......................................................................................54

    7.1.5 Shkarkuesit e mbitensionit .......................................................................54

    7.1.5.1 Shkarkuesit gypor t mbitensionit .............................................54

    7.1.5.2 Shkarkuesit ventil t mbitensionit .............................................55

    7.1.5.3 Shkarkuesit Metal-Oksid t mbitensionit ..................................56

    7.1.5.3.1 Shkarkuesit metal-oksid t mbitensionit n

    TS 220/35/10(20) kV n Podujev..............................56

    7.1.5.3.2 Varistort Metal-Oksid t mbitensionit .......................56

    7.2 Linjat pr bartjen e energjis elektrike ................................................................. 58

    7.2.1 Pruesit ...................................................................................................59

    7.2.2 Shtyllat .....................................................................................................61

    7.2.3 Izolatort ................................................................................................. 64

    KAPITULLI 8

    8.1 Mundsit e kalimit nga 220/35/10(20) kV n 110/20 kV ......................................65

    Prfundimi ...................................................................................................................68

    Literatura ......................................................................................................................79

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    5/70

    Punim Diplome

    HYRJE

    Ne kt punim diplome me titull TS 220/35/10(20) kV Podujev , mundsit e

    kalimit ne 110/20 kV kryesisht do te flasim pr TS 220/35/10 kV n Podujev , por

    do te flasim edhe pr historikun e zhvillimit energjetik ne Kosov , prodhimin eenergjis elektrike n Kosov si dhe pr minierat e linjitit , Termocentraletdhe ujrat

    Hidrocentralet si dhe pr energjin e riprtrishme.

    Energjia elektrike si nj faktor kryesor i zhvillimit shoqror dhe ekonomik te nj

    vendi duhet ti kushtohet nj vmendje te posame energjis elektrike prkatsisht

    prodhimit bartjes dhe shprndarjes s saj. Energjia elektrike pr her t par filloj te

    prdoret ne vitin 1882, duke vepruar me tension 2000 [V] n prues eliku me gjatsi

    prej 57[km] dhe fuqi bartse 1.5 [kW]. Zbulimet e m vonshme kan dhn

    shpjegime te hollsishme pr mnyrn e bartjes s energjis elektrike me sa me pakhumbje dhe shfrytzimit sa m racional t saj.

    Problemi i prodhimit te energjis elektrike, i bartjes s saj dhe shpenzimit, u zgjodh

    teknikisht mir dhe pati arsyeshme-ri ekonomike. Sot centralet elektrike ndrtohen ne

    afrsi te lndve djegse sepse bartja e energjis elektrike prej centralit (prodhimit) te

    energjis elektrike deri te shpenzuesi (konsumatori) mundsohet me ndihmn e

    stabilimenteve te tensionit te lart dhe lart pruesve. Pra centrali ndrtohet ne afrsi te

    minierave te linjitit, te liqeneve akumuluese, lumenjve me rrjedhje t shpejt t ujit dhe

    burimeve te tjera energjetike.

    Nevoja pr energji elektrike po rritet pr do dit e m shum. Kjo po kushtzon

    ndrtimin e centraleve me kapacitete te mdha. Rndsi e posame sht bartja e

    energjis me humbje energjetike sa m t vogla. Nj terkes e till mund t mund t

    plotsohet nse bartja e energjis elektrike bhet me tensione sa m t larta, mirpo

    bartja e energjis elektrike me tensione shum t larta paraqet nj pun te vshtir,

    gjat bartjes s energjis elektrike paraqiten probleme shum t mdha, te cilat

    krkojn zgjidhje shkencore dhe praktike. Problem i veant ne sistemin

    elektroenergjetik paraqitja e mbitensioneve, dega e cila merret me zgjedhjen eproblemeve te mbrojtjes nga mbitensionet sht teknika e tensioneve te larta, sht

    deg relativisht e re shkencore. Zhvillimi i saj sht kushtzuar me rritjen e nivelit t

    tensioneve bartse, duke filluar nga sistemet bartse 10kV, 20kV, 35kV, 110kV,

    220kV, 400kV, 765kV. Ne shtetet ku distanca nga burimi deri te shpenzuesi jan

    shum te mdha, jan ne eksperimentim edhe sistemet 1050kV e ka propozime qe te

    provohet edhe sistemi prej 2000kV. Pr nevojat e shtetit t Republiks s Kosovs

    sistemi prej 420kV sht i mjaftueshm, por pr integrim ne Evrop sht e

    nevojshme te ndrtohen sisteme bartse prej 750kV.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    6/70

    Punim Diplome

    Kosova disponon me nj potencial t konsiderueshm energjetik t qymyrit (linjitit),

    po ashtu posedon edhe disa burime tjera si hidrocentrale dhe tash se voni jan ndrtuar

    edhe tre mullinj ere pr prodhimin e energjis elektrike. Rezervat kryesore te linjitit

    shtrihen ne dy basene t linjitit n Kosov, eksploatimi i linjiti sot behet vetm nga

    baseni i Kosovs, n minierat siprfaqsore n Bardh dhe Mirash planifikohet te niseksploatimi i linjitit edhe n Sibovc. Minierat shtrihen n nj siprfaqe t hapur dhe

    me nj shkall t lart t efikasitetit s nxjerrjes s linjitit. Linjiti qe nxirret ne kto

    miniera kryesisht prdoret pr nevojat e termocentraleve (rreth 98%). Termocentralet

    e ndrtuara dhe lshuara ne pun n mes te viteve 1960-1984 jan t ndrtuara afr

    minierave te qymyrit, rreth 10-15 km nga Prishtina.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    7/70

    Punim Diplome

    KAPITULLI 1

    1.1 Nj historik i shkurtr i sistemit energjetik n Kosov

    Sistemi energjetik n Kosov e ka nj histori prej disa dekadash. N vitin 1922Kosova inauguroi zhvillimin e saj energjetik me hapjen e miniers s par nntoksoret thngjillit. Nga ajo minier sht nxjerr thngjill deri n vitin 1958, kur ka filluarpunn mihja siprfaqsore e linjitit n miniern e Mirashit. Sot, miniera e Mirashit,miniera e Bardhit, dhe miniera e Sibovcit Jugperndimor jan burimet kryesore tthngjillit q prdoret pr energji n Kosov, duke siguruar nj prodhim tprgjithshm vjetor prej prafrsisht 7 milion tone linjit. N vitin 1960, filloindrtimi i termocentralit t par t bazuar n thngjill. Ishte ky termocentrali KosovaA, blloku i par i t cils kishte nj kapacitet prej 65 MW. Deri m 1975, n kuadr tKosovs A u ndrtuan edhe katr blloqe t tjera, q gjithsej arrinin nj kapacitet prej

    800 MW. Prej vitit 1977 deri m 1984, u ndrtua edhe termocentrali i dyt, Kosova B,me nj kapacitet t prgjithshm prej 678 MW dhe me dy blloqe prodhuese. Pr njkoh t gjat, Kosova ishte pjes prbrse e sistemit energjetik t ish-Jugosllavis.Gjat asaj periudhe, prodhimi i energjis n Kosov ishte i prqendruar n prodhimine bazuar n linjit (termo), me nj kontribut t vogl t prodhimit t bazuar n uj(hidro).

    Furnizimi i vet Kosovs me energji bhej nga termocentralet e saj por edhe ngaburime t tjera t prodhimit t energjis q gjendeshin gjithandej territorit t ishJugosllavis.N vitet e 90ta, gjat shprbrjes s Jugosllavis, sistemi energjetik i vendit u

    mirmbajt shum dobt ose n t u investua shum pak. Prej vitit 1989 deri m 1999shumica e ekspertve vendor u larguan nga vendet e tre t puns. Megjithat, nmesin e qershorit t vitit 1999, kur prfundoi lufta e fundit me Serbin, puntortshqiptar filluan t ktheheshin n Kosov dhe ishin n gjendje q t kthehen n vendete tyre t puns. Pas nj dekade t lnies anash, n sektorin e energjis u bninvestime, s pari nga institucionet ndrkombtare e pastaj edhe nga institucionetvendore n mnyr q t ringjalleshin kapacitetet energjetike t vendit.N periudhn e paslufts sektori i energjis mori nj infuzion t madh nga ndihma

    ndrkombtare. Ndonse nuk ka n dispozicion shifra t sakta, llogaritet se q nga viti1999 n ket sektor jan investuar m shum se 1 miliard euro. Megjithat, as kto

    fonde nuk ishin t mjaftueshme pr t zgjidhur problemet q ka vendi n sektorin eenergjis.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    8/70

    Punim Diplome

    1.2 Mihjet siprfaqsore

    Nxjerrja e qymyrit(linjitit) n basenin qymyror t njohur me emrin Baseni i Kosovs

    ka filluar n vitin 1922 me metodn nntoksore. Fillimisht, qymyri sht eksploatuarnga miniera KOSOVA, e m pastaj nga minierat: Dardhisht, Sibovc, Zgafella e Re

    dhe Babushi i Muhaxherve. Kjo form e nxjerrjes s qymyrit ka vazhduar deri n

    vitin 1956, n miniern e athershme t Mirashit fillimisht me largimin e djerrins n

    vitin 1956, ndrsa tont e par t qymyrit nga kjo minier jan realizuar n vitin 1958.

    Me rritjen e kapaciteteve gjeneruese ka lindur nevoja pr hapjen e miniers s Bardhit.

    Punt minerare n hapjen e miniers s Bardhit kan filluar me largimin e djerrins

    n vitin 1964 ndrsa eksploatimi i tonve t par t qymyrit nga kjo minier ka

    ndodhur n vitin 1969. Q nga viti 1922 e deri n dhjetor t vitit 2009 nga t gjitha

    kto miniera n kuadr t basenit t qymyrit(Linjitit) t KOSOVS jan eksploatuargjithsej 300.1 milion ton qymyr.

    Organizimi aktual i prodhimit t qymyrit n kuadr t KEK-t sht :

    DIVIZIONI PR PRODHIMIN E QYMYRIT, n kuadr t ktij divizioni ekzistojtri fronte kryesore t puns:

    Fig 1.1 Burimet e linjitit n

    Kosov

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    9/70

    Punim Diplome

    Mihjet ekzistuese apo Sektori lindor dhe perndimor Sektori i Sitnics Mihja e re Sibovci Jug-Perndimor

    Fig 1.2Harta e baseneve t linjitit t Kosovs

    Fusha e Sibovcit Fusha Jugore Fusha DRezervat e linjitit

    Gjeologjike/Eksploatabile990 mt / 830 mt 537 mt / 370 mt 395 mt / 280 mt

    T mjaftueshme pr TC

    me kapacitet :

    2000-2500 MW Ca. 1000 MW Ca. 600 MW

    Djerrina / linji m /t 0.9:1 2.8:1 0.9:1Vlera kalorike neto 8300 kJ/kg 8000/8300 kJ/kg 7300 kJ/kg

    Tabela 1.1 Baseni i linjitit i Kosovs

    Rezervat aktuale n miniern ekzistuese jan : 7.1. milion ton dhe pritet tprfundohen gjat vitit 2012.

