Page 1 of 27 Pump Performance Datasheet Customer : 6115- SPP Inc Mexico Customer enquiry : 500-125 INL Item number : 001 Usage - Tertiary : Quantity : 1 Quote number : 319328 Pump Size : KFL10X Stages : 1 Based on curve number : KFL10X Date last saved : 11 Apr 2019 1:18 PM Operating Conditions Flow, rated : 500.0 USgpm Differential Head (requested) : 125.0 psi Suction pressure, rated / max : 0.00 / 0.00 psi.g NPSH available, rated : Ample Frequency : 60 Hz NFPA Limits Flow, rated : 500.0 USgpm Head, rated : 125.0 psi Power, rated : 46.64 hp NPSHr, rated : - Efficiency, rated : 78 % Flow at 150% : 750.0 USgpm Head at 150%, actual/limit : 101.6 psi Efficiency at 150% : 75 % NPSHr at 150% flow : - Power required at 150% flow : 58.94 hp Peak power : 66.89 hp Closed valve pressure : 142.8 psi.g 140% Head at shutoff : 175.0 psi 65% Head at 150% flow : 81.27 psi Cooling flow (None) : 0.00 USgpm Pressure Data Maximum working pressure : 142.8 psi.g Maximum allowable working pressure : 222.0 psi.g Maximum allowable suction pressure : 75.00 psi.g Hydrostatic test pressure : 214.2 psi.g Liquid Liquid Type/ Application : Water Additional liquid description : Temperature, max : 68.00 deg F Fluid density, rated / max : 1.000 / 1.000 SG Viscosity, rated : 1.00 cP Performance Speed, rated : 3500 rpm Impeller diameter, rated (approx.) : 8.74 in Impeller diameter, maximum : 8.82 in Impeller diameter, minimum : 7.72 in Efficiency : 78 % NPSH required / margin required : - / 0.00 ft Head, maximum, rated diameter (approx.) : 142.8 psi Diameter ratio (rated / max) : 99.11 % Driver & Power Data (@Max density) Power, hydraulic : 36.47 hp Power, rated : 46.64 hp Power, maximum, rated diameter : 66.89 hp Material Material selected : Code X - CI / BR /SS Selection status FM/UL/cUL approved : FM/UL Near miss reasons : 0 20 40 60 80 Power - hp Power 0 20 40 60 80 100 120 140 160 180 200 0 10 20 30 40 50 60 70 80 90 100 0 100 200 300 400 500 600 700 800 900 1,000 1,100 1,200 Head - psi Efficiency - % Flow - USgpm 8.74 in Efficiency

Upload: others

Post on 08-Apr-2020

22 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 1 of 27

Pump Performance DatasheetCustomer : 6115- SPP Inc MexicoCustomer enquiry : 500-125 INLItem number : 001Usage - Tertiary :Quantity : 1

Quote number : 319328 Pump Size : KFL10XStages : 1Based on curve number : KFL10XDate last saved : 11 Apr 2019 1:18 PM

Operating ConditionsFlow, rated : 500.0 USgpmDifferential Head (requested) : 125.0 psiSuction pressure, rated / max : 0.00 / 0.00 psi.gNPSH available, rated : AmpleFrequency : 60 Hz

NFPA LimitsFlow, rated : 500.0 USgpmHead, rated : 125.0 psiPower, rated : 46.64 hpNPSHr, rated : -Efficiency, rated : 78 %Flow at 150% : 750.0 USgpmHead at 150%, actual/limit : 101.6 psiEfficiency at 150% : 75 %NPSHr at 150% flow : -Power required at 150% flow : 58.94 hpPeak power : 66.89 hpClosed valve pressure : 142.8 psi.g140% Head at shutoff : 175.0 psi65% Head at 150% flow : 81.27 psiCooling flow (None) : 0.00 USgpm

Pressure DataMaximum working pressure : 142.8 psi.gMaximum allowable working pressure : 222.0 psi.gMaximum allowable suction pressure : 75.00 psi.gHydrostatic test pressure : 214.2 psi.g

LiquidLiquid Type/ Application : WaterAdditional liquid description :Temperature, max : 68.00 deg FFluid density, rated / max : 1.000 / 1.000 SGViscosity, rated : 1.00 cP

PerformanceSpeed, rated : 3500 rpmImpeller diameter, rated (approx.) : 8.74 inImpeller diameter, maximum : 8.82 inImpeller diameter, minimum : 7.72 inEfficiency : 78 %NPSH required / margin required : - / 0.00 ftHead, maximum, rated diameter(approx.)

