Page 1: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

NFN

VESDA-HLI-GW

Programming and Operation Manual

Document: LS10023-000NF-E6/26/12 Rev: A2

P/N: LS10023-000NF-E: Rev. A2 ECN: 12-0294

Page 2: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

2 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Fire Alarm System LimitationsWhile a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!An automatic fire alarm system—typically made up of smoke detec-tors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability—can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.

The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommenda-tions of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. These documents can be found at http://www.systemsensor.com/html/applicat.html.

A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:

Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.

Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:

• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.

• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.

• Smoke particles may be blown away from detectors by air outlets.

• Smoke particles may be drawn into air returns before reaching the detector.

The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.

Smoke detectors, even when working properly, have sensing limita-tions. Detectors that have photo-electronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visi-ble smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec-tor may not provide adequate warning of a fire.

Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in

bedrooms), smoking in bed, and violent explosions (caused by escap-ing gas, improper storage of flammable materials, etc.).

Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.

IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connec-tion of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.

Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:

• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.

• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.

• In rare instances, the sounding of a warning device can cause tempo-rary or permanent hearing loss.

A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly main-tained and replaced regularly.

Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.

Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily dis-abled. For added protection against telephone line failure, backup radio transmission systems are recommended.

The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent work-ing order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent mainte-nance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be sched-uled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.

Page 3: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

3VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Installation PrecautionsAdherence to the following will aid in problem-free installation with long-term reliability:WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. The control unit and associated equipment may be dam-aged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.

CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product must be tested in accor-dance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any mod-ification, repair or adjustment to system hardware or wiring.

All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper sys-tem operation verified.

This system meets NFPA requirements for operation at 0°C to 49°C (32°F to 120°F) and at a relative humidity 93% ± 2% RH (non-con-densing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.

Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.

Like all solid state electronic devices this system may operate errati-cally or can be damaged when subjected to lightning-induced tran-sients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibil-ity. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services if any problems are anticipated or encountered.

Disconnect AC power and batteries prior to removing or inserting cir-cuit boards. Failure to do so can damage circuits.

Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.

Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.

Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-sup-pressive packaging to protect electronic assemblies removed from the unit.

Follow the instructions in the installation, operating, and program-ming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.

HARSH™, NIS™ and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NOTIFIER®, ONYX®, ONYXWorks®, VeriFire® and VIEW® are all registered

trademarks of Honeywell International, Inc. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of theMicrosoft Corporation.

© 2012 by Honeywell International, Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

FCC WarningWARNING: This equipment generates, uses, and can radi-ate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause inter-ference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environ-ment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.

Canadian Requirements: This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communica-tions. This Class A digital apparatus complies with Cana-dian ICES-003.

Le present appareil numerique n'emet pas de bruits radio-electriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada. Cet appareil numerique de la classe A est conforme a la norme NMB-003 du Canada.

Page 4: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

4 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Documentation FeedbackYour feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or manuals, please e-mail us at [email protected].

On-Line Help – Please include the following information:

• Product name and version number (if applicable)

• Topic title

• The content you think should be corrected/improved

• Detailed suggestions for correction/improvement

Documents – Please include the following information:

• Document part number and title

• Page number and paragraph

• The content you think should be corrected/improved

• Detailed suggestions for correction/improvement

Please Note: If you have any technical issues, please contact Technical Services.

Manual UsageThis manual is written with the understanding that the user has been trained in the proper operations and services for this product. The information provided in this manual is intended to assist the user by describing the configurations and how they affect operations.

Page 5: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

Table of Contents

1VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Table of Contents

Section 1 Product Overview ....................................................................................................31.1: Product Description .......................................................................................................................................31.2: Features..........................................................................................................................................................31.3: Compatibility .................................................................................................................................................41.4: System Architecture.......................................................................................................................................4

Figure 1.1 Network Architecture............................................................................................................51.5: IP Port Requirements .....................................................................................................................................61.6: Installation Overview.....................................................................................................................................6

1.6.1: Required Equipment ............................................................................................................................61.6.2: Power Supply and Communication Connections ................................................................................71.6.3: Board Layout .......................................................................................................................................7

Figure 1.2 VESDA-HLI-GW Board.......................................................................................................7Table 1.1 LED Definitions .....................................................................................................................8

Section 2 Configuration ...........................................................................................................92.1: Configuration Web Page................................................................................................................................92.2: Connecting the Configuration Computer.......................................................................................................92.3: Configuring the VESDA-HLI-GW................................................................................................................9