    Rezervat n sektorin e Sitnics jan : 7.4 milion tonRezervat n mihjen e re SJP jan : 123.4 milion ton .

    Kto rezerva jan parapar t furnizojn kapacitetet ekzistuese gjeneruese deri n vitin2024 . Prodhimi mesatar vjetor aktualisht n DPQ sht rreth 8.0 milion ton qymyr

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    10/70

    Punim Diplome

    n vit. Linjiti sht burimi kryesor i energjis n Kosov, 98% te linjitit te nxjerr idedikohet i dedikohet prodhimit t energjis elektrike n KEK-, ndrsa prodhimi ienergjis elektrike varet plotsisht nga furnizimi me linjit.

    Fig 1.3 Miniera e qymyrit (linjitit)

    1.3 Termocentralet

    Divizioni i Gjenerimit t Energjis prbhet nga termocentralet "Kosova A", "KosovaB" dhe Seperimet Kimike, q jan t vendosura n rrethinn e Kastriotit, q gjenden

    rreth 8 km larg Prishtins, kryeqytetit t Republiks s Kosovs.

    1.3.1 Termocentrali Kosova A

    Termocentrali "Kosova A" prbhet nga pes Blloqe punuese t njohura si A1, A2,

    A3, A4 dhe A5. Blloku A1ka filluar te ndrtohet m 10.03.1960 kurse ky Bllok sht

    lshuar n pun n vitin 21.10.1962 me fuqi prej 65MW, Blloku A1 ishte i pajisur me

    kaldajn nga Babcock (Gjermani), kurse turbina nga Westinghouse (Amerika).Kurse Blloku A2 ka filluar te ngritt n vitin 1962 dhe ka startuar me prodhim me

    20.05.1965 me fuqi prej 125MW, Blloku A2 ishte i pajisur me kaldajn nga

    Babcock (Gjermani), kurse turbina nga General Electrics (Amerika). Blloku A3

    ka startuar m 18.04.1970 me fuqi 200MW , Blloku A3 ishte i pajisur me kaldajn nga

    Rafako (Poloni), kurse turbina dhe gjeneratori nga Leningradski Metaljurgski

    Zavod nga ish Bashkimi i Republikave Socialiste Sovjetike (BRSS-Rusia). Blloku

    A4 ka filluar prodhimin m 15.05.1971 mefuqi prodhuese t instaluar prej 200MW

    dhe Blloku A5 n vitin 08.07.1975 me fuqi prodhuese t instaluar prej 210MW.

    Pajisjet e prodhimit te ktyre dy Blloqeve jan t njjta me at t Bllokut A3. BlloqetA3, A4 dhe A5 jan funksional. Sipas planit aktual n prodhim prdoren dy blloqe,

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    11/70

    Punim Diplome

    kurse njri prej tyre sht rezerv e nxeht pr shkak te gatishmris se tyre t

    ult, q sht pasoj e vjetrsis s tyre. Blloqet A1 dhe A2 jan jasht pune, pa status

    t definuar, dhe sipas planeve aktuale ato do t mbesin kshtu deri n fund, kur pritet

    t bhet dekomisionimi i tyre s bashku me njsit tjera.

    Prodhimi vjetor i energjis elektrike nga TC Kosova A sht rreth 1500GWh.

    Njsia gjeneruese Fuqia e instaluar(MW)

    Periudha e ndrtimit Lshimi i par n pun

    A1 65 1960-1962 21.10.1962

    A2 125 1962-1965 20.05.1965

    A3 200 1966-1970 18.04.1970

    A4 200 1967-1971 15.05.1971

    A5 210 1971-1975 08.07.1975

    Tabela 1.2 Termocentrali Kosova A

    Fig 1.4 Termocentrali Kosova A

    1.3.2 Termocentrali Kosova B

    Ndrtimi i Termocentralit Kosova B sht kryer nga konsorciumi Man dhe Alstom

    Atlantique-ggee. Termocentrali "Kosova B" prbhet nga dy njsi (blloqe) punuese t

    njohura si B1 dhe B2. Blloku i par (B1) i ktij termocentrali sht lshuar n pun

    me 10.09.1983 me fuqi prej 340MW, kurse blloku i dyt (B2) n vitin 14.07.1984 me

    fuqi t njjt, 339 MW. T dy blloqet jan funksional dhe kan nj gatishmri t mir

    kohore. Me investimet q jan br dhe q vazhdimisht jan duke u br ne ket

    termocentral sht prmirsuar dukshm gjendja e blloqeve, q ndonse kan nj

    vjetrsi prej 25 vitesh, jan n nj gatishmri t lart teknike.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    12/70

    Punim Diplome

    Vitet 2008 dhe 2009 jan vitet kur ky termocentral ka arritur prodhimet rekorde n

    historin e tij q nga ndrtimi i tij n vitin 1984 .

    Prodhimi vjetor i energjis elektrike nga TC Kosova B sht rreth 3650GWh.

    Njsiagjeneruese

    Fuqia e instaluar(MW)

    Viti i ndrtimit Lshimi i par n pun

    B1 339 1977-1983 10.09.1983

    B2 339 1977-1984 14.07.1984

    Tabela 1.3 Termocentrali Kosova B

    Fig 1.5 Termocentrali Kosova B

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    13/70

    Punim Diplome

    1.4 Skema teknologjike e sistemit prodhues

    Tabela 1.4

    1.5 Hidrocentralet

    Hidrocentralet :- Hidrocentrali i Radavcit ,- Hidrocentrali Ujman ,- Hidrocentrali Lumbardh,- Hidrocentrali Dikance.

    Hidrocentrali Ujmani (2x17.5MW) i menaxhuar nga kompania publike Ibr-Lepenci.Po ashtu edhe disa hidrocentrale t vogla jan n operim, dy prej tyre Lumbardhi dheDikance jan dhn me koncesion investueseve privat dhe s shpejti pritet q edhehidrocentralet Radavci dhe Burimi t jepen me koncesion. N tabeln 4-2 janparaqitur t dhnat kryesore pr hidrocentralet t cilat jan n operim.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    14/70

    Punim Diplome

    Njsia Gjeneruese Kapaciteti i Njsive t HC [MW] Futja n operimInstaluar Neto Dispozicion

    Hidrocentrali i UJMANITG 1 17.5 16 16 1983

    G 2 17.5 16 16 1983Hidrocentrali i LUMBARDHITG 1 4.04 4.00 4.0 1957(2005)G 2 4.04 4.00 4.0 1957(2005)

    Hidrocentrali i BURIMITG 1 0.34 0.34 0.34 1948(2010)G 2 0.136 0.13 0.13 1948(2010)

    Hidrocentrali i DIKANCITG 1 0.67 0.66 0.66 1957(2010)G 2 0.67 0.66 0.66 1957(2010)

    Hidrocentrali i RADAVCITG 1 0.14 0.14 0.14 1934(2010)G 2 0.14 0.14 0.14 1934(2010)

    Tabela 1.5 Hidrocentralet

    1.6 Burimet e riprtrishme (turbinat me er)

    N dy vitet e fundit sht vrejtur interesim i madh i investitorve privat n instalimine kapaciteteve gjeneruese nga era. N Kosov n fillim t vitit 2010 n kodrn eGolesh-it jan instaluar tri turbinat e para t gjeneratorve me er, t nj teknologjie tvjetr (gjenerator asinkron me shpejtsi konstante). Kto tri turbina jan t kyura nnivelin e tensionit 10kV dhe secila prej tyre ka kapacitetin e instaluar prej 0.45MW.

    N baz t parashikimit t prodhimit q ka dhn investitori kto tri njsi mund tgjenerojn rreth 2.59GWh/vit, q rezulton me nj faktor t ngarkess rreth 0.22.

    Fig 1.6 Tre turbinat e gjeneratorve me er ne kodrn e Golesh-it

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    15/70

    Punim Diplome

    KAPITULLI 2

    2.1 Rrjeti i transmisionit i Republiks s Kosovs

    Operatori i Sistemit, Transmisionit dhe Tregut-KOSTT-i, sht themeluar me 1 korrikt vitit 2006. KOSTT-i sht krijuar si rrjedhoj e procesit t ristrukturimit t sektoritt energjis n Kosov, n baz t obligimeve q rrjedhin nga Traktati prKomunitetin e Energjis pr Evropn Juglindore. I emruar nga Qeveria dhe iliensuar nga Zyra e Rregullatorit t Energjis n tetor t vitit 2006, KOSTT-i shtpronare e dy liensave:

    pr Operim t Sistemit t Transmisionit pr Operim t Tregut t energjis elektrike.

    Operatori i Sistemit, Transmisionit dhe Tregut-KOSTT-i sht kompani publike e cilamerret me planifikimin, zhvillimin, mirmbajtjen dhe operimin e sistemit t

    transmisionit t energjis elektrike n Kosov. KOSTT sht prgjegjs prtransmisionin e energjis elektrike t tensionit t lart 400 kV, 220 kV dhe 110 kV dhepo ashtu sht prgjegjs pr organizimin dhe administrimin e tregtimit t energjiselektrike. Prandaj edhe TS 220/35/10 kV Podujev qe ne e kemi ne shqyrtim sht nnprgjegjsin e KOSTT-it.

    Energjia elektrike e transmetuardo t prkufizohej si energjia elektrike (n GWh) etransmetuar tek konsumatort gjat periods s raportimit nprmjet sistemit ttransmisionit t vn n funksion nga OST. Kjo prfshin humbjet e sistemit ttransmisionit dhe eksportin prgjat interkonekcionit. Ky prkufizim paraqitetgrafikisht n Fig 2.1

    Fig 2.1 Energjia Elektrike e transmetuar duhet t llogaritet duke shtuar gjith energjin elektrike (n

    GWh) q rrjedh prgjat vijs s ndrprer gjat periudhs raportuese.

    Vlera duhet t jet e barabart me gjenerimin me t cilin furnizohet sistemi itransmisionit plus importi nga interkonekcioni si tregohet n Fig 1.7

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    16/70

    Punim Diplome

    Energjia Transmetuar = Energjia Eksportua r + Ngarkesa Prdoruesve Fundor Transmisionit

    TPF1+ Ngarkesa Shprndarje + Humbjet Sistemin Transmetues

    Energjia Transmetuar = Energjia Importuar + Energjia Prodhuar

    Fig 2.2 Energjia Elektrike e transmetuar duhet t llogaritet duke shtuar gjith energjin elektrike (n

    GWh) q transmetohet prgjat vijs s ndrprer gjat periudhs raportuese.