: 142.8 psi

Diameter ratio (rated / max) : 99.11 %Driver & Power Data (@Max density)

Power, hydraulic : 36.47 hpPower, rated : 46.64 hpPower, maximum, rated diameter : 66.89 hp

MaterialMaterial selected : Code X - CI / BR /SS

Selection statusFM/UL/cUL approved : FM/ULNear miss reasons :

0

20

40

60

80

Pow

er -

hp

Power

0

20

40

60

80

100

120

140

160

180

200

0

10

20

30

40

50

60

70

80

90

100

0 100 200 300 400 500 600 700 800 900 1,000 1,100 1,200

Hea

d - p

si

Effic

ienc

y - %

Flow - USgpm

8.74 in

Efficiency

Page 2: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 2 of 27

Pump Performance DatasheetCustomer : 6115- SPP Inc MexicoCustomer enquiry : 500-125 INLItem number : 001Usage - Tertiary :Quantity : 1

Quote number : 319328 Pump Size : KFL10XStages : 1Based on curve number : KFL10XDate last saved : 11 Apr 2019 1:18 PM

Operating ConditionsFlow, rated : 500.0 USgpmDifferential Head (requested) : 125.0 psiSuction pressure, rated / max : 0.00 / 0.00 psi.gNPSH available, rated : AmpleFrequency : 60 Hz

LiquidLiquid Type/ Application : WaterAdditional liquid description :Temperature, max : 68.00 deg FFluid density, rated / max : 1.000 / 1.000 SGViscosity, rated : 1.00 cP

Flow Head Pump Efficiency Power Required NPSH required(USgpm) (psi) (%) (hp) (ft)0.00 142.8 0 24.76 -133.6 138.7 37 29.58 -267.2 134.8 60 35.25 -400.8 130.0 73 41.62 -534.4 122.9 79 48.39 -668.0 111.6 79 55.09 -801.6 93.88 72 61.18 -935.2 67.12 56 65.81 -1,068.8 28.28 27 65.10 -

Page 3: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 3 of 27

11.02 11.02

6.22 7.32

6.007.52

11.81

10.58

19.67

42.06

14.02

00000000000000000000000000000000000000000

Page 4: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 4 of 27

Page 5: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 5 of 27

Page 6: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 6 of 27

SBP1000-51(C)

STANDARD SUBMITTAL PACKAGE

Page 7: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 7 of 27

FTA1000 Full Voltage Starting Electric Fire Pump ControllersProduct Description

Description – Firetrol® FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fire pumps where the capacity of the power source permits full voltage starting. Full voltage is ap-plied to the motor as soon as the controller is actuated. The controller monitors, displays and records fi re pump system information.

Full voltage starting is simple and low cost and is pre-ferred whenever the utility or emergency generator set will permit this type of starting.

Approvals – Firetrol fi re pump controllers are listed by Underwriters’ Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the require-ments of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code.

Standard Features—The following are included as stan-dard with each controller:• Voltage surge protector• Main Disconnect Switch sized for connected motor

horsepower and voltage• Fire pump Circuit Breaker• Single handle Isolating Disconnect Switch/Circuit

Breaker mechanism• Motor contactor• Emergency Manual Run Mechanism to mechanically

close motor contactor contacts in an emergency con-dition

• Built-in Start and Stop push-buttons to bypass auto-matic start circuits

• Minimum Run Timer / Off Delay Timer• Daylight Savings Time Option• Weekly Test Timer• Elapsed Time Meter

• Door mounted display/interface panel featuring a 128 x 64 pixel backlit LCD Graphical Display, Membrane Type User Control Push-buttons and easy to read LED Indicators for:

• POWER AVAILABLE • ALARM • TRANSFER SWITCH NORMAL (If unit ordered with

Automatic Power Transfer Switch) • TRANSFER SWITCH EMERGENCY (If unit ordered with

Automatic Power Transfer Switch) • SYSTEM PRESSURE LOW • PUMP RUNNING • DELUGE OPEN • REMOTE START • INTERLOCK ON

• FAIL TO START• MOTOR OVERLOAD

• EMERGENCY ISO SWITCH OFF (If unit ordered with Automatic Power Transfer Switch)

• PHASE FAILURE• PHASE REVERSAL• AUTOMATIC SHUTDOWN DISABLED• OVERVOLTAGE• UNDERVOLTAGE

• Digital Pressure Display• USB Host Controller and Port• Solid State Pressure Transducer• Data Log• Event Log (3000 Events)• True RMS Metering with simultaneous 3 Phase Display

of Amps, Volts, Frequency, Pressure and Alarm Mes-sages

• Disk Error message• Disk Near Full message• Pressure Error message• Motor Over 320% message• Local Start message• Remote Start message• Emergency Start message• Fail To Start message• Undervoltage message• Overvoltage message• NEMA Type 2 (IEC IP22) enclosure• Suitable for use as Service Equipment• Each standard controller comes with user confi gurable

options for: • Interlock Alarm • Low Pressure Audible •Low Suction • Pump Run • User Defi ned Input • Weekly Test