2.3.1: Logging into the Web Page .................................................................................................................92.3.2: VESDA-HLI-GW Configuration Menus...........................................................................................102.3.3: VESDA-HLI-GW Configuration Settings.........................................................................................102.3.4: Zone Mapping and Control by Event ................................................................................................12

Table 2.1 Zone Setting/Alarm State Relationships ..............................................................................122.3.5: Error Log ...........................................................................................................................................13

Table 2.2 Error Log Message Definition..............................................................................................13

Appendix A: IP Settings ......................................................................................................... 15A.1: Viewing Existing Settings...........................................................................................................................15A.2: Resetting Factory Default Settings .............................................................................................................15

Appendix B: Viewing Gateway Configuration...................................................................... 17B.1: Required Equipment ...................................................................................................................................17B.2: Viewing the Configuration..........................................................................................................................17

Page 6: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

Table of Contents

2 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Page 7: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

3VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Section 1 Product Overview

1.1 Product DescriptionThe VESDA-HLI-GW provides a communication link between the NFN network and the VESDAnet. This link enables event notification and control of devices on the VESDAnet through the NFN network. Event notifications are displayed on the fire network annunciators. Control can be initiated from these annunciators.

1.2 FeaturesMonitor (NCA-2, LCD-160, ONYXWorks) - Highest Priority event is shown on annunciators.

• Prealarm

• Fire Alarms

• Point Disable

• Troubles:

– Detector Fault

– Scanner Fault

– Power Fault

– Low Flow

– High Flow

– Filter Fault

– Field Wiring Fault

– Auto learn Failure

– No Answer.

• Supervision Troubles:

– Modbus Communications Fault (Indicates that VESDA-HLI-GW can not talk to VESDA devices.)

– VESDA Trouble

Read Status:

• Device Type

• Alarm State - Alert/Action/Fire1/Fiew2/Trouble/Isolated

• Smoke Level - This is a percentage of obscuration from 0% to 3.1% as defined by VESDA

• Detector Alarm Thresholds

Control (From NCA-2 and ONYXWorks):

• Reset - Resets all detectors on the VESDAnet

• Isolate/Enable - Isolates (Disables) and enables single detector on the VESDAnet

• Silence - Silences all local piezos on detectors

• Acknowledge

NOTE: The trouble categorizations are generic and each encompasses several troubles. Further information can be obtained by referring to XTralis resources.

Page 8: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

Product Overview Compatibility

4 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Other:

• Zone Mapping

• DCC mode is supported for Canadian applications

• Walk test is not supported by the VESDA gateway

• History - Rolling history is maintained on the gateway

• Alarms and Prealarms are latched by the VESDA detectors. Reset is required to unlatch.

1.3 Compatibility Refer to the LS10026-051NF-E VESDA-HLI-GW Listing Document for supported panels and annunciators.

Microsoft Internet Explorer version 8 or later with the latest version of JAVA is required to configure the VESDA-HLI-GW.

1.4 System ArchitectureThe VESDA-HLI-GW:

• Uses a Modbus RS-232 interface to VHX-1420-HFS

• Supervises the communications to the VHX-1420-HFS

• Monitors 100 detectors

• Displays VESDA devices as type “Aspiration” on the display nodes.

Multiple events per point are not supported. The detector will be in one of the following states:

• All Systems Normal

• Prealarm

• Fire alarm

The following events can be simultaneous with the above events:

• Disabled

• Trouble

Supported VESDA Detectors:

• VESDA Laserplus (VLP)

• VESDA Laserfocus (VLF)

• VESDA Laserscanner (VLS)

• VESDA Lasercompact (VLC)

Page 9: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

System Architecture Product Overview

5VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Figure 1.1 Network Architecture

FACP FACP

NFN Network

FACP

VESDA-HLI-GW

HS-NCMOR

NCM

VHX-1420-HFS

VESDA VLP VESDA VLF

VESDA VLC VESDA VLS

RS-232

RS-485

VESDAnet

Workstation Embedded Gateway

Display Node

Page 10: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

Product Overview IP Port Requirements

6 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

1.5 IP Port RequirementsThe following IP ports must be available to the VESDA-HLI-GW:

The following restrictions apply:

1.6 Installation Overview

Install the VESDA-HLI-GW as described in the VESDA-HLI-GW Listing Document (LS10023-051NF-E).