    2.1.1 Historiku i rrjetit t transmisionit t Republiks s Kosovs

    Rrjeti i transmisionit i Republiks s Kosovs gjat viteve sht zhvilluar n disa fazat zgjerimit, prforcimit dhe konsolidimit.

    Mes viteve 1953 dhe 1958, sht ndrtuar linja e par 110 kV n Kosov, nga NoviPazari (n Serbi) deri n Butel (n Maqedoni), duke i lidhur nnstacionet (NS): NSValla, NS Treps, NS Vushtrris, NS Kosova A, NS Prishtina 1 dhe NS Prishtina 4,NS Ferizaji dhe NS Sharri. N t njjtn periudh u ndrtua linja e dyt 110 kV nmes NS Kosova A dhe NS Prishtina 1 dhe linja radiale 110 kV nga Vallai n Pejduke u lidhur me Burimin.

    M 1959 u ndrtua linja e dyt 110 kV nga NS Vallai n NS Kosova A pr tforcuar lidhjen n Termocentralin (TC) Kosova A e cila n at koh ishte duke undrtuar. M 1960 u ndrtua linja e par 220 kV n Kosov, nga Krushevci (Serbi)deri n NS Kosova A.

    M 1963 u ndrtua linja tjetr 220 kV, nga NS Kosova A deri n Shkup (Maqedoni)dhe nj inerkonekcion i dyt u shtua mes ktyre dy nnstacioneve n vitin 1971.

    M 1967, linja 110 kV n veri-perndim u zgjerua nga Peja, pr t lidhur nnstacionetDeani dhe Gjakova 1 t pjess perndimore t regjionit. M 1969 kjo u zgjerua m

    tej drejt NS Prizrenit 2 n jug duke e lidhur at me NS Gjakova 2. M 1972 u ndrtualinja e dyt radiale 110 kV nga Ferizaji n Therand, dhe pastaj me

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    17/70

    Punim Diplome

    1973 n NS Prizreni 3, NS Prizreni 1 dhe NS Prizreni 2 duke kompletuar nj unaz110 kV pr rreth regjionit.

    Po ashtu me 1973 u ndrtua nj linj e dyt 110 kV nga NS Prishtina 1 e cila me vonn vitin 1988 u lidh me NS Prishtinn 4 dhe u zgjerua deri n NS Gjilani, n pjesnlindore t Kosovs.

    M 1977 u ndrtua linja e dyt 110 kV nga NS Kosova A n NS Prishtinn 1, dukeforcuar furnizimin pr qytet dhe duke u lidhur kshtu me NS Prishtina 2 e NSPrishtina 3 (1986). Po ashtu me 1977, u ndrtuan linjat e dyfishta 220 kV duke lidhurkshtu NS Kosova A dhe NS Kosova B.

    N vitin 1978 u ndrtua linja e par 400 kV n Kosov duke u lidhur Nishin (Serbi)me Shkupin (Maqedoni) prmes NS Kosova B,. M 1980 linja 110 kV drejt Gjilanit, uzgjerua pr n Bujanovc (Serbi). M 1981 u ndrtua linja 110 kV pr lidhjen e HCUjmanit me NS Vallai.

    M 1983 u ndrtua linja e dyt 400 kV e interkonekcionit nga Ribarevina (Mali i Zi)pr n NS Kosova B, dy linjat 400 kV duke lidhur kshtu TC Kosova B me NSKosova B, dhe linja 220 kV pr furnizim vetjak t TC Kosova B. N t njjtin vit undrtua linja 220 kV nga NS Kosova B n NS Prizreni 2, prmes nnstacionitshprndars n Drenas. Po ashtu n t njjtin vit u ndrtua edhe linja e dyt 220 kVpr Drenas duke pasuar me linjn e dyfisht pr furnizim t objekteve industriale tFeronikelit. N t njjtn koh u ndrtua linja radiale 110 kV nga NS Kosova A n NSe Bardhit.

    N vitin 1984 u ndrtua linja nga NS Gjilani pr n NS Sharri prmes NS Vitia, dukeprmbyllur kshtu rrethin jug-lindor t rrjetit 110 kV t Kosovs.

    M 1988 u ndrtua linja interkonektive 220 kV nga NS Prizren 2 pr nHidrocentralin (HC) Fierza (Shqipri), po ashtu n t njjtin vit u ndrtua linja edyfisht 220 kV nga NS Kosova B n NS Prishtina 4. Po n at vit u ndrtuan edhelinjat 110 kV nga NS Gjakova 2 n NS Klina dhe linja nga NS Prizren2 n NS Prizren

    3 duke forcuar kshtu furnizimin e Prizrenit.M 1990 u ndrtua linja e dyt 110 kV nga NS Prizreni 2 n NS Gjakova 2.

    M 1991 u ndrtua nnstacioni i Lipjanit duke u ndrlidhur me NS Prishtina 4 prmeslinjs 110 kV q u ndrtua po at vit. Ky vit paraqet fundin e investimeve n rrjetin etransmisionit pr nj periudh kohore prej 10 vitesh deri n vitin 2001, q paraqet njpauz mjaft t gjat 10 vjeare n prforcimin dhe zhvillimin e rrjetit ttransmisionit.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    18/70

    Punim Diplome

    Fig 2.3. Periudha kohore dhe numri i instalimeve t NS dhe linjave pr vit

    Emrtimi Karakteristikat VitiAT3 ne NS Kosova B 400/220 kV Auto transformatori i tret 400

    MVA2003

    AT3 ne NS Kosova A, 220/110 kV AT3 ndrrim, 150 MVA 2003NS Podujeva 220/35/10 kV 2x40 MVA 2003Ndrrim pruesi n linjn 110 kV, nr164/1 NS Gjakova 1- NS Gjakova 2

    Ndrrimi i pruesit nga 150mm2n 240mm2, 4.9 km

    2003

    Linja dyfishe 110 kV nga NS Kosova

    A n NS Prishtina 5

    Al e 240mm2, 5.5 km 2005

    Ndrrim pruesi n linjn 110 kV, nr125,NS Kosova A- NS Vushtrria1& 2

    HW 150mm2, 24km 2007

    Ndrrim pruesi n linjn 110 kV,nr 164/3,NS Prizreni 1- NS Prizreni 2

    HW 150mm2, 3.2 km 2007

    Linja 110 kV NS Prizren 2- NSRahoveci

    Ale 240mm2, 17.25 km 2008

    Tab 2.1 Rrjetit t transmisionit t realizuara nga viti 2000 deri n 2008

    Nj pauz aq e gjat e mos zhvillimit t rrjetit t transmisionit, mirmbajtja jo e mir,vjetrsia e pajisjeve jan faktort kryesor t cilt e kan sjell rrjetin transmetues t

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    19/70

    Punim Diplome

    Kosovs n situat shum t vshtir. Pr shkak t mungess s mjeteve financiareedhe pas lufts nuk ka pas investime t nevojshme t cilat do t prmirsoninprformancat e rrjetit. N vijim n tab. 2.1 sht dhn lista e projekteve tkategoris s rritjes s kapaciteteve t rrjetit t transmisionit t realizuara nga viti 2000deri n 2008.

    2.1.2 Kapacitetet aktuale t rrjetit t transmisionit

    Rrjeti i transmisionit i Kosovs operon me tri nivelet e tensioneve 400 kV, 220 kVdhe 110 kV. Sistemi i transmisionit i Republiks s Kosovs sht i ndrlidhur,prmes linjave ndrkufitare me katr shtetet fqinje: Serbia, Maqedonia, Mali i Zi dheShqipria. N aspektin regjional Sistemi i Transmisionit t Kosovs luan rol mjaft trndsishm n transaksionet tregtare t energjis elektrike t cilat zhvillohen nrajon.. Rrjeti i fuqishm horizontal sidomos ai 400 kV, ndrlidhja e fuqishme me

    vendet fqinje prcakton rolin e rndsishm t sistemit ton n aspektinelektroenergjetik. Aktualisht prmes rrjetit horizontal tranzitohet sasia vjetore tejet emadhe e energjis elektrike e cila sillet rreth 62% t konsumit vjetor t Kosovs. Nvazhdim do t paraqiten kapacitetet e linjave dhe transformatorve sipas gjendjes prfundin e vitit 2009, duke marr parasysh edhe projektet t cilat kan prfunduar.

    2.1.2.1 Kapaciteti i linjave t transmisionit

    N Tab. 2.2 mund t shihen gjatsit dhe kapacitetet transmetuese pr gjatsi tlinjave ekzistuese t rrjetit t transmisionit t Kosovs, me prfshirje edhe t dy

    linjave 110 kV t cilat jan futur n operim n vitin 2009.

    Linjat ajrore 2008 Gjatsia totale n Kosov[km]

    Kapaciteti transmetuesCt=Sn*L [MVA km]

    400kV 181.4 238846220kV 231.82 1 77506110kV 685.4 69443

    Tab 2.2 Gjatsit e linjave t transmisionit dhe kapaciteti transmetues i tyre.

    1 Nuk jan marr parasysh dy linjat e dmtuara NS Kosova A- Shkup me gjatsi 2*65=130km2 Linja 17.24 km 110 kV NS RahovecNS Prizren 2 dhe linja 23.1,110 kV NS Peja 3NS Klina sht e prfshir.

    2.1.2.2 Kapaciteti i linjave t shprndarjesGjatsia e rrjetit t shprndarjes s energjis s prodhuar n Kosov ose importit tenergjis elektrike sht si vijon:

    - 35 kV 776.8 km- 20 kV 331.7 km- 10 kV 12873.3 km- 0.4 kV 37988.9 km

    Ky Divizion ka n pronsi t vet 6.200 trafo stacione t nivelit nga 220 kV (nga transformatori ) deri n 10(20)/ 0.4

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    20/70

    Punim Diplome

    2.1.2.3 Kapacitetet transformuese

    Kapacitetet aktuale transformuese t rrjetit t transmisionit t cilat menaxhohen ngaKOSTT-i jan n nnstacionet e niveleve t tensioneve 400/220 kV, 220/110 kV dhe

    400/110 kV.Kapaciteti m i madh transformues sht i instaluar n NS Kosova B 400/220 kV. Nkt nnstacion jan t instaluar tre autotransformator t fuqis nominale prej 400MVA. Kapaciteti total transformues i ktij nnstacioni sht 3*400 = 1200 MVA.