Page 8: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 8 of 27

FTA1000 — FTA1930 Electric Fire Pump ControllersSpecifications

Main Fire Pump Controller The main fi re pump controller shall be a factory assembled, wired and tested unit and shall conform to all the requirements of the latest edition of NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection and NFPA 70, National Electrical Code. The controller shall be listed by Underwriters Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Con-trollers, CSA, and Canadian Standards Association CSA-C22.2, Standard for Industrial Control Equipment (cULus), approved by Factory Mutual and approved by the City of New York for fi re pump service.

Starting Method The controller shall be of the combined manual and auto-matic type designed for:

� Full Voltage Starting � Wye (Star)-Delta Open Transition Starting � Wye (Star)-Delta Closed Transition Starting � Part Winding Starting � Primary Resistance Reduced Voltage Starting � Autotransformer Reduced Voltage Starting � Digital Soft Start Reduced Current Starting

of the fi re pump motor having the horsepower, voltage, phase and frequency rating shown on the plans and drawings. The controller components shall be housed in a NEMA Type 2 (IEC IP22) drip-proof, wall mounted enclosure.

Withstand Ratings (Short Circuit Current Ratings) All controller components shall be front mounted, wired and front accessible for maintenance. The minimum withstand rating of the controllers shall not be less than 100,000 Amps RMS Symmetrical at 200-600 Volts*. If the available system fault current exceeds these ratings, the controllers shall be supplied with a withstand rating of 150,000 or 200,000 Amps RMS Symmetrical, as required. *Note: 100,000 Amp withstand rating not available in some larger horsepowers. Consult factory for details.

Isolation Switch and Circuit Breaker The controller shall include a motor rated combination isolating disconnect switch/circuit breaker, mechanically inter-locked and operated with a single, externally mounted handle. When moving the handle from OFF to ON, the interlocking mechanism shall sequence the isolating disconnect switch ON fi rst, and then the circuit breaker. When the handle is moved from ON to OFF, the interlocking mechanism shall sequence the circuit breaker OFF fi rst, and then the isolating disconnect switch. The isolating disconnect switch/circuit breaker shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated bypass mechanism. The isolating disconnect switch/circuit breaker shall be capable of being padlocked in the OFF position for installation and maintenance safety, and shall also be capable of being locked in the ON position without affecting the tripping characteristics of the circuit breaker. The controller door shall have a locking type handle and three point cam and roller vault type hardware. The circuit breaker

trip curve adjustment shall be factory set, tested and sealed for the full load amps of the connected motor. The circuit breaker shall be capable of being fi eld tested to verify actual pick up, locked rotor, and instantaneous trip points after fi eld installa-tion without disturbing incoming line and load conductors.

Operator Interface The fi re pump controller shall feature an operator interface with user keypad. The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and pressure conditions shall be displayed with a time and date stamp. The display shall be a 128x64 Backlit LCD capable of customized graphics. The display and interface shall be NEMA rated for Type 2, 3R, 4, 4X, and 12 protection and shall be fully accessible without opening the controller door. The display and user interface shall utilize multiple levels of password protection for system security. A minimum of 3 password levels shall be provided.

Ammeter/Voltmeter The fi re pump controller operator interface shall be capable of displaying true RMS digital motor voltage and current measurements for all three phases simultaneously. Displays requiring push-button and selector switches to toggle between phases or current and voltage shall not be accepted. Voltage and current shall be measured by True RMS technology to provide the most accurate measurement for all sine waves, including non-sinusoidal waveforms. Average responding meters will not be accepted.

Digital Status/Alarm Messages The digital display shall indicate text messages for the status and alarm conditions of:• Motor On • Sequential Start Time • Minimum Run Time • Local Start / Off Delay Time • Remote Start• Fail to Start • System Battery Low• Under Voltage • Over Voltage• Locked Rotor Trip • Over Frequency • Emergency Start • Motor Over 320% • Drive Not Installed • Motor Overload • Disk Error • Printer Error • Disk Near Full • Pressure Error

The Sequential Start Timer and Minimum Run Timer/Off Delay Timer shall be displayed as numeric values refl ecting the value of the remaining time.