1.6.1 Required Equipment

VESDA-HLI-GW Assembly:

The following components are shipped with the VESDA-HLI-GW:

• VESDA-HLI-GW printed circuit board

• NUP-to-NUP Cable (P/N 75556) - Used to connect the VESDA-HLI-GW board to a standard NCM and supported panel

• USB Cable (P/N 75665) - Used to connect the VESDA-HLI-GW board an HS-NCM board:.

• Wire Leads to NUP Network Communications Module power cable (P/N 75583)

Network Components:• RJ45 to RJ45 standard Ethernet network cable - Customer’s internet or intranet connection

• NFN Network, version 5.0 or later

• Cables - P/N 50110140-001 Serial cable between the HS-NCM and the VHS-1420-HFS

• High-Speed Network Communication Module:

• Standard Network Communication Module

Customer-Supplied Equipment:

• A computer to run Internet Explorer and configure the VESDA Gateway

Port Type

80 TCP

4016 TCP

62957 TCP

Functionality Restriction

Infrastructure • Must have a Static IP Address, DHCP is not supported.• Web Access does not support access through an HTTP Proxy server, because

port 62957 is not accessible

! CAUTION: Multiple VESDA-HLI-GW InstallationsAll VESDA-HLI-GWs must be installed and configured one at a time because all VESDA-HLI-GWs use the same predefined IP address and node number.

– HS-NCM-W – HS-NCM-MF– HS-NCM-WMF – HS-NCM-SF– HS-NCM-WSF – HS-NCM-MFSF

– NCM-W– NCM-F

Page 11: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

Installation Overview Product Overview

7VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

VESDA Required Equipment (not including power supplies)

• VHS-1420-HFS

1.6.2 Power Supply and Communication Connections

The VESDA-HLI-GW must be correctly connected to a power source meeting applicable requirements and other equipment in the system in order to function properly. For detailed connection information, refer to the VESDA-HLI-GW Listing Document (LS10023-051NF-E).

1.6.3 Board Layout

Figure 1.2 VESDA-HLI-GW Board

D7

D8

D18

D2

0

D12

D10

D13

D11

D19

D14

D15

D9

D45

D33

D25

Ethernet Connector (J8)

TB1:-24 V Out

+24 V Out

-24 V In

+24 V In

USB “B” Device (J14)USB “A” Host (J13)

NUP B Serial Data Connector (J7)

Trouble Relay (TB6)

Mounting Hole (1 of 12)

LED(See Table 1.1)

NUP A Serial Data Connector (J6)

Page 12: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

Product Overview Installation Overview

8 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Table 1.1 LED Definitions

Reference Designator

Label Description

D7 WDT Active/Lit indicates the system has undergone a reset due to a Watchdog circuit firing.

D8 PWR FAIL TBD

D9 ACTIVE Active/Lit indicates that WinCE is running.

D10 NUPA RX Toggles on when data is received at the NUP A port.

D11 NUPB RX Toggles on when data is received at the NUP B port.

D12 NUPA TX Toggles on when data is sent on the NUP A port.

D13 NUPB TX Toggles on when data is sent on the NUP B port

D14 NFN A TBD

D15 NFN B TBD

D18 PROGRAM Not Used

D19 USB A Active/Lit indicates a device is connected to the USB A port.

D20 USB B Active/Lit indicates a device is connected to the USB B port.

D33 LINK Active/Lit indicates an Ethernet connection.

D45 DATA Blinks to indicate data transmission to or from the Ethernet port.

Page 13: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

9VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Section 2 Configuration

2.1 Configuration Web PageThe VESDA-HLI-GW is configured through a dedicated web page running on the embedded gateway itself. Microsoft Internet Explorer version 8 or later with the latest version of JAVA is required to configure the VESDA-HLI-GW.

2.2 Connecting the Configuration ComputerThe computer used to configure the VESDA-HLI-GW must be able to establish an IP connection to the VESDA-HLI-GW. The default IP address of the VESDA-HLI-GW is 192.168.1.2. Consult your network administrator if unsure how to make this connection.

Refer to Appendix A, “IP Settings” for instructions on resetting and reviewing the IP settings for the VESDA-HLI-GW.

2.3 Configuring the VESDA-HLI-GW

2.3.1 Logging into the Web Page1. Start Microsoft Internet Explorer.

2. Navigate to the IP address of the VESDA-HLI-GW (default is http://192.168.1.2).

3. Depending on the version of Java installed on the configuration computer, a security prompt may appear. If it does, click NO to proceed to the configuration web page.