    NS Kosova Aparaprakisht kishte t instaluar tre autotransformator AT1-100 MVA,AT2 dhe AT3-150 MVA deri n momentin e avaris s autotransformatorit AT1 -100MVA n fund t vitit 2008. Gjat fundit t vitit 2009 sht instaluarautotransformatori i ri prej 150 MVA. Kapaciteti total transformues n NS Kosova Apas instalimit t autotransformatorit t ri sht 450 MVA..

    NS Prishtina 4, aktualisht ka dy autotransformator AT1=150 MVA dhe AT2 = 150MVA, me kapacitet total t transformimit prej 300 MVA. Edhe ktu shum shpejtpritet(n muajin gusht 2010) t shtohen kapacitete transformuese dhe ne gjysmn edyt t vitit 2010 planifikohet t futet n operim autotransformatori i tret 150 MVAduke rritur kapacitetin transformues nga 300MVA ne 450MVA.

    NS Prizreni 2, aktualisht ka dy autotransformator AT1-150 MVA dhe AT2 - 150VA, me kapacitet total t transformimit prej 300 MVA.

    NS Peja 3 400/110 kV i cili operon qe nga fundi i vitit 2009 fillimisht ka t instaluarnj autotransformator me kapacitet transformues prej 300 MVA.

    AUTOTRANSFORMATOR Numri iAutotransformatorve

    Kapaciteti totaltransformues (MVA)

    400/220kV-NS Kosova B

    3 1200MVA

    400/110kV-NS Peja 3

    1 300 MVA

    220/110kV- NS Kosova A-NS Prishtina 4- NS Prizreni 2

    322

    1050MVA450MVA300MVA300MVA

    Tab. 2.3 Kapacitetet aktuale Transformuese n Rrjetin e Transmisionit

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    21/70

    Fig 2.4 Skema njpolshe e SEE n Republikn e Kosovs 400/220/110 kV

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    22/70

    Punim Diplome

    21

    2.2 Linjat interkonektive

    Kapaciteti maksimal i shkmbimeve t energjis me fqinjt (me fuqi natyrore t linjave)

    me linjat e transmisionit t tensionit t lart sht 1740 MW. N linjat 400 kV kapacitetitransmetues ekzistues ndrkufitar sht rreth 1500 MW (3x500 MW), ndrsa n at 220kV arrin deri n 240 MW (120 MW linja me Shqiprin dhe 120 MW linja meKrushevcinSerbin . Planet e ardhshme pr prmirsimin gjegjsisht ngritjen ekapacitetit transmetues t linjave ndrkufitare prfshijn ndrtimin e nj linje 400 kV qdo t lidh Kosovn me Shqiprin me nj kapacitet t fuqis natyrore prej 500 MW, sidhe nj linj 400 kV shtes me Maqedonin me kapacitet prej 500 MW. NTC-ja (NetoKapaciteti i Transferit) t linjave ndrkufitare t Kosovs sht m e vogl se fuqia e tyrenatyrore dhe e njjta varet edhe nga bilanci rajonal i energjis elektrike n vendet fqinjesi dhe nga kufizimet n linjat e transmisionit q mund t paraqiten n linjat ndrkufitare

    t nivelit 400 kV. N fig.5-3 mund t shihen kapacitete aktuale t linjave interkonektivesipas fuqis natyrore t tyre (P) , NTC mesatare dhe fuqia nominale (Sterm)

    Fig 2.5 SEE e Kosovs dhe kapacitetet aktuale dhe t planifikuara t interkoneksionitNTC dhekapacitetet sipas fuqis natyrore t linjave

    NTC - paraqet maksimumin e totalit t shkmbimit

    t fuqis elektrike n mes t dy zonave kontrolluese,

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    23/70

    Punim Diplome

    22

    Fig 2.6 SEE e Komuns s Podujevs

    Fig. 2.7 Linjat ekzistuese Interkonektive ne Sistemet e ndrlidhura t Transmisioneve t Evrops Jug-

    Lindore

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    24/70

    Punim Diplome

    23

    2.3 Nnstacionet Elektrike

    1 Nnstacion 400/220 kV me kapacitet t transformatorve 3x400 MVA

    3 Nnstacione 220/110 kV me kapacitet t transformatorve 4x150 +100 =1000MVA 1 Stacion shprndars 220kV 1 Nnstacion 220/35/10 kV vetm fushat 220kV; 24 Nnstacione 110/(35 ose 10) kV vetm fushat 110kV

    Rrjeti 400kV sht i lidhur me at 220kV me an t tre autotransformatorve prej400MVA me gjeneratort n Kosova B t lidhur me zbara 400kV-she.

    Rrjeti 220kV dhe 110kV jan t ndrlidhur nprmjet shtat transformatorve me njkapacitet total prej 1000MVA. Shumica e ngarkess (konzumit) s Kosovs furnizohet

    nprmjet ktyre transformatorve megjithse rreth 40MW furnizohen direkt prejsistemit 220kV n Podujevku gjenden transformatort 2x40MVA 220kV/TUdheG1 n TC Kosova A dhe hidrocentrali i Ujmanit jan direkt t lidhura n rrjetin 110kV. Po ashtu rreth 30MW furnizohen nprmjet transformatorve 2x160MVA ntrafostacionin e klientve n Feronikl. Kapaciteti total i transformatorve n 220kVplus furnizimin direkt nga gjeneratort e lidhur n 110kV sht rreth 1200MVA qmbulon nj ngarkes t prafrt prej 1200MW por mungesa e kapacitetit transformuesn nivelin 220kV prkeqsohet meq ngarkesa nuk shprndahet njtrajtsisht nprsistem.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    25/70

    Punim Diplome

    24

    KAPITULLI 33.1 TS 220/35/10(20) kV Podujev

    Stacioni Transformator-ik TS 220/35/10(20) kV (hyrje-dalje) dhe largpruesit 220 kV

    n Podujev, u lshuan ne tension me 13 nntor 2003 me pranin e prfaqsuesve tSiemens-it Austria, punkryersit Umel nga Tuzlla e Bosnjs dhe Montingut ngaPrishtina.

    Fig 3.1 Pamja e nj pjese t NS 220/35/10(20) kV, Podujev

    Projekti i ndrtimit t ksaj stacioni transformator-ik sht donacion i AgjensionitEvropian pr Rindrtim.Punkryesi i trafos 220/35/10(10) kV Podujev sht firma e njohur Siemens nga Austriakurse projektin e ka br ndrmarrja Umel nga Tuzlla e Bosnjs. Ky stacion

    transformator-ik ka rndsi sidomos pr industrin e komuns s Podujevs, por edhe prpopullatn e cila do t furnizohet m mir me energji elektrike.N te kaluarn Komuna e Podujevs sht furnizuar me 16 MVA energji elektrike, me

    futjen n funksion t ktij stacioni transformator-ik, Podujeva do te furnizohet me 80MVA energji elektrike, aq sa jan kapacitetet e ktyre dy Transformator-ve

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    26/70

    Punim Diplome

    25

    3.2 Pamja e ndrtimit , dhe elementet kryesore te nj stacionitransformator-ik

    Pjesa baz e ndrtimit e nj stacioni transformator-ik sht baza se ku do t vendosenelementt e nj stacioni t till, pasi ka nj pesh bukur t madhe. Baza e stacionit

    transformator-ik 220/35/10(20) kV Podujev sht paraqit ne fig. n vijim.

    Fig 3.2 Baza (themelet) e ndrtimit t stacion it transformator-ik me dimensione.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    27/70

    Punim Diplome

    26

    Fig 3.3 Pamja dhe dimensionet e TS 220/35/10(20)kV, Podujev

    Fig 3.4 Shtylla dhe pruesit ne hyrje t TS 220/35/10(20) kV, Podujev

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    28/70

    Punim Diplome

    27

    Fig 3.5 Dimensionet e vendosjes s disa elementeve t nj TS.

    Nj stacion transformator-ik prbhet prej disa pjesve baz: Transformatorveenergjetik, transformatorve t tensionit, transformatorve t rryms , shkarkuesve tembitensionit, ndarsve, izolatorve t ndryshm, zbarrave etj.

    N fig. n vazhdim sht paraqit vendosja e elementeve te TS 220/35/10(20) nPodujev.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    29/70

    Punim Diplome

    28

    Fig 3.6 Figura e vendosjeve te elementeve t TS 220/35/10(20) kV n Podujev m dimensione

    3.3 Transformatort

    Transformatori elektrik sht nj pajisje statike e cila, me induksion elektromagnetik,transformon nj sistem te rryms alternativ aktuale n nj ose m shum sistem t rrymsalternative me frekuencn t nyejt dhe vlera t ndryshme t rrymave dhe tensione.

    Roli i transformatorve n sistemet elektroenergjetike sht shum i rndsishme sepse ajofron nj prodhimin m te sigurt m ekonomik dhe m t besueshme t energjis

    elektrike, transmetimit dhe shprndarjes s energjis elektrike n nivelet m t

    prshtatshme t tensionit Prandaj, zbatimi i tij, me shum pak humbje t energjis,zgjidhjen problemet ne nivelet e ndryshme te tensionit t izolimit t ndrsjell t qarkut

    q ndodhen n nivele t ndryshme t tensionit.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    30/70

    Punim Diplome

    29

    Pjest themelore t transformatorit:

    - Qarkut magnetik,

    - Mbshtjellave,

    - Izolimit,

    - Ens s transformatorit dhe

    - Pjesve ndihmse t transformatorit.

    Transformatort ndahen n transformator njfazor dhe trefazor, transformatort trefazorndahen edhe sipas lidhjeve t mbshtjellave.Mbshtjellat ne ann primare dhe sekondare mund te lidhen ne yll (Y), trekndsh (D),yll te thyer (Z) ose (cik-cak lidhja). Me shkronja t mdha shkruajm pjesn primare

    kurse me te vogla pjesn sekondare t transformatorit.

    Fig 3.7 Pjest kryesore te transformatorit

    Fig 3.5 Lidhjet m t shpeshta n

    transformator

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    31/70

    Punim Diplome

    30

    KAPITULLI 4

    4 .1 Transformatort n TS 220/35/10(20) Podujev

    TS 220/35/10(20) prbehet nga dy transformator me fuqi 2 x 40 MVA, transformatoriT1 sht transformator dy mbshtjell-or 220/10(20) kV m mbshtjella yll (Y) -trekndsh (d), YNd5 me yll t tokzuar, kurse transformatori T2 sht transformatortre mbshtjell-or terciar 220/35/10(20) kV m mbshtjella yll (Y)yll (Y)trekndsh(d) YNyn0d5 , me yll te tokzuar ne pjesn e tensionit 220 kV dhe me yll t tokzuar

    prmes rezistencs ne pjesn e tensionit 35 kV, te tokzuar m rezistenc 69 .