LED Visual Indicators LED indicators, visible with the door closed, shall indicate:• Power Available • Alarm• Pump Running • System Pressure Low• Remote Start • Transfer Switch Normal• Deluge Open • Transfer Switch Emergency• Phase Failure • Phase Reversal• Interlock On • Fail To Start• Motor Overload • Emerg. Iso. Switch Off• Automatic Shutdown Disabled• Overvoltage • Undervoltage

Page 9: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 9 of 27

While every precaution has been taken to ensure accuracy and completeness herein, ASCO assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Information and specifications are subject to change without notice.Emerson, Consider It Solved., Emerson Network Power, the Emerson Network Power Logo, ASCO, Firetrol and the Firetrol Logo are trademarks or registered trademarks of Emerson Electric Co. All other names and logos referred to are trade names, trademarks, or registered trademarks of their respective owners. ©2013 Emerson Electric Co.

Emerson Network Power - Global Headquarters1050 Dearborn DriveColumbus, OH 43085Tel +1 614 888 0246

EmersonNetworkPower.com

ASCO Power Technologies - Firetrol Brand Products111 Corning Road, Suite 120Cary, NC 27518Tel +1 1 460 5200 Fa +1 1 460 5250

Firetrol.com

SP1000-50 (C)

Data Logging The digital display shall monitor the system and log the following data:• Motor Calls/Starts • Pump Total Run Time• Pump Last Run Time • Total Controller Pwr On Time• Last Pump Start • Min/Max System Pressure• Last Phase Fail/Reversal • Last Locked Rotor Trip• Last Locked Rotor Current • Min/Max Frequency• Max Starting Currents • Max Run Currents• Min/Max Voltage per Phase while idle (not running)• Min Voltage per Phase during Start• Min/Max Voltage per Phase during Run Event Recording Memory - The controller shall record all operational and alarm events to system memory. All events shall be time and date stamped and include an index number. The system memory shall have the capability of storing 3000 events and allow the user access to the event log via the user interface. The user shall have the ability to scroll through the stored messages in groups of 1 or 10.

USB Host Controller The controller shall have a built-in USB Host Controller. A USB port capable of accepting a USB Flash Memory Disk shall be provided. The controller shall save all operational and alarm events to the fl ash memory on a daily basis. Each saved event shall be time and date stamped. The total amount of histori-cal data saved shall solely depend on the size of the fl ash disk utilized. The controller shall have the capability to save settings and values to the fl ash disk on demand via the user interface.

Serial Communications The controller shall feature a RS485 serial communications port for use with 2 or 4 wire Modbus RTU communications.

Solid State Pressure Transducer The controller shall be supplied with a solid state pressure transducer with a range of 0-300 psi (0-20.7 bar) ±1 psi. The solid state pressure switch shall be used for both display of the system pressure and control of the fi re pump controller. Systems using analog pressure devices or mercury switches for operational control will not be accepted. The START, STOP and SYSTEM PRESSURE shall be digi-tally displayed and adjustable through the user interface. The pressure transducer shall be mounted inside the controller to prevent accidental damage. The pressure transducer shall be directly pipe mounted to a bulkhead pipe coupling without any other supporting members. Field connections shall be made externally at the controller coupling to prevent distortion of the pressure switch element and mechanism.

Seismic Certification The controller shall be certified to meet or exceed the requirements of the 2006 International Building Code and the 2010 California Building Code for Importance Factor 1.5 Electrical Equipment for Sds equal to 1.88 or less severe seismic regions. Qualifi cations shall be based upon successful tri-axial shake-table testing in accordance with ICC-ES AC-156. Certifi -cation without testing shall be unacceptable. Controller shall be clearly labeled as rated for installation in seismic areas and a Certifi cate of Conformance shall be provided with the controller.NOTE: Not available on Model FTA1500 Controllers

Operation A digitally set On Delay (Sequential Start) timer shall be provided as standard. Upon a call to start, the user interface shall display a message indicating the remaining time value of the On Delay timer. The controller shall be fi eld programmable for manual stop or automatic stop. If set for automatic stopping, the controller shall allow the user to select either a Minimum Run Timer or an Off Delay Timer. Both timers shall be programmable through the user interface. A nonadjustable restart delay timer shall be provided to allow the residual voltage of the motor to decay prior to restart-ing the motor. At least 2 seconds, but no more than 3 seconds, shall elapse between stopping and restarting the pump motor. A weekly test timer shall be provided as standard. The controller shall have the ability to program the time, date, and frequency of the weekly test. In addition, the controller shall have the capability to display a preventative maintenance mes-sage for a service inspection. The message text and frequency of occurrence shall be programmable through the user inter-face. A Lamp Test feature shall be included. The user interface shall also have the ability to display the status of the system inputs and outputs. A Audible Test feature shall be included to test the opera-tion of the audible alarm device. The controller shall not start the fi re pump motor under a single-phase condition. If the motor is already running when a phase loss occurs, the controller shall continue to run the motor, but still display a Phase Failure alarm. The fi re pump controller software shall be automatically upgradable through the USB port by simply inserting a fl ash disk with the new software. Fire pump controllers that require laptop computers, handheld equipment or specialized devices for software upgrades shall be prohibited. The controller shall be a Firetrol brand.