4. If prompted, click Run to enable the applet.

5. When the login dialog box displays, enter the password (default is eight zero characters) and then click Login.

Page 14: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

Configuration Configuring the VESDA-HLI-GW

10 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 : 6/26/12

2.3.2 VESDA-HLI-GW Configuration Menus

2.3.3 VESDA-HLI-GW Configuration Settings

Menu Sub-Menu Description

File Reboot Displays a dialog box allowing the user to reboot the VESDA-HLI-GW.

Tools History Displays an events log with date, time, type of event, and description.

Set Gateway Password

Displays a dialog box allowing the user to change the current password.Default: 00000000 (eight zeros)

• Passwords are case sensitive.• Alpha and numeric characters are supported.• One character minimum and 8 characters maximum.

Backup... Browse to the folder where you would like to store current VESDA-HLI-GW configuration settings, and then click Save.

Restore... Displays a dialog box allowing that allows the user to restore the VESDA-HLI-GW configuration settings to a previously saved state.

Delete Objects Database

Displays a dialog box allowing the user to choose to delete the objects database and reboot.

Upgrade Firmware In the “Look In” drop down menu, select the file name that begins, “#VGNUW” and has the extension .AR. Then click Open. An on-screen dialog indicates a successful upgrade.

Language Displays a dialog box from which the user can navigate to and select the desired language file.

Navigation Pane Item

Sub-ItemProperty/

NodeDescription

VESDA Gateway(read only)

Type Displays the gateway type by name.

Version Displays the gateway version number.

Board Type Displays the hardware model type.

Kernel Version Displays additional software version information.

Boot Version Displays additional software version information.

Current Time/Date

Displays the current date/time information.

Additional Properties

IP Address Settings

IP Address Click the value to change the IP address. (Default is 192.168.1.2)Refer to Appendix A:, "IP Settings" for additional information.

Subnet Mask Click the value to change the subnet address. (Default is 255.255.255.0)

IP Gateway Click the value and enter the IP address of the IP Gateway for the hostnetwork.(Default is 0.0.0.0)

MAC Address This is the Media Access Control (MAC) address of the gateway Ethernet port and is not configurable.

NFN Settings Node Click value to assign the NFN node number of the VESDA-HLI-GW.(Default is 0)

Page 15: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

Configuring the VESDA-HLI-GW Configuration

11VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Navigation Pane Item

Sub-ItemProperty/

NodeDescription

Additional Properties(Cont’d)

NFN Settings (Cont’d)

Panel Label Click value to enter panel label.(Default is Vesda Gateway)

DCC Enable Check the box for DCC (Display and Control Center) participation. This network function ensures that one location at a time is in command of the Acknowledge, System Reset, Signal Silence, and Drill functions.

Channel A Threshold

Select High for a high-noise NFN network.Set to Low for a low-noise NFN network.

Channel B Threshold

Select High for a high-noise NFN network.Set to Low for a low-noise NFN network.

Style 7 • Check the box for a Style 7 SLC (Signaling Line Circuit) configured NFN network.

• Uncheck the box for a Style 4 SLC configured NFN network.

NFN Information(Read Only)

Connection Port

• Displays “Serial” when the VESDA-HLI-GW connects to an NCM through the serial port or if there is no NFN connection.

• Displays “USB” when the VESDA-HLI-GW connects to an HS-NCM via USB.

Connection Type

Describes how the gateway is connected to the NFN.

NCM Version Displays the NCM version number.

Note: NCM Version does not appear when there is no NFN connection.

NCM Status Bits

Displays the NCM status, which can be: Piezo, UPS Failure, Network Fail Port A, Network Fail Port B, High Speed Audio, NCM Sniffer Mode Active, Local Connection Limit Exceeded, or None.

Note: NCM Status Bits does not appear if when there is no NFNconnection.

Fire Network Time Policy

Always displays “Accept Time” since VESDA-HLI-GW accepts the time from the network, but does not broadcast time to the network.

Mapping Check the box next to each detector with which the gateway will communicate. Once mapped, the gateway is able to access detector information.

Zone Label Configuration

• Double-click to display a list of zone labels. • Click on the zone to display its property screen.

Label • Click on the value to change the zone label. • Click Save to save the change.

Monitored Zone List

Label Click the value to enter the label for the detector.