    Fig 4.1 Pamja e transformatorit t par T1 220/10(20) kV

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    32/70

    Punim Diplome

    31

    Fig 4.2 Pamja e transformatorit t dyt T2 220/35/10(20) kV

    Transformatori i par T1 ka nnt (9) dalje 10 kV, e qe jan te shprndara nepertransformatort 10/0.4 kV qe ndodhen neper kto vende:TS Podujeva 1, TS Podujeva 2Spitali, TS Podujeva 3, TS Fabrika Agro Produkt Peran, TS Ballofc, TS Sillosi

    Brecalit, TS Fabrika e Polisterit, TS Llaush, TS Letanc. Transformatori i dyt T2 katr (4) dalje 35 kV prej t cilave dy rezerv, dhe tet (8) dalje10 kV dhe shprndahen neper kto trafo stacione 35 kV : dalja e par sht rezerv kurse

    e dyta n TS Ujsjellsi regjional Batllava Shajkovc , dalja e tret n TS Koliqi dhedalja e katrt rezerv. Kurse daljet 10 kV jan t shprndara npr TS 10/0.4 qe njihenme kto emrtime: TS Fabrika e Tjegullave Podujev, TS shtpiak-e qe ndodhe noborrin e TS 220/35/10(20) kV n Podujev, TS Fabrika e Armaturs, TS Podujeva 4Lagjja e Kuvajtit, TS Podujeva 5, TS Livadic, TS Fshatrat 1dhe TS Fshatrat 2.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    33/70

    32

    Fig 4.3 Skema njpolshe e TS 220/35/10(20) kV, Podujev

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    34/70

    33

    Fig 4.4 Skema njpolshe e TS 220/35/10(20) kV Podujev, dhe shprndarja 35 dhe 10 kV

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    35/70

    34

    Kontrolli, qkyja- kyja realizohet ne meny kompjuterike si ne hyrje tetransformatorve ashtu edhe ne dalje te tyre, po ashtu mund te qyqen dhe tokzohen edhedaljet 35 dhe 10 kV, nj gj e till realizohet prej qendrs kontrolluese. Ne vijim doparaqesim se si duket pamja vizuale e kontrollimit n qendrn kontrolluese. Kontrollimibhet meSIEMENSSICAM PAS Software (6MD90) .

    4.2 elsat automatik

    Prpos te mnyrs kompjuterike te kyje-qkyjevesi dhe tokzimi mund t realizohet

    edhe ne mnyr mekanike me elsa automatik me ajr t izoluar ne shtpizn e linjavedalse 35dhe 10 kV si dhe ne hyrje te transformatorve ne shtpizat kontrolluese prmeselsave mekanik .N TS 220/35/10(20) kV n Podujev per daljet 10 kV jan prdor elsat me air-izoluart tipit NXAIR-M te prodhuar nga SIEMENS, kurse pr daljet 35 kV jan prdor elsatte tipit SF6-8DA te prodhuar nga SIEMENS.

    Fig 4.5 Paraqitja e qendrs kontrolluese SICAM PAS Software 6MD90 n TS 220/35/10(20) kV.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    36/70

    Punim Diplome

    35

    Fig 4.6 Pamja e elsat te tipit NXAIR-M pr daljet 10 kV

    Fig 4.7 Pamja e elsat te tipit SF6-8DA me gaz te izoluar pr daljet 35 kV

    4.3 elsat me gaz SF6

    elsat e tipit SF6 lejojn nj numr kyje-kyjesh prej t paktn 10 000 here pa qenee nevojshme q t behet mirmbajtje apo zvendsim i pjesve t tyre.Te gjith elsat e gazit SF6 jan t testuar sipas standardeve IEC 62271-100 t testuar n

    laborator si: CESI Italia,KEMA Holanda , Keri Koren e Jugut dhe CPRI Indi.N varsi t aplikimit, elsat e gazit SF6 jan t ndar n dy lloje si m posht;- Tre elsa t vendosur n nj mekanizm t prbashkt,- Tre elsa t vendosur n mekanizma t veant pr do faz.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    37/70

    Punim Diplome

    36

    Fig 4.8 Llojet e elsave SF6, tre elsa t vendosur n nj mekanizm t prbashkt

    Fig 4.9 Parimi i puns

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    38/70

    Punim Diplome

    37

    Fig 4.10 Principi mekanik i puns

    Fig 4.11Tre elsa t vendosur n mekanizma t veant, dhe procesi mekanik i punes

    4.4 elsat ndars ajrorPrpos elsave automatik dhe elsave SF6 ndrprerja mund t bhet edhe prmes

    elsave ndars ajror qe ndajn edhe fizikisht pruesit.

    Fig 4.12 elsat ndars ajror n TS 220/35/10(20) kV n Podujev

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    39/70

    Punim Diplome

    38

    4.5 Sistemi pr furnizim t pa ndrprerUPS

    Qllimi kryesor i UPS-it sht q t siguroj furnizim t sigurt t pajisjeve t ndjeshmedhe kritike. Rniet e rrjetit, ndrprerjet n furnizim.Variacionet n tensionin dhe frekuenc, vettimat, zbrazjet elektrostatike dhembitensionet jan dukuri t shpeshta n zyrat dhe n mjediset industriale dhe shkaktojndmtim t harduerit dhe humbje t t dhnave.Sistemi i UPS-ve prbhet nga kto komponente :

    - Ridrejtuesit- Invertori- Burimet rezerv te furnizimit (zakonisht grup i baterive)- elsi statik

    Skema baz e lidhjes s UPS-ve sht treguar n fig.

    Fig4.13 Furnizimi i shpenzuesve te rndsishm me UPS

    UPS-i automatikisht hedhet n kt regjim t puns gjat rnies s rrjetit ( oscilime nfurnizim ose ndrprerje m t gjat ), ose n qoft se rrjeti nuk sht i mir; konsumuesitfurnizohen duke e shfrytzuar energjin e akumuluar n baterin t shndrruar n tensionalternativ nga invertori.

    Lajmrohet alarm akustik i ngadalshm, derisa LED-i/LCD-i pr PUN T

    BATERIS n pllakn e prparm vezullon. Gjat rnies m t gjat t rrjetit, UPS-i ifurnizon konsumuesit deri n kyqjen e tij kur bateria plotsisht do t zbrazet.Para kyqjes, kur bateria sht plotsisht e zbrazur, lajmrohet sinjalizim pr bateri tdobt me alarm t shpejt akustik t ndrprer.UPS-i automatikisht kthehet n pun normale pr rreth dy sekondave pas kthimit tfurnizimit t rrjetit. Koha e hedhjes nga puna normale e bateris dhe anasjelltas, sht epavrejtshme pr konsumuesit.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    40/70

    Punim Diplome

    39

    4.5.1 Ndarja e UPS-ve sipas fuqis

    Fuqia e UPS-ve mund te shprehet ne (W) vat ose ne (VA) volt-amper. Prodhuesitzakonisht pr madhsi t fuqis prdorin Volt-Amper (VA), varsia n mes t [W] dhe[VA]e japim n prmjet faktorit t fuqis.

    Ndarja e UPS-ve sipas fuqis sht:- Sisteme mikro t UPS-ve me fuqi deri n 250VA,- Sisteme mini t UPS-ve me fuqi prej 500-2000VA,- Sisteme mesatar t UPS-ve me fuqi prej 3000-200000VA,- Sisteme t mdha t UPS-ve me fuqi prej 30000-400000VA,

    Stacioni transformatorik 220/35/10(20) kV n Podujev shfrytzon dy UPS-a te

    prodhuara nga SIEMENS, njri me fuqi 12500 VA dhe i dyti me fuqi 25000 VA.

    Fig 4.14 Ridrejtuesit n TS 220/35/10(20) kV Podujev

    4.5.2 Ridrejtuesit

    Ridrejtojn tensionin alternativ te burimit kryesor t furnizimit, n at te vazhduar prnevojat:

    - furnizimin e invertorit- mbushjeve t baterive.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    41/70

    Punim Diplome

    40

    Rryma e mbushjes plus rryma e shpenzuesve sht e barabart me rrymn e nevojshmepr mbushjen e baterive dhe furnizimin e shpenzuesve ( ne rastin ton kemi 12500 VA dhekoha pr mbushjen e baterive 10 min duhet rrym prej 100 A, 25000 VA dhe koha prmbushjen e baterive 10 min duhet rrym prej 160 A).

    4.5.3 Baterit

    Siguron furnizimin e invertorit nse vjen deri te :- Zhdukja e tensionit t furnizimit kryesor- Penges n burimin kryesor t cilt jan jasht kufijve te lejuar.

    Fig 4.15 Baterit n TS 220/35/10(20) kV Podujev

    Fuqia e UPS-it(kVA)

    Koha e autonomis(min)

    Lartsia x gjersia x gjatsia(mm)

    Pesha(kg)

    4.5102045

    Brenda UPS-it 690x200x690Dy shtpiza 690x200x690Tri shtpiza 690x200x690

    95160270

    10

    10

    2045

    Brenda UPS-it 1300x490x800

    Brenda UPS-it 1300x490x800Brenda UPS-it 1300x490x800

    225

    27532520 10

    30Brenda UPS-it 1200x430x800Dy shtpiza 1200x430x800

    325590

    60 6 Brenda UPS-it 1300x800x800 650Tab 4 Dimensionet e baterive

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    42/70

    Punim Diplome

    41

    4.5.4 Invertort

    Shndrron tensionin e vazhduar hyrs n at alternativ dals me krkesa m t ashpra sesa jan krkesat ne burimin kryesor t furnizimit.

    Fuqia e dukshme e UPS-it:

    Fuqia e ngarkess:

    Fig 4.16 Invrtort n TS 220/35/10(20) kV Podujev

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    43/70

    Punim Diplome

    42

    KAPITULLI 55.1 Transformatort e tensionit

    Transformatort e tensionit jan tip i transformatorve pr matje. Prdoret kur keminevoj pr matjen e tensionit t lart q sht e vshtir pr matje me metodn direkte pran qoft se pajisje t tilla ekzistojn, ato do t jen shum t vshtira dhe t shtrenjta. Prprdorimi i transformatorit t tensionit, tensioni i lart transformohet n vlern qmundson prdorimin e mjeteve matse standarde dhe releve. Me kt arrihet edhe njsiguri e personelit punues. Transformatorve t tensionit jan t dizajnuara q tken raport t sakt pr t ulur tensionin n mnyr q t mund t matet n nj tension tsigurt (zakonisht 100V). Jan t dizajnuara pr t prfaqsuar nj ngarkes t vogl ttension q matet.