Page 10: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 10 of 27

Page 11: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 11 of 27

Page 12: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 12 of 27

Page 13: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 13 of 27

Page 14: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 14 of 27

Page 15: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 15 of 27

Page 16: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 16 of 27

SBP550F (A)

STANDARD SUBMITTAL PACKAGE

FTA550FJOCKEY PUMP CONTROLLERS

Page 17: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 17 of 27

FTA550F XG Jockey Pump ControllersProduct Description

Description—Firetrol® FTA550F XG Jockey Pump Controllers are intended for use with fire pump systems. They are used for pressure maintenance in fi re pump installations to prevent unnecessary operation of the main fi re pump.

Approvals—Firetrol jockey pump controllers are listed by Underwriters’ Laboratories, Inc., in ac-cordance with UL508A, Standard for Industrial Controls, and CSA, Standard for Industrial Control Equipment. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest edition NFPA 70, National Electrical Code.

Standard Features—The following are included as standard with each controller:· NEMA Type 2/12 (IEC IP22/IP54) Polycarbonate

enclosure (UL50E Construction)· Horsepower rated motor circuit protector and

starting contactor· Suitable for use as service equipment· HAND-OFF-AUTO selector switch· Minimum run timer· On-Delay timer· Pump Restart Timer· Control circuit transformer with 24VAC secondary· 0-300 psi (0-20.7 bar) stainless steel solid state

pressure transducer· Overpressure indication

· Low Pressure indication· Failed to start indication· Main switch not in “Auto” alarm· Pressure recording· Event log (3000 events stored in controller

memory)· Data log (including cycle counter)· Door mounted display/user interface featuring

a 128 x 64 pixel backlit LCD Graphical Display, Membrane Type User Controller Push-buttons and LED indication for:· Power ON

· Pump Running · Alarm· 2 lines of user selectable display information

NOTE: FTA550F XG Jockey Pump Controllers are only available in the voltage/horsepower combinations shown below and with the op-tions shown on the reverse side. For other combinations and options, see documen-tation for FTA550E series XG Jockey Pump Controllers.

VOLTAGE 3-PHASE MAX HP Short Circuit(50/60 Hertz) (MCP) Current Rating

-H 200-208 7.5 30kA-A 220-240 10 30kA-F 380-415V - WYE 15 30kA-B 440-480V - WYE 20 30kA-C 550-600V - WYE 20 18kA

VOLTAGE 1-PHASE MAX HP Short Circuit(50/60 Hertz) (MCP) Current Rating

-D 110-120 Volts 2 5kA-T 200-208 Volts 3 5kA-E 220-240 Volts 5 5kA

NOTE: Firetrol Brand Jockey Pump controllers DO NOT CONTAIN MERCURY f lled pressure switches.

Page 18: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 18 of 27

FTA550F XG Jockey Pump ControllersSpecifications

Jockey Pump Controller The auxiliary jockey pump controller, if required and specifi ed on the plans and specifi cations, shall be factory assembled, wired, and tested and specifi cally designed for this type of service. This controller shall be of the same manufacturer as the main fi re pump controller.

Approvals Firetrol Jockey Pump Controllers are listed by Under-writers Laboratories, Inc., in accordance with UL508A, Standard for Industrial Controls, and CSA, Standard for Industrial Control Equipment (cUL). They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest edition of NFPA 70, National Electrical Code.

Construction The jockey pump controller shall be full voltage start-ing, rated for wye-connected power systems above 240V. The controller components shall be housed in a NEMA Type 2/12 (IEC IP22/IP54) polycarbonate, wall mounted enclosure (UL50E Construction). The controller shall incorporate a horsepower rated manual circuit protector and starting contactor, control circuit transformer with 24VAC secondary and 200-600V multi-tap primary, main disconnect switch, HAND-OFF-AUTOMATIC selector switch and a 0-300 psi (0-20.7 bar) stainless steel solid state pressure transducer.

Short Circuit Current Ratings The jockey shall have standard short circuit current ratings of:30kA @ 480 Volts Max. (3-Phase)18kA @ 600 Volts (3-Phase)5kA @ 240 Volts Max. (1-Phase)

Operator Interface The jockey pump controller shall feature an operator interface with user keypad. The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. The display shall be a 128x64 Backlit LCD capable of customized

graphics. The display and interface shall be NEMA rated for Type 2, 3R, 4, 4X, and 12 protection and shall be fully accessible without opening the controller door. The display and user interface shall utilize multiple levels of password protection for system security. A minimum of 3 password levels shall be provided. The operator shall have the ability to choose up to 2 lines of data to be displayed on the main (home) information screen.