Extended Label

Read only.

Zone Configuration

Displays a list of the ten general zones supported by the gateway and their settings.

• Click on the zone number or <Enter Zone> label to enter/change the zone to be monitored.

• Click the value and select the Cooperative Control By Event (CCBE) level from the drop-down menu.

• Click Save to save the changes.

Refer to 2.3.4, "Zone Mapping and Control by Event" for details.

Error Log Label text is red when there is an error. Click to display date, time, and error description information. Refer to 2.3.5, "Error Log" for details.

Page 16: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

Configuration Configuring the VESDA-HLI-GW

12 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 : 6/26/12

2.3.4 Zone Mapping and Control by Event

The VESDA-HLI-GW can be configured for 10 general zones per VESDA device. Zones 0 to 999 are supported with Zone 0 being a general alarm zone that is active if any detectors are in the FIRE1 or FIRE2 state. The zones have the following characteristics:

• All Zones activated by the gateway remain active until there is a reset issued from the NFN. At that time, all the zones related to detectors being reset are cleared.

• A zone remains active as long as any detectors assigned to that zone are active.

• A zone goes into trouble state when any of its detectors become disabled or in trouble. The zone remains in a troubled state until all of its detectors are enabled and not in trouble.

• When the detector is disabled, zones can go off (if the point goes off), but cannot go on (if the point goes on). Note that enabling a point may also result in zones going active, if the point went active while it was disabled.

• Disabling of zones is not supported by the VESDA-HLI-GW. Zone disables are ignored. Points must be disabled individually.

• Force On/Off of zones is not supported.

• Read Status of zones is supported.

The Table 2.1, “Zone Setting/Alarm State Relationships” describes when zones are activated for each zone setting for each alarm state. An “X” indicates that the zone will be activated.

There are two labels, the 20-byte standard label and the 12-byte custom label. The Network Control Annunciator (NCA) displays them along with the events. There are 10 slots for Cooperative Control By Event (CCBE) per detector. Each slot can be set to one of the zones 1-999. In the Value column of the slot there is a selection for what type of event will cause the one to go active. The possible types of events are Alert, Action, Fire1, Fire2 and Any. Zones are cumulative in the given order. For example, an Action event triggers the Action and Alert zones. A Fire1 event triggers the Fire1, Action and Alert zones. A Fire 2 event triggers all zones.

Table 2.1 Zone Setting/Alarm State Relationships

Alarm State

Alert Action Fire1 Fire2

Alert X X X X

Action X X X

Fire1 X X

Fire2 X

Any X X X X

Zo

ne

Sta

te S

etti

ng

Page 17: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

Configuring the VESDA-HLI-GW Configuration

13VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

2.3.5 Error Log

The error log displays specific information when the VESDA-HLI-GW detects a trouble condition. When a trouble condition is present, the output relay also de-energizes. The following table defines the possible errors displayed in the log:

Table 2.2 Error Log Message Definition

Error Description

VESDA Trouble The VESDAnet has encountered a condition such as a break or open condition. A VSC from Xtralis is necessary to interpret the error code.

Connection Not Supported Device has an invalid wiring configuration on the NUP port, for example, trying to attach an HSNCM with a serial cable.

Modbus Communication Fault Cannot communicate with HLI. For example, HLI is unplugged.

Missing Detector # Indicates a detector programmed into the system is offline (for example # is a numeric value which is the detector number).

Page 18: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

Configuration Configuring the VESDA-HLI-GW

14 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 : 6/26/12

Page 19: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

Viewing Existing Settings IP Settings

15VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Appendix A: IP Settings

A.1 Viewing Existing Settings1. Connect the flash drive to the VESDA-HLI-GW.

2. Reboot the gateway.

A file is created that matches the configured IP address of the gateway, followed by the extension “.txt” (e.g., 192.168.1.2.txt). If the file already exists on the drive, it will be altered to match the Gateway configuration. The file contains additional information such as the MAC address of the gateway.

3. Connect the drive to a PC and view the files.

The flash drive should contain a file that matches the configured IP address of the gateway, followed by the extension “.txt” (e.g., 192.168.1.2.txt). If the file already exists on the drive, it has been altered to match the gateway configuration. The file contains additional information such as the MAC address of the gateway.

A.2 Resetting Factory Default Settings1. Connect the flash drive to a PC and create a file named “default.ldc”. The contents of the file is not

significant; however, ensure that the file does not have an additional hidden file extension. This file will be automatically deleted from the flash drive.