    5.1.1 Konstruksioni i transformatorve t tensionit

    Mbshtjellja e transformatorve mats jan zakonisht prej bakri, tela bakri t trhequr tbakrit elektrolitik i cili sht s paku 99,9% i pastrt. Teli i bakrit sht i izoluar merrshir sintetike . Prve telit te izoluar me llak prdoret edhe tel i izoluar me fijemndafshi, ky izolim prdoret kur dshirojm t arrijm kapacitet t vogl ne bshtjella,

    qe te mundet te prdoret pr frekuenca t larta.Sipas llojit t izolimit t prdorura n mes t mbshtjellave, dallojm transformator

    mats t tensionit me izolim t:

    - that (deri n 145 kV)- me pak vaj pr t gjitha tensione- vajit

    - t gazit SF6

    Fig 5.1 Transformatort e tensionit dhe ata rrymor

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    44/70

    Punim Diplome

    43

    Transformatort e tensionit ndahen n transformator induktiv dhe kapacitiv t tensionit

    5.2 Transformatort rrymor

    Me qen se sistemi elektrik zakonisht ka fuqi t madhe e cila realizohet n tensione tlarta dhe rryma t mdha, kto madhsi konvertohen n madhsi t standardizuara tprshtatshme pr tu aplikuar n rele me an t transformatorve mats.

    Fig 5.3 Transformatori rrymor, pjest kryesore

    1. Kapaku mbrojts2. Mmbrama3. Lidhja primare4. Pjes aktive5. Izolatori6. Kutia sekondare

    7. Ventili pr lshimin e vajit

    Fig 5.2 Transformator induktiv dhe

    kapacitiv t tensionit

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    45/70

    Punim Diplome

    44

    Funksioni kryesor i transformatorve rrymor sht:- T ul rrymat e sistemit te primarit n nivelin i cili mund t prdort nga

    instrumentet dhe mbrojtja,- T mundson prdorimin e instrumenteve dhe releve te standardizuara,

    - T mundson prdorimin e sistemit t centralizuar t matjes dhe mbrojtjes.

    5.3 Transformatort e kombinuar

    Transformatort mats t kombinuar pr rregulluar matur rryma dhe tensione t lartashumat brenda nj saktsi t prcaktuar t prshtatshme pr lidhjen e pajisjeve matse,mbrojtjen dhe menaxhimin. N t njjtn koh izolojm lidhjet t rrjetit t tensionit tlart.Transformator kombinuar prbhet nga dy njsi matse : transformatorveinduktiv t tensionit dhe transformatorve rrymor.

    5.3.1 Projektimi i transformatorve t kombinuar

    - Tensioni maksimal veprues Um: 72,5-550 kV- Rryma primare: deri n 6000 nj- Rrymat afatshkurtr: termike n 100 kA,dinamike, deri n 250 kA- Numri i transformatorit kryesor i tanishm: 5 (n baz t krkess deri n 10)- Numri sekondar i mbshtjellave t transformatorit t tensionit: 3 (n baz tkrkess deri n 6)- T gjitha klasat e matjes dhe t siguris pr t gjitha standardet e aplikueshme.

    Fig 5.4 Transformatort e kombinuar

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    46/70

    Punim Diplome

    45

    KAPITULLI 66.1 Mbrojtjet

    6.1.1 Mbrojtja e Transformatorit n TS 220/35/10(20) kV Podujev

    me Rele Siemens SIPROTEC

    Fig 6.1 Releja Siemens SIPROTEC

    1. LED pr t treguar statusin q vepron

    2. LCD pr shfaqje tekstuale e procesit t pajisjes dhe informacioni

    3. elsat navigator pr t lvizur npr rrjetn operativ

    4. MENYA kryesore : asnj funksion

    5. Enter:pr konfirmim t hyrjeve, pr t hyr n nivelin e ardhshm, ose pr kaluar mes kodit urdhrues (MLFB)

    dhe vlerat e matura operacionale ESC ky t shkoj deri nj nivel,

    6. elsat funksion:F1 qasje e drejtprdrejt pr rrjetin operativ pr ndryshimin e modelit, F2 Fillon test els

    elektrik, F3: qasje t drejtprdrejt n rrjetin operative pr kalimin e

    funksionit rishikimin,F4: ndryshim transformues t polarizimit

    7. Butoni ON / OFF pr furnizimin me energji elektrike

    8. Priza 9-pol pr lidhjen e nj PC funksionim DIGSI

    9. LED kryesore pr testim dhe rivendosjen,LED pr shfaqjen e vlerat operative t matura n 4-linja,

    10. LED pr shfaqjen procesit t parametrizimit t lirshm apo pajisje informacion. LED tjetr , ka nj

    rrip etiketimit pr etiketimin e funksionit t secilit LED.

    11. LED pr parametrizim total.

    Mbrojtjet kryesore

    1. Mbrojtja e linjave

    2. Mbrojtja e motorve

    3Mbrojtja e transformatorve

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    47/70

    Punim Diplome

    46

    Mbrojtja e transformatorit me rele digjitale (mikroprocesorike, numerike) 7UT6.Teknologjia mikroprocesorike siguron karakteristika si te relet statike e bile edhe mshum, rrymat ne hyrje dhe funksionet e integruar mbrojtse. Karakteristikat e releve

    numerike jan:- N nj rele jan t integruara m shum funksione mbrojtse,- Mund t bhet kontrolli vetjak i harduerit dhe softuerit ,- Zgjerohet prdorimi i informacioneve pr shkak t komunikimeve,- N terminalet e ushqimit jan te integruara, mbrojtja, matja, kontrolli dhe

    monitorimi, prcjellja e informacioneve n distanc.

    Fig 6.2 Releja dhe funksionet e integruara mbrojtse

    Fig 6.3 Pamja e releve ne TS 220/35/10(20) kV Podujev

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    48/70

    Punim Diplome

    47

    Fig 6.4 Realizimi i mbrojtjeve t transformatorve ne TS 220/35/10(20) n Podujev

    6.1.2 Mbrojtja termike e transformatorve

    Jeta e izolimit varet nga temperatura e mbshtjellave, temperatura m e lart se 6 OC ,rrit plakjen e izolimit nga faktori 2!.

    - Dy termo-pajisje mund t jen t lidhura me interfejs serial shrbim,- Monitorimi deri n 12 pik matse (6 pr termo- pajisje),- Nj hyrje sht e rezervuar pr monitorimin vendeve t nxehta (matjen

    e temperaturs s vajit ).- Termoelementet: Pt100, Ni100 or Ni120

    Temperatura e lart t vajit matet drejtprdrejt nga prdorimi i termoelement.Temperatura llogaritet duke transmetuar temperaturn n modelin termik Cu-vaj:

    Fig 3.5 Monitorimi i temperaturs

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    49/70

    Punim Diplome

    48

    6.1.3 Mbrojtja distancionale

    Mbrojtja distancionale realizohet me rele t drejtimit dhe t nn impedancs. Releja emat raportin U/I dhe vepron n qoft se vlera e matur sht m e vogl se vlera e

    akorduar n t. Kjo mbrojtje prdoret pr mbrojtjen e linjave t transmisionit.

    Fig 6.6 Mbrojtje distancionale

    Prparsit dhe te metat e mbrojtjes distancionale jan:

    - sht mbrojtje selektive e linjs n rrjetet konturale ( t mbyllura),- Koha e veprimit t reles zakonisht sht rreth 30 ms,- Kjo mbrojtje sht mbrojtje rezerv me zonn e dyt dhe t tret pr relet tjera

    pasuese,- Zonat e para t cilat e mbulojn s paku 85% te elementit (linjs) q mbrohet jan

    me veprime t shpejt dhe kan selektivitet absulut,- Nuk ka nevoj pr linja kanale t ndrlidhjes,- Nuk ndikohet nga shtimi dhe ndryshimi i ngarkess,- Vepron pr dmtime t ndryshme (lidhje t shkurtra, lidhje me tokn dhe pr

    mbingarkesa t palejuara ).

    T metat jan:- Ndjeshmria varet nga impedanca e ngarkess,- N veprimet e mbrojtjes ndikojn:

    Linja e shkurtr ,Lkundja e fuqis,Ndikimi i rezistencs s dmtimit

    6.1.4 Mbrojtja diferenciale

    Rryma fazore matet n t dy ant e zons s mbrojtur. Diferenca e rryms s fazs

    shkaktojn veprimin e mbrojtjes Kjo sht mbrojtje e shpejt dhe prdoret pr mbrojtjen e:Transformatorve, makinave rrotulluese dhe linjave.- Mbrojtja aktuale aplikohet pr kabllot dhe linja e tensionit t lart,- Dy deri n gjasht linja prfundimtare- Trajton zonat mbrojtse t transformatorve- Lidhje t drejtprdrejta t rrjetave komunikuese etj.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    50/70

    Punim Diplome

    49

    Fig 6.7 Mbrojtja diferenciale n tri linja dhe transformator

    Nuk ka kufizime pr komunikim me:- Direkt m lidhjen deri n 100 km- Rrjetin digjital t komunikimit (G703, X21)- ISDN-lidhjet- 2 deri n 3 fije drejtues fije (tel).

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    51/70

    Punim Diplome

    50

    KAPITULLI 77.1 Mbrojtja nga mbitensionet

    Mbrojtja nga mbitensionet sht nj problem q preokupon shum ekspert t teknikss tensioneve t larta. Meq tensionet klasifikohen n tensione t jashtme (atmosferike),dhe te brendshme (komutimit dhe rezonances), edhe mbrojtja nga kto ka veantit e veta.Sipas te dhnave edhe mbrojtja do t klasifikohet n mbrojtje nga mbitensionet e

    jashtme(atmosferike) dhe mbrojtja nga mbitensionet e brendshme.

    7.1.1 Mbrojtja nga mbitensionet e jashtme (atmosferike)

    Pr mbrojtje nga mbitensionet e jashtme prdoren kto pajisje:- Rrufepritsi,- Pruesi mbrojts,- Sferat mbrojtse dhe- Shkarkuesit e mbitensioneve.

    Si element prcjells i do pajisje mbrojtse nga mbitensionet sht gjithmon tokzimi-rezistenca e prtokzimit.

    7.1.2 Rrufepritsi

    Nuk ka mbrojtje absolute nga goditja e rrufes. Megjithat mbrojtje shum efikase ngagoditjet direkte e rrufes bhet me ann e rrufepritsit. do rrufeprits prbhet prejmarrsit, prcjellsve, dhe rezistencs s tokzimit.Karakteristika themelore e rrufepritsit sht zona mbrojtse e tij, e cila n raste m tshpeshta prcaktohet eksperimentalisht.