Digital Status/Alarm Messages The digital display shall indicate text messages for the status and alarm conditions of:• Pump Running • Sequential Start Time • Minimum Run Time • Low System Pressure • Pump Restart Timer • Fail to Start • Automatic Start • System Overpressure • User Selectable #11 • Main Switch Position • User Selectable #21 1 User may choose from the following to be shown on main display (stop pressure setting, start pressure setting, cycles/period, cycles/month, cycles/day, cycles/hour, total cycle count, pump total run time)

The Sequential Start Timer, Minimum Run Timer/Off Delay Timer and Pump Restart Timer shall be displayed as numeric values refl ecting the value of the remaining time.

LED Visual Indicators LED indicators, visible with the door closed, shall indicate:• Power ON • Alarm• Pump Running

Data Logging The digital display shall monitor the system and log the following data:• Motor Calls/Starts • Pump Total Run Time• Pump Last Run Time • Total Controller Pwr On Time• Last Pump Start • Min/Max System Pressure• Last Phase Fail/Reverse • Cycle Counts

Page 19: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 19 of 27

While every precaution has been taken to ensure accuracy and completeness herein, ASCO assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Information and specifications are subject to change without notice.Emerson, Consider It Solved., Emerson Network Power, the Emerson Network Power Logo, ASCO, Firetrol and the Firetrol Logo are trademarks or registered trademarks of Emerson Electric Co. All other names and logos referred to are trade names, trademarks, or registered trademarks of their respective owners. ©2013 Emerson Electric Co.

Emerson Network Power - Global Headquarters1050 Dearborn DriveColumbus, OH 43085Tel +1 614 888 0246

EmersonNetworkPower.com

ASCO Power Technologies - Firetrol Brand Products111 Corning Road, Suite 120Cary, NC 27518Tel +1 1 460 5200 Fa +1 1 460 5250

Firetrol.com

SP550F-01 (C)

Event Recording Memory - The controller shall record all operational and alarm events to system memory. All events shall be time and date stamped and include an index number. The system memory shall have the capability of storing 3000 events and allow the user access to the event log via the user interface. The user shall have the ability to scroll through the stored messages in groups of 1 or 10.

Serial Communications The controller shall feature a RS485 serial communica-tions port for use with 2 or 4 wire Modbus communica-tions.

Solid State Pressure Transducer The controller shall be supplied with a stainless steel solid state pressure transducer with a range of 0-300 psi (0-20.7 bar) ±1 psi. The solid state pressure transducer shall be used for both display of the system pressure and control of the jockey pump controller. Systems using ana-log pressure devices or mercury switches for operational control will not be accepted. The START and STOP PRESSURE shall be adjustable through the user interface. The pressure transducer shall be mounted inside the controller to prevent accidental damage. The pressure transducer shall be directly pipe mounted to a bulkhead pipe coupling without any other supporting members. Field connections shall be made externally at the controller coupling to prevent distortion of the pressure switch element and mechanism.

Seismic Certification The controller shall be certifi ed to meet or exceed the requirements of the 2006 International Building Code and the 2010 California Building Code with Importance

Factor 1.5 and Sds equal to 1.88 or less. Qualifi cations shall be based upon successful tri-axial shake-table testing in accordance with ICC-ES AC-156. Certifi cation without testing shall be unacceptable. Controller shall be clearly labeled as rated for installation in seismic areas and a Certifi cate of Conformance shall be provided with the controller.

Operation A digitally set On Delay (Sequential Start) timer shall be provided as standard. Upon a call to start, the user interface shall display a message indicating the remaining time value of the On Delay timer. The controller shall include a Minimum Run Timer to allow the motor to run for a set period of timer after starting. The timer shall be programmable through the user interface. A pump restart delay timer shall be provided to al-low the residual voltage of the motor to decay prior to restarting the motor and to prevent severe short cycling of the motor. The timer shall be programmable through the user interface. A Lamp Test feature shall be included. The user interface shall also have the ability to display the status of the system inputs and outputs. An Audible Test feature shall be included to test the operation of the audible alarm device (if supplied). The disconnect switch shall be mechanically inter-locked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The disconnect switch shall be capable of being padlocked in the OFF position for installation and maintenance safety. The controller shall be a Firetrol brand.