2. Eject the flash drive from the PC.

3. Disconnect power from the gateway.

4. Disconnect the communication cable to the Gateway USB port (if present) and connect the flash drive.

5. Reconnect the 24 VDC power supply to the gateway.

6. After approximately one minute, disconnect the flash drive from the USB port and (if necessary) reconnect the cable removed in Step 4.

7. Connect the flash drive to the PC and verify that the file named 192.168.12.txt is on the drive.

• If the file is on the flash drive, the reset has been accomplished.

• If the file is not on the flash drive

– The flash drive may not have been connected during the reboot period or was removed early.

– The flash drive is not seen as a valid drive by the hardware.

– A software error has occurred and technical support may need to be contacted.

NOTE: The procedures in this appendix require the use of a USB flash memory drive.

Page 20: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

IP Settings Resetting Factory Default Settings

16 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Page 21: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

Required Equipment Viewing Gateway Configuration

17VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev: A2 6/26/12

Appendix B: Viewing Gateway Configuration

B.1 Required Equipment• VESDA-HLI-GW

• USB flash memory drive

• PC

B.2 Viewing the Configuration1. Connect the flash drive to the VESDA-HLI-GW.

2. Reboot the Gateway.

A file is created that matches the configured IP address of the gateway, followed by the extension “.txt” (e.g., 192.168.1.2.txt). If the file already exists on the drive, it will be altered to match the Gateway configuration. The file contains additional information such as the MAC address of the Gateway.

3. Connect the drive to a PC and view the files.

The flash drive should contain a file that matches the configured IP address of the gateway, followed by the extension “.txt” (e.g., 192.168.1.2.txt). If the file already exists on the drive, it has been altered to match the Gateway configuration. The file contains additional information such as the MAC address of the Gateway.

Page 22: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

Viewing Gateway Configuration Viewing the Configuration

18 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev: A2 6/26/12

Page 23: Programming and Operation Manual - Notifier · VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3 Installation Precautions Adherence to the …

25BACNET-GW-3 Operation and Programming Manual - P/N: LS10014-000NF-E: Rev. A2 6/26/12

Limited WarrantyHoneywell International Inc. warrants products manufactured byit to be free from defects in materials and workmanship foreighteen (18) months from the date of manufacture, under normaluse and service. Products are date stamped at time ofmanufacture. The sole and exclusive obligation of HoneywellInternational Inc. is to repair or replace, at its option, free of chargefor parts and labor, any part that is defective in materials orworkmanship under normal use and service. All returns for creditare subject to inspection and testing at the factory before actualdetermination is made to allow credit. Honeywell InternationalInc. does not warrant products not manufactured by it, but assignsto the purchaser any warranty extended by the manufacturer ofsuch products. This warranty is void if the product is altered orrepaired by anyone other than Honeywell International Inc. or asexpressly authorized by Honeywell International Inc. in writing, oris serviced by anyone other than Honeywell International Inc. orits authorized distributors. This warranty is also void if there is afailure to maintain the products and systems in which they operatein a proper and workable manner. In case of defect, secure aReturn Material Authorization form from our Return AuthorizationDepartment.

This writing constitutes the only warranty made by HoneywellInternational Inc., with respect to its products. HoneywellInternational Inc., does not represent that its products will preventany loss by fire or otherwise, or that its products will in all casesprovide the protection for which they are installed or intended.Buyer acknowledges that Honeywell International Inc., is not aninsurer and assumes no risk for loss or damages or the cost of anyinconvenience, transportation damage, misuse, abuse, accident orsimilar incident.

HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY,EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FORANY PARTICULAR PURPOSE, OR OTHERWISE WHICHEXTENDS BEYOND THE DESCRIPTION ON THE FACEHEREOF. UNDER NO CIRCUMSTANCES SHALL HONEYWELLINTERNATIONAL INC. BE LIABLE FOR ANY LOSS OF ORDAMAGE TO PROPERTY, DIRECT, INCIDENTAL ORCONSEQUENTIAL, ARISING OUT OF THE USE OF, ORINABILITY TO USE HONEYWELL INTERNATIONAL INC.’SPRODUCTS. FURTHERMORE, HONEYWELL INTERNATIONALINC. SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY ORDEATH WHICH MAY ARISE IN THE COURSE OF, OR AS ARESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USEOF ITS PRODUCTS.