    Fig 7.1 Zona mbrojtse e rrufepritsit

    hx- lartsia e rrufepritsit

    ha- lartsia aktive mbrojtse

    x- rrezja mbrojtse

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    52/70

    Punim Diplome

    51

    7.1.2.1 Realizimi i rrufepritsit n TS 220/35/10(20)kV, Podujev

    Fig 7.2 pamja e rrufepritsve n TS 220/35/10(20) kV, Podujev.

    Jan t vendosur katr rrufeprits me lartsi t ndryshme,dy t paret m t shkurtr sedy tjert si nfig 7.2 ku sht dhn pamja e rrufepritsve.Zona mbrojtse e ktyre dy rrufepritsve sht dhn n fig 7.3.

    Fig 7.3 Zona mbrojtse e dy rrufepritsve dhe zona mbrojtse e rrufepritsve n TS 220/35/10(20) kV n Podujev

    Parametri b ndikon q t caktohet projeksioni i zons mbrojtse te dy rrufepritsve.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    53/70

    Punim Diplome

    52

    7.1.3 Pruesi mbrojts

    M qllim t mbrojtjes s pruesve t fazs nga goditja e drejtprdrejt e rrufes, nlargprues vendoset pruesi mbrojtsfig.Mbrojtja e pruesve fazor nga goditja e drejtprdrejt varet shum nga kndi mbrojts ipruesit mbrojts.

    a) b)Fig 7.4 a) Goditja e drejtprdrejt e rrufes n pruesin mbrojts n pruesin fazor dhe n afrsi t

    shtylls s tensionit t lart, b) kndi mbrojts i pruesit mbrojts

    7.1.3.1 Pruesi mbrojts n TS 220/35/10 kV, Podujev

    Fig 7.5 Vendosja e pruesve mbrojts n TS 220/35/10(20) kV

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    54/70

    Punim Diplome

    53

    Njri prues mbrojts vije nga linja L205-1 nga Kosova B hyn n TS 220/35/10(20)kV n Podujev dhe pastaj del nga t njjtat shtylla deri ne linjn L205-2 q shkon ndrejtim t Krushevcit, si nfig 7.5.

    7.1.4 Sferat mbrojtse

    Sferat mbrojtse-sferat matse mbrojtse ndrtohen prej metali, me siprfaqe shum tlmuet-veanrisht prpunohet pjesa ku bhet kaprcimi i tensionit.Njra sfer sht n potencial t toks, ndrsa tjetra n potencial t lart. Zakonishtvendosen paralel me izolimin, me qellim t mbrojtjes s tij nga tensioni q sht m ilart se vlera e tensionit t durimit te izolimit (Uk

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    55/70

    Punim Diplome

    54

    a) b)

    Fig 7.7 a) Skema e konstruksionit t SHGM b) Skema ideore e SHGM

    SHGM prbhen prej dy sferave dhe nj gypi prej fiberi. Njra sfer sht vendosur

    brenda gypit, ndrsa tjetra jasht. Kto sfera n mes veti jan t lidhura n seri. Sfera nbrendi t gypit prbhet prej dy elemente, njra lidhet m token kurse tjetra ne elektrodne sfers s jashtme.

    7.1.5.2 Shkarkuesit ventil t mbitensionit

    Shkarkuesit ventil t mbitensionit (SHVM) ose si quhen shpesh shkarkuesit katodik,jan aparate me t cilt bhet mbrojtja m efikase nga mbitensionet, kto aparateprbhen nga tri pjes kryesore

    Fig 7.8 shkarkuesit ventil t mbitensionit SHVM

    Kur vala e mbitensionit bredh neper linja dhe ndeshet me SHVM, e kur vlera e valsbredhse sht m e madhe se tensioni i prballimit t izolimit tensioni kaprcen n mest sferave, arrin deri t rezistenca jo lineare e cila kt impuls t shkurtr e prcjell n tok.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    56/70

    Punim Diplome

    55

    7.1.5.3 Shkarkuesit metal-oksid t mbitensionit

    Elemente t vetme aktive t shkarkuesit metal-oksid t mbitensionit jan varistortmetal-oksid. Nga aspekti konstruktiv komponenta shkarkuese metal-oksid sht m ethjesht sepse n t nuk ekziston hapsira xix, vendosen n shtpizn prej porcelani.

    Shkarkuesit metal-oksid mund t ndrtohen me m nj apo m shum shtylla paralelevaristorsh .

    7.1.5.3.1 Shkarkuesit metal-oksid t mbitensionit n TS220/35/10(20) kV n Podujev

    N TS 220/35/10(20) kV n Podujev jan t vendosur shkarkuesit metal-oksid tmbitensionit me izolator silikon-gom dy llojesh. Lloji i par i shkarkuesve t mbitensionitq jan t vendosur n TS n Podujev jan gjasht shkarkues metal-oksid t vendosurvertikal te tipit Siemens 3EQ-1, dhe gjasht shkarkues t mbitensionit metal-oksid tvarrur n konstruksionin e TS n Podujev t tipit Siemens 3EL-2 t cilt jan paraqitur

    n (fig 7.9).

    Fig 7.9 Shkarkuesit metal-oksid n TS 220/35/10(20) kV n Podujev

    Fig 7.10 Diagrami i nnstacionit i me SH M-O t mbitensionit 3EQ-1

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    57/70

    Punim Diplome

    56

    7.1.5.3.2 Varistor metal-oksid

    Varistor metal-oksidjan t vetmit elemente aktive q prdoren pr ndrtimin eshkarkuesve metal-oksid te mbitensionit. Varistoret ndrtohen n form t diskut. Ngaaspekti teknologjik, varistoret prbjn kryesisht oksid zinku ZnO, (94-96%) dhe sasi tvogl t disa oksideve tjerash: Bi2O3, CoO, Cr2O3, MnO, Sb2O3, etj.Varistor metal-oksid ka karakteristik V-A jashtzakonisht jo linear dhe aftsi prlargimin e nxehtsis q krijohet n t.

    Fig 7.11 Konstruksioni i shkarkuesit metal-oksid t mbitensionitSiemens 3EQ dhe Siemens 3EL.

    Fig 7.12 Skema e thjeshtuar e vendosjes s SHMT dhe zona e tyre mbrojtse.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    58/70

    Punim Diplome

    57

    Llojet e SHMT silikon-gom: 3EQ1 - 420 kV, 3EQ4 deri n 500 kV, 3EQ3- 800 kV, 3EQ5 - 1200kVFig 7.8 Disa lloje t SHMT qe mund t vendosen n natyr

    Llojet e SHMT-ve silikon-gom: 3EL5 deri n 145 kV, 3EL1 - 362 kV, 3EL2 - 550 kV,

    Fig 7.13 Disa lloje t SHMT-ve pr mbrojtjen e stacioneve n rast t mbitensionit n linja

    Llojet e SHMT-ve porcelan: 3EP5 deri n 123kV 3EP 800 kV 3EP4362 kV 3EP2550 kV

    Fig 7.14Disa lloje t SHMT-ve pr mbrojtjen e stacioneve n rast t mbitensionit n linja

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    59/70

    Punim Diplome

    58

    7.2 Linjat pr bartjen e energjis elektrike

    N prputhje me ndarjen e tensionit n: tension t ult deri n 1000 V, dhe tension tlart mbi 1000 V edhe linjat ndahen n:

    - Linja te tensionit t ult dhe- Linja t tensionit t lart.

    N prputhje me kt linjat e tensionit t lart ndahen n:- Linjat e tensionit t mesm ( p.sh. 10, 20, 35 kV)- Linjat e tensionit t lart ( p.sh. 110, 220 kV)- Linjat e tensionit shum t lart (p.sh. 400, 750, 1150 kV).

    Rrjetin e transmisionit q prmban linjat e tensionit t lart dhe shum t lart.

    Elementet baz t linjave energjetike jan:- Pruesit,- Litart sigurues,

    - Shtyllat (koka, trupi, themeli),- Izolatort dhe- Tokzimi.

    7.2.1 Pruesit

    Pruesit mund t jen masiv, gypor dhe n form litari. Pr linja elektrike, prues tipiksht litari i prbr nga telat e ktyre materialeve: bakri (Cu), alumini (Al), eliku(Fe)etj.

    Litari prbhet nga disa tela t prdredhur n mes veti qe te arrihet fortsia e duhurmekanike. Numri i telave npr shtresa sht prcaktuar saktsisht ndrsa numri i

    trsishm i telave prcaktohet n baz te relacionit:

    Fig 7.15 Disa nga llojet e pruesve

    Linjat ajrore L205 qe furnizojn TS 220/35/10(20) kV n Podujev gjegjsisht linjainterkonektive q lidhin termocentralin Kosova B me Krushevcin, jan prues Al/Fe 6:1me seksion 3x360/57 mm2.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    60/70

    Punim Diplome

    59

    SeksioniStandard(mm2)

    TensioniNominalUn(kV)

    Tab. 7.1 seksionet standarde pr linjat ajrore Al/Fe 6:1

    SeksioniStandard(mm2)

    RrymakufitareIk(A)

    90 125 145 170 235 290 345 400 455 490 530 615 780 950

    Tab. 7.2 Ngarkesa e pruesve Al/Fe 6:1

    Seksioni i pruesit Niveli i tensionit In (t0=40 C)Linjat AjroreCu 150 mm 110 kV 480 A 90 MVA

    Al/e 150/25 mm 110 kV 440 A 84 MVAAl/e 240/40 mm2 110 kV 605 A 115 MVA

    Al/e 360/57 mm2 110 kV 780 A 149 MVA

    Al/e 360/57 mm2 220 kV 780 A 297 MVA

    Al/e 490/65 mm2 220 kV 951 A 362 MVA

    Al/e 2x490/65 mm2 400 kV 1900 A 1316 MVAKabllo nntoksoreAl/e 300 mm2 110 kV 475 A 90

    Al/e 400 mm2 110 kV 510 A 100

    Al/e 1000 mm2 110 kV 740 A 140

    Tab. 7.3 Nivelet e pruesve Al/Fe 6:1Dimensionet e pruesve fazor dhe atij mbrojts pr linjat e transmisionit po ashtu jan

    t standardizuara si n vijim:Pr linjat 110 kV: pruesi 1x240/40 mm2 prej Ale, pruesi i tokzimit C 1x50 mm2;Pr linjat 220 kV: pruesi 1x360/65 mm2 prej Ale, pruesi i tokzimit C 2x50 mm2ose 1x490/65 mm2 prej Ale pruesi i tokzimit C 2x70 mm2.Pr linjat 400 kV: pruesi 2x490/65 mm2 prej Ale, pruesi i tokzimit Al 2x126mm2.