Page 20: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 20 of 27

Page 21: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 21 of 27

Page 22: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 22 of 27

Page 23: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 23 of 27

Applications

- Fire Sprinkeler Systems- Suitable for all media that will not obstruct the pressure system or attack copper alloy parts

Special features

- UL-listed (UL-393), United States and Canada (Discharge Only)

- Factory Mutual (FM) approved (Discharge Only)- Reliable and economical

Standard FeaturesPressure connection

Design Material: copper alloyEN 837-1 & ASME B40.100 1/4“ NPT lower mount (LM)

Sizes Movement4” (100 mm) Copper alloy

Accuracy class Dial± 3/2/3% of span (ASME B40.100 Grade B) White aluminum with stop pin; black and

red letteringRanges0/80 psi, retard to 250 psi (air) Pointer0/300 psi (water) Black aluminumVacuum/Compound - 30“Hg /0-300 psi (Suction Only)

CaseWorking pressure Black polycarbonateSteady: 3/4 of full scale valueFluctuating: 2/3 of full scale valueShort time: full scale value Window

Snap-in clear polycarbonateOperating temperatureAmbient: -40°F to 140°F (-40°C to 60°C) ApprovalsMedia: 140°F (+60°C) maximum UL listed (UL-393) – (Discharge Only)

Factory Mutual – (Discharge Only)Temperature errorAdditional error when temperature changes from reference temperature of 68°F (20°C) +0.4% for every 18°F (10°C) rising or falling. Percentage of span.

PRESSURE GAUGES DATASHEET

SPP Pumps Inc

Page 24: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 24 of 27

 FIRE PUMP FLOW METER 

 DP SERIES 

 Construction & Specifications Meter Dial Data Materials: Machined 1018 or 1026 Carbon Steel Construction: Aluminum Body Valves: ¼” Brass Ball  Operation: Diaphragm (Buna Convoluted)Brass Fitting: CA360  Accuracy: +2% Full ScaleFlange Option: 150# ANSI B 16.5                          300# ANSI B 16.5 

Temperature: 180 Degree F/ 80 Degrees CPressure: 500 PSIG / 3450 KPA 

ID Tag: Polycarbonate  Approx. Weight: 3/75 lbs / 1.7 KGS   4” Dial Standard – 6” Dial Available 

  

   Pressure 500 PSI  Pressure 275 PSI  Pressure 500 PSI 

SIZE  Butt Weld & Grooved  Class 150 Flanged  Class 300 Flanged 

“A” Dim  Approx Weight 

“A” Dim  Approx Weight 

“A” Dim  Approx Weight 

1‐1/4”  4.875  2 lbs  ‐‐‐  ‐‐‐  ‐‐‐  ‐‐‐ 

2”  5.000  3.5 lbs  ‐‐‐  ‐‐‐  ‐‐‐  ‐‐‐ 

2‐1/2”  4.000  5 lbs  9.250  21 lbs  10.000  28 lbs 

3”  4.000  6 lbs  3.975  30 lbs  10.250  36 lbs 

3‐1/2”  ‐‐‐  ‐‐‐  ‐‐‐  ‐‐‐  ‐‐‐  ‐‐‐ 

4”  5.375  10 lbs  11.375  40 lbs  12.125  60 lbs 

5”  6.000  20 lbs  13.000  58 lbs  13.750  84 lbs 

6”  7.000  22 lbs  14.000  70 lbs  14.750  106 lbs 

8”  7.250  45 lbs  15.250  107 lbs  16.000  195 lbs 

10”  8.000  61 lbs  16.000  165 lbs  17.250  243 lbs 

12”  12.000  128 lbs  21.000  288 lbs  22.250  408 lbs 

14”  14.000  ‐‐‐  ‐‐‐  ‐‐‐  ‐‐‐  ‐‐‐ 

16”  28.000  ‐‐‐  ‐‐‐  ‐‐‐  ‐‐‐  ‐‐‐ 

  

 

Page 25: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 25 of 27

 Engineering Specification 

  

The Venturi Style Fire Pump Test Flow Meter shall be SPP Pumps, Inc. style as follows and must be FM approved at ± 2% and rated for 500 PSI.  Venturi: 

Std. Material shall be either 1026 Carbon Steel Tubing or WCB Steel Casting, or special material specified. 

The Venturi shall have all the interior dimensions Machined to ±0.005” and all the critical outside dimensions shall also be machined to ±0.005” 

The Venturi must be Powder Coated “RED” with zero imperfections in the coating. 

The Venturi must be independently tested.  Gauge: 

Shall be Mid‐West style 140 or 142 

Shall be Aluminum body, SS springs, 4.5” Dial Face, and Acrylic Lens. 

Must have ± 2% full scale accuracy. 

The needle shall have very little to zero movement for easy reading. 

Vent fittings shall be one piece brass needle valve style. 

Side pressure fittings shall be Aluminum.  Hoses and Fittings: 

Hoses must be Goodyear Style, 24” Long with Brass 7/16” JIC F‐Swivel ends (1) must be RED in color for the high side and (1) must be GREEN for the low side. 