    (1-10 kV)

    (20-35 kV)

    110 kV

    220 kV

    400 kV

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    61/70

    Punim Diplome

    60

    Prve linjave ajrore jan edhe linjat kabllore, ku gjat konstruktimit t tyre rndsi eveant duhet ti jepet temperaturs s kabllove, ku temperatura nuk guxon t kaloj +40oCt temperaturs maksimale t ambientit +350C.Nse krahasojm linjat ajrore dhe ato kabllore, linja kabllore sht m e sigurt sepse ka

    prishje m pak, linjat ajrore m leht caktohen prishjet dhe jan m t lira.

    Fig 7.16 Disa lloje t kabllove

    7.2.2 Shtyllat

    Linjat elektrike prbhen prej tri pjesve kryesore Pruesve, izolatorve dhe shtyllave.Shtyllat si konstruksione mbajtse, mbajn pruesit dhe litart mbrojts.Sipas ndrtimit shtyllat ndahen n: shtylla prej druri, betoni dhe eliku.Sipas destinimit shtyllat ndahen n:

    - Shtylla mbshtetse,- Shtylla shtrnguese,- Shtylla kndore, fundore, kryqore etj.

    Fig 7.17 Shembulli i shtyllave te drurit: 1)linjat e tensionit t ult, 2)10-20 kV, 3) 35 kV 4) 110 kV, 5) 35-

    110 kV

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    62/70

    Punim Diplome

    61

    Fig 7.18 Shembulli i shtyllave te betonit:1) shtylla e tensionit t ult, 2) 10-20 kV, 3) 110 kV,4) 35-110 kV,

    5)35-110 kV.

    Fig 7.19 Shembujt e shtyllave t elikut a)nj rendore dhe b) dy rendore

    Shtyllat duhet t dimensionohen me standarde ashtu q t sigurojn bartje t fuqis nmeny kualitative, p.sh.

    Pr linja 380 kV, lartsia e shtylls sht 50 m dhe fuqia q bartin sht 1600 MW,Pr linja 220 kV, lartsia e shtylls sht 35 m dhe fuqia q bartin sht 480 MW,Pr linja 110 kV, lartsia e shtylls sht 30 m dhe fuqia q bartin sht 120 MW.

    Llogaritja mesatare gjeometrike e prcjellsve te linjave pr linjat trefazore mund tellogaritet nga ekuacioni:

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    63/70

    Punim Diplome

    62

    Pr 110 kV ~ 4.0-6.0 [m]

    Pr 220 kV - || - ~ 7 [m]Pr 400 kV - || - ~ 12[m]

    Fig 7.20 Koka e shtyllave pr disa lloje t linjave

    Fig 7.21 Standardet e ndrtimit te shtylls 110 kV.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    64/70

    Punim Diplome

    63

    Fig 7.22 Standardet e ndrtimit te shtylls 220 kV.

    Fig 7.23 Standardet e ndrtimit te shtylls 400 kV.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    65/70

    Punim Diplome

    64

    7.2.3 Izolatort

    Izolator e linjave ajrore duhet te ken aftsi izoluese, pra izolatort duhet t pengojnrrjedhje e rryms npr ta me fjal t tjera duhet te ken rezistenc t madhe dhe duhet tiprballojn forcat shtrnguese qe ti mbajn pruesit n pozitat e tyre standarde, dhe t

    mbajn peshn e pruesve dhe peshat shtes.Sipas mnyrs se mbajtjes izolatort mund te jen: mbshtets (n form kapaku), vars

    (vargor), kalimtar.Izolatort mbshtets prdoret deri n 10 kV ndrsa pr 35 kV e m shum prdoren m

    rrall.

    Fig 7.24 Izolatort: (1) tipit NN, (2) tipit SN, (3) tipit VK, (4)tipit L (form shkopi), (5 )i prbr

    Izolatort vars sipas mnyrs se ndrtimit mund t jen:- Izolator n form kapele- Izolator masiv dhe- Izolator n form shkopi.

    Izolatort n form kapele prbhet nga disa elemente n form kapele te lidhura nvarg me lidhza specialefig 4.25, ku numri i tyre varet nga tensioni standard dhe vendi iprdorimit.

    Fig 7.25 a) Izolatort n form pjate:1) porcelan, 2)-3) gjam 4) aerodinamik

    b)Izolator pjat t lidhur n zinxhir: (1) t vetm 120 kN, (2) dyfisht 210 kN

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    66/70

    Punim Diplome

    65

    a) b)

    c) d)Fig 7.27 Izolatort 220 kV a). EPS 220-120-2432-22,16NN16, b). EPS 220-160-2653-31,22-NN20

    c). Nj rendsh shtrngues 120 kN d). Dy rendsh shtrngues 210 kN

    Fig 7.26 Izolatort zinxhir forcues

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    67/70

    Punim Diplome

    66

    KAPITULLI 8

    8.1 Mundsit e kalimit nga 220/35/10 kV n 110/20 kV

    Kalimi n nivelin e tensionit 110/20 sht zgjedhje e mir qe te kemi nj furnizim same te mir me energji elektrike jo vetm ne komunn e Podujevs po edhe n trKosovn kjo sht vrtetuar si ne aspektin teknik ashtu edhe n at ekonomik.Si rezultat i kalimit nga 10 kV n nivelin 20 kV rniet e tensionit dhe humbjet e fuqis dot zvoglohen shum, kapaciteti i linjave do te dyfishohet n krahasim me at gjatoperimit n 10 kV.

    Derisa te bhet komplet kalimi ne nivel t tensionit 20 kV, krkohet qe t prdort njnivel i tensionit kalimtar i przier (35 kV, 20 kV, 10 kV). Kjo bhet n meny q t keminj furnizim rezerv m t mir n 35/10 kV dhe veanrisht n trafo stacionet 35/20

    /(10) (kV/kV/kV) qe do te jen n dispozicion gjat periudhs s rikonstruktimit.

    E mira e ktij kalimi t transformimi t tensioni nga niveli 10/0.4 (kV/kV) n at 20/0.4(kV/kV) sht se humbjet jan dukshm m t vogla dhe at pr shkak se:

    - Eliminohen TR 400/220/110 (kV/kV/kV) duke e zvendsuar n at 400/110(kV/kV),

    - Rniet e tensionit zvoglohen dukshm si pasoj si pasoj e zvoglimit t humbjevevetanake me zvoglimin e transformatorve.

    Kjo pr komunn e Podujevs mund te realizohet n dy mnyra:- Mnyra e par, mund te realizohet ather kur t eliminohet nga sistemi, rrjeti 220

    kV sipas nj standardi ndrkombtar , dhe n dhe n baz t ksaj adaptojmlinjn 220 kV Kosova B-Podujev t ndrtohet linja 110 kV deri n nj NS 110/20kV q do t ndrtohet n vend t TS 220/35/10 kV.

    - Kurse mnyra e dyt sht eliminimi i linjs 220 kV dhe vendosja e njtransformatori 440/110 (kV/kV), n linjn interkonektive L437 Kosova BNish.

    Nnstacioni 400/110 kV do t jet me konfiguracion t zbarrave t dyfishta me fushlidhse dhe n sistem t hapur.N figurn 8.1 sht paraqitur konfiguracioni standard prnnstacionet e nivelit t tensionit 400/110 kV. Sistemi i zbarrave t dyfishta pr nivelin etensionit 400 kV i treguar n fig 8.1 mund t avancohet me sistemin shtes t zbarrsndihmse, n nnstacionet t cilat jan t lidhura m shum se tri linja 400 kV.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    68/70

    Punim Diplome

    67

    Fig 8.1 Planifikimi standard i konfiguracionit t zbarrave t nnstacionit t ri t planifikuar

    n rrjetin e transmisionit 400 kV

    Ndrsa pr nnstacionet t cilat do t lidhen m shum se dy linja aplikohet sistemi mezbarra t dyfishta me fush lidhse ashtu si sht treguar n fig 8.2.

    Fig 8.2

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    69/70

    Punim Diplome

    68

    PRFUNDIMI

    N kt tem me titull TS 220/35/10(20) kV Podujev, mundsit e kalimit n 110/20

    kV sht paraqit stacioni transformator-ik n Podujev dhe jan dhn disa mundsi prkalimin n sistemin 110/20 kV.

    Tema sht ndar n tet kapituj. N fillim ( hyrje ) sht br prshkrimi i rndsis sfurnizimit m energji elektrike dhe bartja e saj deri n stacionin transformator-ik prmeslart pruesve. N kapitullin e par, pika t shkurta kemi folur kemi folur pr mihjetsiprfaqsore, termo dhe hidro centralet dhe turbinat me er n prgjithsi prodhimi ienergjis n Republikn e Kosovs. N kapitullin e dyt kemi folur pr rrjetin etransmisionit t Republiks s Kosovs, Linjat interkonektive, nnstacionet aktuale

    elektrike. N kapitullin e tret kryesisht kemi folur pr TS 220/35/10(20) kV nPodujev, konstruksionin e ti dhe elementet kryesore dhe transformatort n t. Nkapitullin e katrt jan prshkruar elementet kryesore t TS 220/35/10(20) kV nPodujev, dhe sht br prshkrimi i tyre. N kapitullin e pest kemi prfshir dheshpjeguar rolin dhe punn e transformatorve mats. N kapitullin e gjasht shtshpjeguar mbrojtja e TS 220/35/10(20) kV n Podujev. Dhe n kapitullin e fundit kemishpjeguar mundsit e kalimit nga sistemi 220/35/10(20) kV n at 110/20 kV nKomunn e Podujevs, ku kam paraqitur dy mundsi qe un kam vrejtur pr kt kalim.

  • 7/30/2019 Punim Diplome, Bashkim Statovci

    70/70

    Punim Diplome

    LITERATURA:

    1. Dr.sc. Isuf Krasniqi dhe Mr.sc. Gani Latifi, Teknika e tensioneve t larta, Prishtin1996.2. Korporata Energjetike e Kosovs KEK, distribucioni Podujev. www.kek-energy.com3. Operatori i Sistemit, Transmisionit dhe Tregut-KOSTT sh.a , www.kostt.com4. Dr. Sabri Limari, Rrjetat elektrike ( dispens ) Prishtin.5. Dr. Ali Gashi, Mbrojtja Rele ( dispens ) Prishtin.6. Dr. Sabri Limari, Dr Luan Ahma, elementet e sistemeve elektroenergjetike Prishtin1997.7. Dr. Vjollca Komoni Sistemi pr furnizim t pandrprer-UPS (dispens ) Prishtin.