Fittings shall all be 1/4" NPT Brass style W/Vibra seal sealant. 

Valve shall be Rated for 600 WOG.  Installations: 

The Venturi shall be installed with a minimum “FIVE” pipe diameters upstream and “TWO” Pipe diameters down stream 

The gauge shall be installed on the Venturi W/ two screws provided 

Hose shall be installed W/ Red hoses on red fittings “HIGH PRESSURE SIDE” and Green hoses on green fittings “LOW PRESSURE SIDE” 

Page 26: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 26 of 27

Fire Protection System ServiceThe Model 55L-60 is typically used in afire protection system to tr im waterpressure, thus preventing pressure build-up whenever line pressure exceeds thesetting of the spring.

The 55L-60 will relieve excess pressure toatmosphere to prevent damage to thedistribution network.

NOTE:  Model 55L-60 is not suitable fordischarging the full-rated pump capacity ofa fire pump. See Model 50B-4KG-1 FirePump Relief Valve for such applications.

Typical Application for Fresh Water or Seawater Service

Pump Casing Relief Valve55L-60• UL Listed

• Factory Mutual Approved

• UL Listed/FM Approved for use as a Fire Pump Casing

Relief Valve

• Direct Acting - Precise Pressure Control

• Positive Dependable Opening

• Drip Tight Closure

• No Packing Glands or Stuffing Boxes

• Sensitive to Small Pressure Variations

The Cla-Val Model 55L-60 (UL Listed, FM approved) Pressure Relief Valveis a direct-acting, spring loaded, diaphragm type relief valve. The valve maybe installed in any position and will open and close within very close pressurelimits. The bottom plug may be removed and installed in the inlet to convert itto an angle pattern flow path.

The Model 55L-60 is normally held closed by the force of the compressionspring above the diaphragm. When the controlling pressure applied under thediaphragm exceeds the spring setting, the disc is lifted off its seat, permittingflow through the control. When control pressure drops below the springsetting, the spring forces the control back to its normally closed position. Thecontrolling pressure is applied to the chamber beneath the diaphragmthrough an internal passage. Gauge Port is provided for accurate pressuresetting.

Pressure adjustment is done by turning the adjusting screw to vary the springload on the diaphragm. The 55L-60 is available in pressure ranges suited toagency approval tests. To prevent tampering, the adjustment cap can be wiresealed by using the lock wire holes provided in the cap and cover.

Available in a wide rangeof materials including

nickel aluminum bronzeand stainless steel.

Certified to meet low leadrequirements

Fire Pump CasingRelief Valve

Page 27: Pump Performance Datasheet INF...The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and

Page 27 of 27

Size 1/2" & 3/4" Threaded NPTTemperature Range Water, Air: to 180°F Max.Materials

Body & Cover: Cast Bronze ASTM B62 Low LeadStainless Steel ASTM A743-CF-16Fa

Trim: 303 Stainless Steel Rubber: Buna-N® Synthetic Rubber

3.50

3.12

A A

9.24

1.31

2.00

2.00

6.75

1.31

Pressure Ratings Cast Bronze 400 psi Max.Stainless Steel 400 psi Max.

Other Materials Available on special orderAdjustment Ranges: UL Listed and FM Approved

0 to 75 psi20 to 200 psi

100 to 300 psi

Pressure Drop Chart (Full Open Valve)

Dimensions: 0 to 75 and 20 to175 psi design

When Ordering, Please Specify1. Catalog No. 55L-60 3. Adjustment Range Required2. Valve Size 4. Optional Materials

E-55L-60 (R2-01/2014)

UL Listed/FM Approved55L-60 Range

psi

Approximate Increasefor Each Clockwise Turn

of Adjusting Screw

0 to 75 8.5 psi

20 to 200 28.0 psi

100 to 300 18.0 psi

ValveSize

CvFactor

Flow of Water - Gallons Per Minute

5 10 16 20 30

1/2" 6 0.7 2.7 6 11 --

3/4" 8.5 0.3 1.4 3.1 5.5 12.2

Dimensions: 100 - 300 psi design

INLET

Specifications

(applies to bothconfigurations)

1/8” NPTPressure

Gauge Port

1/8” NPTPressure

Gauge Port

Part Number Size Spring Range

1 20881501D 1/2" 0-75

2 20881502C 1/2" 20-200

3 20885301G 1/2" 100-300

4 20881503B 3/4" 0-75

5 20881504A 3/4" 20-200

6 20885302F 3/4" 100-300

* Part #s listed are for Bronze Valves only.For Stainless Steel Valve Part #s, please consult factory.

Note :-Please refer to the Dolphin item price sheets for size information